Cornelius CH1500-CH7500, CH1500, CH7500 Operator's & Installation Manual

Page 1
CHILLER
MODELS: CH5000 & CH7500
Operator’s & Installation Manual
Release Date: July, 1997
Publication Number: 91961OPR
Revision Date: March 24, 2011
Revision: F
Visit the IMI Cornelius web site at www.cornelius.com
Page 2
The products, technical information, and instructions contained in this manual are subject to change without notice. These instructions are not intended to cover all details or variations of the equipment, nor to provide for every possible contingency in the installation, operation or maintenance of this equipment. This manual assumes that the person(s) working on the equipment have been trained and are skilled in working with electrical, plumbing, pneumatic, and mechanical equipment. It is assumed that appropriate safety precautions are taken and that all local safety and con­struction requirements are being met, in addition to the information contained in this manual.
This Product is warranted only as provided in Cornelius’ Commercial Warrant applicable to this Product and is subject to all of the restrictions and limitations contained in the Commercial Warranty.
Cornelius will not be responsible for any repair, replacement or other service required by or loss or damage resulting from any of the following occurrences, including but not limited to, (1) other than normal and proper use and normal service conditions with respect to the Product, (2) improper voltage, (3) inadequate wiring, (4) abuse, (5) accident, (6) alteration, (7) misuse, (8) neglect, (9) unauthorized repair or the failure to utilize suitably qualified and trained persons to perform service and/or repair of the Product, (10) improper cleaning, (11) failure to follow installation, operating, cleaning or maintenance instructions, (12) use of “non-authorized” parts (i.e., parts that are not 100% compatible with the Product) which use voids the entire warranty, (13) Product parts in contact with water or the product dispensed which are adversely impacted by changes in liquid scale or chemical composition.
Contact Information:
To inquire about current revisions of this and other documentation or for assistance with any Cornelius product con­tact:
www.cornelius.com
800-238-3600
Trademarks and Copyrights:
This document contains proprietary information and it may not be reproduced in any way without permission from Cornelius.
Printed in U.S.A.
Page 3
TABLE OF CONTENTS
Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Read and Follow ALL Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Recognition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Different Types of Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Qualified Service Personnel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Shipping And Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specification Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chiller with Reservoir . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chiller without Reservoir . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Water Flow Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chiller with Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chiller without Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Standard Therostat Eliwell IC902 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dual Point Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fluid Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Safety Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
High Pressure Control (HPC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Low Temperature Control (LTC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Low Pressure Control (LPC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chiller Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Pump and Tank Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Page 4
Electrical Box Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Page 5
CH5000 & CH7500 Chiller Operator’s & Installation Manual
!
DANGER:
!
WARNING:
CAUTION:
!
!
WARNING:
!
SAFETY INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Safety Overview
• Read and follow ALL SAFETY INSTRUCTIONS in this manual and any warning/caution labels on the unit (decals, labels or laminated cards).
• Read and understand ALL applicable OSHA (Occupational Safety and Health Administration) safety regulations before operating this unit.
Recognition
Recognize Safety Alerts
This is the safety alert symbol. When you see it in this manual or on the unit,
be alert to the potential of personal injury or damage to the unit.
DIFFERENT TYPES OF ALERTS
Indicates an immediate hazardous situation which if not avoided WILL result in serious injury, death or equipment damage.
Indicates a potentially hazardous situation which, if not avoided, COULD result in serious injury, death, or equipment damage.
Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury or equipment damage.
SAFETY TIPS
• Carefully read and follow all safety messages in this manual and safety signs on the unit.
• Keep safety signs in good condition and replace missing or damaged items.
• Learn how to operate the unit and how to use the controls properly.
• Do not let anyone operate the unit without proper training. This appliance is not intended for use by very young children or infirm persons without supervision. Young children should be supervised to ensure that they do not play with the appliance.
• Keep your unit in proper working condition and do not allow unauthorized modifications to the unit.
