Cornelius Cold Beverage Dispenser User Manual

INTELLICARB
Training Manual
Release Date: April 29, 2004 Publication Number: TP01071 Revision Date: NA Revision: A Visit the IMI Cornelius web site at www.cornelius.com
for all your Literature needs.
INTELLICARB TRAINING MANUAL
The products, technical information, and instructions contained in this manual are subject to change without notice. These instructions are not intended to cover all details or varia­tions of the equipment, nor to provide for every possible contingency in the installation, operation or maintenance of this equipment. This manual assumes that the person(s) working on the equipment have been trained and are skilled in working with electrical, plumbing, pneumatic, and mechanical equipment. It is assumed that appropriate safety precautions are taken and that all local safety and construction requirements are being met, in addition to the information contained in this manual.
To inquire about current revisions of this and other documentation or for assistance with any Cornelius product contact:
www.cornelius.com
800-238-3600
Trademarks and copyrights: Aurora, Cornelius, Decade, Hydro Boost, Sitco, Spirit, UF-1, Vanguard, Venture, Olympus,
and Vista are registered trademarks of IMI Cornelius Inc. Optifill trademark is pending.
This document contains proprietary information and it may not be
reproduced in any way without permission from Cornelius.
Printed in U.S.A.
Copyright © 2004, All Rights Reserved, IMI Cornelius Inc.
InelliCarb Training Manual
TABLE OF CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Delivery Inspection and Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Cornelius IntelliCarb Carbonator Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Carbonator Time Out Reset Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Carbonator Relief Valve Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Mechanical Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Gate Restrictor Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Ice Diverter Kit 02394 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Removal and Replacement of Agitators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
To Remove Agitators For Cleaning (300 shown) . . . . . . . . . . . . . . . . . . . . . . . .10
Post-Mix Valve Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Set-up Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Dimensions & Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
System Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Water Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Adjusting Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Calculating Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Syrup/Concentrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Setting Ratios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Shurflo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Shurflow Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Shurflow Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Plumbing Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Flow Diagram 1xx (Six Flavor Model) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Flow Diagram 1XX (Eight Flavor Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Flow Diagram 2xx (Eight Flavor Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Flow Diagram 2xx (Ten Flavor Models)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Flow Diagram 300 (Twelve Flavor Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
© 2004, IMI Cornelius Inc. - i - Publication Number: TP01071
IntelliCarb Training Manual
Electrical Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Carbonator Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Wiring Diagram 1xx (120V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Schematic 1xx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Wiring Diagram 2xx (120V Model) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Wiring Diagram 2xx (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Wiring Diagram 2xx (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Wiring Diagram 300 (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Wiring Diagram 300 (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Schematic 300 (120V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Schematic 300 (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
SHURflow Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Pumping Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Pumps in Series for Long Distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Pump Sanitizing / Winterizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Pump Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
DOES NOT OPERATE / GAS APPLIED / DISPENSER VALVE OPEN . . . 37
OPERATES BUT WILL NOT PRIME / DISPENSER VALVE OPEN . . . . . .37
DOES NOT ACHIEVE SOLD-OUT WITH EMPTY B-I-B . . . . . . . . . . . . . . . 37
AIR IN INLET AND/OR OUTLET TUBING . . . . . . . . . . . . . . . . . . . . . . . . . .37
STROKES WITH DISPENSER VALVE CLOSED . . . . . . . . . . . . . . . . . . . . 37
FLUID FROM EXHAUST OR VISIBLE WITHIN GAS INLET TUBING . . . . . 37
GAS BLOWING FROM EXHAUST CONTINUOUSLY . . . . . . . . . . . . . . . . . 37
Dispenser Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Valve Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Excess Foam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Off Taste . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Valve Stuck Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
No Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Carbonator Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Solid State Carbonator Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Test Solid State Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Publication Number: TP01071 - ii - © 2004, IMI Cornelius Inc.
UNIT DESCRIPTION
Built-in cold carbonator produces bottle-quality drinks every time
InelliCarb Training Manual
INTRODUCTION
No seasonal CO
A complete system for simplified installation
Reduces service frequency and lowers equipment life cost
Generates increased beverage sales and greater consumer satisfaction
Illuminated merchandiser delivers unique, high impact marketing message
Ice used to cool cold plate kept separate from ice dispensed into cups
One piece ABS thermoformed plastic ice storage hopper. Durabide design provides durability and
ensures all ice in the hopper is dispensable
Unit readily accepts top mount cubers with manual ice fill capability
adjustments required for changes in water temperature
2
THEORY OF OPERATION
The rate of CO2 solubility increases with cold water. IntelliCarb System provides pre–chilled cold water from the cold plate and mix with CO high volume 125gph Procon pump and high torque motor.
The amount of carbonated water reserve is controlled by a probe mounted in the tank. The probe is called a liquid level probe. The liquid level probe senses the water level in the tank. Probe controls the pump ON and OFF cycle through the electronic board called liquid level board”.
NOTE: The probe works on a 5 M.V. D.C. current that continually reverses direction to prevent probe corrosion.
in the carbonator tank. The water is introduced into the tank with a
2
DESCRIPTION
The Enduro IntelliCarb series of ice dispensers solves your ice and beverage service needs in a sanitary, space saving, economical way. Designed to be automatically filled with ice from a top mounted ice machine or manually filled with ice from any remote ice-making source, these dispensers will dispense cubes (up to 1-1/4 inch in size), cubelets, and hard-chipped or cracked ice. In addition, the units include beverage faucets, a cold plate, an internal carbonator tank and an external pump for the carbonator, and are designed to be supplied direct from syrup tanks with no additional cooling required.
IMPORTANT: For dispensing compressed or extruded style ice, an Ice Diverter Kit must be installed on the dispenser, see FIGURE 13 on page 9.
© 2004, IMI Cornelius Inc. - 1 - Publication Number: TP01071
IntelliCarb Training Manual
SPECIFICATIONS
ED150 ED175 ED200 ED250 ED300
B=(Beverage)
Model
Descriptions:
Ice Storage:
Maximum
Number of
Faucets
Available:
Built-in Cold
Plate:
Electrical:
Dimensions:
CO
2 Operating
Pressure
C=(Coldplate) H=(Internal Carb) Z=(No DripTray) 150 Pounds 175 Pounds 200 Pounds 250 Pounds 300 Pounds
Yes Yes Yes Yes Yes
$PSV7RWDO8QLW'UDZ 120/1/60, 3.5 Amps Total Unit Draw
Width 22 Deep 30--11/16 High 35--5/8
Z--Models Width 22
Deep 23--1/16” High 35--5/8” 75--psig (max) 75--psig (max) 75–psig (max) 75–psig (max) 75–psig (max)
B=(Beverage) C=(Coldplate) H=(Internal Carb) Z=(No DripTray)
6 8 10 10 12
Outlet should be within 6 feet of dispenser.
Width 24.5 Deep 30--11/16 High 35--5/8
Width 24--1/2 Deep 23--1/16 High 35--5/8
B=(Beverage) C=(Coldplate) H=(Internal Carb) Z=(No DripTray)
230/1/50, 2.0 Amps Total Unit Draw
Width 22 Deep 30–11/16” High 35–5/8”
Z–Models Width 22
Deep 23–1/16” High 35–5/8”
B=(Beverage) C=(Coldplate) H=(Internal Carb) Z=(No DripTray)
Width 24.5 Deep 30–11/16” High 39–5/8”
Width 24–1/2” Deep 23–1/16” High 39–5/8”
B=(Beverage) C=(Coldplate) H=(Internal Carb) Z=(No DripTray)
120/1/60, 4.0 Amps Total Unit Draw 230/1/50, 3.0 Amps Total Unit Draw
Width 44–3/8” Deep 31–1/2” High 37
Z–Models Width 44–3/8”
Deep 23–1/16” High 37
REQUIREMENTS
Weight: counter must be level and able to support 450 lbs.
Environment: Indoor installation only
Temp eratu re: 40 to 100
CO2: 75 psi at unit
Syrup: 60 psi., 0.70 -- 0.75 ounces per sec. (0.6 gpm) at unit
Water: 60 psi at pump
Electrical: See name plate
o
F
DELIVERY INSPECTION AND UNPACKING
Upon delivery inspect the unit for damage or irregularities and immediately report problems to the delivering carrier and file a claim with that carrier.
Open loose parts packages and inspect parts.
Part No. Description Qty.
710000030 Pump and Motor Assy 1
70970 4Legs 4 70750 Clamps 2
620702201 Brush 1
51774 Drain Pan Drain Line 1 50335 Drain Line Insulation 1
 )LWWLQJ6RF[)SW 1  )LWWLQJ0SW[µ%DUE 1
Publication Number: TP01071 - 2 - © 2004, IMI Cornelius Inc.
INSTALLATION
1. Locate the dispenser indoors on a level counter top.
A. LEG OPTION
Unpack the four (4) legs and install them into the threaded holes provided in the bottom of the unit. The installer must provide flexibility in the product and utility supply to permit shifting the position of the dispenser sufficiently to clean the area beneath it.
B. COUNTER MOUNTING
If counter mounted the ice drink dispenser must be sealed to the counter. The template drawing indicates where openings can be cut in the counter. Locate the desired position for the dispenser, then mark the outline dimensions on the counter using the template drawings. Cut openings in counter. Apply a continuous bead of NSF International (NSF) silastic sealant (Dow 732 or equal) approxi­mately 1/4--inch inside of the unit outline dimensions and around all openings. Then, position the unit on the counter within the outline dimensions. All excess sealant must be wiped away immedi­ately.
