1.1About this document ...................................................................................................................................................... 5
1.2Meaning of warnings and symbols.................................................................................................................................6
1.3Installer reference guide at a glance .............................................................................................................................. 7
2 General safety precautions9
2.1For the installer............................................................................................................................................................... 9
2.1.2Installation site ............................................................................................................................................... 10
2.1.3Refrigerant — in case of R410A or R32.......................................................................................................... 10
4.1Overview: About the box ................................................................................................................................................ 20
4.2Outdoor unit ................................................................................................................................................................... 20
4.2.1To handle the outdoor unit ............................................................................................................................ 20
4.2.2To unpack the outdoor unit ........................................................................................................................... 21
4.2.3To remove the accessories from the outdoor unit........................................................................................ 23
5.1.1Identification label: Outdoor unit .................................................................................................................. 25
5.2Combining units and options.......................................................................................................................................... 26
5.2.1Possible options for the outdoor unit ............................................................................................................ 26
5.2.2Possible combinations of outdoor unit and domestic hot water tank.......................................................... 29
6.2Setting up the space heating/cooling system ................................................................................................................ 32
6.3Setting up an auxiliary heat source for space heating ................................................................................................... 45
6.4Setting up the domestic hot water tank......................................................................................................................... 48
6.4.1System layout – Standalone DHW tank ......................................................................................................... 48
6.4.2Selecting the volume and desired temperature for the DHW tank .............................................................. 48
6.4.3Setup and configuration – DHW tank ............................................................................................................ 50
6.4.4DHW pump for instant hot water .................................................................................................................. 50
6.4.5DHW pump for disinfection ........................................................................................................................... 51
6.4.6DHW pump for tank preheating..................................................................................................................... 52
6.5Setting up the energy metering...................................................................................................................................... 52
6.5.3Power supply layouts with power meters ..................................................................................................... 54
6.6Setting up the power consumption control ................................................................................................................... 59
6.6.1Permanent power limitation .......................................................................................................................... 59
6.6.2Power limitation activated by digital inputs .................................................................................................. 60
6.6.4BBR16 power limitation.................................................................................................................................. 62
6.7Setting up an external temperature sensor ................................................................................................................... 63
7 Unit installation64
7.1Preparing the installation site......................................................................................................................................... 64
7.1.1Installation site requirements of the outdoor unit........................................................................................ 64
7.1.2Additional installation site requirements of the outdoor unit in cold climates............................................ 67
7.2Mounting the outdoor unit............................................................................................................................................. 67
7.2.1About mounting the outdoor unit ................................................................................................................. 67
7.2.2Precautions when mounting the outdoor unit .............................................................................................. 68
7.2.3To provide the installation structure ............................................................................................................. 68
7.2.4To install the outdoor unit ............................................................................................................................. 68
7.2.5To provide drainage........................................................................................................................................ 69
7.2.6To install the discharge grille.......................................................................................................................... 71
7.3Opening and closing the unit.......................................................................................................................................... 71
Installer reference guide
2
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Table of contents
7.3.1About opening the units................................................................................................................................. 71
7.3.2To open the outdoor unit ............................................................................................................................... 72
7.3.3To close the outdoor unit ............................................................................................................................... 72
8 Piping installation73
8.1Preparing water piping ................................................................................................................................................... 73
8.1.2Formula to calculate the expansion vessel pre-pressure .............................................................................. 76
8.1.3To check the water volume and flow rate ..................................................................................................... 76
