Daikin ARYN-L, ATYN-L User manual

INSTALLATION MANUAL
WALL MOUNTED R410A SPLIT TYPE AIR CONDITIONER
MODELS
ATYN20LV1 ARYN20LV1 ATYN25LV1 ARYN25LV1 ATYN35LV1 ARYN35LV1 ATYN50LV1 ARYN50LV1 ATYN60LV1 ARYN60LV1
Installation Manual
R410A Split Type Air Conditioner
Руководство по установке
R410A разделить Кондиционер
воздуха типа
English
Русский
IM-5WMJR-0515(0)-DAIKIN SIESTA
Indoor Unit [ATYN]
OUTLINE AND DIMENSIONS
THE MARK SHOWS PIPING DIRECTION
A
LEFT
B
BOTTOM
REAR REAR
TOP VIEW
LOUVER
FRONT GRILLE FIXED SCREWS (INSIDE)
BOTTOM
FRONT VIEW
RIGHT
SIGNAL RECEIVER
INDOOR UNIT ON/OFF SWITCH
ROOM TEMPERATURE THERMISTOR (INSIDE)
B
C
SIDE VIEW
English
Original Instruction
NAME PLATE
TERMINAL BLOCK WITH EARTH TERMINAL
NOTE: PLEASE BASED ON ACTUAL INSTALLATION PLATE DESIGN IN THE UNIT FOR INSTALLATION PLATE
20/25/35J DIMENSION REFERENCE AT PAGE 1&2.
«
Recommended mounting plate retention spots
(5 spots in all)
D
F
B
G
H
J
L
Liquid pipe end
M
Use tape measure as shown. Position the end of a tape measure at
A
Gas pipe end
Ñ
E
F
Through the wall hole Ø 65mm
G
K
I
Drain hose position
INSTALLATION PLATE 20/25/35J
Dimension
Model
ABCDE FGHI J KLM
20/25/35J 800 288 206 166 184 42 46 55 56 154 182 263 52
All dimensions are in mm
1-1
« Recommended mounting plate retention spots
(5 spots in all)
D
E
F
Through the wall hole Ø 65mm
G
Drain hose position
IK
Model
F
B
G
Dimension
JH
ML
Liquid pipe end
ALTERNATIVE INSTALLATION PLATE 20/25/35J
A
Gas pipe end
ABCDE FGHI J KLM
20/25/35J 800 288 206 104 141 30 46 55 56 153 181 207 52
«
Recommended mounting plate retention spots
(7 spots in all)
E
F
Through the wall hole Ø 65mm
G
K
I
Drain hose position
B
Model
F
G
Dimension
D
H
J
Liquid pipe end Gas pipe end
L
M
A
INSTALLATION PLATE 50/60J
ABCDE FGHI J KLM
50/60J 1065 310 224 190 173 61 40 45 48 91 219 580 45
1-2
All dimensions are in mm
Outdoor Unit [ARYN]
KLL
N
All dimensions are in mm
English
M
C
T
A
O
PQ
B
D
N
FE
SR
C
GH
I
J
Mode
Dimension
l
ABCDE FGHI J KLMN
20C 600 475 245 418 177 35 93 81 83 55 398 101 97 17 25/35C 700 521 250 485 175 36 95 93 86 68 441 130 111 15
Mode
Dimension
l
OPQRST
20C 22 3 19658030 25/35C 18 3 19658030
Outdoor Unit [ARYN]
KLL
N
M
Q
A
O
B
D
N
F
E
All dimensions are in mm
C
H
G
S R
IJ
Model
Dimension
P
ABCDE FGHI J KL
50C 855 628 328 520 179 46 93 149 101 113 603 126 60C 855 730 328 520 179 46 93 149 101 113 603 126
Model
Dimension
MNO P Q R S
50C 164 15 34 23 362 73 75 60C 164 15 34 23 362 73 75
1-3
INSTALLATION MANUAL
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirement. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons. This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
SAFETY PRECAUTIONS
! WARNING ! CAUTION
Installation and maintenance should be performed by
• qualified persons who are familiar with local code and regulation, and experienced with this type of appliance. All field wiring must be installed in accordance with the
• national wiring regulation. Ensure that the rated voltage of the unit corresponds to
• that of the name plate before commencing wiring work according to the wiring diagram. The unit must be GROUNDED to prevent possible
• hazard due to insulation failure. All electrical wiring must not touch the water piping or
• any moving parts of the fan motors. Confirm that the unit has been switched OFF before
• installing or servicing the unit. Risk of electric shock, can cause injury or death.
