Daikin ECFWEB6, ECFWER6, ECFWDER6, ECFWDEB6 User Manual

ECFWEB6 ECFWER6 ECFWDER6
INSTALLATION AND
OPERATION MANUAL
Microprocessor controller for fan coils
3
2
5
1
3 4 5 6 7 8 9
34 5 6 789
2
3
16.5°C 28.5°C
22.5°C
5
4
12
2
6 7 8
22
11
91011 12
130
86
9.3
7
19
24
93
4 5
7 86
22
11
105
90
7
0
22
11
2 x (ø5x8)
17.7
7
109
11
12
13 16
13 16
14
14 17
15
19
17
19
20
18
15 18
20
21
21
ECFWEB6 ECFWER6 ECFWDER6
T
ABLE OF CONTENTS
Main features .................................................................1
Main functions and equipment....................................... 1
Packing list.............................................................. 2
Control panel ..........................................................2
Temperature range .................................................2
LED indicators ........................................................2
Description of the operating modes........................ 3
Technical data and operation limits ........................5
Possible configurations.................................................. 7
Before installation ..........................................................9
ECFWEB6 installation instructions ................................9
Installation on the support and on the fan coil........9
ECFWER6 + ECFWDER6 installation instructions...... 10
Installation ............................................................10
Setting the microswitches ............................................10
Installing the air and water temperature probes...........11
Position of the air temperature probe ...................11
Position of the water temperature probe...............11
Installing the power contactor ......................................12
Wiring diagrams...........................................................12
Wiring parts table .................................................12
Read this manual attentively before starting up the unit. Do not throw it away. Keep it in your files for future reference.
Improper installation or attachment of equipment or accessories could result in electric chock, short-circuit, leaks, fire or other damage to the equipment. Be sure only to use accessories made by Daikin which are specifically designed for the use with the equipment and have them installed by a professional.
If unsure of installation procedures or use, always contact your Daikin dealer for advice and information.
Microprocessor controller
for fan coils
Page
Installation and
operation manual
If options need to be installed, always refer to the relevant manual of the option for additional information.
M
AIN FEATURES
This controller is designed to control Daikin fan coil units.
ECFWEB6 Built-in for FWV and FWL
ECFWER6 Remote for FWV, FWL and FWM
ECFWDER6 Remote for FWD
M
AIN FUNCTIONS AND EQUIPMENT
Regulation of the air temperature via automatic variation of the fan speed.
Regulation of the air temperature via ON/OFF switch of the fan at a fixed speed.
Time function (only for ECFWEB6).
Regulation of the air temperature via control of ON/OFF valves (on 2-pipe or 4-pipe systems).
Control of the electric heater as integration or replacement of a heating circuit with delayed fan stopping.
Cooling/Heating switching mode in following way:
Manual — on the controller
Manual — on the remote switch
Automatic — based on the water temperature
Automatic — based on the air temperature
The controller is also equipped with:
Free contacts for external enabling signal (i.e.: reed contact, remote ON/OFF switch, proximity contact etc.) that may enable or disable the unit. (Closed contact = OFF; open contact= ON)
Free contacts for the centralized cooling/heating switching system. (Closed contact = cooling, open contact = heating)
Water temperature probe (white)
Air temperature probe (black)
Installation and operation manual
1
4PW17551-1
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
Part
(See figure 1)
ECFWEB6 ECFWER6 ECFWDER6
111
integrated in controller

Packing list

1
Controller 1 1 1
2
Manual 1 1 1
3
Cover plate left 1 0 0
4
Cover plate right 1 0 0
5
Support 1 0 0
6
Accessory bag
•wire clamp
•2 screws
•probe holder
7
Water probe 1 1 1
8
Air probe 1
9
Power interface 0 0 1

Control panel

Refer to figure 2 to catch the look of the controller.
1
Operation mode selector, to turn the fan coil on and off, to choose the type of operating mode (automatic or at fixed speed) and to control the electric heating.
2
Operation LED indicating that cooling operation mode is active (blue).
3
Cooling/Heating selector.
4
Operation LED indicating that heating operation mode is active (red).
5
Thermostat to control the room temperature.

Temperature range

The print around the selector switch of the thermostat represents temperature ranges from minimum, over comfort, to maximum. The ranges refer to different temperatures, depending on the selected operating mode as illustrated in the figure below.
Cooling mode Heating mode
25°C
19°C31°C
20°C
14°C26°C
When automatic cooling/heating switching mode based on the air temperature is running, the temperature of the thermostat is as illustrated in figure 3.

