CommScope FL1000 User Manual

User Manual
ADCP-90-545 Issue 4, July 2016
Rack-Mount Panel and Wall-Mount Box
Content Page
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1 UNPACKING AND INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 RACK-MOUNT PANEL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 WALL-MOUNT BOX INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 TECHNICAL ASSISTANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FL1000
. . . . . . . . . . .2
2.1 Installing a Rack-Mount Chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1 19-Inch Rack, 5-Inch Recess (as Shipped). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1.2 19-Inch Rack, Flush; 23-Inch Rack, 5-Inch Recess; 23-Inch Rack, Flush. . . . . . . . . . . . . . . . . . . . . 4
2.2 Installing 6pak Adapter Plates and Pigtails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Adapter Plates Without Pigtails (Blank or 6Pak) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2.2 Adapter Plates With Pigtails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Installing Cables and Routing Fibers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 12-Fiber Termination Rack Mount Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3.2 24-Fiber Termination Rack Mount Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3.3 24-Fiber Termination/Splicing Rack-Mount Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4 Splicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Installing the Wall-Mount Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Installing 6pak Adapter Plates and Pigtails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Installing Cables and Routing Fibers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 12-Fiber Termination/Splicing Wall-Mount Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3.2 24-Fiber Termination/Splicing Wall-Mount Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.3.3 48-Fiber Splicing Wall-Mount Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Splicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Installing Patch Cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Cleaning Adapters and Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .14
. . . . . . . .14
. . . . . . . . . . . . .32
. . . . . . . . . . . . . . .33
. . . . . . . . . .33
. . . . . . . . . . .34
. . . . . . . .3
. . . . . .5
6
. . . . . . . .8
. . . . . . .14
. . . . .17
. . . . . . .19
29
. . . . . . .33
INTRODUCTION
FL1000 products provide solutions for terminating and splicing fibers in small fiber networks. The product line consists of three rack-mount panels and three wall-mount boxes. The rack-mount panels include a 12-fiber termination panel, a 24-fiber termination panel, and a 24-fiber termination/splicing panel. The wall-mount boxes include a 12-fiber termination/splicing box, a 24-fiber termination/ splicing box, and a 48-fiber splicing box. Options include 6pak adapter plates, with or without pigtails, splice trays, and cable kits.
300001735123 Rev C Page 1
www.commscope.com © 2016 CommScope. All Rights Reserved.
ADCP-90-545 • Issue 4 • July 2016
This manual contains all procedures required to install and operate any FL1000 product or product option. The procedures are presented in the order in which they would normally be done, with separate installation sections for rack-mount and wall-mount units. Select from the procedures based on your specific installation.
Revision History
ISSUE DATE REASON FOR CHANGE
Issue 1 09/1998 Original. Issue 2 04/2001 Non-technical update. Issue 3 08/2011 Revised for new two-door design for wallbox. Issue 4 July 2016 Reformatted for CommScope.
Trademark Information
FL1000
is a registered trademark of CommScope . In c.
ST is a registered trademark of AT&T Technologies, Inc.
Admonishments
Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment. The admonishments — in the form o f Dangers, Warnings, and Caution s — must be followed at all times.
Danger: Danger is used to indicate the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the hazard is not avoided.
Warning: Warning is used to indicate the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the hazard is not avoided.
Caution: Caution is used to indicate the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided.
1 UNPACKING AND INSPECTION
Unpack and inspect the various components as follows:
1. Inspect the exterior of the shipping container(s) for evidence of rough handling that may ha
ve damaged the components in the container.
2. Unpack each container while carefully checking the conte
3. File a claim with the commercial carrier and notify BCG Technical Assistance Center, if damage is detected
4. Save all shipping containers for use if the equipment requires
Page 2
© 2016 CommScope. All Rights Reserved.
nts for damage.
or if parts are missing. Save damaged cartons for inspection by the carrier.
shipment at a future date.
2 RACK-MOUNT PANEL INSTALLATION
11247-C
DANGER
INVISIBLE LASER RADIATION
AVOID DIRECT EXPOSURE TO BEAM
CAT #
S/N
DATE
CODE
MADE IN USA
MOUNTING
BRACKET
POSITIONED
FOR 5-INCH
RECESS
MOVE MOUNTING
BRACKETS TO THIS
POSITION FOR FLUSH MOUNT
2.1 Installing a Rack-Mount Chassis
The FL1000 rack-mount panel can be installed on either a 19-inch (48.26 cm) or 23-inch (58.42 cm) rack. It is designed for mounting in an EIA style rack, but a WECO style rack can also be used. It can be mounted flush on the rack or with a 5-inch (12.7 cm) recess. The panel is shipped ready to be installed with a 5-inch recess on a 19-inch rack. For other mounting positions, the mounting brackets must be removed and remounted in a different orientation. Select from the procedures below based on your specific installation.
