Daikin ECB2MUCW, ECB3MUCW Operation manuals

OPERATION MANUAL
Packaged water-cooled water chillers
EOMHP01008-17EU_01
D-
EWWQ049KAW1M EWWQ064KAW1M
Operation manual
Packaged water-cooled water chillers
Bedienungsanleitung
Kompakte wassergekühlte Kaltwassererzeuger
Manuel d'utilisation
Gebruiksaanwijzing
Watergekoelde ijswaterkoelgroepen
Manual de funcionamiento
Enfriadores de agua empaquetados
Manuale d'uso
Refrigeratori d'acqua monoblocco con raffreddamento ad acqua
∂Б¯ВИЪ›‰ИФ ПВИЩФ˘ЪБ›·˜
™˘БОЪФЩ‹М·Щ· ˘‰Ъfi„˘ОЩˆУ „˘ОЩТУ УВЪФ‡
Manual de operação
Grupos produtores de água refrigerada arrefecidos por água
English
Deutsch
Français
Nederlands
Español
Italiano
EППЛУИО¿
Portugues
ECB2MUCW ECB3MUCW
Инструкция по эксплуатации
Моноблочные чиллеры с водяным охлаждением
русский
EWWQ049KAW1M ECB2MUCW EWWQ064KAW1M ECB3MUCW
Packaged water-cooled water chillers

Operation manual

CONTENTS Page
Introduction ....................................................................................... 1
Technical specifications............................................................................. 2
Electrical specifications ............................................................................. 2
Description........................................................................................ 3
Function of the main components.............................................................. 4
Safety devices............................................................................................5
Internal wiring - Parts table........................................................................5
Before operation................................................................................ 6
Checks before initial start-up..................................................................... 6
Water supply.............................................................................................. 6
General recommendations ........................................................................ 6
Operation 98~192 ............................................................................. 6
Digital controller.........................................................................................6
Working with the 98~192 units .................................................................. 6
Advanced features of the digital controller................................................. 9
Troubleshooting............................................................................... 14
Maintenance.................................................................................... 15
Important information regarding the refrigerant used .............................. 15
Maintenance activities ............................................................................. 15
Disposal requirements.............................................................................15
READ THIS MANU AL ATTENTIVELY BEFORE ST ARTING UP THE UNIT. DO NOT THROW THIS MANUAL AWAY. KEEP IT IN YOUR FILES FOR FUTURE REFERENCE. Read the chapter "User settings menu" on page 9 before changing the parameters.

INTRODUCTION

This operation manual concerns packaged water-cooled water chillers of the Daikin EWWQ-KA series. These units are provided for indoor installation and used for cooling and/or heating applications. The units can be combined with Daikin fan coil units or air handling units for air conditioning purposes. They can also be used for supplying water for process cooling.
This manual has been prepared to ensure adequate operation and maintenance of the unit. It will tell you how to use the unit properly and will provide help if problems occur. The unit is equipped with safety devices, but they will not necessarily prevent all problems caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local dealer.
Before starting up the unit for the first time, make sure that it has been properly installed. It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in "Checks before initial
start-up" on page 6.
The English text is the original instruction. Other languages are translations of the original instructions.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Operation manual
1
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
(mm)
(kg)
(1)
1200x600x1200 1800x600x1200
620 650 680 930 960 990 1020
Technical specifications
General EWWQ 98 113 128 147 162 177 192
Dimensions HxWxD Machine weight
Connections
•water inlet
•water outlet
Compressor 98 113 128 147 162 177 192
Model 4x JT236DJ-Y1
2x 2x G1-1/2 3x 3x G1-1/2 2x 2x G1-1/2 3x 3x G1-1/2
2x JT236DJ-Y1 +
2x JT315DJ-Y1
4x JT315DJ-Y1 6x JT236DJ-Y1
4x JT236DJ-Y1 +
2x JT315DJ-Y1
2x JT236DJ-Y1 +
4x JT315DJ-Y1
6x JT236DJ-Y1
Speed 2900 2900 Oil type FVC68D FVC68D Oil charge volume
(l)
4x 3.0 6x 3.0 Refrigerant type R410A R410A Refrigerant charge
Evaporator 049 064 079 094 109 124 139
(kg)
2x4.6 4.6+5.6 2x5.6 3x4.6 2x4.6+5.6 4.6+2x5.6 3x5.6
Type Brazed plate heat exchanger Nom Water volume Water flow range
Condenser 049 064 079 094 109 124 139
(l/min) (l/min)
205 311 417 523 629 735 841
202 - 493 262 - 642 304 - 745 333 - 814 393 - 963 435 - 1066 456 - 1118
Type Brazed plate heat exchanger Water flow range
(l/min)
157 - 629 205 - 819 237 - 948 260 - 1038 307 - 1293 339 - 1357 355 - 1422
Electrical specifications
General EWWQ 98 113 128 147 162 177 192
(1)
Power Supply
• Phase
•Frequency (Hz)
•Voltage (V)
•Voltage tolerance (%)
3N~ 3N~
50 50 400 400 ±10 ±10
Unit
• Nominal running current
• Maximum running current
• Recommended fuses (A)
(A)
(A)
43 52 61 64 73 82 91 65 73 81 97 105 113 121
3x80 3x80 3x100 3x100 3x125 3x125 3x125
Compressors
• Phase
•Frequency (Hz)
•Voltage (V)
• Nominal running current
(A)
10.5 10.5/15 15 10.5 10.5/15 10.5/15 15
3N~ 3N~
50 50
400 400
(1) Refer to the engineering data book for the complete list of specifications.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
2

DESCRIPTION

98~128 Hp
147~192 Hp
17 26 11
14
23
20
27
18
12 15
24
21
27
19
13
25 16
22
27
10
5
2 3
8 6
1
1
9 7
4
500 500
500
Figure - Main components
1 Compressor 15 2 Evaporator 16 3 Condenser 17 4 Switchbox 18 5 Chilled water in 1 19 6 Chilled water in 2 20 7 Chilled water in 3 21 8 Chilled water out 1 22
9 Chilled water out 2 23 10 Chilled water out 3 24 11 Condenser water out 1 25 12 Condenser water out 2 26 13 Condenser water out 3 27 14 Condenser water in 1
Required space around the unit for service
Condenser water in 2 Condenser water in 3 Evaporator entering water temperature sensor 1 Evaporator entering water temperature sensor 2 Evaporator entering water temperature sensor 3 Freeze up sensor 1 Freeze up sensor 2 Freeze up sensor 3 Condenser entering water temperature sensor 1 Condenser entering water temperature sensor 2 Condenser entering water temperature sensor 3 Digital display controller 98~192 Power supply intake
Operation manual
3
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01

Function of the main components

Water
inlet
Water
outlet
Condenser
S1HP
S2HP
Filter
Filter
Compressor
Q1D
Compressor
Q2D
M1C
HP
LP
M2C
HP
LP
S4LP
S5LP
Evaporator
R4TR5T
Water outlet
R3T
Water inlet
98~113
147~192
S1HP
S2HP
S1HP
S2HP
M1C
Q1D
HP
LP
M2C
Q2D
HP
LP
M1C
Q1D
HP
LP
M2C
Q2D
HP
LP
S4LP
R4TR5T
R3T
S5LP
S4LP
R4TR5T
R3T
S5LP
Figure - Functional diagram As the refrigerant circulates through the unit, changes in its state or
condition occur. These changes are caused by the following main components:
Compressor The compressor (M*C) acts as a pump and circulates the refrigerant in the refrigeration circuit. It compresses the refri­gerant vapour coming from the evaporator to a pressure at which it can easily be liquified in the condenser.
Condenser The function of the condenser is to change the state of the refrigerant from gaseous to liquid. The heat gained by the gas in the evaporator is discharged through the condenser and the vapour condenses to liquid.
Filter The filter installed behind the condenser removes small particles from the refrigerant to prevent blockage of the tubes.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve. The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator.
Evaporator The main function of the evaporator is to take heat from the water that flows through it. This is done by turning the liquid refrigerant, coming from the condenser, into gaseous refrigerant.
Water inlet/outlet connection The water inlet and outlet connections allow an easy connection of the unit to the water circuit of the air handling unit or industrial equipment.
Operation manual
4

Safety devices

Overcurrent relay The overcurrent relay (K*S) is located in the switch box of the unit and protects the compressor motor in case of overload, phase failure or too low voltage . The relay is factory-set and may not be adjusted. When activated, the overcurrent relay has to be reset in the switch box and the controller needs to be reset manually.
High-pressure switch The high-pressure switch (S*HP) is installed on the discharge pipe of the unit and measures the condenser pressure (pressure at the outlet of the compressor). When the pressure is too high, the pressure switch is activated and the circuit stops. When activated, it resets automatically, but the controller needs to be reset manually.
Low pressure switch The low-pressure switch (S*LP) is installed on the suction pipe of the unit and measures the evaporator pressure (pressure at the inlet of the compressor). When the pressure is too low, the pressure switch is activated and the circuit stops. When activated, it resets automatically, but the controller needs to be reset manually.
Reverse phase protector The reverse phase protector (R1P) is installed in the switch box of the unit. It prevents the compressor from running in the wrong direction. If the unit does not start, two phases of the power supply must be inverted.
Discharge thermal protector The discharge thermal protector (Q*D) is activated when the temperature of the refrigerant leaving the compressor becomes too high. When the temperature retur ns to normal, the protector resets automatically, but the controller needs to be reset manually.
Freeze-up protection The freeze-up protection prevents the water in the evaporator from freezing during operation. When the outlet water temperature is too low, the controller disables the circuit. When the outlet water temperature returns to normal, the circuit can start up again. When freeze-up protection occurs several times in a certain period, the freeze-up alarm will be activated and the circuit will be shut down. The cause of freezing up should be investigated and after outlet water temperature has risen enough, the alarm indicator on the controller needs to be reset manually.
Additional interlock contact To avoid that the unit could be started or run without water circulating through the water heat exchanger, an interlock contact (S11L) of e.g. a flo w switch must be installed in the start­up circuit of the unit.

Internal wiring - Parts table

Refer to the internal wiring diagram supplied with the unit. The abbreviations used are listed below:
A1P ........................PCB terminal unit
A2P ................**....PCB address card
F1,2,3U ..........#.....Main fuses for the unit
F1B, F2B, F3B #.... fuses for each unit
F5B,F6B.................Automatic fuse for the control circuit/secondary
of TR1
F8U ........................Surge-proof fuse
F9U ................##...Surge-proof fuse
H1P................*......Indication lamp alarm
H3P................*......Indication lamp operation compressor (M1C)
H4P........................Indication lamp operation compressor (M2C)
K1A ........................auxiliary contactor for high pressure
K1M........................Compressor contactor (M1C)
K1P ................*......Pumpcontactor
K2M........................Compressor contactor (M2C)
K4S.........................Overcurrent relay (M1C)
K5S.........................Overcurrent relay (M2C)
K19T.......................Timer, time delay for M2C
M1C,M2C...............Compressor motor
PE...........................Main earth terminal
Q1D........................Discharge thermal protector (M1C)
Q2D........................Discharge thermal protector (M2C)
R1P ........................Reverse phase protector
R3T.........................Evaporator inlet water temperature sensor
R4T.........................Evaporator outlet water temperature sensor
(Freeze up sensor)
R5T.........................Condenser inlet temperature sensor
S1HP,S2HP............High pressure switch
S4LP,S5LP .............Low pressure switch
S7S.........................Changeable digital input 1
S9S.................*......Changeable digital input 2
S10L...............#.....Flowswitch
S11L...............#.....Contact that closes if the pump is working
S12S...............#.....Main isolator switch
TR1.........................Transfo 230 V 24 V for power supply of
controllers
Y1R ........................Reversing valve
Y1S.........................Solenoid valve for injection line
X1
...........................Connector for digital inputs, analog inputs, analog
outputs and for power supply controller (A1P)
X2...........................Connector for digital outputs (A1P)
X3...........................Connector for (A1P)
X4,X5,X6................Interconnection connector Main Control
switchbox
Not included with standard unit
Not possible as option Possible as option
Obligatory # ##
Not obligatory * **
Terminal unit: Digital Inputs
X1 (ID1-GND).........flowswitch
X1 (ID2-GND).........remote cooling/heating selection
X1 (ID3-GND).........high pressure switch + discharge protector +
overcurrent
X1 (ID4-GND).........low pressure switch
X1 (ID5-GND).........remote On/Off
Terminal unit: Digital outputs (relays)
X2 (C1/2-NO1) .......compressor M1C on
X2 (C1/2-NO2) .......compressor M2C on
X2 (C3/4-NO3) .......voltage free contact for pump
X2 (C3/4-NO4) .......voltage free contact for reversing valve
X2 (C5-NO5) ..........alarm voltage free contact
Terminal unit: Analog inputs
X1 (B1-GND)..........evaporator inlet water temperature
X1 (B2-GND)..........evaporator outlet water temperature (Freeze up
sensor)
X1 (B3-GND)..........condenser inlet water temperature
Operation manual
5
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01

BEFORE OPERATION

Checks before initial start-up

Make sure that the circuit breaker on the power supply panel of the unit is switched off.
After the installation of the unit, check the following before switching on the circuit breaker:
1 Field wiring
Make sure that the field wiring between the local supply panel and the unit has been carried out according to the instructions described in the installation manual, according to the wiring diagrams and according to European and national regulations.
2 Additional interlock contact
An additional interlock contact S11L should be provided (e.g. flow switch, contact of pump motor contactor). Make sure that it has been installed between the appropriate terminals (refer to the wiring diagram supplied with the unit). S11L should be a normal open contact.
3 Fuses or protection devices
Check that the fuses or the locally installed protection devices are of the size and type specified in the installation manual. Make sure that neither a fuse nor a protection device has been bypassed.
4 Earth wiring
Make sure that the earth wires have been connected properly and that the earth terminals are tightened.
5 Internal wiring
Visually check the switch box on loose connections or damaged electrical components.
6 Fixation
Check that the unit is properly fixed, to avoid abnormal noises and vibrations when starting up the unit.
7 Damaged equipment
Check the inside of the unit on damaged components or squeezed pipes.
8 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak, call your local dealer.
9 Oil leak
Check the compressor on oil leakage. If there is an oil leak, call your local dealer.
10 Power supply voltage
Check the power supply voltage on the local supply panel. The voltage should correspond to the voltage on the identification label of the unit.

Water supply

Fill the water piping, taking into account the minimum water volume required by the unit. Refer to the "installation manual".
Make sure that the water is of the quality as mentioned in the installation manual.
Purge the air at the high points of the system and check the operation of the circulation pump and the flow switch.

General recommendations

Before switching on the unit, read following recommendations: 1 When the complete installation and all necessary settings have
been carried out, close all front panels of the unit.
2 The service panels of the switch boxes ma y only be opened b y a
licensed electrician for maintenance purposes.

OPERATION 98~192

The 98~192 units are equipped with a built-in digital controller offering a user-friendly way to set up, use and maintain the unit.
This part of the manual has a task-oriented, modular structure. Apart from the first section, which gives a brief description of the controller itself, each section or subsection deals with a specific task you can perform with the unit.
Depending on the model there are two or three modules in the system. The models 98~113 only have two modules, whereas the models 147~192 consist of three modules. These modules are generally named M1, M2 and M3 in the following descriptions. All information about module 3 (M3) is not applicable for 98~113 models.