LED indicators

The various combinations in which the LED lights up indicate procedures and operating status of the controller.
Blue LED lit
running. The unit is running or waiting for an input from the thermostat.
Red LED lit
running. The unit is running or waiting for an input from the thermostat.
Blue and red LEDs lit
receive an enabling signal. The water temperature does not enable the air cooling or heating functions (see "Automatic cooling/heating switching mode
based on the water temperature" on page 3) or the
temperature of the air is within the neutral zone (see
"Automatic cooling/heating switching mode based on the air temperature" on page 4).
NOTE
Double flashing of the blue LED
thermostat has sent an input to the unit for starting cooling mode. It flashes when the room temperature and the set cooling temperature are the same.
Double flashing of the red LED
thermostat has sent an input to the unit for starting heating mode. It flashes when the room temperature and the set heating temperature are the same.
The temperature of the air in the room can be seen at any time on the thermostat range turning the knob of the thermostat.
indicates that the cooling mode is
indicates that the heating mode is
indicates that the unit did not
To determine which operating mode is selected when an enabling signal is missing (blue and red LEDs are both lit), turn the knob of the thermostat until one of the two LEDs starts to flash and then remains lit. This LED points out the selected operating mode. Once the operating mode has been established, turn the thermostat back to the desired position.
means that the
means that the
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
4PW17551-1
Installation and operation manual
2

Description of the operating modes

D
O
Room thermostat with air temperature control
With the speed selector switch turned to , the fan speed is switched automatically based on the difference between the temperature set on the thermostat and the room temperature.
With the selector switch turned to , , or the ventilation mode is of the ON/OFF type.
Room thermostat with ON/OFF valve control for 2-pipe systems
With the speed selector switch turned to , the fan speed is switched automatically based on the difference between the temperature set on the thermostat and the room temperature.
With the selector switch turned to , , or the ventilation mode is of the ON/OFF type.
The water valve is shut off once the desired temperature is reached
In cooling mode the fan continues at minimum speed, even after the valve of the cooling circuit has shut off.
In heating mode the fan is stopped as soon as the valve of the heating circuit is shut off.
Room thermostat with ON/OFF valve control for 4-pipe systems
Manual built-in cooling/heating switching mode
M
The controller is pre-arranged to operate manually in the desired mode. It is enabled by pressing the selector key. The blue (cooling) and red (heating) LEDs point out the selected operating mode.
Manual remote cooling/heating switching mode
M
The controller is pre-arranged to operate manually and remotely in the desired mode. This mode is carried out by connecting the system to a remote switch. Use the special terminals on the electronic PCB of the controller.
Automatic cooling/heating switching mode based on the water temperature
H
2
The controller automatically selects the cooling or heating mode based on the temperature of the water and according to the following logic:
Water temperature <17°C — cooling mode is set Water temperature >37°C — heating mode is set Water temperature between 17°C and 37°C — the system is disabled
For switching based on water temperature, the supplied water probe needs to be installed.
See chapter "Position of the water temperature
probe" on page 11 for installation of the water
temperature probe.
With the speed selector switch turned to , the fan speed is switched automatically based on the difference between the temperature set on the thermostat and the room temperature.
With the selector switch turned to , , or the ventilation mode is of the ON/OFF type.
The water valve is shut off once the desired temperature is reached
In cooling mode the fan continues at minimum speed even after the valve of the cooling circuit has shut off.
In heating mode the fan is stopped as soon the valve of the heating circuit is shut off.
Installation and operation manual
3
4PW17551-1
In this type of configuration, the input for the centralised cooling/heating switching mode is disabled.
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
Automatic cooling/heating switching mode
R
21
based on the air temperature
AI
The controller selects the cooling or heating mode based on the temperature of the air compared to a neutral temperature interval (neutral zone) centred on the set value of the thermostat.
When this function is selected, the temperature range of the thermostat refers to the values indicated in figure 3, both for cooling and for heating.
In this type of configuration, the input for the centralised cooling/heating switching mode is disabled.
Selecting the range of the neutral zone
The neutral zone is a parameter related to the function "automatic cooling/heating switching mode based on the air temperature".
The neutral zone is a temperature interval astride the set temperature. When the air is warmer than the top limit of the neutral zone, the cooling mode is selected.
When the air is cooler than the lower limit of the neutral zone, the heating mode is selected.
The following figure illustrates an example with:
Neutral zone = 5°C Set room air temperature = 21°C For temperatures above 23.5°C the cooling operating mode is selected For temperatures below 18.5°C the heating operating mode is selected.
Neutral zone
<18.5°C =
>23.5°C =
21
°C21°C
On the controller, the range of the neutral zone is 2°C or 5°C and can be defined by setting microswitch number 4 (see "Setting the microswitches" on page 10).
Position of microswitch no. 4
Range of the neutral zone
ON 2°C
OFF 5°C
Time function
The time function is used to start the fan at medium speed for 2 minutes at regular intervals (every 10 minutes) once the room temperature has reached the level as set on the thermostat. It ensures the constant monitoring of the air temperature in the room. It is only used in summer and only if the enabling signal of the water temperature probe is positive.
The time function cycle is also executed when the controller is powered (first start-up or voltage reset).
The thermostat and the operating mode selector switch are disabled when the time function is in use.
The time function can be used only for units without valves and only in summer.
The time function is not foreseen for the ECFWER6 and ECFWDER6 versions.
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
4PW17551-1
Installation and operation manual
4
Electric heater control
The thermostat controls an electric heater as integration or replacement of a hot water heating system.
When the operating mode selector switch is turned to and the electric heater is turned on, the fan runs continuously at medium speed.
For safety reasons, the fan is turned off 2 minutes after the electric heater is turned off, whether this occurs when the desired air temperature is reached or when the electric heater is turned off manually using the operating mode selector.
During operation of the electric heater, the fan runs at medium speed only.
During heating operation of 2-pipe system units equipped with an electric heater and motorised valves, only the electric heater works.
Fan coil enabling system based on the water temperature
The controller starts the unit according to the following logic based on the water temperature that is detected by a dedicated probe:
Water temperature <17°C: Cooling mode enabling signal
Water temperature >37°C: Heating mode enabling signal
In installations with electric heater control, the same probe sends the enabling signal for the electric heater to turn on according to the following logic:
Water temperature <37°C: Additional electric heater enabling signal. (This enabling signal is sent only if the operating mode selector switch is turned
to ).
Water temperature >39°C: The additional electric heater is switched off.
For switching based on water temperature, the supplied water probe needs to be installed.
See "Position of the water temperature probe"
on page 11 for installation of the water
temperature probe.