8.1.4Changing the pre-pressure of the expansion vessel...................................................................................... 79
8.1.5To check the water volume: Examples .......................................................................................................... 79
8.2Connecting water piping................................................................................................................................................. 80
8.2.1About connecting the water piping ............................................................................................................... 80
8.2.2Precautions when connecting the water piping ............................................................................................ 80
8.2.3To connect the water piping .......................................................................................................................... 80
8.2.4To protect the water circuit against freezing ................................................................................................ 82
8.2.5To fill the water circuit ................................................................................................................................... 85
8.2.6To fill the domestic hot water tank ................................................................................................................ 85
8.2.7To insulate the water piping .......................................................................................................................... 86
9 Electrical installation87
9.1About connecting the electrical wiring .......................................................................................................................... 87
9.1.1Precautions when connecting the electrical wiring....................................................................................... 87
9.1.2Guidelines when connecting the electrical wiring......................................................................................... 88
9.1.4About preferential kWh rate power supply ................................................................................................... 89
9.1.5Overview of electrical connections except external actuators ..................................................................... 90
9.2Connections to the outdoor unit.................................................................................................................................... 91
9.2.1To connect the electrical wiring to the outdoor unit .................................................................................... 96
9.2.2To connect the main power supply................................................................................................................ 97
9.2.3To connect the backup heater power supply ................................................................................................ 100
9.2.5To connect the user interface ........................................................................................................................ 108
9.2.6To connect the shut-off valve ........................................................................................................................ 111
9.2.7To connect the electricity meters .................................................................................................................. 112
9.2.8To connect the domestic hot water pump .................................................................................................... 113
9.2.9To connect the alarm output ......................................................................................................................... 113
9.2.10To connect the space cooling/heating ON/OFF output................................................................................. 114
9.2.11To connect the changeover to external heat source..................................................................................... 115
9.2.12To connect the power consumption digital inputs........................................................................................ 116
9.2.13To connect the safety thermostat (normally closed contact)....................................................................... 117
9.2.14To connect a Smart Grid................................................................................................................................. 118
10 Finishing the outdoor unit installation122
10.1 To check the insulation resistance of the compressor .................................................................................................. 122
11.1.1To access the most used commands ............................................................................................................. 124
11.1.2To connect the PC cable to the switch box.................................................................................................... 126
11.3 Possible screens .............................................................................................................................................................. 128
11.3.3Main menu screen.......................................................................................................................................... 131
11.4.2Using and programming schedules................................................................................................................ 134
11.4.4Setting the energy prices................................................................................................................................ 142
11.5.1What is a weather-dependent curve? ........................................................................................................... 144
11.6 Settings menu ................................................................................................................................................................. 149
11.7 Menu structure: Overview user settings ........................................................................................................................ 217
11.8 Menu structure: Overview installer settings .................................................................................................................. 219
12.4.3Operation test run.......................................................................................................................................... 225
12.4.4Actuator test run ............................................................................................................................................ 226
15.2 Precautions when troubleshooting ................................................................................................................................ 234
15.3 Solving problems based on symptoms ........................................................................................................................... 235
15.3.1Symptom: The unit is NOT heating or cooling as expected........................................................................... 235
15.3.2Symptom: Hot water does NOT reach the desired temperature.................................................................. 235
15.3.3Symptom: The compressor does NOT start (space heating or domestic water heating) ............................ 236
15.3.4Symptom: The system is making gurgling noises after commissioning........................................................ 236
15.3.5Symptom: The pump is blocked..................................................................................................................... 237
15.3.6Symptom: The pump is making noise (cavitation)......................................................................................... 237