Digital controller

User interface
The digital controller consists of an alphanumeric display, labelled keys which you can press and a number of LEDs.
Figure - Digital controller
f key, to enter the main menu o key, to start up or to shut down the unit. p key, to enter the safeties menu or to reset an alarm.
keys, to scroll up or down through the screens of a menu
g
(only in case W, X or C appears) or to raise, respectively
h
lower a setting.
q key, to confirm a selection or a setting.
NOTE

Working with the 98~192 units

This chapter deals with the everyday usage of the unit. Here, you will find how to perform routine tasks, such as:
"Setting the language" on page 7
"Switching the unit on" on page 7 and "Switching the unit off" on
"Consulting actual operational information" on page 7
"Selecting cooling or heating operation" on page 8
"Adjusting the temperature setpoint" on page 8
"Resetting the unit" on page 8
Temperature readout tolerance: ±1°C. Legibility of the alphanumeric display may decrease in
direct sunlight.
page 7
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
6
Setting the language
Consulting actual operational information
If desired, the operating language can be changed to any of the following languages: English, German, French, Spanish or Italian.
1 Enter the usersettings menu. Refer to chapter "Main menu" on
page 9
2 Go to the appropriate screen of the usersettings menu using the
g and h keys.
3 Select the appropriate field (LANGUAGE) using the q key. 4 Press the g and h keys to adjust the language setting. 5 Press q to confirm the adjusted language setting.
When the setting has been confirmed, the cursor switches to the next setting.
Switching the unit on
1 Press the J key on the controller.
Depending on whether or not the remote ON/OFF switch is configured (refer to the service manual), the following conditions may occur. When no remote ON/OFF switch is configured, the LED inside the J key lights up and an initialization cycle is started. Once all the timers have reached zero, the unit starts up. When a remote ON/OFF switch is configured, the following table applies:
Local key Remote switch Unit o LED
ON ON ON ON
ON OFF OFF Flashing OFF ON OFF OFF OFF OFF OFF OFF
2 When the unit is started up for the first time, or when the unit has
been out of operation for a longer period, it is recommended to check the following.
Abnormal noise and vibrations
Make sure that the unit does not produce abnormal noises or vibrations: check the fixation, stop valves and piping. If the compressor makes abnormal noises, this may also be caused by an overcharge of refrigerant.
3 If the water chiller does not start after a few minutes, refer to
"Troubleshooting" on page 14.
Switching the unit off
If the remote on/off control parameter is set to NO:
Press the o key on the controller. The LED inside the o key goes out.
If the remote on/off control parameter is set to YES:
Press the o key on the controller or switch the unit off using the remote on/off switch. The LED inside the o key goes out in the first case and star ts blinking in the second case.
1 Enter the readout menu through the main menu. (Refer to the
chapter "Main menu" on page 9.) The controller automatically shows the first screen of the
readout menu which provides the following information:
MANUAL MODE or INLSETP1/2: manual/automatic control mode operation. If the automatic control mode is selected, the controller will indicate the active temperature setpoint. Depending on the status of the remote contact, setpoint one or setpoint two is active.
INL WATER E/C: actual inlet water temperature.
THERMOSTAT STEP: actual thermostat step. The maximum number of thermostat steps are as listed:
98 4 147 6 113 4 162 6 128 4 177 6
192 6
2 Press the h key to enter the next screen of the readout menu.
This screen of the readout menu provides the following information on the evaporator:
M1: OUTLWATER: actual outlet water temperature of module 1.
M2: OUTLWATER: actual outlet water temperature of module 2.
M3: OUTLWATER: actual outlet water temperature of module 3.
3 Press the h key to enter the next screen of the readout menu.
The COMPRESSOR STATUS screen of the readout menu provides information concerning the status of the different compressors.
C11: actual status of compressor 1 of module 1.
C12: actual status of compressor 2 of module 1.
C21: actual status of compressor 1 of module 2.
C22: actual status of compressor 2 of module 2.
C31: actual status of compressor 1 of module 3.
C32: actual status of compressor 2 of module 3. When a circuit is OFF, the following status information may
appear.
SAFETY ACTIVE: one of the circuit safety devices is activated (refer to the chapter "Troubleshooting" on page 14).
(LIMIT): the circuit is limited by a remote contact.
TIMERS BUSY: the actual value of one of the software timers is not zero (refer to the "Timers menu" on page 9).
CAN STARTUP: the circuit is ready to start up when extra cooling load is needed.
The preceding OFF messages are written down in order of priority. If one of the timers is busy and one of the safeties is active, the status information says SAFETY ACTIVE.
4 Press the h key to enter the next screen of the readout menu.
To consult actual operational information about the total running hours of the compressors.
In case of emergency, switch off the unit by pushing the emergency stopbutton.
NOTE
Operation manual
Also consult "Defining the schedule timer" on page 12.
7
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Selecting cooling or heating operation
The "cooling/heating" menu allows the user to set the unit in cooling or heating operation.
The COOL/HEAT menu provides information concerning the selected operation mode.
COOLING (EVAP): cooling mode. The two setpoints for inlet water temperature control of the evaporator can be used.
HEATING (COND): heating mode. The two setpoints for inlet water temperature control of the condenser can be used.
To define cooling/heating operation, proceed as follows:
1 Enter the cooling/heating menu through the main menu. (Refer
to the chapter "Main menu" on page 9.)
2 Position the cursor behind MODE using the q key. 3 Select the appropriate setting using the g and h keys. 4 Press q to confirm.
The cursor returns to the upper left corner of the screen.
Adjusting the temperature setpoint
The unit provides definition and selection of four or two independent temperature setpoints.
In cooling operation, two setpoints are reserved for inlet control of the evaporator.
INLSETP 1 E: inlet water temperature of evaporator, setpoint 1,
INLSETP2 E: inlet water temperature of evaporator, setpoint 2.
In heating operation, two setpoints are reserved for inlet control of the condenser.
INLSETP 1 C: inlet water temperature of condenser, setpoint 1,
INLSETP 2 C: inlet water temperature of condenser, setpoint 2.
In double thermostat operation, two setpoints are reserved for inlet control of the evaporator and two others are reserved for inlet control of the condenser.
INLSETP 1 E: inlet water temperature of evaporator, setpoint 1,
INLSETP2 E: inlet water temperature of evaporator, setpoint 2.
INLSETP 1 C: inlet water temperature of condenser, setpoint 1,
INLSETP 2 C: inlet water temperature of condenser, setpoint 2.
The selection between setpoint 1 and 2 is done by a remote dual setpoint switch (to be installed by the customer). The actual active setpoint can be consulted in the readout menu.
If the manual control mode is selected (refer to "User settings menu"
on page 9), none of the above-mentioned setpoints will be active.
To adjust a setpoint, proceed as follows:
1 Enter the setpoints menu through the main menu. (Refer to the
chapter "Main menu" on page 9). If the user password is disabled for setpoint modifications (refer
to the "User settings menu" on page 9), the controller will immediately enter the setpoints menu. If the user password is enabled for setpoint modifications, enter the correct code using the g and h keys. (Refer to the "User
password menu" on page 10). Press q to confirm the password
and to enter the setpoints menu.
2 Select the setpoint to be adjusted using the q key.
A setpoint is selected when the cursor is blinking behind the setpoint's name. The ">" sign indicates the actual active temperature setpoint.
3 Press the g and h keys to adjust the temperature setting.
The default, limit and step values for the cooling (evaporator) and heating (condenser) temperature setpoints are:
EE
default value 12°C 30°C limit values
(a) For glycol units the lower limit of the cooling temperature setpoint can be
(a)
step value 0.1°C 0.1°C
adapted in the factory. The following values apply:
INLSETP IN E/C: 5°C, 3°C, –2°C, –7°C
IIIINNNNLLLLSSSSEEEETTTTPPPP IIIINNNN EE
8 --> 23°C 15--> 50°C
IIIINNNNLLLLSSSSEEEETTTTPPPP IIIINNNN CC
CC
4 Press q to save the adjusted temperature setpoint.
When the setting has been confirmed, the cursor switches to the next setpoint.
5 To adjust other setpoints, repeat from instruction 2 onwards.
NOTE
Also consult "Defining the schedule timer" on page 12.
Resetting the unit
The units are equipped with three kinds of safety devices: unit safeties, module safeties and network safeties.
When a unit safety occurs, all compressors are shut down. The safeties menu will indicate which safety is activated. The COMPRESSOR STATUS screen of the readout menu will indicate OFF - SAFETY ACTIVE for all circuits. The red LED inside the p key lights up and the buzzer inside the controller is activated.
When a module safety occurs, the compressors of the corresponding module are shut down. The COMPRESSOR STATUS screen of the readout menu will indicate OFF - SAFETY ACTIVE for the module concerned. The red LED inside the p key lights up and the buzzer inside the controller is activated.
If the unit has been shut down due to a power failure, it will carry out an autoreset and restart automatically when the electrical power is restored.
To reset the unit, proceed as follows:
1 Press the p key to acknowledge the alarm.
The buzzer is deactivated. The controller automatically switches to the corresponding screen of the safeties menu: unit safety or module safety.
2 Find the cause of shutdown and correct.
Refer to "Listing activated safeties and checking the unit status"
on page 12 and the chapter "Troubleshooting" on page 14.
When a safety can be reset, the LED under the p key starts blinking.
3 Press the p key to reset the safeties that are no longer active.
Once all safety devices are disactivated and reset, the LED under the p key goes out. If one of the safeties is still activ e, the LED under the p key goes on again. In this case, return to instruction 2.
4 If a unit safety occurred or if all modules were shut down due to
module safeties, switch on the unit using the o key.
If the user shuts down the power supply in order to repair a safety, the safety will automatically be reset after power-up.
NOTE
The history information, i.e. the number of times a unit safety or a circuit safety occurred and the unit status at the moment of shutdown, can be checked by means of the history menu.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
8