Technical data and operation limits

Warehouse temperatures –40°C~85°C Operation temperatures 0°C~40°C Accuracy of temperature probes ±0.5°C Maximum current on terminal V1, V2
and V3 (fan speed) Maximum current on terminal R and
V (valve and electric heater)
1.1 A
0.15 A
Installation and operation manual
5
4PW17551-1
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
NOTES
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
4PW17551-1
Installation and operation manual
6
P
D
O
R
OSSIBLE CONFIGURATIONS
In this chapter we describe all possible configurations (C1➞C18) for controlling the unit.
Select the configuration that best complies to the system characteristics. Possible functions are combined in various configurations and are defined by setting the microswitches on the electronic PCB accordingly. Refer to "Installation on the support and on the fan coil" on
page 9 and to "Setting the microswitches" on page 10.
To find the relation of the system characteristics with the correct wiring diagram and the correct setting of the microswitches to be used in function of the desired control, combine the table on page 8 with the table at the very end of this manual.
This table lists the following items for all possible configurations:
activated functions
Room thermostat with air temperature control
Room thermostat with ON-OFF valve for 2-pipe systems
Room thermostat with ON-OFF valve for 4-pipe systems
M
M
H
2
AI
Manual built-in cooling/heating switching mode
Manual remote cooling/heating switching mode
Automatic cooling/heating switching mode based on the water temperature
Automatic cooling/heating switching mode based on the air temperature
Choice of the range of the neutral zone
Operational enabling signal based on the water temperature
Time function (not available for ECFWER6 + ECFWDER6)
Electric heater control
system characteristics
Number of pipes (2 or 4) Valve (✔ = present, — not present) Electric heater (✔ = present, — not
present)
position of the microswitches
corresponding controllers
relevant reference to dedicated wiring diagram ()
other conventions for complete understanding of the table:
with a number of units in parallel 1~ 1 phase 3~ 3 phase
Installation and operation manual
7
4PW17551-1
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
Characteristics List of functions activated
O
C1
Standard two pipe system
C2
Tw o pipe system – Remote switching mode
C3
Tw o pipe system – One valve
C4
Tw o pipe system – One valve – Remote switching mode
C5
Four pipe system – Two valves
C6
Four pipe system – Two valves – Remote switching mode
C7
Four pipe system
C8
Four pipe system – Remote switching mode
C9
Tw o pipe system – Electric heater
C10
Tw o pipe system – Electric heater – Remote switching mode
C11
Tw o pipe system – One valve – Electric heater
C12
Tw o pipe system – One valve – Electric heater – Remote switching mode
C13
Tw o pipe systems – Automatic switching on water side
C14
Tw o pipe systems – One valve – Automatic switching mode on water side
C15
Four pipe systems – Automatic switching on air side
C16
Four pipe systems – Two valves – Automatic switching on air
(b)(c)
side
C17
Tw o pipe systems – Electric heater – Automatic switching mode on air side
C18
Tw o pipe systems – One valve – Electric heater – Automatic switching mode on air side
(a) Electric heater control: during heating operation only the electric heater works (b) In this type of configuration, the input for the centralised cooling/heating switching mode is disabled. (c) For configurations with automatic cooling/heating switching mode based on the air temperature in cooling mode, the fan stops
when the valve shuts off. The enabling signal refers to heating mode only (the water probe is placed on the hot water branch.) Cooling mode (fan) is always enabled apart from the water temperature (there is only one water temperature probe that is used to avoid the fan from running with cold water inside the heat exchanger).
(a)
(b)
(b)
(a)(b)
(a)
(b)
(b)
M MD M MD M MD M MD M MD M MD
H2O H
2
AIR AIR
AIR
AIR
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
4PW17551-1
Installation and operation manual
8

