READ THIS MANU AL ATTENTIVELY BEFORE ST ARTING
UP THE UNIT. DO NOT THROW THIS MANUAL AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
Read the chapter "User settings menu" on page 9 before
changing the parameters.
INTRODUCTION
This operation manual concerns packaged water-cooled water
chillers of the Daikin EWWQ-KA series. These units are provided for
indoor installation and used for cooling and/or heating applications.
The units can be combined with Daikin fan coil units or air handling
units for air conditioning purposes. They can also be used for
supplying water for process cooling.
This manual has been prepared to ensure adequate operation and
maintenance of the unit. It will tell you how to use the unit properly
and will provide help if problems occur. The unit is equipped with
safety devices, but they will not necessarily prevent all problems
caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local dealer.
Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
carefully read the installation manual supplied with the unit
and the recommendations listed in "Checks before initial
start-up" on page 6.
The English text is the original instruction. Other languages are
translations of the original instructions.
This appliance is not intended for use by persons, including children,
with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person
responsible for their safety.
Children should be supervised to ensure that they do not play with
the appliance.
(1) Refer to the engineering data book for the complete list of specifications.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
2
DESCRIPTION
98~128 Hp
147~192 Hp
17
26 11
14
23
20
27
18
12
15
24
21
27
19
13
25 16
22
27
10
5
2
3
8
6
1
1
9
7
4
500500
500
Figure - Main components
1Compressor15
2Evaporator16
3Condenser17
4Switchbox18
5Chilled water in 119
6Chilled water in 220
7Chilled water in 321
8Chilled water out 122
9Chilled water out 2 23
10Chilled water out 324
11Condenser water out 125
12Condenser water out 226
13Condenser water out 327
14Condenser water in 1
Required space around the unit for service
Condenser water in 2
Condenser water in 3
Evaporator entering water temperature sensor 1
Evaporator entering water temperature sensor 2
Evaporator entering water temperature sensor 3
Freeze up sensor 1
Freeze up sensor 2
Freeze up sensor 3
Condenser entering water temperature sensor 1
Condenser entering water temperature sensor 2
Condenser entering water temperature sensor 3
Digital display controller 98~192
Power supply intake
Operation manual
3
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Function of the main components
Water
inlet
Water
outlet
Condenser
S1HP
S2HP
Filter
Filter
Compressor
Q1D
Compressor
Q2D
M1C
HP
LP
M2C
HP
LP
S4LP
S5LP
Evaporator
R4TR5T
Water
outlet
R3T
Water
inlet
98~113
147~192
S1HP
S2HP
S1HP
S2HP
M1C
Q1D
HP
LP
M2C
Q2D
HP
LP
M1C
Q1D
HP
LP
M2C
Q2D
HP
LP
S4LP
R4TR5T
R3T
S5LP
S4LP
R4TR5T
R3T
S5LP
Figure - Functional diagram
As the refrigerant circulates through the unit, changes in its state or
condition occur. These changes are caused by the following main
components:
■Compressor
The compressor (M*C) acts as a pump and circulates the
refrigerant in the refrigeration circuit. It compresses the refrigerant vapour coming from the evaporator to a pressure at
which it can easily be liquified in the condenser.
■Condenser
The function of the condenser is to change the state of the
refrigerant from gaseous to liquid. The heat gained by the gas in
the evaporator is discharged through the condenser and the
vapour condenses to liquid.
■Filter
The filter installed behind the condenser removes small particles
from the refrigerant to prevent blockage of the tubes.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
■Expansion valve
The liquid refrigerant coming from the condenser enters the
evaporator via an expansion valve. The expansion valve brings
the liquid refrigerant to a pressure at which it can easily be
evaporated in the evaporator.
■Evaporator
The main function of the evaporator is to take heat from the
water that flows through it. This is done by turning the liquid
refrigerant, coming from the condenser, into gaseous refrigerant.
■Water inlet/outlet connection
The water inlet and outlet connections allow an easy connection
of the unit to the water circuit of the air handling unit or industrial
equipment.
Operation manual
4
Safety devices
■Overcurrent relay
The overcurrent relay (K*S) is located in the switch box of the
unit and protects the compressor motor in case of overload,
phase failure or too low voltage . The relay is factory-set and may
not be adjusted. When activated, the overcurrent relay has to be
reset in the switch box and the controller needs to be reset
manually.
■High-pressure switch
The high-pressure switch (S*HP) is installed on the discharge
pipe of the unit and measures the condenser pressure (pressure
at the outlet of the compressor). When the pressure is too high,
the pressure switch is activated and the circuit stops.
When activated, it resets automatically, but the controller needs
to be reset manually.
■Low pressure switch
The low-pressure switch (S*LP) is installed on the suction pipe
of the unit and measures the evaporator pressure (pressure at
the inlet of the compressor). When the pressure is too low, the
pressure switch is activated and the circuit stops.
When activated, it resets automatically, but the controller needs
to be reset manually.
■Reverse phase protector
The reverse phase protector (R1P) is installed in the switch box
of the unit. It prevents the compressor from running in the wrong
direction. If the unit does not start, two phases of the power
supply must be inverted.
■Discharge thermal protector
The discharge thermal protector (Q*D) is activated when the
temperature of the refrigerant leaving the compressor becomes
too high. When the temperature retur ns to normal, the protector
resets automatically, but the controller needs to be reset
manually.
■Freeze-up protection
The freeze-up protection prevents the water in the evaporator
from freezing during operation. When the outlet water
temperature is too low, the controller disables the circuit. When
the outlet water temperature returns to normal, the circuit can
start up again.
When freeze-up protection occurs several times in a certain
period, the freeze-up alarm will be activated and the circuit will
be shut down. The cause of freezing up should be investigated
and after outlet water temperature has risen enough, the alarm
indicator on the controller needs to be reset manually.
■Additional interlock contact
To avoid that the unit could be started or run without water
circulating through the water heat exchanger, an interlock
contact (S11L) of e.g. a flo w switch must be installed in the startup circuit of the unit.
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:
A1P ........................PCB terminal unit
A2P ................**....PCB address card
F1,2,3U ..........#.....Main fuses for the unit
F1B, F2B, F3B #.... fuses for each unit
F5B,F6B.................Automatic fuse for the control circuit/secondary
X2 (C3/4-NO3) .......voltage free contact for pump
X2 (C3/4-NO4) .......voltage free contact for reversing valve
X2 (C5-NO5) ..........alarm voltage free contact
Terminal unit: Analog inputs
X1 (B1-GND)..........evaporator inlet water temperature
X1 (B2-GND)..........evaporator outlet water temperature (Freeze up
sensor)
X1 (B3-GND)..........condenser inlet water temperature
Operation manual
5
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
BEFOREOPERATION
Checks before initial start-up
Make sure that the circuit breaker on the power supply
panel of the unit is switched off.
After the installation of the unit, check the following before switching
on the circuit breaker:
1Field wiring
Make sure that the field wiring between the local supply panel
and the unit has been carried out according to the instructions
described in the installation manual, according to the wiring
diagrams and according to European and national regulations.
2Additional interlock contact
An additional interlock contact S11L should be provided (e.g.
flow switch, contact of pump motor contactor). Make sure that it
has been installed between the appropriate terminals (refer to
the wiring diagram supplied with the unit). S11L should be a
normal open contact.
3Fuses or protection devices
Check that the fuses or the locally installed protection devices
are of the size and type specified in the installation manual.
Make sure that neither a fuse nor a protection device has been
bypassed.
4Earth wiring
Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.
5Internal wiring
Visually check the switch box on loose connections or damaged
electrical components.
6Fixation
Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.
7Damaged equipment
Check the inside of the unit on damaged components or
squeezed pipes.
8Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local dealer.
9Oil leak
Check the compressor on oil leakage. If there is an oil leak, call
your local dealer.
10 Power supply voltage
Check the power supply voltage on the local supply panel. The
voltage should correspond to the voltage on the identification
label of the unit.
Water supply
Fill the water piping, taking into account the minimum water volume
required by the unit. Refer to the "installation manual".
Make sure that the water is of the quality as mentioned in the
installation manual.
Purge the air at the high points of the system and check the operation
of the circulation pump and the flow switch.
General recommendations
Before switching on the unit, read following recommendations:
1When the complete installation and all necessary settings have
been carried out, close all front panels of the unit.
2The service panels of the switch boxes ma y only be opened b y a
licensed electrician for maintenance purposes.
OPERATION 98~192
The 98~192 units are equipped with a built-in digital controller
offering a user-friendly way to set up, use and maintain the unit.
This part of the manual has a task-oriented, modular structure. Apart
from the first section, which gives a brief description of the controller
itself, each section or subsection deals with a specific task you can
perform with the unit.
Depending on the model there are two or three modules in the
system. The models 98~113 only have two modules, whereas the
models 147~192 consist of three modules. These modules are
generally named M1, M2 and M3 in the following descriptions. All
information about module 3 (M3) is not applicable for 98~113 models.
Digital controller
User interface
The digital controller consists of an alphanumeric display, labelled
keys which you can press and a number of LEDs.
Figure - Digital controller
fkey, to enter the main menu
okey, to start up or to shut down the unit.
pkey, to enter the safeties menu or to reset an alarm.
keys, to scroll up or down through the screens of a menu
g
(only in case W, X or C appears) or to raise, respectively
h
lower a setting.
qkey, to confirm a selection or a setting.
NOTE
Working with the 98~192 units
This chapter deals with the everyday usage of the unit. Here, you will
find how to perform routine tasks, such as:
■"Setting the language" on page 7
■"Switching the unit on" on page 7 and "Switching the unit off" on
■"Consulting actual operational information" on page 7
■"Selecting cooling or heating operation" on page 8
■"Adjusting the temperature setpoint" on page 8
■"Resetting the unit" on page 8
Temperature readout tolerance: ±1°C.
Legibility of the alphanumeric display may decrease in
direct sunlight.
page 7
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
6
Setting the language
Consulting actual operational information
If desired, the operating language can be changed to any of the
following languages: English, German, French, Spanish or Italian.
1Enter the usersettings menu. Refer to chapter "Main menu" on
page 9
2Go to the appropriate screen of the usersettings menu using the
g and h keys.
3Select the appropriate field (LANGUAGE) using the q key.
4Press the g and h keys to adjust the language setting.
5Press q to confirm the adjusted language setting.
When the setting has been confirmed, the cursor switches to the next
setting.
Switching the unit on
1Press the J key on the controller.
Depending on whether or not the remote ON/OFF switch is
configured (refer to the service manual), the following conditions
may occur.
When no remote ON/OFF switch is configured, the LED inside
the J key lights up and an initialization cycle is started. Once all
the timers have reached zero, the unit starts up.
When a remote ON/OFF switch is configured, the following table
applies:
Local keyRemote switchUnito LED
ONONONON
ONOFFOFFFlashing
OFFONOFFOFF
OFFOFFOFFOFF
2When the unit is started up for the first time, or when the unit has
been out of operation for a longer period, it is recommended to
check the following.
Abnormal noise and vibrations
Make sure that the unit does not produce abnormal noises or
vibrations: check the fixation, stop valves and piping. If the
compressor makes abnormal noises, this may also be caused by
an overcharge of refrigerant.
3If the water chiller does not start after a few minutes, refer to
"Troubleshooting" on page 14.
Switching the unit off
If the remote on/off control parameter is set to NO:
Press the o key on the controller.
The LED inside the o key goes out.
If the remote on/off control parameter is set to YES:
Press the o key on the controller or switch the unit off using the
remote on/off switch.
The LED inside the o key goes out in the first case and star ts
blinking in the second case.
1Enter the readout menu through the main menu. (Refer to the
chapter "Main menu" on page 9.)
