CUE Power Express User Manual

User Manual
Power Express
User Manual Power Express
UM012_04, 22.03.2007
Copyright © CUE, a.s. Praha, Czech Republic 1996 - 2006.
All rights reserved. Specifications are subject to change without prior notice.
Table of Contents
Introduction....................................................................................................................................... 4
1.1. Overview.............................................................................................................................................. 4
1.2. Models................................................................................................................................................. 4
1.3. Features .............................................................................................................................................. 5
2. System Block Diagram .................................................................................................................... 6
3. Control Units..................................................................................................................................... 7
3.1. Converter PEC25................................................................................................................................. 7
3.2. Dimmer PED108.................................................................................................................................. 8
3.3. Dimmer PED202.................................................................................................................................. 9
3.4. Dimmer PET102.................................................................................................................................10
3.5. Dimmer PET105.................................................................................................................................11
3.6. Analog Outputs Interface PEA208......................................................................................................12
3.7. Dimming Ballasts Interface PEF150...................................................................................................13
3.8. Dimming Ballasts Interface PEF200...................................................................................................14
3.9. Switching Unit PER610.......................................................................................................................15
3.10. Suppressor PES03.............................................................................................................................16
4. Specifications................................................................................................................................. 17
4.1. General...............................................................................................................................................17
4.2. Converter PEC25................................................................................................................................17
4.3. Dimmer PED108.................................................................................................................................17
4.4. Dimmer PED202.................................................................................................................................17
4.5. Dimmer PET102.................................................................................................................................18
4.6. Dimmer PET105.................................................................................................................................18
4.7. Analog Outputs Unit PEA208 .............................................................................................................18
4.8. Dimming Ballasts Interface PEF150...................................................................................................19
4.9. Dimming Ballasts Interface PEF200...................................................................................................19
4.10. Switching Unit PER610.......................................................................................................................19
4.11. Suppressor PES03.............................................................................................................................19
5. Software and Firmware License ...................................................................................................20
6. Warranty Conditions......................................................................................................................21
7. CE Declaration of Conformity....................................................................................................... 22
8. FCC.................................................................................................................................................. 23
User Manual Power Express
www.cue.cz
Page 3 of 24

1. Introduction

1.1. Overview ..........................................................................................
Power Express is a modular system, which controls lights, drapes, screens etc. All modules are fully compatible with ipCUE, Assistant and Assistant-S. It is suitable wherever sensitive work with light system is needed, or central control by integrated control system is necessary. Simple installation into a switchboard on DIN rail, small dimensions. The 2.5 kV isolation between power and control circuits. Easy programming of parameters on PC under Windows. Immediate information about status of the modules. Manual control by contact closure and switches (any standard types). Communication between modules via PEbus - two twisted-pair cables. Interference suppre ssion according to EN55014 and EN55011 norm.
Usage for
Smart houses
Conference and versatile halls, boardrooms
Classrooms, auditorium (with video projection) Entertaining halls
Theatres, galleries, museums
Information centers
Exhibition stands
1.2. Models..............................................................................................
Model Product code Description
PEC25 CS0163 Converter between RS-232 and PEbus. PED108 (version 110VAC) CS0164-1 One-channel dimmer. Output 1x 110 VAC, 8 A. PED108 (version 230 VAC) CS0164-2 One-channel dimmer. Output 1x 230 VAC, 8 A. PED202 (version 110 VAC) CS0165-1 Two-channel dimmer. Output 2x 110 VAC, 2.7 A (total max. 4 A). PED202 (version 230 VAC) CS0165-2 Two-channel dimmer. Output 2x 230 VAC, 2.7 A (total max. 4 A). PET102 (version 110 VAC) CS0244-1 One-channel dimmer. Output 1x 110 VAC, 2A PET102 (version 230 VAC) CS0244-2 One-channel dimmer. Output 1x 230 VAC, 2A PET105 (version 110 VAC) CS0245-1 One-channel dimmer. Output 1x 110 VAC, 5A PET105 (version 230 VAC) CS0245-2 One-channel dimmer. Output 1x 230 VAC, 5A PEA208 (version 110 VAC) CS0225-1 Two-channel analog output 0 - 10 V PEA208 (version 230 VAC) CS0225-2 Two-channel analog output 0 - 10 V PEF150 (version 110 VAC) CS0249-1 15-channel controller for DALI fluo lamp dimming ballasts. PEF150 (version 230 VAC) CS0249-2 15-channel controller for DALI fluo lamp dimming ballasts. PEF200 (version 110 VAC) CS0166-1 Two-channel controller for DSI fluo lamp dimming ballasts. PEF200 (version 230 VAC) CS0166-2 Two-channel controller for DSI fluo lamp dimming ballasts. PER610 (version 110 VAC) CS0167-1 Six-channel relay unit. Output 6x max. 230 VAC, 10 A. PER610 (version 230 VAC) CS0167-2 Six-channel relay unit. Output 6x max. 230 VAC, 10 A. PES03 CS0168 Three-channel suppressor unit.
User Manual Power Express
www.cue.cz
Page 4 of 24
1.3. Features ...........................................................................................
Easy installation (into switchboard on DIN rail)
Small dimensions
Consistent galvanic isolation between control and power circuits
Easy setting of parameters (under Windows PC application)
Immediate information about current status of the units
Manual control from current push buttons and switches (great variety of designs and colors)
Communication between units and switchboards via twisted pair cable.
Serial control from CUE controllers (port S1 on ipCUE, S9/CUEring on Assistant) via PEbus.
User Manual Power Express
www.cue.cz
Page 5 of 24