BEFORE INSTALLATION

All field wiring and components must be installed by a licensed electrician and must comply with relevant local and national regulations.
Before obtaining access to terminals, all power circuits must be interrupted.

ECFWEB6 INSTALLATION INSTRUCTIONS

Built-in type controller
The controller has been specially designed for FWV and FWL units; if used to control other units, make sure its operation limits are respected.

Installation on the support and on the fan coil

It is advisable to set the microswitches before installing the controller, see paragraph "Setting the microswitches"
on page 10.
The controller can be installed on both sides of the unit using a support and a cover plate.
Proceed as follows to install the controller.
1 Unscrew the four screws hidden behind the hatches
at the end of the grid and remove the fan coil cabinet
(See figure 6).
2 Remove the blank plastic tabs from one of the two
slots of the support to be able to reach the "fast-on's" of the controller (see figure 4). (The supplied cables with fast-on's will need to pass through one of the slots of the support, depending on whether the controller is to be installed on the right hand or left hand side of the unit).
1 Support 2 Blank tabs
3 Feed the cables of the probes if any, in one of the
slots of the support and secure the support and controller together using the two screws supplied. (See figure 10, it illustrates the installation of the support and controller when the controller is to be installed on the right hand side of the unit. If the controller is to be installed on the left hand side of the unit, the support is to be turned by 180° compared to the drawing).
Ensure that all terminals required for the electrical connections foreseen in the configuration chosen (valve, electric heater, external contacts, ...) can be accessed, even after the support has been installed (see the correct wiring diagram). If this is not the case, remove the protective blank tabs from the base of the support first.
4 Complete all electrical connections according to the
wiring diagrams.
5 Once the electrical connections have been
completed, it is advisable to execute the autodiagnosis procedure to verify functioning of all outputs before you finish installation of the controller (outputs of the fan at various speeds, of the valves and electric heaters if installed): Refer to the paragraph "Installing the air and water temperature
probes" on page 11.
6 Assemble the controller-support unit on the fan coil
using the bayonet fittings (see figure 11).
7 Install the air temperature probe (black) and water
temperature probe (white) (see figures 13 unto 20) following the instructions given in the paragraph
"Installing the air and water temperature probes" on page 11.
8 Fit the cabinet back in place fix it with the four screws
and then insert the correct cover plate, as illustrated in figure 12.
Installation and operation manual
9
4PW17551-1
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
ECFWER6 + ECFWDER6 INSTALLATION
INSTRUCTIONS
Remote type controller

Installation

It is advisable to set the microswitches before installing the controller, see paragraph "Setting the microswitches"
on page 10.
The remote controller can be installed to a wall.
Proceed as follows to fit the controller.
1 Remove the controller lock screw and remove the
cover.
To facilitate its re-installation, be careful not to modify the position of the 2 rotating knobs on the controller cover (operating mode selector switch and thermostat) and of the corresponding potentiometers fit on the electronic PCB.
2 Drill 2 holes in the wall where the controller shall be
installed, at the exact same position of the fixing slots (5 x 8 mm) located on the control base (see figure 9).
3 Make the electric connections to the control terminal
board according to the wiring diagram of the selected configuration.
4 By means of screws, fix the control base to the wall. 5 Reassemble the control cover part and make sure
the rotating knobs are in the same position as they were upon disassembly. Secure the controller lock screw back into place again.
6 Make the electric connections to the unit according to
the wiring diagram of the selected configuration.
When installing the ECFWDER6 controller, always install the supplied power contactor (see "Installing the power contactor" on
page 12).

