1. SPECIFICATIONS
¡ DSB-070LH
MODEL
ITEM
FunctionCooling & Heating
ClassT
Power AC 220~ 240V/ 50Hz
Capacity W2,051/2,051
Btu/h 7,000/7,000
Dehumidificationl/h0.89
Running CurrentA3/3.2
Electrical
Data
Compressor
Power InputW676/693
Starting CurrentA18
TypeRotary
Model QB 134PL 12B
Capacitor25µF/400VAC
DSB-070LH
Indoor UnitOutdoor Unit
Fan
Motor
Refrigerant
(R-22)
Connection
Dimensions (W x H x D)mm750 x 245 x 174654 x 549 x 256
Net Weightkg7.034
TypeCross flow fanPropeller fan
Capacitor1.0µF 400VAC1.8µF 400V
Motor Model NumberIC-8417DWKF5AIC-9625DWLF5A
ControlCapillary
Charge Q'tyg900
TypeFlare
OD
(Liquid/Suction)
in(mm)1/4 (6.35)1/2 (12.7)
2
¡ DSB-091LH
MODEL
ITEM
FunctionCooling & Heating
ClassT
Power AC 220~240V/ 50Hz
Capacity W2,637/2,637
Btu/h 9,000/9,000
Dehumidificationl/h1.15
Running CurrentA4.0/4.2
Electrical
Data
Compressor
Power InputW910/940
Starting CurrentA24
TypeRotary
Model RBB100A001QK 185PN13B
Capacitor30µF / 450VAC35µF / 400VAC
DSB-091LH
Indoor UnitOutdoor Unit
Fan
Motor
Refrigerant
(R-22)
Connection
Dimensions (W x H x D)mm750 x 245 x 174654 x 549 x 256
Net Weightkg7.034
TypeCross flow fanPropeller fan
Capacitor1.0µF 400VAC1.8µF 400V
Motor Model NumberIC-8417DWKF5AIC-9630DWLF5A
ControlCapillary
Charge Q'tyg1,150
TypeFlare
OD
(Liquid/Suction)
in(mm)1/4 (6.35)1/2 (12.7)
3
¡ DSB-121LH
MODEL
ITEM
FunctionCooling & Heating
ClassT
Power AC 220~240V/ 50Hz
Capacity W3,654/3,946
Btu/h 12,500/13,500
Dehumidificationl/h1.6
Running CurrentA7.0/6.5
Electrical
Data
Compressor
Power InputW1,500/1,410
Starting CurrentA37
TypeRotary
Model RCB 150A001
Capacitor35µF/ 400VAC
DSB-121LH
DivisionIndoor UnitOutdoor Unit
Fan
Motor
Refrigerant
(R-22)
Connection
Dimensions (W x H x D)mm925 x 285 x 194
Net Weightkg9.734
TypeCross flow fanPropeller fan
Capacitor1.0µF 400VAC3.5µF 400VAC
Motor Model NumberIC-8428DWKG7CIC-9430DWLC5B
ControlCapillary
Charge Q'tyg1,060
TypeFlare
OD
(Liquid/Suction)
in(mm)1/4 (6.35)1/2 (12.7)
666 x 552 x 264(Before)
654 x 549 x 256(After)
4
750
Plate Mounting
REMOCON
Connecting Pipe
Grille Insert
174
245
REMOTE CONTROLLER
Frame Grille
Body
Plate Mounting
INDOOR UNIT
2. OUTLINE AND DIMENSIONS
1
¡ DSB-070LH/DSB-091LH
5
REMOCON
Filter - LFilter - R
Grille Insert
Frame Grille
Body
Plate Mounting
Connecting Pipe
Plate Mounting
406
194
285
925
REMOTE CONTROLLER
¡ DSB-121LH
6
256
549
654
Inlet
Inlet
Cabinet Side
Panel Top
Guide Support
Outlet
Foot Cushion
OUTDOOR UNIT
Outlet
Cabinet Front
Foot
Handle
7
Service Valve
¡ DSB-070LH/DSB-091LH/DSB-121LH(After)
Cabinet SideHandleCabinet FrontFoot
264
334
Panel Top
Cabinet Back
552
572
Inlet
AIR
Inlet
Outlet
Foot Cushion
Service Valve
666
¡ DSB-121LH(Before)
8
3. OPERATION
REMOTE CONTROLLER
PARTS OF NAME AND FUNCTION
¡ DSB-070LH/DSB-091LH
Indoor Unit
Electrostatic Filter
(option)
Deodorizing Filter
(option)
Air Inlet
Antibacterial
Filter
Fan Direction
(Up, Down)
Air Outlet
Lamp
Remote
Controller
Receiver
Power Plug
Remote Controller
9
¡ DSB-121LH
Power Plug
Electrostatic FilterDeodorizing FilterAir Inlet
Antibacterial
Filter
Air OutletFan Direction
(Up, Down)
Remote Controller
Remote
Controller
Receiver
Lamp
REMOTE CONTROLLER
Indoor Unit
10
¡ DSB-070LH/DSB-091LH
Timer (Yellow)
Lights during the time
reservation mode.
Quick (Red)
ON (Red)
Lights when the
operation is going on.