The controller automatically shows the first screen of the
readout menu which provides the following information:
• MANUAL MODE or INLSETP1/2: manual/automatic control mode
operation. If the automatic control mode is selected, the
controller will indicate the active temperature setpoint.
Depending on the status of the remote contact, setpoint one
or setpoint two is active.
• INL WATER E/C: actual inlet water temperature.
• THERMOSTAT STEP: actual thermostat step. The maximum
number of thermostat steps are as listed:
9841476
11341626
12841776
1926
2Press the h key to enter the next screen of the readout menu.
This screen of the readout menu provides the following
information on the evaporator:
• M1: OUTLWATER: actual outlet water temperature of module 1.
• M2: OUTLWATER: actual outlet water temperature of module 2.
• M3: OUTLWATER: actual outlet water temperature of module 3.
3Press the h key to enter the next screen of the readout menu.
The COMPRESSOR STATUS screen of the readout menu provides
information concerning the status of the different compressors.
• C11: actual status of compressor 1 of module 1.
• C12: actual status of compressor 2 of module 1.
• C21: actual status of compressor 1 of module 2.
• C22: actual status of compressor 2 of module 2.
• C31: actual status of compressor 1 of module 3.
• C32: actual status of compressor 2 of module 3.
When a circuit is OFF, the following status information may
appear.
• SAFETY ACTIVE: one of the circuit safety devices is activated
(refer to the chapter "Troubleshooting" on page 14).
• (LIMIT): the circuit is limited by a remote contact.
• TIMERS BUSY: the actual value of one of the software timers is
not zero (refer to the "Timers menu" on page 9).
• CAN STARTUP: the circuit is ready to start up when extra
cooling load is needed.
The preceding OFF messages are written down in order of priority. If
one of the timers is busy and one of the safeties is active, the status
information says SAFETY ACTIVE.
4Press the h key to enter the next screen of the readout menu.
To consult actual operational information about the total running
hours of the compressors.
In case of emergency, switch off the unit by pushing the
emergency stopbutton.
NOTE
Operation manual
Also consult "Defining the schedule timer" on page 12.
7
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Selecting cooling or heating operation
The "cooling/heating" menu allows the user to set the unit in cooling
or heating operation.
The COOL/HEAT menu provides information concerning the selected
operation mode.
■ COOLING (EVAP): cooling mode. The two setpoints for inlet
water temperature control of the evaporator can be used.
■ HEATING (COND): heating mode. The two setpoints for inlet
water temperature control of the condenser can be used.
To define cooling/heating operation, proceed as follows:
1Enter the cooling/heating menu through the main menu. (Refer
to the chapter "Main menu" on page 9.)
2Position the cursor behind MODE using the q key.
3Select the appropriate setting using the g and h keys.
4Press q to confirm.
The cursor returns to the upper left corner of the screen.
Adjusting the temperature setpoint
The unit provides definition and selection of four or two independent
temperature setpoints.
In cooling operation, two setpoints are reserved for inlet control of the
evaporator.
■INLSETP 1 E: inlet water temperature of evaporator, setpoint 1,
■INLSETP2 E: inlet water temperature of evaporator, setpoint 2.
In heating operation, two setpoints are reserved for inlet control of the
condenser.
■INLSETP 1 C: inlet water temperature of condenser, setpoint 1,
■INLSETP 2 C: inlet water temperature of condenser, setpoint 2.
In double thermostat operation, two setpoints are reserved for inlet
control of the evaporator and two others are reserved for inlet control
of the condenser.
■INLSETP 1 E: inlet water temperature of evaporator, setpoint 1,
■INLSETP2 E: inlet water temperature of evaporator, setpoint 2.
■INLSETP 1 C: inlet water temperature of condenser, setpoint 1,
■INLSETP 2 C: inlet water temperature of condenser, setpoint 2.
The selection between setpoint 1 and 2 is done by a remote dual
setpoint switch (to be installed by the customer). The actual active
setpoint can be consulted in the readout menu.
If the manual control mode is selected (refer to "User settings menu"
on page 9), none of the above-mentioned setpoints will be active.
To adjust a setpoint, proceed as follows:
1Enter the setpoints menu through the main menu. (Refer to the
chapter "Main menu" on page 9).
If the user password is disabled for setpoint modifications (refer
to the "User settings menu" on page 9), the controller will
immediately enter the setpoints menu.
If the user password is enabled for setpoint modifications, enter
the correct code using the g and h keys. (Refer to the "User
password menu" on page 10). Press q to confirm the password
and to enter the setpoints menu.
2Select the setpoint to be adjusted using the q key.
A setpoint is selected when the cursor is blinking behind the
setpoint's name.
The ">" sign indicates the actual active temperature setpoint.
3Press the g and h keys to adjust the temperature setting.
The default, limit and step values for the cooling (evaporator)
and heating (condenser) temperature setpoints are:
EE
default value12°C30°C
limit values
(a) For glycol units the lower limit of the cooling temperature setpoint can be
(a)
step value0.1°C0.1°C
adapted in the factory. The following values apply:
INLSETP IN E/C: 5°C, 3°C, –2°C, –7°C
IIIINNNNLLLLSSSSEEEETTTTPPPP IIIINNNN EE
8 --> 23°C15--> 50°C
IIIINNNNLLLLSSSSEEEETTTTPPPP IIIINNNN CC
CC
4Press q to save the adjusted temperature setpoint.
When the setting has been confirmed, the cursor switches to the
next setpoint.
5To adjust other setpoints, repeat from instruction 2 onwards.
NOTE
Also consult "Defining the schedule timer" on page 12.
Resetting the unit
The units are equipped with three kinds of safety devices: unit
safeties, module safeties and network safeties.
When a unit safety occurs, all compressors are shut down. The
safeties menu will indicate which safety is activated. The COMPRESSORSTATUS screen of the readout menu will indicate OFF - SAFETY ACTIVE
for all circuits. The red LED inside the p key lights up and the buzzer
inside the controller is activated.
When a module safety occurs, the compressors of the corresponding
module are shut down. The COMPRESSOR STATUS screen of the
readout menu will indicate OFF - SAFETY ACTIVE for the module
concerned. The red LED inside the p key lights up and the buzzer
inside the controller is activated.
If the unit has been shut down due to a power failure, it will carry out
an autoreset and restart automatically when the electrical power is
restored.
To reset the unit, proceed as follows:
1Press the p key to acknowledge the alarm.
The buzzer is deactivated.
The controller automatically switches to the corresponding
screen of the safeties menu: unit safety or module safety.
2Find the cause of shutdown and correct.
Refer to "Listing activated safeties and checking the unit status"
on page 12 and the chapter "Troubleshooting" on page 14.
When a safety can be reset, the LED under the p key starts
blinking.
3Press the p key to reset the safeties that are no longer active.
Once all safety devices are disactivated and reset, the LED
under the p key goes out. If one of the safeties is still activ e, the
LED under the p key goes on again. In this case, return to
instruction 2.
4If a unit safety occurred or if all modules were shut down due to
module safeties, switch on the unit using the o key.
If the user shuts down the power supply in order to repair a
safety, the safety will automatically be reset after power-up.
NOTE
The history information, i.e. the number of times a unit
safety or a circuit safety occurred and the unit status at
the moment of shutdown, can be checked by means of
the history menu.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
8
Advanced features of the digital controller
This chapter gives an overview and a brief functional description of
the screens provided by the different menus. In the following chapter,
you will find how you can set up and configure the unit using the
various menu functions.
The down arrow X on the display indicates that y ou can go to the next
screen of the current menu using the h key. The up arrow W on the
display indicates that you can go to the previous screen of the current
menu using the g key. If C is displayed, this indicates that you can
either return to the previous screen or can go to the next screen by
using the g and h keys.
Main menu
Scroll through the main menu using the g and h keys to move the >
mark in front of the menu of your choice. Push the q key to enter the
selected menu.
>READOUT MENU
SETPOINTS MENU
USERSETTINGS MENU
TIMERS MENU
HISTORY MENU
INFO MENU
I/O STATUS MENU
USERPASSWORD MENU
COOL/HEAT MENU
User settings menu
The "user settings" menu, protected by the user password, allows a
full customization of the units.
BC CONTROL SETTINGS
MODE :MANUAL CONTROL
C11 : OFF 12 ; OFF
C21 : OFF 22 ; OFF
To consult actual operational information about the control mode, the
inlet water temperature of the
evaporator/condenser and the
thermostat step.
To consult information about the
outlet water temperature of the
modules 1, 2 and 3 (only for
147~192).
To consult information about the
compressor status (first screen).
To consult information about the
compressor status (second screen).
To consult actual operational
information about the total running
hours of the compressors.
Setpoints menu
Depending upon the settings in the user settings menu and on the
selected cooling/heating operation mode, the "setpoints" menu can
either be entered directly or by means of the user password.
B>INLSETP1 E : 12.0°C
INLSETP2 E : 12.0°C
INLSETP1 C : 30.0°C
INLSETP2 C : 30.0°C
To define the temperature setpoints.
BC PUMPCONTROL
PUMPLEADTIME : 020s
PUMPLAGTIME : 000s
DAILY ON : Y AT : 00h00
BC SCHEDULE TIMER
ENABLE TIMER : N
ENABLE HOLIDAY PER : N
BC HOLIDAY : 01 TO 03
1 : 00h00 2: 00h00 3: 00h00 -
BC DUAL EVAP. PUMP
MODE : AUTOM. ROTATION
OFFSET ON RH : 0048h
BC DISPLAY SETTINGS
LANGUAGE : ENGLISH
TIME : 00h00
DATE : 00/01/2001
BC SETPOINT PASSWORD
PASSWORD NEEDED TO
CHANGE SETPOINTS : Y
To define whether or not a password
is needed to enter the setpoints
menu.
To enter the service menu. (Only a
qualified installer is allowed to
access this menu.)
To check the actual value of the
general software timers (first screen).
Operation manual
9
BC COMPRESSOR TIMERS
COMPR. STARTED : 00s
BC COMPRESSOR TIMERS
C11 GRD : 000s AR : 000s
C12 GRD : 000s AR : 000s
C21 GRD : 000s AR : 000s
To check the actual value of the
general software timers (second
screen).
To check the actual value of the
compressor timers (first screen).
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
BW COMPRESSOR TIMERS
C22 GRD : 000s AR : 000s
C31 GRD : 000s AR : 000s
C32 GRD : 000s AR : 000s
Safeties menu
To check the actual value of the
compressor timers (second screen).
Info menu
BX TIME INFORMATION
TIME : 00h00
DATE : 00/01/2001
To consult time and date information.
The "safeties" menu provides useful information for trouble shooting
purposes. The following screens contain basic information.
BX UNIT SAFETY
0C9 : INL E SENSOR ERR
BX MODULE 1 SAFETY
1CA : OUT E SENSOR ERR
BX MODULE 2 SAFETY
2CA : OUT E SENSOR ERR
BX MODULE 3 SAFETY
3CA : OUT E SENSOR ERR
To consult which unit safety caused
the shutdown.
To consult which module 1 safety
caused the shutdown.
To consult which module 2 safety
caused the shutdown.
To consult which module 3 safety
caused the shutdown.
Along with the basic information, more detailed information screens
can be consulted while the safety menu is active. Press the q key.
Screens similar to the following will appear.
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
00h00 - 12/01/2001
MANUAL MODE
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
INL.E : 12.0°C STEP:
INL.C : 30.0°C 0
To check the time and control mode
at the moment of the unit shutdown.
To check which were the common
evaporator and condenser inlet water
temperature.
BC UNIT INFORMATION
UNITTYPE : WW-HP-32
MANUFACT. NR.: 0000000
REFRIGERANT : R134a
To consult additional information
about the unit such as the unit type,
the refrigerant used and the manufacturing number.