SETTING THE MICROSWITCHES

1 Unscrew the controller lock screw from the bottom
side of the controller. Remove the front panel of the controller.
To facilitate its re-installation, be careful not to modify the position of the 2 rotating knobs on the controller cover (operating mode selector switch and thermostat) and of the corresponding potentiometers fit on the electronic PCB.
2 Arrange the microswitches in the sequence
corresponding to one of the configurations explained (see "Possible configurations" on page 7).
List of microswitches and their functions
(See figure 7)
Micros
witch
number
Function
cooling/heating
1
switching cooling/heating
2
switching automatic cooling/
heating switching
3
mode based on the temperature of the
range of the neutral zone for the automatic
4
cooling/heating mode based on the air temperature
valve presence on
5
hydraulic circuit electric heater
6
presence number of pipes of
7
the hydraulic circuit
Position
OFF ON
controller remote
manual automatic
air water
5°C 2°C
24
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
4PW17551-1
if the desired configuration does not include the electric heaters control function and the operating mode selector switch is turned to the electric heater symbol, the fan coil will continue to run with an automatic fan speed and will regulate the air temperature by means of the fan.
Installation and operation manual
10
INSTALLING THE AIR AND WATER
TEMPERATURE

Position of the air temperature probe (black)

This chapter is valid for ECFWEB6 controllers only (FWV and FWL units). For ECFW(D)ER6 controllers, the probe is integrated in the controller itself.
Use the plastic adhesive probe-holder supplied with the controller.
Refer to the following figures for installing the air probe:
Unit without supporting feet (figure 13)
Unit with supporting feet (figure 14)
Unit with front air intake (figure 15)
Position of the water temperature probe (white)
NOTE
PROBES
The standard wires connected to the
water probe (1.5 m) are not shielded. These wires are only intended to be used inside the unit and need to be installed away from the power supply cable. Always use shielded cable if the water probe wires can not be installed away from the power supply cables.
The water probe cable can be
shortened if required.
Always use shielded cable to lengthen
the water probe cable.
The specifications of the shielded
cable are as follows:
- maximum length: 100 m
- minimum section: 0.5 mm
- the shield must be connected to of the basic unit. Do not
connect the shield on the controller side in order to avoid electromagnetic interference.
For the electrical connection, refer to the appropriate wiring diagram.
2
Position for FWV FWL FWM
Use the special copper probe-holder for the water temperature probe and install it as described below.
For 2-pipe system units without valve, the water temperature probe has to be placed on the heat exchanger (see figure 16 and figure 17).
For 4-pipe system units without valve, the water temperature probe has to be placed on the heat exchanger of the heating circuit. (See figure 18)
For 2-pipe system units with valve, the water temperature probe has to be placed on the valve inlet (on the branch coming from the system). (See
figure 19).
For 4-pipe system units with valve, the water temperature probe has to be placed on the heating valve inlet (on the branch coming from the circuit).
(See figure 20).
Position for FWD
Valve fit on the left side, see figure 21.
4 Water probe for 4-pipe system 2 Water probe for 2-pipe system
Direction of the air Direction of the waterflow
For 2-pipe system FWD units without valve, the water probe has to be placed on the inlet pipe of the heat exchanger.
For 4-pipe system FWD units without valve, the water probe has to be placed on the inlet pipe of the heating circuit heat exchanger.
Installation and operation manual
11
4PW17551-1
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils

INSTALLING THE POWER CONTACTOR

This chapter is valid for FWD units only
The power interface permits to use ECFWDER6 microprocessor-based control panels on the whole range of FWD units, even for models with current consumption greater than 1 A.
The capacity of the power interface contacts is 16 A, IP 30 rating.
Always install the power contactor.
Dimensions of the power interface are shown in figure 8. Install the supplied DIN guide at the side of the FWD
unit, on the side opposite the hydraulic fittings. (See
figure 5).
Fit the power interface into place on the DIN guide. Make the electrical connections according to the wiring
diagram.

WIRING DIAGRAMS

Once the configuration of the controller has been chosen amongst those listed in the section "Possible
configurations" on page 7, combine the table on page 8
with the table at the very end of this manual to find the wiring diagram indicated for the desired solution. The wiring diagrams can also be found at the end of this manual.
Each unit requires a switch (IL) on the power supply line with a distance of at least 3 mm between the opening contacts, and a suitable safety fuse (F).

