Crown GBD-II Installation Instructions Manual

1 2
3
GBD-II
SHOCK & BREAKAGE
GLASS BREAK DETECTOR
ELECTRONIC ENGI NEERING LTD.
INSTALLATION INSTRUCTIONS
P/N 7101108 Ver. 2.0 A.Y.
The GBD -II is the ultimate answer f or all those tired of f alse alarms. It listens for sounds of breaking glass, which produce two sequential signals of different frequencies. The unique phased frequency detection circuitry of this detector allows det ection of both shock signal and the strong signal of glass breakage creating a “false alarm free” glass br eak detector. The detector does not need to be attached to the window, providing volume protection, and allowing you to protect se veral windows with one detector.
FEATURES
Phased Frequency Detection system, detects low frequency impact sound as well as the glass breakage sound thereby eliminating false alarms.
Separate sound & shock adjustment.
Memory funct ion.
Volume protection.
Ceiling or wall mounting.
FIG. 1 - MOUNTING
The detector offer s f lexible installation. It can be Either ceiling mounted or wall mounted as shown in the figure above.
4 5 6
MOUNTING LOCATION ( See FIG. 1 )
If heavy blinds or curtains cover the glass, you must locate the detector behind the blinds on the window frame or above it, otherwise the blinds might block the sound. Make sure to test t he unit thoroughly for proper detect ion.
Install the detector in a direct line of sight with the protected glass.
Do not mount the unit in fr ont of air ducts, or close to bells (measuring 0.5m (or larger) in diameter).
For a few protected glasses in one room, locate the detector in optimal distance from them to achieve the best detection.
Note: for symmetrical cover of the detect ion
area it is recommended to place the detector on the ceiling.
MOUNTING THE DETECTOR ( FIG. 2 )
1. Use a small screwdriver to push the prong on top of the case and open the case.
2. There is no need to remove the PCB (Printed Circuit Board) from the case.
3. Insert the wires through the wiring hole (B).
4. Use the mounting holes (A) to mount the
detector.
5. Connect the wires to t he terminal.(See Terminal Connections)
6. Close the case.
JUMPERS ( FIG . 4 )
JP1 - Shock / Glass select or f or detection calibration.
JP2 - Reduces the sensitivity of sound detection by 50%.
JP3 - Lat ch. See The Memory Function.
FIG. 2 - T HE BACK COVER
AAB
7 8 9
FIG. 3 - T ERMINAL BLOCK
TERM INAL BLO CK CONNECTIO NS Terminal 1 - Marked - ( -12V )
Connect to the negative Voltage output or ground of the control panel.
Terminal 2 - Marked + ( + 12V )
Connect to the positive Voltage output of 9-16 Vdc source (usually from the alarm control unit)
Terminals 3 & 4 - Marked TAMPER
If a Tamper function is required connect these terminals to a 24hour normally closed protective zone in the control unit. If the front cover of the detector is opened, an immediate alarm signal will be sent to the control unit.
Terminals 5 & 6 - Marked RELAY
These are the output relay contacts of the detector.
THE CALIBRATION TOO L ( * )
The Simulator/Tester & Calib ration to ol is especially designed to check phased frequency glass break detectors. Since the detector w ill react t o t he high frequency breakage sound only when it comes sequentially after a low f r equency SHOCK sound, this device is necessary to check for proper operat ion of the GBD-II without actually breaking the glass.
Manual mode: In this mode, the Simulator w ill emit the high frequency sound of breaking glass for "Glass" adjustment.
Automatic mode: In order to simulate breaking glass, place the Simulator on the surface of the protected glass, and gently hit it with your hand. The Simulator will then emit the sound of breaking glass. Be careful not to break the glass while testing the detector.
