Fig.1
Creda
5
7
6
4
3
2
1
+
FLOW
S
T
T
O
R
P
/
T
A
S
+
++
5
4
3
2
1
6
7
8
9
T
E
E
R
M
U
P
T
E
R
A
3
SECTION
GENERAL INTRODUCTION
Electrical wiring of the mains system.
5. Fuses do not give personal protection
against electric shock.
6. It is strongly recommended to fit a
30mA residual current device (RCD).
This may be part of the consumer unit
or a separate unit.
INTRODUCTION
This book contains all the necessary fitting
and operating instructions for your Creda
power shower.
Take time to read this book thoroughly and
familiarise yourself with all instructions
BEFORE beginning installation. Please
keep it for future reference.
The shower installation must be carried
out by a suitably competent person and in
the sequence of this instruction book.
Care taken during the installation will
ensure a long and trouble-free life from
your shower
IMPORTANT: All plumbing connections
must be completed BEFORE making
the electrical connections.
IMPORTANT: The fittings on the pipe
Inlet elbows are of the push-in type.
The pipework must be cut with a pipe
cutter and all burrs and rough edges
removed from the end of the tube. The
fittings can be used with copper and
plastic pipe.
Where chrome plated pipe is used,
remove the first 25mm of plating.
I
I
I
I
I
b. Under no circumstances must this
product be connected to mains COLD
or HOT water supplies. Failure to
comply will invalidate the guarantee.
c. The shower MUST NOT be used if
suspected of being frozen.
d. The outlet of this appliance must not be
connected to any form of tap or fitting
not recommended by the manufacturer.
e. The sprayhead cartridge must be
cleaned regularly to remove scale and
debris.
f. This appliance must be earthed.
g. Switch off immediately at the isolating
switch if water ceases to flow during
use. Contact Customer Service for
advice.
h. If it is intended to operate the shower
outside the guidelines laid out in site
requirements, contact Customer Service
for advice.
In the interest of electrical safety a
30mA residual current device (RCD)
should be installed in all UK 230V
electric and pumped shower circuits.
This may be part of the consumer
Unit or a separate unit.
SPECIFICATIONS
HOT water temperature
Maximum temperature 65°C.
BS 6700 recommends that the temperature
of stored water should never exceed 65°C.
A stored water temperature of 60°C is
considered sufficient to meet all normal
requirements and will minimise the effects
of scale in hard water areas.
a. DO NOT insert fingers into the push-in
inlet fittings. Doing so could cause
injury.
SAFETY WARNINGS
This appliance is not intended for use by
persons (Including children) with reduced
physical, sensory or mental capabilities, or
lack of experience and knowledge, unless
they have been given supervision or
instruction concerning use of the appliance
by a person responsible for their safety.
Children should be supervised to ensure that
they do not play with the appliance.
Maximum static inlet pressures
1 bar or 10m (supplies must be gravity fed
at nominally equal pressures).
Minimum static inlet pressure
0.0075 bar or 75mm (required to prime the
integral centrifugal pump).
4
SECTION
SITE REQUIREMENTS
BS 6700. For correct operation of this
s
The water circuit should be installed so
that the flow is not significantly affected by
other taps and appliances being operated
elsewhere on the premises.
Fig.1 shows a recommended installation
where the HOT water supply for the
shower is made via a tee connection on
the underside of the horizontal section of
pipework from the cylinder. Alternatively,
hower unit, both HOT and COLD water
supplies to the appliance must be gravity
fed, at nominally equal pressures, from a
COLD water storage cistern and a HOT
water storage cylinder.
Water
The installation must be in accordance
with Water Regulations/Byelaws and