Air clean (Green)
EMR. REMOCON
Indoor Unit DisplaySwitch Panel
■
Remote Control Signal Receiver
This place is the part to receive the signal if it
receive the signal, you can hear the signal “beep.
“beep. beep .”
■
There is a switch panel at inside of Front
Panel. At the time of operating, open the
Front Panel.
Emergency switch can be used when the remote
controller is lost or Testing.
Remote switch is usually used by remote
controller.
11
EMERGENCYREMOTE
ONAIR CLEANQUICKTIMER
¡ DSB-121LH
Indoor Unit DisplaySwitch P anel
Remote Control Signal Receiver
This place is the part to receive the signal if it
receive the signal, you can hear the signal
"beep, beep".
§ There is a switch panel at inside of Front
Panel. At the time of operating, open the
Front Panel.
Emergency switch can be used when the remote
controller is lost or testing.
ON (Red)
Lights when the
operation is
going on.
Timer (Y ello w)
Lights during the time
reservation mode.
Remote switch is usally used by Remote
Controller.
Air clean (Green)
Quick(Red)
12
¡ DSB-070LH/DSB-091LH/DSB-121LH(After)
Outdoor Unit
Air Inlet (Side Back)
Connection Wire
Air Outlet
Connecting Pipe
Drain Hose
13
AIR
Air Inlet (side Back)
Air Outlet
Connection
Wire
Connecting
Pipe
Drain Hose
¡ DSB-121LH(Before)
Outdoor Unit
NOTE:
How to remove Top Panel
1. Loosen the screw at left and right side.
2. Push the three parts op Front and Back sides like figure orderly.
3. Unhook the locking parts of T op Panel.
The front locking parts
FRONT SIDEBACK SIDE
The back locking parts
14
REMOTE CONTROLLER
MODE
SLEEP
ON/OFF
TIMER
ENTER/
CANCEL
FAN SPEED
TURBO/MILD
Display
Displays information
pertaining to unit.
TURBO/MILD
Press to be colder the unit.
TIMER ENTER/CANCEL Button
Press to enter a timer setting or
to cancel timer setting
TIMER ON/OFF Button
Press to set the unit of or on time.
(0.5, 1, 1.5, 2, 2.5, 3, 4, 5, 6, 8,
10, 12, 16, 20, 24hr)
MODE Button
Press to cycle through the modes
(Auto/Quick/Cooling/Fan/Dry)
SLEEP Button
Press to set the unit for
the sleep mode.
FAN DIR.
FAN DIR. Button
Press to select up/down
direction for fan.
ON/OFF Button
Press to turn the unit
on or off.
TEMPERATURE Buttons
Press to raise or lower
the desired temperature.
FAN SPEED Button
Press to select the fan speed
(High " ", Middle " ",
Low " ").
COVER
Slide down to access most
of the remote buttons.
Slide down further to
access the battery
compartment.
Lights to indicate the
speeds simulating a loreeze.
FAN Indicators
Lights to indicate
the fan speed.
AUTO
¡ DSB-070LH/DSB-091LH/DSB-121LH
Replacing Batteries
Open the cover after
pressing the arrow
1
direction and pulling out.
Put the drycell by §]§^
direction.
2
16
3
Close the cover after
pushing into arrow
direction.
DESCRIPTION OF FUNCTIONS
Unit ON
Unit OFF
SET Time
HOUR
ON
OFF
Unit ON
Unit OFF
SET Time
HOUR
ON
OFF
COMP (ON)
*RT: ROOM TEMPERATURE
DT: DESIRED TEMPERATURE
COMP (OFF)
-1°C0°C
(COOLING)
(RT-DT)
COMP (OFF)
COMP (ON)
-1°C0°C
HEATING
(RT-DT)
OFF-Timer
If you set time in OFF-Timer Mode, the unit will stop at the set time.
ON-Timer
If you set time in ON-Timer Mode, the unit will run at the set time.
Control of Room Temperature
(1) Range of setting temperature: 18~32°C
(2) Setting temperature: Operating temperature of compressor
(3) During the time of test operating, Fan (Indoor , Outdoor) and Compressor is running regardless of room
temperature.
Buzzer
If the Indoor Unit Display receive the signal of Remote Controller , y ou can hear the signal "beep –" or "beep,
beep".
(1) In the case of receiving ON/OFF signal-"beep" "beep"
(2) And so on-"beep"
17
Fan Speed (Indoor Unit)
0°C
L
M
H
1°C2°C
(R.T-D.T)
(D.T)
L
M
H
012345°C(DT-RT)
(1) Motor speed (Super high speed, high speed, normal speed, low speed, ultra low speed).
(2) Remote controller setting fan speed. (Auto , L, M, H, Natural)
(3) Relation of operating mode between fan speed. (legned: X-no relation)
FAN ONLYCOOL
HHHLHH H
MMMLMH M
L LLLLH L
AutoAutoAutoLAutoHAuto
NaturalNaturalNaturalLNaturalHNatural
DEHUMI-
DIFICATION
AUTO QUICKHEAT
(4) Automatic Operation
If the unit is set in 'AUT O' mode , the unit operates automatically according to the room temperature to keep the
room temperature comfortable.