Advanced features of the digital controller

This chapter gives an overview and a brief functional description of the screens provided by the different menus. In the following chapter, you will find how you can set up and configure the unit using the various menu functions.
The down arrow X on the display indicates that y ou can go to the next screen of the current menu using the h key. The up arrow W on the display indicates that you can go to the previous screen of the current menu using the g key. If C is displayed, this indicates that you can either return to the previous screen or can go to the next screen by using the g and h keys.
Main menu
Scroll through the main menu using the g and h keys to move the > mark in front of the menu of your choice. Push the q key to enter the selected menu.
>READOUT MENU SETPOINTS MENU USERSETTINGS MENU TIMERS MENU HISTORY MENU INFO MENU I/O STATUS MENU USERPASSWORD MENU COOL/HEAT MENU
User settings menu
The "user settings" menu, protected by the user password, allows a full customization of the units.
BC CONTROL SETTINGS MODE :MANUAL CONTROL C11 : OFF 12 ; OFF C21 : OFF 22 ; OFF
BC THERMOST.SETTINGS STEPS : 6 STPL.: 1.5°C STEPDIFFERENCE: 0.5°C LOADUP: 180s-DWN: 30s
C LEAD-LAG SETTINGS LEAD-LAG MODE : AUTO LEAD-LAG HOURS: 1000h
BC CAP. LIM. SETTINGS MODE : REMOTE DIG INP. L1M1 : OFF 2: OFF 3: OFF L2M1 : OFF 2: OFF 3: OFF
BC CAP. LIM. SETTINGS L3M1 : OFF 2: OFF 3: OFF L4M1 : OFF 2: OFF 3: OFF
To define the manual settings and to select the control mode.
To define the thermostat settings.
To define the lead-lag mode of the modules.
To define capacity limitation. (first screen)
To define capacity limitation. (second screen)
Readout menu
BX MANUAL MODE INL WATER E: 12.0°C INL WATER C: 30.0 °C THERMOSTAT STEP :2/6
BC EVAPORATOR M1 : OUTLWATER: 07.0 °C M2: OUTLWATER: 07.0 °C M3: OUTLWATER:-03.0 °C
BC COMPRESSOR STATUS C11 : OFF-CAN STARTUP C12: OFF-CAN STARTUP C21: OFF-CAN STARTUP
BC COMPRESSOR STATUS C22: OFF-CAN STARTUP C31 : OFF- SAFETY ACT. C32: OFF- LIMIT
BW RUNNING HOURS C11 : 00010h 12 ; 00010h C21 : 00010h 22 ; 00010h C31 : 00010h 32 ; 00010h
To consult actual operational infor­mation about the control mode, the inlet water temperature of the evaporator/condenser and the thermostat step.
To consult information about the outlet water temperature of the modules 1, 2 and 3 (only for 147~192).
To consult information about the compressor status (first screen).
To consult information about the compressor status (second screen).
To consult actual operational information about the total running hours of the compressors.
Setpoints menu
Depending upon the settings in the user settings menu and on the selected cooling/heating operation mode, the "setpoints" menu can either be entered directly or by means of the user password.
B>INLSETP1 E : 12.0°C INLSETP2 E : 12.0°C INLSETP1 C : 30.0°C INLSETP2 C : 30.0°C
To define the temperature setpoints.
BC PUMPCONTROL PUMPLEADTIME : 020s PUMPLAGTIME : 000s DAILY ON : Y AT : 00h00
BC SCHEDULE TIMER ENABLE TIMER : N ENABLE HOLIDAY PER : N
BC HOLIDAY : 01 TO 03 1 : 00h00 ­2: 00h00 ­3: 00h00 -
BC DUAL EVAP. PUMP MODE : AUTOM. ROTATION OFFSET ON RH : 0048h
BC DISPLAY SETTINGS LANGUAGE : ENGLISH TIME : 00h00 DATE : 00/01/2001
BC SETPOINT PASSWORD PASSWORD NEEDED TO CHANGE SETPOINTS : Y
BC ENTER SERVICE
PASSWORD : 0000
Timers menu
BX GENERAL TIMERS LOADUP : 000s - DWN : 000s PUMPLEAD : 000s FLOWSTOP : 00s
To define the pump control settings.
To define the schedule timer.
To define the dual evaporator pump.
To define the display settings.
To define whether or not a password is needed to enter the setpoints menu.
To enter the service menu. (Only a qualified installer is allowed to access this menu.)
To check the actual value of the general software timers (first screen).
Operation manual
9
BC COMPRESSOR TIMERS COMPR. STARTED : 00s
BC COMPRESSOR TIMERS C11 GRD : 000s AR : 000s C12 GRD : 000s AR : 000s C21 GRD : 000s AR : 000s
To check the actual value of the general software timers (second screen).
To check the actual value of the compressor timers (first screen).
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
BW COMPRESSOR TIMERS C22 GRD : 000s AR : 000s C31 GRD : 000s AR : 000s C32 GRD : 000s AR : 000s
Safeties menu
To check the actual value of the compressor timers (second screen).
Info menu
BX TIME INFORMATION TIME : 00h00 DATE : 00/01/2001
To consult time and date information.
The "safeties" menu provides useful information for trouble shooting purposes. The following screens contain basic information.
BX UNIT SAFETY 0C9 : INL E SENSOR ERR
BX MODULE 1 SAFETY 1CA : OUT E SENSOR ERR
BX MODULE 2 SAFETY 2CA : OUT E SENSOR ERR
BX MODULE 3 SAFETY 3CA : OUT E SENSOR ERR
To consult which unit safety caused the shutdown.
To consult which module 1 safety caused the shutdown.
To consult which module 2 safety caused the shutdown.
To consult which module 3 safety caused the shutdown.
Along with the basic information, more detailed information screens can be consulted while the safety menu is active. Press the q key. Screens similar to the following will appear.
BC UNIT HISTORY : 004 0C9 : INL E SENSOR ERR 00h00 - 12/01/2001 MANUAL MODE
BC UNIT HISTORY : 004 0C9 : INL E SENSOR ERR INL.E : 12.0°C STEP: INL.C : 30.0°C 0
To check the time and control mode at the moment of the unit shutdown.
To check which were the common evaporator and condenser inlet water temperature.
BC UNIT INFORMATION UNITTYPE : WW-HP-32 MANUFACT. NR.: 0000000 REFRIGERANT : R134a
To consult additional information about the unit such as the unit type, the refrigerant used and the manu­facturing number.
BC UNIT INFORMATION SW : V1.0M6 (01/11/01) SW CODE : FLDKNMCH0A
BW PCB INFORMATION BOOT : V2.02-02/08/00 BIOS : V2.32-31/07/01
To consult information about the con­troller's software version.
To consult information about the PCB.
Input/output menu
The "input/output" menu gives the status of all the digital inputs and the relay outputs of the unit.
BX DIGITAL INPUTS M1 SAFETY OK M2 SAFETY OK M3 SAFETY NOK
BC DIGITAL INPUTS FLOWSWITCH : FLOW OK REV.PHASE PR. : OK
BC CHANG. DIG. INPUTS DI1 DUAL SETP : SETP.1 DI2 REM. ON/OFF : OFF DI3 REM. C/H : COOL
To check whether any module safeties are active.
To check the reverse phase protector and if there's any waterflow to the evaporator.
To check the status of the change­able digital inputs.
BC UNIT HISTORY : 004 0C9 : INL E SENSOR ERR OUTE1 : 07.0°C OUTE3 : OUTE2 : 07.0°C 07.0°C
BC UNIT HISTORY : 004 0C9 : INL E SENSOR ERR C11 : ON C21 : C12 : ON ON
BC UNIT HISTORY : 004 0C9 : INL E SENSOR ERR C22 : ON
BC UNIT HISTORY : 004 0C9 : INL E SENSOR ERR RH11 : 00000h RH21: RH12 : 00000h 00000h
To check which were the evaporator outlet water temperature of all modules at the moment of shutdown.
To check which was the status of the compressors at the moment of shutdown (first screen).
To check which was the status of the compressors at the moment of shutdown (second screen).
To check which were the total amount of running hours of the com­pressors at the moment of shutdown (first screen).
BC UNIT HISTORY : 004 0C9 : INL E SENSOR ERR RH22 : 00000h
To check which were the total amount of running hours of the com­pressors at the moment of shutdown (second screen).
History menu
The "history" menu contains all the information concerning the latest shutdowns. The structure of those menus is identical to the structure of the safeties menu. Whenever a failure is solved and the operator performs a reset, the concerning data from the safeties menu is copied into the history menu. Warnings are also recorded.
Additionally the number of safeties that already occurred, can be consulted on the first line of the history screens.
BC RELAY OUTPUTS C11 : ON C12 : ON C21 : ON C22 : ON C31 : ON C32 : OFF
BC RELAY OUTPUTS LPBYPASS1 : CLOSED LPBYPASS2 : CLOSED LPBYPASS3 : OPEN
BC RELAY OUTPUTS GEN. ALARM : CLOSED PUMP/GEN OPER : CLOSED
BW CHANG. REL OUTPUTS DO1 REV.VALVE(C/H) : O
User password menu
B CHANGE PASSWORD
NEW PASSWORD : 0000 CONFIRM : 0000
Cooling/heating menu
B COOLING/HEATING MODE : COOLING (EVAP)
To check the status of the compres­sor relay outputs.
To check the status of the modules low pressure bypass.
To check the status of the alarm voltage free contact and the pump/ general operation contact.
To check the status of the change­able relay output.
To change the user password.
To select cooling or heating mode.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
10
Tasks of the user settings menu
Entering the user settings menu
The user settings menu is protected by the user password, a 4-digit number between 0000 and 9999.
1 Enter the USERSETTINGS MENU through the main menu. (Refer to
the chapter "Main menu" on page 9). The controller will request the password.
2 Enter the correct password using the g and h keys. 3 Press q to confir m the password and to enter the user settings
menu. The controller automatically enters the first screen of the user
settings menu.
To define settings of a certain function:
1 Go to the appropriate screen of the usersettings menu using the
g and h keys.
2 Position the cursor behind the parameter to be modified using
the q key.
3 Select the appropriate setting using the g and h keys. 4 Press q to confirm the selection.
When the selection has been confirmed, the cursor switches to the next parameter which can now be modified.
5 Repeat from instruction 2 onwards to modify the other
parameters.
Defining and activating the control mode
The unit is equipped with a thermostat which controls the cooling capacity of the unit. Two different control modes exist:
manual control mode: the operator controls the capacity himself
- MANUAL CONTROL
inlet control mode: uses the evaporator and/or condenser entering water temperature to control the capacity of the unit -
INLET WATER
When the operator wants to control the capacity himself, he can activate manual control mode using the CONTROL SETTINGS screen of the user settings menu. In this case, he has to define the following parameters:
MODE (present mode): manual control.
C11, C12, C21, C22, C31, C32 (compressor status of module 1, 2
and 3 in manual mode or capacity limitation value in case the "capacity limitation remote contact" is enabled): ON or OFF.
NOTE
To activate manual control mode, select MANUAL as present mode. To deactivate the manual control mode, select INLET WATER as present mode.
Defining the thermostat settings
When automatic control mode is selected, the unit uses a thermostat to control the cooling or heating capacity. The maximum number of thermostat steps are as listed:
98 4 147 6 113 4 162 6 128 4 177 6
192 6
However, the thermostat parameters are not fixed and can be modified via the THERMOST. SETTINGS screen of the user settings menu.
The default, limit and step values for the thermostat parameters are:
STPL (°C) 0.4 2.0 0.1 1.5 STEPDIFFERENCE (°C) 0.2 0.8 0.1 0.5 LOADUP (sec) 15 300 1 180 LOADDOWN (sec) 15 300 1 20
NOTE
A functional diagram showing the thermostat parame-
Lower limit Upper limit Step Default
ters can be found in "Annex I" on page 16.
Defining the lead-lag mode
The lead/lag mode determines which module starts up first in case of a capacity demand.
The lead-lag parameters are:
LEAD-LAG MODE
Automatic: the controller decides whether module 1, module 2, or module 3 starts up first. The modules follow the entered order of starting up (see table below).
3 modules 2 modules
first > next > last first > last
123 12 231 21 312
NOTE
LEAD-LAG HOURS: In the automatic mode, the number of hours
If a module is de-activated due to a failure, the next module will start up instead.
indicated on the display is the maximum difference between the running hours of the modules. This value is impor tant for main­tenance purposes. It should be set high enough so that the modules do not require maintenance at the same time and that at least one module can remain constantly active. The lower and upper limits are 100 and 1000 hours respectively. The default value is 1000 hours.
Operation manual
11
Defining the pump control settings
The PUMPCONTROL screen of the user settings menu allows the user to define the pump-leadtime and pump-lagtime.
PUMPLEADTIME: used to define the time that the pump must run before the unit can start up.
PUMPLAGTIME: used to define the time that the pump keeps running after the unit has been stopped.
Defining the display settings
The DISPLAY SETTINGS screen of the user settings menu allows the user to define the choice of language, time and date.
LANGUAGE: used to define the language of the displayed information of the controller.
TIME: used to define the present time.
DATE: used to define the present date.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Defining dual evaporator pump control
The DUAL EVAP. PUMP screen of the user settings menu allows the user to define the steering of two evaporator pumps (for this to be possible a changeable digital output has to be configured for a second evaporator pump in the service menu).
MODE: used to define which kind of control will be used for the two evaporator pumps. When automatic rotation is chosen the offset on running hours also has to be entered.
OFFSET ON RH: used to define the offset in running hours between the two pumps. Used to switch over between pumps when they work in automatic rotation mode.
Defining the schedule timer
The SCHEDULE TIMER screen of the user settings menu allows the user to define the schedule timer settings.
MON, TUE, WED, THU, FRI, SAT and SUN: used to define to which group each day of the week belongs (-/G1/G2/G3/G4).
For each of the four groups up to nine actions can be set, each with their respective timing. Actions include: putting the unit on/ off, setting a setpoint, setting cooling/heating and setting capacity limitation.
Beside these four groups there is also a holiday period group which is set the same way as the other groups. Up to 12 holiday periods can be entered in the HD PERIOD screen. During these periods the schedule timer will follow the settings of the holiday period group.
NOTE
A functional diagram showing the schedule timer working can be found in "Annex II" on page 17.
NOTE
The unit always works with "last command". This means that the last command given, whether manually by the user or by the schedule timer, is always executed.
Examples of command that can be given are switching the unit on/off or changing a setpoint.
Activating or deactivating the setpoints password
The SETPOINT PASSWORD screen of the user settings menu allows the user to activate or deactivate the user password needed to change the temperature setpoint. When deactivated, the user does not have to enter the password each time he wants to change the setpoint.
Tasks of the timers menu
Checking the actual value of the software timers
To check the actual value of the software timers, proceed as follows:
1 Enter the TIMERS MENU through the main menu. (Refer to the
chapter "Main menu" on page 9.) The controller displays the actual value of the GENERAL TIMERS:
the loadup timer, the loaddown timer, the flowstart timer, the flowstop timer (when the unit is on and the flowstart timer has reached zero), the pumplead timer and the pumplag timer.
2 Press the h key to check the compressor timers (first screen).
The controller shows the actual value of the COMPRESSOR TIMERS: the guard timers (one per compressor) and the antirecycling timers (one per compressor).
3 Press the h key to check the compressor timers (second
screen). The controller shows the actual value of the COMPRESSOR TIMERS:
the guard timers (one per compressor) and the antirecycling timers (one per compressor).
Tasks of the safeties menu
Listing activated safeties and checking the unit status
If the alarm buzzer is activated and the user presses the p key, the controller automatically enters the safeties menu.
The controller will enter the UNIT SAFETY screen of the safeties menu when a unit safety was the cause of shutdown. This screen provides the following information:
•the activated safety: emergency stop, flow switch, sensor
error or reverse phase
•the unit status at the moment of shutdown
inlet water temperature setpoint of the evaporator, inlet water temperature setpoint of the condenser, time and date at the moment of shutdown.
The controller will enter the MODULE 1, MODULE 2 or MODULE 3 SAFETY screen of the safeties menu when a safety of module 1,
respectively module 2 or module 3 was activated. These screens provide information about the module status at the moment of shutdown.
•the activated safety: freeze-up, general safety or sensor error
•the unit status at the moment of shutdown
inlet water temperature setpoint of the evaporator, inlet water temperature setpoint of the condenser, time and date at the moment of shutdown.
1 Press the p key when the alarm buzzer is activated.
The appropriate safety screen with the basic information appears. Press the q key to see the detailed information.
2 If more than one kind of safety is active (indicated by means of
W, X or C), use the g and h keys to consult them.
As a protective measure and to ensure correct operation, the controller's software features several countdown timers:
LOADUP (LOADUP – refer to the thermostat parameters): star ts counting when a thermostat step change has occurred. During the countdown, the unit is not able to enter a higher thermostat step.
LOADDOWN (DWN – refer to the thermostat parameters): starts counting when a thermostat step change has occurred. During the countdown, the unit will not be able to enter a lower thermo­stat step.
FLOWSTOP (FLOWSTOP – 5 sec): starts counting when the water flow through the evaporator stops after the flowstart timer has reached zero. If the water flow has not restarted during the countdown, the unit will shut down.
PUMPLEAD (PUMPLEAD – refer to the pump control settings): starts counting whenever the unit is switched on. During the countdown, the unit cannot start up.
PUMPLAG (PUMPLAG – refer to the pump control settings): starts counting whenever the unit is switched off. During the count­down, the pump keeps running.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
12
Tasks of the history menu
Checking the safety info and the unit status after a reset
The information available in the safeties menu is also stored in the history menu, where it is stored after resetting the unit or the module. In this way, the history menu provides a means of checking the unit status at the moment of the latest 10 shutdowns.
To check the safety info and the unit status, proceed as follows:
1 Enter the HISTORY MENU through the main menu. (Refer to the
chapter "Main menu" on page 9.) The controller enters the UNIT HISTORY screen which contains the
following information: the number of shutdowns, the unit safety which caused the most recent shutdown and the basic information at the moment of this shutdown.
2 Press the g and h keys to consult the M1, M2 or M3 HISTORY
screens.
3 Press the q key to see the detailed information.
Tasks of the info menu
Consulting additional unit information
1 Enter the INFO MENU through the main menu. (Refer to the
chapter "Main menu" on page 9). The controller enters the UNIT INFORMATION screen which contains
the following information: the unit name, the refrigerant used and the manufacturing (serial) number.
2 Press h to consult the next UNIT INFORMATION screen.
This screen contains information about the controller's software version.
Tasks of the input/output menu
Checking the status of the inputs and outputs
The input/output menu provides a means of checking the status of the digital inputs and the status of the relay outputs.
The locked digital inputs are:
M1, M2 or M3 SAFETY: indicates the status of the general module safeties.
FLOWSWITCH: indicates the status of the flowswitch, activated or deactivated.
REVERSE PHASE PROTECTOR: indicates the status of this safety.
The changeable digital inputs are:
REM. C/H: indicates the status of the remote cooling/heating switch.
DUAL SETPOINT: indicates the status of the remote dual setpoint switch, setpoint 1 or setpoint 2.
REM. ON/OFF: indicates the status of the remote on/off switch.
CAP LIM1/2/3: indicates the status of the enable/disable capacity
limitation switch(es).
The locked relay outputs are:
LPBYPASS 1/2/3: indicates whether the low pressure of the module is in bypass mode or not.
C11, C12, C21, C22, C31, C32: indicates whether the compressor is running or not.
PUMP/GEN OPER: indicates the status of this voltage free contact. It is activated if the pump should be ON, which also indicates general operation.
The changeable relay outputs are:
REV. VALVE (C/H): indicates whether the unit is running in cooling or in heating.
2ND EVAP PUMP: indicates the status of the second evaporator pump.
CONDENSER PUMP: indicates the status of the condenser pump.
100% CAPACITY: indicates when the unit is working at 100%.
To check the inputs and outputs, proceed as follows:
1 Enter the I/O STATUS MENU through the main menu. (Refer to the
chapter "Main menu" on page 9.) The controller enters the first DIGITAL INPUTS screen.
2 Consult the other screens of the input/ouput menu using the g
and h keys.
Tasks of the user password menu
Changing the user password
Access to the user settings menu and the setpoints menu is protected by the user password (a 4-digit number between 0000 and
9999).
To change the user password, proceed as follows:
1 Enter the USERPASSWORD MENU through the main menu. (Refer to
the chapter "Main menu" on page 9). The controller will request the password.
2 Enter the correct password using the g and h keys. 3 Press q to confirm the password and to enter the password
menu. The controller requests the new password.
4 Press q to start the modification.
The cursor is positioned behind NEW PASSWORD.
5 Enter the new password using the g and h keys. 6 Press q to confirm the new password.
When the new password has been confirmed, the controller will ask to enter the new password a second time (for safety reasons). The cursor is positioned behind CONFIRM.
7 Enter the new password again using the g and h keys. 8 Press q to confirm the new password.
NOTE
The actual password will only be changed when the new password and the confirmed password have the same value.
Operation manual
13
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01