2. System Block Diagram

User Manual Power Express
www.cue.cz
Page 6 of 24

3. Control Units

3.1. Converter PEC25.............................................................................

3.1.1. Overview

PEC25 is a converter between RS-232 and PEbus. Transmission way indication by LED indicators. Host computer connector on the front panel for system setup.

3.1.2. Connections

The connector Sub-D, 9-pin, female and terminals are connected in parallel. TxD means transmit data, RxD means receive data and GND is a digital ground.
2 - TxD 3 - RxD 5 - GND
TxD
RxD
GND
SUBD 9F
PEbus
GND
69
DB9 – Male rear view
to PEC25
Cable from ipCUE to PEC25
15
Phoenix 5-pin 3.5 mm
to S1 port on ipCUE
User Manual Power Express
www.cue.cz
Page 7 of 24
3.2. Dimmer PED108 ..............................................................................

3.2.1. Overview

PED108 is a one-channel dimmer for resistive and inductive loads up to 8 A. The unit features PEbus and contact closure control. Programmable parameters (input response, min. and max. value of output voltage, dimming speed, output characteristic). Indication of output level by yellow OUT LED, max. temperature overload and over­current fuse by red F/O LED. Indication of power by green P/D LED. This LED is flashing while data is being transmitted or received through the PEbus.

3.2.2. Connections

LOAD max. 8 A
NL
OUT
OUT
LIVE
LIVE
NEUTRAL
NEUTRAL
DOWNUPGND
PEbus
User Manual Power Express
www.cue.cz
Page 8 of 24
3.3. Dimmer PED202 ..............................................................................

3.3.1. Overview

PED202 is a two-channel dimmer for resistive and inductive loads up to
2.7 A per channel (max. 4 A total). The unit features PEbus and contact closure control. Programmable parameters (input response, min. and max. value of output voltage, dimming speed, output characteristic). Indication of output levels by yellow OUT LEDs, max. temperature overload and over­current fuse by red F/O LED. Indication of power by green P/D LED. This LED is flashing while data is being transmitted or received through the PEbus.
.3.2. Connections
3
2 x LOAD total max. 4 A
NL
LIVE
LIVE
NEUTRAL
DOWN1
OUT1
OUT2
NEUTRAL
UP1
GND
DOWN2
UP2
GND
PEbus
User Manual Power Express
www.cue.cz
Page 9 of 24
3.4. Dimmer PET102...............................................................................