QUALIFIED SERVICE PERSONNEL
Only trained and certified electrical, plumbing and refrigeration technicians should service this unit. ALL WIRING AND PLUMBING MUST CONFORM TO NATIONAL AND LOCAL CODES. FAILURE TO COMPLY COULD RESULT IN SERIOUS INJURY, DEATH OR EQUIPMENT DAMAGE.
© 2006-2011, IMI Cornelius Inc. - 1 - Publication Number: 91961OPR
Page 6
CH5000 & CH7500 Chiller Operator’s & Installation Manual
!
WARNING:
CAUTION:
!
CAUTION:
!
SAFETY PRECAUTIONS
This unit has been specifically designed to provide protection against personal injury. To ensure continued protection observe the following:
Disconnect power to the unit before servicing following all lock out/tag out procedures established by the user. Verify all of the power is off to the unit before any work is performed.
Failure to disconnect the power could result in serious injury, death or equipment damage.
Always be sure to keep area around the unit clean and free of clutter. Failure to keep this area clean may result in injury or equipment damage.
SHIPPING AND STORAGE
Before shipping, storing, or relocating the unit, the unit must be sanitized and all sanitizing solution must be drained from the system. A freezing ambient environment will cause residual sanitizing solution or water remaining inside the unit to freeze resulting in damage to internal components.
Publication Number: 91961OPR - 2 - © 2006-2011, IMI Cornelius Inc.
Page 7
CH5000 & CH7500 Chiller Operator’s & Installation Manual
!
WARNING:
GENERAL INFORMATION
INTRODUCTION
Remcor “CH” Series Refrigerated Recirculating Water Chillers are designed to provide a continuous flow of clean cooling water at a constant temperature and to handle a variety of closed loop and tank cooling applications.
The CH consists of a refrigeration system with associated operating controls housed in a sturdy sheet metal cabinet. A standard pump and reservoir package provides a complete self-contained water cooling and circulating system.
CH Chillers are designed to operate in a clean laboratory or industrial environment where ambient temperatures range from 40
free and provide a constant supply of cooling liquid to the application.
NOTE: Please read through this manual before starting the chiller.
Cooling Capacity* Watts/BTU 17,584/60,000 26,376/90,000
Compressor 5 H.P. 7.5 H.P.
Condenser Air Cooled
Temperature Controller
Pump** 2CS (12 GPM @ 50 PSI)
Reservoir 40 Gallons
Voltage (Full Load Amps)
Dimensions W x D x H (inches) 36” x 36” x 65” (91.4cm x 91.4cm x 165cm)
Inlet/Outlet Fitting Size 1 inch
o
F (4.4o C) to 110o F (43.3o C). Once properly installed, the CH Chiller will run virtually maintenance
Table 1. Specifications
Model CH5000 CH7500
o
Digital Display 40-100
CH5002A 230/60/3 (28) CH7502A 230/60/3 (36)
CH5003A 460/60/3 (14) CH7503A 460/60/3 (18)
F (4.4-37.8o C.)
SPECIFICATION NOTES
1. The figures for power and cooling capacity are listed for air-cooled units with a circulation temperature of
o
68
F, and ambient temperature of 80o F and standard pump.
2. Cooling capacity will be affected as follows: Derate 17% for 50 Hz operation. Derate 1% for each degree Fahrenheit drop in recirculating temperature. Derate .5% for each degree Fahrenheit increase in ambient temperature. Optional pumps will decrease net cooling capacity.
3. The operating water temperature range for water is 40 or temperatures are required, the Technical Service Department must be contacted so the appropriate ranges can be set.
4. Water-cooled units require about 20% less input power.
5. All CH Chillers are thoroughly tested before leaving the factory to ensure that each unit meets these spec­ifications prior to shipment.