ADCP-90-545 • Issue 4 • July 2016
2.1.1 19-Inch Rack, 5-Inch
Recess (as Shipped)
See Figure 1. Use the following procedure.
1. Position the chassis on the rack.
2. Attach the mounting brackets to the rack
using the #12-24 screws supplied.
Figure 1. Installing a Chassis on a 19-Inch Rack
© 2016 CommScope. All Rights Reserved.
Page 3
ADCP-90-545 • Issue 4 • July 2016
11248-C
DANGER
INVISIBLE LASER RADIATION
AVOID DIRECT EXPOSURE TO BEAM
CAT #
S/N
DATE
CODE
MADE IN USA
MOUNTING
BRACKET
POSITIONED
FOR 5-INCH
RECESS
MOVE MOUNTING
BRACKETS TO THIS
POSITION FOR FLUSH MOUNT
2.1.2 19-Inch Rack, Flush; 23-Inch Rack, 5-Inch Recess; 23-Inch Rack, Flush
For these positions, the mounting brackets must be removed and remounted orientation. Use the following procedure.
1. Remove the mounting brackets.
2. Remount the mounting brackets
in the position shown: a. For 19-inch rack, flush mount, use Figure 1 forward position; b. For 23-inch rack, 5-inch
recess mount, use Figure 2 back position;
c. For 23-inch rack, flush mount, use Figure 2 forward position.
3. Attach the mounting brackets to the rack
using the #12-24 screws supplied.
in a different
Page 4
© 2016 CommScope. All Rights Reserved.
Figure 2. Installing a Chassis on a 23-Inch Rack
2.2 Installing 6pak Adapter Plates and Pigtails
The 6pak adapter plates may be any of several types including:
• Simplex or duplex with adapters only
• Blank plates for filling in unused slots
ADCP-90-545 • Issue 4 • July 2016
• Simplex or duplex with adapters and attached pi
gtails
To install adapter plates without pigtails, refer to the first procedure below. To install adapter plates with pigtails, refer to the second procedure. Adapter plat
es with pigtails are used in the
24-fiber termination/splicing panel only.
2.2.1 Adapter Plates Without Pigtails (Blank or 6Pak)
Use the following procedure to install blanks
or 6pak plates without pigtails:
1. Remove the front cover.
2. Align the adapter plate tabs with
3. Slide the 6pak or blank up into the slot until
the notches in the mounting slot as shown in Figure 3.
it snaps in place.
SLOT
SPLICE
DECK
END TAB
6 PAK PLATE
(LOADED)
Figure 3. Installing 6pak Plates
11418-B
Page 5
© 2016 CommScope. All Rights Reserved.
ADCP-90-545 • Issue 4 • July 2016
2.2.2 Adapter Plates With Pigtails
Use the following procedure to install 6pak plates wit
h pigtails in the 24-fiber termination/splicing
panel.
1. Remove the front cover and slide out the splice deck.
2. Thread the pigtails through the empty mounting slot and loop the pigtails around the radius limiters i
n the chassis as shown in Figure 4.
END TAB
SLOT
6 PAK PLATE
(LOADED)
11367-C
SPLICE
DECK
RADIUS LIMITER
(4 PLACES)
PIGTAILS
Figure 4. Installing 6pak Plates with Pigtails
3. Align the adapter plate tabs with the notches in the mounting slot as shown in Figure 4.
4. Slide the 6pak plate into the
5. Fan out the fibers and tie them
slot until it snaps in place.
to the radius limiter on the right rear side of the splice deck
as shown in Figure 5. To tie the fibers, use cord lacing.
6. Route the fibers to the splice tray. For an
illustration of correct routing, refer to
subsection 3.4, Splicing, below.
Page 6
© 2016 CommScope. All Rights Reserved.
TOP VIEW WITH SPLICE DRAWER CLOSED
TOP VIEW WITH SPLICE DRAWER OPEN
TIE DOWN
USING CORD
LACING
TIE DOWN
USING CORD
LACING
11434-B
PROPER BEND RADIUS
MUST BE MAINTAINED
ADCP-90-545 • Issue 4 • July 2016
Figure 5. Correct Pigtail Routing within 24-Fiber Termination/Splicing Module
© 2016 CommScope. All Rights Reserved.
Page 7
ADCP-90-545 • Issue 4 • July 2016
2.3 Installing Cables and Routing Fibers
The rack-mount panel can accommodate either IFC or OSP cable. The procedures used to install the cable differ slightly for the three chassis types (12-fiber termination panel, 24-fiber termination panel, and 24-fiber termination/splicing panel). Refer to the appropriate topic below for the type being installed.
2.3.1 12-Fiber Termination Rack Mount Panel
Figure 6 shows cable routing options and breakout dimensions for the 12-fiber termin ation rack-
mount panel. The cable can enter from above or below
Use the following procedure to install the cable.
the chassis and from the left or right side.
