IMI CORNELIUS INC g One Cornelius Place g Anoka, MN 55303-6234
Telephone (800) 238-3600 Facsimile (612) 422-3246
Installation/Service
Manual
FCB 3 H.P. POST-MIX DISPENSER
TWO-FLAVOR W/HOT-GAS DEFROST
AND V3+ FEATURES
IMPORTANT:
TO THE INSTALLER.
It is the responsibility of the Installer
to ensure that the water supply to the
dispensing equipment is provided
with protection against backflow by
an air gap as defined in ANSI/ASME
A112. 1.2-1979; or an approved
vacuum breaker or other such
method as proved effective by test.
Water pipe connections and fixtures
directly connected to a potable water
supply shall be sized, installed, and
maintained according to Federal,
State, and Local laws.
Part No. 312026000
March 14, 1995
Revised: February 3, 1998
Control Code A–B–C
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION
This Manual must be read and understood before installing or operating this equipment
IMPORTANT: To the user of this manual - This manual is a guide for installing, operating, and maintaining
this equipment. Refer to Table of Contents for page location of information pertaining to questions that
arise during installation, operation, service and maintenance, or troubleshooting this equipment.
Warranty Registration Date
(to be filled out by customer)
Model Number:
Serial Number:
Install Date:
Local Authorized
Service Center:
GENERAL DESCRIPTION
This section gives the description, theory of operation, and design data for the FCB 3 H.P. Two-Flavor Post-Mix
Dispenser with Hot-Gas Defrost and V3+ Features (hereafter referred to as a Unit).
UNIT DESCRIPTION
The Two-Flavor FCB Dispenser (see Figure 1) consists basically of two freeze cylinders each containing an internal
beater driven by an electric motor, one refrigeration system with a 3-horsepower compressor, two carbonated water
tanks which feed both carbonator-blender tanks, a timer-controlled automatic hot-gas defrost system to defrost the
freeze cylinders, and interconnecting tubing, components, and fittings necessary to regulate, transfer, and dispense
product.
The components are attached to a steel frame and are enclosed in a steel cabinet. The cabinet panels are easily
removed to facilitate installation and service and maintenance. A transparent faceplate, with an integral relief valve
and a removable self-closing dispensing valve, is mounted on front of each freeze cylinder. A removable drip tray,
with cup rest, is located directly below the dispensing valves.
FIGURE 1. FCB DISPENSER
1312026000
CAUTION: Before shipping, storing, or relocating Unit, syrup systems must be sanitized
and all sanitizing solution must be purged from syrup systems. All water must also be
purged from plain and carbonated water systems. A freezing ambient environment will
cause residual sanitizing solution or water remaining inside Unit to freeze resulting in damage to
internal components.
Operating VoltageSee Unit Nameplate
Current DrawSee Unit Nameplate
REFRIGERATION SYSTEMS
NOTE: The FCB Dispenser (depending upon the model number) refrigeration system is either
“air-cooled” or “water-cooled”.
“AIR-COOLED”
The “air-cooled” FCB Dispenser refrigeration system is equipped with a condenser coil that is cooled by a
condenser coil fan.
“WATER-COOLED”
The “water-cooled” Two-Flavor FCB Dispenser refrigeration system is equipped with a Refrigeration Cooling Coil
Assembly that contains both refrigerant and plain water cooling coils. Circulating cool plain water through the
cooling coil cools the refrigerant also inside the coil. During installation, City cold plain water is connected to the
FCB Dispenser Refrigeration Cooling Coil water inlet line labeled “COOLING WATER IN”. The water drain line
labeled “COOLING WATER OUT” must be routed to and be connected to a permanent drain.
2312026000
THEORY OF OPERATION
(see Figure 2)
IMPORTANT: Before connecting electrical power to Unit, refer to nameplate and note if Unit is to be
operated with 50 or 60 Hz power source.
Note: The following paragraph describes the theory of operation for the Two-Flavor FCB Dispenser (see
Figure 2).
A CO2 cylinder delivers carbon dioxide (CO2) gas to an adjustable primary CO2 regulator assembly attached to the
cylinder. The primary CO2 regulator assembly in turn delivers CO2 gas to an adjustable secondary CO2 regulators
inside the Unit and also to the soft drink tanks. CO2 is delivered from the adjustable secondary CO2 regulators to
the two carbonated water tanks and also to the product-blender tanks inside the Unit. CO2 gas pressure pushes
syrup out of the soft drink tanks through the syrup sold-out switches, through adjustable syrup flow regulators,
through electrically-operated syrup solenoid valves, and on to the product blender tanks. At the same time, plain
water passes through the water pressure regulator and is pumped into the carbonated water tanks by the water
pump and is carbonated by CO2 gas pressure also entering the tank. Carbonated water is pushed by CO2 gas
pressure from the carbonated water tanks, through adjustable carbonated water flow regulators, through
electrically operated carbonated water solenoid valves, and on to the product blender tanks. Carbonated water and
syrup enter the tanks properly proportioned (blended) for desired BRIX of dispensed product by adjustment of the
syrup flow regulators. From product blender tanks, product is pushed by the CO2 gas into the freeze cylinders. The
beater in each freeze cylinder is driven by an electric motor. Scraper blades, attached to the beaters, scrapes
product from the cylinder walls as product enters the freeze cylinders and is frozen. Transparent faceplate,
attached to the front of each freeze cylinder, includes a self-closing dispensing valve and a spring-loaded relief
valve that protects freeze cylinder from accidental over pressure. The relief valve is also used to bleed CO2 gas
pressure from the freeze cylinder to atmosphere when filling the cylinder with product. Electronic sensing on each
freeze cylinder motor provides a means of adjusting viscosity (consistency) of the dispensed product to suit
customer preference.