Never operate the chiller with the panels removed. Always use the power switch to turn off the chiller when it is not being used. Always ensure that all air inlets and outlets are free of obstructions.
o
F (4.4o C) to 100o F (37.8o C). If use of other fluids
© 2006-2011, IMI Cornelius Inc. - 3 - Publication Number: 91961OPR
Page 8
CH5000 & CH7500 Chiller Operator’s & Installation Manual
Control Panel
(See Detail)
Electrical Junction Box
Tank Fill 1 In. FPT
Tank Level Gauge
Air Outlet
(Air Inlet on Opposite Side)
Water Inlet
Water Outlet
Tank Drain
INSTALLATION
LOCATION
Install the chiller indoors in a well ventilated area where ambient temperatures will never fall below 40o F or rise above
o
110
F. To obtain optimum cooling capacity, the ambient temperature should be 80o F or below.
Standard CH Chillers have air-cooled condensers. On air-cooled units it is important that the air intake and discharge are not obstructed. Avoid hot air discharge from other equipment or enclosed areas where heat buildup could cause a significant rise in ambient temperatures. A minimum of two feet of space on all four sides of the chiller will be sufficient to prevent obstruction. Water-cooled units should be located near a water source and drain.
ELECTRICAL
All wiring must conform to the National Electric Code and any applicable local codes. The chiller must be PERMANENTLY wired by means of electrical conduit to a properly fused disconnect of proper amperage or wired to a properly rated power cord and plugged into an outlet with the appropriate disconnect and amperage rating. The
Publication Number: 91961OPR - 4 - © 2006-2011, IMI Cornelius Inc.
Figure 1. Installation Details
Page 9
CH5000 & CH7500 Chiller Operator’s & Installation Manual
CAUTION:
!
Reservoir
Low Temp. Control
Evaporator
Chiller Inlet
From Process
To Process
Pump
Bypass Valve
Chiller Outlet
electrical junction box located on the upper rear of the chiller, includes a four–terminal strip for power supply connections The data plate, located beside the junction box, indicates the actual phase, voltage and amperage for each chiller.
After the electrical connections are made, power switched off) to allow the compressor crankcase heater to warm the compressor lubricant.
On three phase applications, it is important that the rotation of the pump, when supplied, is correct. Running the pump in reverse for more than a few seconds results in permanent pump damage. When the pump is running, shaft rotation must match the direction indicated on the pump housing. If the rotation is incorrect, reverse two of the three incoming power supply leads.
must
be supplied to the chiller for a period of 12 hours (with control
PLUMBING
Follow standard plumbing practices and local codes in making water connections. The chiller inlet and outlet connections are 1-inch FPT. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh strainer should be installed on the chiller inlet to prevent foreign particles from entering the system and should be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient temperatures should be insulated to prevent condensation and/or significant liquid heat loss.
Chiller with Reservoir
The reservoir can be filled by removing the water fill cap located on the upper rear of the chiller (See Fluid Recommendations section). After ensuring that the drain valve is closed, fill the reservoir via the full port with clean water until the water level sight glass on the front of the unit indicates “FULL” the fill cap should then be reinstalled before operation begins.
Chiller without Reservoir
The chiller and system piping should be filled with clean water ensuring that all air is purged from the system.
Figure 2. Chiller Plumbing Schematic with Pump and Tank (Standard)
© 2006-2011, IMI Cornelius Inc. - 5 - Publication Number: 91961OPR
Page 10
CH5000 & CH7500 Chiller Operator’s & Installation Manual
Low Temp. Control
Evaporator
Chiller Inlet
From Process
To Process
Pump
Bypass Valve
Chiller Outlet
Low Temp. Control
Evaporator
Chiller Inlet
Chiller Outlet
From Process
To Process
Figure 3. Chiller Plumbing Schematic No Tank (Option)
Figure 4. Chiller Plumbing Schematic No Pump, No Tank (Option)
Publication Number: 91961OPR - 6 - © 2006-2011, IMI Cornelius Inc.
Page 11
CH5000 & CH7500 Chiller Operator’s & Installation Manual
!
WARNING:
START UP
WATER FLOW START-UP
Chiller with Pump
It is important to check the pump rotation on the three phase units. Remove the lower side panel to expose the pump. Turn the pump power switch to the “ON” position for a few seconds. Observe the motor shaft to ensure that it is turning in the direction indicated by the arrow located on the pump housing. If the rotation is incorrect, reverse two of the three incoming power supply leads at the terminal strip. After changing the leads, check the pump rotation.