2. The beverage tubes, drain tube and power cord are routed through the large opening in the bottom
of the unit. See the mounting template for locating the required clearance opening in the counter for these utility lines.
3. Drip tray assembly: Route the drain tube to an open drain with the end of the tube above the “flood”
level of the drain. Use the tubing, fittings, clamps, and insulation provided with the Dispenser to assemble the drain. The completed drain line must pitch continuously downward and contain no traps or improper drainage will result. Must have a 4 inch air gap between drain line and drain.
NOTE: This equipment must be installed with adequate backflow protection to comply with fed­eral, state, and local codes.
InelliCarb Training Manual
NOTE: IMI Cornelius Inc. recommends that a water shutoff valve and water filter be installed in the plain water inlet supply line. A Cornelius Water Filter (P/N 313860000) and QUICK DISCON­NECT SET (P/N 313867000) are recommended.
CAUTION: Check the minimum flow rate and the maximum pressure of the plain water inlet supply line. MINUMUM FLOW RATE MUST BE AT LEAST 125--GALLONS PER HOUR. If flow rate is less than 125-
-gallons per hour, starving of the carbonator water pump will occur. Starving will damage the water pump and could cause the carbonator to time out. INCOMING PLAIN WATER INLET SUPPLY LINE WATER TO PUMP PRESSURE MUST REMAIN A MINIMUM OF 10--PSI BELOW THE CARBONATOR C
O2
OPERATING PRESSURE. (Example: Carbonator CO2 operating pressure is 75--PSI and the maximum water pressure can be no more than 65--psi, etc.). Water over pressure (higher than C
O2 operating pres-
sure) can cause carbonator flooding, malfunction, and leakage through the carbonator relief valve. If water is exceeding maximum pressure specifications, a Water Pressure Regulator Kit (P/N 310150000) or equivalent must be installed in the plain water inlet supply line. If fitting connector is not available, water line must be 1/2 or 3/4 diameter with a shut off valve within 6 feet of the dispenser.
4. Locate the carbonator pump assembly and connect probe wires from Ice/Drink Unit and pump. Con-
nect inlet water to pump and pump outlet to Ice/Drink Unit using 3/8--inch food--grade tubing.
NOTE: Locate carbonator assembly within 6 feet of the dispenser. Do not lengthen the control board harness.
5. Connect the beverage system product tubes as indicated in applicable Plumbing Flow Diagram, see
page 19. This work should be done by a qualified service person.
NOTE: Water pressure for non carbonated beverages must be 60 P.S.I. minimum.
NOTE: See applicable Flow Diagram or Decal on the lower front of the unit for the location of syrup and water connections.
6. Clean the hopper interior.
7. Connect the two power cords to a 120 volt, 60 cycle, 3-wire grounded receptacle. For 220--240 Volt
International Units, a 3--wire power cord is provided. An adapter plug for the particular country will need to be provided by the Installer.
© 2004, IMI Cornelius Inc. - 3 - Publication Number: TP01071
IntelliCarb Training Manual
Drains
Use a 1 - 1/2 rigid pipe (e.g. ABS on P.V.C.) this is to prevent kinking or collapsing. Make sure to leave a 4 inch air gap between the drain line and the floor drain.
CORNELIUS INTELLICARB CARBONATOR ASSEMBLY
1. Ice Drink / Drop-In Carbonator Pump & Motor Unit
Vent to Atmosphere Check Valve
Liquid Level Control Box
Preset CO2 Regulator (75P.S.I.)
Carbonator Time Out Reset Switch
The board can be set to turn the carbonator off after three or seven minutes of continuos time. The fea­ture can also be disabled. See the carbonator instruction in this manual.
FIGURE 2 FIGURE 3
1. Locate carbonator assembly below dispenser no more than 6 feet away. Important: Make sure there is clearance for the liquid level control reset switch on the side of the control box to avoid accidentally tripping the switch. The control board has an internal timer to prevent the
pump motor from running continuously. In the event of a water supply interruption or malfunction of the water level probe and/or motor relay circuit. If there is a time-out event, make necessary repairs to what caused the time out, then depress and release the reset switch to put the control board back in service. By moving a jumper on the control you can select either a 7 minute or 3 minute time out or this feature can also be disabled.
A. Hook-up a 3/8 ID water supply line 125 G.P.H. minimum (60 psig. max.) to pump inlet. Minimum
flowing pressure is 30 psig. Important: Tap for non-carb water supply must be upstream of
pump inlet. Do not tap in the pump outlet.
B. Hook-up a 3/8 (.375 ID) CO
psig.) on the Pump & Motor base. Note: If using a bulk CO
regulator must be set to 100-105 psig. The regulator on the bulk tank should be a second­ary.
supply line (100 psig.) to the inlet of the pre-set CO2 regulator (75
2
FIGURE 1
Carbonator Time Out Reset Switch
Time Out
Selector Pins
Liquid Level
Control Board
125 G.P.H. ProCon Water Pump
High Torque Pump Motor
tank as supply, tank pressure
2
Publication Number: TP01071 - 4 - © 2004, IMI Cornelius Inc.
C. Initial start-up procedure for carbonated water system: Turn on the CO2 supply to the car-
bonator tank, vent air from carbonator tank by pulling the tank relief valve. Turn on water supply to the pump. Connect electrical power to the pump and motor unit. Bleed the air out of the system by energizing a beverage valve until carbonated water is flowing from the valve.
NOTE:If the carbonator Pump and Motor does not cycle (turn on and off) properly, check that the probe harness connector and ground lead are secured to the carbonator tank connection points.
D. If service is required on Ice Drink units, it will be necessary to lower the beverage valve panel to
gain access to the probe and ground connection. Remove the lower front panel (2 screws) from the cabinet and the ice chute cover (“snap” fit). Remove the 6 screws that secure the beverage panel to the cabinet. The panel can now be moved downward due to the flexibility of the beverage tubing to expose the carbonator tank connections.
Carbonator Relief Valve Locations
The carbonator tank is located behind the splash panel, on the right side of the dispenser. You will need to pull the relief valves to purge air from the system after the CO
do this will cause low carbonation volume and popping of the relief valves.
Relief
Valve Ring
Agitator
Motor
Carbonator
Tan k
Carbonator
Tank Relief
Valve
InelliCarb Training Manual
supply has been hooked up. Failure to
2
2. Dispenser
Total Flex Manifold
(with insulation)
Cold Plate Inlets
(3/8 Barb)
Carb. Tank Liquid
Level Probe Harness
FIGURE 6
FIGURE 7
Ice Drink Model ED175BCH (Lower Front Panel Removed)
FIGURE 8
Insulated Cold Plate Cover & Carbonator Tank Assembly
Total Flex Manifold (insulation removed)
Carb Tank CO2 Supply Line
© 2004, IMI Cornelius Inc. - 5 - Publication Number: TP01071
IntelliCarb Training Manual
Ice Drink Model ED150/175/300 Coldplate Cover
Liquid Level Probe
CO2 Check Valve with Ground Stud
FIGURE 9
Ice Drink Model ED200/250 Coldplate Cover
In-line CO2 Check Valve
3. Total Flex System for Ice Drink Models ED150/175/200/250/300
Total Flex Manifold (Insulation Removed)
Water Line
Retainer Clip
Probe
FIGURE 10
Ground Plate/Stud
Plugs
Manifold Block
FIGURE 11
Total Flex is a system of water manifold blocks located at the front of the cold plate, adjacent to the cold plate inlets, for easy switch over of carbonated / non-carbonated beverage drinks. The right hand mani­fold block is for the beverage valves located to the right side of the ice chute, and the left block is for the left bank of valves. Each beverage valve on the dispenser can be set up for either carbonated or non-car­bonated drinks. Refer to the units plumbing diagram for the factory carbonated / non-carbonated valve locations. The procedure for switching carbonated / non-carbonated water lines on a beverage valve is as follows:
A. Shut off the water supply to the dispenser. Depressurize and drain both the carbonated and non-
carbonated water circuits.
B. Remove the retainer clip (2 screws) from the manifold block. Switch the plug and water line fitting
to their respective carbonated / non-carbonated outlet locations on the block.
C. Replace the retainer clip. Turn on the water supply and energize the “switched” valve(s). Check
for water leaks.
4. Important: Route the dispensers drain line to an open drain with the end of the tube above the flood level of the drain. The drain line must pitch downward and contain no “traps”.
5. Connect both the carbonator pump and motor unit and the dispenser to a grounded
electrical sup-
ply outlet.
Publication Number: TP01071 - 6 - © 2004, IMI Cornelius Inc.
IntelliCarb Training Manual
6. Check list for proper “finished” drink carbonation:
A. Fill ice storage hopper with ice. B. Water supply must be from a continuous source (no tank supply). C. Use only filtered water. D. Supply water line to the carbonator pump must be a minimum of .375 ID. E. Syrup supply lines must be a minimum of .265 ID. F. Water inlet pressure range: 45-60 max. static psig. with a minimum flowing pressure of 30 psig. G. Syrup CO
H. CO
2
secondary regulator pressure set to 60 psig.
2
supply must be high quality, food grade.
I. Purge all water, carb-water, and product lines of air before brixing valves. J. Important: Brix valves with cold product. Allow at least 15-20 minutes for ice to cool down the
coldplate on initial start-up before brixing the valves.