DEFROST SYSTEMS
The Unit is equipped with both manual and automatic hot-gas defrost systems. The automatic defrost system may
be programmed into the Unit to occur up to nine different times a day with a minimum of two hours between defrost
time settings or the system may be completely turned off.
MANUAL DEFROST SYSTEM
The Manual hot-gas defrost system may be activated at any time by pressing the ‘‘DEFROST’’ switch on front of
the Unit. Refrigeration compressor will operate for a short time, then both freeze cylinders will go into defrost and
defrost for approximately 60-seconds. At the end of the manual defrost cycle, the Unit will return to normal
operation. Manual defrost may be cancelled at any time by pressing the ‘‘CANCEL DEFROST’’ switch.
AUTOMATIC DEFROST SYSTEM
The automatic hot-gas defrost system may be programmed into the Unit to occur up to nine different times a day
with a minimum of two hours between defrost settings. At the start of each automatic defrost cycle, refrigeration
compressor will operate for 30-seconds to pump freon out of the freeze cylinders evaporator coils. After freon has
been pumped out of the freeze cylinders evaporator coils, No. 1 freeze cylinder only will go into defrost cycle and
defrost for approximately 7-minutes, then will return to normal operation. This ends the automatic defrost cycle of
No. 1 freeze cylinder. No. 2 freeze cylinder will defrost 30-minutes after the start of No. 1 freeze cylinder. The next
automatic defrost cycle will occur according to the time programmed into the Unit. Automatic defrost may be
cancelled at any time by pressing the ‘‘CANCEL DEFROST’’ switch.
3312026000
‘‘SLEEP’’ (SLEEP TIME)
‘‘SLEEP’’ (SLEEP TIME) may be programmed into Unit to allow Unit to go into sleep time (Unit shut down, freeze
cylinders beaters and refrigeration systems not operating). At start of sleep time, refrigeration compressor will
operate for 30-seconds to pump freon out of freeze cylinders evaporator coils, then No. 1 freeze cylinder will go
into defrost and defrost for 60-seconds. After No. 1 freeze cylinder has defrosted, No. 2 freeze cylinder will go into
defrost and defrost for 60-seconds. At end of No. 2 freeze cylinder defrost, Unit will shut down and go into sleep
time.
‘‘WAKE UP’’ (WAKE UP TIME)
‘‘WAKE UP’’ (WAKE UP TIME) may be programmed into the Unit to allow Unit to resume normal operation at a
desired time. When programmed wake up time is reached, an alarm will sound for a short duration, then Unit will
resume normal operation.
NOTE: Automatic defrost, sleep time, and wake up time may be used in any combination together or
separately.
4312026000
*WATER PRESSURE REGULATOR IS
FACT ORY ADJUSTED TO 45–PSI AND
SHOULD NOT BE READJUSTED.
**SYRUP SOLD–OUT SWITCHES ARE
FACTORY ADJUSTED AND SHOULD
NOT BE READJUSTED.
LINE LEGEND
CO
2
PLAIN WATER
CARB WATER
SYRUP
PRODUCT
CARBONATOR
TANK
PRODUCT BLENDER
TANK(2)
PRODUCT SHUTOFF
VALVE(2)
FREEZE
CYLINDER(2)
FREEZE CYLINDER
OVERFLOW TUBE
PRODUCT SAMPLE
VALVE(2)
CARBONATED WATER
VOLUME SAMPLE VALVE
CARBONATED WATER
SOLENOID VALVE(2)
CARBONATED WATER
FLOW REGULATOR(2)
SYRUP SOLENOID
VALVE(2)
PRIMARY CO
REGULATOR ASS’Y
CO
2
CYLINDER
2
SYRUP SOLD–OUT
FLOAT SWITCH(2)
**SYRUP SOLD–OUT
SWITCH
CO
2
CHECK
VALVE
SYRUP FLOW
REGULATOR(2)
LIQUID CHECK
VALVE(2)
DOUBLE
LIQUID
CHECK
VALVE
CO
2
PRESSURE
SWITCH
CO
CHECK
2
VALVE(3)
SOFT DRINK
TANK(2)
SECONDARY CO2 REGULATORS
TO PRODUCT BLENDER
TANKS (60–PSI GAGE) (2)
SECONDARY CO2 REGULATOR
TO CARBONATOR TANK
(100–PSI GAGE)
FIGURE 2. FLOW DIAGRAM
CARBONATOR
WATER PUMP
*WATER PRESSURE
REGULATOR
WATER
PRESSURE
SWITCH
PLAIN WATER
SOURCE
3120260005
INSTALLATION
This section covers unpacking and inspection, installing LOOSE-SHIPPED PARTS, selecting location, installing
Unit, preparing for operation, and operation.