3.4.1. Overview

PET102 is a one-channel dimmer for resistive and capacitive loads up to 2 A suitable for dimmable electronic transformers. The unit features PEbus and contact closure control. Programmable parameters (input response, min. and max. value of output voltage, dimming speed, output characteristic). Indication of output level by yellow OUT LED, max. temperature overload and over­current electronic fuse by red F/O LED. Indication of power by green P/D LED. This LED is flashing while data is being transmitted or received through the PEbus.

3.4.2. Connections

NL
LOAD max. 2 A
OUT
NEUTRAL
NEUTRAL
LIVE
LIVE
DOWNUPGND
PEbus
User Manual Power Express
www.cue.cz
Page 10 of 24
3.5. Dimmer PET105...............................................................................

3.5.1. Overview

PET105 is a one-channel dimmer for resistive and capacitive loads up to 5 A suitable for dimmable electronic transformers. The unit features PEbus and contact closure control. Programmable parameters (input response, min. and max. value of output voltage, dimming speed, output characteristic). Indication of output level by yellow OUT LED, max. temperature overload and over-current electronic fuse by red F/O LED. Indication of power by green P/D LED. This LED is flashing while data is being transmitted or received through the PEbus.

3.5.2. Connections

NL
LOAD max. 5 A
OUT
NEUTRAL
NEUTRAL
LIVE
LIVE
DOWNUPGND
PEbus
User Manual Power Express
www.cue.cz
Page 11 of 24
3.6. Analog Outputs Interface PEA208.................................................

3.6.1. Overview

PEA208 is a two-channel analog output 0 - 10V interface for devices with analog control 0 - 10V (dimmable ballast for fluorescent lamps – Osram, Siemens, Helvar, Philips, dimmers, frequency converters ...). Analog outputs have 10–bit resolution (1024 levels). Sink current can be up to 100mA to each output (more then 100 of ballasts). Unit has two switching outputs (max. 8A) automatically switched on, if analog output voltage is greater then 1V (for power supply of ballasts). The unit features PEbus and contact closure control. Programmable parameters (inputs response, min. and max. value of output voltage, scan speed). Indication of output levels by yellow OUT LEDs.
3.6.2. Connections 3.6.2. Connections
Indication of power by green P/D LED. This LED is flashing while data is being transmitted or received
flashing while data is being transmitted or received through
through
power by green P/D LED. This LED is
the PEbus. the PEbus.
N L
N
DIMMABLE BALLAST
L
1-10 V ANALOG CONTROL
A+ A-
LIVE
OUT1+
DOWN1
OUT1-
UP1
OUT2+
GND
OUT2-
NEUTRAL
PWR OUT1
PWR OUT2
DOWN2
UP2
GND
LIVE
NEUTRAL
N
DIMMABLE BALLAST
L
1-10 V ANALOG CONTROL
A+ A-
max.
100 ballasts
LOAD
max. 8 A
PEbus
User Manual Power Express
www.cue.cz
Page 12 of 24
3.7. Dimming Ballasts Interface PEF150..............................................

3.7.1. Overview

PEF150 is interface for control up to 64 dimmable ballasts for fluorescent lamps on one bus divided up to 15 independent groups. Interface is compatible with ballasts DALI (Philips, Osram, Tridonic, Helvar ...). The unit features PEbus and contact closure control. All groups is possible to control by PEXbus and two of them by external press buttons. Programmable parameters (inputs response, min. and max. value of output voltage, scan speed). Indication of output levels of two groups by yellow G/S LEDs. Indication of power by green P/D LED. This LED is flashing while data is being transmitted or received through the PEbus. Indication of DALI communication by yellow OUT LED.

3.7.2. Connections

N L
N
DIMMABLE BALLAST
DA
DOWN1
DA
UP1
LIVE
LIVE
NEUTRAL
NEUTRAL
GND
DOWN2
UP2
GND
max.
64 ballasts
L
DALI
DA DA
N
DIMMABLE BALLAST
L
DALI
DA DA
PEbus
User Manual Power Express
www.cue.cz
Page 13 of 24
3.8. Dimming Ballasts Interface PEF200..............................................