K. Dispense at least (2) 12 oz. drinks before taking a carbonation level reading. L. Carbonation tester thermometer must read 32-33
o
F. for accurate carb-level reading. Store tester
in ice water bath during use.
M. Hold cup at valve nozzle for drink to be tested. Pour drink slowly down the side wall into the carb-
tester to avoid agitation during pouring. Press vent valve once on carb-tester after tightening lid.
N. Shake carb-tester in vertical motion until peak pressure reading is obtained. Use Pepsi chart for
carbonation level reading.
NOTE: Carbonator troubleshooting procedure located on page 43.
© 2004, IMI Cornelius Inc. - 7 - Publication Number: TP01071
IntelliCarb Training Manual
MECHANICAL SECTION
GATE RESTRICTOR PLATE
NOTE: Disconnect power to dispenser before installing, removing, or adjusting restrictor.
ADJUSTMENT
Adjustment
This plate may be adjusted as shown to reduce or increase the dispensing rate of ice, especially desirable when using glasses or other containers with small openings. Adjustment can be made by sliding up or down with nuts loosened, to obtain the desired amount of restriction.
INSTALL PLATE
ON STUDS AS
SHOWN
FIGURE 12
Publication Number: TP01071 - 8 - © 2004, IMI Cornelius Inc.
ICE DIVERTER KIT 02394
NOTE: For dispensing Scotsman, Wilshire, and Hoshizaki compressed ice cubes:
1. Disconnect power to dispenser.
2. Remove Merchandiser from dispenser.
3. Remove ice chute and discard gate restrictor.
4. Install ice diverter on gate mounting plate as shown below.
5. Apply RTV to back surface of ice diverter, to seal to gate mounting plate.
6. Reinstall gasket and ice chute.
7. Reinstall merchandiser and energize unit.
IntelliCarb Training Manual
IC E C H UT E
COVE R
10--32 WA S HE R
GATE MOUNTING P LATE
IC E DIV E R T E R
IC E C H UT E
GASKET
STORAGE HOPPER
FLANGE E XTENDS
INTO S TORA GE HOP-
PER THROUGH GATE
OPE NING
APPLY RTV TO
THIS SUR FACE TO
SEAL TO HOPPER
GATE MOUNTING
PLATE
10--32 NU T
FIGURE 13
© 2004, IMI Cornelius Inc. - 9 - Publication Number: TP01071
IntelliCarb Training Manual
REMOVAL AND REPLACEMENT OF AGITATORS
To Remove Agitators For Cleaning (300 shown)
NOTE: All other models have only one agitation Assembly.
COUNTERCLOCKWISE
ROTATION
LEFT HAND
AGITATOR
O–RING
FRONT (VALVE SIDE) VIEW FROM TOP OF DISPENSER
RIGHT HAND AGITATOR WITH HOLE IN UPRIGHT
CLOCKWISE
ROTATION
FIGURE 14
1. Lift agitator and disc from unit.
2. Remove O-Ring starting at notch. Warm the O-Ring with water to ease removal.
3. Lift the plastic agitator disc off of the stainless-steel agitator.
4. Replace by reversing steps.
NOTE: Refer to Sanitize Procedure in the Owners Instruction for complete cleaning and sanitiz-
instructions.
ing
Publication Number: TP01071 - 10 - © 2004, IMI Cornelius Inc.
POST-MIX VALVE SECTION
SET-UP INSTRUCTIONS
IntelliCarb Training Manual
Concentrate valve sleeve
has only one hole
A side water lever kit can be added to a valve allowing for dispensing of water without syrup or concentrate. The side water lever can be added to either a carbonated drink valve or a noncarbonated drink valve.
Post-mix valves control:
the ONOFF of syrup and water,
the flow rates of syrup and water,
the mixing of the two ingredients as they pour into the
cup, and
in some instances - dispensed portion.
Dimensions & Capacities
Fast Flow ............................................................................................................... 1 ½ to 3 oz./sec.
UFB-1 ......................................................................................................................... 2 to 4 oz./sec.
Ultra Flow .............................................................................................................. 3 to 4 ½ oz./sec.
Operational temperature range: ......................................................... 10°C (50°F) to 43°C (110° F)
Voltage requirements:................................................................................ 22 to 27 VAC (50/60 Hz)
Syrup valve sleeve has six holes
FIGURE 15
Mounting
screw
Water
lever
FIGURE 16
Transformer (electronic valves) ........................................................................................80 VA min.
Operating Pressure (flowing)...............................................................................syrup = 20 psi min.
.............................................................................................................................water = 35 psi min.
Concentrates and juices that contain particulates must be dispensed from a juice valve. A slanted drip tray is necessary when using an Optifill valve.
SYSTEM DETAILS
Water
Water Quality
Water quality issues have an affect on dispensing valves. Chloramine, a combination of chlorine and ammonia is responsible for some degradation of rubber components. Chloramine is used in many U. S. water supplies. Its affects can be minimized by installing and maintaining a water filtration system.
Ultra pure water affects the sensitivity of the Optifill™ valve. Because ultra pure water has less mineral content, it reduces the conductivity of the water keeping the circuit open and overfilling the beverage container.
Water Flow
The size of the orifice in the piston varies depending on whether the piston is used for syrup or water, and whether it is high flow or ultra flow valve.
© 2004, IMI Cornelius Inc. - 11 - Publication Number: TP01071
IntelliCarb Training Manual
NOTE: The notched water piston on the Ultra Flow and UFB-1 valve. results in at least one orifice in the sleeve always open. This elimi­nates pulsating and smooths water flow at higher flow rates.
In operation the liquid flows through the knife–edged orifice in the bottom of the piston and then out the orifices in the sleeve. The outlet orifice size in the sleeve is regulated by the position of the piston. In the illustration, the piston is restricting approximately 1/2 of the outlet orifices.
Orifice
Sleeve
Piston
Notch in
piston
FIGURE 17
UFB-1 Flow Module
FIGURE 18
Lower Fluid Pressure BUT
Larger Orifice Openings
Knife
edge
Syrup/Water Flow
Lower Fluid Pressure Push­ing Against Pis­ton & Spring
Same Volume Of
Syrup/Water Flows
From Orifices
Higher Fluid
Pressure Pushing
Against Piston &
Spring
Higher Fluid Pressure BUT
Smaller Orifice Openings
FIGURE 19
The position of the piston inside the sleeve is determined by the upward pressure of the liquid against the base of the piston and the downward pressure of the spring inside the piston (not shown here). The pressure of the spring is regulated by the adjusting screw.
If the pressure of the liquid increases, the flow rate through the knife–edged orifice will increase. The piston is moved upward closing off more of the outlet orifices. The same flow rate is thereby maintained.
Publication Number: TP01071 - 12 - © 2004, IMI Cornelius Inc.
IntelliCarb Training Manual
Adjusting Flow Rates
Flow rates of the water and syrup are adjusted based on the desired ratio. For example: if the desired ratio is 5:1, then the flow rate of the water is 5 times that of the syrup.
If the desired finished drink total flow rate is 3.0 ounces per second, then the water flow rate is 2.5 oz./ sec and the syrup flow rate is 0.5 oz./sec. (The water at 2.5 oz./sec is five times the 0.5 oz./sec syrup flow rate.)
NOTE: Always adjust water within its range.
Water Flow Rates At Selected Ratios
Water To Syrup
Ratio
2 to 1 1.00 oz./sec. 2.00 oz./sec. 2.50 oz./sec. 3.00 oz./sec. 3 to 1 1.13 oz./sec. 2.25 oz./sec. 2.81 oz./sec. 3.38 oz./sec. 4 to 1 1.20 oz./sec. 2.40 oz./sec. 3.00 oz./sec. 3.60 oz./sec. 5 to 1 1.25 oz./sec. 2.50 oz./sec. 3.13 oz./sec. 3.75 oz./sec. 6 to 1 1.29 oz./sec. 2.57 oz./sec. 3.21 oz./sec. 3.86 oz./sec. 7 to 1 1.31 oz./sec. 2.63 oz./sec. 3.28 oz./sec. 3.94 oz./sec.
Calculating Flow Rates
The most frequent ratio is 5:1. The charts above list the breakdown for many ratios and flow rates. It is useful to be able to calculate flow rates when a chart is not available.
An example of calculating the water and syrup flow rates given the finished drink flow rate and the water to syrup ratio:
Given:
1. Finished Drink Flow Rate = 3.0 oz./sec.
2. Water to Syrup Ratio = 5 to 1 To calculate Water Flow Rate:
1. Calculate the Total Portions = Water Portion + Syrup Portion (example 5 + 1 = 6)
2. Calculate Syrup Flow Rate = Finished Drink Flow Rate ÷ Total Portions (example 3.0 oz./sec ÷ 6 = .5 oz./sec)
3. Calculate Water Flow Rate = Finished Drink Flow Rate – Syrup Flow Rate (example 3.0 oz./sec - .5 oz./sec = 2.5 oz./sec)
Prove the calculation is correct by adding water flow rate of 2.5 oz./sec + syrup flow rate of .5 oz./sec = finished drink flow rate of 3.0 oz./sec.
Water flowing at 2.5 oz./sec and syrup flowing at .5 oz./sec achieves a ratio of 5:1 and 3.0 oz./sec. flow rate.
