Cleveland 2DLLE Operators Manual

Cleveland Range
UNITED STATES
CANADA
REPAIR MANUAL
MODEL NO.
2DE24/2DE/2DLE/2DLLE 2DG24/2DG/2DLG/2DLLG 2DS24/2DS 2DSC24/2DSC
Cleveland Range, Inc.
1333 East 179th St. Cleveland, Ohio 44110 Phone: (216) 481-4900FAX: (216) 481-3782
Garland Commercial Ranges • 1777 Kamato Rd. Mississauga, Ontario CN L4W 1X4 Phone: (416) 624-0260 • FAX: (416) 624-0623
FCS-07
Installation Instructions For Steam Generators, Steamers, Steamer/Kettles: Gas Electric Steam Coil
Installation Instructions For All Models
1) These instructions must be retained by the owner / user for future reference. For installation only in noncombustible locations. Gas units
are only to be installed in areas that have provisions for adequate air supply.
2) Position: For proper operation and drainage, steam generator must be level. It must be set near a floor drain. Attach 1 1/2" piping to all drain connections to carry exhaust steam away from the cabinet Ends of drain lines must vent to atmosphere to avoid back pressure. Allow a MINIMUM of 6" clearance to the rear and sides of the equipment. The surrounding area must be free and clear of combustibles.
3) Install in accordance with local codes and/or the National Electric Code ANSI/NFPA No. 70-1984. installation in Canada shall be in accordance with the Canadian Electric Code CSA Standard C22-1 A unit that is connected 10 electricity must be grounded. A wiring diagram is provided inside the relay box.
4) Connect supply lines for 140° 160° hot water, and cold water, to the unit. Water pressure must be maintained between 35 and 60 psi. Locations and pressure data are shown on the connection drawing. Long hot water lines should be at least 1/2" IPS. Rush water supply lines thoroughly before connecting. Use water which is low in total solids content and low in gas content to prevent internal scaling, pitting and corrosion of the steam generator and carry-over of minerals into the steam. Water which is fit to drink can still contain highly detrimental impurities. Refer to Water Quality Requirements page.
5) Turn on water supply to steam generator. Water valve is inside of base.
6) Connect fuel supply
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or ar., other appliance.
For Steam Coil Steam Generators —
— Connect steam supply: Location is shown on the connection drawing. Incoming steam pressur e must be regulated between 35 and
45psi (30 — 45 psi for pressure steamers). Install a strainer ahead of the regulating valve. Rush line thoroughly before connecting.
— Connect the outlet end of the steam coil to an inverted bucket trap. Pill trap with water before installing. — Connect electricity if unit is equipped with electrical controls. Permanent 115V connection is required. Junction box location is
shown on the connection drawing. Unit must be electrically grounded by the installer.
For Gas Fired Generators—
— Post, in a prominent location, instructions to be followed in the event the user smells gas. This information shall be
obtained by consulting the local gas supplier.
— Connect gas: Location and pressure data are shown on the connection drawing. Installation shall be in accord ance with local codes, or
in the absence of local codes, with the National Fuel Gas Code, ANSI 2223.1 —1984 Installation in Canada shall be in accordance with Installation Codes for Gas Burning Appliances and Equipment B1 49.1 and B149.2. Use a gas pipe joint compound, which is resistant to LP gas. Test all pipe joints for leaks with soap and water solution. Allow 12 inch clearance on right side of all Gas Fired Steam Generator models for servicing gas burners and for proper operation. This 12" clearance also provides adequate air openings into the combustion chamber. Never obstruct the flow of combustion and ventilation air. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of V1/2 psig (3-45 kPa). The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testin g of the gas supply piping system at test pressure equal to or less than % psig (3.45 kPa).
— Connect electricity if unit is equipped with electrical controls. Permanent 115V connection is required- Junction box location is
shown on the connection drawing. Unit must be electrically grounded by the installer.
----Lighting and Shutdown Instructions: Flip electrical switch on. Open water valve. Open gas valve. Slightly depress and turn control
knob to "off" for 5 minutes before lighting gas. Turn control knob to "pilot", depress it completely and light pilot burner. Continue to hold knob in for about 60 seconds, then release. Pilot burner is lighted through hole in panel at bottom of steam generator. Never leave panel oft. as this will damage controls. Turn control knob to "on". Depress electrical "reset" switch for main burner ignition. Burners will not light without water in the steam generator. For main burner off, with pilot on, turn control knob to "pilot". For main and pilot burner off., slightly depress and turn control knob to "off". Flip electrical switch off.