3.8.1. Overview

PEF200 is a two-channel interface for fluorescent lamp dimming ballasts with DSI control signal (TRIDONIC, ZUMTOBEL). The unit features PEbus and contact closure control. Programmable parameters (inputs response, min. and max. value of output voltage, scan speed). Indication of output levels by yellow OUT LEDs. Indication of power by green P/D LED. This LED is flashing while data is being transmitted or received through the PEbus.

3.8.2. Connections

N L
N
DIMMABLE BALLAST
L
DSI CONTROL
D1 D2
N
DIMMABLE BALLAST
L
DSI CONTROL
D1 D2
DOWN1
OUT1D1
UP1
OUT1D2
OUT2D1
GND
LIVE
LIVE
OUT2D2
DOWN2
UP2
GND
NEUTRAL
NEUTRAL
max.
50 ballasts
PEbus
User Manual Power Express
www.cue.cz
Page 14 of 24
3.9. Switching Unit PER610...................................................................

3.9.1. Overview

PER610 is a six-channel relay switching unit for loads up to 10 A per channel. The unit features PEbus and contact closure control. Programmable parameters for each channel (response on input, delayed on/off, memory, motor control sequence). Indication of output status by yellow OUT LEDs. Indication of power by green P/D LED. This LED is flashing while data is being transmitted or received through the PEbus.
.9.2. Connections
3
NC1
LIVE
COM1
LIVE
NO1
NEUTRAL
NC2
NEUTRAL
COM2
NC is normally closed con COM is common contact. NO is normally opened contact. Max. load is 230V/10A pe
COM4
NC5
NO4
NC3
NO2
COM3
NC4
NO3
COM5
NC6
COM6
NO6
NO5
GND
IN1
IN2
IN3
GND
IN4
IN5
IN6
tact.
r channel.
PEbus
NL
User Manual Power Express
www.cue.cz
Page 15 of 24
3.10. Suppressor PES03..........................................................................

3.10.1. Overview

PES03 is a three-channel EMI suppressor unit for switching channels. In a connection with PER610, this unit is suitable for suppression of noise peaks generated especially during switching inductive loads (motors of drapes, screens etc.)