Water at 1.5 oz./
sec. Total Flow
Water at 3.0 oz./
sec. Total Flow
Water at 3.75 oz./
sec. Total Flow
Water at 4.5 oz./
sec. Total Flow
Syrup/Concentrate
Syrup should always be precooled before setting the ratio. Syrup takes a path through the valve
parallel to the water path. It is introduced in the block, travels through a syrup flow control, banjo, valve head and out the nozzle. Note, concentrate is not cooled.
High sugar syrups are more viscous (thicker) than diet syrups and consequently have more pressure drop within a system. This pressure drop results in less flow at the valve and therefore a slower fill time. Increasing the pump pressure will help overcome the pressure drop caused by high sugar syrups.
© 2004, IMI Cornelius Inc. - 13 - Publication Number: TP01071
IntelliCarb Training Manual
Setting Ratios
If the ratio varies and must be adjusted often, it is probably the result of a restricted syrup system. It is then time to clean and sanitize the syrup tubing and cooling coils and check for other
problems such as syrup pumps, etc.
NOTE: Try raising the pressure on the pump before cleaning.
Set the water flow rate first, then adjust the syrup to the desired ratio. This gives the most accurate
valve flow setting possible. Measure the ratio and adjust the syrup flow, if necessary. This will result in uniform flow, better carbonation retention, and improved drink quality.
When using a ratio cup always take these precautions to ensure accuracy:
After installing the separator tube, open the valve to fill the syrup tube before starting the ratio test.
Clean the cup thoroughly between tests so there is no carryover from one test to the next.
Fill the cup to approximately 3/4 full and use approximately the same quantity for each test to ensure
accurate settings.
Take another sample to verify the settings.
Ratio Cup and Syrup Separator
FIGURE 20
NOTE: Valve troubleshooting information is available on page 39.
Publication Number: TP01071 - 14 - © 2004, IMI Cornelius Inc.
SHURFLOW OVERVIEW
SHURflos Beverage Gas Pump supplies syrup under pressure to a post-mix dispenser, which mixes the syrup with water to an exact ratio (brix). The pump is used in conjunction with non-pressurized Bag-In­Box (B-I-B) containers and a bag connector (Q.D.) fitting.
IntelliCarb Training Manual
SHURFLO
The pump can be operated on regulated C drives the pump and is not in contact with the syrup. Separate syrup and gas chambers prevent contamination, foaming, and purging of the tubing when the B-I-B has emptied.
The pump retains pressure in the outlet line, operating only when syrup is needed. When the dispenser valve is opened, the pump reacts to the pressure drop by operating to maintain pressure in the line. When the dispenser is closed, the incoming gas and output syrup pressures equalize and the pump stops. Actual dynamic line pressure is dependant upon system losses as outlined in the section "Pumping Capability".
The automatic "sold-out" feature within the pump ensures consistent syrup delivery right up to the moment the B-I-B is empty. Vacuum produced by the pump evacuates the syrup within the bag. Once the preset vacuum point is achieved and held, incoming gas pressure to the pump is shutoff causing the outlet syrup pressure to drop to zero. When a new B-I-B is installed, the vacuum drops, the pump automatically restarts and pressurizes the system. The SHURflo Beverage Gas Pump ensures quality from the first drink to the last.
Beverage Gas Pumps are intended for soda syrups and low viscosity concentrates that do not contain solids.
The use of a SHURflo Juice Pump (-09) is recommended for concentrates containing soft solids, classed as round, up to 0.025 in. [0.6 mm] or that are of higher viscosity than soda syrups.
When concentrates contain pulp classed as long/stringy, seed particles or are exceptionally viscous, the Particulate Juice Pump (-10) should be used as it can handle soft solids up to
Standard gas pump models are for installations where geographic elevation is less than 5000 ft.[1523M]. For elevations above 5000 ft. specific high altitude models with a reduced sold-out spring rate must be used to compensate for the loss in atmosheric pressure.
O2, nitrogen or compressed filtered air. The compressed gas
1 /4" [6 mm] cubed.
For further application and model information please contact SHURflo.
NOTE: Shurflow Troubleshooting information available on page 35.
© 2004, IMI Cornelius Inc. - 15 - Publication Number: TP01071
IntelliCarb Training Manual
SHURFLOW INSTALLATION
As indicated on the pump, the outlet port is to be mounted up.
Pumps are to be mounted at the same level or higher than the B-I-B. The best choice is to have the
pump above the B-I-B.
INLET
[3mm])
tubing from the B-I-B to the pump use; 3/8" I.D. [10mm] minimum, heavy wall (1/8"
clear, NSF listed vacuum tubing. Inlet tubing should not have excessive length. Tub­ing that is allowed to drape down can trap air in the B-I-B creating a potential for pump "sold­out" problems.
not exceed 5 ft [1.5 M
If plumbing multiple B-I-Bs to a pump, B-I-B's should be "Teed" side-by-side horizontally,
rather than one on top of the other
OUTLET tubing from the pump to the dispenser should be high pressure rated and NSF
listed. Consult "Pumping Capability"
Always cut CO2 and outlet tubing at least 2 ft. [.6 M] longer to provide a "service loop" so the
The maximum vertical distance from the bottom of the B-I-B to the pump must
]. Maximum inlet tubing length is 10 ft. [3 M ].
(vertically).
(see page 2) for appropiate tubing I.D.
B-I-B rack can be moved for cleaning or service.
Use new (clean), 1/4" I.D. [6 mm], flexible, high pressure, braided tubing from the CO2 / air
regulator to the pump.
NEVER connect a transfer tank "system" in series with a B-I-B system. Syrup contaminants in
old components may work their way through the air supply causing premature failure of the gas pump. Gas used to operate pumps
water, etc tanks should be drained regularly. Pumps subjected to contaminated air are not covered by warranty.
). Air compressors may be used with proper particle filters and moisture separators. Air storage
MUST be clean and contain no contaminants (syrup, oil, rust,
High concentrations of CO2 can be fatal as it will displace the air from non-ventilated areas. Pumps operated by CO
2 must be in ventilated areas.
If placed in a confined area the room air on a continuous basis should be used.
All tubing connections must be secured with stainless steel, stepless Oetiker ® clamps.
Cable-tie all tubing securely to prevent kinks or sags that inhibit performance or cause damage to the
pump fittings.
START-UP PROCEDURE
1. Confirm that all tubing connections are properly clamped, fittings are tight, and tubing is not kinked. Install bag connector to the B-I-B.
2.
Adjust gas regulator to about 20 psi. [1.4 bar] allowing the pump to stroke slowly.
3. Operate the valve until all air trapped within the tubing has been purged.
4.
Once the air has been purged, adjust the CO2 regulator to the pressure necessary to main-
tain the desired brix. The most efficient gas usage occurs at 40 psi. static gas pressure to the pump is 85 psi. [5.8 bar], minimum 20 psi. [1.4 bar].
Flowrates that result in a stroke-rate of more than two strokes per second will decrease pump
(Consult factory) Pump failure due to "overrunning" is not covered by the limited warranty.
life. To prevent air from entering the system always leave the bag connector attached to the empty
B-I-B until a new B-I-B can be installed. Air entered into the system, via air in the bags or vacuum leaks, may cause brix fluctuation, foaming, spitting, non-operation of the vacuum sold­out or pump "run-on" with the valve closed.
pump.
(basement, closet, cooler box, etc.), exhaust fans capable of changing
[2.8 bar]. MAXIMUM
Symptoms of this kind can lead to a misdiagnosis of the
Publication Number: TP01071 - 16 - © 2004, IMI Cornelius Inc.
TYPICAL INSTALLATION
IntelliCarb Training Manual
PLUMBING
FIGURE 21. Typical Installation
© 2004, IMI Cornelius Inc. - 17 - Publication Number: TP01071
IntelliCarb Training Manual
PLUMBING LAYOUT
3-5 Per Side
Brand Syrup Inlets
B
Plain Water In
Carb Water In
BB
C
Brand Syrup Inlets
Carbonator Tank CO2 Inlet
C
3-5 Per Side
B
E
Connection Legend
3/8" Female Fir Nut
A
3/8" Barb Conn
B
C
1/4" Barb Conn
3/8" Hose Barb - 3/4" NP
D
1/4" Female Flr Nut
E
Direct Conn to SUR
F
Outlet on BIB Pmp
Direct Conn to CO2
G
Inlet on BIB Pmp
Syr Inlet BIB Pmp
H
BIB Syrup
6-10 Brand Flavors
Carb
Pump
Water Filter
I
A
75 psi Fixed Reg
Regulator 100 psi
G
G
BIB Pump
BIB Pump
F
E
H
A
D
I D
F
3/4" NPT TEE
CO2 Supply
Regulator 55-60 psi
E
BIB Syrup
Publication Number: TP01071 - 18 - © 2004, IMI Cornelius Inc.
