Cornelius CH1500, CH7500 User Manual

Models: CH1500–CH7500
Operator’s Manual with Installation, Service, and Parts
IMI CORNELIUS INC
CHILLER
Part No. 91961OPR September 12, 2006 Revised: N/A Revision: A
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must be read and understood before installing or operating this equipment
IMI CORNELIUS INC; 2006©
PRINTED IN U.S.A
TABLE OF CONTENTS
GENERAL INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SPECIFICATION NOTES 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOCATION 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PHASE PROTECTION / 3–PHASE OPTION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PHASE PROTECTION / 3–PHASE OPTION ADJUSTMENT 3. . . . . . . . . . . . . . .
PLUMBING 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER-COOLED CONDENSERS 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER WITH RESERVOIR 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AUTO REFILL OPTION 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER WITHOUT RESERVOIR 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START UP 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER FLOW START-UP 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER WITH PUMP 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER WITHOUT PUMP 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THERMOSTAT ADJUSTMENT 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STANDARD THERMOSTAT 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DUAL POINT ADJUSTMENT 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COOLING START-UP 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONTROL PANEL 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MAINTENANCE 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
FLUID RECOMMENDATIONS 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER DOES NOT OPERATE. CONTROL POWER LIGHT “OFF” 12. . . . . . . . .
PUMP DOES NOT OPERATE. PUMP POWER LIGHT “OFF” 12. . . . . . . . . . . . . . .
PUMP DOES NOT OPERATE. PUMP POWER LIGHT “ON”. 12. . . . . . . . . . . . . . . .
CHILLER DOES NOT COOL. COOLING LIGHT “OFF”. 12. . . . . . . . . . . . . . . . . . . . .
CHILLER DOES NOT OPERATE. COOLING LIGHT “ON”. 12. . . . . . . . . . . . . . . . . .
A. LOW PRESSURE ALARM LIGHT CYCLES ON/OFF. 13. . . . . . . . . . . . . . . . . . . .
HIGH PRESSURE ALARM LIGHT “ON”. 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOW TEMPERATURE ALARM 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONTROLS 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HIGH PRESSURE CONTROL (HPC) 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOW TEMPERATURE CONTROL (LTC) 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOW PRESSURE CONTROL (LPC) 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PARTS LIST 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i
91961OPR
TABLE OF CONTENTS (cont’d)
Page
LIST OF FIGURES
FIGURE 1. INSTALLATION DETAILS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 2. CHILLER PLUMBING SCHEMATIC WITH PUMP AND TANK
(STANDARD) 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 3. CHILLER PLUMBING SCHEMATIC NO TANK (OPTION) 5. . . . . . . . .
FIGURE 4. CHILLER PLUMBING SCHEMATIC NO PUMP, NO TANK (OPTION) 5
FIGURE 5. SAMPLE DATA PLATE FOR CH5002-A 14. . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 6. REFRIGERATION PIPING SCHEMATIC WITH HOT GAS BYPASS 17
FIGURE 7. REFRIGERATION PIPING SCHEMATIC WITHOUT HOT GAS
BYPASS 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 8. CHILLER PARTS BREAKDOWN 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 9. PUMP AND TANK COMPONENTS 19. . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 10. ELECTRICAL BOX COMPONENTS 20. . . . . . . . . . . . . . . . . . . . . . . . . .
91961OPR
ii
GENERAL INFORMATION
INTRODUCTION
Remcor “CH” Series Refrigerated Recirculating Water Chillers are designed to provide a continuous flow of clean cooling water at a constant temperature and to handle a variety of closed loop and tank cooling applica­tions.
The CH consists of a refrigeration system with associated operating controls housed in a sturdy sheet metal cabinet. A standard pump and reservoir package provides a complete self-contained water cooling and circulat­ing system.
CH Chillers are designed to operate in a clean laboratory or industrial environment where ambient temperatures range from 40F to 110F. Once properly installed, the CH Chiller will run virtually maintenance free and provide a constant supply of cooling liquid to the application.
NOTE: Please read through this manual before starting the chiller.