15.3.7Symptom: The pressure relief valve opens.................................................................................................... 238
15.3.8Symptom: The water pressure relief valve leaks........................................................................................... 238
15.3.9Symptom: The space is NOT sufficiently heated at low outdoor temperatures........................................... 239
15.3.10 Symptom: The pressure at the tapping point is temporarily unusually high................................................ 240
15.3.11 Symptom: Tank disinfection function is NOT completed correctly (AH-error)............................................. 240
15.4 Solving problems based on error codes ......................................................................................................................... 240
15.4.1To display the help text in case of a malfunction.......................................................................................... 241
15.4.2Error codes of the unit ................................................................................................................................... 241
16 Disposal246
16.1 To recover refrigerant..................................................................................................................................................... 246
16.1.1To open the stop valves ................................................................................................................................. 247
16.1.2To manually open the electronic expansion valves....................................................................................... 247
16.1.3Recovery mode — In case of 3N~ models (7-segments display) .................................................................. 248
16.1.4Recovery mode — In case of 1N~ models (7-LEDs display) .......................................................................... 251
17 Technical data253
17.1 Service space: Outdoor unit ........................................................................................................................................... 254
17.2 Piping diagram: Outdoor unit ......................................................................................................................................... 256
17.3 Wiring diagram: Outdoor unit ........................................................................................................................................ 258
Installer reference guide
4
18 Glossary266
19 Field settings table267
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
1 About the documentation
In this chapter
1.1About this document..............................................................................................................................................................5
1.2Meaning of warnings and symbols.........................................................................................................................................6
1.3Installer reference guide at a glance......................................................................................................................................7
1.1 About this document
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
▪ General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the outdoor unit)
1 | About the documentation
▪ Operation manual:
- Quick guide for basic usage
- Format: Paper (in the box of the outdoor unit)
▪ User reference guide:
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
▪ Installation manual:
- Installation instructions
- Format: Paper (in the box of the outdoor unit)
▪ Installer reference guide:
- Preparation of the installation, good practices, reference data,…
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
▪ Addendum book for optional equipment:
- Additional info about how to install optional equipment
- Format: Paper (in the box of the outdoor unit) + Digital files on http://
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Latest revisions of the supplied documentation may be available on the regional
Daikin website or via your dealer.
The original documentation is written in English. All other languages are
translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
Installer reference guide
5
1 | About the documentation
▪ The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
Online tools
In addition to the documentation set, some online tools are available for installers:
▪ Daikin Technical Data Hub
- Central hub for technical specifications of the unit, useful tools, digital
- Publicly accessible via https://daikintechnicaldatahub.eu.
▪ Heating Solutions Navigator
- Digital toolbox that offers a variety of tools to facilitate the installation and
- To access Heating Solutions Navigator, registration to the Stand By Me
▪ Daikin e-Care
- Mobile app for installers and service technicians that allows you to register,
resources, and more.
configuration of heating systems.
platform is required. For more information, see https://
professional.standbyme.daikin.eu.
configure and troubleshoot heating systems.
- The mobile app can be downloaded for iOS and Android devices using the QR
codes below. Registration to the Stand By Me platform is required to access
the app.
App StoreGoogle Play
1.2 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or
cold temperatures.
Installer reference guide
6
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
SymbolExplanation
Before installation, read the installation and operation
manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the
service manual.
1 | About the documentation
For more information, see the installer and user reference
guide.
The unit contains rotating parts. Be careful when servicing or
inspecting the unit.
Symbols used in the documentation:
SymbolExplanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
1.3 Installer reference guide at a glance
ChapterDescription
About the documentationWhat documentation exists for the installer
General safety precautionsSafety instructions that you must read before
Specific installer safety
instructions
installing
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
About the boxHow to handle the box, unpack the units and
remove their accessories
About the units and options▪ How to identify the units
▪ Possible combinations of units and options
Application guidelinesVarious installation setups of the system
Installer reference guide
7
1 | About the documentation
Unit installationWhat to do and know to install the system,
Piping installationWhat to do and know to install the piping of the
Electrical installationWhat to do and know to install the electrical
ChapterDescription
including information on how to prepare for an
installation
system, including information on how to
prepare for an installation
components of the system, including
information on how to prepare for an
installation
Finishing the outdoor unit
installation
What to do after unit installation, piping
installation and electrical installation
ConfigurationWhat to do and know to configure the system
after it is installed
CommissioningWhat to do and know to commission the system
after it is configured
Hand‑over to the userWhat to give and explain to the user
Maintenance and serviceHow to maintain and service the units
TroubleshootingWhat to do in case of problems
DisposalHow to dispose of the system
Technical dataSpecifications of the system
GlossaryDefinition of terms
Field settings tableTable to be filled in by the installer, and kept for
future reference
Note: There is also an installer settings table in
the user reference guide. This table has to be
filled in by the installer and handed over to the
user.