(COOLING)
(HEATING)
18
Sleep Mode
00.51.0HOUR
(COOLING CYCLE)
DT
+0.5°C
+0.5°C
+0.5°C
00.51.0HOUR
(HEATING CYCLE)
DT
–0.5°C
–0.5°C
–0.5°C
0°C7°C
Compressor and
Outdoor Fan
OFF
OFF
ON
Set Speed
Indoor Fan
(1) When you are going to sleep , select sleep s witch and the unit controls the room to the desired temper ature.
(The unit will not operate after 4 hour)
(2) For changing the temperature.
(3) To cancel sleep mode, press the SLEEP button again or press the MODE button once.: the SLEEP
indicator will disappear in the display.
Emergency Operation
(1) When the remote controller is lost, damaged or the battery is discharged, the Emergency operation can be
used to run the unit.
(2) The setting conditions of Emergency operation are as follows.
• Operation mode: AUTO
• Preset temperature: 26°C
• Fan speed: LO W
¡You cannot operate with remote controller.
Frost Prevention of Indoor Unit
When the unit operates at low ambient temperature, frost may appear on the Ev aporator. When the indoor coil
temperature is lower than 0°C at the end of 10 minutes of continuous compressor operation from the start, the
microcomputer of the unit stops the compressor to protect the unit from the frost. The control procedure for
indoor coil freeze protection.
1) The compressor and outdoor fan turn off.
2) Indoor fan operates according to user set speed.
3) The normal operation returns when the indoor coil
temperature is higher than 7°C or equal to 7°C.
(Indoor coil temperature)
19
3 min. Time Delay of Compressor
In normal operation, there is a time delay of three minutes between turn off and turning back on including initial
power up.
5 Seconds Time Delay of Indoor Fan Motor
Wnen the speed of indoor fan motor changes, there is a time dela y of 5 seconds at each speed step.
Auto Mode (I)
(1) In Auto Mode (I)
After the indoor fan is operated f or 20 seconds in the Auto Mode (I), the unit will operate automatically b y
selecting operating Mode according to the room temperature
(RT: Room temperature)
ROOM TEMPERATURE
28°C §ZRT
22°C < RT < 28°C
RT §Z22°C
(2) Selecting Operating Mode Again
Room temperature meets desired temperature and the compressor stops running over 30 minutes, then the unit
selects operating Mode again.
OPERA TING MODE
Cooling
Dehumidifier
Heating
FLAP POSITION
Cooling Position
Cooling Position
Heating Position
20
Dehumidification Mode
-1
OFF
ON
(Room temperature-18˚C)
01
-1
OFF
ON
(Room temperature-32˚C)
01
!Desired temperature < Room temperature
Outdoor Fan, Compressor : ON
Indoor Fan : Low speed
@ Desired temperature ¡ˆRoom temperature
Compressor : 3 min/ON, 5 min/OFF
Indoor Fan : 3 min 30 second/ON, 4 min 30 second/OFF
Fan Speed : low speed
# Room temperature ¡´18°C
Compressor : OFF
Indoor Fan : 1 min/ON, 7 min/OFF
Fan speed : Low speed
Air Discharge Direction(only remocon operation)
The air discharge direction procedure is below.
Fixed Up/DownFixed
Up/Down
Quick Mode(Powerful Cooling & Heating)
1) Cooling Mode
ƒƒNN
When the room temperature is higher than 22°C
!F an Speed: Super high speed
@ Air discharge direction: Fixed
# Set temperature: 18°C (Fixed)
$ Compressor and Outdoor F an
The air discharge direction procedure is below
Fixed Up/Down
Up/Down Fixed
ƒƒRR
The option is LEFT/RIGHT direction.
1) Heating Mode
ƒƒNN
When the room temperature is higher than 22°C
!F an Speed: Super high speed
@ Air discharge direction: Fixed
# Set temperature: 18°C (Fixed)
$ Compressor and Outdoor F an
The air discharge direction procedure is below
ƒƒRR
The option is LEFT/RIGHT direction.
COOLING POSITION
HEATING POSITION
Fixed Up/Down
Up/Down Fixed
21
Self-Diagnostic Function
The control will contain diagnostic test to verify the integrity of the system.