3.10.2. Connections

CH2
LOAD
CH3
L
CH1
COMMON
N
User Manual Power Express
www.cue.cz
Page 16 of 24

4. Specifications

4.1. General

EMI radiation .......................................According to EN55014 and EN55011 standard
Power supply.......................................230 VAC (version 230V) or 110 VAC (version 110V), 50/60 Hz
Communication....................................PEbus (RS-485)
Enclosure.............................................Plastic
Storage temperature............................-20 to 90 °C
4.2. Converter PEC25.............................................................................
Power supply.......................................From PEbus or external 7.5 - 30 VDC, 100 mA
Baud rate.............................................19 200 bits/sec
Connectors ..........................................2x RJ-11-4 for PEbus
Sub-D, 9-pin, female for RS-232
Terminals for RS-232
Weight..................................................0.1 kg
Dimensions..........................................36 x 90 x 58 mm (2 modules 17.5 mm)
Operating ambient temperature ..........0 to 60 °C
Supplied accessories...........................PEbus Cable CA0130
4.3. Dimmer PED108 ..............................................................................
Regulated output.................................1x 8 A
Way of regulation.................................Leading - edge phase control
Over-current protection........................Quick-brake fuse 5 x 20 mm, F8A
Cooling system....................................Passive aluminum heat sink
Insulation strength...............................2.5 kV between power and control circuits
Connectors ..........................................2x RJ-11-4 for PEbus
Terminals up to 1.5 mm
Weight..................................................0.75 kg
Dimensions..........................................106 x 90 x 58 mm (6 modules 17.5 mm)
Operating ambient temperature ..........0 to 40 °C
Supplied accessories...........................PEbus Cable CA0130
2
for inputs and outputs
4.4. Dimmer PED202 ..............................................................................
Regulated outputs ...............................2x 2.7 A per channel (4 A total)
Way of regulation.................................Leading - edge phase control
Over-current protection........................Quick-brake fuse 5 x 20 mm, F4A
Cooling system....................................Passive aluminum heat sink
Insulation strength...............................2.5 kV between power and control circuits
Connectors ..........................................2x RJ-11-4 for PEbus
Terminals up to 1.5 mm
Weight..................................................0.5 kg
Dimensions..........................................106 x 90 x 58 mm (6 modules 17.5 mm)
Operating ambient temperature ..........0 to 40 °C
Supplied accessories...........................PEbus Cable CA0130
2
for inputs and outputs
User Manual Power Express
www.cue.cz
Page 17 of 24
4.5. Dimmer PET102...............................................................................
Regulated output.................................1x 2 A
Way of regulation.................................Trailing - edge phase control
Over-current protection........................Electronic fuse
Cooling system....................................Passive aluminum heat sink
Insulation strength...............................2.5 kV between power and control circuits
Connectors ..........................................2x RJ-11-4 for PEbus
Terminals up to 1.5 mm
2
for inputs and outputs
Weight..................................................0.5 kg
Dimensions..........................................53 x 90 x 58 mm (3 modules 17.5 mm)
Operating ambient temperature ..........0 to 40 °C
Supplied accessories...........................PEbus Cable CA0130
4.6. Dimmer PET105...............................................................................
Regulated output.................................1x 5 A
Way of regulation.................................Trailing - edge phase control
Over-current protection........................Electronic fuse
Cooling system....................................Passive aluminum heat sink
Insulation strength...............................2.5 kV between power and control circuits
Connectors ..........................................2x RJ-11-4 for PEbus
Terminals up to 1.5 mm
Weight..................................................0.75 kg
Dimensions..........................................106 x 90 x 58 mm (6 modules 17.5 mm)
Operating ambient temperature ..........0 to 40 °C
Supplied accessories...........................PEbus Cable CA0130
2
for inputs and outputs
4.7. Analog Outputs Unit PEA208.........................................................
Power consumption.............................12 W
Regulated outputs ...............................2x 0 – 10V, 15mA source, 100 mA sink per channel
D/A converter resolution......................10 bits (1024 levels)
Switching outputs ................................2 relays, up to 230V, 8A per channel
Insulation strength...............................2.5 kV between power and control circuits
Connectors ..........................................2x RJ-11-4 for PEbus
Terminals up to 1.5 mm
Weight..................................................0.25 kg
Dimensions..........................................71 x 90 x 58 mm (4 modules 17.5 mm)
Operating ambient temperature ..........0 to 60 °C
Supplied accessories...........................PEbus Cable CA0130
User Manual Power Express
www.cue.cz
Page 18 of 24
2
for inputs and outputs
4.8. Dimming Ballasts Interface PEF150..............................................
Power consumption.............................12 W
Output..................................................15 groups, up to 64 electronic DALI compatible ballasts
Connectors ..........................................2x RJ-11-4 for PEbus
Terminals up to 1.5 mm
2
for inputs and outputs
Weight..................................................0.25 kg
Dimensions..........................................71 x 90 x 58 mm (4 modules 17.5 mm)
Operating ambient temperature ..........0 to 60 °C
Supplied accessories...........................PEbus Cable CA0130
4.9. Dimming Ballasts Interface PEF200..............................................
Power consumption.............................12 W
Outputs................................................2x up to 50 electronic DSI compatible ballasts per channel
Connectors ..........................................2x RJ-11-4 for PEbus
Terminals up to 1.5 mm
Weight..................................................0.25 kg
Dimensions..........................................71 x 90 x 58 mm (4 modules 17.5 mm)
Operating ambient temperature ..........0 to 60 °C
Supplied accessories...........................PEbus Cable CA0130
2
for inputs and outputs
4.10. Switching Unit PER610...................................................................
Power consumption.............................12 W
Outputs................................................6 relays, up to 230 VAC, 10 A per channel
Insulation strength...............................2.5 kV between power and control circuits
Connectors ..........................................2x RJ-11-4 for PEbus
Terminals up to 1.5 mm
2
for inputs and outputs
Weight..................................................0.5 kg
Dimensions..........................................106 x 90 x 58 mm (6 modules 17.5 mm)
Operating ambient temperature ..........0 to 60 °C
Supplied accessories...........................PEbus Cable CA0130
4.11. Suppressor PES03..........................................................................
Number of suppressed channels.........3
Max. load voltage ................................275 VAC
Max. load current.................................10 A
Connectors ..........................................Terminals up to 1.5 mm
Weight..................................................0.1 kg
Dimensions..........................................36 x 90 x 58 mm (2 modules 17.5 mm)
Operating ambient temperature ..........0 to 60 °C
2
for inputs and outputs
User Manual Power Express
www.cue.cz
Page 19 of 24