UNPACKING AND INSPECTION
(see Figure 4)
NOTE: The Unit was thoroughly inspected before leaving the factory and the carrier has accepted and
signed for it. Any damage or irregularities should be noted at time of delivery (or not later than 15 days
from date of delivery) and immediately reported to the delivering carrier. Request a written inspection
report from Claims Inspector to substantiate any necessary claim. File claim with the delivering carrier,
not with IMI Cornelius Inc.
1. After Unit has been unpacked, remove shipping tape and other packing material.
2. Remove Unit sides, top and back panels as instructed.
3. Unpack LOOSE-SHIPPED PARTS. Make sure all items are present and in good condition.
IDENTIFICATION OF LOOSE-SHIPPED PARTS
1. TAPERED GASKETS, WHITE (item 1) are used to seal connections when connecting Unit product inlet
lines to product tanks and connecting Unit CO2 inlet line to CO2 source.
2. SPANNER WRENCH, DISPENSING VALVE (item 2) is used to remove shank nuts securing dispensing
valves to faceplates.
3. CLEANING BRUSH (item 3) is used to clean faceplate relief valves passages.
Note: All parts for the Sound Baffle/Drip Tray Assembly are shipped with the Dispenser in a separate
box and must be installed on the Dispenser. Refer to Installation Instructions provided with the Sound
Baffle/Drip Tray Assembly for installation procedure.
4. TAPERED GASKET, BLACK (item 4) is used to seal connection when connecting plain water source line to
Unit water inlet line.
5. WRENCH, REAR SEAL HOUSING (item 5) used to remove the drive shaft/seal assembly from inside the
freeze cylinder.
6. TOOL, DRIVE/COUPLER ADJUSTMENT GAUGE (item 6) is used for servicing the beater motor drive
shaft/seal assembly (see Figure 7).
6312026000
7. CASTER KIT (item 7) to be installed on the Unit as instructed in Instructions provided in the Kit.
8. All parts for the SOUND BAFFLE/DRIP TRAY ASS’Y (item 8) are shipped with the Dispenser in a
separate box and must be installed on the Dispenser during Dispenser installation.
ELECTRICAL POWER REQUIREMENTS
IMPORTANT: Before connecting electrical power to Unit, refer to nameplate and Note if Unit is to be
operated with 50 or 60 Hz power source.
A properly grounded 198-253 VAC, 60Hz single-phase electrical circuit with a 30-amp minimum-rated
disconnect switch (not provided) fused at 30 amps (slow-blow) or circuit connected through an equivalent HACR
circuit breaker must be available to the Unit. ALL WIRING MUST CONFORM TO NATIONAL AND LOCAL
CODES. MAKE SURE UNIT IS PROPERLY GROUNDED.
SELECTING LOCATION
CAUTION: This Unit is intended for indoor installation only. Do not install this Unit in an
outdoor environment which would expose it to the outside elements.
IMPORTANT: Unit operating ambient temperature MUST NOT EXCEED 100° F. Operating ambient in
excess of 100° F will automatically void the factory warranty and will eventually result in Unit failure.
Several means are available to achieve proper ambient temperature and air circulation around the Unit
which are wall air intake grilles and ceiling exhaust fans, air conditioning, etc. Consult local codes.
Locate Unit so the following requirements are satisfied.
1. Close to a plain water inlet supply line with a minimum pressure of 12-psig.
NOTE: “AIR-COOLED FCB DISPENSER
The “air-cooled” FCB Dispenser refrigeration system is equipped with a condenser coil that is cooled
by a condenser coil fan. Circulating air, required to cool the refrigeration system’s condenser coil, is
drawn in through the grille on front and exhausted out through the sides and back of Unit. Restricting
air circulation through the Unit will decrease its cooling efficiency.
2. When installing Unit, do not allow obstruction to block grille on front which will block off air intake to inside
of Unit. If installation dictates only one side or back being unobstructed, allow 18-inches clearance between
Unit and obstruction. If both sides or one side and back are unobstructed, allow 12-inches clearance. If
both sides and back are unobstructed, allow 6-inches clearance.
CAUTION: Do not place or store anything on top of the Unit.
INSTALLING UNIT
PLACING UNIT IN OPERATING LOCATION
1. Place Unit in operating location meeting requirements of SELECTING LOCATION.
The FCB Dispensers manufactured prior to the model documented in this manual were elevated in the
front (dispensing valve side) 1/4 to 3/8-inch higher than the back when placing the Unit in operating
position to eliminate gas pockets being trapped inside the freeze cylinders. Due to a redesign of the foam
pack in the models documented in this manual, elevating the front of the Dispenser is no longer required.
The Dispenser must be leveled at time of placing in operating location.