For Electrical Steam Generators —
— Connect electric power Location is shown on the connection drawing. Provide connection as required by your unit. Electric supply
must match power requirements specified on data plate attached to base. Wiring must be adequate to carry required current at rated voltage. A separate fused disconnect must be supplied and installed. Unit must be electrically grounded by the installer.
1066 LITHO IN U.S.A. Manufacturer reserves right of design improvement or modification, as warranted
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
data sheet— 260-LB-2 (R2)
7) Turn on electricity at control circuit switch on steamer console. A red light glows when electricity is on. If water level is correct, steam generator will operate by pressing the "reset" button. Heaters will not work without water in the steam generator. This manual reset button must be pressed to start up the generator initially, and to restart the steam generator after every shut oft. or power interruption. No attempt should be made to operate the equipment during a power failure.
8) Check to make sure that the water in the sight gauge glass automatically stays at about 2/3 full when the unit is started up.
9) When installation is complete and free of leaks, refer to Operating Procedures sheet
Instructions For Steam Generator Care
Protect your steam generator, prolong its life and preserve its performance by giving it the required daily attention, on a regular schedule. Follow servicing instructions for your steam generator which are printed on Data Sheet 260-LC in your Owner s Manual, and also on an adhesive label attached to the unit To obtain an additional data sheet or label carrying servicing instructions, write to the Cleveland Range Company.
WARNING
No work should be done on the steam generator while it is pressurized or hot. Service of the steam generator should only be performed by a trained and experienced service technician, thoroughly familiar with servicing steam generators. When maintenance or repairs are required, contact a local food service equipment service agency, or call the factory, or a factory representative, for the name and address of one in your area.
Rigid regulations govern the design and construction of a boiler- However, the responsibility for the safe and efficient operation of a
Steam Generator (Boiler) Safety
boiler shifts to the owner/ user after the boiler leaves the factory. A sound boiler, if improperly installed, or if improperly maintained, or if improperly repaired, will create a dangerous situation and may
cause iniury to personnel. M ost states, provinces and some cities have a boiler safety law. Many underwriters require that their clients' boilers comply with these boiler safety laws. These safety laws call for action by the boiler manufacturer and action by the boiler owner/user. As a manufacturer, The Cleveland Range Company delivers steam generators built to the ASME Boiler Code, Section IV. which have been inspected by a National Board Inspector. Also. each Cleveland Range Company boiler is built to comply with the boiler safety law of the state to which it is sent.
Safe and Efficient Boiler Operation Depends on Proper Installation
Install (the boiler in compliance with following regulations, where they apply:
— The National Fuel Gas Code. ANSI 2223-1-1984 — The local and municipal building code (plumbing and — Installation Codes for Gas Burning Appliances and electrical)
Equipment B149.1 and B149.2 — The state and city boiler laws
---The Cleveland Range Company Installation instructions. — The recommendations of the owner/user's under writers
— The National Electrical Code ANSI/NPPA No- 70-1984 The water for the boiler should be analyzed by a reputable boiler water specialist, to see if the quality will permit safe and efficient boiler operation. Water treatment is becoming increasingly necessary because the quality of water sources is deteriorating, although treatment will not be required in every ease. A boiler will not operate property for very long if the water causes boiler corrosion or
scale. Even water which is safe to drink may be detrimental to a boiler. Refer to Water Quality Requirements page for details.
Safety Requires Periodic Inspection and Maintenance
Any leaks around the boiler's hand hole plate must be quickly stopped. Small leaks, if unchecked, cause corrosion and pitting on the boiler face. around the hand hole gasket making it unsealable. Application of undue stress on the parts that are used to seal the boiler's hand hole opening, in an attempt to seal an unsealable opening, by sledging the handle of the wrench, by increasing the leverage of the wrench by a length of pipe, or by other means, is dangerous because it may result in the breakage of pans, or injury. No attempts should be made to tighten up the nut on the retaining stud beyond the recommended 15 foot pounds of torque. When a repair affecting the safety of the boiler is necessary, call a National Board inspector for consultation and advice as to the best method of making the repair, so that the completed work will get his approval. Repairs to the boiler must conform to the applicable provisions in the ASME Code or the National Board Rules for Repairs. A boiler will last many years before it has to be retired from service. Periodic inspection will reveal the approaching retirement time. It is better to schedule a convenient replacement time than to wart for the boiler to fail. When a boiler older than 10 years is replaced the entire steam generator base assembly should be replaced for a number of reasons:
— Replacement pans become increasingly difficult to obtain for older controls. — Dependable performance of the new controls can be assured for a longer time. — The new steam generator including controls will comply with the latest industry and safety standards.
