Comnet FDC80R485 Specsheet

8-Channel Supervised Contact Closure
Transmitter and Receiver
FDC80 Series
HARDENEDINCLUDED
The ComNet™ FDC80 Series contact closure transmitter and receiver units provide transmission of up to eight independent supervised or unsupervised dry switch or relay contact closures over a single optical fiber, or any two-wire RS-485 copper circuit. Microprocessor-based logic transmits the contact closure information in packets that are ordered and encoded, ensuring extremely robust and reliable transmission. Packets that are garbled, or packets out of sequence with transmission bit errors will not cause random changes of state in the FDC80R receiver unit relays. The supervising function in the FDC80T transmitter allows for the detection of short and open circuit conditions, and normally open or normally closed contact inputs are supported. System faults are displayed via LED status indicators, and user-programmable summary fault alarm contacts are triggered in the FDC80R receiver unit. The FDC80R receiver is offered in both latching and non-latching relay configurations. External series and shunt resistors are included for each of the 8 contact input channels, for contact supervision.
8
FEATURES
› Transmits up to eight independent supervised or unsupervised dry switch or relay contacts over one optical fiber, or via a 2-wire RS-485 point-to-point copper circuit
› Microprocessor-based logic and latching relays in the
receiver unit eliminate random contact closure states in the event of a loss of the link, or a loss of prime operating power
› Tested and certified by an independent laboratory for full
› Indicating LEDs for monitoring power, contact closure status,
and summary fault
› Automatic resettable solid-state current limiters
› Hot-swappable rack modules
› Interchangeable between stand-alone or rack mount use –
ComFit
› Lifetime Warranty
APPLICATIONS
› Alarm Event Triggering
› Fire Alarm & Intrusion Detection Systems
› Lane/Gate Control
› PIR Signal Transmission
› Building Automation and Environmental Control Systems
LIFETIME WARRANTY WWW.COMNET.NET TECH SUPPORT: 1.888.678.9427
FDC80 Series
SPECIFICATIONS
8-Channel Supervised Contact Closure
Transmitter and Receiver
Contacts
Input/Output Channels 8 Input Contacts Normally open or normally closed Output Contact Rating 30 VDC, 1A, resistive load only, normally open Response Time 25 msec, typ. 35 msec, max Summary Fault Alarm 1 (RX Only), dry relay contacts, Form C, 30 VDC 1A, non-latching
Electrical & Mechanical
Rack Slots 1 (Transmitter), 2 (Receiver) Current Protection Automatic Resettable Solid-State Current Limiters Circuit Board Meets IPC Standard Size (L×W×H) Transmitter: 6.1 × 5.3 × 1.1 in (15.5 × 13.5 × 2.8 cm)
Receiver: 6.1 × 5.3 × 2.2 in (15.5 × 13.5 × 5.6 cm)
Shipping Weight <2 lb / 0.9 kg
Connectors:
LED Indicators Contact
Power
Summary Fault
Power
Operating Voltage Range 8 to 15 VDC (or from C1 Rack, sold separately) Power Consumption 3 W Max
Contact Input Screw Terminals Contact Output Screw Terminals Power Screw Terminals Summary Fault Alarm Screw Terminals
Environmental
MTBF >100,000 hours Operating Temp -40˚ C to +75˚ C Storage Temp -40˚ C to +85˚ C Relative Humidity 0% to 95% (non-condensing)¹
ORDERING INFORMATION
Part Number Description
FDC80TM1 8-Channel Supervised Contact Closure Transmitter 1 Multimode‡ – 62.5/125µm 16 dB 16 km (10 mi) 1
FDC80TS1 8-Channel Supervised Contact Closure Transmitter 1 Single Mode‡ – 9/125µm 23 dB 69 km (43 mi) 1
FDC80NLRM1 8-Channel Supervised Contact Closure Receiver (Non-Latching) 1 Multimode‡ – 62.5/125µm 16 dB 16 km (10 mi) 2
FDC80NLRS1 8-Channel Supervised Contact Closure Receiver (Non-Latching) 1 Single Mode‡ – 9/125µm 23 dB 69 km (43 mi) 2
FDC80RM1 8-Channel Supervised Contact Closure Receiver 1 Multimode‡ – 62.5/125µm 16 dB 16 km (10 mi) 2
FDC80R S1 8-Channel Supervised Contact Closure Receiver 1 Single Mode‡ – 9/125µm 23 dB 69 km (43 mi) 2
FDC80T485 8-Channel Super vised Contact Closure Transmit ter, RS-485 Interface — 457 m (1500 ft)³ 1
FDC80R485 8-Channel Supervised Contac t Closure Receiver, RS- 485 Interface 457 m (1500 ft)³ 2
FDC80NLR485
Accessories Options
8-Channel Supervised Contact Closure Receiver (Non-Latching), RS-485 Interface
9 Volt DC Plug-in Power Supply, 90-264 VAC, 50/60 Hz (Included) [1] Add ‘/C’ for Conformally Coated Circuit Boards to extend board to condensation conditions(Extra charge, consult factory) DIN-Rail Mounting Adaptor Plate Kit – With mounting hardware (Optional, order model DINBKT1)
Fibers Req’d Fiber
457 m (1500 ft)³ 2
Optical Pwr Budget
Maximum Distance²
#Rack Slots
[2] Optical transmission distance is limited to optical loss of the fiber and any additional loss introduced by connectors, splices and patch panels.
Distance can also be limited by fiber bandwidth. For 50/125µm Fiber subtract 4 dB from Optical Power Budget.
[3] Distances greater than 1500 ft are possible. Contact factory for further details.
TYPICAL APPLICATION
C C
1k
1k
3 CORPORATE DRIVE
8 TURNBERRY PARK ROAD
8 8
FDC80TS1 FDC80RS1
Optical Fiber
|
DANBURY, CONNECTICUT 06810
|
GILDERSOME
|
MORLEY
|
|
USA
T: 203.796.5300
|
LEEDS, UK LS27 7LE
|
T: +44 (0)113 307 6400
|
F: 203.796.5303
|
TECH SUPPORT: 1.888.678.9427
|
F: +44 (0)113 253 7462
|
INFO-EUROPE@COMNET.NET
ALARM
NC Common NO
|
INFO@COMNET.NET
20 Nov 2014© 2014 Communic ation Netwo rks. All Righ ts Reserv ed. “ComNet ” and the “ComNe t Logo” are regi stered tra demarks of Com munication Ne tworks.
Loading...