Installer reference guide
8
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
2 General safety precautions
In this chapter
2.1For the installer.......................................................................................................................................................................9
2.1.2Installation site ....................................................................................................................................................... 10
2.1.3Refrigerant — in case of R410A or R32 ................................................................................................................. 10
If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
▪ Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return
to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
2 | General safety precautions
WARNING
Improper installation or attachment of equipment or accessories could result in
electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable
legislation (on top of the instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…)
when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially
children, can play with them. Possible risk: suffocation.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
Installer reference guide
9
2 | General safety precautions
In accordance with the applicable legislation, it might be necessary to provide a
logbook with the product containing at least: information on maintenance, repair
work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the
product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
CAUTION
▪ Do NOT place any objects or equipment on top of the unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to
avoid water ingress.
2.1.2 Installation site
▪ Provide sufficient space around the unit for servicing and air circulation.
▪ Make sure the installation site withstands the weight and vibration of the unit.
▪ Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
▪ In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
2.1.3 Refrigerant — in case of R410A or R32
If applicable. See the installation manual or installer reference guide of your
application for more information.
Installer reference guide
10
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
2 | General safety precautions
WARNING
During tests, NEVER pressurize the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
▪ Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Selfcombustion and explosion of the compressor because of air going into the
operating compressor.
▪ Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen
to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
▪ When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after
performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of
oxygen going into the operating compressor.
▪ In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
▪ The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the
system.
▪ Charge the liquid refrigerant as follows:
Installer reference guide
11
2 | General safety precautions
IfThen
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid
filling siphon attached")
A siphon tube is NOT presentCharge with the cylinder upside down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of
the refrigerant tank immediately. If the valve is NOT closed immediately, remaining
pressure might charge additional refrigerant. Possible consequence: Incorrect
refrigerant amount.
2.1.4 Water
2.1.5 Electrical
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before
servicing. The voltage MUST be less than 50VDC before you can touch electrical
components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
categoryIII condition, MUST be installed in the fixed wiring.
Installer reference guide
12
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
2 | General safety precautions
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable legislation.
▪ All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
▪ NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
▪ Make sure to install the required fuses or circuit breakers.
▪ Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
▪ When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
CAUTION
▪ When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
▪ When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
▪ The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened
before the earth wire is in case the power supply is pulled loose from the stress
relief.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness, do as shown in the figure
above.
▪ For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Install power cables at least 1 m away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1 m may not be
sufficient.
Installer reference guide
13
2 | General safety precautions
WARNING
▪ After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes on and off while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.
Installer reference guide
14
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
3 | Specific installer safety instructions
3 Specific installer safety instructions
Always observe the following safety instructions and regulations.
Handling the unit (see
"To handle the outdoor unit"[420]
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.
Application guidelines (see
"6Application guidelines"[431]
CAUTION
If there is more than one leaving water zone, ALWAYS install a mixing valve station in
the main zone to decrease (in heating)/increase (in cooling) the leaving water
temperature when the additional zone has demand.
Installation site (see
"7.1Preparing the installation site"[464]
WARNING
Follow the service space dimensions in this manual for correct installation of the unit.
See "17.1Service space: Outdoor unit"[4254].
Special requirements for R32 (see
unit"[464]
)
WARNING
▪ Do NOT pierce or burn.
▪ Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
▪ Be aware that R32 refrigerant does NOT contain an odour.
)
)
)
"Installation site requirements of the outdoor
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a wellventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater).
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation (for example national gas regulation) and
are executed only by authorised persons.
Mounting the outdoor unit (see
WARNING
Fixing method of the outdoor unit MUST be in accordance with the instructions from
this manual. See "7.2Mounting the outdoor unit"[467].