It is r ecommended to use simulator CROW
P/N: 0040011
TESTING THE DETECTOR
First use the Simulator in manual mode to simulate the noise of glass breaking. Check that the yellow LED is ON. If it does not light, the sensitivity calibration is necessary (See Sound Calibration). Now use your hand or a padded object to carefully strike the glass. If the green LED does not light, adjust as necessary (See Shock Calibration). Now use the Simulator in automatic mode and check that the red LED lights. If the red LED is ON, your detector is wor king properly. Otherwise try adjusting the sound and shock setting until the red LED lights.
10 11
12
GLASS BREAK ADJUSTMENT
To adjust the glass break setting (increase/decrease sensitivity) place the jumper JP1 below the GLASS marking (connecting the middle pin with the left pin) ­(See Fig. 4) Gr een LED is constantly ON. Now you can adjust the sensitivity by rotating the right potentiometer (marked as GLASS CALIB. - see Fig. 4). Operate t he Sound Break Simulator and rotate the potentiometer clock-wise to increase sensitivity, and counter-clock-wise to decrease sensitivity until the Yellow and Red LED’s are illuminating for each glass break sound. Remember that rotating the potentiometer will have no effect upon the settings if the middle pin of JP1 is not connected to the left p in.
Note
When the jumper is set for G LASS adjustment, only the high frequency sound of breaking glass is detected.
SHOCK ADJUSTMENT
To adjust the shock setting (increase/decrease sensitivity) place the jumper JP1 below the SHO CK ma rking (connecti ng the middle pin with the right pin) - (See Fig. 4) Yellow LED is constantly ON. Now you can adjust the sensitivity by rotating the left potentiometer (marked as SHOCK CALIB. - see Fig. 4). Hit gently on the protected glass and rotate the potentiometer clock-wise to increase sensitivity, and counter-clock-wise to decrease sensitivity until the Green and Red LED’s are illuminating for ea ch hit. Remember that rotating the potentiometer will have no effect upon the settings if the middle pin of JP1 is not connected to the right pin.
Note
When the jumper is set for SHOCK adjustment, only the low frequency of the shock signal prior to glass breakage is detected.
SENSITIVITY SETTING
For some installations you may find that GBD­II is too sensitive. Use JUMPER JP2 to decrease sensitivity to 50%.
JP2 OPEN - 100% sensitivity JP2 CONNECTED - 50% sensitivity
FINAL TESTING
Make sure to disconnect the jumper at JP1. When the jumper is disconnected, the detector will detect both shock and sound frequencies.
To ensure maximum protection against false alarms, activate any device in the area, which might automatically cycle pumps, generators, heating/air conditioning units, etc. If the cycling devices trigger an alarm, mount the unit in a different location.
13 14 15
The alarm memory function allows the identification of an alerting detector out of multiple detectors connected to one (or the same) zone of the control panel. To enable this function, Set on jumper JP3
(connected on both pins - See Fig. 4)
In case of an alarm,
the red LED will stay
ON until until memory function is reset.
To reset the memory function, switch off (disconnect)
the voltage wire (+12V) fr om the TERMINAL BLOCK (See Fig. 4) for minimum 15 seconds then switch on (reconnect) voltage wire (+12V) . (The control panel key ON/OFF can be used for this application if it control the voltage (+12V).
FIG. 4 - PCB Layout
MICROPHONE
- +
TAMP RELAY
12Vdc
JP1
JP3
JP2
A 50%
SHOCK
CALIB.
JUMPER
JP2
JUMPER JP1
GREEN LED
SHOCK
TAMPER
RELAY
TERMINAL
BLOCK
SOUND
ADJ.
SHOCK
ADJ.
GLASS
CALIB.
LATCH
GAIN
YELLOW LED
GLASS
RED LED
ALARM
JUMPER
JP3
WIRE SIZE REQUIREMENTS
Use #22 AWG (0.5mm) or wires w ith a larger diameter. Use the following table to determine required wire gauge (diameter) and length of wire betw een the detector and the control panel.