Wiring parts table

V1.......... Minimum speed
V2.......... Medium speed
V3.......... Maximum speed
L............ Phase
PE ......... Earth
N ........... Neutral
RE......... Electric heater
V............ Valve
RM ........ Remote control
EX ......... Auxiliary contact
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
4PW17551-1
SW........ Water probe
SA......... Air probe
BK......... Black (maximum speed)
BU......... Blue (medium speed)
RD......... Red (minimum speed)
WH........ White (common)
BR......... Brown
GNYE.... Green/yellow
BL ......... Clear blue
F............ Fuse (field supply)
IL........... Line switch (field supply)
CN......... Wire terminal
RHC...... Remote cooling/heating selector switch
EXT....... External auxiliary contact
CRHC ... Centralised remote cooling/heating selector
EPIMSA6.
IPM ....... Power interface for FWD units
M........... Fan coil motor
VHC ...... Solenoid valve
VC......... Cooling solenoid valve
VH......... Heating solenoid valve
TSA....... Automatic safety thermostat
TSM ...... Safety thermal fuse
SC......... Cabling box
The code of the terminals on ECFWEB6 controllers can be found on the rear side of the plastic support.
(closed contact = cooling; open contact = heating) (field supply)
(closed contact = OFF; open contact = ON)
switch Power interface for the control of 4 fan coils
.......... Ground
.... Electrical connections to be made by the
installer
.... Part of diagram valid only for the centralised
remote Cooling/Heating selector switch (CRHC)
Installation and operation manual
12

