Remcor “CH” Series Refrigerated Recirculating Water Chillers are designed to provide a continuous flow of
clean cooling water at a constant temperature and to handle a variety of closed loop and tank cooling applications.
The CH consists of a refrigeration system with associated operating controls housed in a sturdy sheet metal
cabinet. A standard pump and reservoir package provides a complete self-contained water cooling and circulating system.
CH Chillers are designed to operate in a clean laboratory or industrial environment where ambient temperatures
range from 40F to 110F. Once properly installed, the CH Chiller will run virtually maintenance free and provide
a constant supply of cooling liquid to the application.
NOTE: Please read through this manual before starting the chiller.
1. The figures for power and cooling capacity are listed for air-cooled units with a circulation temperature of
68 F, and ambient temperature of 80F and standard pump.
2. Cooling capacity will be affected as follows: Derate 17% for 50 Hz operation. Derate 1% for each F drop
in recirculating temperature. Derate .5% for each F increase in ambient temperature. Optional pumps will
decrease net cooling capacity.
3. The operating water temperature range for water is 40F (5 C) to 100F (38C). If use of other fluids or
temperatures are required, the Technical Service Department must be contacted so the appropriate ranges
can be set.
4. Water-cooled units require about 20% less input power.
5. All CH Chillers are thoroughly tested before leaving the factory to ensure that each unit meets these specifications prior to shipment.
WARNING: Never operate the Chiller with the panels removed. Always use the power
switch to turn off the Chiller when it is not being used. Always ensure that all air inlets and
outlets are free from obstruction.
1
91961OPR
INSTALLATION
LOCATION
Install the Chiller indoors in a well ventilated area where ambient temperatures will never fall below 40F or rise
above 110F. To obtain optimum cooling capacity, the ambient temperature should be 80F or below.
Standard CH Chiller have air-cooled condensers. On air-cooled units it is important that the air intake and discharge are not obstructed. Avoid hot air discharge from other equipment or enclosed areas where heat build-up
could cause a significant rise in ambient temperatures. A minimum of two feet of space on all four sides of the
Chiller will be sufficient to prevent obstruction. Water-cooled units should be located near a water source and
drain.
TANK FILL, 1–INCH FPT
CH1500, 2000, 3000
ELECTRICAL JUNCTION BOX
CONTROL PANEL
(SEE DETAIL)
TANK LEVEL GAUGE
CH 5000 AND 7500
ON REAR FOR
CH1500, 2000 AND 3000
AIR OUTLET
(AIR INLET ON
OPPOSITE END)
TANK FILL 1–INCH FPT
S.S. (CH5000, 7500)
TANK DRAIN
WATER OUTLET
3/4–INCH OR 1–INCH
FPT S.S.
WATER INLET
3/4–INCH OR 1–INCH
FPT S.S.
91961OPR
FIGURE 1. INSTALLATION DETAILS
2
ELECTRICAL
All wiring must conform to the National Electric Code and any applicable local codes. The Chiller must be
PERMANENTLY wired by means of electrical conduit to a properly fused disconnect of proper amperage or
wired to a properly rated power cord and plugged into an outlet with the appropriate disconnect and amperage
rating. The electrical junction box located on the upper rear of the Chiller, includes a four-terminal strip for power
supply connections The DATA PLATE, located beside the junction box, indicates the actual phase, voltage and
amperage for each Chiller.
After the electrical connections are made, power must be supplied to the Chiller for a period of 12 hours (with
control switched off) to allow the compressor crankcase heater to warm the compressor lubricant.
CAUTION: On three phase applications, it is important that the rotation of the pump, when
supplied, is correct. Running the pump in reverse for more than a few seconds will result in
permanent pump damage. When the pump is running, shaft rotation must match the
direction indicated on the pump housing. If the rotation is incorrect, reverse two of the three
incoming power supply leads. The Phase Protection/3–Phase Monitor Option will prevent the
pump from operating backwards. See the option description.