Opening and closing the unit (see
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
"7.2Mounting the outdoor unit"[467]
"7.3Opening and closing the unit"[471]
)
)
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Installer reference guide
15
3 | Specific installer safety instructions
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
Piping installation (see
"8Piping installation"[473]
WARNING
Field piping method MUST be in accordance with the instructions from this manual.
See "8Piping installation"[473].
In case of freeze protection by glycol:
WARNING
Ethylene glycol is toxic.
WARNING
Due to the presence of glycol, corrosion of the system is possible. Uninhibited glycol
will turn acidic under the influence of oxygen. This process is accelerated by the
presence of copper and high temperatures. The acidic uninhibited glycol attacks
metal surfaces and forms galvanic corrosion cells that cause severe damage to the
system. Therefore it is important that:
▪ the water treatment is correctly executed by a qualified water specialist,
▪ a glycol with corrosion inhibitors is selected to counteract acids formed by the
oxidation of glycols,
▪ no automotive glycol is used because their corrosion inhibitors have a limited
lifetime and contain silicates which can foul or plug the system,
▪ galvanized pipes are NOT used in glycol systems since the presence may lead to
the precipitation of certain components in the glycol's corrosion inhibitor.
)
Electrical installation (see
WARNING
Electrical wiring connection method MUST be in accordance with the instructions
from:
▪ This manual. See "9Electrical installation"[487].
▪ The wiring diagram, which is delivered with the unit, located at the inside of the
service cover. For a translation of its legend, see "17.3 Wiring diagram: Outdoor
unit"[4258].
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
"9Electrical installation"[487]
)
Installer reference guide
16
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
3 | Specific installer safety instructions
WARNING
▪ All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
▪ If the power supply has a missing or wrong N-phase, equipment might break
down.
▪ Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
▪ Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
Rotating fan. Before powering ON the outdoor unit, make sure that the discharge
grille covers the fan as protection against a rotating fan. See "To install the discharge
grille"[471].
CAUTION
Do NOT push or place redundant cable length in the unit.
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by
the safety devices required by the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, always connect the backup heater
power supply and the earth cable.
WARNING
Stripped wire. Make sure that stripped wire cannot make contact with possible
water on the bottom plate.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Configuration (see
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
"11Configuration"[4123]
)
Installer reference guide
17
3 | Specific installer safety instructions
WARNING
Be aware that the domestic hot water temperature at the hot water tap will be equal
to the value selected in field setting [2-03] after a disinfection operation.
When the high domestic hot water temperature can be a potential risk for human
injuries, a mixing valve (field supply) shall be installed at the hot water outlet
connection of the domestic hot water tank. This mixing valve shall secure that the
hot water temperature at the hot water tap never rise above a set maximum value.
This maximum allowable hot water temperature shall be selected according to the
applicable legislation.
CAUTION
Be sure that the disinfection function start time [5.7.3] with defined duration [5.7.5]
is NOT interrupted by possible domestic hot water demand.
CAUTION
BSH allowance schedule [9.4.2] is used to restrict or allow booster heater
operation based on a weekly program. Advice: In order to avoid unsuccessful
disinfection function, at least allow the booster heater (by the weekly program) for
minimum 4hours starting from the scheduled start-up of disinfection. If the booster
heater is restricted during disinfection, this function will NOT be successful and the
applicable warning AH will be generated.
Commissioning (see
"12Commissioning"[4220]
WARNING
Commissioning method MUST be in accordance with the instructions from this
manual. See "12Commissioning"[4220].
Maintenance and service (see
CAUTION
Water coming out of the valve may be very hot.
WARNING
If the internal wiring is damaged, it has to be replaced by the manufacturer, its
service agent or similarly qualified persons.
Troubleshooting (see
"15Troubleshooting"[4234]
WARNING
▪ When carrying out an inspection on the switch box of the unit, ALWAYS make
sure that the unit is disconnected from the mains. Turn off the respective circuit
breaker.