(1)Error Code Display P attern
!ON LAMP: ON (Red) LED ON/OFF
@ Error Code
# Only Emergency mode
ERROR CODE
3
DISPLAY PATTERNERROR CONTENTS
8 seconds
0.5 second
Compressor, Electrical parts of
comp. Gas leak
22
4. WIRING DIAGRAM
OUTDOOR UNITINDOOR UNIT
FAN MOTOR
BRN
BLUE
BROWN
BLUE
BLU
BLKBLKBLK
WHT
BLU
COMP
BLU
BRN
BRN
YEL/GRN
YEL/GRN
BROWN
YELLOW/GREEN
BRN
BRN
BLU
POWER CORD
BLK
YEL/GRN
CAPACITOR
OUTDOOR
TERMINAL
BLOCK
INDOOR
TERMINAL
BLOCK
YEL
RED
S
C
R
COMPRESSOR
FAN
HERM
C
O/D FAN
4WAY
1
1
1
1
BLK
BLK
RED
RED
BLU
ORG
RED
BLK
RED
PINK
BLU
ORG
YEL
YEL
WHT
BLK
BRN
RED
YEL
GRN
BLU
GRY
BLK
BLK
BLK
BLK
BLK
BLK
2
TRANSFORMER
1123456781 21 234
INDOOR
SENSOR
OUTDOOR
SENSOR
LED PCB
2
123
S
C
R
FAN MOTOR
FAN MOTOR
CAPACITOR
SWING
MOTOR
12
12345
Y
2
1
L
Y
2
1
L
1
2
3
4WAY
¡ DSB-070LH/DSB-091LH/DSB-121H
23
MAIN ELECTRIC PARTS
1
¡ DSB-070LH
Fan Motor3108003800IC-8417DWKF5A1
Indoor
Unit
Outdoor
Unit
Fan Motor Capacitor31069003001.0µF 400VAC1
Fuse5FVLB3152L250V 3.15A1
Transformer5EPV050120230V 50Hz1
Stepping Motor3108003900GSP-24SW-0611
Terminal Block3108912301SN-DBW-05P1
Compressor3107101200QB134PL12B1
Fan Motor3108004000IC-9625DWLF5A1
Dual Capacitor31095012011.8+25µF 400VAC1
Terminal Block3108912301SN-DBW-05P1
¡ DSB-091LH
Fan Motor3108003800IC-8417DWKF5A1
Indoor
Unit
Outdoor
Unit
Fan Motor Capacitor31069003001.0uF 400VAC1
Fuse5FVLB3152L250V 3.15A1
Transformer5EPV050120230V 50Hz1
Stepping Motor3108003900GSP-24SW-0611
Terminal Block3108912301SN-DBW-05P1
Fan Motor Capacitor31069003001.0uF 400VAC1
Fuse5FVLB3152L250V 3.15A1
Transformer5EPV050100220V/18V1
Stepping Motor3108000100MP28GA (L=400mm)1
Terminal Block3108912301SN-DBW-05P1
Compressor3100030CE0RCB150A0011
Fan Motor3108000800IC-9430DWLC5A1
Dual Capacitor31095007003.5+25µF 400VAC1
Terminal Block3108912301SN-DBW-05P1
Reversing Valve3105401000VH7-A TYPE1
Solenoid coil1
PART NAMEPART CODESPEC.QUANTITYREMARK
24
5. REFRIGERANT CYCLE
Note) If the pipe length exceeds the standard length, add 30g of refrigerant per extra meter .
Contents
Model Name
Capillary T ube
Charge Quantity
Cool
Heat
DSB-070LH
IDØ1.78 x ODØ3.2 x 500L
IDØ1.78 x ODØ3.2 x 700L
900 g
25
DSB-091LH
IDØ1.8 x ODØ3.2 x 800L
IDØ1.78 x ODØ3.2 x 1,000L
1,150 g
DSB-121LH
IDØ1.8 x ODØ3.2 x 500L
IDØ1.8 x ODØ3.2 x 900L
1,060 g
6. CONTROL BLOCK DIAGRAM
Relay RL1
Indoor fan
motor
Compressor
Relay RL2
Outdoor
fan motor
Relay RL3
4 way
valve
TRIAC
DC12V
Operating Mode
Fan Speed
Timer Selection
Flap Position
Unit on lamp
Room air temp.
Indoor coil temp.
Outdoor coil
temp
Air clean lamp
Quick lamp
Remote
Emergency
Operation
Signal
receiver
Timer lamp
A/D converterlnitialization
Clock generation
DC power supply
Circuit for
relay driving
Circuit for
TRIAC control
Transformer
Circuit for signal receiver
MICRO
CONTROLLER
Beeper
circuit for
motor driving
Stepping
motor
Temp. Setting
ON/OFF
SLEEP
REMOCON
AC220V
50Hz
STEPPING MOTOR
ON/OFF
COMPRESSOR
ON/OFF
DC5V
¡ DSB-070LH/DSB-091LH/DSB-121LH
26
7. ELECTRIC CIRCUIT DIAGRAM
ELECTRIC CIRCUIT DIAGRAM
1
¡ DSB-070LH/DSB-091LH/DSB-121LH
27
Description
1. After the power ON/OFF button is pressed once, the rela y and triac are turned ON or OFF per the remote
control setpoint.
– TRIAC is controlled per the fan speed selection.
– RELAY is controlled per the operation mode selection.
2. If the power ON/OFF button is pressed once more, the rela y and triac are turn off and the unit stops
operation.
3. The unit turns on or off according to the temperature set point by sensing the room air temperature through
thermistor.
4. If the fan speed selection is set to the auto position, the fan speed is automatically controlled according to the
temperature differance between room temperature and temperature set point.
5. If you press the ON/OFF button during operating the unit, Relay and LED is OFF and the unit is OFF.
28
8. TROUBLE SHOOTING
Outdoor unit does
not run?(note. 1)
Does
the compressor run
normally?
Indoor unit does
not run(note 1)
Check the failure
code according to
the self diagnostic
(note 2)
Is the unit
display
mormal?
check the failure
code according to
the self-diagonostic
(note 2)
Normal
check the
connecting
point of
magnetic
contactor
YES
YES
YES
YES
NO
NO
YES
Trouble
Is the power
applied to the
unit
Is the
power normal?
check the voltage between
L & N of terminal
block
press the power ON/OFF
button on remote controller
Does the
beeper beep two
times?