BC UNIT INFORMATION
SW : V1.0M6 (01/11/01)
SW CODE : FLDKNMCH0A
BW PCB INFORMATION
BOOT : V2.02-02/08/00
BIOS : V2.32-31/07/01
To consult information about the controller's software version.
To consult information about the
PCB.
Input/output menu
The "input/output" menu gives the status of all the digital inputs and
the relay outputs of the unit.
BX DIGITAL INPUTS
M1 SAFETY OK
M2 SAFETY OK
M3 SAFETY NOK
BC DIGITAL INPUTS
FLOWSWITCH : FLOW OK
REV.PHASE PR. : OK
BC CHANG. DIG. INPUTS
DI1 DUAL SETP : SETP.1
DI2 REM. ON/OFF : OFF
DI3 REM. C/H : COOL
To check whether any module
safeties are active.
To check the reverse phase protector
and if there's any waterflow to the
evaporator.
To check the status of the changeable digital inputs.
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
OUTE1 : 07.0°C OUTE3 :
OUTE2 : 07.0°C 07.0°C
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
C11 : ON C21 :
C12 : ON ON
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
C22 : ON
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
RH11 : 00000h RH21:
RH12 : 00000h 00000h
To check which were the evaporator
outlet water temperature of all
modules at the moment of shutdown.
To check which was the status of the
compressors at the moment of
shutdown (first screen).
To check which was the status of the
compressors at the moment of
shutdown (second screen).
To check which were the total
amount of running hours of the compressors at the moment of shutdown
(first screen).
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
RH22 : 00000h
To check which were the total
amount of running hours of the compressors at the moment of shutdown
(second screen).
History menu
The "history" menu contains all the information concerning the latest
shutdowns. The structure of those menus is identical to the structure
of the safeties menu. Whenever a failure is solved and the operator
performs a reset, the concerning data from the safeties menu is
copied into the history menu. Warnings are also recorded.
Additionally the number of safeties that already occurred, can be
consulted on the first line of the history screens.
BC RELAY OUTPUTS
C11 : ON C12 : ON
C21 : ON C22 : ON
C31 : ON C32 : OFF
BC RELAY OUTPUTS
LPBYPASS1 : CLOSED
LPBYPASS2 : CLOSED
LPBYPASS3 : OPEN
BC RELAY OUTPUTS
GEN. ALARM : CLOSED
PUMP/GEN OPER : CLOSED
BW CHANG. REL OUTPUTS
DO1 REV.VALVE(C/H) : O
User password menu
B CHANGE PASSWORD
NEW PASSWORD : 0000
CONFIRM : 0000
Cooling/heating menu
B COOLING/HEATING
MODE : COOLING (EVAP)
To check the status of the compressor relay outputs.
To check the status of the modules
low pressure bypass.
To check the status of the alarm
voltage free contact and the pump/
general operation contact.
To check the status of the changeable relay output.
To change the user password.
To select cooling or heating mode.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
10
Tasks of the user settings menu
Entering the user settings menu
The user settings menu is protected by the user password, a 4-digit
number between 0000 and 9999.
1Enter the USERSETTINGS MENU through the main menu. (Refer to
the chapter "Main menu" on page 9).
The controller will request the password.
2Enter the correct password using the g and h keys.
3Press q to confir m the password and to enter the user settings
menu.
The controller automatically enters the first screen of the user
settings menu.
To define settings of a certain function:
1Go to the appropriate screen of the usersettings menu using the
g and h keys.
2Position the cursor behind the parameter to be modified using
the q key.
3Select the appropriate setting using the g and h keys.
4Press q to confirm the selection.
When the selection has been confirmed, the cursor switches to
the next parameter which can now be modified.
5Repeat from instruction 2 onwards to modify the other
parameters.
Defining and activating the control mode
The unit is equipped with a thermostat which controls the cooling
capacity of the unit. Two different control modes exist:
■manual control mode: the operator controls the capacity himself
- MANUAL CONTROL
■inlet control mode: uses the evaporator and/or condenser
entering water temperature to control the capacity of the unit -
INLET WATER
When the operator wants to control the capacity himself, he can
activate manual control mode using the CONTROL SETTINGS screen of
the user settings menu. In this case, he has to define the following
parameters:
■MODE (present mode): manual control.
■C11, C12, C21, C22, C31, C32 (compressor status of module 1, 2
and 3 in manual mode or capacity limitation value in case the
"capacity limitation remote contact" is enabled): ON or OFF.
NOTE
To activate manual control mode, select MANUAL as
present mode. To deactivate the manual control mode,
select INLET WATER as present mode.
Defining the thermostat settings
When automatic control mode is selected, the unit uses a thermostat
to control the cooling or heating capacity. The maximum number of
thermostat steps are as listed:
9841476
11341626
12841776
1926
However, the thermostat parameters are not fixed and can be
modified via the THERMOST. SETTINGS screen of the user settings menu.
The default, limit and step values for the thermostat parameters are:
A functional diagram showing the thermostat parame-
Lower limit Upper limitStepDefault
ters can be found in "Annex I" on page 16.
Defining the lead-lag mode
The lead/lag mode determines which module starts up first in case of
a capacity demand.
The lead-lag parameters are:
■LEAD-LAG MODE
Automatic: the controller decides whether module 1, module 2,
or module 3 starts up first.
The modules follow the entered order of starting up (see table
below).
3 modules2 modules
first > next > lastfirst > last
12312
23121
312
NOTE
■LEAD-LAG HOURS: In the automatic mode, the number of hours
If a module is de-activated due to a failure, the next
module will start up instead.
indicated on the display is the maximum difference between the
running hours of the modules. This value is impor tant for maintenance purposes. It should be set high enough so that the
modules do not require maintenance at the same time and that
at least one module can remain constantly active.
The lower and upper limits are 100 and 1000 hours respectively.
The default value is 1000 hours.
Operation manual
11
Defining the pump control settings
The PUMPCONTROL screen of the user settings menu allows the user to
define the pump-leadtime and pump-lagtime.
■PUMPLEADTIME: used to define the time that the pump must run
before the unit can start up.
■PUMPLAGTIME: used to define the time that the pump keeps
running after the unit has been stopped.
Defining the display settings
The DISPLAY SETTINGS screen of the user settings menu allows the
user to define the choice of language, time and date.
■LANGUAGE: used to define the language of the displayed
information of the controller.
■TIME: used to define the present time.
■DATE: used to define the present date.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Defining dual evaporator pump control
The DUAL EVAP. PUMP screen of the user settings menu allows the
user to define the steering of two evaporator pumps (for this to be
possible a changeable digital output has to be configured for a
second evaporator pump in the service menu).
■MODE: used to define which kind of control will be used for the
two evaporator pumps. When automatic rotation is chosen the
offset on running hours also has to be entered.
■OFFSET ON RH: used to define the offset in running hours between
the two pumps. Used to switch over between pumps when they
work in automatic rotation mode.
Defining the schedule timer
The SCHEDULE TIMER screen of the user settings menu allows the user
to define the schedule timer settings.
■MON, TUE, WED, THU, FRI, SAT and SUN: used to define to which
group each day of the week belongs (-/G1/G2/G3/G4).
■For each of the four groups up to nine actions can be set, each
with their respective timing. Actions include: putting the unit on/
off, setting a setpoint, setting cooling/heating and setting
capacity limitation.
■Beside these four groups there is also a holiday period group
which is set the same way as the other groups. Up to 12 holiday
periods can be entered in the HD PERIOD screen. During these
periods the schedule timer will follow the settings of the holiday
period group.
NOTE
A functional diagram showing the schedule timer
working can be found in "Annex II" on page 17.
NOTE
The unit always works with "last command". This
means that the last command given, whether manually
by the user or by the schedule timer, is always
executed.
Examples of command that can be given are switching
the unit on/off or changing a setpoint.
Activating or deactivating the setpoints password
The SETPOINT PASSWORD screen of the user settings menu allows the
user to activate or deactivate the user password needed to change
the temperature setpoint. When deactivated, the user does not have
to enter the password each time he wants to change the setpoint.
Tasks of the timers menu
Checking the actual value of the software timers
To check the actual value of the software timers, proceed as follows:
1Enter the TIMERS MENU through the main menu. (Refer to the
chapter "Main menu" on page 9.)
The controller displays the actual value of the GENERAL TIMERS:
the loadup timer, the loaddown timer, the flowstart timer, the
flowstop timer (when the unit is on and the flowstart timer has
reached zero), the pumplead timer and the pumplag timer.
2Press the h key to check the compressor timers (first screen).
The controller shows the actual value of the COMPRESSOR TIMERS:
the guard timers (one per compressor) and the antirecycling
timers (one per compressor).
3Press the h key to check the compressor timers (second
screen).
The controller shows the actual value of the COMPRESSOR TIMERS:
the guard timers (one per compressor) and the antirecycling
timers (one per compressor).
Tasks of the safeties menu
Listing activated safeties and checking the unit status
If the alarm buzzer is activated and the user presses the p key, the
controller automatically enters the safeties menu.
■The controller will enter the UNIT SAFETY screen of the safeties
menu when a unit safety was the cause of shutdown. This
screen provides the following information:
inlet water temperature setpoint of the evaporator,
inlet water temperature setpoint of the condenser,
time and date at the moment of shutdown.
■The controller will enter the MODULE 1, MODULE 2 or MODULE 3
SAFETY screen of the safeties menu when a safety of module 1,
respectively module 2 or module 3 was activated. These
screens provide information about the module status at the
moment of shutdown.
•the activated safety: freeze-up, general safety or sensor error
•the unit status at the moment of shutdown
inlet water temperature setpoint of the evaporator,
inlet water temperature setpoint of the condenser,
time and date at the moment of shutdown.
1Press the p key when the alarm buzzer is activated.
The appropriate safety screen with the basic information
appears. Press the q key to see the detailed information.
2If more than one kind of safety is active (indicated by means of
W, X or C), use the g and h keys to consult them.
As a protective measure and to ensure correct operation, the
controller's software features several countdown timers:
■LOADUP (LOADUP – refer to the thermostat parameters): star ts
counting when a thermostat step change has occurred. During
the countdown, the unit is not able to enter a higher thermostat
step.
■LOADDOWN (DWN – refer to the thermostat parameters): starts
counting when a thermostat step change has occurred. During
the countdown, the unit will not be able to enter a lower thermostat step.
■FLOWSTOP (FLOWSTOP – 5 sec): starts counting when the water
flow through the evaporator stops after the flowstart timer has
reached zero. If the water flow has not restarted during the
countdown, the unit will shut down.
■PUMPLEAD (PUMPLEAD – refer to the pump control settings):
starts counting whenever the unit is switched on. During the
countdown, the unit cannot start up.
■PUMPLAG (PUMPLAG – refer to the pump control settings): starts
counting whenever the unit is switched off. During the countdown, the pump keeps running.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
12
Tasks of the history menu
Checking the safety info and the unit status after a reset
The information available in the safeties menu is also stored in the
history menu, where it is stored after resetting the unit or the module.
In this way, the history menu provides a means of checking the unit
status at the moment of the latest 10 shutdowns.
To check the safety info and the unit status, proceed as follows:
1Enter the HISTORY MENU through the main menu. (Refer to the
chapter "Main menu" on page 9.)
The controller enters the UNIT HISTORY screen which contains the
following information: the number of shutdowns, the unit safety
which caused the most recent shutdown and the basic
information at the moment of this shutdown.
2Press the g and h keys to consult the M1, M2 or M3 HISTORY
screens.
3Press the q key to see the detailed information.
Tasks of the info menu
Consulting additional unit information
1Enter the INFO MENU through the main menu. (Refer to the
chapter "Main menu" on page 9).