Running the pump in reverse for more than a few seconds results in permanent pump damage.
After ensuring that the system piping is free from obstruction and that all valves are open, turn the pump power switch to the “ON” position. The pump power indicator should illuminate, indicating that the pump is operating.
All Chillers with pumps are provided with a pressure regulating valve on the pump discharge. This valve is preset at the factory to ensure that system pressure does not exceed the capabilities of the pump motor and/or piping. If this valve requires adjustment, please contact the factory for proper setting procedure and pressures.
A flow meter and throttling valve can be added in the chiller inlet line in order to monitor and/or adjust the flow rate through the Chiller.
Once the flow has been established, the thermostat can be adjusted to the desired set–point.
Chiller without Pump
A flow meter and throttling valve can be added in the Chiller inlet line in order to monitor and/or adjust the flow rate through the Chiller.
Once the flow has been established, the thermostat can be adjusted to the desired set–point. See thermostat adjustment.
STANDARD THEROSTAT ELIWELL IC902
The following procedure should be followed to adjust the Eliwell IC902 thermostat temperature setting:
1. To set the “SET POINT”, press and release the “SET” button. “SET” displays.
2. Press the “SET” button again, the current “SET POINT” is displayed. Press the UP or DOWN button to change the “SET POINT” to the desired temperature.
3. Press the “fnc” button twice to exit the program. The current liquid temperature is displayed.
The thermostat has a range that is preset at the factory. The range is 40 outside of this range is required, please contact the Technical Service Department.
o
F (4.4o C) to 100o F (37.8o C). If operation
© 2006-2011, IMI Cornelius Inc. - 7 - Publication Number: 91961OPR
Figure 5. IC902 Eliwell Thermostat
Page 12
CH5000 & CH7500 Chiller Operator’s & Installation Manual
Dual Point Adjustment
1. To set the “SET POINT” for Level 1. Press and release the “SET” button, Re1 should be displayed.
2. Press the “SET” button, the current SET POINT TEMPERATURE should be displayed. Press the UP or DOWN button to change the SET POINT.
3. To set the “SET POINT” for Level 2. Press and release the “SET” button, Re2 should be displayed.
4. Press the “SET” button, the current SET POINT TEMPERATURE should be displayed. Press the UP or DOWN button to change the SET POINT.
5. Press the fnc button to exit the program.
The thermostat has a range that has been preset at the factory. The range is 40
o
F (4.4
o
C) to 100o F (37.8o C). If
operation outside of this range is required, please contact the Technical Service Department.
Cooling Start-Up
Once flow is established and the thermostat is set to the desired set–point, turn the control power switch to “ON”. Ensure that the air is flowing in the left side (facing the control panel) and out the right side. If not, reverse two of the three incoming power supply leads at the terminal strip. Once again, check for correct air flow. All alarm indicators should be extinguished and the Chiller refrigeration system will cycle in order to maintain the established set–point.
Re-check the reservoir level to ensure that it is ”FULL” (if so equipped) and add water if necessary.
The Chiller is now ready for normal operation.
Control Panel
1. TEMPERATURE INDICATOR/CONTROLLER (Thermostat)– Combines a precise temperature control and accurate set ability with a convenient LED temperature readout that indicates system liquid temperature.
2. CONTROL POWER SWITCH– A simple (ON/OFF) switch that switches power to the control circuit. This switch must be “ON” for the Chiller to operate.
3. COOLING LIGHT– A green light that indicates refrigeration system operation. This light cycles on and off in response to the thermostat.
4. HIGH PRESSURE ALARM LIGHT– A red light that indicates high refrigeration pressure.
5. LOW PRESSURE ALARM LIGHT– A red light that indicates low refrigeration pressure.
6. LOW TEMPERATURE ALARM LIGHT– A red light that indicates and abnormally low system fluid temperature.
7. PUMP POWER SWITCH (OPTIONAL)– A simple (ON/OFF) switch that switches power to the Chiller pump. This switch must be “ON” for the Chiller to operate.