• Disconnect all remain electric power supplies before servicing. DO NOT pull out the power cord when the power is
• ON. This may cause serious electrical shocks which may result in the fire hazards. Keep the indoor and outdoor units, power cable and
• transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than 1m away}.
Please take note of the following important points when installing.
Do not install the unit where leakage of flammable gas
• may occur.
If gas leaks and accumulates around the unit, it may
cause fire ignition.
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it may
cause water leakage which will dampen the furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause
over-current or damage to the compressor.
Ensure that the unit’s panel is closed after service or
• installation.
Unsecured panels will cause the unit to operate
noisily.
Sharp edges and coil surfaces are potential locations which
• may cause injury hazards. Avoid from being in contact with these places. Before turning off the power supply set the remote controller’s
• ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start
turning automatically when power resumes, posing a hazard to service personnel or the user.
Do not install the units at or near doorway.
• Do not operate any heating apparatus too close to the air
• conditioner unit or use in room where mineral oil, oil vapour or oil steam exist, this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction. When the unit is used in kitchen, keep flour away from going
• into suction of the unit. This unit is not suitable for factory used where cutting oil mist
• or iron powder exist or voltage fluctuates greatly. Do not install the units at area like hot spring or oil refinery
• plant where sulphide gas exists. Ensure the color of wires of the outdoor unit and the terminal
• markings are same to the indoors respectively. IMPORTANT : DO NOT INSTALL OR USE THE AIR
• CONDITIONER UNIT IN A LAUNDRY ROOM. Don’t use joined and twisted wires for incoming power
• supply. The equipment is not intended for use in a potentially explosive
• atmosphere.
1-4
INSTALLATION DIAGRAM
Indoor unit
Front panel
50mm or more from walls (on both sides)
Air filter
Outdoor Unit
M4 x 12L
75mm or more from ceiling
Service lid
Opening service lid
¢
Service lid is opening/closing type.
Opening method
¢
1) Remove the service lid screws.
2) Pull out the service lid diagonally down in the direction of the arrow.
3) Pull down.
Caulk pipe hole gap with putty.
500mm from wall
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe’s cut line.
Wrap the insulation pipe with the finishing tape from bottom to top.
English
1-5
INSTALLATION OF THE OUTDOOR UNIT
The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or obstruction to the smooth air flow. Please follow the installation clearances shown in the figure. Select the coolest possible place where intake air temperature is not greater than the outside air temperature (please refer operating range).
Installation clearances
Dimension
ABCD
Minimum Distance, mm 300 1000 300 500
Note: If there is any obstacle higher than half, of the unit’s
height (H), please allow more space than the figure indicated in the above table.
Condensed Water Disposal Of Outdoor Unit (Heat Pump Unit Only)
There are 2 holes on the base of Outdoor Unit for condensed
• water to flow out. Insert the drain elbow to one of the holes. To install the drain elbow, first insert one portion of the
• hook to the base (portion A), then pull the drain elbow in the direction shown by the arrow while inserting the other portion to the base. After installation, check to ensure that the drain elbow clings to base firmly. If the unit is installed in a snowy and chilly area, condensed
• water may freeze in the base. In such case, please remove plug at the bottom of unit to smooth the drainage.
BASE
Obstacle
C
Obstacle
Return air
A
A
Return air
PLUG
DRAIN ELBOW
DRAIN ELBOW
B
H
Discharge air
H/2
Obstacle
D
Obstacle
Service access
1-6
Please remove side plate when connecting the piping and connecting cord
PUSH & PULL UP
INSTALLATION OF THE INDOOR UNIT
The indoor unit must be installed in such a way so as to prevent short circuit of the cool discharged air with the hot return air. Please follow the installation clearance shown in the figure. Do not place the indoor unit where there could be direct sunlight shining on it. Also, this location must be suitable for piping and drainage, and be away from doors or windows.