Is the display
all off?
• Check the connector on display
PCB connected to control PCB
• Check the display PCB itself
Check power supply mains
or interconnection wires
Check the wiring of indoor
Is the
switch position
on switch pannel at
"Remote"
Does
control PCB
status LED repeat one
second "on and
off"?
• control PCB fault
• Micom or reset
IC fault
• Check the remote signal receiver
• Check the connection between signal
receiver and control PCB
Place the switch
position to the
"Remote" and then
Check it once
more
YES
NO
YES
NO
NO
NO
NO
YES
YES
YES
YES
YES
NO
NO
NO
Is the
unit display
normal?
29
Note 1)
! Neither indoor unit nor outdoor unit runs.
Check the following points first. (There are f ollo wing case in normal operation)
a. Is the timer mode set the "timer ON".
b. Is the timer mode set the "timer-OFF" and the time had passed?
@ Neither outdoor fan nor compressor runs while indoor fan runs.
Check following points first. (There are f ollo wing cases in normal operation)
a. Is the temperature set point suitable?
b. Has the 3 minutes time guard f or compressor operated?
Self-Diagnostic Function
• Error Code •
! When the compressor do not run.
i) Check the voltage between and of terminal block.
(Indoor Unit, Outdoor Unit)
ii) Check connecting wire of indoor unit and outdoor unit.
iii)Check relay RL1 on power P.C.B
@ Check fixing of indoor coil thermistor.
# Check the GAS LEAKAGE of the pipe.
L
Y
30
Neither Indoor Unit nor Outdoor Unit Runs
Confirm following statement.
When the unit operate normally , Sometimes the outdoor unit and indoor unit cannot operate.
! Chec k the function select switch. Is it timer mode?
@ The function select switch locate the sleep mode and is the setting time over?
# Is the setting mode DEHUMIDIFIER mode?
$ When the unit is DEHUMIDIFIER mode while in the auto mode, the outdoor unit and indoor unit does
not run.
The power is applied to the unit
Check the voltge between and
Y
of terminal block
Rating voltage more than 90%
Check the indoor unit display
is the display all off?
Yes
Press the ON/OFF switch of
Remote Control
Is the indoor unit display all off?
Pull out the power plug
and then insert the power plug
after 5 second
L
Rating voltage
under 90%
NoNo
No
Check the
Breaker or Fuse
Self Diagnostic
function is ON
Yes
Check according to
self Diagnostic function
Control P.C.B defect
Control P.C.B is normal
Recheck from the beginning
31
Outdoor Unit Runs but Indoor Fan Do Not Run
Check rotation of indoor fan
Rotate indoor fan by hand
YES
Check input Voltage of Fan
Motor connector at power P.C.B
Rating V oltage more than 90%
Check the winding resistance of
Indoor unit fan motor
Normal
Check the fan motor capacitor
NO
Rating voltage
under 90%
Open or short
Check the F an Motor
bearing and fan
Check the power P.C.B.
The circuit for triac control
Change of fan motor
Check the connecting wire of
indoor fan motor
Run again
Check the starting of indoor fan motor
Run again
No
Normal
32
Outdoor Fan and Compressor Do Not
Confirm following statement.
When the unit operate normally , Sometimes the outdoor unit and indoor unit cannot operate.
! Is the setting temperature proper?
@ Is the unit during 3min. Time delay of compressor.
# During frost prevention of lndoor unit.
$ During dehumidifier mode.
! TEMPERATURE SENSING
@ STEPPING MOTOR DRIVING
# TRIAC DRIVING FOR DIF
$ BUZZER DRIVING
%
COMPRESSOR RELAY
DRIVING
^ AC POWER SUPPLY
& POWER LINE FREQENCY
MONITORING INPUT
* DC POWER SUPPLY
( LED DRIVING
) SELECT SWITCH INPUT
1 RESET CIRCUIT
2 CLOCK GENERA TION
3 MODE OPTION
6
Power Supply(1)
AC 220V
CL1
275V
104K
VAR
FUSE1
3.15A
POWER TRANS
D2
CC1CE1
D3
D1
D4
104
+
35V
1000µF
IC2
7812
VI VO
G
IC3
7805
VI VO
G
+
25V
470µF
CC2CC3CE3CE2
104
+
16V
100µF
104
12V5V
19
OSC
CC13
104
5V
8M
20
VDD-10%
VSS+10%
DESCRIPTION
DC Po wer Supply in circuit needs +12V and +5V. +12V is used for Compressor Driving Rela y, Triac Driving
Photo Triac, Buzzer Driving Swing, Sweep Motor. A C v oltage of secondary Po wer Transformer is rectified by
Bridge Diode, and it is filtering by Main Condensor CE1.
Filtered DC voltage is about +18V, is regulated +12V DC by Regulator IC7812.
And it is regulated +5V DC by Regulator IC7805.
V AR is serge filter and CC1, CC2, CC3 is Noise filter .
Oscillator(2)
DESCRIPTION
Oscillatory Frequency drive Micom, it is made up 8MHz resonator oscillatory Freqency.
Ocillatory wave is as follo wing Fig 2-1.