5. Software and Firmware License

END-USER NOTICE AND LICENSE AGREEMENT FROM CUE, a.s. NOTICE TO END-USER: CAREFULLY READ THE FOLLOWING LEGAL AGREEMENT (THIS "LICENSE"). INSTALLATION OR USE OF THE ENCLOSED CUE, a.s. SOFTWARE PROGRAMS (COLLECTIVELY, "SOFTWARE") ON YOUR COMPUTER SYSTEMS OR HARDWARE DEVICES CONSTITUTES YOUR ACCEPTANCE OF THESE TERMS. IF YOU DO NOT AGREE TO THE TERMS OF THIS LICENSE, PROMPTLY DELETE THE SOFTWARE FROM YOUR COMPUTER SYSTEMS AND HARDWARE DEVICES, DESTROY ANY COPIES YOU MADE OF THE SOFTWARE OR ANY INSTALLATION MEDIA OF THE SOFTWARE INCLUDED WITH YOUR SYSTEM, AND DISPOSE OF ALL WRITTEN MATERIALS IN YOUR POSSESSION REGARDING THE SOFTWARE. License Grant: CUE grants to You, as an individual, a license to install and use one (1) copy of the Software on a single computer at a time; provided, however, that You may make copies of the Software solely for Your development of applications for CUE hardware and demonstration versions of such applications. Any applications created with the Software may only be used with Cue hardware. Your license to use the Software is conditioned upon Your compliance with the terms of this License. A License is required for each end-user of the Software. A license is required for each installation of the Software. You may make one (1) copy of the Software for archival purposes only. You may use this Software only in connection with CUE hardware. You must have acquired the Software directly in connection with the purchase of CUE hardware from CUE or from a CUE approved reseller for this license to be effective. If You have purchased a Site License, You may complete only the number of installations specified in the License Agreement accompanying the Software. Copyright: The Software and software built into CUE har dware ("Firmware") are protected by copyright law and international treaty provisions. You acknowledge that no title to the intellectual property in the Software and Firmware is transferred to You. You further acknowledge that title and full o wnership rights to the Software and Firmware will remain the exclusive property of CUE, and You will not acquire any rights to the Software and Firmware except as expressly set forth in this License. You agree that any copies of the Software will contai n the same proprietary notices which appear on and in the Software. Prohibited Uses: Without obtaining prior written permissio n from CUE, You may n ot (a.) use, copy, modify, alter, or transfer the Software or documentation except as expressly provided in this License; (b.) translate, disassemble, decompile, reverse program or otherwise reverse engineer the Software and Firmware; (c.) sublicense or lease the Software or its documentation (d.) use this Software with any hardware other than products produced by CUE or in connection with applicat ions being devel oped for CUE hard ware; or (e.) use the Software in a multi-user, network, or multiple computer environment or in a rental, time sharing or computer service business. Without prejudice to any other rights, CUE may terminate this License if You fail to comply with its terms and conditions. In such event, You must immediately destroy all copies of the Software. No Other Warranties: CUE DOES NOT WARRANT THAT THE SOFTWARE AND FIRMWARE IS ERROR FREE. CUE DISCLAIMS ALL WARRANTIES WITH RESPECT TO THE SOFTWARE AND FIRMWARE, EITHER EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT OF THIRD PARTY RIGHTS. SOME JURISDICTIONS DO NOT ALLOW THE EXCLUSION OF IMPLIED WARRANTIES OR LIMITATIONS OF HOW LONG AN IMPLIED WARRANTY MAY LAST, OR THE EXCLUSION OF LIMITATION OF INCIDENTAL DAMAGES, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM JURISDICTION TO JURISDICTION. No Liability for Consequential Damages: IN NO EVENT SHALL CUE BE LIABLE TO YOU FOR ANY CONSEQUENTIAL, SPECIAL, INCIDENTAL, OR INDIRECT DAMAGES OF ANY KIND ARISING OUT OF THE PERFORMANCE OR USE OF THE SOFTWARE, EVEN IF CUE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. Label on Hardware: Use of this hardware and the software programs controlling this hardware is subject to the terms of the Software and Hardware License Agreements (the “License Agreements”). You should not use the software and hardware until you have read the License Agreements. By using the software and hardware, you signify that you have read the Licenses Agreements and accept their terms. The “License Agreement” is available at www.cuesystem.com. Trademark Notice: CUE and the CUE logo are trademarks of CUE, a.s. in the United States and in other countries.
User Manual Power Express
www.cue.cz
Page 20 of 24