H
Tubing Legend
3/8" Bev Tubing
1/4" Bev Tubing
3/8" Tycon Tubing
FIGURE 22. Plumbing Layout
© 2004, IMI Cornelius Inc. - 19 - Publication Number: TP01071
FIGURE 23. Flow Diagram 1xx (Six Flavor Model)
FAUCETS VIEWED FROM THIS SIDE
FA UC E TS
6
5
4
FLOW DIAGRAM 1XX (SIX FLAVOR MODEL)
DOUBLE CHECK
VA LV E
W1,
W1
S6
S5
W2
S4
VALVES 1,2,
3,6
W2,
VALVES 4,5
CARB ONATOR
PUMP
NON--CARB
WAT ER
OPTIONAL PRESSURE
REGULATOR
CHECK VA LV E
FILTER
INSTALL FOR NON--CARB A S
REQUIRED
POTABL E WAT ER SUPPLY
COLDPLATE
INLET
CONNECTIONS
CARBONATOR
TAN K
3
2
1
W2
S3
S2
S1
ITEMS INSIDE BROK EN LINE
INCLUDED WITH UNIT
W1
COLD PLATE
S5
S6
S7
S1
S2
S3
OPTIONAL FOR
DIET DRINKS
OR ROOT B EER
5--15 PSIG
PLUGGED
S1
S2
S3
SYRUP TANKS
15--50 PSIG
S6S7
S5
PRESSURE
REGULATORS
75 PSI
IntelliCarb Training Manual
CO2
CYLINDER
Publication Number: TP01071 - 20 - © 2004, IMI Cornelius Inc.
FLOW DIAGRAM 1XX (EIGHT FLAVOR MODELS)
IntelliCarb Training Manual
FAUCETS
8
7
FAUCETS VIEWED FROM THIS SIDE
COLDPLATE
CONNECTIONS
6
5
INLET
TAN K
4
3
2
1
FIGURE 24. Flow Diagram 1XX (Eight Flavor Models)
S8
S7
S6
S5
CARBONATOR
S4
S3
S2
S1
W1
W2
S5
S6
S7
S8
S1
S2
S3
S4
W2
W1
COLD PLATE
W1,
VALVES 1,2,
3,7,8
W2,
VALVES 4,
5,6
5--15
PSIG
OPTIONAL FOR
DIET DRINKS
OR ROOT B EER
DOUBLE CHECK
VA LV E
OPTIONAL
PRESSURE
REGULATOR
CARB ONATOR
PUMP
NON-- CARB
WAT ER
S4 S5
S2
S3
SYRUP TANKS
15--50 PSIG
S1
CHECK VA LV E
S8
FILTER
INSTALL FOR
NON-- CARB A S
REQUIRED
S6S7
PRESSURE
REGULATORS
CYLINDER
POTABL E
WAT ER
SUPPLY
75 PSI
CO2
ITEMS INSIDE BROK EN LINE
INCLUDED WITH UNIT
© 2004, IMI Cornelius Inc. - 21 - Publication Number: TP01071
FIGURE 25. Flow Diagram 2xx (Eight Flavor Models)
FAUCETS
8
7
6
5
W1
W2
W1
VALVES 1,2
3,6,7,8
W2
VALVES 4,5
DOUBLE CHECK
VALV E
CARBONATOR
OPTIONAL PRESSURE
REGULATOR
CHECK
VALV E
FILTER
INSTALL FOR
NON–CARB AS
REQUIRED
FLOW DIAGRAM 2XX (EIGHT FLAVOR MODELS)
POTABLE
WATER
SUPPLY
COLDPLATE
INLET
CONNECTIONS
CARBONATOR
TANK
4
3
2
1
S8
S7
S6
S5
W2
W1
S4
S3
S2
S1
COLD PLATE
W2
W1
5–15 PSIG
OPTIONAL FOR
DIET DRINKS
OR ROOT BEER
Non–Carb Water
75 PSI
IntelliCarb Training Manual
S1
S2 S3
S4 S5
SYRUP TANKS
15–50 PSIG
S6
S8S7
PRESSURE
REGULATORS
ITEMS INSIDE BROKEN LINE
INCLUDED WITH UNIT
CO2
Cylinder
IntelliCarb Training Manual
FLOW DIAGRAM 2XX (TEN FLAVOR MODELS))
POTABLE
WATER
SUPPLY
FILTER
PRESSURE
OPTIONAL
REGULATOR
VALV E
DOUBLE CHECK
W1
VALVES 1,2,3
4,7,8,9,10
W2
VALVES 5,6
INSTALL FOR
NON–CARB AS
CHECK
VALV E
CARBONATOR
PUMP
REQUIRED
NON CARB WATER
75 PSI
S10S9
S8S1 S2
S6 S7
S3 S4 S5
5–15
PSIG
DIET DRINKS
OPTIONAL FOR
OR ROOT BEER
15–50 PSIG
SYRUP TANKS
PRESSURE
REGULATORS
CO2
CYLINDER
S4S3S2
S5
INLET
COLDPLATE
CONNECTIONS
S1
CARBONATOR TANK
W2
S4
S5
4
5
W1
COLD PLATE
S2
S3
3
2
S1
1
INCLUDED WITH UNIT
ITEMS INSIDE BROKEN LINE
10
FAUCETS
S10
W1
S6
S7
S8
S9
S10
W2
S6
S7
S8
S9
9
7
8
6
FAUCETS VIEWED FROM THIS SIDE
FIGURE 26. Flow Diagram 2xx (Ten Flavor Models)
Publication Number: TP01071 - 22 - © 2004, IMI Cornelius Inc.
© 2004, IMI Cornelius Inc. - 23 - Publication Number: TP01071
FLOW DIAGRAM 300 (TWELVE FLAVOR MODELS)
FAUCETS
FIGURE 27. Flow Diagram 300 (Twelve Flavor Models)
FAUCETS VIEWED FROM THIS SIDE
12
11
10
COLDPLATE
INLET
CONNECTIONS
9
8
7
FAUCETS
6
5
4
COLDPLATE
INLET
CONNECTIONS
3
2
1
COLD PLATE
S12
S11
S10
W1 W2 S10
S11 S12 S7 S8 S9
S9
S8
S7
COLD PLATE
S6
S5
S4
W1 W2
S4 S5 S6 S1 S2 S3
S3
S2
S1
W2
W2
W2
W2
W1
W1
W1
W1
TO COLDPLATE SYRUP INLETS
OPTIONAL FOR
DIET DRINKS
OR ROOT BEER
5–15 PSIG
DOUBLE CHECK
VALV E
NON–CARB WATER
S1 S6 S5
CARBONATOR PUMP
SYRUP TANKS
15–50 PSIG
CHECK
VALV E
S4 S9
S8S3 S2
OPTIONAL
PRESSURE
REGULATOR
INSTALL FOR NON–CARB AS
REQUIRED
S12S7
FILTER
S10S11
PRESSURE
REGULATORS
POTABLE WATER SUPPLY
CO2
CYLINDER
CO2
75 PSI
IntelliCarb Training Manual
CARBONATOR TANK
ITEM INSIDE BROKEN LINE INCLUDED WITH UNIT
IntelliCarb Training Manual
One Transformer Powers the Left Bank
and the Other Powers the Right Bank. Will Power All Valves Simultaneously.
Transformers
ELECTRICAL SECTION
FIGURE 28. Electrical Box 1xx Single Transformer
Control Box Single Transformer Will Power
up to Three Valves Simultaneously.
FIGURE 29. Electrical Box 2xx Single Transformer
Transformer
FIGURE 30. Electrical Box 2XX Dual Transformer
Publication Number: TP01071 - 24 - © 2004, IMI Cornelius Inc.
CARBONATOR WIRING DIAGRAM
Time Out Selection Pins.
7min/3 min/Disabled
(Move Jumper to Select)
IntelliCarb Training Manual
RESET CONNECTIONS
© 2004, IMI Cornelius Inc. - 25 - Publication Number: TP01071
Publication Number: TP01071 - 26 - © 2004, IMI Cornelius Inc.
WIRING DIAGRAM 1XX (120V)
IntelliCarb Training Manual
SERVICE INFORMATION
FIGURE 31. Wiring Diagram 1xx (120V)
CCW
AGITATOR
MOTOR
Q.C.
CONNECTOR
GRD 115 V
SUPPLY
TO HINGE
MOTOR HEATER
GRN
DISPENSE
SWITCH
N L
+
--
O
W
B
B
B
R
H
L
A
I
U
N
T
E
G
E
E
G
W
B
R
H
L
E
I
A C
E
T
N
E
K
G R E E N
BLACK
BLACK
OPTIONAL
B
B
B
B
R
R
L
L
L
L
L
L
E
E
A
A
A
U
A
U
D
D
C
C
C
E
C
K
K
BLACK
E
K
K
BLUE
WHITE
BLACK
RED
WHITE
PINK
RED
BLUE
GATE
SOLENOID
(106VDC)
OPTIONAL
PINK
DANG ER!
BLACK
BLACK
NC
NCNOCOM
L2
COMNO
L1
WHITE
ELECTRIC SHOCK HA ZA RD. DISCONNECT
POWER B EFORE SERVICING UNIT.
YELLOW
YELLOW
W
B
H
L
I
A
T
C
E
K
WHITE
G
BLACK
RED
R E E N
WHITE
WHITE
WHITE
W H I T E
BLACK
R E D
B
R
L
E
A
D
C K
BLACK
BLACK
BLACK
WHITE
TO BEVERAGE FAUCET
KEY SWITCH
T’STAT
1
ICE LEVEL
OPTIONAL
2
WHT
OPTION
LIGHT
SCHEMATIC 1XX
IntelliCarb Training Manual
L
G
TIMER
VEND SWITCH
L2
MOTOR HEATER
N.O.
C
N.C.
CAPACITOR
RECTIFIER
L1
AGITATOR MOTOR
N
OPTIONAL
BALLAST
BEVERAGE
VALVES
GATE SOLENO ID
OPTIONAL LIGHT
OPTIONAL
STARTER
BEVERA GE TRA NSFOR MER
OPTIONAL LOW ICE LEVEL
BEVERA GE PANEL
T’STAT
BEVERAGE
VALVES
LIGHT
FIGURE 32. Schematic 1xx
© 2004, IMI Cornelius Inc. - 27 - Publication Number: TP01071
Publication Number: TP01071 - 28 - © 2004, IMI Cornelius Inc.