The controller enters the UNIT INFORMATION screen which contains
the following information: the unit name, the refrigerant used and
the manufacturing (serial) number.
2Press h to consult the next UNIT INFORMATION screen.
This screen contains information about the controller's software
version.
Tasks of the input/output menu
Checking the status of the inputs and outputs
The input/output menu provides a means of checking the status of
the digital inputs and the status of the relay outputs.
The locked digital inputs are:
■M1, M2 or M3 SAFETY: indicates the status of the general module
safeties.
■FLOWSWITCH: indicates the status of the flowswitch, activated or
deactivated.
■REVERSE PHASE PROTECTOR: indicates the status of this safety.
The changeable digital inputs are:
■REM. C/H: indicates the status of the remote cooling/heating
switch.
■DUAL SETPOINT: indicates the status of the remote dual setpoint
switch, setpoint 1 or setpoint 2.
■REM. ON/OFF: indicates the status of the remote on/off switch.
■CAP LIM1/2/3: indicates the status of the enable/disable capacity
limitation switch(es).
The locked relay outputs are:
■LPBYPASS 1/2/3: indicates whether the low pressure of the
module is in bypass mode or not.
■C11, C12, C21, C22, C31, C32: indicates whether the compressor is
running or not.
■PUMP/GEN OPER: indicates the status of this voltage free contact.
It is activated if the pump should be ON, which also indicates
general operation.
The changeable relay outputs are:
■REV. VALVE (C/H): indicates whether the unit is running in cooling
or in heating.
■2ND EVAP PUMP: indicates the status of the second evaporator
pump.
■CONDENSER PUMP: indicates the status of the condenser pump.
■100% CAPACITY: indicates when the unit is working at 100%.
To check the inputs and outputs, proceed as follows:
1Enter the I/O STATUS MENU through the main menu. (Refer to the
chapter "Main menu" on page 9.)
The controller enters the first DIGITAL INPUTS screen.
2Consult the other screens of the input/ouput menu using the g
and h keys.
Tasks of the user password menu
Changing the user password
Access to the user settings menu and the setpoints menu is
protected by the user password (a 4-digit number between 0000 and
9999).
To change the user password, proceed as follows:
1Enter the USERPASSWORD MENU through the main menu. (Refer to
the chapter "Main menu" on page 9).
The controller will request the password.
2Enter the correct password using the g and h keys.
3Press q to confirm the password and to enter the password
menu.
The controller requests the new password.
4Press q to start the modification.
The cursor is positioned behind NEW PASSWORD.
5Enter the new password using the g and h keys.
6Press q to confirm the new password.
When the new password has been confirmed, the controller will
ask to enter the new password a second time (for safety
reasons). The cursor is positioned behind CONFIRM.
7Enter the new password again using the g and h keys.
8Press q to confirm the new password.
NOTE
The actual password will only be changed when the
new password and the confirmed password have the
same value.
Operation manual
13
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
TROUBLESHOOTING
This section provides useful information for diagnosing and correcting
certain troubles which may occur in the unit.
Before starting the trouble shooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will
save you time and money.
When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.
When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no circumstances safety devices may be bridged or changed to a value other
than the factory setting. If the cause of the problem cannot be found,
call your local dealer.
Symptom 1: The unit does not start, but the ON LED lights up
POSSIBLECAUSESCORRECTIVEACTION
The temperature setting is not
correct.
The flowstart timer is still running.The unit will start after approx. 15
Neither one of the circuits can start
up.
Unit is in manual mode (all
compressors at 0%).
Power supply failure.Check the voltage on the supply
Blown fuse or interrupted protection
device.
Loose connections.Inspect connections of the field
Shorted or broken wires.T est circuits using a tester and repair
Symptom 2: The unit does not start, but the ON LED is flashing
POSSIBLECAUSESCORRECTIVEACTION
The remote ON/OFF input is
enabled and the remote switch is off.
Symptom 3: The unit does not start and the ON LED does not light up
POSSIBLECAUSESCORRECTIVEACTION
All circuits are in failure mode.Refer to Symptom 5: One of the
One of the following safety de vices is
activated:
•Flow switch (S8L,S9L)
• Emergency stop
The ON LED is broken.Contact your local dealer.
The unit is in bypass mode.Check the bypass remote contact.
Check the controller setpoint.
seconds. Make sure that water is
flowing through the evaporator.
Refer to Symptom 4: One of the
circuits does not start up.
Check on the controller.
panel.
Inspect fuses and protection
devices. Replace by fuses of the
same size and type (refer to
"Electrical specifications" on
page 2).
wiring and the internal wiring of the
unit. Tighten all loose connections.
if necessary.
Put the remote switch on or disable
the remote ON/OFF input.
following safety devices is activated.
Refer to Symptom 5: One of the
following safety devices is activated.
Symptom 4: One of the circuits does not start up
POSSIBLECAUSESCORRECTIVEACTION
One of the following safety de vices is
activated:
• Compressor thermal protector (Q*M)
•Overcurrent relay (K*S)
•Discharge thermal protector (S*T)
•Low pressure switch
•High pressure switch (S*HP)
•Reverse phase protector (R*P)
•Freeze-up
The anti-recycling timer is still active. The circuit can only start up after
The guard timer is still active.The circuit can only start up after
The circuit is limited to 0%.Check the "enable/disable capacity
Symptom 5: One of the following safety devices is activated
Symptom 5.1: Overcurrent relay of compressor
POSSIBLECAUSESCORRECTIVEACTION
Failure of one of the phases.Check fuses on the supply panel or
Voltage too low.Measure the supply voltage.
Overload of motor.Reset. If the f ailure persists, call y our
Symptom 5.2: Low pressure switch
POSSIBLECAUSESCORRECTIVEACTION
Water flow to water heat exchanger
too low.
Shortage of refrigerant.Check for leaks and refill refrigerant,
Unit is working out of its operation
range.
Inlet temperature to the water heat
exchanger is too low.
Flow switch is not working or no
water flow.
Symptom 5.3: High-pressure switch
POSSIBLECAUSESCORRECTIVEACTION
Water flow to condenser is too low.Increase the water flow and/or check
Symptom 5.4: Reverse phase protector is activated
POSSIBLECAUSESCORRECTIVEACTION
Two phases of the power supply are
connected in the wrong phase
position.
One phase is not connected
properly.
Symptom 5.5: Discharge thermal protector is activated
POSSIBLECAUSESCORRECTIVEACTION
Unit is working outside the operation
range.
Check on the controller and refer to
Symptom 5: One of the following
safety devices is activated.
approximately 10 minutes.
approximately 1 minute.
limitation" remote contact.
measure the supply voltage.
local dealer.
RESET
Push the blue button on the overcurrent relay inside the switch box
and reset the controller.
Increase the water flow.
if necessary.
Check the operation conditions of
the unit.
Increase the inlet water temperature.
Check the flow switch and the water
pump.
RESET
After pressure rise, this safety resets
automatically, but the controller still
needs to be reset.
the strainer for clogging.
RESET
After finding the cause, push the
button on the high-pressure switch
housing and reset the controller.
Invert two phases of the power
supply (by licensed electrician).
Check the connection of all phases.
RESET
After inverting two phases or fixing
the power supply cables properly,
the protector is reset automatically,
but the controller still needs to be
reset.
Check the operation condition of the
unit.
RESET
After temperature decrease, the
thermal protector resets
automatically but the controller still
needs to be reset.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
14
Symptom 5.6: Flow switch is activated
POSSIBLECAUSESCORRECTIVEACTION
No water flow.Check the water pump.
RESET
After finding the cause, the flow
switch is reset automatically, but the
controller still needs to be reset.
Symptom 5.7: Freeze-up protection is activated
POSSIBLECAUSESCORRECTIVEACTION
Water flow too low.Increase the water flow.
Inlet temperature to the evaporator is
too low.
Flow switch is not working or no
water flow.
Symptom 5.8: Compressor thermal protector is activated
POSSIBLECAUSESCORRECTIVEACTION
Compressor motor coil temperature
too high.
Symptom 6: Unit stops soon after operation
POSSIBLECAUSESCORRECTIVEACTION
The schedule timer is activated and
is in off mode.
One of the safety devices is
activated.
Voltage is too low.Test the voltage in the supply panel
Symptom 7: Unit runs continuously and the water temperature remains
higher than the temperature set on the controller
POSSIBLECAUSESCORRECTIVEACTION
The temperature setting on the
controller is too low.
The heat production in the water
circuit is too high.
Water flow is too high.Recalculate the water flow.
The circuit is limited.Check the "enable/disable capacity
Symptom 8: Excessive noises and vibrations of the unit
POSSIBLECAUSESCORRECTIVEACTION
Unit has not been fixed properly.Fix the unit as described in the
Increase the inlet water temperature.
Check the flow switch and the water
pump.
RESET
After temperature increase the
freeze-up is reset automatically, but
the circuit controller needs to be
reset.
Compressor is not cooled sufficiently
by the refrigerant medium.
RESET
After temperature decrease the
thermal protector is reset
automatically, but the circuit
controller needs to be reset.
If the protector is activated
frequently, call your local dealer.
Work according to the settings in the
schedule timer or disable the
schedule timer.
Check safety devices (refer to
Symptom 5: One of the following
safety devices is activated).
and, if necessary, in the electrical
compartment of the unit (voltage
drop due to supply cables is too
high).
Check and adjust the temperature
setting.
The cooling capacity of the unit is too
low. Call your local dealer.
limitation" remote contact.
installation manual.
Before carrying out any maintenance or repair activity,
always switch off the circuit breaker on the supply panel,
remove the fuses or open the protection devices of the
unit.
Do never clean the unit with water under pressure.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.
Refrigerant type:R410A
(1)
GWP
value:2090
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.
Maintenance activities
The wiring and power supply must be checked by a
licensed electrician.
■Field wiring and power supply
• Check the power supply voltage on the local supply panel.
The voltage should correspond to the voltage marked on the
identification label of the unit.
• Check the connections and make sure they are properly
fixed.
• Check the proper operation of the circuit breaker and the
earth leak detector provided on the local supply panel.
■Internal wiring of the unit
Visually check the switch boxes on loose connections (terminals
and components). Make sure that the electrical components are
not damaged or loose.
■Earth connection
Make sure that the earth wires are still connected properly and
that the earth terminals are tightened.
■Refrigerant circuit
• Check for leaks inside the unit. In case a leak is detected, call
your local dealer.
• Check the working pressure of the unit. Refer to paragraph
"Switching the unit on" on page 7.
■Compressor
• Check on oil leaks. If there is an oil leak, call your local
dealer.
• Check for abnormal noises and vibrations. If the compressor
is damaged, call your local dealer.
■Water supply
• Check if the water connection is still well fixed.
• Check the water quality (refer to the installation manual of the
unit for specifications of the water quality).
■Water filters
• Check if the mesh width is 1 mm maximum.
MAINTENANCE
In order to ensure optimal availability of the unit, a number of checks
and inspections on the unit and the field wiring have to be carried out
at regular intervals.
If the unit is used for air conditioning application, the described
checks should be executed at least once a year. In case the unit is
used for other applications, the checks should be executed every
4 months.
Operation manual
15
Disposal requirements
Dismantling of the unit, treatment of the refrigerant, oil and any other
parts, should be done in accordance with the relevant local and
national regulations.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
ANNEX I
0
1
6
5
4
3
2
ab
Stepnumber
Setpoint
Temperature
Thermostat parameters
Cooling: Inlet water temperature control of evaporatorHeating: Inlet water temperature control of condenser
The figures below show the thermostat diagram in case of inlet water temperature control.