AUTODIAGNOSIS PROCEDURE

For checking the correct operational efficiency of the controller when installing or for searching for possible faults, all outputs can be operated manually (fan, valves, electric heater) thanks to the autodiagnosis mode.
Proceed as follows to access the autodiagnosis mode and to run the tests
1 Tu rn the operating mode selector switch to the "OFF"
position.
2 Tu rn the knob of the thermostat anti-clockwise until it
reaches the minimum temperature position.
3 Hold the cooling/heating selector pushed for at least
5 seconds. At this stage both LEDs light up.
4 Within 5 seconds, turn the knob of the thermostat
clockwise to the maximum temperature position. The red LED switches off and the blue LED remains lit to indicate that the autodiagnosis mode has been accessed.
NOTE
If you wait more than 5 seconds before turning the knob again, the autodiagnosis mode will be automatically exited.
5 In the autodiagnosis mode, each position of the
operating mode selector switch corresponds to the simulation of an output.
Position Output Terminals
Valve N-V
Minimum speed N-V1
Medium speed N-V2
Maximum speed N-V3
Electric heater or second valve
N-RE
By running through the various positions of the operating mode selector switch, the electronic controller outputs can be checked one after the other either by observing the related component (valve, fan, electric heater) or by checking if the corresponding terminals are powered at a voltage of 230 V.
NOTE
If the operating mode selector switch is not moved for more than one minute, the autodiagnosis mode is automatically exited.
6 Exit the autodiagnosis mode by turning the operating
mode selector switch to the position.
Installation and operation manual
13
4PW17551-1
ECFWEB6+ECFWER6+ECFWDER6 Microprocessor controller for fan coils
ECFWEB6
SA
ECFWEB6
SA
CRHC
L N
L
N
ECFWEB6
SA
SW
SW
230V 1~ 50Hz
230V 1~ 50Hz
SW
BK
V3
BU
V2
RD
V1
BR
L
GNYE
PE
WH
N
BL
N
RE
V RM RM
EX EX
FC66000633
BK
V3
BU
V2
RD
V1
BR
L
GNYE
PE
WH
N
BL
N
RE
V RM RM
EX EX
IL
F
IL
F
FC66000634
BK
V3
BU
V2
RD
V1
BR
L
GNYE
PE
WH
N
BL
N
RE
V RM RM
EX EX
FC66000635
CN
WH
4
BK BU RD
ILF
ILF
230V 1~ 50Hz
M
1~
CRHC
L
230V 1~ 50HzN
L N
5 6 7
BR
L
BL
N
RHC
RM
EXT
RM
ECFWEB6
RM RM
ECFWER6
3TW60016-1
CN
WH
4
BK
M
BU
1~
RD
WH
BK
M
BU
1~
RD
WH
BK
M
BU
1~
RD
WH
BK
M
BU
1~
RD
RHC
RM RM
ECFWEB6
EXT
RM RM
ECFWER6
2
C
3
1
4
2
5
3
13 L 14 N 15 L 16 N
EPIMSA6
POWER RELAY
3A 250V ~
POWER RELAY
3A 250V ~
POWER RELAY
3A 250V ~
5 6 7 L
22 19
4
20 21
26 23
3
30 27
2
1
32 33
N
CN
4 5 6 7 L N
CN
4 5 6 7 L N
CN
4 5 6 7 L N
3TW60016-2
CN
WH
4
BK
M
5
BU
6
1~
RD
7
ILF
L
N
RHC
L N
230V 1~ 50Hz
ILF
230V 1~ 50Hz
CRHC
L N
VHC
BR
BL
RM
EXT
RM
ECFWEB6
RM RM
ECFWER6
3TW60016-3
ECFWEB6
ECFWEB6
SA
ECFWEB6
SA
SW
SW
SW
BK
V3
BU
V2
RD
V1
BR
L
GNYE
PE
WH
N
BL
N
RE
V RM RM
EX EX
FC66000636
BK
V3
BU
V2
RD
V1
BR
L
GNYE
PE
WH
N
BL
N
RE
V RM RM
EX EX
FC66000637
BK
V3
BU
V2
RD
V1
BR
L
GNYE
PE
WH
N
BL
N
RE
V RM RM
EX EX
FC66000638
VCSAVH
VC
EXT
EXT
TSA
2
048
TS TS
EXT
TSA
2
048
TS TS
CN
WH
4
BK
M
BU
1~
RD
ILF
L N
230V 1~ 50Hz
RHC
ILF
230V 1~ 50Hz
CRHC
L N
RM RM
ECFWEB6
BR
BL
RM RM
ECFWER6
5 6 7 L
N
3TW
BK BU
M
RD
1~
WH
RHC
RM
RETSM
61
SC
NLN
L
RM
ECFWEB6
RM RM
ECFWER6
ILF
230V 1~ 50Hz
ILF
230V 1~ 50Hz
CRHC
L N
L N
3TW
BK BU
M
RD
1~
WH
RHC
RM
RETSM
61
SC
NLN
L
RM
ECFWEB6
RM RM
ECFWER6
ILF
230V 1~ 50Hz
ILF
230V 1~ 50Hz
CRHC
L N
L N
3TW
ECFWER6
SA
SW
FC66000627
ECFWER6
SA
SW
CRHC
L
N
230V 1~ 50Hz
L
N
230V 1~ 50Hz
FC66000628
ECFWER6
SA
SW
FC66000629
CN
RM RM
ECFWER6
WH
4
BK
5 6 7 L N
M
BU
1~
RD
ILF
L N
230V 1~ 50Hz