SPECIFICATIONS
Model CH1500 CH2000 CH3000 CH5000 CH7500
Cooling Capacity* Watts/BTU
Compressor
Condenser
Temperature Controller
Pump**
Reservoir
Voltage (Full Load Amps)***
Dimensions W x D x H (inches)
Inlet/Outlet Fitting Size
5,570/19,000 8,500/29,000 12,000/41,000 18,000/61,500 25,800/85,000
1.5 H.P. 2 H.P. 3 H.P. 5 H.P. 7.5 H.P.
Air Cooled (Water Cooled Optional)
Digital Display 30–100 F (0–39C.)
Many Available
10 Gallons 40 Gallons
230/60/1(17) 230/60/3(13)
460/60/3(8)
230/60/3(13)
460/60/3(8)
28 x 28 41 36 x 36 x 65
3/4–inch 1–inch
230/60/3(16) 460/60/3(10)
230/60/3(26.5)
460/60/3(14)
230/60/3(35) 460/60/3(22)
SPECIFICATION NOTES
1. The figures for power and cooling capacity are listed for air-cooled units with a circulation temperature of 68 F, and ambient temperature of 80F and standard pump.
2. Cooling capacity will be affected as follows: Derate 17% for 50 Hz operation. Derate 1% for each F drop in recirculating temperature. Derate .5% for each F increase in ambient temperature. Optional pumps will decrease net cooling capacity.
3. The operating water temperature range for water is 40F (5C) to 100F (38C). If use of other fluids or temperatures are required, the Technical Service Department must be contacted so the appropriate ranges can be set.
4. Water-cooled units require about 20% less input power.
5. All CH Chillers are thoroughly tested before leaving the factory to ensure that each unit meets these speci­fications prior to shipment.
WARNING: Never operate the Chiller with the panels removed. Always use the power switch to turn off the Chiller when it is not being used. Always ensure that all air inlets and outlets are free from obstruction.
1
91961OPR
INSTALLATION
LOCATION
Install the Chiller indoors in a well ventilated area where ambient temperatures will never fall below 40F or rise above 110F. To obtain optimum cooling capacity, the ambient temperature should be 80F or below.
Standard CH Chiller have air-cooled condensers. On air-cooled units it is important that the air intake and dis­charge are not obstructed. Avoid hot air discharge from other equipment or enclosed areas where heat build-up could cause a significant rise in ambient temperatures. A minimum of two feet of space on all four sides of the Chiller will be sufficient to prevent obstruction. Water-cooled units should be located near a water source and drain.
TANK FILL, 1–INCH FPT
CH1500, 2000, 3000
ELECTRICAL JUNCTION BOX
CONTROL PANEL
(SEE DETAIL)
TANK LEVEL GAUGE
CH 5000 AND 7500
ON REAR FOR
CH1500, 2000 AND 3000
AIR OUTLET
(AIR INLET ON
OPPOSITE END)
TANK FILL 1–INCH FPT
S.S. (CH5000, 7500)
TANK DRAIN
WATER OUTLET
3/4–INCH OR 1–INCH
FPT S.S.
WATER INLET
3/4–INCH OR 1–INCH
FPT S.S.
91961OPR
FIGURE 1. INSTALLATION DETAILS
2
ELECTRICAL
All wiring must conform to the National Electric Code and any applicable local codes. The Chiller must be PERMANENTLY wired by means of electrical conduit to a properly fused disconnect of proper amperage or wired to a properly rated power cord and plugged into an outlet with the appropriate disconnect and amperage rating. The electrical junction box located on the upper rear of the Chiller, includes a four-terminal strip for power supply connections The DATA PLATE, located beside the junction box, indicates the actual phase, voltage and amperage for each Chiller.
After the electrical connections are made, power must be supplied to the Chiller for a period of 12 hours (with control switched off) to allow the compressor crankcase heater to warm the compressor lubricant.
CAUTION: On three phase applications, it is important that the rotation of the pump, when supplied, is correct. Running the pump in reverse for more than a few seconds will result in
permanent pump damage. When the pump is running, shaft rotation must match the direction indicated on the pump housing. If the rotation is incorrect, reverse two of the three incoming power supply leads. The Phase Protection/3–Phase Monitor Option will prevent the pump from operating backwards. See the option description.
