Cornelius CH 250, CH 251 User Manual

IMI CORNELIUS REMCOR INC g 500 REGENCY DRIVE g GLENDALE HEIGHTS, IL 60139–2268
Telephone (800) 551–4423 Facsimile (800) 519–4423
Operator’s Manual
CHILLER (“CH” SERIES)
Models: CH 250
CH 251
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must be read and understood before installing or operating this equipment
IMI CORNELIUS INC; 1999–2002
PRINTED IN U.S.A
TABLE OF CONTENTS
GENERAL INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNPACKING AND INSPECTION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DESIGN DATA 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DATA PLATE INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER INSTALLATION 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOCATION OF CHILLER 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL CONNECTIONS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START UP 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROCESS WATER FLOW, UNITS WITH PUMP AND TANK (STANDARD) 2. . PROCESS WATER FLOW, UNITS WITHOUT RESERVOIR (OPTIONAL) 3. . .
THERMOSTAT ADJUSTMENT 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STANDARD THERMOSTAT 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER MAINTENANCE 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSER 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FAN MOTOR 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP MOTOR 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CIRCULATION SYSTEM 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FILTERS/STRAINERS 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FLUID RECOMMENDATION 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
TROUBLESHOOTING 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHILLER DOES NOT OPERATE, CONTROL POWER LIGHT “OFF” 6. . . . . . . . .
PUMP DOES NOT OPERATE, BUT POWER LIGHT IS “ON”.6. . . . . . . . . . . . . . .
UNIT RUNS CONTINUOUSLY, BUT IS NOT COOLING PROCESS
WATER ENOUGH. 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF FIGURES
FIGURE 1. SAMPLE DATA PLATE 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 2. EXTERNAL RESERVOIR WATER LEVEL 3. . . . . . . . . . . . . . . . . . . . . .
FIGURE 3. WIRING DIAGRAM (115V) 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 4. WIRING DIAGRAM (230V) 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 4. CABINET SECTION EXPLODED VIEW 8. . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS
TABLE 1. DESIGN DATA 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i
620914801
GENERAL INFORMATION
INTRODUCTION
The REMCOR ”CH” Series Recirculating Water Chiller is designed to provide an accurate, reliable, and user– friendly system for cooling a continuous flow of water and keep it at a constant temperature in various closed loop or tank cooling applications.
The CH Series Chiller consists of an air–cooled refrigeration system housed in a sturdy sheet metal frame and cabinet. A standard pump and insulated water reservoir package provides a complete liquid cooling and circu­lating system.
The CH Series Chiller is designed to operate in a clean laboratory or industrial environment where ambient temperatures range from 40 to100° F (5 to 38° C). With proper installation, operation, and maintenance, the CH Series Chiller will provide years of trouble free service.
UNPACKING AND INSPECTION
This unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it. Any damage or irregularities should be noted at the time of delivery and immediately reported to the carrier. Re­quest a written inspection report from the Claims Inspector to substantiate any necessary claims. In the event that an immediate replacement is necessary, please contact REMCOR Chiller Sales at 1–800–551–4423.
DESIGN DATA
Table 1. Design Data
CH250 CH251
Cooling Capacity:
BTU/hr (W) at 80_ F(27_ C) and 70_ F (21_ C) Liquid Temperature.
3,000 (879) 3,000 (879)
Compressor Horsepower .25 (.2 kW) .25 (.2 kW) Electrical Data:
Voltage/Phase/Hertz/Amperage
115/1/60
7.5 Amps
230/1/60
3.8 Amps Refrigerant Type: R134a R134a Physical Dimensions, Width X Depth
X Height
17.125 X 14.125 X 13.375 (43.5 cm X 35.9 cm X 34cm)
17.125 X 14.125 X 13.375 (43.5 cm X 35.9 cm X 34cm
Fittings:
Process Connections 1/2 FPT (S/S)
Optimum Process Liquid Flow GPM
0.6 (2.72) 0.6 (2.72)
1/2I FPT (S/S)
(Liters/Min) Condenser Air Flow (CFM) 225 225
DATA PLATE INFORMATION
REMCOR PRODUCTS COMPANY
GLENDALE HEIGHTS, IL. 60139–2268
MODEL NO. SERIAL NO.PART NO.
VOLTS AMPS
MADE IN U.S.A.
BAR CODE
R134AHZ PH
FIGURE 1. SAMPLE DATA PLATE
1
620914801
When servicing a REMCOR Chiller, it is important to note the information contained on the data plate located in the upper rear of the Unit.