MOTOR
AGITATOR
MOTOR
FIGURE 33. Wiring Diagram 2xx (120V Model)
Q.C. CONNECTOR
GATE SOLENOID (106VDC)
Y
B
E
L
L
K
TO HINGE
HEATER
BLK
GRN
N L
DISPENSE
SWITCH
DANGER!
SERVICE INFORMATION
ELECTRIC SHOCK HAZA RD. DISCONNECT
POWER BEFORE SERVICING UNIT.
LIGHTT’STAT
2
1
BLUE
I CE LEVEL SI GNAL
OPTI ON
TO 24V
TRANSFORMER
BLUE
TO BEVERAGE VALVES
KEY SWITCH
YELLOW
WIRING DIAGRAM 2XX (120V MODEL)
IntelliCarb Training Manual
MOTOR START
CAPACITOR
B
W
B
B
L
H
L
L
A
I
U
U
C
T
E
E
K
E
BLACK
WHITE
OPTIONAL
LIGHT SOC KET
RECTIFIER
W
B
H
L
I
U
T
E
E
R
Y
B
W
G
B
B
BLACK
RED
+
--
R E D
B L U E
B
B
L
L
U
U
E
E
B L A
OPTIONAL C K
STARTER
E
L
L
A
L
C
O
K
W
LIGHT
B
B
R
G
E
H
R
L
L
L
L
E
R
D
I
E
A
A
A
A
D
E
T
E
C
C
C
E
C
E
K
N
K
K
K
N
W H I T E
WHITE
BLACK
Y E
MOTOR
L
START
R
L
RELAY
O W
3
R E D
4
2
W H I T E
NC E D
NO
NC
G R E E N
BLACK
COM
AGITATION
TIMER
NOCOM
G R E E N
BLACK
L2
L1
WHITE
BLACK
WHITE
BLACK
OPTI ONAL
LIGHT BALLAST
WHITE
WHITE
BLACK
BLACK
BLACK
WHITE
TRANSFORMER W H I T E
WHITE
BEVERAGE
(O PTIONAL )
BEVERAGE
TRANSFORMER
(O PTIONAL )
W H
B L A C K
I T E
OPTIONAL
LIGHT SOCKET
BLACK
WHITE
B L A C K
WIRING DIAGRAM 2XX (220/240V MODELS)
BLACK
POWER
SWITCH
BROWN
TO BEVERAGE VALVES
BROWN
BEVERAGE
(OPTIONAL)
TRANSFORMER
WHITE
IntelliCarb Training Manual
WHITE
BLACK
LIGHT
SOCKET
OPTIONAL
LIGHT
T’S TAT
KEY SWITCH
YELLOW
BEVERAGE
(OPTIONAL)
OPTION
BLUE
ICE LEVEL SIGNAL
TO 24V
TRANSFORMER
.
BLUE
2
1
POWER BEFORE SERVICING UNIT
ELECTRIC SHOCK HAZARD. DISCONNECT
SER VICE INFORMATION
TRANSFORMER
LIGHT
BALLAST
OPTIONAL
LINE
LAMP
LT BLUE
LOA
FILTER
N
POWER LINE
GRN
WHITE
LT BLUE
D
L
WHITE
BLACK
WHITE
BROWN
BROWN
WHITE
BLACK
WHITE
BLACK
FIL TER
WHITE
ASY
L2
NC
LT BLUE
J10
COM NO
N
AGITATION
J9
TIMER
COM
NO
BROWN
L
L1
NC
BLACK
BLACK
RED
RED
BLACK
BROWN
BROWN
BLU
E
BLACK
LT B LU E
BROWN
GRN/YEL
GRN/YEL
MOTOR
HEATER
TO
BLU
BLK
MOTOR
AGITATOR
BLK
N
E
PANEL
BEVERAGE
E
Q.C. CONNECTOR
DANGER!
L
GUSSET
TO HINGE
SWITCH
DISPENSE
GATE
SOLENOID
GRN/YEL
GRN/YEL
GRN/YEL
GRN/YEL
RED BLACK BLACK BLACK GRN/YEL
GRN/YEL LTBLU BROWN
GRN/YEL RED YELLO
GRN/YEL BLACK BLU
E GRN/YEL BLU
E
BLACK
CAPACITOR
MOTOR START
BLACK
START
RELAY
MOTOR
E
W
RED
3
4
2
WHITE
LIGHT
OPTIONAL
BLACK
WHITE
STARTER
BLACK
OPTIONAL
WHITE
LIGHT
SOCKET
FIGURE 34. Wiring Diagram 2xx (220/240V Models)
© 2004, IMI Cornelius Inc. - 29 - Publication Number: TP01071
IntelliCarb Training Manual
WIRING DIAGRAM 2XX (220/240V MODELS)
G
L
N
VEND SWITCH
TIMER
L1
RECTIFIER
MOTOR HEATER
N.O.
C
N.C.
GATE SOLENOID
L2
AGITATOR MOTOR
OPTIONAL BALLAST
OPTIONAL BEVERAGE VALVES
OPTIONAL LIGHT
OPTIONAL STARTER
OPTIONAL
BEVERAGE TRANSFORMER
BEVERAGE PANEL
OPTIONAL ICE LEVEL
FIGURE 35. Wiring Diagram 2xx (220/240V Models)
OPTIONAL BEVERAGE VALVES
Publication Number: TP01071 - 30 - © 2004, IMI Cornelius Inc.
WIRING DIAGRAM 300 (220/240V MODELS)
BLACK
BLACK
BLACK
RED
YELLOW
YELLOW
YELLOW
BEVERAGE
(OPTIONAL)
TRANSFORMER
MOTOR
HEATER
KEY
SWITCH
SWITCH
DISPENSE
(OPTIONAL)
TO BEVERAGE
FAUCET
BLACK
BLACK
WHITE
WHITE
WHITE
BLACK
WHITE
WHITE
BLACK
IntelliCarb Training Manual
LIGHT
SOCKET
OPTIONAL
RED
WHITE
RED
WHITE
LIGHTT’STAT
BLUE
2
ICE LEVEL
1
SIGNAL OPTION
BLU
E
FAUCET
TO BEVERAGE
TO 24V TRANSFORMER
BLU
GRN/YEL BLU
RED
BLU ORN BLACK WHITE
YELLOW
YELLOW
YELLOW
GATE
SOLENOID
(DC COIL)
(CW)
RIGHT
MOTOR
AGITATOR
SWITCH
MOTOR
HEATER
POWER BEFORE SERVICING UNIT.
ELECTRIC SHOCK HAZARD. DISCONNECT
SERVICE INFORMATION
DISPENSE
KEY
SWITCH
(OPTIONAL)
BLUE
E
E
E
BLACK
BEVERAGE
TRANSFORMER
BLUE
WHITE
BLUE
BLACK
(OPTIONAL)
BLUE
BLACK
RED
WHITE
OPTIONAL
LIGHT STARTER
BLUE
WHITE
BLUE
LIGHT
BALLAST
OPTIONAL
BLACK
BLACK
BLACK
WHITE
BLACK
BLACK
BLACK
WHITE
BLACK
BLACK
WHITE
PINK
BLACK
L2
LIGHT
OPTIONAL
WHITE
WHITE
BLACK
J10
COM
NC NO
RED
MOTOR
SOCKET
TIMER
AGITATION
CAPACITOR
RED
WHITE
J9
BLACK
L1
COMNO
NC
RED
DANGER!
LEFT
MOTOR
(CCW)
AGITATOR
TO HINGE BRACKET
LIGHTT’STAT
BLUE
2
ICE LEVEL
1
SIGNAL OPTION
BLU
E
TO 24V TRANSFORMER
GATE
SOLENOID
(DC COIL)
GRN
GRN
L
N
BLU
BLU
RED
BLU BLACK
ORN
WHITE
GREEN WHITE BLACK
GREEN/YELLOW
E
E
E
BLACK
GREEN
WHITE
OPTIONAL
LIGHT STARTER
GREEN
LIGHT
OPTIONAL
BALLAST
BLACK
BLACK
BLACK
LIGHT
SOCKET
OPTIONAL
RED
MOTOR
CAPACITOR
PINK
BLUE
FIGURE 36. Wiring Diagram 300 (220/240V Models)
© 2004, IMI Cornelius Inc. - 31 - Publication Number: TP01071
IntelliCarb Training Manual
WIRING DIAGRAM 300 (220/240V MODELS)
BRN
BRN
YELLOW
YELLOW
TO 24V TRANSFORMER
BLU BLU
RED
BLU
ORN
BLACK WHITE
YELLOW
YELLOW
BLACK
BEVERAGE
(OPTIONAL)
TRANSFORMER
E E
E
BLACK
BEVERAGE
(OPTIONAL)
TRANSFORMER
BLACK
BLACK
WHITE
WHITE
BLACK
OPTIONAL
BLACK
RED
LIGHT STARTER
SERVICE INFORMATION
ON/OFF
SWITCH
RIGHT
MOTOR
AGITATOR
MOTOR
HEATER
(CW)
MOTOR
HEATER
T’STAT LIGHT
KEY
SWITCH
SWITCH
DISPENSE
(OPTIONAL)
BLUE
2
1
GATE
SWITCH
DISPENSE
YELLOW
FAUCET
TO BEVERAGE
ICE LEVEL
SIGNAL OPTION
BLU
E
SOLENOID
(DC COIL)
RED
POWER BEFORE SERVICING UNIT.
