Daikin DZ13SC Installation Instructions Manual

INSTALLATION INSTRUCTIONS
CONDENSING UNIT
HEAT PUMP INSTALLATION & SERVICE REFERENCE
Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Fail­ure to heed safety information increases the risk of personal in­jury, property damage, and/or product damage.
HIGH VOLTAGE! Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death .
ONLY individuals meeting th e r equiremen ts (at a minimum) of an “Entry Level Technician” as specified by the Air Conditioning, Heating, and Refrigeration Institute (AHRI) may use this information. At tem pt ing t o inst a ll o r repair this unit without such background may result in product damage, personal injury, or death.
Codes & Regulations
This product is designed and manufactured to comply with na­tional codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the in­staller. The manufacturer assumes no responsibility for equip­ment installed in violation of any codes or regulations. Rated performance is achieved after 72 hours of operation. Rated per­formance is delivered at the specified airflow. See outdoor unit specification sheet for split system models or product specifica­tion sheet for packaged and light commercial models. Specifica­tion sheets can be found at www.daikincomfort.com for Daikin brand products. Within the website, please select the residential or commercial products menu and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
The United States Environmental Protection Agency (EPA) has is­sued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
Should you have any questions please contact the local office of the EPA.
If replacing a condensing unit or air handler, the system must be manufacturer approved and Air Conditioning, Heating and Refrig­eration Institute (AHRI) matched. NOTE: Installation of unmatched systems is not allowed.
CAUTION
Scroll equipped units should never be used to evacuate the air conditioning system. Vacuums this low can cause internal electrical arcing resulting in a damaged or failed compressor.
Shipping Inspection
Always keep the unit upright; laying the unit on its side or top may cause equipment damage. Shipping damage, and subsequent in­vestigation is the responsibility of the carrier. Verify the model number, specifications, electrical characteristics, and accesso­ries are correct prior to installation. The distributor or manufac­turer will not accept claims from dealers for transportation dam­age or installation of incorrectly shipped units.
IOD-4002A 9/2013
Our continuing commitment to quality products may mean a change in specifications without notice.
© 2013
5151 San Felipe St., Suite 500, Houston, TX 77056
www.daikincomfort.com
Outdoor units are approved for operation above 55°F in cooling mode. Operation below 55°F in cooling mode requires the use of an approved low ambient kit.
Operating the unit in a structure that is not complete (either as part of new construction or renovation) will void the warranty.
Installation Clearances
Special consideration must be given to location of the condensing unit(s) in regard to structures, obstructions, other units, and any/ all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions require placement beneath an ob­struction there should be a minimum of 60 inches between the top of the unit and the obstruction(s). The specified dimensions meet requirements for air circulation only. Consult all appropri­ate regulatory codes prior to determining final clearances.
Another important consideration in selecting a location for the unit(s) is the angle to obstructions. Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance. Corner in­stallations are strongly discouraged.
In more severe weather locations, it is recommended that the unit be elevated to allow unobstructed drainage and air flow. The following elevation minimums are recommended:
Des ign T em perature
+15° and above 2 1/2"
-5° to +14 ° 8" belo w -5 ° 12"
Suggested
Minimum Elevation
Safe Refrigerant Handling
While these items will not cover every conceivable situation, they should serve as a useful guide.
To avoid possible injury, explosion or death, practice safe handling of refrigerants.
Mi ni m um Ai rf l ow Clea ra nce
Model Type A B C AA
Residential 10" 10" 18" 20"
Light Co mmercial 12" 12" 18" 24"
This unit can be located at ground floor level or on flat roofs. At ground floor level, the unit must be on a solid, level foundation that will not shift or settle. To reduce the possibility of sound transmission, the foundation slab should not be in contact with or be an integral part of the building foundation. Ensure the foun­dation is sufficient to support the unit. A concrete slab raised above ground level provides a suitable base.
Rooftop Installations
If it is necessary to install this unit on a roof structure, ensure the roof structure can support the weight and that proper consider­ation is given to the weather-tight integrity of the roof. Since the unit can vibrate during operation, sound vibration transmission should be considered when installing the unit. Vibration absorb­ing pads or springs can be installed between the condensing unit legs or frame and the roof mounting assembly to reduce noise vibration.
NOTE: These units require special location consideration in areas of heavy snow accumulation and/or areas with prolonged continuous subfreezing temperatures. Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation. Situate the unit to permit free unobstructed drainage of the defrost water and ice.
To avoid possible explosion:
Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it in warm water.
Never fill a cylinder more than 80% full of liquid refrigerant.
• Never add anything other than R-22 to an R-22 cylinder or R-410A to an R-410A cylinder. The service equipment used must be listed or certified for the type of refrigerant used.
• Store cylinders in a c ool, dry p la c e . Never use a cylind er as a platform or a roller.
To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrigerant from a system.
• Ensure the cylinder is free of damage which could lead to a leak or explosion.
• Ensure the hydrostatic test date does not exceed 5 ye a rs.
• Ensure the pressure rating meets or exceeds 400 lbs. When in doubt, do not use cylinder.
2
Refrigerant Lines
8
8
CAUTION
The compressor POE oil for R-410A units is extremely susceptible to moisture ab so rpt i on and could cause compr e s sor fa i lur e. Do not leave system open to atmosphere any longer than necessary for installation.