If technical assistance is needed, the phone technician will need the Serial Number of your Chiller. That informa­tion is found on the Data Plate along with the model number, voltage requirement, and refrigerant information.
The serial Number is also needed when replacement parts are being ordered or for warranty claims. See CHILLER WARRANTY PAGE.
Be sure to include the serial number on any documentation or billing information.
CHILLER INSTALLATION
Location of Chiller
THE CHILLER MUST BE LOCATED NEAR A PROPERLY GROUNDED ELECTRICAL OUTLET. THE CIR­CUIT SHOULD BE FUSED AND NO OTHER ELECTRICAL APPLIANCE SHOULD BE CONNECTED TO THE CIRCUIT. ALL ELECTRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL CODES.
The Chiller must be located in a well ventilated, indoor area where ambient temperatures will remain above 40_ F (5_ C) and will never increase above 100_ F (38_ C). To obtain optimum cooling capacity, the ambient temperature should be at or below 80_ F (27_ C).
It is very important that the air intake and discharge sides of the chiller are not obstructed by other free standing objects. A minimum of two feet of space on all four sides of the chiller will be sufficient to prevent air flow ob­structions.
It is also important to direct any hot air discharge from other equipment away from the air intake side of the chill­er. Condenser air entering the CH unit should be below 100_ F (38_ C) .Condenser air temperatures above 100_ F (38_ C) can cause the high pressure safety control to shut down the unit.
Electrical Connections
(see Figure 3) All wiring must conform to the National Electric Code and any applicable local codes. The Chiller must be
permanently wired by means of electrical conduit to a properly fused disconnect of proper amperage or wired to a properly rated power cord and plugged into an outlet with the appropriate disconnect and amperage rating. The electrical junction box, located on the back panel of the Chiller, includes a four terminal strip for power supply connection.
The data plate, located next to the junction box, includes the actual voltage, phase, and amperage of the Chiller.
START UP
WARNING: Never operate the Chiller with its panels removed.
Always use the power switch to turn off the Chiller when it is not being used. Always ensure that all air inlets and outlets are free from obstruction. Be sure that the reservoir is filled with fluid prior to powering up the unit (see Fluid
Recommendations page).
Process Water Flow, Units with Pump and Tank (Standard)
Follow standard plumbing practices and local codes in making water connections. The Chiller inlet and outlet connections are 3/4. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh strainer should be installed on the Chiller inlet to prevent foreign particles from entering the system and should be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near
620914801
2
radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient temperatures should be insulated to prevent condensation and/or significant liquid heat loss.
After ensuring that the system is free from the obstruction, that all valves are open, and the reservoir when avail­able is full, push the CONTROL POWER switch to the ON position. The pump should now be operating.
Process Water Flow, Units Without Reservoir (Optional)
Follow standard plumbing practices and local codes in making water connections. The Chiller inlet and outlet connections are 3/4. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh strainer should be installed on the Chiller inlet to prevent foreign particles from entering the system and should be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient temperatures should be insulated to prevent condensation and/or significant water heat loss.
Proper priming of the water lines is essential to prevent pump cavitation. Be certain all air has been purged from the lines before operating the pump for an extended period of time. Be sure to remove any loops in the lines that may trap air. The pump must have a supply of water with the level of the water above the inlet of the Chiller. The supply tank must feed the Chiller from the side of the tank below the water level (see Figure 2).
CHILLER
INLET
LINE
WATER LEVEL
CHILLER
INLET
LINE
CHILLER
W/O TANK
WATER LEVEL IS
BELOW CHILLER INLET
INCORRECT
CHILLER
W/O TANK
WATER LEVEL
EXTERNAL
RESERVOIR
EXTERNAL
RESERVOIR
CORRECT
CHILLER
INLET
LINE
CHILLER
W/O TANK
AIR CAN BE TRAPPED IN CHILLER INLET
INCORRECT
WATER LEVEL
EXTERNAL
RESERVOIR
CHILLER
INLET
LINE
CHILLER
W/O TANK
WATER FEEDING FROM
TOP OF TANK
INCORRECT
WATER LEVEL
EXTERNAL
RESERVOIR
FIGURE 2. EXTERNAL RESERVOIR WATER LEVEL
THERMOSTAT ADJUSTMENT
Standard Thermostat
The following procedure should be followed to adjust the standard thermostat:
3
620914801
Loading...
+ 9 hidden pages