Daikin E8.1124 Operation manuals

Mixer module E8.1124
!
E8.1124
Mixer module
System diagram E8.1124
Configuration
2 mixed heating circuits remoted by BUS or 1 mixed heating circuit and fixed value-/swimming bath / DHW-control (LPS = 00)
With boiler control as mixer expansion module
The E8.1124 is for stand-alone-control too.
In this case you have to add the external sensor.
Without boiler control as zone-control
Mixer module E8.1124
Electrical connection
~230 V Switching capacity of relays 2(2) A, ~250 V
! If E6.1111 should be replaced, please change
the wiring of the additional relay (plug VI) from clamp 2 to clamp 1.
Power terminal assignments
Connector 2 [II]
N: Neutral conductor, mains L1: Power supply, unit L1´: Power supply, relay
D 1: Heat circuit pump HK 1 D 2: Heat circuit pump HK 2
v: Mixer open, heating circuit 2 v: Mixer closed, heating circuit
2
Connector 6 [VI]
1
1
VI
2
Multifunction relay 1
Connector 4 [IV]
1
v
1
M
2
3
IV
4
5
v: Mixer open, heating circuit 1 v
: Mixer closed, heating circuit 1
Sensor terminal assignments
Connector 9 [IX]
Bus
HL
IX
+-
CAN Bus Pin 1 = H (Data) CAN Bus Pin 2 = L (Data) CAN Bus Pin 3 = - (ground, Gnd) CAN Bus Pin 4 = + (12 V supply)
Connector 3 [III] (without solar integration)
Pin 1: FBR heating circuit 2 (room sensor)
-
III
Pin 2: FBR heating circuit 2 (ground) Pin 3: FBR heating circuit 2 (set value/
operating mode)
Elster GmbH Geschäftssegment Comfort Controls Kuhlmannstraße 10 31785 Hameln
www.kromschroeder.de
Terminal assignment
VII (1 + 2): eBUS (HS) or eBUS - DCF I (1 - 3): FBR2 (FBR1) for heating circuit 1 I (4 + 5): Flow sensor, heating circuit 2 I (9 + 10): Outdoor sensor V (1 + 2): Flow sensor, heating circuit 1 VIII (1 + 2): Multifunction relay
1 sensor III (1 - 3): FBR2 (FBR1) for heating circuit 2 IX (1 + 2): Data line CAN bus IX (3 + 4): Power supply CAN bus
II (1): Neutral conductor, mains II (2): Power supply, unit II (3): Power supply, relay II (4): Pump, heating circuit 1 II (5): Pump, heating circuit 2 II (7): Mixer, heating circuit 2 open II (8): Mixer, heating circuit 2 closed VI (1): Multifunction relay
1 IV (1): Mixer, heating circuit 1 open IV (2): Mixer, heating circuit 1 closed
Sensor terminal assignments
Connector 3 [III] (with solid fuel/ solar integration)
Pin 2: Heat circuit 2 RFB (room sensor)
-
III
Pin 2: Buffer sensor, lower and Room
sensor (ground)
Pin 3: Buffer sensor, lower (BUFFER-
T-LOW) in infeed area of solar/solid fuel
Connector 8 [Connector 1 [I]
1
VIII
Pin 1: Multifunction relay 1 sensor (ground) Pin 2: Multifunction relay
Connector 5 [Connector 1 [I]
1
V
D
Pin 1: Flow sensor, heating circuit 1 (ground) Pin 2: Flow sensor, heating circuit 1
Connector 1 [I]
Pin 1: FBR heating circuit 1 (room sensor)
-
Pin 2: FBR heating circuit 1 (ground) Pin 3: FBR heating circuit 1 (set val­ue/operating mode) Pin 4: Flow sensor, heating circuit 2
I
(ground) Pin 5: Flow sensor, heating circuit 2
Pin 9: Outdoor sensor (ground) Pin 10: Outdoor sensor
Connector 7 [VII]
FA
1
+
_
VII
2
eBUS
Pin 1: eBUS (HS) or eBUS - DCF Pin 2: DCF (ground)
EN 0414 6.6702.153-03 Printed in Germany, Subject to modification
1 sensor