■2 step thermostat control
Stepnumber
■2 step thermostat control
Stepnumber
147~192
0
1
2
Setpoint
ab
Temperature
0
1
2
ab
Setpoint
Temperature
■4 step thermostat control (default 98~128) ■4 step thermostat control (default 98~128)
98~128
Stepnumber
0
1
2
3
4
Setpoint
ab
147~192
Temperature
98~128
Stepnumber
0
1
2
3
4
ab
Setpoint
Temperature
■6 step thermostat control (default 147~192) ■6 step thermostat control (default 147~192)
Stepnumber
ab
0
1
2
3
4
5
6
Setpoint
Temperature
The default value and the upper and lower limits of the thermostat parameters are listed in the table below.
INLET CONTROLDefault valueLower limitUpper limit
Steplength - a
Step difference - b
Load-up time
Load-down time
Setpoint Cooling
Setpoint Heating
NOTE
The thermostat parameters mentioned above only apply to standard units.
Vorschriften zur Entsorgung.................................................................... 16
LESEN SIE SICH DIESE ANLEITUNG SORGFÄLTIG
DURCH, BEVOR SIE DIE EINHEIT IN BETRIEB NEHMEN.
WERFEN SIE DIESE ANLEITUNG NICHT WEG, SONDERN
BEWAHREN SIE SIE AUF, DAMIT SIE AUCH SPÄTER
NOCH DARIN NACHSCHLAGEN KÖNNEN. Lesen sie sich
das kapitel "Menü Benutzereinstellungen" auf Seite 9 durch,
bevor sie die parameter ändern.
Bei der englischen Fassung der Anleitung handelt es sich um das
Original. Bei den Anleitungen in anderen Sprachen handelt es sich
um Übersetzungen des Originals.
Das Gerät ist nicht konzipiert, um von folgenden Personengruppen
einschließlich Kindern benutzt zu werden: Personen mit eingeschränkten körperlichen, sensorischen oder geistigen Fähigkeiten
oder Personen mit mangelhafter Erfahrung oder Wissen, es sei denn,
sie sind von einer Person, die für ihre Sicherheit verantwor tlich ist,
darin unterwiesen worden, wie das Gerät ordnungsgemäß zu
verwenden und zu bedienen ist.
Kinder sollten beaufsichtigt werden, um sicher zu sein, dass sie nicht
mit dem Gerät spielen.
EINLEITUNG
Diese Bedienungsanleitung bezieht sich auf die kompakten
wassergekühlten Kaltwassererzeuger der Reihe Daikin EWWQ-KA.
Diese Einheiten sind für Innenanwendungen im Bereich Kühlung
und/oder Heizung vorgesehen und sind mit Daikin Fan-Coil-Einheiten
oder mit Lüftungseinheiten zu Klimatisierungszwecken kombinierbar.
Sie können zudem zur Versorgung mit Kühlwasser zur
Verfahrenskühlung eingesetzt werden.
Diese Anleitung wurde erarbeitet, um eine ordnungsgemäße
Funktion und Wartung des Geräts zu gewährleisten. Sie beschreibt
die sachgemäße Bedienung des Geräts und gibt bei etwaigen
Problemen Hilfestellung. Das Gerät ist zwar mit Schutzvorrichtungen
ausgestattet, diese verhindern jedoch nicht automatisch alle
Probleme, die auf unsachgemäße Bedienung oder Wartung
zurückzuführen sind.
Wenden Sie sich bei länger anhaltenden Störungen an Ihren
nächsten Händler.
Vergewissern Sie sich vor der Erstinbetriebnahme des
Geräts, ob es ordnungsgemäß installiert wurde. Lesen Sie
sich hierzu die mit dem Gerät gelieferte Installationsanleitung und die Empfehlungen unter "Kontrollen vor der
(1) Die vollständigen technischen Daten sind dem technischen Datenbuch zu entnehmen.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Bedienungsanleitung
2
BESCHREIBUNG
98~128 Hp
147~192 Hp
17
26 11
23
14
20
27
18
12
24
15
21
27
19
13
25 16
22
27
10
5
2
3
8
6
1
1
9
7
4
500500
500
Abbildung: Hauptbauteile
1Verdichter15Verflüssiger-Wasser ein 2
2Verdampfer16Verflüssiger-Wasser ein 3
3Verflüssiger17Wassertemperaturfühler an Verdampfereingang 1
4Schaltkasten18Wassertemperaturfühler an Verdampfereingang 2
5Kaltwasser ein 119Wassertemperaturfühler an Verdampfereingang 3
6Kaltwasser ein 220Frostschutzfühler 1
7Kaltwasser ein 321Frostschutzfühler 2
8Kaltwasser aus 122Frostschutzfühler 3
9Kaltwasser aus 223Wassertemperaturfühler an Verflüssigereingang 1
10Kaltwasser aus 324Wassertemperaturfühler an Verflüssigereingang 2
11Verflüssiger-Wasser aus 125Wassertemperaturfühler an Verflüssigereingang 3
12Verflüssiger-Wasser aus 226Steuerung mit digitaler Anzeige 98~192
13Verflüssiger-Wasser aus 327Netzanschluß
14Verflüssiger-Wasser ein 1
Für Wartung erforderlicher Abstand um die Einheit
Bedienungsanleitung
3
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01
Funktion der Hauptbauteile
Wasser-
einlaß
Wasser-
auslaß
Verflüssiger
S1HP
S2HP
Filter
Filter
Q1D
Q2D
Verdichter
M1C
HP
LP
Verdichter
M2C
HP
LP
S4LP
S5LP
Verdampfer
R4TR5T
Wasserauslaß
R3T
Wassereinlaß
98~113
147~192
S1HP
S2HP
S1HP
S2HP
M1C
Q1D
HP
LP
M2C
Q2D
HP
LP
M1C
Q1D
HP
LP
M2C
Q2D
HP
LP
S4LP
R4TR5T
R3T
S5LP
S4LP
R4TR5T
R3T
S5LP
Abbildung: Funktionsplan
Beim Durchlauf durch das Gerät kann sich der Status oder die
Beschaffenheit des Kältemittels verändern. Diese Änderungen
werden durch die folgenden Hauptbauteile verursacht:
■Verdichter
Der Verdichter (M*C) arbeitet wie eine Pumpe und läßt das
Kältemittel im Kältemittelkreislauf zirkulieren. Er verdichtet den
Kältemitteldampf aus dem Verdampfer, und zwar mit einem
Druck, mit dem er am leichtesten im Verflüssiger verflüssigt
werden kann.
■Verflüssiger
Der Verflüssiger wandelt den Zustand des Kältemittels vom
gasförmigen in einen flüssigen Zustand um. Die durch das Gas
im Verdampfer aufgenommene Wärme wird durch den Verflüssiger abgeleitet, so daß der Dampf kondensiert.
■Filter
Der hinter dem Verflüssiger installierte Filter filtert kleine Partikel
aus dem Kältemittel heraus, so daß ein Verstopfen der Rohre
verhindert wird.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
■Expansionsventil
Das flüssige Kältemittel, das aus dem Verflüssiger kommt,
gelangt über ein Expansionsventil in den Verdampfer. Das
Expansionsventil bringt das flüssige Kältemittel auf einen Druck,
bei dem es im Verdampfer leicht verdampft werden kann.
■Verdampfer
Wichtigste Funktion des Verdampfers ist es, die Wärme aus dem
Wasser, das durch ihn fließt, abzuziehen. Dies geschieht durch
Umwandlung des flüssigen Kältemittels aus dem Verflüssiger in
gasförmiges Kältemittel.
■Anschlüsse für Wassereinlaß und Wasserauslaß
Die Anschlüsse für Wassereinlaß und Wasserauslaß ermöglichen einen einfachen Anschluß des Geräts an den Wasserkreislauf des Luftbehandlungsgeräts oder an industrielle
Anlagen.
Bedienungsanleitung
4
Schutzvorrichtungen
■Überstromrelais
Das Überstromrelais (K*S) befindet sich im Schaltkasten des
Geräts und schützt den Verdichtermotor bei Überlastung,
Phasenausfall oder zu niedriger Spannung. Das Relais wurde
werksseitig eingestellt und darf nicht verstellt werden. Ist es
aktiviert, muß die Rücksetzung von Hand erfolgen. Danach muß
der Regler zurückgesetzt werden.
■Hochdruckschalter
Der Hochdruckschalter (S*HP) ist an der Austrittsleitung des
Geräts eingebaut. Er mißt den Verflüssigerdruck (Druck am
Austritt des Verdichters). Steigt der Druck zu sehr an, wird der
Druckschalter aktiviert, und der Schaltkreis wird abgeschaltet.
Nach Aktivierung stellt er sich automatisch zurück, der Regler
muß jedoch von Hand zurückgesetzt werden.
■Niederdruckschalter
Der Niederdruckschalter (S*LP) ist am Saugrohr des Geräts
installiert und mißt den Verdampferdruck (Druck am Verdichtereingang). Ist der Druck zu niedrig, löst der Druckschalter aus
und schaltet den Stromkreis ab.
Nach Aktivierung stellt er sich automatisch zurück, der Regler
muß jedoch von Hand zurückgesetzt werden.
■Phasenumkehrschutz
Die Phasenumkehrschutzvorrichtung (R1P) ist im Schaltkasten
des Geräts installiert. Sie verhindert, daß der Verdichter in die
falsche Richtung dreht. Läßt sich das Gerät nicht einschalten,
müssen zwei Phasen der Netzleitung vertauscht werden.
■Austrittsthermoschutz
Die Austrittsthermoschutzvorrichtung (Q*D) spricht bei einem
übermäßigen Anstieg der Kältemitteltemperatur bei Austritt aus
dem Verdichter an. Hat die Temperatur wieder den normalen
Wert erreicht, setzt sich der Thermoschutz automatisch zurück.
Der Regler muß jedoch manuell zurückgesetzt werden.
■Frostschutz
Der Frostschutz verhindert ein Einfrieren des Wassers im
Verdampfer während des Betriebes. Ist die Wassertemperatur
bei Austritt zu niedrig, schaltet der Hauptregler das Gerät ab.
Wenn die Wassertemperatur beim Austritt wieder einen
normalen Wert erreicht, kann die Einheit wieder anlaufen.
Wenn der Frostschutz in einem bestimmten Zeitraum mehrmals
anspricht, wird der Frostschutzalarm ausgelöst, und das Gerät
wird abgeschaltet. Die Ursache für das Auslösen dieses Alarms
muss untersucht werden. Nachdem die Temperatur des Auslasswassers wieder akzeptabel ist, muss die Alarmanzeige am
Regler manuell zurückgesetzt werden.
■Zusätzlicher Verriegelungskontakt
Um zu verhindern, daß das Gerät eingeschaltet oder betrieben
wird, wenn kein Wasser durch den Wasserwärmetauscher
zirkuliert, muß in den Anlaufkreis des Geräts ein Verriegelungskontakt (S11L), z.B. ein Strömungsschalter, eingebaut werden.
Innenverdrahtung - Teileübersicht
Siehe den dem Gerät beiliegenden Innenverdrahtungsplan. Die verwendeten Abkürzungen sind im folgenden aufgeführt:
Überprüfen Sie, ob der Hauptschalter des Geräts auf der
Verteilertafel ausgeschaltet ist.
Überprüfen Sie nach der Installation des Geräts vor dem Einschalten
des Hauptschalters folgende Punkte:
1Bauseitige Verdr ahtung
Überprüfen Sie, ob die bauseitige Verdrahtung gemäß den in der
Installationsanleitung enthaltenen Anweisungen, den
Elektroschaltplänen und den europäischen und nationalen
Vorschriften durchgeführt wurde.