Return Air
Air flow (Indoor)
min. 75
(Space for
performance)
min. 50
(Space for maintenance)
Required space
min. 50
(Space for maintenance)
All dimensions are in mm
The refrigerant piping can be routed to the unit in a number of ways (left or right from the back of the unit), by using the cut-out holes on the casing of the unit (see figure). Bend the pipes carefully to the required position in order to align it with the holes. For the side and bottom out, hold the bottom of the piping and then position it to the required direction (see figure). The condensation drain hose can be taped to the pipes.
Right-Side, Right-Back or Right-Bottom Piping
Right-side piping
Remove pipe port cover here for right-side piping
Remove pipe port cover here for right-bottom piping
Right-bottom piping
Right-back piping
Bind coolant pipe and drain hose together with insulating tape.
Left-Side, Left-Back or Left-Bottom Piping
Remove pipe port cover here for left-side piping
English
Mounting Installation Plate
Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars. Use the level gauge for horizontal mounting, fix it with 5 suitable screws for 20/25/35J and 7 suitable screws for 50/60J. In case the rear piping draws out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside wall (see figure).
Mounting plate
Left-side piping
Remove pipe port cover here for left-bottom piping
Left-bottom piping
20/25/35J (ALTERNATIVE INSTALLATION PLATE)
Mounting plate
Mounting plate fixing screw
50/60J20/25/35J
Mounting plate
Left-back piping
Mounting plate fi xing screw
Mounting plate fixing screw
1-7
Recommended Mounting Plate Retention Spots And Dimensions
20/25/35J
«
Recommended mounting plate retention spots (5 spots in all)
166
42.2
288
45.9
54.5 153.8
20/25/35J
30
288
263 51.9
(ALTERNATIVE INSTALLATION PLATE)
Recommended mounting plate retention spots
(5 spots in all)
104
Use tape measure as shown. Position the end of a tape measure at
184
800
Gas pipe endLiquid pipe end
181.7 55.5
All dimensions are in mm
141
42.2
Through the wall hole Ø 65mm
45.9
Drain hose position
30
Through the wall hole Ø 65mm
Ñ
Mount The Unit Onto The Installation Plate
Hook the indoor unit onto the upper portion of the installation plate (Engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate). Ensure that the hooks are properly seated on the installation plate by moving it to the left and right.
How To Attach The Indoor Unit
Hook the claws of the bottom frame to the mounting plate.
How To Remove The Indoor Unit
Push up the marked area (at the lower part of the front grille) to release the claws.
Mounting plate
Clip
Bottom frame
Front grille
Mark (rear side)
46
55
Liquid pipe end
153
52
207
800
Gas pipe end
50/60J
«
Recommended mounting plate retention spots (7 spots in all)
190 173
61
310
40
45
Liquid pipe end
91
580
45
1065
Gas pipe end
Hole With Cone Drill
Wall embedded pipe (Field supply)
Inside
46
Drain hose position
56181
All dimensions are in mm
61
Through the wall hole Ø 65mm
40
48
219
Drain hose position
All dimensions are in mm
Outside
Caulking
Hang indoor unit’s hook here.
When stripping the
Mounting plate
ends of interconnecting wires in advance, bind right ends of wires with insulating tape.
Interconnecting wires
Wire guide
Water Drainage Piping
The indoor drain pipe must be in a downward gradient for smooth drainage. Avoid situations that are likely to cause water to leak.
Water Drainage
Water Retention
Water
leaking
Wrong
End dipped into water
Drain
Correct
Water
leaking
Wrong
Water
leaking
Wrong
Wall hole cover (Field supply)
Ø 65
Wall embedded pipe (Field supply)
! CAUTION
• Do not install the unit at altitude over 2000m for both indoor and outdoor.