IMPORTANT NOTICE
3120260007
Note: An alternate to sealing the Unit base to the floor would be to install the available 4-inch Caster Kit
(P/N 309570000).
2. After Unit has been placed in operating location, make sure it is sitting in a level position.
3. To comply with National Sanitation Foundation (NSF) requirements, Unit installed with base contacting floor
must have base sealed to floor with Dow Corning RTV 731 or equivalent.
INSTALLING SOUND BAFFLE/DRIP TRAY ASS’Y ON UNIT
All parts for the SOUND BAFFLE/DRIP TRAY ASS’Y (item 8) are shipped with the Dispenser in a separate
box. Refer to Installation Instructions provided with the Sound Baffle/Drip Tray Assembly and install as
instructed.
INSTALLING PRIMARY CO2 REGULATOR ASSEMBLY ON CO2 CYLINDER
(see Figure 2)
WARNING: To avoid personal injury and/or property damage, always secure CO2 cylinder in
upright position with a safety chain to prevent it from falling over. Should the valve become
accidentally damaged or broken off, CO2 cylinder can cause serious personal injury.
WARNING: CO2 displaces oxygen. Strict attention must be observed in the prevention of
CO2 (carbon dioxide) gas leaks in the entire CO2 and soft drink system. If a CO2 gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before
attempting to repair the leak. Personnel exposed to high concentration of CO2 gas will experience
tremors which are followed rapidly by loss of consciousness and suffocation.
1. Unscrew protector cap (with chain attached) from CO2 cylinder valve. Open CO2 cylinder valve slightly
counterclockwise to blow any dirt or dust from outlet fitting before installing primary CO2 regulator, then
close valve.
2. Remove shipping plug from primary CO2 regulator assembly coupling nut and make sure gasket is in place
inside nut. Install regulator assembly on CO2 cylinder so gages can be easily read, then tighten coupling
nut. DO NOT OPEN CO2 CYLINDER VALVE AT THIS TIME.
CONNECTING SOFT DRINK TANKS CO2 LINES TO PRIMARY CO2 REGULATOR
ASSEMBLY
(see Figure 2)
1. Connect soft drink tanks CO2 lines to primary CO2 regulator manifold assembly as shown in Figure 2.
2. Install gas quick disconnects on ends of soft drink tanks CO2 lines. DO NOT CONNECT CO2 LINES TO
TANKS AT THIS TIME.
PREPARING UNIT SYRUP INLET LINES FOR CONNECTION TO SOFT DRINK TANKS
(see Figure 2)
1. Route Unit syrup inlet lines, labeled No. 1 and No. 2, out through hole provided in the Unit base to the soft
drink tanks location.
8312026000
2. Install liquid disconnects on ends of Unit syrup inlet lines. DO NOT CONNECT SYRUP LINES TO TANKS
AT THIS TIME.
CONNECTING CITY PLAIN WATER SOURCE LINE (S) TO UNIT
NOTE: All of the Units require connection to a city plain water source line with a minimum water
pressure of 12-psig to be connected to the Unit plain water inlet line, which provides plain water to the
Unit post-mix system. The Unit equipped with a water-cooled refrigeration system also requires a city
plain water source line be connected to the refrigeration cooling coil assembly plain water inlet line.
Proceed as follows to connect a city plain water source line to the Unit.
Connecting City Plain Water Source Line to Unit Post-Mix System.
(see Figure 2)
NOTE: IMI Cornelius Inc. recommends that a water shutoff valve and water filter be installed in the city
plain water source line (see applicable Figure NO TAG) that provides plain water to the Dispenser
post-mix system. A Cornelius Water Filter (P/N 313860000) and Quick Disconnect Set (P/N 313867000)
are recommended.
1. Before connecting the city plain water source line to the Unit that provides plain water to the post-mix
system, open shutoff valve in city plain water source line for a period of time to flush out any metal
shavings.
2. Route Unit plain water inlet line out through hole in bottom of Unit base.
NOTE: The carbonator plain water inlet adjustable water pressure regulator (see Figure 2) is factory
adjusted to 45-psi and should not be readjusted.
3. Connect Unit plain water inlet line to the city plain water source line (12-psi minimum pressure). Seal
connection with TAPERED GASKET, BLACK (item 4). DO NOT OPEN THE CITY PLAIN WATER
SOURCE LINE SHUTOFF VALVE AT THIS TIME.
Connecting City Plain Water Source Line to Unit With Water-Cooled Refrigeration System.
(See Figure 16)
NOTE: The water-cooled Two-Flavor FCB Post-Mix Dispenser has one water-cooled refrigeration
system that requires connection of a City plain water source line to its refrigeration cooling coil plain
water inlet line. THE CITY PLAIN WATER SOURCE LINE MUST INCLUDE A WATER SHUTOFF VALVE.
Proceed as follows to connect the City plain water source line to the Dispenser refrigeration cooling
coil plain water inlet line.
1. Route the refrigeration cooling coil plain water inlet line labeled “COOLING WATER IN” and line labeled “
COOLING WATER OUT” out through hole in bottom of the Unit base.