YELLOW
KEY
FAUCET
SWITCH
TO BEVERAGE
T’STAT LIGHT
(OPTIONAL)
BLUE
2
1
ICE LEVEL
SIGNAL OPTION
BLU
E
TO 24V TRANSFORMER
BLUE
WHITE
DANGER ELECTRIC SHOCK HAZARD. DISCONNECT
LIGHT
BALLAST
OPTIONAL
BLACK
BLACK
GREEN
OPTIONAL
BLACK
LIGHT
BALLAST
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
BLACK
BLACK
BLUE
BLACK
BLACK
WHITE
PINK
BLACK
BLACK
LIGHT
OPTIONAL
WHITE
L2
LIGHT
OPTIONAL
WHITE
WHITE
SOCKET
J10
COMNO
NC
RED
MOTOR
CAPACITOR
SOCKET
TIMER
AGITATION
BLACK
D
E
R
RED
WHITE
RED
BLUE
BLACK
J9
L1
NOCOM
NC
RED
BRN
PINK
BLUE
LEFT
AGITATOR
MOTOR
(CCW)
TO HINGE
GATE
SOLENOID
(DC COIL)
BLU
E
BLU
GRN
GRN
E
RED
BLU
E BLACK ORN WHITE
GREEN
BLU BRN
L
N
OPTIONAL
GREEN
LIGHT STARTER
BLACK
MOTOR
BLACK
CAPACITOR
BLACK
LIGHT
SOCKET
OPTIONAL
BRN
FIGURE 37. Wiring Diagram 300 (220/240V Models)
Publication Number: TP01071 - 32 - © 2004, IMI Cornelius Inc.
SCHEMATIC 300 (120V MODELS)
G
L
L1
TIMER
RECTIFIER
MOTOR HEATER
IntelliCarb Training Manual
N
L2
VEND SWITCH
BALLAST
OPTIONAL BEVERAGE VALVES
BEVERAGE PANEL
VEND SWITCH
N.O.1
C
N.C.1
CAPACITOR
GATE SOLENOID
OPTIONAL LIGHT
STARTER
OPTIONAL
BEVERAGE TRANSFORMER
MOTOR HEATER
N.O.2
C
N.C.2
CAPACITOR
AGITATOR MOTOR
OPTIONAL ICE LEVEL
AGITATOR MOTOR
GATE SOLENOID
BALLAST
OPTIONAL LIGHT
STARTER
OPTIONAL
BEVERAGE TRANSFORMER
BEVERAGE PANEL
OPTIONAL ICE LEVEL
OPTIONAL BEVERAGE VALVES
FIGURE 38. Schematic 300 (120V Models)
© 2004, IMI Cornelius Inc. - 33 - Publication Number: TP01071
IntelliCarb Training Manual
SCHEMATIC 300 (220/240V MODELS)
G
E–BOX GD.
POWER PUSH BUTTON SWITCH
L
VEND SWITCH
OPTIONAL BALLAST
L1
N.C1
N.O1
EMC
LINE
FILTER
MOTOR HEATER
MOTOR HEATER
TIMER
RECTIFIER
C
OPTIONAL LIGHT
OPTIONAL STARTER
L2
GATE
SOLENOID
AGITATOR MOTOR
N
VEND SWITCH
OPTIONAL BALLAST
BEVERAGE
KEYLOCK SWITCH
OPTIONAL BEV. TRANSFORMER
24V
BEV. FAUCETS
GATE SOLENOID
N.C2
C
N.O2
OPTIONAL LIGHT
OPTIONAL STARTER
24V
BEV. FAUCETS
OPTIONAL
BEV. TRANSFORMER
EMC
AGITATOR MOTOR
FIGURE 39. Schematic 300 (220/240V Models)
Publication Number: TP01071 - 34 - © 2004, IMI Cornelius Inc.
TROUBLESHOOTING
SHURFLOW TROUBLESHOOTING
Pumping Capability
The distance syrup can be delivered is limited by inherent factors the inlet
& outlet sides of the beverage
dispensing system. Due to variances in system configuration and equipment, an accurate determination of pressure drop is difficult. Before deciding on a system’s tubing size, SHURflo recommends estimating system losses by considering the following:
Syrup viscosity and temperature (coldplate, re-circ., etc.).
Total syrup flow rate of valve(s) connected
to a pump.
Inside diameter of the inlet/outlet tubing,
fittings, bag connector, etc.
Horizontal & vertical distance of the outlet
tubing.
Vertical tubing runs will reduce total achievable tubing run length. To estimate the losses within
the vertical distance, use the chart to the
. Take 1% of the distance in feet [3% if
right
meters
]. The resulting number is multiplied by
the vertical distance. This product is then subtracted from the maximum horizontal distance. The resulting length is the total horizontal/vertical (horz./vert.)
obtainable for that flow rate, tubing I.D. and viscosity.
For example:
(restrictions) within
tubing run that is
IntelliCarb Training Manual
MAXIMUM HORIZONTAL TUBING
BY
Meter
152+
152
138
65
31
19
9
--
152
40
24
9
3
39
23
16
8
VISCOSITY
3
/8" I.D.
[10mm]
Feet
Meter
500+
500+
500+
500+
500
398
297
212
500
500
388
193
127
500
345
239
127
152+
152+
152+
152+
152
121
90
65
152
152
118
59
39
152
105
73
39
500+
500+
500+
500+
500+
500+
500+
500+
500+
1
/2" I.D.
[13mm]
Feet
500
500
500
500
500
366
500
425
Meter
152+
152+
152+
152+
152+
152
152
152
152+
152+
152
152
112
152+
152+
152
129
LENGTHS
Distances shown are intended as a guidline only.
(cPs.=Centipose)
mL
15
22.5
30
45
60
75
90
105
15
22.5
30
45
60
15
22.5
30
45
1
Feet
500+
500
453
212
102
64
32
--
500
133
79
32
10
129
75
53
26
/4" I.D.
[6 m m ]
FLO W RATE
SEC.
/
OZ.
.5
.7 5
Diet
Soda
Syrup
(5 cPs.±3)
Standard
Soda
Syrup
(20 cP s.±3)
Heavy
Soda
Syrup
(35 cP s.±3)
1.0
1.5
2.0
2.5
3.0
3.5
.5
.7 5
1.0
1.5
2.0
.5
.7 5
1.0
1.5
Distances shown are the results of tests conducted at 70°F
[21°C] ambient with a static pressure of 85 psi. [5.8 bar] to the
pump. All distances assume a dynamic pressure of 35 psi. [2.38
bar] at the dispenser to maintain brix.
FAST FLOW VALVE
1
/2 oz./sec. [15 mL]
(syrup flow only)
GAS IN
HEAVY SODA
SYRUP
3
/8" I.D. [10mm] TUBING (min.)
TOTAL TUBING RUN
[113M]
370 ft.
3
/8" I.D. [10mm]
TUBING
22 ft.
VERTICAL
[6.7M]
© 2004, IMI Cornelius Inc. - 35 - Publication Number: TP01071
IntelliCarb Training Manual
The chart indicates that heavy syrup with 1/2 oz./sec [15mL] flow-rate (per the illustration) can be sustained over a horizontal distance of 500 ft.
[152M] when 3/8" I.D. [10mm] tubing is used.
Feet: Take
1% of 500 ft. (500 x 1%) = 5. Which then is multiplied by the 22 ft. vertical, (22 x 5) =
110 ft. Subtract this product from the 500 ft.
(horz./vert.) is possible, while the example only requires a distance of 370 ft.
Meters: Take
= 30.5M.
6.7)
Subtract this product from the 152
3% of 152M (152 x 3%) = 4.56. Which then is multiplied by the 6.7M vertical, (4.56 x
M (152-30.5)=121.5. The results indicate a 121.5M tubing run
(horz./vert.) is possible, while the example only requires a distance of 113M.
NOTE: Had the example above resulted in a value that was equal to, or less than the nec-
essary total tubing run, consider a larger I.D. tubing or installation of a pum using a SHURflo Vacuum Regulator.
Pumps in Series for Long Distances
Long tubing runs or high vertical lift can be achieved by installing pumps in series. Standard SHURflo Beverage pumps are not designed to have positive pressure on the inlet side. The SHURflo Vacuum Regulating Valve source. By positioning a VRV at the inlet of the secondary pump, incoming pressure is to zero, permitting syrup to be drawn in under vacuum.
SHURflo can recommend several other methods to meet the requirements for a particular installation, including Pressurized Inlet Pumps or Accumulators. Contact SHURflo for more information.
(VRV) allows the pump to receive liquid from a pressurized
(500 - 110) =390. The results indicate a 390 ft. tubing run
p(s) in series
reduced
FIRST
GAS IN
B-I-B
PUMP
Pump Sanitizing / Winterizing
Sanitization of the SHURflo Beverage Gas Pump is required. The frequency of Sanitization is
dependant on the concentrate type and its manufacturers requirements.
affect the frequency of this procedure are: temperature, concentrate volatility, facility conditions, installation and equipment. The sanitizing procedure fulfills a required 10 minute contact time with a 200 ppm Sodium Hypochlorite solution. Refer to SHURflo Service Bulletin #1025 for the N.S.F. listed sanitizing procedure for the SHURflo pump freezing Service Bulletin #1025 for complete winterizing procedure. Refer to the equipment manufacturers instructions for sanitizing and winterizing procedure for carbonators, dispensers and tubing.