TROUBLESHOOTING

This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.
Before starting the trouble shooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will save you time and money.
When carrying out an inspection on the supply panel or on the switch box of the unit, always make sure that the circuit breaker of the unit is switched off.
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no circum­stances safety devices may be bridged or changed to a value other than the factory setting. If the cause of the problem cannot be found, call your local dealer.
Symptom 1: The unit does not start, but the ON LED lights up
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not correct.
The flowstart timer is still running. The unit will start after approx. 15
Neither one of the circuits can start up.
Unit is in manual mode (all compressors at 0%).
Power supply failure. Check the voltage on the supply
Blown fuse or interrupted protection device.
Loose connections. Inspect connections of the field
Shorted or broken wires. T est circuits using a tester and repair
Symptom 2: The unit does not start, but the ON LED is flashing
POSSIBLE CAUSES CORRECTIVE ACTION
The remote ON/OFF input is enabled and the remote switch is off.
Symptom 3: The unit does not start and the ON LED does not light up
POSSIBLE CAUSES CORRECTIVE ACTION
All circuits are in failure mode. Refer to Symptom 5: One of the
One of the following safety de vices is activated:
•Flow switch (S8L,S9L)
• Emergency stop
The ON LED is broken. Contact your local dealer. The unit is in bypass mode. Check the bypass remote contact.
Check the controller setpoint.
seconds. Make sure that water is flowing through the evaporator.
Refer to Symptom 4: One of the
circuits does not start up.
Check on the controller.
panel. Inspect fuses and protection
devices. Replace by fuses of the same size and type (refer to
"Electrical specifications" on page 2).
wiring and the internal wiring of the unit. Tighten all loose connections.
if necessary.
Put the remote switch on or disable the remote ON/OFF input.
following safety devices is activated.
Refer to Symptom 5: One of the
following safety devices is activated.
Symptom 4: One of the circuits does not start up
POSSIBLE CAUSES CORRECTIVE ACTION
One of the following safety de vices is activated:
• Compressor thermal protector (Q*M)
•Overcurrent relay (K*S)
•Discharge thermal protector (S*T)
•Low pressure switch
•High pressure switch (S*HP)
•Reverse phase protector (R*P)
•Freeze-up
The anti-recycling timer is still active. The circuit can only start up after
The guard timer is still active. The circuit can only start up after
The circuit is limited to 0%. Check the "enable/disable capacity
Symptom 5: One of the following safety devices is activated
Symptom 5.1: Overcurrent relay of compressor
POSSIBLE CAUSES CORRECTIVE ACTION
Failure of one of the phases. Check fuses on the supply panel or
Voltage too low. Measure the supply voltage. Overload of motor. Reset. If the f ailure persists, call y our
Symptom 5.2: Low pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to water heat exchanger too low.
Shortage of refrigerant. Check for leaks and refill refrigerant,
Unit is working out of its operation range.
Inlet temperature to the water heat exchanger is too low.
Flow switch is not working or no water flow.
Symptom 5.3: High-pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to condenser is too low. Increase the water flow and/or check
Symptom 5.4: Reverse phase protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Two phases of the power supply are connected in the wrong phase position.
One phase is not connected properly.
Symptom 5.5: Discharge thermal protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Unit is working outside the operation range.
Check on the controller and refer to
Symptom 5: One of the following safety devices is activated.
approximately 10 minutes.
approximately 1 minute.
limitation" remote contact.
measure the supply voltage.
local dealer.
RESET
Push the blue button on the over­current relay inside the switch box and reset the controller.
Increase the water flow.
if necessary. Check the operation conditions of
the unit. Increase the inlet water temperature.
Check the flow switch and the water pump.
RESET
After pressure rise, this safety resets automatically, but the controller still needs to be reset.
the strainer for clogging.
RESET
After finding the cause, push the button on the high-pressure switch housing and reset the controller.
Invert two phases of the power supply (by licensed electrician).
Check the connection of all phases.
RESET
After inverting two phases or fixing the power supply cables properly, the protector is reset automatically, but the controller still needs to be reset.
Check the operation condition of the unit.
RESET
After temperature decrease, the thermal protector resets automatically but the controller still needs to be reset.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
14
Symptom 5.6: Flow switch is activated
POSSIBLE CAUSES CORRECTIVE ACTION
No water flow. Check the water pump.
RESET
After finding the cause, the flow switch is reset automatically, but the controller still needs to be reset.
Symptom 5.7: Freeze-up protection is activated
POSSIBLE CAUSES CORRECTIVE ACTION Water flow too low. Increase the water flow. Inlet temperature to the evaporator is
too low. Flow switch is not working or no
water flow.
Symptom 5.8: Compressor thermal protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION Compressor motor coil temperature
too high.
Symptom 6: Unit stops soon after operation
POSSIBLE CAUSES CORRECTIVE ACTION The schedule timer is activated and
is in off mode.
One of the safety devices is activated.
Voltage is too low. Test the voltage in the supply panel
Symptom 7: Unit runs continuously and the water temperature remains higher than the temperature set on the controller
POSSIBLE CAUSES CORRECTIVE ACTION The temperature setting on the
controller is too low. The heat production in the water
circuit is too high. Water flow is too high. Recalculate the water flow. The circuit is limited. Check the "enable/disable capacity
Symptom 8: Excessive noises and vibrations of the unit
POSSIBLE CAUSES CORRECTIVE ACTION Unit has not been fixed properly. Fix the unit as described in the
Increase the inlet water temperature.
Check the flow switch and the water pump.
RESET
After temperature increase the freeze-up is reset automatically, but the circuit controller needs to be reset.
Compressor is not cooled sufficiently by the refrigerant medium.
RESET
After temperature decrease the thermal protector is reset automatically, but the circuit controller needs to be reset.
If the protector is activated frequently, call your local dealer.
Work according to the settings in the schedule timer or disable the schedule timer.
Check safety devices (refer to
Symptom 5: One of the following safety devices is activated).
and, if necessary, in the electrical compartment of the unit (voltage drop due to supply cables is too high).
Check and adjust the temperature setting.
The cooling capacity of the unit is too low. Call your local dealer.
limitation" remote contact.
installation manual.
Before carrying out any maintenance or repair activity, always switch off the circuit breaker on the supply panel, remove the fuses or open the protection devices of the unit.
Do never clean the unit with water under pressure.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Refrigerant type: R410A
(1)
GWP
value: 2090
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.

Maintenance activities

The wiring and power supply must be checked by a licensed electrician.
Field wiring and power supply
• Check the power supply voltage on the local supply panel. The voltage should correspond to the voltage marked on the identification label of the unit.
• Check the connections and make sure they are properly fixed.
• Check the proper operation of the circuit breaker and the earth leak detector provided on the local supply panel.
Internal wiring of the unit Visually check the switch boxes on loose connections (terminals and components). Make sure that the electrical components are not damaged or loose.
Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened.
Refrigerant circuit
• Check for leaks inside the unit. In case a leak is detected, call
your local dealer.
• Check the working pressure of the unit. Refer to paragraph
"Switching the unit on" on page 7.
Compressor
• Check on oil leaks. If there is an oil leak, call your local
dealer.
• Check for abnormal noises and vibrations. If the compressor
is damaged, call your local dealer.
Water supply
• Check if the water connection is still well fixed.
• Check the water quality (refer to the installation manual of the
unit for specifications of the water quality).
Water filters
• Check if the mesh width is 1 mm maximum.

MAINTENANCE

In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals.
If the unit is used for air conditioning application, the described checks should be executed at least once a year. In case the unit is used for other applications, the checks should be executed every 4 months.
Operation manual
15

Disposal requirements

Dismantling of the unit, treatment of the refrigerant, oil and any other parts, should be done in accordance with the relevant local and national regulations.
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01

ANNEX I

0 1
6
5
4
3
2
ab
Stepnumber
Setpoint
Temperature

Thermostat parameters

Cooling: Inlet water temperature control of evaporator Heating: Inlet water temperature control of condenser
The figures below show the thermostat diagram in case of inlet water temperature control.
2 step thermostat control
Stepnumber
2 step thermostat control
Stepnumber
147~192
0 1 2
Setpoint
ab
Temperature
0 1 2
ab
Setpoint
Temperature
4 step thermostat control (default 98~128) 4 step thermostat control (default 98~128)
98~128
Stepnumber
0 1 2 3 4
Setpoint
ab
147~192
Temperature
98~128
Stepnumber
0 1 2 3 4
ab
Setpoint
Temperature
6 step thermostat control (default 147~192) 6 step thermostat control (default 147~192)
Stepnumber
ab
0 1 2 3 4 5 6
Setpoint
Temperature
The default value and the upper and lower limits of the thermostat parameters are listed in the table below.
INLET CONTROL Default value Lower limit Upper limit
Steplength - a Step difference - b Load-up time Load-down time Setpoint Cooling Setpoint Heating
NOTE
The thermostat parameters mentioned above only apply to standard units.
(sec) (sec)
(°C) (°C)
(K) (K)
1.5 0.4 2.0
0.5 0.2 0.8
180 15 300
20 15 300
12.0 8.0 23.0
30.0 15.0 50.0
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
16

ANNEX II

14.0

Schedule timer example

MARCH
MON TUE WED THU FRI SAT SUN
1 G1 2 G1 3 G2 4 G1 5 G1 6 G3 7 G3
8 G1 9 G1 10 G2 11 G1 12 G1 13 G3 14 G3 15 G1 16 G1 17 G2 18 G1 19 G1 20 G3 21 G3 22 G1 29 H 30 G1 31 G2
To come to the schedule above following settings have to be made:
All days assigned to the same group will work according to the settings of this group.
In this example setting:
all Mondays, Tuesdays, Thursdays and Fridays will work accord-
all Wednesdays will work according to the settings in group 2
all Saturdays and Sundays will work according to the group 3
all holiday days will work according to the settings in the holiday
All group settings of groups G1, G2, G3, G4 and H work similar as following example (settings for group 1):
23 H 24 H 25 H 26 H 27 H 28 H
BX SCHEDULE TIMER MON : G1 THU : G1 SAT : G3 TUE : G1 FRI : G1 SUN : G3 WED : G2
BX HD PERIOD : 01 TO 03 01 : 23/03 TO 29/03 02 : 00/00 TO 00/00 03 : 00/00 TO 00/00
ing to the settings in group 1 (G1),
(G2),
(G3),
group (H).
Cooling inlet setpoint 1
Heating inlet setpoint 1
Cooling Heating
14.0°C
12.0°C
On Off
68 1213 15 18 20
14.0
35.0°C
°C30.0°C
time (h)
BX GROUP1 : 01 TO 03 1 : 06h00 ISP1 E : 12.0 2 : 06h00 ON COOL 3 : 08h00 ISP1 E : 14.0
BX GROUP1 : 04 TO 06 4 : 12h00 OFF 5 : 13h00 ISP1 C : 30.0 6 : 13h00 ON HEAT
BX GROUP1 : 07 TO 09 7 : 15h00 ISP1 C : 35.0 8 : 20h00 OFF 9 : 00h00 - -
Operation manual
17
Screen 1
Screen 2
Screen 3
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01