2. Connect the refrigeration cooling coil plain water inlet line labeled “COOLING WATER IN” to the City plain
water inlet line. Seal connection with TAPERED GASKET, BLACK (item 4).
3. Route the line labeled “COOLING WATER OUT” to a permanent drain and connect. Seal connection with a
black TAPERED GASKET, BLACK (item 4).
3120260009
CONNECTING ELECTRICAL POWER CIRCUIT TO UNIT
(see Figure 17)
WARNING: Make sure disconnect switch (not provided) or equivalent HACR circuit breaker
is in ‘‘OFF’’ position.
IMPORTANT: Power circuit voltage across L1 and L2 terminals on the contactor inside the lower control
box, with refrigeration compressor operating, must be in the range of 198-253 VAC, 60Hz single-phase
for proper operation. Use No. 10 AWG copper wire, or larger, depending upon line length, in suitable
conduit or BX sheath. POWER CIRCUIT TO UNIT MUST BE MADE UP OF COPPER CONDUCTORS AND
ALL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES.
1. Remove lower control box (located on lower-right side facing front of Unit) cover for access to contactor
L1 and L
2. Connect electrical power from a 30-amp minimum-rated disconnect switch (not provided) fused at
30-amps slow-blow or through an equivalent HACR circuit breaker to L1 and L2 terminals on the contactor
inside the control box. MAKE SURE GROUND WIRE IS CONNECTED TO GREEN GROUND SCREW
INSIDE CONTROL BOX.
terminals.
2
WARNING: This Unit must be electrically grounded to avoid possible fatal electrical shock
or serious injury to the operator. A green screw, with lock washer, is provided inside
control box to connect power circuit ground wire electrically grounding the Unit.
3. Install lower control box cover and secure with screws.
PREPARATION FOR OPERATION
TURNING ON ELECTRICAL POWER TO UNIT
Turn on electrical power to Unit. Operational status of Unit is now being displayed as fault messages on control
panel message display. The following fault messages will be continuously displayed at 2-second intervals until
necessary operation requirements are satisfied.
‘‘OFF 1’’ (Beater Motor No. 1 not operating)
‘‘OFF 2’’ (Beater Motor No. 2 not operating)
‘‘H2O OUT’’ (No water supply to Unit)
‘‘CO2 OUT’’ (No CO2 gas supply to Unit)
‘‘SYRUP 1’’ (No syrup supply to Unit No. 1 syrup
system)
‘‘SYRUP 2’’ (No syrup supply to Unit No. 2 syrup
system)
TURNING ON CO2 SUPPLY TO UNIT
1. Open CO2 cylinder valve slightly to allow lines to slowly fill with gas, then open valve fully to back seat
valve. Back-seating valve prevents leakage around valve shaft.
IMPORTANT: If bag-in-box syrup supply system will be connected to the Unit instead of soft drink
tanks, the primary CO2 regulator (see figure 2) must be adjusted to no less than 80-PSI.
2. For soft drink tanks installation (see Figure 2), adjust primary CO2 regulator by turning regulator adjusting
screw to the right (clockwise) until regulator pressure reads 80 to 100-psig. OUT OF CO2 warning light on
control panel message display should have gone out.
312026000
10
3. Pull up on product blender tanks relief valves to purge air from tanks.
4. Remove Unit lower stainless steel access panel as instructed for access to carbonator secondary CO
regulators (see Figure 4).
5. Check product blender tanks secondary CO2 regulators with 60-psi gages for pressure setting which
should be set at 25 to 30-psi for best textured product. If further adjustment is necessary, adjust as
instructed.
IMPORTANT: The carbonated water tanks secondary CO2 regulators must be adjusted 25-psi higher or
more above product blender tanks secondary CO2 regulators pressure settings. Carbonated water and
syrup pressures must be able to overcome and vent product blender tanks head pressures while tanks
are filling with carbonated water and syrup. Carbonated water tanks secondary CO2 regulators not
adjusted high enough will cause decreased flow of carbonated water into the product blender tanks
which will increase brix of the dispensed product.
6. Adjust carbonated water tanks secondary CO2 regulators, with 100-psi gages, by turning regulators
adjusting screws to the right (clockwise) until gages reads 50 to 60-psi.
7. Pull up on carbonated water tanks relief valves plastic covers to purge air from the tanks.
2
TURNING ON CITY PLAIN WATER SOURCE LINE TO UNIT
City Plain Water Source Line Connected to Unit Post-Mix System (Water-Cooled and Air-Cooled Refrigeration
Units).
Open shutoff valve in City plain water line connected to the Unit Post-mix system. Check for water leaks and
tighten or repair if evident. ‘‘H2O OUT’’ fault message should have gone out but ‘‘SYRUP 1’’, and ‘‘SYRUP 2’’
fault messages will continue to be displayed.
City Plain Water Source Line Connected to Unit With Water-Cooled Refrigeration System.
Open shutoff valve in City water line connected to the refrigeration cooling coil assembly. Check for water leaks
and tighten or repair if evident.