▪ When a safety device was activated, stop the unit and find out why the safety
device was activated before resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default setting. If you are unable to
find the cause of the problem, call your dealer.
)
"14Maintenance and service"[4231]
)
)
Installer reference guide
18
DANGER: RISK OF ELECTROCUTION
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
3 | Specific installer safety instructions
WARNING
Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this
appliance MUST NOT be supplied through an external switching device, such as a
timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
DANGER: RISK OF BURNING/SCALDING
WARNING
Air purging heat emitters or collectors. Before you purge air from heat emitters or
collectors, check if or is displayed on the home screen of the user interface.
▪ If not, you can purge air immediately.
▪ If yes, make sure that the room where you want to purge air is sufficiently
ventilated. Reason: Refrigerant might leak into the water circuit, and
subsequently into the room when you purge air from the heat emitters or
collectors.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Installer reference guide
19
4 | About the box
4 About the box
In this chapter
4.1 Overview: About the box
4.1Overview: About the box........................................................................................................................................................ 20
4.2Outdoor unit ........................................................................................................................................................................... 20
4.2.1To handle the outdoor unit.................................................................................................................................... 20
4.2.2To unpack the outdoor unit ................................................................................................................................... 21
4.2.3To remove the accessories from the outdoor unit ............................................................................................... 23
This chapter describes what you have to do after the box with the outdoor unit is
delivered on-site.
Keep the following in mind:
▪ At delivery, the unit MUST be checked for damage. Any damage MUST be
reported immediately to the claims agent of the carrier.
▪ Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
▪ Prepare the path along which you want to bring the unit inside in advance.
4.2 Outdoor unit
4.2.1 To handle the outdoor unit
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.
Forklift or pallet truck
While the unit is still on its pallet, handle the unit using a forklift or pallet truck.
Installer reference guide
20
Manually
After unpacking, carry the unit using the slings delivered as accessory.
See also:
▪ "To unpack the outdoor unit"[421]
▪ "To remove the accessories from the outdoor unit"[423]
▪ "To install the outdoor unit"[468]
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
4 | About the box
a1
a2
a1
a2
±150
kg
12
4.2.2 To unpack the outdoor unit
a1, a2 Slings
NOTICE
Unpacking – Top packaging. When you remove the top packaging, hold the box
containing the discharge grille to prevent it from falling.
1Remove the plastic foil and the top packaging.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Installer reference guide
21
4 | About the box
2Remove the outside accessories. See "To remove the accessories from the
outdoor unit"[423]. (There is also one accessory inside the unit that must be
removed after opening the unit.)
3Remove the top and corners cardboard packaging.
4Remove the plastic foil.
Installer reference guide
22
5Remove the transportation screws and washers.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
6×
M6
6×
4.2.3 To remove the accessories from the outdoor unit
a
g
d
bc
e
f
ENERG
IJAY
IAIE
ENERG
IJAY
IAIE
h
i
j
1Remove the accessories on top and in front of the unit.
4 | About the box
a Slings to carry the unit
b General safety precautions
c Operation manual
d Installation manual
e Addendum book for optional equipment
f Energy label
g User interface (front plate, rear plate, screws, and wall plugs)
h Discharge grille
i Screws for discharge grille
2After opening the unit (see "To open the outdoor unit"[4 72]), remove the
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
5.1.1Identification label: Outdoor unit .......................................................................................................................... 25
5.2Combining units and options.................................................................................................................................................. 26
5.2.1Possible options for the outdoor unit.................................................................................................................... 26
5.2.2Possible combinations of outdoor unit and domestic hot water tank ................................................................. 29
5.1 Identification
NOTICE
When installing or servicing several units at the same time, make sure NOT to switch
the service panels between different models.