Wire Length m 200 300 400 800 Wire Diameter mm .5 .75 1.0 1.5 Wire Length ft 800 1200 2000 3400 Wire Gauge # 22 20 18 16
16 17 18
TECHNICAL SPECIFICATIONS
Power Input 9 - 16 Vdc
Current Consumption Standby: 22mA at 12Vdc
Active: 25mA at 12Vdc
Detection Range 10m (33ft), Adjustable Dimensions 93mm x 55mm x 24mm Mounting Ceiling or Wall Alarm Output Relay N.C 50mA/24Vdc with
10 Ohm in line resistor Tamper Switch N.C 50mA 24Vdc with
10 Ohm in line resistor
Operating Temperature -20°C to 50°C Range (-4°F to 122°F)
Operating Humidity 95% max relative humidity Range non condensing
Storage Temperature -30°C to 70°C Range (-22°F to 158°F)
microphone RFI Protection 30V/m 10 -1000MHz EMI Protection 50,000V electrical
interference from
CROW LIMITED WARRANTY
(Crow) warr ants this product to be free from defects in materials and workm anship under normal use and service for a period of one year from the last day of the week and year whose numbers are printed on the printed circuit board inside this product. Crow’s obligation is limited to repairing or r eplacing this product, at its option, free of charge for materials or labor , if it is proved to be defective in materials or workmanship under nor mal use and ser vice. Cr ow shall have no obligation under this Limited Warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other then Crow. There are no warr anties, expr essed or implied, of mer chantability or fitness for a particular purpose or otherwise, which extend beyond the description on the face hereof. In no case s hall Crow be liable to anyone for any consequential or incidental damages for breach of this or any other warr anty, expr es s ed or implied, or upon any other basis of liability whatsoever, ev en if the loss or damage is caused by Crow’s own negligence or fault. Crow does not repr es ent that this product can not be comprom is ed or cir c um vented; that this product will prevent any pers on injury or property loss or damage by burglary, robbery, fire or otherwise; or that this product will in all cases provide adequate warning or pr otection. P urc has er under stands that a properly ins talled and maintained product can only reduce the risk of burglary, robbery or other events occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss or damage as a result. Consequently, Crow shall have no liability for any per s onal injury; proper ty dam age or any other los s bas ed on claim that this product failed t o gi ve any warning. However, if Crow is held liable, whether directly or indirec tly, for any loss or dam age arising under this limited warranty or otherwise, regardless of cause or origin, Crow’s maximum liability shall not in any case exceed the pur c has e pric e of this product, which shall be the com plete and exclus ive remedy against Crow.
CROW ELECTRONIC ENGINEERING LTD.
IS RAEL : 57 Hamelacha St., Holon 58855 Tel: 972-3-5569937 /8 /9 Fax: 972-3-5592981 E-mail:
support@crow.co.il
USA: 2160 North Central Road, Fort Lee, N.J. 07024 Tel: 1-800-GET CROW or (201) 944 0005 Fax: (201) 944 1199 E-mail:
AUST RAL IA: 429 Nepean HWY Brighton East Vic 3187
support@crowelec.com
Tel: 61-3-9596 7222 Fax: 61-3-9596 0888 E-mail:
crow@crowaust.com.au
POL AND: VIDICON S P. ZO. O. 15 Povazkow ska St. 01 – 797 Warsaw Poland Tel: 48 22 562 3000 Fax: 48 22 562 3030 E-mail:
vidicon@vidicon.pl
LATIN AMERICA: CROW LA TIN AMERICA
5753 NW 151
ST
.Street MIAMI LAK ES, FL 33014 – USA Tel: +1-305-823-8700 Fax: +1-305-823-8711
E-mail:
sales@crowlatinamerica.com
ITALY: DEATRONIC VIA Giulianello 4/14
00178 ROMA, ITALY Tel: +39-0676-12912 Fax: +39-0676-12601 E-mail:
info@deatronic.com
35108BE50
N345
Loading...