2Zusätzlicher Verriegelungsk ontakt
Es sollte ein zusätzlicher Verriegelungskontakt S11L eingebaut
werden (z.B. Strömungsschalter, Kontakt von Pumpenmotorstecker). Achten Sie darauf, daß er zwischen den entsprechenden Klemmen eingebaut wird (siehe den dem Gerät
beiliegenden Elektroschaltplan). S11L muß ein Arbeitskontakt
sein.
3Sicherungen oder Schutzvorrichtungen
Überprüfen Sie, ob Größe und Ausführung der Sicherungen
oder der bauseitig installierten Schutzvorrichtungen der
Installationsanleitung entsprechen. Achten Sie außerdem
darauf, daß keine Sicherung und keine Schutzvorrichtung
überbrückt werden.
4Erdung
Achten Sie darauf, daß die Erdleitungen ordnungsgemäß
angeschlossen und die Erdungsklemmen angezogen sind.
5Innenverdrahtung
Überprüfen Sie den Schaltkasten auf lose Verbindungen oder
beschädigte elektrische Bauteile.
6Verankerung
Überprüfen Sie, ob das Gerät ordnungsgemäß verankert wurde,
um bei Inbetriebnahme ungewöhnliche Betriebsgeräusche und
Vibrationen zu vermeiden.
7Beschädigte Ausrüstung
Überprüfen Sie das Gerät innen auf beschädigte Teile oder
zusammengedrückte Rohrleitungen.
8Austreten von Kältemittel
Überprüfen Sie das Gerät innen auf austretendes Kältemittel. Ist
dies der Fall, verständigen Sie bitte Ihren Händler.
9Austreten von Öl
Überprüfen Sie den Verdichter auf austretendes Öl. Ist dies der
Fall, verständigen Sie bitte Ihren Händler.
10 Anschlußspannung
Überprüfen Sie die Anschlußspannung auf der bauseitigen
Verteilertafel. Die Spannung muß mit der auf dem Typenschild
des Geräts angegebenen Spannung übereinstimmen.
Allgemeine Empfehlungen
Lesen Sie sich vor Einschalten des Geräts die folgenden
Empfehlungen durch:
1Wenn sämtliche Installationsarbeiten und Einstellungen
fertiggestellt sind, schließen Sie alle Vorderblenden des Geräts.
2Die Bedienungstafel des Schaltkastens darf nur von einem
zugelassenen Elektriker zu Wartungszwecken geöffnet werden.
BETRIEB 98~192
Die Geräte der Baureihe 98~192 sind mit einem integrierten
Digitalregler ausgestattet, der die Inbetriebnahme, die Anwendung
und die Wartung des Geräts besonders bedienerfreundlich macht.
Dieser Teil der Anleitung ist funktionsorientiert und modular
aufgebaut. Mit Ausnahme des ersten Abschnitts, der einen kurzen
Überblick über den Regler selbst vermittelt, behandelt jeder Abschnitt
oder Unterabschnitt eine bestimmte Funktion, die mit dem Gerät
möglich ist.
Je nach Modell gibt es zwei oder drei Module im System. Die Modelle
98~113 verfügen über nur zwei Module, die Modelle 147~192
hingegen über drei. Diese Module sind im Folgenden durchgehend
mit M1, M2 und M3 bezeichnet. Alle Informationen über Modul 3 (M3)
gelten nicht für die Modelle 98~113.
Digitalregler
Benutzerschnittstelle
Der Digitalregler besteht aus einem alphanumerischen Display,
beschrifteten Tasten und einer Reihe von LEDs.
Abbildung: Digitalregler
fTaste, um das Hauptmenü aufzurufen.
oTaste zum Ein- oder Ausschalten des Geräts.
Taste um das Menü Schutzvorrichtungen aufzurufen oder
p
um einen Alarm zurückzusetzen.
Taste zum Vor- oder Zurückblättern durch die Bildschirme
g
eines Menüs (nur wenn W, X oder C erscheint) oder zum
h
Erhöhen bzw. Senken einer Einstellung.
qTaste zur Bestätigung einer Auswahl oder Einstellung.
HINWEIS
Arbeiten mit dem 98~192 Gerät
Temperaturausgabetoleranz: ±1°C.
Bei direkter Einstrahlung von Sonnenlicht kann die
Sichtbarkeit des alphanumerischen Displays beeinträchtigt werden.
Wasserzufuhr
Füllen Sie die Wasserleitungen, und halten Sie sich dabei an die für
das Gerät erforderliche Mindestwassermenge. Siehe die
Installationsanleitung.
Achten Sie darauf, daß das Wasser der in der Installationsanleitung
aufgeführten Qualität entspricht.
Evakuieren Sie die hohen Stellen im System, und überprüfen Sie den
Betrieb der Umwälzpumpe und des Strömungsschalters.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Dieses Kapitel behandelt den alltäglichen Betrieb des Geräts. Er
erläutert Ihnen Routinefunktionen wie z.B.:
■"Festlegen der Sprache" auf Seite 7
■"Einschalten des Geräts" auf Seite 7 und "Ausschalten des
Geräts" auf Seite 7
■"Abrufen der aktuellen Betriebsinformationen" auf Seite 7
■"Auswahl von Kühl- oder Heizbetrieb" auf Seite 8
■"Ändern der Temperatureinstellung" auf Seite 8
■"Zurücksetzen des Geräts" auf Seite 8
Bedienungsanleitung
6
Festlegen der Sprache
Ausschalten des Geräts
Die folgenden Sprachen können als Dialogsprache ausgewählt
werden: Deutsch, Englisch, Französisch, Italienisch oder Spanisch.
1Gehen Sie in das Menü Benutzereinstellungen. Siehe auch
Kapitel "Hauptmenü" auf Seite 9
2Öffnen Sie über die Tasten g und h den entsprechenden
Bildschirm des Menüs Benutzereinstellungen.
3Gehen Sie mit Hilfe der Taste q in das entsprechende Feld
(SPRACHE).
4Drücken Sie die Tasten g und h, um die Spracheinstellung zu
ändern.
5Drücken Sie die Taste q, um die neu ausgewählte Sprache zu
bestätigen.
Nachdem die Einstellung bestätigt wurde, rückt der Cursor zur
nächsten Einstellung weiter.
Einschalten des Geräts
1Drücken Sie die Taste o auf dem Regler.
Abhängig davon, ob der Fernbedienungsschalter EIN/AUS konfigu-
riert wurde (siehe Installationsanleitung), können die folgenden
Bedingungen auftreten.
Wenn der Fernbedienungsschalter EIN/AUS konfiguriert wurde,
leuchtet die LED in der Taste J auf, und ein Inbetriebnahme-Zyklus
startet. Stehen alle Uhren auf Null, nimmt das Gerät seinen Betrieb
auf.
Wenn ein Fernbedienungsschalter EIN/AUS konfiguriert wurde, gilt
die folgende Tabelle:
Lokale TasteFernschalterGeräto LED
EINEINEINEIN
EINAUSAUSBlinkt
AUSEINAUSAUS
AUSAUSAUSAUS
Wenn die Fernbedienungseinstellung Ein/Aus auf NEIN steht:
Drücken Sie die Taste o auf dem Regler.
Die LED in der Taste o erlischt.
Wenn die Fernbedienungseinstellung Ein/Aus auf JA steht:
Drücken Sie die Taste o auf dem Regler, oder schalten Sie das
Gerät mit dem Fernbedienungsschalter Ein/Aus aus.
Im ersten Fall erlischt die LED in der Taste o, im zweiten Fall
beginnt sie zu blinken.
In einem Notfall muß das Gerät durch Drücken des
Notabschalters ausgeschaltet werden.
HINWEIS
Lesen Sie auch die Kapitel "Festlegen der Programm-
Uhr" auf Seite 12.
Abrufen der aktuellen Betriebsinformationen
1Gehen Sie über das Hauptmenü in das Ausgabe-Menü. (Siehe
Kapitel "Hauptmenü" auf Seite 9.)
Der Regler zeigt automatisch den ersten Bildschirm des
Anzeigemenüs an, der die folgenden Informationen liefert:
• MANUELLER MODUSoder EIN. SOLL1/2: Hand-oder
Automatikbetrieb. Wenn Automatikbetrieb gewählt wurde,
zeigt das Regelgerät den aktiven Temperatureinstellpunkt an.
Je nach dem Status des Fernbedienungskontaktes ist
Einstellung 1 oder Einstellung 2 aktiv.
• EIN. WASS. E/C: Aktuelle Wassertemperatur bei Eintritt.
• TEMPERATURSTUFE: die tatsächliche Schritteinstellung des
Thermostats. Die maximale Anzahl der Schritte des
Thermostats entspricht den Angaben:
9841476
11341626
12841776
1926
2Wenn die Einheit zum ersten Mal in Betrieb genommen wird,
oder wenn sie über einen längeren Zeitraum nicht in Betrieb war,
sollten unbedingt die folgenden Punkte überprüft werden.
Ungewöhnliche Geräusche und Vibrationen
Achten Sie darauf, daß das Gerät keine ungewöhnlichen
Geräusche oder Vibrationen verursacht: Überprüfen Sie
Verankerung, Absperrventile und Leitungen. Erzeugt der
Verdichter ungewöhnliche Geräusche, kann dies auch daran
liegen, daß zuviel Kältemittel eingefüllt wurde.
3Nimmt der Kaltwassererzeuger nach einigen Minuten den
Betrieb nicht auf, siehe "Fehlersuche" auf Seite 14.
2Mit der Taste h gelangen Sie zum nächsten Bildschirm des
Anzeigemenüs.
Dieser Bildschirm des Anzeigemenüs bietet folgende
Informationen über den Verdampfer:
• M1 AUSL. WASS: die tatsächliche Temperatur des Auslasswassers aus Modul 1.
• M2 AUSL. WASS: die tatsächliche Temperatur des Auslasswassers aus Modul 2.
• M3 AUSL. WASS: die tatsächliche Temperatur des Auslasswassers aus Modul 3.
3Mit der Taste h gelangen Sie zum nächsten Bildschirm des
Anzeigemenüs.
Der Bildschirm VERDICHTER STATUS des Ausgabe-Menüs bietet
Informationen zum Status der unterschiedlichen Schaltkreise.
• C11: Aktueller Status des Verdichters 1 von Modul 1.
• C12: Aktueller Status des Verdichters 2 von Modul 1.
• C21: Aktueller Status des Verdichters 1 von Modul 2.
• C22: Aktueller Status des Verdichters 2 von Modul 2.
• C31: Aktueller Status des Verdichters 1 von Modul 3.
• C32: Aktueller Status des Verdichters 2 von Modul 3.
Wenn ein Schaltkreis auf AUS steht, können die folgenden
Statusinformationen erscheinen:
• ALARM AKTIV: eine der Schutzvorrichtungen des Kreislaufs
wurde ausgelöst (s. Kapitel "Fehlersuche" auf Seite 14).
• (LIMIT): der Kreislauf wird durch einen Fernkontakt
beschränkt.
• TIMER AKTIV: der aktuelle Wert einer der Software-Uhren ist
nicht gleich Null (siehe "Menü Zeitschaltuhren" auf Seite 10).
• BETRIEBSBER.: der Schaltkreis ist betriebsbereit, wenn eine
zusätzliche Kühllast benötigt wird.
Bedienungsanleitung
7
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01
Die vorhergehenden AUS-Anzeigen sind gemäß ihrer Rangfolge
wiedergegeben. Ist eine der Zeitschaltuhren in Betrieb und eine
Schutzvorrichtung aktiv, so lautet die Statusinformation ALARM AKTIV.
4Mit der Taste h gelangen Sie zum nächsten Bildschirm des
Anzeigemenüs.
Zum Einsehen tatsächlicher Betriebsinformationen über die
Gesamtbetriebsstunden der Verflüssiger.