Use only refrigerant grade (dehydrated and sealed) copper tubing to connect the condensing unit with the indoor evaporator. After cutting the tubing, install plugs to keep refrigerant tubing clean and dry prior to and during installation. Tubing should always be cut square keeping ends round and free from burrs. Clean the tubing to prevent contamination.
Do NOT let refrigerant lines come in direct contact with plumbing, ductwork, floor joists, wall studs, floors, and walls. When run­ning refrigerant lines through a foundation or wall, openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap be­tween foundation or wall and refrigerant lines should be filled with a pliable silicon-based caulk, RTV or a vibration damping material. Avoid suspending refrigerant tubing from joists and studs with rigid wire or straps that would come in contact with the tubing. Use an insulated or suspension type hanger. Keep both lines separate and always insulate the suction line.
These sizes are recommended for line lengths of 79 feet or less to obtain optimum performance. For alternate line sizing options or runs of more than 79 feet, refer to Remote Cooling Service Manual, or TP-107 Long Line Set Application R-410A, or contact your dis­tributor for assistance.
RECOMMENDE D INTERCONNECTING TUBING (Ft )
Cond
Unit
Tons Suct Liq Suct Liq Suct Liq
1 1/2 5/8 1 /4 3/ 4 3/8 3/4 3/8
2 5/81/43/43/83/43/8
2 1/2 5/8 1/4 3/4 3/8 7/8 3/8
3 3/4 3/8 7 / 8 3/ 8 1 1/8 3 / 8
3 1/2 7/
47/ 5 7/8 3/81 1/83/81 1/83/8
* Lines gr eater t h an 79 feet i n leng th or ve rti cal el evatio n cha nges more than 50 feet refer to the Remote Cooli ng S ervice Manual or cont act your
distributor for assistance.
0-24 25-49 50-79*
Line Diameter (In. OD)
3/81 1/83/81 1/83/8 3/81 1/83/81 1/83/8
Insulation is necessary to prevent condensation from forming and dropping from the suction line. Armflex (or satisfactory equivalent) with 3/8” min. wall thickness is recommended. In severe conditions (hot, high humidity areas) 1/2” insulation may be required. Insulation must be installed in a manner which protects tubing from damage and contamination.
Where possible, drain as much residual compressor oil from ex­isting systems, lines, and traps; pay close attention to low areas where oil may collect. NOTE: If changing refrigerant types, ensure the indoor coil and metering device is compatible with the type of refrigerant being used; otherwise, the indoor coil must be replaced.
Burying Refrigerant Lines
If burying refrigerant lines can not be avoided, use the following checklist.
1. Insulate liquid and suction lines separately.
2. Enclose all underground portions of the refrigerant lines in waterproof material (conduit or pipe) sealing the ends where tubing enters/exits the enclosure.
3. If the lines must pass under or through a concrete slab, ensure lines are adequately protected and sealed.
3
Refrigerant Line Connections
IMPORTANT
To avoid overheating the service valve, TXV valve, or filter drier while brazing, wrap the component with a wet rag, or use a thermal heat trap compound. Be sure to follow the manufacturer’s instruction when using the heat trap compound. Note: Remove Schrader valves from service valves before brazing tubes to the valves. Use a brazing alloy of 2% minimum silver content. Do not use flux.
Torch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed. Note: The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit.
1. The ends of the refrigerant lines must be cut square, de­burred, cleaned, and be round and free from nicks or dents. Any other condition increases the chance of a refrigerant leak.
2. “Sweep” the refrigerant line with nitrogen or inert gas dur­ing brazing to prevent the formation of copper-oxide inside the refrigerant lines. The POE oils used in R-410A applica­tions will clean any copper-oxide present from the inside of the refrigerant lines and spread it throughout the system. This may cause a blockage or failure of the metering device.
3. After brazing, quench the joints with water or a wet cloth to prevent overheating of the service valve.
4. Ensure the filter drier paint finish is intact after brazing. If the paint of the steel filter drier has been burned or chipped, repaint or treat with a rust preventative. This is especially important on suction line filter driers which are continually wet when the unit is operating.
NOTE: Be careful not to kink or dent refrigerant lines. Kinked or dented lines will cause poor performance or compressor damage.
Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing.
Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure then apply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to sys­tem evacuation.
System Evacuation
Condensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with the valve stems closed and caps installed. Do not open valves until the
system is evacuated.
NOTE: Scroll compressors should never be used to evacuate or
pump down a heat pump or air conditioning system.
CAUTION
Prolonged operation at suction pressures less than 20 psig for more tha n 5 seconds will result in overheat ing of the scrolls and permanent damage to the scroll tips, drive bearings and internal seal.
1. Connect the vacuum pump with 250 micron capability to the service valves.
2. Evacuate the system to 250 microns or less using suction and liquid service valves. Using both valves is necessary as some compressors create a mechanical seal separating the sides of the system.
3. Close pump valve and hold vacuum for 10 minutes. Typi­cally pressure will rise during this period.
NOTE: Before brazing, verify indoor piston size by checking the piston kit chart packaged with indoor unit.
Leak Testing (Nitrogen or Nitrogen-Traced)
To avoid the risk of fire or e xplosion, never use oxygen, high pressure air or flammable gases f o r l ea k testing of a refriger ation system.
4
Loading...
+ 8 hidden pages