Phase Protection / 3–Phase Option
The 3–Phase Monitor detects phase loss, low voltage, and phase reversal by continuously monitoring the
3–Phase power lines for abnormal conditions. When correct voltage and phase rotation are applied, the internal
relay will energize. A fault condition will de–energize the relay. When the fault is corrected, the monitor will automatically reset. Both Trip and Norm condition indicators are provided on the relay to aid in adjustment and system trouble–shooting.
This control is located in the enclosure labeled “Monitor” on top of the electrical box.
Phase Protection / 3–Phase Option Adjustment
The following procedure will allow the 3–Phase Monitor to achieve a trip point just below the nominal phase-tophase voltage, where the unit is applied.
Rotate the adjustment control fully clockwise, or until the red (Trip) indicator illuminated. Slowly rotate the adjustment control in a counter-clockwise direction, just until the green (Norm) indicator illuminates. At this point,
the 3–Phase Monitor is the most sensitive to irregular power line conditions. If nuisance tripping occurs, turn the
control slightly further counter–clockwise.
PLUMBING
Follow standard plumbing practices and local codes in making water connections. The Chiller inlet and outlet
connections are 3/4–inch or 1–inch FPT. Flexible hose and fittings are recommended for plumbing the system.
A No. 20 mesh strainer should be installed on the Chiller inlet to prevent foreign particles from entering the system and should be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from
running near radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient temperatures should be insulated to prevent condensation and/or significant liquid heat loss.
Water-Cooled Condensers
Water-cooled units must be connected to a source of tap water of chilled water and a drain. The connections for
the water supply (3/4–inch FPT or 1–inch FPT) are located on the rear of the unit. These units are supplied with
a WATER REGULATING VALVE that allows only the required amount of water to pass through the condenser
for a given heat load. The water flow through the condenser can vary from 0 when the cooling system is in the
“OFF” cycle to approximately 5.0–gpm at maximum rated loads for 1–1/2 ton units and approximately 20–gpm
at maximum rated loads for 7–1/2 ton units. This valve is factory set to operate where the water supply temperature ranges from 50F (10C) to 80F (27C) with a supply pressure of 30 to 60–PSIG. For temperatures or
pressure outside these ranges, contact our Technical Service Department for assistance in “field” adjustment of
the valve. Once the system as been properly plumbed, it is important that the circulation system be filled with
water.
3
91961OPR
Chiller with Reservoir
The reservoir can be filled by removing the water fill cap located on the upper rear of the Chiller (See Fluid Recommendations page). After ensuring that the drain valve is closed, fill the reservoir via the full port with clean
water until the water level sight glass on the front of the unit indicates “FULL” the fill cap should then be reinstalled before operation begins.
Auto Refill Option
If the Chiller is provided with the Auto Refill Option, install 1/4–inch or 1/2–inch tubing from the auto refill fitting
located on the lower rear of the Chiller to a fresh water supply line. The Chiller reservoir will fill with water automatically and the proper reservoir level will always be maintained.
Chiller without Reservoir
The Chiller and system piping should be filled with clean water ensuring that all air is purged from the system.
91961OPR
4
RESERVOIR
LOW TEMP. CONTROL
FROM PROCESS
EVAPORATOR
PUMPBYPASS VALVE
CHILLER INLET
TO PROCESS
CHILLER OUTLET
FIGURE 2. CHILLER PLUMBING SCHEMATIC WITH PUMP AND TANK (STANDARD)
FROM PROCESS
EVAPORATOR
EVAPORATOR
CHILLER INLET
LOW TEMP. CONTROL
BYPASS VALVE
CHILLER OUTLET
FIGURE 3. CHILLER PLUMBING SCHEMATIC NO TANK (OPTION)
CHILLER INLET
LOW TEMP. CONTROLCHILLER OUTLET
TO PROCESS
FROM PROCESS
TO PROCESS
FIGURE 4. CHILLER PLUMBING SCHEMATIC NO PUMP, NO TANK (OPTION)
5
91961OPR
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.