6. Warranty Conditions

Warranty Duration
CUE, a.s. provides warranty for all CUE products for a period of 3 years from the day of purchase. The provided warranty for touch screens is 2 years from the day of purchase. CUE accepts reclamation of 5 not properly working dots and more (2 dots join – 1 counts). The warranty provided for rechargeable accumulators is 6 months from the day of purchase
Liability
CUE is not liable for any consequential damage caused by CUE products including any loss of profits, incidental or consequential damages or any claims made by a third parties.
General Warranty Terms
a) CUE warrants that its products are without defects in material and are fully functional for the duration of the warranty. b) Warranty repairs are free of charge. The customer will send the damaged device to CUE at his cost. c) All warranty repairs and after warranty services are made at CUE premises. It is strictly prohibited to repair CUE
products or to change any accessory parts, except those parts with limited service life. CUE is not liable for consumables or parts with limited service life (lamps, batteries etc.)
d) The warranty further does not apply to the following cases
Damages caused by operating the system not according to the conditions defined in user manual or instruction (wrong power supply voltage, operation outside deferred temperature range, operation in humid environment and mechanical damages).
Damages caused by faulty service, maintenance, connection, and use of other than original connection cable.
Damage caused by agencies i.e. incidental or unpredictable impacts (fire, earthquake, flood, thunder, strong electric induction, water, strong wind, theft, vandalism etc.)
After Warranty Services
a) All warranty repairs are normally on a ‘back to base’ basis, as defined in 3 c) b) All out warranty repair costs will be fully charged to the customer. c) In cases where our staff are called out to assist, cost of transport and time will be at customer cost
User Manual Power Express
www.cue.cz
Page 21 of 24