CONNECTING SOFT DRINK TANKS TO UNIT SYRUP SYSTEMS
IMPORTANT: Product shutoff valves, located in lines leading from product blender tanks to freeze
cylinders (see Figure 2 and 5), must be closed at this time. Closing valves prevents product from
filling freeze cylinders while checking BRIX of product in product blender tanks.
1. Close product shutoff valves, located in lines leading from product blender tanks to freeze cylinders, to
prevent product from entering cylinders.
IMPORTANT: The following CO2 and liquid disconnects disconnecting and connecting procedure for
soft drink tank replacement or filling soft drink tank in place must be performed in order as follows:
To disconnect soft drink tank from Unit syrup system.
A.Disconnect liquid disconnect from soft drink tank. NOTE - Disconnecting liquid quick disconnect
from soft drink tank first prevents syrup from backflowing through Unit syrup flow regulator
which may alter regulator adjustment.
B.Second, disconnect CO2 quick disconnect from soft drink tank.
2. Pressurize soft drink tanks containing syrup, then connect tanks to Unit syrup systems. ‘‘OFF 1’’, ‘‘OFF 2’’,
‘‘SYRUP 1’’, and ‘‘SYRUP 2’’ fault messages will continue to be displayed.
11312026000
ADJUSTING BRIX (WATER-TO-SYRUP) ‘‘RATIO’’ OF DISPENSED PRODUCT
NOTE: The Unit is equipped with one control panel (see Figure 4) which controls operation of the two
freeze cylinders. The Unit control panel is equipped with a hidden ‘‘SECURITY SWITCH’’ located
between ‘‘FILL 1’’ and ‘‘ERROR RESET’’ control switches (see Figure 4). Pressing in and holding the
‘‘SECURITY SWITCH’’ for 10-seconds deactivates the control switches preventing tampering with the
Unit normal operation. To reactivate the control switches, press in and hold the ‘‘SECURITY SWITCH’’
for 10-seconds.
The following steps 1 through 9 are instructions for adjusting Brix (Water-to-Syrup ‘‘Ratio’’ (mixture) of
dispensed product on one of the two systems.
Note: The adjustable carbonated water flow regulators (see Figure 2 and 13 ) located in their respective
systems, control carbonated water flow rate to the product blender tanks. The water flow regulators are
factory adjusted at 1.3 0.05 oz/sec and should not normally require adjustment. If adjustment is
necessary, adjust as instructed.
1. Press ‘‘FILL 1’’ switch to fill No. 1 syrup system sold-out float. ‘‘SYRUP 1’’ fault message will go out and
‘‘FILL 1’’ fault message will come on. ‘‘OFF 1’’, ‘‘OFF 2’’, and ‘‘SYRUP 2’’ fault messages will continue to be
displayed.
2. Press ‘‘AUTO BLEND 1’’ switch to fill No. 1 system product blender tank with product. ‘‘FILL 1’’ fault
message will go out when ‘‘AUTO BLEND 1’’ switch is pressed. When product blender tank is full, press
‘‘FILL 1’’ switch to prevent more product from entering tank.
‘‘OFF 1’’, ‘‘OFF 2’’, and ‘‘SYRUP 2’’ fault messages will continue to be displayed.
3. Open No. 1 product blender tank product sample valve (see Figure 2) and take sample (approximately
6-ounces) of product in a cup or glass.
NOTE: Temperature compensated hand-type refractometers (P/N 511004000) are available from The
Cornelius Company.
4. Check product BRIX with a temperature compensated hand-type refractometer. BRIX should read 13 ± 1.
If BRIX is not within tolerance, adjust white syrup flow regulator for No. 1 syrup system as follows:
Turn regulator adjusting screw to the left (counterclockwise) no more than 1/8-turn at a time to reduce
syrup flow rate or turn screw to the right (clockwise) no more than 1/8-turn to increase flow rate.
5. Place container under No. 1 product sample valve. Open valve to purge product out of product blender
tank, line, and valve, then close valve. ‘‘OFF 1’’, ‘‘OFF 2’’, and ‘‘SYRUP 2’’ will continue to be displayed.
6. Press ‘‘AUTO BLEND 1’’ switch to run new batch of product into product blender tank. When product
blender tank is full, press
‘‘FILL 1’’ switch to prevent more product from entering product blender tank. ‘‘OFF 1’’,
‘‘OFF 2’’, and ‘‘SYRUP 2’’ fault messages will continue to be displayed.
7. Repeat steps 3 and 4 preceding to check product sample for BRIX.
8. Repeat steps 5 through 7 preceding until proper BRIX adjustment is achieved.
9. Repeat steps 1 through 8 preceding to adjust BRIX of dispensed product on No. 2 system. After
completing BRIX adjustment on No. 2 system, only the ‘‘OFF 1’’ and ‘‘OFF 2’’ fault messages should
continue to be displayed.
NOTE: Syrup systems may be sanitized at this time as instructed.
FILLING FREEZE CYLINDERS WITH PRODUCT
1. Open product shutoff valves, located in lines leading from product blender tanks to freeze cylinders.
2. Press ‘‘AUTO BLEND 1’’ and ‘‘AUTO BLEND 2’’ switches to begin filling freeze cylinders. Open freeze
cylinders faceplates relief valves to bleed air from cylinders while filling with product, then close valves. Do
not relieve freeze cylinder pressure too fast or product will foam excessively in cylinder and lose
carbonation.