RHC
ILF
230V 1~ 50Hz
CRHC
L N
V3 V2 V1
L PE
N N N
RE
V RM RM
EX EX
EXT
RM RM
ECFWEB6
3TW60026-1
V3 V2 V1
L PE
N
N
N RE
V RM RM EX EX
IL
IL
RHC
F
F
RM RM
ECFWEB6
EXT
RM RM
ECFWER6
2
C
3
1
4
2
5
3
13 L 14 N 15 L 16 N
EPIMSA6
POWER RELAY
3A 250V ~
POWER RELAY
3A 250V ~
POWER RELAY
3A 250V ~
22 19
4
20 21
26 23
3
30 27
2
1
32 33
CN
WH
4
BK
5 6 7 L N
CN
4 5 6 7 L N
CN
4 5 6 7 L N
CN
4 5 6 7 L N
M
BU
1~
RD
WH
BK
M
BU
1~
RD
WH
BK
M
BU
1~
RD
WH
BK
M
BU
1~
RD
3TW60026-2
CN
RM RM
ECFWER6
WH
4
BK
5 6 7 L N
M
BU
1~
RD
ILF
L
230V 1~ 50Hz
N
RHC
ILF
230V 1~ 50Hz
CRHC
L N
V3 V2 V1
L PE
N
N
N RE
V RM RM EX EX
VHC
EXT
RM RM
ECFWEB6
3TW60026-3
ECFWER6
SA
SW
10
FC66000630
ECFWER6
SA
SW
11
FC66000631
ECFWER6
SA
SW
12
FC66000632
CN
RM RM
ECFWER6
WH
4
BK
5 6 7 L N
M
BU
1~
RD
ILF
L N
230V 1~ 50Hz
RHC
ILF
230V 1~ 50Hz
CRHC
L N
V3 V2 V1
L PE
N
N
N RE
V RM RM EX EX
VC VH
EXT
RM RM
ECFWEB6
3TW
CN
RM RM
ECFWER6
WH
4
BK
5 6 7 L N
M
BU
1~
RD
RHC
ILF
230V 1~ 50Hz
230V 1~ 50Hz
ILF
CRHC
L N
L N
V3 V2 V1
L PE
N
N
N RE
V RM RM EX EX
EXT
TSA
61
2
048
TS TS
L
RM
RETSM
SC
NLN
RM
ECFWEB6
3TW
CN
RM RM
ECFWER6
WH
4
BK
5 6 7 L N
M
BU
1~
RD
RHC
ILF
230V 1~ 50Hz
230V 1~ 50Hz
ILF
CRHC
L N
L N
V3 V2 V1
L PE
N
N
N RE
V RM RM EX EX
VC
EXT
TSA
61
2
048
TS TS
L
RM
RETSM
SC
NLN
RM
ECFWEB6
3TW
ECFWDER6
SA
V3 V2 V1
L PE
N
N
N RE
V RM RM EX EX
EXT
SW
CRHC
L N
230V 1~ 50Hz
L N
230V 1~ 50Hz
13
UT66000279
ECFWDER6
SA
SW
1
C
2
V1
3
V2
C
4
V3
RM
RHC
IL
F
F
IL
RM
ECFWER6
RM RM
ECFWER6
14 L 15 L 16 N 17 N
V3 V2 V1
IPM
CN
4 5 6 7 L N
WH
BK
BU or GY
RD
M 1~
3TW60226-1
1
C
2
V1
3
V2 V3 V2 V1
L
PE
N N N
RE
V RM RM EX EX
VHC
EXT
4
V3
14 L 15 L 16 N 17 N
ECFWER6
C V3 V2 V1
IPM
RM RM
RM RM
ECFWER6
CN
4 5 6 7 L N
WH
BK
BU or GY
RD
RHC
M 1~
ILF
230V 1~ 50Hz
CRHC
L N
14
UT66000280
ILF
230V 1~ 50Hz
3TW60226-2
L N
ECFWDER6
SA
SW
1
C
2
V1
3
V2 V3 V2 V1
L
PE
N N N
RE
V RM RM EX EX
VC VH
EXT
4
V3
14 L 15 L 16 N 17 N
ECFWER6
C V3 V2 V1
IPM
RM RM
RM RM
ECFWER6
CN
4 5 6 7 L N
WH
BK
BU or GY
RD
RHC
M 1~
ILF
230V 1~ 50Hz
ILF
230V 1~ 50Hz
CRHC
L N
L N
15
UT66000281
ECFWDER6
SA
SW
16
UT66000282
3TW60226-3
C
1
V1
2
V2 V3 V2 V1
L
PE
N N N
RE
V RM RM EX EX
EXT
TSM
TSA
A2 1 3
TS TS
RE
4A1
2
NLN
L
3
C
V3
4
V3 V2 V1
14 L 15 L 16 N
IPM
17 N
RM RM
ECFWER6
SC
RM RM
ECFWER6
CN
4 5 6 7 L N
WH
BK
BU or GY
RD
RHC
M 1~
ILF
230V 1~ 50Hz
230V 1~ 50Hz
ILF
CRHC
L N
L N
3TW60226-4
ECFWDER6
SA
SW
17
UT66000313
ECFWDER6
SA
SW
1
C
2
V1
3 V3 V2 V1
L
PE
N N N
RE
V RM RM
EX EX
V3 V2 V1
L
PE
N
N
N
RE
V RM RM
EX EX
VC
EXT
TSM
TSA
A1
A2 3 5
TS N
TSA
A1
A2 3 5
TS N
N L2 L3L1
EXT
TSM
N L2 L3L1
SC
SC
RE RE RE
2
1
RE RE RE
2
1
6
4
6
4
V2
4
V3
14 L 15 L 16 N 17 N
ECFWER6
1
C
2
V1
3
V2
4
V3
14 L 15 L 16 N 17 N
ECFWER6
C V3 V2 V1
IPM
RM RM
C V3 V2 V1
IPM
RM RM
RM RM
ECFWER6
RM RM
ECFWER6
CN
4 5 6 7 L N
CN
4 5 6 7 L N
WH
BK
BU or GY
RD
WH
BK
BU or GY
RD
RHC
RHC
M
1~
400V 3+N 50Hz
M
1~
400V 3+N 50Hz
ILF
230V 1~ 50Hz
IL
F
ILF
230V 1~ 50Hz
IL
F
CRHC
CRHC
L N
L N
18
UT66000314
ECFWDER6
SA
SW
1
C
2
V1
3 V3 V2 V1
L
PE
N N N
RE
V RM RM
EX EX
VC
EXT
TSM
TSA
RE
61
2
048
TS TS
L
SC
NLN
V2
4
V3
14 L 15 L 16 N 17 N
ECFWER6
C V3 V2 V1
IPM
RM RM
RM RM
ECFWER6
CN
4 5 6 7 L N
WH
BK
BU or GY
RD
RHC
M 1~
ILF
230V 1~ 50Hz
230V 1~ 50Hz
ILF
CRHC
L N
L N
19
UT66000283
3TW
C1
FWV • FWL • FWM FWD
ECFWER6
ECFWEB6
12 76543
M
––2
ECFWEB6
ECFWER6
612345 7 89101112 13141516 171819
ECFWDER6
3~
1~
C2
C3
C4
C5
C6
C7
C8
C9
C10
C11
C12
C13
C14
C15
C16
MD
M
MD
M
MD
M
MD
M
MD
M
MD
H2O
H2O
AIR
AIR
2––
2–
22–
4–
4–
4–
4–
2–
2
2
2––
22–
4–––
4–
C17
C18
AIR
AIR
2
Zandvoordestraat 300, B-8400 Oostende, Belgium
4PWEN17551-1
Loading...