Publication Number: 91961OPR - 8 - © 2006-2011, IMI Cornelius Inc.
Figure 6. Control Panel
Page 13
CH5000 & CH7500 Chiller Operator’s & Installation Manual
!
WARNING:
MAINTENANCE
Disconnect power to the unit before servicing. Follow all lock out/tag out procedures established by the user. Verify all power is off to the unit before performing any work.
Failure to comply could result in serious injury, death or damage to the equipment.
The chiller requires very little normal maintenance.
1. On AIR-COOLED Chillers, the condenser fins should be cleaned by blowing compressed air through the condenser from the fan side as required to eliminate any dirt or debris that may accumulate over time. This can severely reduce the performance of the Chiller. Cleanable air filters are available as an option. Contact the factory for information.
2. On AIR-COOLED Chillers the condenser fan motor should be lubricated every 6-months with a few drops of SAE10 oil.
3. The pump motor should be lubricated with thirty drops of SAE20 oil once a year.
4. The circulation system should be drained and flushed periodically to avoid build-up and possible restriction of flow by contaminates.
5. The strainer at the Chiller inlet should be removed and cleaned monthly (field installed).
© 2006-2011, IMI Cornelius Inc. - 9 - Publication Number: 91961OPR
Page 14
CH5000 & CH7500 Chiller Operator’s & Installation Manual
FLUID RECOMMENDATION
Chillers are designed to operate with water to provide maximum performance for temperatures of 40o F (4.4
o
100
F (37.8o C).
Table 2.
Distilled Water Acceptable
De-Ionized Water (1-5 MEG/OHMS)
De-Ionized Water (5+MEG/OHMS)
Propylene Glycol (Lab & Industrial Grade)
Lab & Industrial Grade Ethylene Glycol
Mineral/Hydraulic Oils (Viscosity<50 Centistokes)
Ethylene Glycol (Commercial/Automotive Antifreeze)
Acidic/Basic Solutions (Above 8/Below 6 PH)
Mineral/Hydraulic Oils (Viscosity>50 Centistrokes)
Acceptable
Acceptable with Stainless Steel & PVC only *No Copper or Brass
Acceptable - 30% Glycol/70% Water
o
*For Applications with Temperatures below 40
Acceptable - 30% Glycol/70% Water
*For Applications with Temperatures below 40
Acceptable
NOT Acceptable *Silicate Rust Inhibitors in Automotive/Commercial Antifreeze dam-
ages pump seals and housing which leads to failure.
Not Acceptable
Not Acceptable
F (4.4o C)
o
F (4.4
o
C)
o
C) to
For questions regarding special or other fluids contact IMI Cornelius at 800-238-3600.
To Purchase Lab or Industrial Glycol contact:
IMI Cornelius - (800) 551-4423 - Part # 111521000, 5 gallons
Bevcor (866) 275-6392 - Part # 1008534, Chem Glycol Food Grade , 5 gallons
Publication Number: 91961OPR - 10 - © 2006-2011, IMI Cornelius Inc.
Page 15
CH5000 & CH7500 Chiller Operator’s & Installation Manual
SAFETY CONTROLS
Each chiller is provided with three standard safety controls. These controls are arranged in series in the control circuit to automatically shut down the unit in the event that a condition exists which could be harmful to the refrigeration system components. This section includes a brief description of each control, its location and some troubleshooting hints that may be helpful.
HIGH PRESSURE CONTROL (HPC)
This control prevents system operation in the event that the high side pressure exceeds 250 PSIG (17.2 bar). If this occurs, check the following:
1. That the condenser is clean and that the air inlets and outlets are unobstructed.
2. That the ambient temperature at the chiller location is below 110
3. That the fan blade is rotating.
Press the reset button located on the front of the control to restart the chiller. This control is located in the upper left hand corner of the electric box. If the control opens again, check the control setting with refrigeration gauges. If the setting is correct, contact technical service department.
LOW TEMPERATURE CONTROL (LTC)
o
F (43.3o C).