5.1.1 Identification label: Outdoor unit
5 | About the units and options
Location
Model identification
Example: EBLA16DA3V3
CodeExplanation
EMonobloc outdoor heat pump
BB=Reversible (heating+cooling)
D=Heating only
LLow water temperature – ambient zone 2 (see operation
range)
ARefrigerant R32
16Capacity class
DAModel series
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
33=Model with integrated backup heater
[—]=Model without integrated backup heater
V3Power supply:
V3=1N~, 230VAC, 50Hz
W1=3N~, 400VAC, 50Hz
Installer reference guide
25
5 | About the units and options
5.2 Combining units and options
5.2.1 Possible options for the outdoor unit
Multi-zoning wired controls
You can connect the following multi-zoning wired controls:
▪ Multi-zoning base unit 230V (EKWUFHTA1V3)
▪ Digital thermostat 230V (EKWCTRDI1V3)
▪ Analogue thermostat 230V (EKWCTRAN1V3)
▪ Actuator 230V (EKWCVATR1V3)
For installation instructions, see the installation manual of the control, and the
addendum book for optional equipment.
Room thermostat (EKRTWA, EKRTR1)
INFORMATION
Certain options might not be available in your country.
You can connect an optional room thermostat to the outdoor unit. This thermostat
can either be wired (EKRTWA) or wireless (EKRTR1).
For installation instructions, see the installation manual of the room thermostat
and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use the remote indoor temperature sensor (EKRTETS) only in combination
with the wireless thermostat (EKRTR1).
For installation instructions, see the installation manual of the room thermostat
and the addendum book for optional equipment.
Digital I/O PCB (EKRP1HBAA)
The digital I/O PCB is required to provide following signals:
▪ Alarm output
▪ Space heating/cooling On/OFF output
▪ Changeover to external heat source
For installation instructions, see the installation manual of the digital I/O PCB and
addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install
the demand PCB.
Installer reference guide
26
For installation instructions, see the installation manual of the demand PCB and
addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal sensor of the dedicated Human Comfort Interface
(BRC1HHDA used as room thermostat) will be used as room temperature sensor.
As an option the remote indoor sensor can be installed to measure the room
temperature on another location.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
5 | About the units and options
For installation instructions, see the installation manual of the remote indoor
sensor and addendum book for optional equipment.
INFORMATION
▪ The remote indoor sensor can only be used in case the user interface is
configured with room thermostat functionality.
▪ You can only connect either the remote indoor sensor or the remote outdoor
sensor.
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor
temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor
temperature on another location (e.g. to avoid direct sunlight) to have an
improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor
sensor and the addendum book for optional equipment.
INFORMATION
You can only connect either the remote indoor sensor or the remote outdoor sensor.
PC cable (EKPCCAB4)
The PC cable makes a connection between the hydro PCB (A1P) of the outdoor unit
and a PC. It gives the possibility to update the hydro software and EEPROM.
For installation instructions, see:
▪ Installation manual of the PC cable
▪ "To connect the PC cable to the switch box"[4126]
Heat pump convector (FWXV, FWXT, FWXM)
For providing space heating/cooling, it is possible to use the following heat pump
convectors:
▪ FWXV: floor-standing model
▪ FWXT: wall-mounted model
▪ FWXM: concealed model
For installation instructions, see:
▪ The installation manual of the heat pump convectors
▪ The installation manual of the heat pump convector options
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
For models without integrated backup heater, you can install the external backup
heater kit (EKLBUHCB6W1).
For installation instructions, see:
▪ Installation manual of the external backup heater kit
▪ "To connect the backup heater kit" [4102] (this topic partially supersedes the
installation manual of the backup heater)
If you install the external backup heater kit, then under certain conditions you also
need to install a bypass valve kit (EKMBHBP1). See:
Installer reference guide
27
5 | About the units and options
▪ "Bypass valve kit necessity"[4106]
▪ "To connect the bypass valve kit"[4 107] (this topic supersedes the instruction
sheet delivered with the bypass valve kit)
WLAN cartridge (BRP069A78)
You can install the wireless LAN cartridge to control the system via a smartphone
app.
For installation instructions, see the installation manual of the WLAN cartridge.