37
Fig 2-1
Sensor(3)
Room
PT-K43C
EVA
PT-K43C
5267-04A
CN10
5V
1
2
3
4
R10
12.7K
330
CC6
103
R6
330
R7
R11
12.7K
CC5
10
24
25
MICOM
Room temperature and Evaporator temperature Sensor Input
DESCRIPTION
Number 24, 25 of Micom is Terminal of A/D convertor Input.
Room temperature and Evaporator temperature is sensing by change of Thermister Resistance, Micom is put
in 5V by ratio between R10 (12.7KΩ) and R11 (12.7KΩ).
Relation between temperature and voltage is follo wing Table 3-1.
CC5, 6 is Noise filter.
Temperature
(°C)
-51.1271.127
0 1.3781.378
5 1.6501.650
10 1.9361.936
152.2282.228
Table 3-1
Voltage (V)
No. 1No. 3
38
T riac Driving(4)
N
L
AC 220V
TO MOTOR
T1
SM3JZ47
L1
12
130µH
3A
SN1
0.1µF
120Ohm
TLP561
PT1
12V
R5
1K
1/2W
IC4
KID 65004
MICOM
38
215
AC220V
TRIGGER
MOTOR
INPUT
LOW SPEEDMEDIUM SPEEDHIGH SPEED
DESCRIPTION
Number 38 Terminal of Micom is put out Pulse Output, by way of Buffer it is driving Photo Triac is supplied
Trigger Signal.
Trigger Test of Triac is detected Zero Cross Part of AC input and it is triggered from Zero Cross part to Time
delay part according to Fan Speed. (Ref. Fig 4-1) SN1 is Snub ber .
LOW SPEED
MEDIUM SPEED
Fig 4-1
39
HIGH SPEED
LEADER CODE
CUSTOM
CODE
DATA
CODE
CHECK
SUM
TAILER
9ms4.5ms16bit16bit24bit8bit
Remote Controller(5)
0.56ms0.56ms1.69ms
1.12ms2.25ms
bit 0bit 1
MICOM
13
R14
1K
RA1
5V
CA1
F4104Z
P2
MODE
SELECT
PUSH S/W
DESCRIPTION
Signal from Remote Controller put in only Control Data Signal at Micom Terminal of Number 33, which is gotten
fid of Carrier (38KHz) from Receive Module. Signal Wa v e repeat third as follo wing Fig 5-1.
But in Secondary Wave Custom Code is Re v ersed F ace .
Fig 5-1
Selecting Mode(6)
(SELECT S/W INPUT, OUTPUT)
Fig 5-2
BIT STRUCTURE
DESCRIPTION
There are Mode according to SW position as
following Table 6-1.
According as port of fixed Micom is Low, the unit is
operating as following Table 6-1.
40
POSITION MODE
OPENREMOCON
GN DEMERGENCY
Table 6-1
Micom Power Supply(7)
VDD 42
CE5
10µF
16V
CC11
104
CC13
104
+
5V
41
40
39
22
21
19
OSC
8MHz
20
VSS
MICOM
DESCRIPTION
MICOM Po wer is supplied 5V at Number 42 using VDD, Number 19, 20 Vsing Oscillator, CC13 is noise filter.
41
Reset(8)
MICOM
18
CC9
103
R12
1K
+
CE4
4.7µF
50V
IC5
7042P
R13
5.6K
5V
4.25V
H
L
t
t
POWER
ON
Vcc (+5V)
DELAY TIME
FOR POWER ON
RESET
DESCRIPTION
V oltage less than about 0.8V put in Micom Terminal of Number 18 and then Micom reset. Reset IC detect
Po wer ON and Voltage less than 4.25V, and then send Reset Signal.
42
VCC
12V
KID 65004
MICOM
34
611
R4
1K
BZ1
JS5
5V
CA1
F4104Z
1K R17
1K R16
14
15
16
30
29
28
27
1K R15
1K R26
R29
5V
test
mild/high
JS3
50/60hz
JS4
heat/cool
1K R25
1K R24
1K R23
CA1
F4104Z
MICOM
COMP ERR
JS1
RA1
5A 103J
RA1
5A 103J
JS2
Function Selecting(9)
DESCRIPTION
Selecting function is as following table 9-1.
ƒRWhen power source is put at fist, Funtion selection input is recognized.
And when the unit is running the microcomputer ignore variation of funtion selection input.
SHORTOPEN
JS6SKIPDETECT
JS4HEATCOOL
JS350Hz60Hz
JS1JS2
070SHORTSHORT
091OPENOPEN
121SHORTOPEN
Buzzer Driving(10)
DESCRIPTION
Micom 34 Terminal put out Buzzer Driving Pulse,
its output is driving Buzzer through Buffer .
Ocillatory Frequency of buzzer is selected by
internal Micom.
This unit is setting at 4KHz.
43
MICOM
TRANS
OUTPUT
D5
D6
R2
5.6K
12
CC4
103
TR1
KRC120M
12 1
23
21
R3
10K
R27
1K
VCC
31
DETECT POINT
H
The
Number
31 of
Micom
terminal
AC18V
L
Zero Crossing Detect(11)
DESCRIPTION
It defect Zero Cross part of Trans output voltage, Transistor TR1 is used to put in the Micom.