This control prevents system operation in the event that the fluid inside the evaporator falls below 35o F (1.67o C). If this occurs, check the following:
1. That the thermostat set point is set at 40
2. That the flow through the system is greater than 2 gallons per minute.
This control is mounted in the lower left hand corner of the electric box. It automatically resets itself once the water temperature is restored to 38
glycol solution is used. Contact Technical Service Department for temperatures below those stated here (See Fluid Recommendations section).
o
F (3.3o C). The low temperature control may be adjusted for lower temperatures if a
o
F (4.4o C) or greater.
LOW PRESSURE CONTROL (LPC)
This control prevents system operation in the event that the low side pressure falls below 44 psi. If this occurs, check the following:
1. That the thermostat set point is set at 40
2. That the flow through the system is greater than 2 gallons (7.6 liters) per minute.
3. That no bubbles are present in the sight glass.
4. That water bypass valve allows flow through the Chiller in a “dead head” situation.
This control is located to the right of the high pressure control in the electric box. It automatically resets itself once the low side pressure rises to approximately 64 psi (4.4 bar). If the control opens again, check the control setting with refrigeration gauges. If setting is correct, contact Technical Service Department.
o
F (4.4o C) or greater.
© 2006-2011, IMI Cornelius Inc. - 11 - Publication Number: 91961OPR
Page 16
CH5000 & CH7500 Chiller Operator’s & Installation Manual
TXV Equalizer Line
TXV
Evaporator
TXV Sensing Bulb
Compressor
Low Pressure Switch
High Pressure Switch
Condenser
Liquid Reveiver
Filter/Drier
Sight Glass
Figure 7. Refrigeration Piping Schematic without Hot Gas Bypass
Publication Number: 91961OPR - 12 - © 2006-2011, IMI Cornelius Inc.
Page 17
CH5000 & CH7500 Chiller Operator’s & Installation Manual
SERVICE
When servicing a chiller, it is important to note the information contained on the data plate located in the upper rear of the unit.
If technical assistance is needed, the phone technician will need the Serial Number of your Chiller. That information is found on the Data Plate along with the model number, voltage requirements and refrigerant information.
The Serial Number is also needed when replacement parts are being ordered or for any warranty claims.
Figure 8. Sample Data Plate for CH5002-A
Be sure to include the serial number on any documentation or billing information.
© 2006-2011, IMI Cornelius Inc. - 13 - Publication Number: 91961OPR
Page 18
CH5000 & CH7500 Chiller Operator’s & Installation Manual
TROUBLESHOOTING
Tabl e 3 .
Trouble Probable Cause Remedy
A. Control power switch “Off”.
Chiller does not operate. Control power light “off”
Pump does not operate. pump power light “off”
Pump does not operate. Pump power light “On”.
Chiller does not cool. Cooling light “Off”.
Chiller does not operate. Cooling light “On”.
Low pressure alarm light cycles on/off.
High pressure alarm light “On”.
Low temperature alarm
B. No power.
C. Defective power supply connection. D. Defective control power switch. E. Defective control transfromer.
A. Pump power switch “Off”.
B. Defective pump power switch. C. Defective control transformer.
A. No water in reservoir.
B. Restriction in the line to or from the
chiller.
C. Open or defective pump overload relay.
D. Defiective pump contactor. E. Defective pump motor or damaged
impller.
A. Defective thermostat. A. Replace thermostat.
A. Process water too cold.
B. Low process water flow.
C. Defective expansion valve. D. Refrigerant loss.
E. Water bypass valve failed.
F. Defective pump.
A. Restricted condenser airflow.
B. Defective condenser fan and/or motor.
C. Defective expansion valve.
D. Low or no condenser water flow.
A. Low or no process liquid flow.
B. Defective thermostat.
C. Process water too cold – below 35
A. Turn the control power switch to the
“On” position.
B. Check the fuse or circuit breaker. C. Check wiring and correct loose or
poor connections. D. Replace the switch. E. Replace the transformer.
A. Turn the pump power switch to the
“On” position.