Universal centralised controller (EKCC8-W)
Controller for cascade control.
Bizone kit (BZKA7V3)
You can install an optional bizone kit.
For installation instructions, see the installation manual of the bizone kit.
Connection kit for third‑party tank (EKHY3PART)
Required when connecting a third-party tank to the system.
Contains a thermistor and a 3-way valve.
For installation instructions, see the installation manual of the connection kit.
Connection kit for third‑party tank with built‑in thermostat (EKHY3PART2)
Kit for the connection of a third‑party tank with built‑in thermostat to the system.
The kit converts a thermostat demand from the tank to a domestic hot water
request for the outdoor unit.
Domestic hot water tank
For providing domestic hot water, a domestic hot water tank can be connected to
the outdoor unit.
The following domestic hot water tanks are available:
TankRemark
Stainless steel tank (standard):
Inclusive booster heater
▪ EKHWS150D3V3
▪ EKHWS180D3V3
▪ EKHWS200D3V3
▪ EKHWS250D3V3
▪ EKHWS300D3V3
Stainless steel tank (+ components):
Inclusive:
Installer reference guide
28
▪ EKHWSU150D3V3
▪ EKHWSU180D3V3
▪ EKHWSU200D3V3
▪ EKHWSU250D3V3
▪ EKHWSU300D3V3
Polypropylene tank:
▪ EKHWP300B
▪ EKHWP500B
▪ Booster heater
▪ Components to comply with the UK
Building Regulation G3.
Tank with drainback solar system.
For these tanks, the booster heater
option (EKBH3S) must be installed.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
5 | About the units and options
TankRemark
Polypropylene tank:
▪ EKHWP300PB
▪ EKHWP500PB
Tank with pressurised solar system.
For these tanks, the booster heater
option (EKBH3S) must be installed.
For installation instructions, see the installation manual of the domestic hot water
tank and the addendum book for optional equipment.
Human Comfort Interface (BRC1HHDA) used as room thermostat
▪ The Human Comfort Interface (HCI) used as room thermostat can only be used in
combination with the user interface connected to the outdoor unit.
▪ The Human Comfort Interface (HCI) used as room thermostat needs to be
installed in the room that you want to control.
For installation instructions, see the installation and operation manual of the
Human Comfort Interface (HCI) as room thermostat, and the addendum book for
optional equipment.
Flow switch (EKFLSW1)
If you add glycol to the water, you also need to install a flow switch (and set
[E-0D]=1).
For installation instructions, see the installation manual of the flow switch.
Smart grid relay kit (EKRELSG)
The installation of the optional Smart grid relay kit is required in case of high
voltage Smart grid contacts (EKRELSG).
For installation instructions, see "To connect a Smart Grid"[4118].
5.2.2 Possible combinations of outdoor unit and domestic hot water tank
Combination table
Outdoor unitDomestic hot water tank
EKHWS*D*EKHWSU*D*EKHWP*Third-party
EBLA09~16OOOO
EDLA09~16OOOO
(a)
When using a third-party tank, make sure it complies with the minimum requirements (see
"Third-party tank requirements"[429]).
Third-party tank requirements
In case of a third-party tank, the tank shall adhere to the following requirements:
▪ The heat exchanger coil of the tank is ≥1.05m² and ≤3.7m².
▪ The tank thermistor must be located above the heat exchanger coil.
tank
(a)
(a)
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
▪ The booster heater must be located above the heat exchanger coil.
NOTICE
Performance. Performance data for third-party tanks CANNOT be provided, and
performance CANNOT be guaranteed.
Installer reference guide
29
5 | About the units and options
aba
b
For more detailed installation instructions, see the installation manual of the
connection kit and the addendum book for optional equipment.
If you have a tank in which you…
Can insert a thermistor.CANNOT insert a thermistor.
Use EKHY3PART.Use EKHY3PART2.
a Outdoor unit
b Tank
Installer reference guide
30
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Loading...
+ 250 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.