Auswahl von Kühl- oder Heizbetrieb
Das Menü Kühlen/Heizen ermöglicht es dem Benutzer, die Einheit in
den Kühlungs- oder Heizbetrieb zu versetzen.
Das KUEHLEN/HEIZEN MENU bietet Informationen über den ausgewählten Betriebsmodus.
■ KUEHL. (VERDA.): Kühlungsmodus. Die beiden Sollwerte
können zum Regeln der Temperatur des Einlasswassers des
Verdampfers verwendet werden.
■ HEIZ. (VERFL.): Heizmodus. Die beiden Sollwerte können zum
Regeln der Temperatur des Einlaßwassers des Verflüssigers
verwendet werden.
So legen Sie den Kühl-/Heizbetrieb fest:
1Wechseln Sie vom Hauptmenü zum Menü Kühlen/Heizen.
(Siehe Kapitel "Hauptmenü" auf Seite 9.)
2Setzen Sie den Cursor mit der Taste q hinter MODUS.
3Wählen Sie mit den Tasten g und h die geeignete Einstellung aus.
4Bestätigen Sie Ihre Auswahl mit q.
Der Cursor wird wieder in der linken oberen Ecke des
Bildschirms angezeigt.
Ändern der Temperatureinstellung
Die Einheit ermöglicht es, zwei oder vier unabhängige TemperaturSollwerte festzulegen und auszuwählen.
Im Kühlbetrieb sind zwei Sollwerte zur Einlassregelung des
Verdampfers reserviert.
■EIN. SOLL 1E: Temperatur des Einlaßwassers des Verdampfers,
Sollwert 1,
■EIN. SOLL 2E: Temperatur des Einlaßwassers des Verdampfers,
Sollwert 2.
Im Heizbetrieb sind zwei Sollwerte für die Einlaßregelung reserviert.
■EIN. SOLL 1C: Temperatur des Einlaßwassers des Verflüssigers,
Sollwert 1,
■EIN. SOLL 2C: Temperatur des Einlaßwassers des Verflüssigers,
Sollwert 2.
Im Doppelthermostatbetrieb sind zwei Sollwerte für die Einlaßregelung des Verdampfers und zwei andere für die Einlaßregelung
des Verflüssigers reserviert.
■EIN. SOLL 1E: Temperatur des Einlaßwassers des Verdampfers,
Sollwert 1,
■EIN. SOLL 2E: Temperatur des Einlaßwassers des Verdampfers,
Sollwert 2.
■EIN. SOLL 1C: Temperatur des Einlaßwassers des Verflüssigers,
Sollwert 1,
■EIN. SOLL 2C: Temperatur des Einlaßwassers des Verflüssigers,
Sollwert 2.
Die Auswahl zwischen Einstellung 1 und 2 erfolgt über einen Fernbedienungsschalter für duale Einstellung (der vom Kunden installiert
werden muß). Die aktuelle gewählte Einstellung kann im AusgabeMenü abgelesen werden.
Wenn die manuelle Regelungsart ausgewählt wurde (siehe "Menü
Benutzereinstellungen" auf Seite 9), wird keine der oben genannten
Einstellungen aktiviert.
Ändern der Einstellung:
1Gehen Sie vom Hauptmenü ins Menü Einstellungen (siehe
Kapitel "Hauptmenü" auf Seite 9).
Wenn das Benutzer-Password deaktiviert wurde, um Ein-
stellungen zu verändern (siehe "Menü Benutzereinstellungen"
auf Seite 9), zeigt der Regler sofort das Menü Einstellungen an.
Wenn das Benutzer-Password aktiviert wurde, um Einstellungen
zu verändern, geben Sie den korrekten Code mit den Tasten g
und h ein (siehe "Menü Benutzer-Password" auf Seite 11).
Drücken Sie die Taste q, um das Password zu bestätigen und
um ins Menü Einstellungen zu gelangen.
2Wählen Sie die Einstellung, die geändert werden soll, mit der
Taste q aus.
Eine Einstellung wurde ausgewählt, wenn der Cursor hinter der
Bezeichnung der Einstellung blinkt.
Das Zeichen ">" zeigt die aktuelle ausgewählte Einstellung an.
3Drücken Sie die Tasten g und h, um die Temperatureinstellung
zu verändern.
Die Standard-, Grenz- und Schrittwerte für die
Temperatursollwerte beim Kühlen (Verdampfer) und Heizen
(Verflüssiger) sind:
EE
Standardwert12°C30°C
Grenzwerte
Stufenwert0.1°C0.1°C
(a) Bei Glykol-Geräten kann der untere Grenzwert für die Einstellung der
(a)
Kühltemperatur werksseitig eingestellt werden:
EIN. SOLL E/C: 5°C, 3°C, –2°C, –7°C
EEEEIIIINNNN.... SSSSOOOOLLLLLLLL EE
8 --> 23°C15--> 50°C
EEEEIIIINNNN.... SSSSOOOOLLLLLLLL CC
CC
4Drücken Sie die Taste q, um die geänderte Temperatur-
einstellung zu speichern.
Wenn die Einstellung bestätigt wurde, rückt der Cursor zur
nächsten Einstellung weiter.
5Befolgen Sie zur Änderung der anderen Einstellungen die
Anweisungen ab Punkt 2.
HINWEIS
Lesen Sie auch die Kapitel "Festlegen der Programm-
Uhr" auf Seite 12.
Zurücksetzen des Geräts
Die Einheiten sind mit drei Arten von Schutzvorrichtungen ausgestattet: Schutzvorrichtungen für die Einheiten, die Module und das
Netzwerk.
Wenn eine Geräte-Schutzvorrichtung anspricht, werden alle
Verdichter abgeschaltet. Das Schutzvorrichtungsmenü zeigt an,
welche Schutzvorrichtung eingeschaltet ist. Der VERDICHTER STATUSBildschirm des Ausgabemenüs zeigt dann AUS-ALARM AKTIV für alle
Kreisläufe an. Die rote LED in der Taste p leuchtet, und der Summer
im Regler wird aktiviert.
Wenn eine Modul-Schutzvorrichtung anspricht, werden die Verdichter
des betreffenden Moduls abgeschaltet. Der VERDICHTER STATUS-
Bildschirm des Ausgabe-Menüs zeigt dann AUS-ALARM AKTIV für das
entsprechende Modul an. Die rote LED in der Taste p leuchtet, und
der Summer im Regler wird aktiviert.
Wenn das Gerät aufgrund eines Stromausfalls abgeschaltet wurde,
setzt es sich automatisch zurück und nimmt seinen Betrieb
automatisch wieder auf, wenn wieder Strom vorhanden ist.
Zurücksetzen des Geräts:
1Drücken Sie die Taste p, um den Alarm zu bestätigen.
Der Summer wird abgeschaltet.
Der Regler schaltet automatisch auf den entsprechenden
Bildschirm des Menüs Schutzvorrichtungen um: GeräteSchutzvorrichtung oder Schaltkreis-Schutzvorrichtung.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Bedienungsanleitung
8
2Stellen Sie fest, weshalb das Gerät abgeschaltet wurde, und
beheben Sie die Ursache.
Siehe "Aufstellung der aktivierten Schutzvorrichtungen und
Überprüfung des Gerätestatus" auf Seite 13sowie Kapitel
"Fehlersuche" auf Seite 14.
Wenn eine Schutzvorrichtung zurückgesetzt werden kann,
beginnt die LED unter der Taste p zu blinken.
3Drücken Sie die Taste p, um die nicht mehr aktivierten
Schutzvorrichtungen zurückzusetzen.
Wenn alle Schutzvorrichtungen deaktiviert und zurückgesetzt
sind, verlischt die LED unter der Taste p. Wenn eine der
Schutzvorrichtungen noch aktiviert ist, leuchtet die LED unter
der Taste p erneut auf. Führen Sie in diesem Fall erneut
Anweisung 2 durch.
4Wenn eine Geräte-Schutzvorrichtung aktiviert wurde, oder wenn
alle Module durch Schutzvorrichtungen abgeschaltet wurden,
schalten Sie das Gerät mit der Taste o wieder ein.
BC VERDICHTER STATUS
C22: AUS-BETRIEBSBER.
C31: AUS-ALARM AKTIV
C32: AUS-LIMIT
Zum Abrufen von Informationen über
den Status des Verdichters (zweiter
Bildschirm).
Zum Abrufen von Betriebsinformationen über die Gesamtbetriebsstunden der Verdichter.
Menü Einstellungen
Je nach Einstellungen im Menü "user setup" (Benutzereinstellungen)
und dem ausgewählten Kühl-/Heiz-Betriebsmodus kann entweder
direkt oder über das Benutzerpaßwort in das Menü "setpoints"
(Sollwerte) gewechselt werden.
B>EIN. SOLL 1E: 12.0°C
EIN. SOLL 2E: 12.0°C
EIN. SOLL 1C: 30.0°C
EIN. SOLL 2C: 30.0°C
Zum Festlegen der Temperatureinstellpunkte.
Wenn der Benutzer den Strom abschaltet, um eine Schutzvorrichtung instandzusetzen, wird die Schutzvorrichtung
nach Einschalten des Stroms automatisch zurückgesetzt.
HINWEIS
Die aufgezeichneten Informationen, d. h. wie häufig
eine Geräte- oder Schaltkreis-Schutzvorrichtung angesprochen hat, sowie der Gerätestatus zum Zeitpunkt
des Abschaltens, können im Aufzeichnungs-Menü
überprüft werden.
Fortschrittliche Funktionen des Digitalreglers
Dieses Kapitel gibt Ihnen einen Überblick über den Menüaufbau
sowie eine kurze Beschreibung der Funktionen aller Menüpunkte. Im
folgenden Kapitel erfahren Sie, wie Sie das Gerät mit Hilfe der
verschiedenen Menüfunktionen einstellen und konfigurieren können.
Der Pfeil X auf dem Display zeigt an, dass Sie im aktuellen Menü mit
der Taste h zum folgenden Bildschirm weiterblättern können. Der
Pfeil W zeigt an, dass Sie im aktuellen Menü mit der Taste g zum
vorhergehenden Bildschirm zurückblättern können. Wenn C
angezeigt wird, können Sie mit den Tasten g und h zum vorhergehenden Bildschirm zurückkehren oder zum folgenden Bildschirm
weiterblättern.
Hauptmenü
Mit den Tasten g und h durch das Hauptmenü blättern, um die
Markierung > vor das Menü Ihrer Wahl zu bewegen. Drücken Sie die
Taste q, um in das ausgewählte Menü zu gelangen.
>AUSLESE MENU
SOLL WERT MENU
BEN. EINST. MENU
TIMERS MENU
HISTORIE MENU
INFO MENU
I/O STATUS MENU
BEN. PASSWORT MENU
KUEHLEN/HEIZEN MENU
Ausgabe-Menü
BX BX MANUELLER MODUS
EIN. WASS. E: 12.0°C
EIN. WASS. C: 30.0°C
TEMPERATURSTUFE: 2/6
BC VERDICHTER STATUS
C11: AUS-BETRIEBSBER.
C12: AUS-BETRIEBSBER.
C21: AUS-BETRIEBSBER.
Zum Abrufen aktueller Betriebsinformationen über den Regelmodus,
die Temperatur des Einlasswassers
des Verdampfers/Verflüssigers und
der Thermostatstufe.
Zum Abrufen von Informationen über
die Temperatur des Auslasswassers
aus den Modulen 1, 2 und 3 (nur für
147~192).
Zum Abrufen von Informationen über
den Status des Verdichters (erster
Bildschirm).
Menü Benutzereinstellungen
Das Menü "Benutzereinstellungen", das mit einem Password
geschützt wird, ermöglicht die vollkommene Anpassung des Geräts
an die Bedürfnisse des Kunden.