ANNEX III - SOFTWARE STRUCTURE

Actual screens can be different than the shown example (147~192).
f
>READOUT MENU SETPOINTS MENU USERSETTINGS MENU TIMERS MENU HISTORY MENU INFO MENU I/O STATUS MENU USERPASSWORD MENU COOL/HEAT MENU
q
BX MANUAL MODE
INL WATER E: 12.0°C INL WATER C: 30.0 °C THERMOSTAT STEP :2/6
ENTER PASSWORD
PASSWORD : 0000
ENTER PASSWORD
PASSWORD : 0000
g
$e SCHEDULE TIMER ENABLE TIMER : N ENABLE HOLIDAY PER : N
g
$e HOLIDAY : 01 TO 03 1 : 00h00 ­2: 00h00 ­3: 00h00 -
BX GENERAL TIMERS LOADUP:000s-DWN:000s PUMPLEAD : 000s FLOWSTOP : 00s
p
BX UNIT SAFETY
0C9 : INL E SENSOR ERR
q
$z UNIT HISTORY : 004 0C9 : INL E SENSOR ERR 00h00 - 12/01/2001 MANUAL MODE
h
$e EVAPORATOR M1 : OUTLWATER: 07.0 °C M2: OUTLWATER: 07.0 °C
h
M3: OUTLWATER:-03.0 °C
$>INLSETP1 E : 12.0°C INLSETP2 E : 12.0°C INLSETP1 C : 30.0°C
q
INLSETP2 C : 30.0°C
$e CONTROL SETTINGS MODE :MANUAL CONTROL C11 : OFF 12 ; OFF 31 ; OFF
q
C21 : OFF 22; OFF 32 ; OFF
$e SCHEDULE TIMER
g
MON : G1 THU : G2 SAT : ­TUE : G1 FRI : G2 SUN : -
h
WED : -
$e DUAL EVAP. PUMP
h
MODE : AUTOM. ROTATION OFFSET ON RH : 0048h
g
$e COMPRESSOR TIMERS COMPR. STARTED : 00s
h
$e UNIT HISTORY : 004 0C9 : INL E SENSOR ERR INL.E : 12.0°C STEP :
qqqqqq
INL.C : 30.0°C 0
$e COMPRESSOR STATUS
g
C11 : OFF-CAN STARTUP C12: OFF-CAN STARTUP
h
C21: OFF-CAN STARTUP
$e THERMOST.SETTINGS STEPS : 6 STPL.: 1.5°C STEPDIFFERENCE: 0.5°C
h
LOADUP: 180s-DWN: 30s
$e GROUP1 : 01 TO 03
g
1 : 00h00 - - ­2 : 00h00 - - -
h
3 : 00h00 - - -
$e DISPLAY SETTINGS
g
LANGUAGE : ENGLISH TIME : 00h00
h
DATE : 00/01/2001
$e COMPRESSOR TIMERS
g
C11 GRD : 000s AR : 000s C12 GRD : 000s AR : 000s
h
C21 GRD : 000s AR : 000s
$e UNIT HISTORY : 004 0C9 : INL E SENSOR ERR OUTE1 : 07.0°C OUTE3 : OUTE2: 07.0°C 07.0°C
$e COMPRESSOR STATUS
g
C22: OFF- CAN STARTUP C31 : OFF- SAFETY ACT.
h
C32: OFF- LIMIT
$e LEAD-LAG SETTINGS
g
LEAD-LAG MODE : AUTO LEAD-LAG HOURS: 1000h
h
$e GROUP2 : 01 TO 03
g
1 : 00h00 - - ­2 : 00h00 - - -
h
3 : 00h00 - - -
$e SETPOINT PASSWORD
g
PASSWORD NEEDED TO CHANGE SETPOINTS : Y
h
$a COMPRESSOR TIMERS
g
C22 GRD : 000s AR : 000s C31 GRD : 000s AR : 000s
h
C32 GRD : 000s AR : 000s
$e UNIT HISTORY : 004 0C9 : INL E SENSOR ERR C11 : ON C21: C12: ON ON
$a RUNNING HOURS
g
C11 : 00010h 12 ; 00010h C21 : 00010h 22 ; 00010h
h
C31 : 00010h 32 ; 00010h
$e CAP. LIM. SETTINGS
g
MODE : REMOTE DIG INP. L1M1 : OFF 2: OFF 3: OFF
h
L2M1 : OFF 2: OFF 3: OFF
$e GROUP3 : 01 TO 03
g
1 : 00h00 - - ­2 : 00h00 - - -
h
3 : 00h00 - - -
$e ENTER SERVICE
g
PASSWORD : 0000
h
g
$e UNIT HISTORY : 004 0C9 : INL E SENSOR ERR C22 : ON C32 : C31 : OFF OFF
g
$e CAP. LIM. SETTINGS
g
L3M1 : OFF 2: OFF 3: OFF L4M1 : OFF 2: OFF 3: OFF
h
$e GROUP4 : 01 TO 03
g
1 : 00h00 - - ­2 : 00h00 - - ­3 : 00h00 - - -
h
g
$e UNIT HISTORY : 004 0C9 : INL E SENSOR ERR RH11 : 00000h RH21: RH12 : 00000h 00000h
$e PUMPCONTROL
g
PUMPLEADTIME : 020s PUMPLAGTIME : 000s
h
DAILY ON : Y AT : 00h00
$e HD PERIOD: 01 TO 03
g
01 : 01/09 TO 04/09 02 : 00/00 TO 00/00
h
03 : 00/00 TO 00/00
$a UNIT HISTORY : 004 0C9 : INL E SENSOR ERR RH22: 00000h RH32: RH31: 00000h 00000h
h
h
q
$z UNIT HISTORY : 003 0AE : FLOW HAS STOPPED 00h00 - 01/01/2001 INLSETP2 E : 30.0°C
gh
$z MOD 1 HISTORY : 002 1EO : GENERAL SAFETY 00h00 - 01/01/2001 INLSETP1 E : 30.0°C
gh
$z MOD 3 HISTORY : 001 3EO : GENERAL SAFETY 00h00 - 12/01/2001 INLSETP1 C : 07.0°C
g
$z TIME INFORMATION TIME : 00h00 DATE : 00/01/2001
$z DIGITAL INPUTS M1 SAFETY OK M2 SAFETY OK M3 SAFETY NOK
ENTER PASSWORD
PASSWORD : 0000
$ COOLING/HEATING MODE : COOLING (EVAP)
$e UNIT HISTORY : 003 0AE : FLOW HAS STOPPED INL.E : 12.0°C STEP : INL.C : 30.0°C 2
$e MOD 1 HISTORY : 002 1EO : GENERAL SAFETY INL.E : 12.0°C STEP :
qqqqqq
INL.C : 30.0°C 2
$e MOD 3 HISTORY : 001 3EO : GENERAL SAFETY INL.E : 12.0°C STEP : INL.C : 30.0°C 2
$e UNIT INFORMATION UNITTYPE : WW-HP-32 MANUFACT. NR.: 0000000
h
REFRIGERANT : R134a
$e DIGITAL INPUTS FLOWSWITCH : FLOW OK REV.PHASE PR. : OK
h
$ CHANGE PASSWORD
NEW PASSWORD : 0000
q
CONFIRM : 0000
$e UNIT HISTORY : 003 0AE : FLOW HAS STOPPED OUTE1 : 07.0°C OUTE3: OUTE2: 07.0°C 07.0°C
$e MOD 1 HISTORY : 002 1EO : GENERAL SAFETY OUTE1 : 07.0°C OUTE3: OUTE2: 07.0°C 07.0°C
$e MOD 3 HISTORY : 001 3EO : GENERAL SAFETY OUTE1 : 07.0°C OUTE3: OUTE2: 07.0°C 07.0°C
$e UNIT INFORMATION
g
SW : V1.0M6 (01/11/01) SW CODE : FLDKNMCH0A
h
$e CHANG. DIG. INPUTS
g
DI1 DUAL SETP : SETP.1 DI2 REM. ON/OFF : OFF
h
DI3 REM. C/H : COOL
$e UNIT HISTORY : 003 0AE : FLOW HAS STOPPED C11 : OFF - SAF C21: C12: OFF - SAF OFF - SAF
$e MOD 1 HISTORY : 002 1EO : GENERAL SAFETY C11 : OFF C21: C12: OFF OFF
$e MOD 3 HISTORY : 001 3EO : GENERAL SAFETY C11 : OFF - F D C21: C12: OFF - F D OFF - F D
$a PCB INFORMATION
g
BOOT : V2.02-02/08/00 BIOS : V2.32-31/07/01
h
$e RELAY OUTPUTS
g
C11 : ON C12 : ON C21 : ON C22 : ON
h
C31 : OFF C32 : OFF
$e UNIT HISTORY : 003 0AE : FLOW HAS STOPPED C22: OFF - SAF C32: C31 : OFF OFF
$e MOD 1 HISTORY : 002 1EO : GENERAL SAFETY C22: OFF C32: C31 : ON ON
$e MOD 3 HISTORY : 001 3EO : GENERAL SAFETY C22: OFF - F D C32: C31 : OFF - SAF OFF - SAF
g
$e RELAY OUTPUTS
g
LPBYPASS1 : CLOSED LPBYPASS2 : CLOSED
h
LPBYPASS3 : OPEN
$e UNIT HISTORY : 003 0AE : FLOW HAS STOPPED RH11 : 00000h RH21: RH12 : 00000h 00000h
$e MOD 1 HISTORY : 002 1EO : GENERAL SAFETY RH11 : 00000h RH21: RH12 : 00000h 00000h
$e MOD 3 HISTORY : 001 3EO : GENERAL SAFETY RH11 : 00000h RH21: RH12 : 00000h 00000h
$e RELAY OUTPUTS
g
GEN. ALARM: CLOSED PUMP/GEN OPER: CLOSED
h
$a UNIT HISTORY : 003 0AE : FLOW HAS STOPPED RH22: 00000h RH32: RH31 : 00000h 00000h
qqqqqq
$a MOD 1 HISTORY : 002 1EO : GENERAL SAFETY RH22: 00000h RH32: RH31 : 00000h 0000h
$a MOD 3 HISTORY : 001 3EO : GENERAL SAFETY RH22: 00000h RH32:
qqqqqq
RH31 : 00000h 00000h
$a CHANG. REL OUTPUTS
g
DO1 REV.VALVE(C/H) : O
h
q
q
q
only for
147~192
g
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01
Operation manual
18
EWWQ049KAW1M ECB2MUCW EWWQ064KAW1M ECB3MUCW
Kompakte wassergekühlte Kaltwassererzeuger

Bedienungsanleitung

INHALTSVERZEICHNIS Seite
Einleitung .......................................................................................... 1
Elektrische Daten ...................................................................................... 2
Elektrische Daten ...................................................................................... 2
Beschreibung.................................................................................... 3
Funktion der Hauptbauteile........................................................................ 4
Schutzvorrichtungen..................................................................................5
Innenverdrahtung - Teileübersicht.............................................................. 5
Vor der Inbetriebnahme..................................................................... 6
Kontrollen vor der Erstinbetriebnahme...................................................... 6
Wasserzufuhr............................................................................................. 6
Allgemeine Empfehlungen......................................................................... 6
Betrieb 98~192.................................................................................. 6
Digitalregler................................................................................................ 6
Arbeiten mit dem 98~192 Gerät ................................................................ 6
Fortschrittliche Funktionen des Digitalreglers............................................ 9
Fehlersuche .................................................................................... 14
Wartung........................................................................................... 16
Wichtige Informationen hinsichtlich des verwendeten Kältemittels ......... 16
Wartungsarbeiten .................................................................................... 16
Vorschriften zur Entsorgung.................................................................... 16
LESEN SIE SICH DIESE ANLEITUNG SORGFÄLTIG DURCH, BEVOR SIE DIE EINHEIT IN BETRIEB NEHMEN. WERFEN SIE DIESE ANLEITUNG NICHT WEG, SONDERN BEWAHREN SIE SIE AUF, DAMIT SIE AUCH SPÄTER NOCH DARIN NACHSCHLAGEN KÖNNEN. Lesen sie sich das kapitel "Menü Benutzereinstellungen" auf Seite 9 durch, bevor sie die parameter ändern.
Bei der englischen Fassung der Anleitung handelt es sich um das Original. Bei den Anleitungen in anderen Sprachen handelt es sich um Übersetzungen des Originals.
Das Gerät ist nicht konzipiert, um von folgenden Personengruppen einschließlich Kindern benutzt zu werden: Personen mit ein­geschränkten körperlichen, sensorischen oder geistigen Fähigkeiten oder Personen mit mangelhafter Erfahrung oder Wissen, es sei denn, sie sind von einer Person, die für ihre Sicherheit verantwor tlich ist, darin unterwiesen worden, wie das Gerät ordnungsgemäß zu verwenden und zu bedienen ist. Kinder sollten beaufsichtigt werden, um sicher zu sein, dass sie nicht mit dem Gerät spielen.

EINLEITUNG

Diese Bedienungsanleitung bezieht sich auf die kompakten wassergekühlten Kaltwassererzeuger der Reihe Daikin EWWQ-KA. Diese Einheiten sind für Innenanwendungen im Bereich Kühlung und/oder Heizung vorgesehen und sind mit Daikin Fan-Coil-Einheiten oder mit Lüftungseinheiten zu Klimatisierungszwecken kombinierbar. Sie können zudem zur Versorgung mit Kühlwasser zur Verfahrenskühlung eingesetzt werden.
Diese Anleitung wurde erarbeitet, um eine ordnungsgemäße Funktion und Wartung des Geräts zu gewährleisten. Sie beschreibt die sachgemäße Bedienung des Geräts und gibt bei etwaigen Problemen Hilfestellung. Das Gerät ist zwar mit Schutzvorrichtungen ausgestattet, diese verhindern jedoch nicht automatisch alle Probleme, die auf unsachgemäße Bedienung oder Wartung zurückzuführen sind.
Wenden Sie sich bei länger anhaltenden Störungen an Ihren nächsten Händler.
Vergewissern Sie sich vor der Erstinbetriebnahme des Geräts, ob es ordnungsgemäß installiert wurde. Lesen Sie sich hierzu die mit dem Gerät gelieferte Installations­anleitung und die Empfehlungen unter "Kontrollen vor der
Erstinbetriebnahme" auf Seite 6 sorgfältig durch.
Bedienungsanleitung
1
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01

Technische Daten

EWWQ Allgemein 98 113 128 147 162 177 192
Abmessungen HxBxT Maschinengewicht
(1)
(mm)
(kg)
1200x600x1200 1800x600x1200
620 650 680 930 960 990 1020
Anschlüsse
•Wassereinlaß
•Wasserauslaß
Verdichter 98 113 128 147 162 177 192
Modell 4x JT236DJ-Y1 Drehzahl
(rpm)
2x 2x G1-1/2 3x 3x G1-1/2 2x 2x G1-1/2 3x 3x G1-1/2
2x JT236DJ-Y1 +
2x JT315DJ-Y1
4x JT315DJ-Y1 6x JT236DJ-Y1
4x JT236DJ-Y1 +
2x JT315DJ-Y1
2900 2900
2x JT236DJ-Y1 +
4x JT315DJ-Y1
6x JT236DJ-Y1
Ölfüllmenge FVC68D FVC68D Ölfüllmenge
(l)
4x 3,0 6x 3,0 Kältemitteltyp R410A R410A Kältemittelfüllung 2x4,6 4,6+5,6 2x5,6 3x4,6 2x4,6+5,6 4,6+2x5,6 3x5,6
Verdampfer 049 064 079 094 109 124 139
Ausführung Plattenwärmetauscher Nennwassermenge (l/min) 205 311 417 523 629 735 841 Wasserdurchfluß-
bereich
Verflüssiger 049 064 079 094 109 124 139
(l/min)
202 - 493 262 - 642 304 - 745 333 - 814 393 - 963 435 - 1066 456 - 1118
Ausführung Plattenwärmetauscher Wasserdurchfluß-
bereich
(l/min)
157 - 629 205 - 819 237 - 948 260 - 1038 307 - 1293 339 - 1357 355 - 1422

Elektrische Daten

EWWQ Allgemein 98 113 128 147 162 177 192
(1)
Netzanschluß
• Phase
•Frequenz (Hz)
• Spannung (V)
• Spannungstoleranz (%)
3N~ 3N~
50 50 400 400 ±10 ±10
Einheit
• Nennbetriebsstrom (A)
• Maximaler Betriebsstrom
• Empfohlene Sicherungen
(A)
(A)
43 52 61 64 73 82 91 65 73 81 97 105 113 121
3x80 3x80 3x100 3x100 3x125 3x125 3x125
Verdichter
• Phase
•Frequenz (Hz)
• Spannung (V)
• Nennbetriebsstrom (A)
10,5 10,5/15 15 10,5 10,5/15 10,5/15 15
3N~ 3N~
50 50
400 400
(1) Die vollständigen technischen Daten sind dem technischen Datenbuch zu entnehmen.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Bedienungsanleitung
2

BESCHREIBUNG

98~128 Hp
147~192 Hp
17 26 11 23
14 20
27
18
12
24
15 21
27
19
13
25 16
22
27
10
5
2 3
8 6
1
1
9 7
4
500 500
500
Abbildung: Hauptbauteile
1 Verdichter 15 Verflüssiger-Wasser ein 2 2 Verdampfer 16 Verflüssiger-Wasser ein 3 3 Verflüssiger 17 Wassertemperaturfühler an Verdampfereingang 1 4 Schaltkasten 18 Wassertemperaturfühler an Verdampfereingang 2 5 Kaltwasser ein 1 19 Wassertemperaturfühler an Verdampfereingang 3 6 Kaltwasser ein 2 20 Frostschutzfühler 1 7 Kaltwasser ein 3 21 Frostschutzfühler 2 8 Kaltwasser aus 1 22 Frostschutzfühler 3
9 Kaltwasser aus 2 23 Wassertemperaturfühler an Verflüssigereingang 1 10 Kaltwasser aus 3 24 Wassertemperaturfühler an Verflüssigereingang 2 11 Verflüssiger-Wasser aus 1 25 Wassertemperaturfühler an Verflüssigereingang 3 12 Verflüssiger-Wasser aus 2 26 Steuerung mit digitaler Anzeige 98~192 13 Verflüssiger-Wasser aus 3 27 Netzanschluß 14 Verflüssiger-Wasser ein 1
Für Wartung erforderlicher Abstand um die Einheit
Bedienungsanleitung
3
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01

Funktion der Hauptbauteile

Wasser-
einlaß
Wasser-
auslaß
Verflüssiger
S1HP
S2HP
Filter
Filter
Q1D
Q2D
Verdichter
M1C
HP
LP
Verdichter
M2C
HP
LP
S4LP
S5LP
Verdampfer
R4TR5T
Wasser­auslaß
R3T
Wasser­einlaß
98~113
147~192
S1HP
S2HP
S1HP
S2HP
M1C
Q1D
HP
LP
M2C
Q2D
HP
LP
M1C
Q1D
HP
LP
M2C
Q2D
HP
LP
S4LP
R4TR5T
R3T
S5LP
S4LP
R4TR5T
R3T
S5LP
Abbildung: Funktionsplan Beim Durchlauf durch das Gerät kann sich der Status oder die
Beschaffenheit des Kältemittels verändern. Diese Änderungen werden durch die folgenden Hauptbauteile verursacht:
Verdichter Der Verdichter (M*C) arbeitet wie eine Pumpe und läßt das Kältemittel im Kältemittelkreislauf zirkulieren. Er verdichtet den Kältemitteldampf aus dem Verdampfer, und zwar mit einem Druck, mit dem er am leichtesten im Verflüssiger verflüssigt werden kann.
Verflüssiger Der Verflüssiger wandelt den Zustand des Kältemittels vom gasförmigen in einen flüssigen Zustand um. Die durch das Gas im Verdampfer aufgenommene Wärme wird durch den Ver­flüssiger abgeleitet, so daß der Dampf kondensiert.
Filter Der hinter dem Verflüssiger installierte Filter filtert kleine Partikel aus dem Kältemittel heraus, so daß ein Verstopfen der Rohre verhindert wird.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Expansionsventil Das flüssige Kältemittel, das aus dem Verflüssiger kommt, gelangt über ein Expansionsventil in den Verdampfer. Das Expansionsventil bringt das flüssige Kältemittel auf einen Druck, bei dem es im Verdampfer leicht verdampft werden kann.
Verdampfer Wichtigste Funktion des Verdampfers ist es, die Wärme aus dem Wasser, das durch ihn fließt, abzuziehen. Dies geschieht durch Umwandlung des flüssigen Kältemittels aus dem Verflüssiger in gasförmiges Kältemittel.
Anschlüsse für Wassereinlaß und Wasserauslaß Die Anschlüsse für Wassereinlaß und Wasserauslaß ermög­lichen einen einfachen Anschluß des Geräts an den Wasser­kreislauf des Luftbehandlungsgeräts oder an industrielle Anlagen.
Bedienungsanleitung
4