7. CE Declaration of Conformity

CE Decl aratio n o f Conformi ty
Produc t N a me
airCUE-6X10 airCUE-6X10 Tabletop Docking Station airCUE-6X10 Tabletop Stand airCUE-6X10 Wall Docking Station airCUE-6X10 Wall Mounting Adapter airCUE-8X10 airCUE-8X10 Tabletop Docking Station airCUE-8X10 Tabletop Stand airCUE-8X10 Wall Docking Station airCUE-8X10 Wall Mounting Adapter airCUE-XM8 airCUE-XM8 Docking Station analogCUE auxCUE CUEadapter / 30W CUEadapter / 65W CUEwire Converter 232/422/485 eCUE inputCUE ipCUE-alpha ipCUE-beta ipCUE-delta ipCUE-epsilon ipCUE-gamma ipC UE Rack Mounti ng Kit IR Adapter /i irCUE 99 irCUE Receiver 485 keyboardCUE-S keyboar d CUE 99 keypadCUE-1G keypadCUE-2G keypadCUE-3G monitorCUE Opto-Input Adapter /i PEA208 PEC2 5 PED108 PED202 PEF1 5 0 PEF2 0 0 PER610 PES0 3 PET1 0 2
We, the producer
, K Nouzovu 6, Praha 4, Czech Republic
CUE, a.s.
acknowledge our sole responsibility, that the product including accessories
Kind of equipment:
Remot e Cont r o l Syst em
Type designation
(in alphabetical order)
Produc t C od e
CS0300-001 to CS0300-005 CS0301-001 to CS0301-005 CS0303-001 CS0302-001 to CS0302-005 CS0304-001 CS0305-001 to CS0305-005 CS0306-001 to CS0306-005 CS0308-001 CS0307-001 to CS0307-005 CS0309-001 CS0254-W, CS0254-O, CS0254-M CS0260-W, CS0260-O, CS0260-M CS0004 CS0005 CS0292-001 to CS0292-003 CS0293-001 to CS0293-003 CS0233 CS0173 CS0191 CS0251 CS0252 CS0267 CS0268 CS0253 CS0251-MR CS0256 CS0149-WA, CS0149-OA, CS0149-MA CS0169-C CS0174-W, CS0174-O, CS0174-M CS0145-W, CS0145-O, CS0145-M CS0221 CS0222 CS0223 CS0203-W, CS0203-O, CS0203-M CS0257 CS0225-1, CS0225-2 CS0163 CS0164-1, CS0164-2 CS0165-1, CS0165-2 CS0249-1, CS0249-2 CS0166-1, CS0166-2 CS0167-1, CS0167-2 CS0168 CS0244-1, CS0244-2
Produc t N a me
PET1 0 5 powerAUX rfbaseCUE rfCU E 9 9 Rx Ex t Rx1 DI N / D a ta Re c e i ver sbi C U E- D M X sensorCU E sma rtCUE soundCUE touchCUE-L touchCUE-L / b touchCUE-L / b Back Box touchCUE-L / b Rack Mount Panel touchCUE-LV touchCUE-LV /b touchCUE-LV 99 touchCUE-M touchCUE-M / b touchCU E-M / b Back Box touchCUE-M / b Rack Mo unt Pane l touchCUE-M V touchCUE-M V / b touchCUE-M V 99 touchCUE-S touchCUE-S / b touchCUE-S / b Back Box touchCUE-S / b Rack Mount Panel touchCUE-S 9 9 touchCUE-SRF touchCUE-SX / b touchCU E-SX / b Back Box touchCUE-SX / b Rack Mount Panel touchCUE-V / i touchCUE-XLV 99 Tx C r o ss 4 Tx Elemen t 2 Tx Elemen t 4 Tx Key Tx Pocket 1 Tx Pocket 4 Tx Time 2 Tx Time 4 Universa l Serial Ca ble Adapter
Produc t C o de
CS0245-1, CS0245-2 CS0016 CS0171-4, CS0171-8, CS017 1-9 CS0170-*4A, CS0170-* 8A, CS0170 -*9A CS0319.401 CS0318.401 CS0201 CS0265 CS0008-R, CS0008-M CS0009 CS0236 CS0238 CS0238-MB CS0238-MR CS0236-V CS0238-V CS0234-W-V, , S0234-O-V, CS0234-M-V CS0237 CS0239 CS0239-MB CS0239-MR CS0237-V CS0239-V CS0235-W-V, CS0235-O-V, CS0235-M-V CS0247 CS0241 CS0241-MB CS0241-MR CS0248-W, CS0248-O, CS0248-M CS0188-4, CS0188-8, CS018 8-9 CS0266 CS0266-MB CS0266-MR CS0190 CS0261-W-V, CS0261-O-V, CS0261-M-V CS0317.401 CS0312.401 to CS0312.424 CS0313.401 to CS0313.424 CS0316.401 CS0314.401 CS0315.401 CS0310.401 to CS0310.434 CS0311.401 to CS0311.434 CS0271
in accordance with EMC Directive 89/336 / EEC,
is in compliance with the following norms or documents:
EN50082-1 (IEC801-2), IEC65(CO)39, DIN VDE 0839 part 82-1, DIN VDE 0843 part 4, IEC801-4, EN50081-1, EN55022 class B, DIN VDE
0839 part 81-1, EN55014, EN55011.
28.5.2007
Jaroslav D i bitanzl
Member of Board of Directors
User Manual Power Express
www.cue.cz
Page 22 of 24

8. FCC

Caution
Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
Note
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio / TV technician for help.
User Manual Power Express
www.cue.cz
Page 23 of 24
Notes
User Manual Power Express
www.cue.cz
Page 24 of 24
Loading...