Daikin DZK-MTS-3 Instructions Manual

Phone: (855) 770-5678 | http://www.daikinac.com
4008862
WIRED THERMOSTAT
Color graphic interface with capacitive screen for controlling zones in DZK systems. Powered by Main Control Board. Finished in steel and glass.
Functionalities:
Control of set point temperature. Displayed in 1ºF/0.5ºC increments.
Configurable set point range for Cooling and He ating.
Auto changeover mode can automatically change to cool/heat mode at set
point ±1ºF/0.5ºC (can be configured from 0 to 7ºF usi ng field settings) with a guard timer of 15, 30, 60 or 90 minutes.
Room temperature and rela tive humidity measurement of the zo ne.
Operation mode, user mode and airflow control (Only Main Wired Thermostat).
Timer function.
Time schedules programming.
Remote access to other zo nes of the system.
Configurable as Main or Zone thermostat.
DZK-MTS-3
Rev. 1.00
10-2016
TECHNICAL SPECS
Power supply and consumption
Type of power supply
Vdc
V max
12 V supplied from the Main Control Board
I max
145 mA
Stand-by consumption
0.876 W
Connection and communications
Shielded twisted pair
AWG 20 – 4 wired
Maximum wiring le ngth
(Control board to thermost at)
130 ft (40 m)
Operating temperatures
Storage
-4 to 158ºF (-20 to 70 ºC)
Operation
32 to 122ºF (0 to 50ºC)
Operating humidity range
5 to 90% (non-condensing)
Set-point temperature range
59 to 86ºF (15 to 30ºC)
Reading accuracy
±1ºF (±0.5 ºC)
Display accuracy
±1ºF (±0.5 ºC)
Relative humidity
±4 %
Mechanical aspects
Assembly
Surface through support
Protection class
IP 20
Type of probe
Airzone_NTC_10K
Weight (Mass)
0.44 lb (198 g)
Dimensions (WxHxD)
3.62x3.62x0.62 inch (92x 92x15.85 mm)
D
H
W
ASSEMBLY
FUNCTIONALITIES
CONNECTION
EXCEPTION CODES
Note: Refer to the DZK inst allation manual for troublesho oting steps.
Significado
Acción
1
xxx
xxxxx
1
2
3 4 5 6 7 8 9
11
10
12 1
2 3 4 5 6
Meaning
Error 1
Communication error with the main controller
Error 5
Temperature sensor is open
Error 6
Temperature sensor is short circuited
Error 8
Wireless Lite thermostat not f ound
Error 9
Communications error b etween the Daikin Interface Board and the system
Error 10
Communication error betwee n the DZK BACnet Interface and the system
Error 11
Communication error betwee n the Daikin Interface Board and the Daikin indoor unit
Meaning
Action
1
On/Off
On/off for the zone
2
Zone settings
Access to zone parameters
3
User settings
Access to user settings menu
4
Time schedules
Access to time schedules menu
5
Local ventilation
Enable / disable the local ventil ation
6
Zone demand
Displayed when the zone is calling for demand
7
Set-point temperature
Change the set-point temperature
8
Room temperature and humidity percentage
Displays the room temperature and the relative humidity in the zone
9
Current zone
Access to remote zone control
10
Operation mode
Access to operation mode menu (Main onl y)
11
User mode
Access to User mode menu (Ma in only)
12
Airflow control
Access to Airflow control menu (Main on ly)
Note: Do not connect t he “-“ pole to the “+” terminal. It may damage the device. h= 5 ft
Idle screen
Main screen
Meaning
Action
1
Date and time
Displays the current date and time
2
Current zone
Displays the name of the curren t zone
3
Room temperature
Displays the room temperature
4
Humidity percentage
Displays the percentage of room humidity
5
On/Off
On/off for the zone
6
Operation mode
Displays the current operation mode