Schutzvorrichtungen

Überstromrelais Das Überstromrelais (K*S) befindet sich im Schaltkasten des Geräts und schützt den Verdichtermotor bei Überlastung, Phasenausfall oder zu niedriger Spannung. Das Relais wurde werksseitig eingestellt und darf nicht verstellt werden. Ist es aktiviert, muß die Rücksetzung von Hand erfolgen. Danach muß der Regler zurückgesetzt werden.
Hochdruckschalter Der Hochdruckschalter (S*HP) ist an der Austrittsleitung des Geräts eingebaut. Er mißt den Verflüssigerdruck (Druck am Austritt des Verdichters). Steigt der Druck zu sehr an, wird der Druckschalter aktiviert, und der Schaltkreis wird abgeschaltet. Nach Aktivierung stellt er sich automatisch zurück, der Regler muß jedoch von Hand zurückgesetzt werden.
Niederdruckschalter Der Niederdruckschalter (S*LP) ist am Saugrohr des Geräts installiert und mißt den Verdampferdruck (Druck am Verdichter­eingang). Ist der Druck zu niedrig, löst der Druckschalter aus und schaltet den Stromkreis ab. Nach Aktivierung stellt er sich automatisch zurück, der Regler muß jedoch von Hand zurückgesetzt werden.
Phasenumkehrschutz Die Phasenumkehrschutzvorrichtung (R1P) ist im Schaltkasten des Geräts installiert. Sie verhindert, daß der Verdichter in die falsche Richtung dreht. Läßt sich das Gerät nicht einschalten, müssen zwei Phasen der Netzleitung vertauscht werden.
Austrittsthermoschutz Die Austrittsthermoschutzvorrichtung (Q*D) spricht bei einem übermäßigen Anstieg der Kältemitteltemperatur bei Austritt aus dem Verdichter an. Hat die Temperatur wieder den normalen Wert erreicht, setzt sich der Thermoschutz automatisch zurück. Der Regler muß jedoch manuell zurückgesetzt werden.
Frostschutz Der Frostschutz verhindert ein Einfrieren des Wassers im Verdampfer während des Betriebes. Ist die Wassertemperatur bei Austritt zu niedrig, schaltet der Hauptregler das Gerät ab. Wenn die Wassertemperatur beim Austritt wieder einen normalen Wert erreicht, kann die Einheit wieder anlaufen. Wenn der Frostschutz in einem bestimmten Zeitraum mehrmals anspricht, wird der Frostschutzalarm ausgelöst, und das Gerät wird abgeschaltet. Die Ursache für das Auslösen dieses Alarms muss untersucht werden. Nachdem die Temperatur des Aus­lasswassers wieder akzeptabel ist, muss die Alarmanzeige am Regler manuell zurückgesetzt werden.
Zusätzlicher Verriegelungskontakt Um zu verhindern, daß das Gerät eingeschaltet oder betrieben wird, wenn kein Wasser durch den Wasserwärmetauscher zirkuliert, muß in den Anlaufkreis des Geräts ein Verriegelungs­kontakt (S11L), z.B. ein Strömungsschalter, eingebaut werden.

Innenverdrahtung - Teileübersicht

Siehe den dem Gerät beiliegenden Innenverdrahtungsplan. Die ver­wendeten Abkürzungen sind im folgenden aufgeführt:
A1P ........................Leiterplatte Anschlußeinheit
A2P ................**....Leiterplatte Adreßkarte
F1,2,3U ..........#.....Geräte-Hauptsicherungen
F1B, F2B, F3B.#.... Sicherungen für jede E
F5B,F6B.................Automatik-Sicherung für Steuerschaltkreis/
Sekundärschaltkreis von TR1
F8U ........................Träge Sicherung
F9U ................##...Träge Sicherung
H1P................*......Anzeigelampe - Alarm
H3P................*......Betriebs-Anzeigelampe V erdichter (M1C)
H4P........................Betriebs-Anzeigelampe V erdichter (M2C)
K1A ........................Hochdruck-Hilfsschütz
K1M........................Verdichterschalter (M1C)
K1P ................*......Pumpenstecker
inheit
K2M........................Verdichterschütz (M2C)
K4S.........................Überstromrelais (M1C)
K5S.........................Überstromrelais (M2C)
K19T.......................Uhr, Zeitverzögerung für M2C
M1C,M2C...............Verdichtermotor
PE...........................Haupterdungsklemme
Q1D........................Austrittsthermoschutz (M1C)
Q2D........................Austrittsthermoschutz (M2C)
R1P ........................Phasenumkehrschutz
R3T.........................Wassertemperaturfühler Verdampf ereingang
R4T.........................Wassertemperaturfühler Verdampf erausgang
(Frostschutzfühler)
R5T.........................T emperaturfühler Verflüssigereingang
S1HP,S2HP............Hochdruckschalter
S4LP,S5LP .............Niederdruckschalter
S7S.........................Veränderbarer digitaler Eingang 1
S9S.........................Veränderbarer digitaler Eingang 2
S10L...............#.....Strömungsschalter
S11L...............#.....Kontakt, der sich bei Pumpenbetrieb schließt
S12S...............#.....Haupttrennschalter
TR1.........................Trafo 230 V 24 V für Netzanschluß der Regler
Y1R ........................Umkehrventil
Y1S.........................Magnetventil der Einspritzleitung
X1...........................Stecker für Digitaleingänge, Analogeingänge,
Analogausgänge und für
Stromversorgungsregler (A1P)
X2...........................Stecker für Digitalausgänge (A1P)
X3...........................Stecker für (A1P)
X4,X5,X6................Zusamenschalt-Konnektor Haupt Steuer-
schaltkasten
Nicht in der Standardausführung
Nicht als Option lieferbar Als Option lieferbar
Verbindlich # ##
Nicht verbindlich * **
Anschlußeinheit: Digitaleingänge
X1 (ID1-GND).........Strömungsschalter
X1 (ID2-GND).........Fernauswahl Kühlung/Heizung
X1 (ID3-GND).........Niederdruckschalter
X1 (ID4-GND).........Fernschaltung Ein/Aus
Anschlußeinheit: Digitalausgänge (Relais)
X2 (C1/2-NO1) .......Verdichter M1C ein
X2 (C1/2-NO2) .......Verdichter M2C ein
X2 (C3/4-NO3) .......Spannungsfreier Pumpenkontakt
X2 (C3/4-NO4) .......Spannungsfreier Kontakt für Umkehrventil
X2 (C5-NO5) ..........Spannungsfreier Kontakt für Alarm
Anschlußeinheit: Analogeingänge (Relais)
X1 (B1-GND)..........Wassertemperatur Verdampfereingang
X1 (B2-GND)..........Wassertemperatur Verdampferausgang
(Frostschutzfühler)
X1 (B3-GND)..........Wassertemperatur Verdichtereingang
Bedienungsanleitung
5
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01

VOR DER INBETRIEBNAHME

Kontrollen vor der Erstinbetriebnahme

Überprüfen Sie, ob der Hauptschalter des Geräts auf der Verteilertafel ausgeschaltet ist.
Überprüfen Sie nach der Installation des Geräts vor dem Einschalten des Hauptschalters folgende Punkte:
1 Bauseitige Verdr ahtung
Überprüfen Sie, ob die bauseitige Verdrahtung gemäß den in der Installationsanleitung enthaltenen Anweisungen, den Elektroschaltplänen und den europäischen und nationalen Vorschriften durchgeführt wurde.
2 Zusätzlicher Verriegelungsk ontakt
Es sollte ein zusätzlicher Verriegelungskontakt S11L eingebaut werden (z.B. Strömungsschalter, Kontakt von Pumpenmotor­stecker). Achten Sie darauf, daß er zwischen den entsprechen­den Klemmen eingebaut wird (siehe den dem Gerät beiliegenden Elektroschaltplan). S11L muß ein Arbeitskontakt sein.
3 Sicherungen oder Schutzvorrichtungen
Überprüfen Sie, ob Größe und Ausführung der Sicherungen oder der bauseitig installierten Schutzvorrichtungen der Installationsanleitung entsprechen. Achten Sie außerdem darauf, daß keine Sicherung und keine Schutzvorrichtung überbrückt werden.
4 Erdung
Achten Sie darauf, daß die Erdleitungen ordnungsgemäß angeschlossen und die Erdungsklemmen angezogen sind.
5 Innenverdrahtung
Überprüfen Sie den Schaltkasten auf lose Verbindungen oder beschädigte elektrische Bauteile.
6 Verankerung
Überprüfen Sie, ob das Gerät ordnungsgemäß verankert wurde, um bei Inbetriebnahme ungewöhnliche Betriebsgeräusche und Vibrationen zu vermeiden.
7 Beschädigte Ausrüstung
Überprüfen Sie das Gerät innen auf beschädigte Teile oder zusammengedrückte Rohrleitungen.
8 Austreten von Kältemittel
Überprüfen Sie das Gerät innen auf austretendes Kältemittel. Ist dies der Fall, verständigen Sie bitte Ihren Händler.
9 Austreten von Öl
Überprüfen Sie den Verdichter auf austretendes Öl. Ist dies der Fall, verständigen Sie bitte Ihren Händler.
10 Anschlußspannung
Überprüfen Sie die Anschlußspannung auf der bauseitigen Verteilertafel. Die Spannung muß mit der auf dem Typenschild des Geräts angegebenen Spannung übereinstimmen.

Allgemeine Empfehlungen

Lesen Sie sich vor Einschalten des Geräts die folgenden Empfehlungen durch:
1 Wenn sämtliche Installationsarbeiten und Einstellungen
fertiggestellt sind, schließen Sie alle Vorderblenden des Geräts.
2 Die Bedienungstafel des Schaltkastens darf nur von einem
zugelassenen Elektriker zu Wartungszwecken geöffnet werden.

BETRIEB 98~192

Die Geräte der Baureihe 98~192 sind mit einem integrierten Digitalregler ausgestattet, der die Inbetriebnahme, die Anwendung und die Wartung des Geräts besonders bedienerfreundlich macht.
Dieser Teil der Anleitung ist funktionsorientiert und modular aufgebaut. Mit Ausnahme des ersten Abschnitts, der einen kurzen Überblick über den Regler selbst vermittelt, behandelt jeder Abschnitt oder Unterabschnitt eine bestimmte Funktion, die mit dem Gerät möglich ist.
Je nach Modell gibt es zwei oder drei Module im System. Die Modelle 98~113 verfügen über nur zwei Module, die Modelle 147~192 hingegen über drei. Diese Module sind im Folgenden durchgehend mit M1, M2 und M3 bezeichnet. Alle Informationen über Modul 3 (M3) gelten nicht für die Modelle 98~113.

Digitalregler

Benutzerschnittstelle
Der Digitalregler besteht aus einem alphanumerischen Display, beschrifteten Tasten und einer Reihe von LEDs.
Abbildung: Digitalregler
f Taste, um das Hauptmenü aufzurufen. o Taste zum Ein- oder Ausschalten des Geräts.
Taste um das Menü Schutzvorrichtungen aufzurufen oder
p
um einen Alarm zurückzusetzen. Taste zum Vor- oder Zurückblättern durch die Bildschirme
g
eines Menüs (nur wenn W, X oder C erscheint) oder zum
h
Erhöhen bzw. Senken einer Einstellung.
q Taste zur Bestätigung einer Auswahl oder Einstellung.
HINWEIS

Arbeiten mit dem 98~192 Gerät

Temperaturausgabetoleranz: ±1°C. Bei direkter Einstrahlung von Sonnenlicht kann die
Sichtbarkeit des alphanumerischen Displays beein­trächtigt werden.