312026000
12
ADJUSTING “WATER-COOLED” UNIT REFRIGERATION SYSTEM VARIABLE WATER
REGULATOR
IMPORTANT NOTICE
Water-Cooled Refrigeration System Dispenser.
Water flow rate through the refrigeration cooling coil varies due to pressure change on the high side
of the refrigeration compressor which influences opening and closing of the variable water regulator (see Figure 16). The variable water regulator must be adjusted to maintain 240-psi refrigeration
high-side pressure.
Adjust the variable water regulator (see Figure 16) to maintain 240-psi refrigeration high-side pressure as
instructed in the SERVICE AND MAINTENANCE section.
ADJUSTING BEATER MOTOR CURRENT (EITHER SIDE)
1. Remove four screws securing the upper control box cover, then remove cover for access to the master
circuit board inside the control box.
2. Adjust beaters motors currents as instructed in SERVICE AND MAINTENANCE section.
PROGRAMMING MAIN MENU SELECTIONS ONTO the MESSAGE DISPLAY
The MAIN MENU SELECTIONS (see Table 3) may be brought up on message display as instructed in
SERVICE AND MAINTENANCE section.
Program ‘‘CLOCK’’ (TIME OF DAY) into Unit as instructed in SERVICE AND MAINTENANCE section.
PROGRAMMING ‘‘DEFROST’’ (AUTOMATIC) SETTINGS INTO the UNIT
The automatic defrost system may be programmed into the Unit to occur up to nine different times during a day
with a minimum of two hours between defrost time settings. Program automatic defrost time settings into the
Unit as instructed in SERVICE AND MAINTENANCE section.
PROGRAMMING ‘‘SLEEP’’ (SLEEP TIME) INTO the UNIT
‘‘SLEEP’’ (SLEEP TIME) may be programmed into the Unit to occur any time of the day after the Unit automatic
defrost cycle has occurred. The Unit will shut down (go into sleep time) and will not wake up (return to normal
operation) until programmed ‘‘WAKE UP’’ (WAKE UP TIME) has occurred. Program ‘‘SLEEP’’ (SLEEP TIME)
into the Unit as instructed in SERVICE AND MAINTENANCE section.
PROGRAMMING ‘‘WAKE UP’’ (WAKE UP) TIME INTO the UNIT
‘‘WAKE UP’’ (WAKE UP TIME) May be programmed into the Unit to occur any time of the day to wake the Unit
up (return to normal operation) after ‘‘sleep time’’ has occurred. Program ‘‘WAKE UP’’ into the Unit as instructed
in SERVICE AND MAINTENANCE section.
PROGRAMMING POINT OF SALE MESSAGE DISPLAY
Three point of sale display messages are available to choose from and may be programmed into the Unit by
placing No. 1 and No. 2 switches on the DIP SWITCH assembly on the master circuit board in appropriate
positions. Program point of sale display messages into the Unit as instructed in SERVICE AND MAINTENANCE
section.
13312026000
ADJUSTING ‘‘VIS SET’’ (PRODUCT VISCOSITY) OF DISPENSED PRODUCT
Adjust ‘‘VIS SET’’ (PRODUCT VISCOSITY) determines what product consistency of the dispensed product will
be present in each freeze cylinder. Adjust ‘‘VIS SET’’ (PRODUCT VISCOSITY) of the dispensed product as
instructed in SERVICE AND MAINTENANCE section.
“VIS READ” (ACTUAL VISCOSITY READOUT) OF PRODUCT IN FREEZE CYLINDERS
“VIS READ” (actual viscosity readout) may be brought up on the message display to actually read the viscosity
(product consistency) of product in the freeze cylinders while the Unit is in operation as instructed in SERVICE
AND MAINTENANCE section.
DISPLAYED EVAPORATOR REFRIGERATION COILS INLETS AND COMMON OUTLET
SENSORS TEMPERATURES
Evaporator refrigeration coils inlet and common outlet temperature readings in degrees Fahrenheit may be
displayed on the message display as instructed in SERVICE AND MAINTENANCE section.
‘‘VOLTAGE’’ (DISPLAYED VOLTAGE READOUT)
Displayed voltage readout may be displayed on the message display as instructed in SERVICE AND
MAINTENANCE section.
PROGRAMMING COMPONENTS ‘‘DIAGNOSE’’ (DIAGNOSTIC MODE) INTO the UNIT
‘‘DIAGNOSE’’ (DIAGNOSTIC MODE) may be programmed into the Unit to check certain components for
operation. Program ‘‘DIAGNOSE’’ into Unit the and check components for proper operation as instructed in
SERVICE AND MAINTENANCE section.
DISPLAYING ‘‘TOTALS’’ (DISPLAYED CYCLES AND HOURS TOTALS) ONTO the
MESSAGE DISPLAY
‘‘TOTALS’’ (DISPLAYED CYCLES AND HOURS TOTALS) may be displayed on the message display as
instructed in SERVICE AND MAINTENANCE section.