1. Route the cable to the chassis and break out the ca
ble corresponding to Figure 6.
2. Secure the cable as follows:
a. Fasten the tie-down bracket to the panel at t
he cable point of entry using the screws
provided.
b. Position the cable on the tie down bracket with the ca
ble sheath extending about 0.75 inch
(1.9 cm) beyond the bracket into the chassis. c. Tie down the cable using cord lacing. d. Secure the cable in a second location on the
rack or wall using a user-provided clamp
per local practice.
3. Remove the front access door and s
4. Route the buffers within the chassis from the cable point of entry to the opposite
lide out the bulkhead deck.
side of
the bulkhead deck, as shown in Figure 6.
5. Tie down the buffers in the location shown in Figure 6 using cord lacing secured to the lan ce.
6. At the buffer breakout point, fan out the fibers
from the buffers and secure them using a
curly lock at the location shown in Figure 6.
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the optical bulkhead of an operational transmitter, or into the launching (output) end of an active fiber. A clean, protective cap or hood MUST be immediately placed over any radiating bulkhead receptacle or optical fiber connector to avoid exposure to potentially dangerous amounts of radiation. This practice also helps prevent contamination of connectors and adapters.
7. Connect the fiber connectors to the adapters on the rear of the 6pak adapter plate.
8. Slide in the bulkhead deck
9. Replace the front access cover.
Page 8
© 2016 CommScope. All Rights Reserved.
to its closed position.
ADCP-90-545 • Issue 4 • July 2016
IFC OR OSP
CABLE
SHEATH
CABLE ENTRY
FROM LEFT
TIE OFF USING
TIE-DOWN BRACKET
SUPPLIED WITH PANEL
A
18.0 IN.
(47.72 CM)
SUB-UNITS
A
(220.98 CM)
B
C
87.0 IN.
(134.62 CM)
53.0 IN.
D
C
16.0 IN.
(40.64 CM)
FIBERS
B
TIE DOWN ON OPPOSITE
SIDE FROM ENTRY USING
CORD LACING SECURED
CONNECTORS
ON LANCE
ATTACH USING
CURLY LOCK
SUPPLIED WITH
PANEL
TIE DOWN ON OPPOSITE
SIDE FROM ENTRY USING
CORD LACING SECURED
ON LANCE
D
A
B
C
D
Figure 6. Cable Breakout for 12-Fiber Panel
CABLE ENTRY
FROM RIGHT
TIE OFF USING
TIE-DOWN BRACKET
SUPPLIED WITH PANEL
11246-D
© 2016 CommScope. All Rights Reserved.
Page 9
ADCP-90-545 • Issue 4 • July 2016
2.3.2 24-Fiber Termination Rack Mount Panel
Figure 7 shows cable routing options and breakout dimensions for the 24-fiber termin ation rack-
mount panel. The cable can enter from above or below
the chassis and from the left or right side.
IFC OR OSP
CABLE
SHEATH
CABLE ENTRY
FROM LEFT
TIE DOWN
USING CORD
LACING
A
57.0 IN.
(144.78 CM)
41.0 IN.
(104.14 CM)
SUB-UNITS
A
B
C
B
16.0 IN.
(40.64 CM)
FIBERS
C
CONNECTORS
Use the following procedure to install a cable in the 24-fiber termination rack-mount panel.
Page 10
© 2016 CommScope. All Rights Reserved.
C
Figure 7. Cable Breakout for 24-Fiber Panel
A
CABLE ENTRY
FROM RIGHT
B
TIE DOWN
USING CORD
LACING
11245-E
ADCP-90-545 • Issue 4 • July 2016
CLAMP
BRACKET
11363-B
CLAMP
YOKES (2)
RUBBER
GROMMET
USE EITHER COVER
OR PLATE IN THIS
POSITION
COVER
NUTS (2)
PLATE
1. Route the cable to the chassis and break out the cable corresponding to Figure 7.
2. Secure the cable as follows (see Figure 8): a. Install the clamp bracket at the chosen clamp lo
cation by inserting the two integral
bolts from inside the chassis.
b. Sort through the rubber grommets in the kit and find the
one that best fits the cable. If the cable is too small to fit snugly in the smallest grommet, build up the cable with tape of a suitable material per local standards.
c. Assemble the cable clamp components on the bracket studs in the order shown in the
figu
re and secure with the two nuts provided.
Figure 8. Installing a Cable Clamp on a Rack-Mount Panel (Select from Four Mounting Locations)
3. If the cable being installed is an OSP cable with a metallic strength member, bond the cable to ground following the instructions for the bonding/grounding kit.
4. Remove the rear door, if not already removed.
5. Route the fibers within the chas
position shown.
sis as shown in Figure 7 and tie down the fibers in the B
Page 11
© 2016 CommScope. All Rights Reserved.
Loading...
+ 23 hidden pages