Pumps that have been winterized and/or out of service for a period of time should be sanitized prior to being placed back in service.
Never apply pressure to the pumps liquid inlet. Pressurized tanks may damage internal components if used to sanitize or purge fluid from the pump
(below 32° F [0°C]) must be purged of fluid to prevent damage. Refer to SHURflo
VRV
SECOND
PUMP
TO NEXT
VRV/PUMP
OR
DISPENSER
GAS TO NEXT
PUMP
Factors which also
(only). Pumps that are subjected to
(operating or not).
Publication Number: TP01071 - 36 - © 2004, IMI Cornelius Inc.
Pump Troubleshooting
DOES NOT OPERATE / GAS APPLIED / DISPENSER VALVE OPEN
B-I-B empty or inlet tubing pinched off activating vacuum "sold-out".
Gas regulator over-pressurizing. (Pump stalled)
Outlet tube kinked or restricted.
Operated without fluid for excessive period. (Dry run)
Transfer tube and gas lines contaminated (syrup, rust, oil, etc.) [ensure clean gas supply, change
out all contaminated pumps]
Internal damage of control cover.
OPERATES BUT WILL NOT PRIME / DISPENSER VALVE OPEN
[consult Start-up Procedure for proper priming]
Pump valves have no moisture/dry (add water/syrup to the inlet port with pump stroking slowly).
Vacuum leaks at Q.D., barb fitting clamps, or inlet fitting o-ring.
Debris in valve seats or warped/swollen valves.
DOES NOT ACHIEVE SOLD-OUT WITH EMPTY B-I-B
Vacuum leaks at Q.D., barb fitting clamps, or inlet fitting o-ring.
IntelliCarb Training Manual
Excessive amount of air in B-I-B from improper packaging.
Air trapped in outlet tubing and/or pump fluid chambers.
AIR IN INLET AND/OR OUTLET TUBING
Vacuum leaks at Q.D. o-ring or barb fitting clamps.
Vacuum leaks at inlet fitting; o-ring pinched or missing.
Large amounts of air noticed only in the outlet tubing when pump operates (diaphragm/piston assem-
blies ruptured).
STROKES WITH DISPENSER VALVE CLOSED
Air trapped in outlet tubing and/or pump fluid chambers (open outlet and purge air, check for vacuum leaks, or air in B-I-B).
Debris in outlet valves or warped/swollen valves.
FLUID FROM EXHAUST OR VISIBLE WITHIN GAS INLET TUBING
Carbonator check valve.
Ensure clean gas supply.
Diaphragm/piston assemblies ruptured.
[change out all contaminated pumps]
GAS BLOWING FROM EXHAUST CONTINUOUSLY
Control cover subjected to contaminated gas supply or damaged (ensure clean gas supply, change out all contaminated pumps).
© 2004, IMI Cornelius Inc. - 37 - Publication Number: TP01071
IntelliCarb Training Manual
DISPENSER TROUBLESHOOTING
Should your unit fail to operate properly, check that there is power to the unit and that the hopper contains ice. If the unit does not dispense, check the following chart under the appropriate symptoms to aid in locating the defect.
Trouble Probable Cause Remedy
BLOWN FUSE OR CIRCUIT BREAKER.
GATE DOES NOT OPEN. AGITATOR DOES NOT TURN.
GATE DOES NOT OPEN OR IS SLUGGISH. AGITATOR TURNS.
ICE DISPENSES CONTINU­OUSLY.
SLUSHY ICE. WATER IN HOPPER.
BEVERAGES DO NOT DIS­PENSE
BEVERAGES TOO SWEET A. Carbonator not operating. A. Repair carbonator.
A. Short circuit in wiring B. Inoperable gate solenoid. C. Inoperable agitator motor.
A. No power. B. Bent depressor plate (does not
actuate switch). C. Inoperable dispensing switch.
A. Inoperable gate solenoid. B. Excessive pressure against gate
slide. C. Inoperable rectifier.
A. Stuck or bent depressor plate (does not release switch).
B. Inoperable dispensing switch. C. Improper switch installation.
A. Blocked drain. B. Unit not sitting level. C. Poor ice quality due to water qual-
ity or icemaker problems. D. Improper use of flaked ice.
A. No 24 volts power to faucets. B. No CO
2 pressure.
A. Repair wiring. B. Replace gate solenoid. C. Replace agitator motor.
A. Restore power. B. Replace depressor plate.
C. Replace dispensing switch. A. Replace gate solenoid.
B. Adjust gate slide. C. Replace rectifier.
A. Replace depressor plate.
B. Replace dispensing switch. C. Make sure switch is installed
properly. A. Unplug drain.
B. Level the unit. C. Correct water quality or repair ice-
maker. D. Call Service Person.
A. Restore 24 volt power to faucets. B. Restore CO 2 pressure.
Publication Number: TP01071 - 38 - © 2004, IMI Cornelius Inc.
VALVE TROUBLESHOOTING
Excess Foam
Excess Foam
Problem:
excess foam
Check
product
temperature
IntelliCarb Training Manual
Temp
?
below 40°
Remove
nozzle
Clean
?
no
Clean
Problem corrected
above 40°
yes
Check
system
Check flow
rates
Correct
?
no
Set flow rate
and ratio
yes
Check system
Problem
corrected
© 2004, IMI Cornelius Inc. - 39 - Publication Number: TP01071
IntelliCarb Training Manual
Off Taste
Off Taste
Problem:
off taste
Remove
nozzle
Clean
?
no
Clean
Problem
corrected
yes
Check ratio
Correct
?
no
Set ratio
Problem
corrected
yes
Check
system
Publication Number: TP01071 - 40 - © 2004, IMI Cornelius Inc.
Valve Stuck Open
Valve Stuck Open
Problem: valve
stuck open
solenoid
IntelliCarb Training Manual
Check
visually
working
?
no
(solenoid down)
Check for
power at
solenoid
Power
?
no
Clean or
replace
solenoid
Problem
corrected
yes
yes
(solenoid up)
Replace
dispensing
switch
Problem
corrected
Check for
damaged
banjos
Damage
?
yes
Replace
banjos
Problem
corrected
no
Undetermined
problem call
800-238-3600
© 2004, IMI Cornelius Inc. - 41 - Publication Number: TP01071
IntelliCarb Training Manual
No Product
No Product
Problem:
no product
Check
solenoid
visually
Replace
switch
no
Working
?
no
Check
voltage
(22-27 AC)
Power
?
no
Check switch
Problem
corrected
yes
yes
no
yes
Check
system
Check
transformer
Check
resistance
of coil
40 ohms
?
no
Replace solenoid
yes
Check system
Problem
corrected
Publication Number: TP01071 - 42 - © 2004, IMI Cornelius Inc.
CARBONATOR TROUBLESHOOTING
WARNING: Disconnect electrical power to the unit to prevent personal injury before attempting any internal maintenance. Only qualified personnel should service the internal components or the elec­trical wiring. If repairs to the carbonated water or the plain water systems must be made, disconnect electrical power to the Unit, then shut off CO carbonator tank CO
Trouble Probable Cause Remedy
CARBONATOR WILL NOT OPERATE.
WATER PUMP MOTOR WILL NOT SHUT OFF. ERRATIC CYCLING OF
CARBONATOR. WATER PUMP MOTOR OPERATES BUT WATER PUMP DOES NOT PUMP WATER. CARBONATOR CARBON­ATED WATER CAPACITY TOO LOW
2 pressure has been relieved.
A. Power cord unplugged or circuit breaker open in panel box. Inoperative carbonator.
B. Inoperative carbonator. A. Carbonator internal problem. A. Call a qualified Service Person.
A. Carbonator internal problem. A. Call a qualified Service Person.
A. Carbonator internal problems or a water supply line problem.
A. Carbonator internal problems or a water supply line problem.
B. Water filter clogged.
IntelliCarb Training Manual
2 and plain water sources. Dispense from dispensing valve until
A. Plug in power cord or reset circuit breaker.
B. Call a qualified Service Person.
A. Call a qualified Service Person.
A. Call a qualified Service Person. B. Replace water filter.
Solid State Carbonator Level Control
C
HI
LO
CARBONATED LIQUID
LEVEL CONTROL
NOTE: Carbonators that are equipped with a pump safety thermostat will have a black wire instead of green connected to the C terminal.
Test Solid State Level Control
1. Remove all wires and:
Carb. motor should run.
2. Jumper C to HI:
Carb. motor should stop. Do not remove jumper wire.
3. Jumper LO to C:
Motor should remain stopped.
4. Remove 1st jumper from C and HI:
Motor should remain stopped.
5. Remove 2nd jumper from C and LO:
Motor should start.
MATING
CARBONATOR TANK
FIGURE 40
CONNECTION
WIRING
PROBE ASS’Y
SHORT ELECTRODE
LONG ELECTRODE
ORANGE
RED
HARNESS
2ND JUMP
GREEN
GROUND
TERMINAL
C
1ST JUMP
HI ORANGE
LO RED
FIGURE 41
If level control passes all above test, replace probe.
© 2004, IMI Cornelius Inc. - 43 - Publication Number: TP01071
IMI Cornelius Inc.
www.cornelius.com
800-238-3600
Loading...