Wasserzufuhr

Füllen Sie die Wasserleitungen, und halten Sie sich dabei an die für das Gerät erforderliche Mindestwassermenge. Siehe die Installationsanleitung.
Achten Sie darauf, daß das Wasser der in der Installationsanleitung aufgeführten Qualität entspricht.
Evakuieren Sie die hohen Stellen im System, und überprüfen Sie den Betrieb der Umwälzpumpe und des Strömungsschalters.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Dieses Kapitel behandelt den alltäglichen Betrieb des Geräts. Er erläutert Ihnen Routinefunktionen wie z.B.:
"Festlegen der Sprache" auf Seite 7
"Einschalten des Geräts" auf Seite 7 und "Ausschalten des
Geräts" auf Seite 7
"Abrufen der aktuellen Betriebsinformationen" auf Seite 7
"Auswahl von Kühl- oder Heizbetrieb" auf Seite 8
"Ändern der Temperatureinstellung" auf Seite 8
"Zurücksetzen des Geräts" auf Seite 8
Bedienungsanleitung
6
Festlegen der Sprache
Ausschalten des Geräts
Die folgenden Sprachen können als Dialogsprache ausgewählt werden: Deutsch, Englisch, Französisch, Italienisch oder Spanisch.
1 Gehen Sie in das Menü Benutzereinstellungen. Siehe auch
Kapitel "Hauptmenü" auf Seite 9
2 Öffnen Sie über die Tasten g und h den entsprechenden
Bildschirm des Menüs Benutzereinstellungen.
3 Gehen Sie mit Hilfe der Taste q in das entsprechende Feld
(SPRACHE).
4 Drücken Sie die Tasten g und h, um die Spracheinstellung zu
ändern.
5 Drücken Sie die Taste q, um die neu ausgewählte Sprache zu
bestätigen.
Nachdem die Einstellung bestätigt wurde, rückt der Cursor zur nächsten Einstellung weiter.
Einschalten des Geräts
1 Drücken Sie die Taste o auf dem Regler. Abhängig davon, ob der Fernbedienungsschalter EIN/AUS konfigu-
riert wurde (siehe Installationsanleitung), können die folgenden Bedingungen auftreten.
Wenn der Fernbedienungsschalter EIN/AUS konfiguriert wurde, leuchtet die LED in der Taste J auf, und ein Inbetriebnahme-Zyklus startet. Stehen alle Uhren auf Null, nimmt das Gerät seinen Betrieb auf.
Wenn ein Fernbedienungsschalter EIN/AUS konfiguriert wurde, gilt die folgende Tabelle:
Lokale Taste Fernschalter Gerät o LED
EIN EIN EIN EIN
EIN AUS AUS Blinkt AUS EIN AUS AUS AUS AUS AUS AUS
Wenn die Fernbedienungseinstellung Ein/Aus auf NEIN steht:
Drücken Sie die Taste o auf dem Regler. Die LED in der Taste o erlischt.
Wenn die Fernbedienungseinstellung Ein/Aus auf JA steht:
Drücken Sie die Taste o auf dem Regler, oder schalten Sie das Gerät mit dem Fernbedienungsschalter Ein/Aus aus. Im ersten Fall erlischt die LED in der Taste o, im zweiten Fall beginnt sie zu blinken.
In einem Notfall muß das Gerät durch Drücken des Notabschalters ausgeschaltet werden.
HINWEIS
Lesen Sie auch die Kapitel "Festlegen der Programm-
Uhr" auf Seite 12.
Abrufen der aktuellen Betriebsinformationen
1 Gehen Sie über das Hauptmenü in das Ausgabe-Menü. (Siehe
Kapitel "Hauptmenü" auf Seite 9.) Der Regler zeigt automatisch den ersten Bildschirm des
Anzeigemenüs an, der die folgenden Informationen liefert:
MANUELLER MODUS oder EIN. SOLL1/2: Hand-oder Automatikbetrieb. Wenn Automatikbetrieb gewählt wurde, zeigt das Regelgerät den aktiven Temperatureinstellpunkt an. Je nach dem Status des Fernbedienungskontaktes ist Einstellung 1 oder Einstellung 2 aktiv.
EIN. WASS. E/C: Aktuelle Wassertemperatur bei Eintritt.
TEMPERATURSTUFE: die tatsächliche Schritteinstellung des Thermostats. Die maximale Anzahl der Schritte des Thermostats entspricht den Angaben:
98 4 147 6 113 4 162 6 128 4 177 6
192 6
2 Wenn die Einheit zum ersten Mal in Betrieb genommen wird,
oder wenn sie über einen längeren Zeitraum nicht in Betrieb war, sollten unbedingt die folgenden Punkte überprüft werden.
Ungewöhnliche Geräusche und Vibrationen
Achten Sie darauf, daß das Gerät keine ungewöhnlichen Geräusche oder Vibrationen verursacht: Überprüfen Sie Verankerung, Absperrventile und Leitungen. Erzeugt der Verdichter ungewöhnliche Geräusche, kann dies auch daran liegen, daß zuviel Kältemittel eingefüllt wurde.
3 Nimmt der Kaltwassererzeuger nach einigen Minuten den
Betrieb nicht auf, siehe "Fehlersuche" auf Seite 14.
2 Mit der Taste h gelangen Sie zum nächsten Bildschirm des
Anzeigemenüs. Dieser Bildschirm des Anzeigemenüs bietet folgende
Informationen über den Verdampfer:
M1 AUSL. WASS: die tatsächliche Temperatur des Auslass­wassers aus Modul 1.
M2 AUSL. WASS: die tatsächliche Temperatur des Auslass­wassers aus Modul 2.
M3 AUSL. WASS: die tatsächliche Temperatur des Auslass­wassers aus Modul 3.
3 Mit der Taste h gelangen Sie zum nächsten Bildschirm des
Anzeigemenüs. Der Bildschirm VERDICHTER STATUS des Ausgabe-Menüs bietet
Informationen zum Status der unterschiedlichen Schaltkreise.
C11: Aktueller Status des Verdichters 1 von Modul 1.
C12: Aktueller Status des Verdichters 2 von Modul 1.
C21: Aktueller Status des Verdichters 1 von Modul 2.
C22: Aktueller Status des Verdichters 2 von Modul 2.
C31: Aktueller Status des Verdichters 1 von Modul 3.
C32: Aktueller Status des Verdichters 2 von Modul 3.
Wenn ein Schaltkreis auf AUS steht, können die folgenden Statusinformationen erscheinen:
ALARM AKTIV: eine der Schutzvorrichtungen des Kreislaufs wurde ausgelöst (s. Kapitel "Fehlersuche" auf Seite 14).
(LIMIT): der Kreislauf wird durch einen Fernkontakt beschränkt.
TIMER AKTIV: der aktuelle Wert einer der Software-Uhren ist nicht gleich Null (siehe "Menü Zeitschaltuhren" auf Seite 10).
BETRIEBSBER.: der Schaltkreis ist betriebsbereit, wenn eine zusätzliche Kühllast benötigt wird.
Bedienungsanleitung
7
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01
Die vorhergehenden AUS-Anzeigen sind gemäß ihrer Rangfolge wiedergegeben. Ist eine der Zeitschaltuhren in Betrieb und eine Schutzvorrichtung aktiv, so lautet die Statusinformation ALARM AKTIV.
4 Mit der Taste h gelangen Sie zum nächsten Bildschirm des
Anzeigemenüs. Zum Einsehen tatsächlicher Betriebsinformationen über die
Gesamtbetriebsstunden der Verflüssiger.
Auswahl von Kühl- oder Heizbetrieb
Das Menü Kühlen/Heizen ermöglicht es dem Benutzer, die Einheit in den Kühlungs- oder Heizbetrieb zu versetzen.
Das KUEHLEN/HEIZEN MENU bietet Informationen über den aus­gewählten Betriebsmodus.
KUEHL. (VERDA.): Kühlungsmodus. Die beiden Sollwerte können zum Regeln der Temperatur des Einlasswassers des Verdampfers verwendet werden.
HEIZ. (VERFL.): Heizmodus. Die beiden Sollwerte können zum Regeln der Temperatur des Einlaßwassers des Verflüssigers verwendet werden.
So legen Sie den Kühl-/Heizbetrieb fest:
1 Wechseln Sie vom Hauptmenü zum Menü Kühlen/Heizen.
(Siehe Kapitel "Hauptmenü" auf Seite 9.)
2 Setzen Sie den Cursor mit der Taste q hinter MODUS. 3 Wählen Sie mit den Tasten g und h die geeignete Einstellung aus. 4 Bestätigen Sie Ihre Auswahl mit q.
Der Cursor wird wieder in der linken oberen Ecke des Bildschirms angezeigt.
Ändern der Temperatureinstellung
Die Einheit ermöglicht es, zwei oder vier unabhängige Temperatur­Sollwerte festzulegen und auszuwählen.
Im Kühlbetrieb sind zwei Sollwerte zur Einlassregelung des Verdampfers reserviert.
EIN. SOLL 1E: Temperatur des Einlaßwassers des Verdampfers, Sollwert 1,
EIN. SOLL 2E: Temperatur des Einlaßwassers des Verdampfers, Sollwert 2.
Im Heizbetrieb sind zwei Sollwerte für die Einlaßregelung reserviert.
EIN. SOLL 1C: Temperatur des Einlaßwassers des Verflüssigers, Sollwert 1,
EIN. SOLL 2C: Temperatur des Einlaßwassers des Verflüssigers, Sollwert 2.
Im Doppelthermostatbetrieb sind zwei Sollwerte für die Einlaß­regelung des Verdampfers und zwei andere für die Einlaßregelung des Verflüssigers reserviert.
EIN. SOLL 1E: Temperatur des Einlaßwassers des Verdampfers, Sollwert 1,
EIN. SOLL 2E: Temperatur des Einlaßwassers des Verdampfers, Sollwert 2.
EIN. SOLL 1C: Temperatur des Einlaßwassers des Verflüssigers, Sollwert 1,
EIN. SOLL 2C: Temperatur des Einlaßwassers des Verflüssigers, Sollwert 2.
Die Auswahl zwischen Einstellung 1 und 2 erfolgt über einen Fern­bedienungsschalter für duale Einstellung (der vom Kunden installiert werden muß). Die aktuelle gewählte Einstellung kann im Ausgabe­Menü abgelesen werden.
Wenn die manuelle Regelungsart ausgewählt wurde (siehe "Menü
Benutzereinstellungen" auf Seite 9), wird keine der oben genannten
Einstellungen aktiviert.
Ändern der Einstellung:
1 Gehen Sie vom Hauptmenü ins Menü Einstellungen (siehe
Kapitel "Hauptmenü" auf Seite 9). Wenn das Benutzer-Password deaktiviert wurde, um Ein-
stellungen zu verändern (siehe "Menü Benutzereinstellungen"
auf Seite 9), zeigt der Regler sofort das Menü Einstellungen an.
Wenn das Benutzer-Password aktiviert wurde, um Einstellungen zu verändern, geben Sie den korrekten Code mit den Tasten g und h ein (siehe "Menü Benutzer-Password" auf Seite 11). Drücken Sie die Taste q, um das Password zu bestätigen und um ins Menü Einstellungen zu gelangen.
2 Wählen Sie die Einstellung, die geändert werden soll, mit der
Taste q aus. Eine Einstellung wurde ausgewählt, wenn der Cursor hinter der
Bezeichnung der Einstellung blinkt. Das Zeichen ">" zeigt die aktuelle ausgewählte Einstellung an.
3 Drücken Sie die Tasten g und h, um die Temperatureinstellung
zu verändern. Die Standard-, Grenz- und Schrittwerte für die
Temperatursollwerte beim Kühlen (Verdampfer) und Heizen (Verflüssiger) sind:
EE
Standardwert 12°C 30°C
Grenzwerte
Stufenwert 0.1°C 0.1°C
(a) Bei Glykol-Geräten kann der untere Grenzwert für die Einstellung der
(a)
Kühltemperatur werksseitig eingestellt werden:
EIN. SOLL E/C: 5°C, 3°C, –2°C, –7°C
EEEEIIIINNNN.... SSSSOOOOLLLLLLLL EE
8 --> 23°C 15--> 50°C
EEEEIIIINNNN.... SSSSOOOOLLLLLLLL CC
CC
4 Drücken Sie die Taste q, um die geänderte Temperatur-
einstellung zu speichern. Wenn die Einstellung bestätigt wurde, rückt der Cursor zur
nächsten Einstellung weiter.
5 Befolgen Sie zur Änderung der anderen Einstellungen die
Anweisungen ab Punkt 2.
HINWEIS
Lesen Sie auch die Kapitel "Festlegen der Programm-
Uhr" auf Seite 12.
Zurücksetzen des Geräts
Die Einheiten sind mit drei Arten von Schutzvorrichtungen aus­gestattet: Schutzvorrichtungen für die Einheiten, die Module und das Netzwerk.
Wenn eine Geräte-Schutzvorrichtung anspricht, werden alle Verdichter abgeschaltet. Das Schutzvorrichtungsmenü zeigt an, welche Schutzvorrichtung eingeschaltet ist. Der VERDICHTER STATUS­Bildschirm des Ausgabemenüs zeigt dann AUS-ALARM AKTIV für alle Kreisläufe an. Die rote LED in der Taste p leuchtet, und der Summer im Regler wird aktiviert.
Wenn eine Modul-Schutzvorrichtung anspricht, werden die Verdichter des betreffenden Moduls abgeschaltet. Der VERDICHTER STATUS- Bildschirm des Ausgabe-Menüs zeigt dann AUS-ALARM AKTIV für das entsprechende Modul an. Die rote LED in der Taste p leuchtet, und der Summer im Regler wird aktiviert.
Wenn das Gerät aufgrund eines Stromausfalls abgeschaltet wurde, setzt es sich automatisch zurück und nimmt seinen Betrieb automatisch wieder auf, wenn wieder Strom vorhanden ist.
Zurücksetzen des Geräts:
1 Drücken Sie die Taste p, um den Alarm zu bestätigen.
Der Summer wird abgeschaltet. Der Regler schaltet automatisch auf den entsprechenden Bildschirm des Menüs Schutzvorrichtungen um: Geräte­Schutzvorrichtung oder Schaltkreis-Schutzvorrichtung.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Bedienungsanleitung
8
2 Stellen Sie fest, weshalb das Gerät abgeschaltet wurde, und
beheben Sie die Ursache. Siehe "Aufstellung der aktivierten Schutzvorrichtungen und
Überprüfung des Gerätestatus" auf Seite 13 sowie Kapitel "Fehlersuche" auf Seite 14.
Wenn eine Schutzvorrichtung zurückgesetzt werden kann, beginnt die LED unter der Taste p zu blinken.
3 Drücken Sie die Taste p, um die nicht mehr aktivierten
Schutzvorrichtungen zurückzusetzen. Wenn alle Schutzvorrichtungen deaktiviert und zurückgesetzt
sind, verlischt die LED unter der Taste p. Wenn eine der Schutzvorrichtungen noch aktiviert ist, leuchtet die LED unter der Taste p erneut auf. Führen Sie in diesem Fall erneut Anweisung 2 durch.
4 Wenn eine Geräte-Schutzvorrichtung aktiviert wurde, oder wenn
alle Module durch Schutzvorrichtungen abgeschaltet wurden, schalten Sie das Gerät mit der Taste o wieder ein.
BC VERDICHTER STATUS C22: AUS-BETRIEBSBER. C31: AUS-ALARM AKTIV C32: AUS-LIMIT
BW BETRIEBSSTD. C11: 00010h 12: 00010h C21: 00010h 22: 00010h C31: 00010h 32: 00010h
Zum Abrufen von Informationen über den Status des Verdichters (zweiter Bildschirm).
Zum Abrufen von Betriebs­informationen über die Gesamt­betriebsstunden der Verdichter.
Menü Einstellungen
Je nach Einstellungen im Menü "user setup" (Benutzereinstellungen) und dem ausgewählten Kühl-/Heiz-Betriebsmodus kann entweder direkt oder über das Benutzerpaßwort in das Menü "setpoints" (Sollwerte) gewechselt werden.
B>EIN. SOLL 1E: 12.0°C EIN. SOLL 2E: 12.0°C EIN. SOLL 1C: 30.0°C EIN. SOLL 2C: 30.0°C
Zum Festlegen der Temperatur­einstellpunkte.
Wenn der Benutzer den Strom abschaltet, um eine Schutz­vorrichtung instandzusetzen, wird die Schutzvorrichtung nach Einschalten des Stroms automatisch zurückgesetzt.
HINWEIS
Die aufgezeichneten Informationen, d. h. wie häufig eine Geräte- oder Schaltkreis-Schutzvorrichtung ange­sprochen hat, sowie der Gerätestatus zum Zeitpunkt des Abschaltens, können im Aufzeichnungs-Menü überprüft werden.