PROGRAMMING FREEZE CYLINDERS BEATER “MOTORS” INTO UNIT ELECTRONICS
IMPORTANT: Note in TABLE 5 MOTOR SELECT the number of freeze cylinders beater drive motors
Manufacturer’s that are listed. Your Unit was manufactured and equipped with freeze cylinders beater
drive motors from one of these Manufacturer’s. The beater motors were programmed at the factory to
match the Unit electronics. THE BEATER MOTORS PROGRAMMING MUST BE RE-CHECKED AT THE
TIME OF UNIT INSTALLATION as instructed in “PROGRAMMING FREEZE CYLINDERS BEATER
MOTORS INTO UNIT ELECTRONICS” in SERVICE AND MAINTENANCE section.
PROGRAMMING PROPER REFRIGERANT TYPE INTO UNIT ELECTRONICS
The Dispenser electronics must be programmed for the proper refrigeration pulse rate according to the type of
refrigerant gas that has been installed in the refrigeration system. Note Dispenser serial plate for the type of
refrigerant gas that has been installed, then proceed to SERVICE AND MAINTENANCE section for
programming instructions.
312026000
14
DISPLAYED ERROR CONDITIONS
Displayed error conditions, associated errors, and items affected by the errors are found in Table 8
DISPLAYED ERROR CONDITIONS.
INSTALLING CONTROL BOX COVER AND BACK, SIDES LOWER ACCESS,
AND TOP PANELS ON UNIT
1. Install upper electrical control box cover and secure with four screws.
2. Install back, sides, lower access, and top panels on Unit by reversing removal procedures.
15312026000
THIS PAGE LEFT BLANK INTENTIONALLY
16312026000
OPERATORS INSTRUCTIONS
This section describes operating controls and indicators, dispensed product conditions, operating
characteristics, Unit operation, replenishing syrup supply, product flavor change, checking CO supply, operators
daily cleaning of Unit, and sanitizing requirements.
WARNING: Disconnect electrical power to the Unit to prevent personnel injury before
attempting any internal maintenance. Only qualified personnel should service internal
components or electrical wiring.
NOTE: The No. 1 freeze cylinder (see Figure 4) is the left-hand cylinder facing the front of the Unit. No.
2 freeze cylinder is to the right of No. 1 freeze cylinder.
CONTROL PANEL SWITCHES AND DISPLAYED MESSAGES
CONTROL PANEL SWITCHES
The Unit is equipped with one control panel which is equipped with a message display (See Figure 4).
The control panel controls operation of the No. 1 and the No. 2 freeze cylinders.
‘‘FILL 1’’ and ‘‘FILL 2’’ Control Switches.
‘‘FILL 1’’ and ‘‘FILL 2’’ control switches, located on control panel (see Figure 4), are touch-type switches and
require only pressing to activate. ‘‘FILL 1’’ and ‘‘FILL 2’’ control switches are used when filling syrup systems
sold-out floats during syrup replenishing, syrup flavor changeover, or sanitizing syrup systems. After syrup
systems sold-out floats have been filled, ‘‘FILL 1’’ and ‘‘FILL 2’’ switches may be used to prevent more product
entering product blender tanks during BRIX test.
‘‘AUTO BLEND 1’’ and ‘‘AUTO BLEND 2’’ Control Switches.
‘‘AUTO BLEND 1’’ and ‘‘AUTO BLEND 2’’ control switches, located on control panel (see Figure 4), are
touch-type switches and require only pressing to activate. These switches are used to fill product blender tanks
after sold-out floats have been filled using ‘‘FILL 1’’ and ‘‘FILL 2’’ switches. ‘‘AUTO BLEND 1’’ and ‘‘AUTO
BLEND 2’’ and ‘‘AUTO 1’’ and ‘‘AUTO 2’’ switches must be pressed to operate freeze cylinders beaters and
refrigeration system during normal operation.
‘‘WASH 1’’ and ‘‘WASH 2’’ Control Switches.
‘‘WASH 1’’ and ‘‘WASH 2’’ control switches, located on control panel (see Figure 4), are touch-type switches and
require only pressing to activate. These switches are used to operate freeze cylinders beaters with no
refrigeration during sanitizing.
’’AUTO 1’’ and ‘‘AUTO 2’’ Control Switches.
‘‘AUTO 1’’ and ‘‘AUTO 2’’ control switches, located on control panel (see Figure 4), are touch-type switches and
require only pressing to activate. These switches are used to operate freeze cylinders beaters and refrigeration
system after cylinders have been filled with product. Freeze cylinders beaters and refrigeration system may be
stopped by pressing ‘‘OFF 1’’ or ‘‘OFF 2’’ switches.
‘‘OFF 1’’ and ‘‘OFF 2’’ Control Switches.
‘‘OFF 1’’ and ‘‘OFF 2’’ control switches, located on control panel (see Figure 4), are touch-type switches and
require only pressing to activate. These switches are used to stop freeze cylinders beaters and refrigeration
system.
17312026000
Loading...
+ 54 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.