Detail Driving is as following Fig 11-1.
R19 is Resistance to limit current.
Fig 11-1
44
Ø 4
Ø 3
Ø 2
Ø 1
B
+
6
5
4
3
2
1
12V
IC6
KID65004
CN13
1
MICOM
2
3
4
M1
FOR SWING
Stepping Motor Driving(12)
DESCRIPTION
There are one Stepping Motor for Flap (up and down) and it is used 4 face Drive Method.
It is driving as following Fig 12-1. (Ring Count Method of 8 Status)
Ø 4
Ø 3
Ø 2
Ø 1
(Normal Rotating)(Reversed Rotating)
Fig 12-1
45
REMOTE CONTROLLER ASSMBLY FUNCTIONAL TEST METHOD
2
TEST START
Po wer Supply
Select ON/OFF button
Is Display at the
beginning ON?
Select Mode button
Is it normal?
Select F AN SPEEDbutton
No
No
No
Po wer supply again
Is Display at the
beginning ON?
Yes
ERROR
No
Check the Follo wing
BATTERY SPRING
MICOM
PCB
LCD
Is it normal?
Select F AN DIR. b utton
Is it normal?
Is display at the
begining ON?
Select TEMP. Button (¡ª,¡ )
Is it normal?
No
▲
( ▼ )
No
No
(Whenever y ou selectted Temp .
Button, it is changed by 1°C (18~32°C)
Buzzer Driving
Remocon Input
Comp Relay Driving
Zero Crosing Detect
Function S/W
Temperature
Sensor Input
LED Driving
Emergency
Mode
Function
S/W
Reset Curcuit
Oscillation
9. KEY COMPONENTS OF ELECTRONIC CIRCUIT
(1) U1 (MICOM)
48
(2) U2, 4 (KID65004) DARLINGTON ARRAYS
IN1 116 OUT 1
IN2 215 OUT 2
IN 3 314 OUT 3
IN 4 413 OUT 4
IN5 512 OUT 5
IN6 611 OUT 6
IN7 710 OUT 7
GND 89 COMMON FREE
WHEELING DIODES
COMMON
10.5K‰
7.2K‰
3K‰
OUTPUT
GND
INPUT
100K500
100
100
0.3
10K
6K
500
1K
5K
28K
6K
30pF
2K
5K
200
240
1.4
K
2.7
K
3.3
K
0.19K
INPUT
OUTPUT
GND
SCHEMATIC DIAGRAM
1
2
3
Fin 2 is ground
for Cose 221A.
Case is ground
for Case 1.
10K
INPUT
GND
10K
300
36K
64K
520
26K
60K
29K
20K
20K
40
pF
50K
50 200
300
200
100
16K
210
012
OUTPUT
KID65004AP
(Equivalent Circuit)
(Top View)
(3) U8 (KIA7805P) : VOLTAGE REGULATOR (5VDC)
Pin 1. INPUT
2. GROUND
3. OUTPUT
(4) U7 (KIA7812P) : VOLTAGE REGULATOR (12VDC)
Pin 1. INPUT
2. GROUND
3. OUTPUT
49
(Equivalent Ciircuit)
(5) U9 (KIA7042P) : RESET IC
KIA70
42P
OUTLINE
INPUT
GROUND
OUTPUT
VCC
1
3
2
OUT
GND
50
10. DISASSEMBLY INSTRUCTIONS
INDOOR UNIT
1
¡ DSB-070LH/DSB-091LH
PROCEDURES PHOTOS
1. Stop the Air conditioner and disconnect the power cord from the wall
outlet.
2. Removing the Insert Grille and F rame Grille. (Fig 1~2)
! Dra w up the Insert Grille and remove it.
@ Loosen one screw for fixing the Cover Ter-Block.
# Loosen two screw at the Fr ame Grille.
$ Remove the F rame Grille.
Fig 1
Fig 2
3. Removing the Control Box. (Fig 3)
! Remov e room and coil thermistors.
@ Disconnect the fan motor lead wire from connection at the
Control PCB.
# Disconnect the stepping motor lead wire from connection at the
Control PCB.
$ Remove the select switch from connection at the Control PCB.
% Loosen a screw for fixing ground wire.
^ Remove the Control Box
4. Removing the Drain Pan. (Fig 4)
! Disconnect the Body drain hole. (left and right Body)
@ Disconnect three hook and remove the Drain Pan.
5. Removing the Indoor Evaporator . (Fig 5~6)
! Remov e one scre w f or fixing indoor Evapor ator at the Body.
@ Remove the hook for fixing Brack et Pipe at the back of Body.
# Remove Indoor Evapor ator .
Fig 3
Fig 4
Fig 5
6. Removing the Cross Flow F an. (Fig 7)
! Remov e set scre w f or fixing Motor shaft.
@ Remove Cross Flow Fan.
7. Remove Motor IDU and Bearing Plastic.
Fig 6
Fig 7
51
¡ DSB-121LH
PROCEDURES PHOTOS
1. Stop the Air conditioner and disconnect the power cord from the wall
outlet.
2. Removing the Insert Grille and F rame Grille. (Fig 1~2)
! Dra w up the Insert Grille and remove it.
@ Loosen two special screw for fixing the Cover Ter-Block.