Phase Protection / 3–Phase Option
The 3–Phase Monitor detects phase loss, low voltage, and phase reversal by continuously monitoring the 3–Phase power lines for abnormal conditions. When correct voltage and phase rotation are applied, the internal relay will energize. A fault condition will de–energize the relay. When the fault is corrected, the monitor will auto­matically reset. Both Trip and Norm condition indicators are provided on the relay to aid in adjustment and sys­tem trouble–shooting.
This control is located in the enclosure labeled “Monitor” on top of the electrical box.
Phase Protection / 3–Phase Option Adjustment
The following procedure will allow the 3–Phase Monitor to achieve a trip point just below the nominal phase-to­phase voltage, where the unit is applied.
Rotate the adjustment control fully clockwise, or until the red (Trip) indicator illuminated. Slowly rotate the ad­justment control in a counter-clockwise direction, just until the green (Norm) indicator illuminates. At this point, the 3–Phase Monitor is the most sensitive to irregular power line conditions. If nuisance tripping occurs, turn the control slightly further counter–clockwise.
PLUMBING
Follow standard plumbing practices and local codes in making water connections. The Chiller inlet and outlet connections are 3/4–inch or 1–inch FPT. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh strainer should be installed on the Chiller inlet to prevent foreign particles from entering the sys­tem and should be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient tempera­tures should be insulated to prevent condensation and/or significant liquid heat loss.
Water-Cooled Condensers
Water-cooled units must be connected to a source of tap water of chilled water and a drain. The connections for the water supply (3/4–inch FPT or 1–inch FPT) are located on the rear of the unit. These units are supplied with a WATER REGULATING VALVE that allows only the required amount of water to pass through the condenser for a given heat load. The water flow through the condenser can vary from 0 when the cooling system is in the “OFF” cycle to approximately 5.0–gpm at maximum rated loads for 1–1/2 ton units and approximately 20–gpm at maximum rated loads for 7–1/2 ton units. This valve is factory set to operate where the water supply temper­ature ranges from 50F (10C) to 80F (27C) with a supply pressure of 30 to 60–PSIG. For temperatures or pressure outside these ranges, contact our Technical Service Department for assistance in “field” adjustment of the valve. Once the system as been properly plumbed, it is important that the circulation system be filled with water.
3
91961OPR
Chiller with Reservoir
The reservoir can be filled by removing the water fill cap located on the upper rear of the Chiller (See Fluid Rec­ommendations page). After ensuring that the drain valve is closed, fill the reservoir via the full port with clean water until the water level sight glass on the front of the unit indicates “FULL” the fill cap should then be rein­stalled before operation begins.
Auto Refill Option
If the Chiller is provided with the Auto Refill Option, install 1/4–inch or 1/2–inch tubing from the auto refill fitting located on the lower rear of the Chiller to a fresh water supply line. The Chiller reservoir will fill with water auto­matically and the proper reservoir level will always be maintained.
Chiller without Reservoir
The Chiller and system piping should be filled with clean water ensuring that all air is purged from the system.
91961OPR
4
RESERVOIR
LOW TEMP. CONTROL
FROM PROCESS
EVAPORATOR
PUMP BYPASS VALVE
CHILLER INLET
TO PROCESS
CHILLER OUTLET
FIGURE 2. CHILLER PLUMBING SCHEMATIC WITH PUMP AND TANK (STANDARD)
FROM PROCESS
EVAPORATOR
EVAPORATOR
CHILLER INLET
LOW TEMP. CONTROL
BYPASS VALVE
CHILLER OUTLET
FIGURE 3. CHILLER PLUMBING SCHEMATIC NO TANK (OPTION)
CHILLER INLET
LOW TEMP. CONTROL CHILLER OUTLET
TO PROCESS
FROM PROCESS
TO PROCESS
FIGURE 4. CHILLER PLUMBING SCHEMATIC NO PUMP, NO TANK (OPTION)
5
91961OPR
Loading...
+ 18 hidden pages