1-8
REFRIGERANT PIPING
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective. Always choose the shortest path and follow the recommendations as tabulated below:
Indoor unit
English
Outdoor Unit
LE
Heat Pump Model
Model
Min. Allowable Length (L), m 3 Max. Allowable Length (L), m 12 12 12 20 20 Max. Allowable Elevation (E), m 5 5 5 15 15 Gas Pipe Size, mm/(in) 9.52
Liquid Pipe Size, mm/(in) 6.35
*Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.
Indoor (ATYN) 20J 25J 35J 50J 60J Outdoor (ARYN) 20C 25C 35C 50C 60C
(3/8")
(1/4")
9.52
(3/8")
6.35
(1/4")
12.70 (1/2")
6.35
(1/4")
12.70 (1/2")
6.35
(1/4")
15.88 (5/8")
6.35
(1/4")
1-9
Equivalent length for various fitting (meter)
Pipe Size L joint
Trap bend
3/8" (OD9.52mm) 0.18 1.3 1/2" (OD12.7mm) 0.20 1.5 5/8" (OD15.9mm) 0.25 2 3/4" (OD19.1mm) 0.35 2.4 7/8" (OD22.2mm) 0.40 3 1" (OD25.4mm) 0.45 3.4 1 1/8" (OD28.6mm) 0.50 3.7 1 3/8" (OD34.9mm) 0.60 4.4
Notes:
1. Equivalent piping length is obtained with actual length of gas piping.
2. 90° bend of piping is equivalent to L joint.
Bending must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe where possible.
Piping Works And Flaring Technique
Do not use contaminated or damaged copper tubing. If
• any piping, evaporator or condenser had been exposed or had been opened for 15 seconds or more, the system must be vacuumed. Generally do not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubing and coils until it is ready to connect suction or liquid line into valves or fittings.
If any brazing work is required, ensure that nitrogen gas
• is passed through coil and joints while the brazing work is being done. This will eliminate soot formation on the inside wall of copper tubings.
Cut the pipe stages by stages, advancing the blade of pipe
• cutter slowly. Extra force and a deep cut will cause more distortion of pipe and therefore extra burr. See Figure I.
Remove burrs from cut edges of the pipes with remover. See
• Figure II. Hold the pipe on top position and burr remover at lower position to prevent metal chips from entering the pipe. This will avoid unevenness on the flare faces which will cause gas leak.
Insert the flare nuts, mounted on the connection parts
• of both the indoor unit and outdoor unit, into the copper pipes.
The exact length of pipe protruding from the top surface
• of the swaging block is determined by the flaring tool. See Figure III.
Fix the pipe firmly on the swaging block. Match the centers
• of both the swaging block and the flaring punch, then tighten the flaring punch fully.
Piping Connection To The Units
Align the center of the piping and tighten the flare nut
• sufficiently with fingers. See Figure IV.
Finally, tighten the flare nut with torque wrench until the
• wrench clicks.
When tightening the flare nut with the torque wrench, ensure that the tightening direction follows the arrow indicated on the wrench.
The refrigerant pipe connection are insulated by closed cell polyurethane.
Figure I
Figure II
Figure III
Cutting Copper Tube
1/4t
Remove Burr
Copper Tube
Swaging Block
Copper Tube
D
A
Ø Tube, D A (mm)
Inch mm Imperial
(Wing-nut Type)
Rigid
(Clutch Type)
1/4" 6.35 1.3 0.7 3/8" 9.52 1.6 1.0 1/2" 12.70 1.9 1.3 5/8" 15.88 2.2 1.7 3/4" 19.05 2.5 2.0
Figure IV
Flare Joint
Flared Tube
Flare NutIndoor Piping
Pipe Size (mm/in) Torque, Nm/(ft-lb)
6.35 (1/4") 18 (13.3)
9.52 (3/8") 42 (31.0)
12.70 (1/2") 55 (40.6)
15.88 (5/8") 65 (48.0)
19.05 (3/4") 78 (57.6)
1-10
Spanner
Torque Wrench
Loading...
+ 28 hidden pages