# Loosen three screw at the Body.
$ Remove the F rame Gille .
3. Removing the Control Box. (Fig 3)
! Remov e room and coil thermistors.
@ Disconnect the fan motor lead wire from connection at the
Control PCB.
# Disconnect the stepping motor lead wire from connection at the
Control PCB.
$ Remove the select switch from connection at the Control PCB.
% Loosen a screw for fixing ground wire.
^ Remove the Control Box
Fig 1
Fig 2
Fig 3
4. Removing the Drain Pan. (Fig 4)
! Disconnect the Body drain hole. (left and right Body)
@ Disconnect three hook and remove the Drain Pan.
5. Removing the Indoor Evaporator . (Fig 5~6)
! Remov e three scre w f or fixing indoor Evapor ator at the Body.
@ Remove the hook for fixing Brack et Pipe at the back of Body.
# Remove Indoor Evapor ator .
6. Removing the Cross Flow F an. (Fig 7)
! Remov e set scre w f or fixing Motor shaft.
@ Remove Cross Flow F an.
7. Remove Motor IDU and Bearing Plastic.
Fig 4
Fig 5
Fig 6
Fig 7
52
OUTDOOR UNIT
2
¡ DSB-070LH/DSB-091LH/DSB-121LH(After)
PROCEDURES PHOTOS
1.Stop the air conditioner and disconnect the wire from Indoor Unit to
Outdoor Unit.
2. Disassemble the case. (Fig 1~2)
!
53
¡ DSB-121LH(Before)
PROCEDURES PHOTOS
1.Stop the air conditioner and disconnect the wire from Indoor Unit to
Outdoor Unit.
2. Disassemble the case. (Fig 1~2)
! Remov e the Top Panel. (Loosen two screw and remove six hook)
@ Remove the F ront Cabinet. (Loosen f our screw and f our hook)
# Remove the Side Cabinet and Back Cabinet. (Loosen eight screw)
3. Removing the Propeller Fan. (Fig 3)
! Loosen the Nut f or fixing the Propeller F an.
@ Remove the Plain W asher.
# Remov e the Propeller F an.
4. Removing the Motor ODU. (Fig 4)
! Loosen f our screw at Br ack et Motor.
@ Disconnect the wire at Control Panel and remov e Motor ODU .
Fig 1
Fig 2
Fig 3
5. Removing the Dual Capacitor. (Fig 5)
! Disconnect the wire at Control P anel.
@ Loosen a screw at Clamp Capacitor .
# Remov e the Dual Capacitor .
6. Removing the Over load Protector . (Fig 6~7)
! Loosen a He x Nut at Terminal Cover.
@ Remove the Terminal Cover.
# Remov e the wire at Over load Protector.
$ Remov e the Ov er load Protector .
13100054410CONTROL PCB ASS’Y1
23108912301TERMINAL BLOCK1
35EPV050120TRANSFORMER1
43106900300CAPACIT OR SH.M.B11.0µF 400V A C
53104896300SENSOR ID ASS’Y1PTM-KD43C-D2
63101300100POWER CORD ASS’Y116A 250V
73102797610HARNESS1I/D COMP
83102797150HARNESS1I/D 4WAY V ALVE
93102704400HARNESS1O/D MOTOR
103102797910HARNESS1I/D EARTH
113102704000HARNESS1POWER
123102702200HARNESS1TH-3-1
133102704500HARNESS1LED PCB
SN-DBW-05P 300V 25A
DWA-220B 220V 50/60Hz
67
¡ DSB-121LH
68
¡ DSB-090LH/DSB-120LH
NoPART CODEPART NAMEQ'TYSPECREMARK
13100503100CONTROL BOX1P.P+G.F 20%
23100054400CONTROL PCB ASS’Y1FR-1
33100054200LED PCB ASS’Y1FR-1
43103400300KNOB RESET SWITCH1ABS
53101395060POWER CORD ASS’Y1BUYER
63108912301TERMINAL BLOCK1SN-DBW-05P
75EPV050100TRANS FORMER1DWA220A-50/60HZ
83106900300CAPACIT OR SH.M.B11.0µF 400V A C
H13102797610HARNESS I/D COMP1
H23102797500HARNESS LED PCB1
H33102797410HARNESS MODE SELECT1
H43102797910HARNESS I/D EARTH1
S3104896300SENSOR ID ASS’Y1PTM-KD-43C-D2
93102702200HARNESS O/D SENSOR16M
69
SERVICE MANUAL
DEAWOO ELECTRONICS CO., LTD
686, AHYEON-DONG MAPOGU,
SEOUL, KOREA.
C.P.O. BOX 8003 SEOUL KOREA
TELEX: DWELEC K28177-8
CABLE:"DAEWOOELEC"
FAX: +82-2-364-5588
TEL: +82-2-360-7114, 8114
http://www.dwe.daewoo.co.kr
S/M NO. : DSB070LH10PRINTED DATE: APR. 1999
OVERSEAS SERVICE DEPT.
DAEWOO ELECTRONICS CO., LTD
Service Manual
Split System Air
Conditioner
Model: DSB-070LH
DSB-091LH
DSB-121LH
DAEWOO ELECTRONICS CO., LTD.
72