BC KONTROLL EINST.
MOD: MANUELLE KONTR.
C11: AUS 21: AUS
C12: AUS 22: AUS
Überprüfung des aktuellen Werts der
Verdichter-Uhren (erster Bildschirm).
Überprüfung des aktuellen Werts der
Verdichter-Uhren (zweiter Bildschirm).
Menü Schutzvorrichtungen
Das Menü "Schutzvorrichtungen" bietet hilfreiche Informationen zur
Fehlersuche.
BX ALARM EINHEIT
0C9: EIN E SENS. FEHL.
BX ALARM MODUL 1
1CA : AUS E SENS.FEHL.
BX ALARM MODUL 2
2CA : AUS E SENS.FEHL.
BX ALARM MODUL 3
3CA : AUS E SENS.FEHL.
Zum Abrufen, welche Sicherheitsfunktion der Einheit für die
Abschaltung verantwortlich ist.
Zum Abrufen, welche Sicherheitsfunktion des Moduls 1 für die
Abschaltung verantwortlich ist.
Zum Abrufen, welche Sicherheitsfunktion des Moduls 2 für die
Abschaltung verantwortlich ist.
Zum Abrufen, welche Sicherheitsfunktion des Moduls 3 für die
Abschaltung verantwortlich ist.
Menü Aufzeichnung
Das Menü "Aufzeichnung" enthält alle Informationen über die letzten
Abschaltungen. Der Aufbau dieses Menüs ist identisch mit dem des
Schutzvorrichtungsmenüs. Sobald eine Störung behoben ist und der
Bediener eine Rückstellung vornimmt, werden die betreffenden
Daten des Schutzvorrichtungsmenüs in das Aufzeichnungsmenü
kopiert. Warnungen werden ebenfalls aufgezeichnet.
Zusätzlich kann die Anzahl der bisher ausgelösten Schutzvorrichtungen auf der ersten Zeile der Aufzeichnungsbildschirme
abgelesen werden.
Info-Menü
BX ZEIT INFORM.
ZEIT: 00h00
DAT: 01/01/2001
BC EINHEIT INFORM.
MODELL: WW-HP-32
HERSTELL. NR.: 0000000
KAELTEMITTEL: R134a
BC EINHEIT INFORM.
SW: V1,0M6 (01/11/01)
SW CODE: FLDKNMCH0A
Abrufen von zusätzlichen Informationen über das Gerät, wie z.B.
Gerätetyp, verwendetes Kältemittel
und Herstellungsnummer.
Abrufen von Informationen über die
Version der Regler-Software.
Abrufen von Informationen über die
Leiterplatte.
Menü Eingang/Ausgang
Neben der Grundinformation können Bildschirmanzeigen mit
detaillierteren Informationen aufgerufen werden, wenn das
Schutzvorrichtungsmenü aktiviert ist. Drücken Sie die Taste q. Es
erscheinen "ähnliche" Bildschirme wie die folgenden:
BC EINHEIT HIST.: 004
0C9: EIN E SENS. FEHL.
00h00 - 12/01/2001
MENUELLER MODUS
BC EINHEIT HIST.: 004
0C9: EIN E SENS. FEHL.
EIN. E: 12.0°C STUFE:
EIN. C: 30.0°C 0
BC EINHEIT HIST.: 004
0C9: EIN E SENS. FEHL.
AUS. 1: 07.0°C
AUS. 2: 07.0°C
Zum Feststellen der Uhrzeit und der
Regelungsart zum Zeitpunkt der
Geräteabschaltung.
Zum Feststellen der gemeinsamen
Temperatur des Einlasswassers in
den Verdampf er und V erflüssiger .
Zum Feststellen der Temperatur des
Auslasswassers aus dem
Verdampfer in allen Modulen zum
Zeitpunkt der Abschaltung.
BC EINHEIT HIST.: 004
0C9: EIN E SENS. FEHL.
C11: EIN C21:
C12: EIN EIN
BC EINHEIT HIST.: 004
0C9: EIN E SENS. FEHL.
C22: EIN
Zum Feststellen des Status der
Verdichter zum Zeitpunkt der
Abschaltung (erster Bildschirm).
Zum Feststellen des Status der
Verdichter zum Zeitpunkt der
Abschaltung (zweiter Bildschirm).
Das Menü "Eingang/Ausgang" zeigt den Status aller digitalen
Eingänge und der Relais-Ausgänge des Geräts an.
BX DIG. EING.
M1 SCHUTZ: OK
M2 SCHUTZ: OK
M3 SCHUTZ: NOK
BC DIG. EING.
STROEMW.: STROEM OK
REV. PHASE PR.: OK
Zur Überprüfung, ob eine ModulSchutzvorrichtung aktiviert ist.
Zur Überprüfung des Phasenumkehrschutzes, und ob der
Wasserzufluss zum Verdampfer
gewährleistet ist.
BC DIG. EING. WECHS.
DI1 DOPP. SOLL: SOLL1
DI2 FB EINAUS: AUS
DI3 FERN. K/H: KUEHL.
BC RELAIS AUSG.
C11: EIN C12: EIN
C21: EIN C22: EIN
C31: EIN C32: AUS
BC RELAIS AUSG.
LPBYPASS1: GESCHL.
LPBYPASS2: GESCHL.
LPBYPASS3: OFFEN
BC RELAIS AUSG.
ALLG. ALARM: GESCHL.
PUMP/ALLG. OP.: GESCHL
Zur Überprüfung des Status der
veränderbaren digitalen Eingänge.
Zur Überprüfung des Status der
Relais-Ausgänge der Verdichter.
Zur Überprüfung des NiederdruckBypasses der Module.
Zum Ermitteln des Status der alarmspannungsfreien Kontakte und der
Pumpen-/allgemeinen
Betriebskontakte.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Bedienungsanleitung
10
BW REL. AUSG. WECHS.
DO1 UMKEHRV. (K/H): O
Zur Überprüfung des Status des
veränderbaren Relais-Ausgangs.
Menü Benutzer-Password
B PASSWORT AEND.
NEUES PASSW.: 0000
BESTAET.: 0000
Änderung des Benutzer-Passwords.
Menü Kühlen/Heizen
B KUEHLEN/HEIZEN
MODUS: KUEHL. (VERDA.)
Funktionen des Menüs Benutzereinstellungen
Zum Auswählen von Kühl- oder
Heizmodus.
Zugang zum Menü Benutzereinstellungen
Das Menü "Benutzereinstellungen" ist vom Benutzer-Password (einer
vierstelligen Zahl zwischen 0000 und 9999) geschützt.
1Wechseln Sie vom Hauptmenü in das BEN. EINST. MENU. (Siehe
Kapitel "Hauptmenü" auf Seite 9.)
Der Regler fragt Sie nach dem Password.
2Geben Sie mit den Tasten g und h das korrekte Password ein.
3Drücken Sie die Taste q, um das Password zu bestätigen und
um ins Menü Benutzereinstellungen zu gelangen.
Der Regler zeigt automatisch den ersten Bildschirm des Menüs
Benutzereinstellungen an.
Definieren von Einstellungen einer bestimmten Funktion:
1Öffnen Sie über die Tasten g und h den entsprechenden Bild-
schirm des Menüs Benutzereinstellungen.
2Platzieren Sie den Cursor mit der Taste q hinter den zu
ändernden Parameter.
3Wählen Sie über die Tasten g und h die entsprechende Ein-
stellung aus.
4Drücken Sie zur Bestätigung der Auswahl die Taste q.
Wenn die Auswahl bestätigt wurde, schaltet der Cursor zum
nächsten Parameter um, der verändert werden kann.
5Wenn Sie die anderen Parameter veränder n möchten, wieder-
holen Sie diese Schritte ab Punkt 2.
Definition der Thermostateinstellungen
Wenn der automatische Regelmodus ausgewählt ist, verwendet die
Einheit zum Regeln der Kühl- oder Heizleistung einen Thermostat.
Die maximale Anzahl der Schritte des Thermostats entspricht den
Angaben:
9841476
11341626
12841776
1926
Die Thermostateinstellungen sind jedoch nicht festgelegt und können
über den Bildschirm THERMOST. EINST. im Menü Benutzereinstellungen
verändert werden.
Standard- und Grenzwerte sowie Stufen der Thermostateinstellungen sind wie folgt:
Die Primär/Sekundär-Betriebsart legt fest, welches Modul bei
Leistungsbedarf zuerst in Betrieb geht.
Die Primär/Sekundär-Parameter lauten wie folgt:
■SEQ-UMSCH. MOD
Automatic: Das Regelgerät entscheidet, ob Modul 1, Modul 2
oder Modul 3 zuerst in Betrieb geht.
Die Module gehen entsprechend der eingegebenen
Startreihenfolge in Betrieb (siehe Tabelle unten).
3 Module2 Module
als erstes > als nächstes > als letztesals erstes > als letztes
123 12
231 21
312
HINWEIS
Wenn ein Modul aufgrund einer Störung abgeschaltet
wurde, geht stattdessen das nächste Modul in Betrieb.
Definition und Aktivierung der manuellen Regelungsart
Die Einheit ist mit einem Thermostat ausgerüstet, der die Kühlleistung der Einheit regelt. Es gibt zwei verschiedene Regelmodi:
■Handbetrieb: der Bediener regelt die Leistung selbst - MANUELLE
KONTR.
■Einlaßsteuermodus: und/oder die Temperatur des in den
Verflüssiger eintretenden Wassers zum Regeln der Leistung der
Einheit - EIN. WASS.
Wenn der Bediener die Leistung selbst regeln möchte, kann er die
Betriebsart "Handbetrieb" auf dem KONTROLL EINST.-Bildschirm des
Menüs "Benutzereinstellungen" einschalten. In diesem Fall muß er
folgende Parameter eingeben:
■MODUS (derzeitige Betriebsart): Handbetrieb.
■C11, C12, C21, C22, C31, C32 (Status des Verdichters von Modul 1, 2
und 3 im manuellen Modus oder Leistungswert im Fall eines
aktivierten "capacity limitation remote contact" (Leistungsbegrenzungsfernkontakts)): EIN oder AUS.
HINWEIS
Zur Aktivierung der manuellen Regelungsart wählen
Sie MANUEL als aktuelle Betriebsart aus. Zur
Deaktivierung der manuellen Regelungsart wählen Sie
EIN. WASS. als aktuelle Betriebsart aus.
Bedienungsanleitung
11
■SEQ-UMSCH. STD: Im Automatikbetrieb ist die auf dieser Anzeige
angegebene Stundenzahl die Maximaldifferenz zwischen den
Betriebsstunden der Module. Dieser Wert ist wichtig für die
Wartung. Er sollte ausreichend hoch eingestellt werden, damit
nicht alle Module zur gleichen Zeit gewartet werden müssen und
mindestens ein Modul ständig in Betrieb bleiben kann.
Die Unter- bzw. die Obergrenze beträgt 100 bzw. 1000 Stunden.
Der Standardwert beträgt 1000 Stunden.
Festlegen der Einstellungen der Pumpensteuerung
Der Bildschirm PUMPENSTEUR des Benutzereinstellungsmenüs ermöglicht dem Benutzer, die Vorlaufzeit und die Nachlaufzeit der Pumpe
einzustellen.
■PUMPENVORL: wird verwendet, um den Zeitraum zu definieren, in
dem die Pumpe arbeiten muß, bevor die Einheit anlaufen kann.
■PUMPENNACHL: wird verwendet, um den Zeitraum zu definieren,
in dem die Pumpe weiterarbeitet, nachdem die Einheit gestoppt
wurde.
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01
Loading...
+ 144 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.