B. Replace the switch. C. Replace the transformer.
A. Fill reservoir.
B. Remove restriction.
C. Manually reset the relay or replace if
necessary and check amp setting
on overload. D. Replace the pump contactor. E. Replace the pump or impeller.
A. Increase the thermostat setting.
B. Ensure that there is adequate flow
through the process piping. C. Replace the expansion valve. D. Check the sight glass. If bubbles are
seen flowing through it, the chiller
needs to be leak checked and
recharged with refrigerant. E. Consult Technical Service Depart-
ment. F. Replace pump.
A. Clean the fins of the condenser and
ensure that the air flow is not
restricted.
B. Check to ensure that the fan blade
is not blocked. Replace the fan
motor if necessary. C. Check to ensure that the fan blade
is not blocked. Replace the fan
motor if necessary. D. Ensure that there is adequate flow
throught piping to condenser.
A. Ensure that there is adequate flow
through the process piping.
B. Replace the thermostat.
o
C. Increase the thermostat setting.
F.
Publication Number: 91961OPR - 14 - © 2006-2011, IMI Cornelius Inc.
Page 19
CHILLER ASSEMBLY
1
2
3
4
5
6
7
8
9
10
11
26
12
13
14
15
16
17
18
19
20
21
4
10
22
23
24
25
CH5000 & CH7500 Chiller Operator’s & Installation Manual
PARTS LIST
Table 4. Chiller Assembly
Index No. Description
1 1/2” FPT Coupling 2 Thermowell, Low Temp. Thermostat (Not Shown) 3 Corner Cover 4 Side Panel 5 Rear Panel 6 Upper Front Panel 7 Lower Front Panel 8Lid
9 Control Panel 10 FPT Coupling 11 Temperature Control 12 Electric Box Assembly 13 Fan Blade 14 Fan Motor
Figure 9. Chiller Parts Breakdown
Index No. Description
15 White Switch/Indicator 16 Red Indicator 17 Green Indicator 18 Compressor 19 Accumulator 20 Filter/Drier 21 TX Valve 22 Evaporator Assembly 23 Condenser 24 Compressor 25 Receiver
26 Caster NS Condenser, Water Cooled NS Regulating Valve, Water Cooled Condenser
* Call the Techncial Service Department for Proper Panel.
Table 4. Chiller Assembly
© 2006-2011, IMI Cornelius Inc. - 15 - Publication Number: 91961OPR
Page 20
CH5000 & CH7500 Chiller Operator’s & Installation Manual
1
2
3
4
5
PUMP AND TANK COMPONENTS
Figure 10. Pump and Tank Components
Table 5. Pump and Tank
Index No. Description
1 Thermowell, Temperature Control
2 Temperature Probe
3 Tank Assembly
4Pump
5 Pump Relief Valve
** Call the Service Department for proper pump identifaction.
Publication Number: 91961OPR - 16 - © 2006-2011, IMI Cornelius Inc.
Page 21
ELECTRICAL BOX COMPONENTS
1
2
3
4
5
6
7
CH5000 & CH7500 Chiller Operator’s & Installation Manual
Table 6. Electrical Box
Index No. Description
1 Low Temperature Thermostat
2 Control Transformer
3 Contactor, Compressor
4 High pressure Control
5 Low Pressure Control
© 2006-2011, IMI Cornelius Inc. - 17 - Publication Number: 91961OPR
Figure 11. Electrical Box Components
Table 6. Electrical Box
Index No. Description
6Contactor, Pump
7 Overload Relay, 1.0 to 1.6A
Overload Relay, 1.4 to 2.0A
Overload Relay, 2.0 to 3.0A
Overload Relay, 2.8 to 4.4A
Overload Relay, 4.0 to 6.0A
Page 22
CH5000 & CH7500 Chiller Operator’s & Installation Manual
WIRING DIAGRAM
Publication Number: 91961OPR - 18 - © 2006-2011, IMI Cornelius Inc.
Figure 12. Wiring Diagram
Page 23
Page 24
IMI Cornelius Inc.
www.cornelius.com
Loading...