Daikin 4P414004-1D Installation manuals

Additional Instructions for equipment using R32 refrigerant
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: 675
R32
WARNING
• Do not use means to accelerate the defrosting process or to clean the equipment, other than those recommended by the manufacturer.
• The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without ignition sources in continuous
operation (for example: open ames, an operating gas appliance or an operating electric heater) and have a room size as specied in
this manual for installation.
• Joints made in the installation between parts of refrigerant system shall be accessible for maintenance purposes.
• Do not reuse joints which have been used once already.
• Make sure installation, servicing, maintenance and repair follow instruction from Daikin and on top comply with applicable legislation (for example national gas regulation) and are executed only by
qualied person.
• Do not pierce or burn.
• Be aware that the R32 refrigerant does not contain an odour.
INSTALLATION SPACE REQUIREMENTS
• Installation of pipework shall be kept to a minimum.
• Pipework shall be protected from physical damage and shall not be installed in an unventilated space, if the space is smaller than the
minimum size as dened in the table below.
• For installation inside a building (this applies to indoor units and
to outdoor units installed inside) a minimum oor area of the room may be required. This is specied in the graph on the right and the table below. The table contains rounded gures. For a more precise
determination, the values can be determined from the graph on the right side.
• For outdoor units installed inside (winter garden, garage, machinery
room etc.) take the determination for oor standing units. If the
outdoor unit is installed at a height of 1.8 meters or more above ground it is possible to use the determination of wall mounted units.
To determine the minimum oor area, the total refrigerant charge needs to be taken into account (total value, which is the sum of pre-charge and additional field charge ).
The minimum oor area [m height of 1.8m for wall-mounted units and 2.2m for ceiling-mounted units.
2
] is determined based on the installation
Installation manual
4P414004-1D
112 110 108 106 104 102 100
98 96 94 92 90 88 86 84 82 80 78 76 74 72 70
]
2
68 66 64 62 60 58 56 54 52 50 48
Minimum floor area [m
46 44 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10
8 6 4 2 0
1 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2 2,1 2,2 2,3 2,4 2,5 2,6 2,7 2,8 2,9 3 3,1 3,2 3,3 3,4 3,5 3,6
Installation requirements for R32 units
Floor standing
Wall mounted
Ceiling mounted
Mass of refrigerant [kg]
Minimum oor area for equipment installed inside
(applies to indoor units and outdoor units installed inside)
Ceiling-mounted units Wall-mounted units Floor-standing units
m(kg) A
(m2) m(kg) A
min
(m2) m(kg) A
min
1.224 Without restriction 1.224 Without restriction 1.224 Without restriction
1.225 0.96 1.225 1.43 1.225 12.88
1.3 1.08 1.3 1.61 1.3 14.50
1.4 1.25 1.4 1.87 1.4 16.82
1.5 1.44 1.5 2.15 1.5 19.31
1.6 1.63 1.6 2.44 1.6 21.97
1.7 1.84 1.7 2.76 1.7 24.80
1.8 2.07 1.8 3.09 1.8 27.80
1.9 2.30 1.9 3.44 1.9 30.98
2.0 2.55 2.0 3.81 2.0 34.32
2.1 2.81 2.1 4.20 2.1 37.84
2.2 3.09 2.2 4.61 2.2 41.53
2.3 3.38 2.3 5.04 2.3 45.39
2.4 3.68 2.4 5.49 2.4 49.42
2.5 3.99 2.5 5.96 2.5 53.63
2.6 4.31 2.6 6.44 2.6 58.00
2.7 4.65 2.7 6.95 2.7 62.55
2.8 5.00 2.8 7.47 2.8 67.27
2.9 5.37 2.9 8.02 2.9 72.16
3.0 5.74 3.0 8.58 3.0 77.22
3.1 6.13 3.1 9.16 3.1 82.46
3.2 6.54 3.2 9.76 3.2 87.86
3.3 6.95 3.3 10.38 3.3 93.44
3.4 7.38 3.4 11.02 3.4 99.19
3.5 7.82 3.5 11.68 3.5 105.11