Fortschrittliche Funktionen des Digitalreglers

Dieses Kapitel gibt Ihnen einen Überblick über den Menüaufbau sowie eine kurze Beschreibung der Funktionen aller Menüpunkte. Im folgenden Kapitel erfahren Sie, wie Sie das Gerät mit Hilfe der verschiedenen Menüfunktionen einstellen und konfigurieren können.
Der Pfeil X auf dem Display zeigt an, dass Sie im aktuellen Menü mit der Taste h zum folgenden Bildschirm weiterblättern können. Der Pfeil W zeigt an, dass Sie im aktuellen Menü mit der Taste g zum vorhergehenden Bildschirm zurückblättern können. Wenn C angezeigt wird, können Sie mit den Tasten g und h zum vorher­gehenden Bildschirm zurückkehren oder zum folgenden Bildschirm weiterblättern.
Hauptmenü
Mit den Tasten g und h durch das Hauptmenü blättern, um die Markierung > vor das Menü Ihrer Wahl zu bewegen. Drücken Sie die Taste q, um in das ausgewählte Menü zu gelangen.
>AUSLESE MENU SOLL WERT MENU BEN. EINST. MENU TIMERS MENU HISTORIE MENU INFO MENU I/O STATUS MENU BEN. PASSWORT MENU KUEHLEN/HEIZEN MENU
Ausgabe-Menü
BX BX MANUELLER MODUS EIN. WASS. E: 12.0°C EIN. WASS. C: 30.0°C TEMPERATURSTUFE: 2/6
BC VERDAMPFER M1 AUSL. WASS: 07.0°C M2 AUSL. WASS: 07.0°C M3 AUSL. WASS: -03.0°C
BC VERDICHTER STATUS C11: AUS-BETRIEBSBER. C12: AUS-BETRIEBSBER. C21: AUS-BETRIEBSBER.
Zum Abrufen aktueller Betriebs­informationen über den Regelmodus, die Temperatur des Einlasswassers des Verdampfers/Verflüssigers und der Thermostatstufe.
Zum Abrufen von Informationen über die Temperatur des Auslasswassers aus den Modulen 1, 2 und 3 (nur für 147~192).
Zum Abrufen von Informationen über den Status des Verdichters (erster Bildschirm).
Menü Benutzereinstellungen
Das Menü "Benutzereinstellungen", das mit einem Password geschützt wird, ermöglicht die vollkommene Anpassung des Geräts an die Bedürfnisse des Kunden.
BC KONTROLL EINST. MOD: MANUELLE KONTR. C11: AUS 21: AUS C12: AUS 22: AUS
BC THERMOST. EINST. STUFE: 6 ST.L: 1.5°C STUFENDIFF.: 0.5°C ANHEB: 180 ABSEN: 030s
C SEQ-UMSCH. EINST. SEQ-UMSCH. MOD: AUTO SEQ-UMSCH. STD: 1000h
BC LEIST. BEGR. EINST. MOD: FB DIG EING. L1M1: AUS 2: AUS 3: AUS L2M1: A US 2: AUS 3: AUS
BC LEIST. BEGR. EINST. L3M1: AUS 2: AUS 3: AUS L4M1: AUS 2: AUS 3: AUS
BC PUMPENSTEUR PUMPENVORL.: 020s PUMPENNACHL.: 000s TAEGL.: J UM: 12h00
BC WOCHENTIMER TIMER AKTIV: N URLAUBSFUNKTION: N
BC URLAUB: 01 ZU 03 1: 00h00 ­2: 00h00 ­3: 00h00 -
BC VERD. ZWILL. PUMPE MOD: AUTOM. DREHZAHL BETR. AUSGL.: 048h
BC DISPLAY EINST. SPRACHE: DEUTSCH ZEIT: 00h00 DAT: 01/01/2001
BC SOLLWERT PASSWORT PASSWORT BEDARF SOLLWERTE VER.: N
Definition der manuellen Einstellungen und Auswahl der Regelungsart.
Definition der Thermostat­einstellungen.
Zum Festlegen des Primär/ Sekundärmodus der Module.
Zum Festlegen der Leistungs­begrenzung (erster Bildschirm).
Zum Festlegen der Leistungs­begrenzung (zweiter Bildschirm).
Zum Festlegen der Pumpen­regelungseinstellungen.
Zum Festlegen der Programm-Uhr.
Zur Definierung der dualen Verdampferpumpe.
Zum Festlegen der Display­einstellungen.
Zur Bestimmung, ob ein Paßwort erforderlich ist, um ins Einstellpunkte-Menü zu gelangen.
Bedienungsanleitung
9
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01
BC EINGABE SERVICE
PASSWORT: 0000
Menü Zeitschaltuhren
BX ALLG. TIMER ANHEB: 000s ABSE: 000s PUMPENVOR: 000s STROEMSTP: 00s
Zum Aktivieren des Wartungsmenüs. (Auf dieses Menü darf nur ein erfahrener Installateur zugreifen.)
Überprüfung des aktuellen Werts der allgemeinen Software-Uhren (erster Bildschirm).
BC EINHEIT HIST.: 004 0C9: EIN E SENS. FEHL. RH11: 00000h RH21: RH12: 00000h 00000h
BC EINHEIT HIST.: 004 0C9: EIN E SENS. FEHL. RH22: 00000h
Zur Überprüfung der Gesamt­betriebsstunden der Verdichter zum Zeitpunkt des Abschaltens (erster Bildschirm).
Zur Überprüfung der Gesamt­betriebsstunden der Verdichter zum Zeitpunkt des Abschaltens (zweiter Bildschirm).
BC VERDICHTER TIMER VERDI. START: 00s
Überprüfung des aktuellen Werts der allgemeinen Software-Uhren (zweiter Bildschirm).
BC VERDICHTER TIMER C11 GRD: 000s AR: 000s C12 GRD: 000s AR: 000s C21 GRD: 000s AR: 000s
BW VERDICHTER TIMER C22 GRD: 000s AR: 000s C31 GRD: 000s AR: 000s C32 GRD: 000s AR: 000s
Überprüfung des aktuellen Werts der Verdichter-Uhren (erster Bildschirm).
Überprüfung des aktuellen Werts der Verdichter-Uhren (zweiter Bildschirm).
Menü Schutzvorrichtungen
Das Menü "Schutzvorrichtungen" bietet hilfreiche Informationen zur Fehlersuche.
BX ALARM EINHEIT 0C9: EIN E SENS. FEHL.
BX ALARM MODUL 1 1CA : AUS E SENS.FEHL.
BX ALARM MODUL 2 2CA : AUS E SENS.FEHL.
BX ALARM MODUL 3 3CA : AUS E SENS.FEHL.
Zum Abrufen, welche Sicherheits­funktion der Einheit für die Abschaltung verantwortlich ist.
Zum Abrufen, welche Sicherheits­funktion des Moduls 1 für die Abschaltung verantwortlich ist.
Zum Abrufen, welche Sicherheits­funktion des Moduls 2 für die Abschaltung verantwortlich ist.
Zum Abrufen, welche Sicherheits­funktion des Moduls 3 für die Abschaltung verantwortlich ist.
Menü Aufzeichnung
Das Menü "Aufzeichnung" enthält alle Informationen über die letzten Abschaltungen. Der Aufbau dieses Menüs ist identisch mit dem des Schutzvorrichtungsmenüs. Sobald eine Störung behoben ist und der Bediener eine Rückstellung vornimmt, werden die betreffenden Daten des Schutzvorrichtungsmenüs in das Aufzeichnungsmenü kopiert. Warnungen werden ebenfalls aufgezeichnet.
Zusätzlich kann die Anzahl der bisher ausgelösten Schutz­vorrichtungen auf der ersten Zeile der Aufzeichnungsbildschirme abgelesen werden.
Info-Menü
BX ZEIT INFORM. ZEIT: 00h00 DAT: 01/01/2001
BC EINHEIT INFORM. MODELL: WW-HP-32 HERSTELL. NR.: 0000000 KAELTEMITTEL: R134a
BC EINHEIT INFORM. SW: V1,0M6 (01/11/01) SW CODE: FLDKNMCH0A
BW PCB INFORM. BOOT: V2,02 - 02/08/00 BIOS: V2,32 - 31/07/01
Abrufen von Informationen über Uhrzeit und Datum.
Abrufen von zusätzlichen Informa­tionen über das Gerät, wie z.B. Gerätetyp, verwendetes Kältemittel und Herstellungsnummer.
Abrufen von Informationen über die Version der Regler-Software.
Abrufen von Informationen über die Leiterplatte.
Menü Eingang/Ausgang
Neben der Grundinformation können Bildschirmanzeigen mit detaillierteren Informationen aufgerufen werden, wenn das Schutzvorrichtungsmenü aktiviert ist. Drücken Sie die Taste q. Es erscheinen "ähnliche" Bildschirme wie die folgenden:
BC EINHEIT HIST.: 004 0C9: EIN E SENS. FEHL. 00h00 - 12/01/2001 MENUELLER MODUS
BC EINHEIT HIST.: 004 0C9: EIN E SENS. FEHL. EIN. E: 12.0°C STUFE: EIN. C: 30.0°C 0
BC EINHEIT HIST.: 004 0C9: EIN E SENS. FEHL. AUS. 1: 07.0°C AUS. 2: 07.0°C
Zum Feststellen der Uhrzeit und der Regelungsart zum Zeitpunkt der Geräteabschaltung.
Zum Feststellen der gemeinsamen Temperatur des Einlasswassers in den Verdampf er und V erflüssiger .
Zum Feststellen der Temperatur des Auslasswassers aus dem Verdampfer in allen Modulen zum Zeitpunkt der Abschaltung.
BC EINHEIT HIST.: 004 0C9: EIN E SENS. FEHL. C11: EIN C21: C12: EIN EIN
BC EINHEIT HIST.: 004 0C9: EIN E SENS. FEHL. C22: EIN
Zum Feststellen des Status der Verdichter zum Zeitpunkt der Abschaltung (erster Bildschirm).
Zum Feststellen des Status der Verdichter zum Zeitpunkt der Abschaltung (zweiter Bildschirm).
Das Menü "Eingang/Ausgang" zeigt den Status aller digitalen Eingänge und der Relais-Ausgänge des Geräts an.
BX DIG. EING. M1 SCHUTZ: OK M2 SCHUTZ: OK M3 SCHUTZ: NOK
BC DIG. EING. STROEMW.: STROEM OK REV. PHASE PR.: OK
Zur Überprüfung, ob eine Modul­Schutzvorrichtung aktiviert ist.
Zur Überprüfung des Phasen­umkehrschutzes, und ob der Wasserzufluss zum Verdampfer gewährleistet ist.
BC DIG. EING. WECHS. DI1 DOPP. SOLL: SOLL1 DI2 FB EINAUS: AUS DI3 FERN. K/H: KUEHL.
BC RELAIS AUSG. C11: EIN C12: EIN C21: EIN C22: EIN C31: EIN C32: AUS
BC RELAIS AUSG. LPBYPASS1: GESCHL. LPBYPASS2: GESCHL. LPBYPASS3: OFFEN
BC RELAIS AUSG. ALLG. ALARM: GESCHL. PUMP/ALLG. OP.: GESCHL
Zur Überprüfung des Status der veränderbaren digitalen Eingänge.
Zur Überprüfung des Status der Relais-Ausgänge der Verdichter.
Zur Überprüfung des Niederdruck­Bypasses der Module.
Zum Ermitteln des Status der alarm­spannungsfreien Kontakte und der Pumpen-/allgemeinen Betriebskontakte.
EWWQ049~064KAW1M + ECB2+3MUCW
Kompakte wassergekühlte Kaltwassererzeuger
D-EOMHP01008-17EU_01
Bedienungsanleitung
10
BW REL. AUSG. WECHS. DO1 UMKEHRV. (K/H): O
Zur Überprüfung des Status des veränderbaren Relais-Ausgangs.
Menü Benutzer-Password
B PASSWORT AEND.
NEUES PASSW.: 0000 BESTAET.: 0000
Änderung des Benutzer-Passwords.
Menü Kühlen/Heizen
B KUEHLEN/HEIZEN MODUS: KUEHL. (VERDA.)
Funktionen des Menüs Benutzereinstellungen
Zum Auswählen von Kühl- oder Heizmodus.
Zugang zum Menü Benutzereinstellungen
Das Menü "Benutzereinstellungen" ist vom Benutzer-Password (einer vierstelligen Zahl zwischen 0000 und 9999) geschützt.
1 Wechseln Sie vom Hauptmenü in das BEN. EINST. MENU. (Siehe
Kapitel "Hauptmenü" auf Seite 9.) Der Regler fragt Sie nach dem Password.
2 Geben Sie mit den Tasten g und h das korrekte Password ein. 3 Drücken Sie die Taste q, um das Password zu bestätigen und
um ins Menü Benutzereinstellungen zu gelangen. Der Regler zeigt automatisch den ersten Bildschirm des Menüs
Benutzereinstellungen an.
Definieren von Einstellungen einer bestimmten Funktion:
1 Öffnen Sie über die Tasten g und h den entsprechenden Bild-
schirm des Menüs Benutzereinstellungen.
2 Platzieren Sie den Cursor mit der Taste q hinter den zu
ändernden Parameter.
3 Wählen Sie über die Tasten g und h die entsprechende Ein-
stellung aus.
4 Drücken Sie zur Bestätigung der Auswahl die Taste q.
Wenn die Auswahl bestätigt wurde, schaltet der Cursor zum nächsten Parameter um, der verändert werden kann.
5 Wenn Sie die anderen Parameter veränder n möchten, wieder-
holen Sie diese Schritte ab Punkt 2.
Definition der Thermostateinstellungen
Wenn der automatische Regelmodus ausgewählt ist, verwendet die Einheit zum Regeln der Kühl- oder Heizleistung einen Thermostat. Die maximale Anzahl der Schritte des Thermostats entspricht den Angaben:
98 4 147 6 113 4 162 6 128 4 177 6
192 6
Die Thermostateinstellungen sind jedoch nicht festgelegt und können über den Bildschirm THERMOST. EINST. im Menü Benutzereinstellungen verändert werden.
Standard- und Grenzwerte sowie Stufen der Thermostat­einstellungen sind wie folgt:
Unterer
ST.L (°C) 0.4 2.0 0.1 1.5 STUFENDIFF. (°C) 0.2 0.8 0.1 0.5 ANHEB (sec) 15 300 1 180 ABSEN (sec) 15 300 1 20
HINWEIS
In "Anhang I" auf Seite 17 finden Sie einen
Grenzwert
Oberer
Grenzwert
Stufe
Standard-
wert
Funktionsplan mit den Thermostateinstellungen.
Festlegen der Primär/Sekundär-Betriebsart
Die Primär/Sekundär-Betriebsart legt fest, welches Modul bei Leistungsbedarf zuerst in Betrieb geht.
Die Primär/Sekundär-Parameter lauten wie folgt:
SEQ-UMSCH. MOD
Automatic: Das Regelgerät entscheidet, ob Modul 1, Modul 2 oder Modul 3 zuerst in Betrieb geht. Die Module gehen entsprechend der eingegebenen Startreihenfolge in Betrieb (siehe Tabelle unten).
3 Module 2 Module
als erstes > als nächstes > als letztes als erstes > als letztes
123 12 231 21 312
HINWEIS
Wenn ein Modul aufgrund einer Störung abgeschaltet wurde, geht stattdessen das nächste Modul in Betrieb.
Definition und Aktivierung der manuellen Regelungsart
Die Einheit ist mit einem Thermostat ausgerüstet, der die Kühl­leistung der Einheit regelt. Es gibt zwei verschiedene Regelmodi:
Handbetrieb: der Bediener regelt die Leistung selbst - MANUELLE
KONTR.
Einlaßsteuermodus: und/oder die Temperatur des in den Verflüssiger eintretenden Wassers zum Regeln der Leistung der Einheit - EIN. WASS.
Wenn der Bediener die Leistung selbst regeln möchte, kann er die Betriebsart "Handbetrieb" auf dem KONTROLL EINST.-Bildschirm des Menüs "Benutzereinstellungen" einschalten. In diesem Fall muß er folgende Parameter eingeben:
MODUS (derzeitige Betriebsart): Handbetrieb.
C11, C12, C21, C22, C31, C32 (Status des Verdichters von Modul 1, 2
und 3 im manuellen Modus oder Leistungswert im Fall eines aktivierten "capacity limitation remote contact" (Leistungs­begrenzungsfernkontakts)): EIN oder AUS.
HINWEIS
Zur Aktivierung der manuellen Regelungsart wählen Sie MANUEL als aktuelle Betriebsart aus. Zur Deaktivierung der manuellen Regelungsart wählen Sie EIN. WASS. als aktuelle Betriebsart aus.
Bedienungsanleitung
11
SEQ-UMSCH. STD: Im Automatikbetrieb ist die auf dieser Anzeige angegebene Stundenzahl die Maximaldifferenz zwischen den Betriebsstunden der Module. Dieser Wert ist wichtig für die Wartung. Er sollte ausreichend hoch eingestellt werden, damit nicht alle Module zur gleichen Zeit gewartet werden müssen und mindestens ein Modul ständig in Betrieb bleiben kann. Die Unter- bzw. die Obergrenze beträgt 100 bzw. 1000 Stunden. Der Standardwert beträgt 1000 Stunden.
Festlegen der Einstellungen der Pumpensteuerung
Der Bildschirm PUMPENSTEUR des Benutzereinstellungsmenüs ermög­licht dem Benutzer, die Vorlaufzeit und die Nachlaufzeit der Pumpe einzustellen.
PUMPENVORL: wird verwendet, um den Zeitraum zu definieren, in dem die Pumpe arbeiten muß, bevor die Einheit anlaufen kann.
PUMPENNACHL: wird verwendet, um den Zeitraum zu definieren, in dem die Pumpe weiterarbeitet, nachdem die Einheit gestoppt wurde.
Kompakte wassergekühlte Kaltwassererzeuger
EWWQ049~064KAW1M + ECB2+3MUCW
D-EOMHP01008-17EU_01
Loading...
+ 144 hidden pages