1086 LITHO IN U.S.A. Manufacturer reserves right of design improvement or modification, as warranted.
CLEVELAND RANGE CO, 1333 EAST 179th ST., CLEVELAND OHIO 44110
MODEL D
CLEVELAND CONVECTION STEAMER OPERATING INSTRUCTIONS
NOTE: These instructions pertain to steamers equipped with self-contained steam generators (boilers). For steamers direct-connected to a remote (in-house) steam source, disregard those instructions which are directly and solely related to the self-contained steam generator. 1A. Open the cabinet base door and close the drain valve if it is open.
B. Make sure the hot and cold water supply valves are open. C. Make sure that the steam tubes in the cooking compartments are in place and not loose.
2. Flip the toggle switch on front of the cabinet console to "ON". The red console light should then glow and the boiler will automatically begin filling with water (if it is not already full).
3. After approximately five minutes (after water appears in the sight gauge), depress the "START" reset button on the console. This will energize the electric heater elements or ignite the gas burners. This cannot be accomplished until the boiler is full of water.
4. In approximately 15 minutes you will notice the console's steam pressure gauge register 10-12 pounds. You can now preheat the cooking compartments. Preheating need only be done once before the day's cooking.
5. Compartments should be preheated before use and should be kept hot between loads. If a kettle and steamer are to be used at the same time, always heat the kettle unit first. When kettle contents begin to simmer, preheat the steamer compartments. When pressure returns to 10 pounds, cooking may begin in the steamer.
6. To preheat, close the compartment door with the palm of your hand on the latch. Turn the outer dial of the timer to 5 minutes and press its inner button. It will be several minutes before the arrow on the inner dial starts to move clockwise, toward the arrow on the outer dial. When the preheating is completed, the steam will automatically shut off and a buzzer will sound.
7. To cook, place the pan of food into the cooking compartment and repeat the operating procedure previously described (step #6) but set the timer for the length of time required, up to 30 minutes. The door may be opened for food inspection anytime during the cooking cycle, BUT KEEP HANDS OUT OF THE COOKING COMPARTMENT TO PREVENT BURNS.
8. If a cooking cycle longer than 30 minutes is desired, do not use the timer. Just depress the red "Manual" operation button to start the flow of steam. Remember, you must press the manual button again to shut the steam off. In either mode of operation, the red indicating light will glow when the compartment is in operation. In the manual mode, the timer can be used, but steam will continue to flow after the buzzer sounds.
9. At the end of each day's operation, flip the console toggle switch to the "Blowdown" position, open the door in the cabinet base and open the boiler drain valve, (red handle). This "Blowdown" drains the boiler and helps to keep it clean. When the boiler is empty, flip the console toggle switch to the "OFF" position, and close the boiler drain valve.
10. It is recommended that the boiler be refilled with water after the "Blowdown" is performed. This can be accomplished by flipping the toggle switch to the "ON" position for a period of five minutes and then returning the switch to the "OFF" position.
TO PROLONG LIFE AND MINIMIZE SERVICE REQUIREMENTS
1. Blow down the steam generator daily.
2. A periodic boiler inspection must be performed by a qualified serviceman, to prolong its life and to minimize service calls.
3. At the end of each day's operation, wash the steam tubes, pan slides, drain screen covers, door gaskets, and compartment interiors with mild detergent and warm water. Thoroughly rinse with clean water. Rinse water should drain freely through the compartment drain openings. If it does not, the drain must be cleaned before using the steamer.
4. Once a week, flush each compartment drain with a food service equipment drain cleaner and a deliming solution.
5. Once every three months, shut off the water supply, (hot and cold), and clean the water line strainers.
6. Once a week, remove and clean the compartment steam tubes. Lubricate the steam tubes' rubber "0" rings with cooking oil prior
to reinserting them into the compartments' back wall openings.
7. Steam tubes, drain screens, and pan slides are stainless steel, and can be washed safely in a mechanical dishwasher.
8. Always leave compartment doors ajar when not in use.
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
LITHO IN U.S.A. 0982
The Cleveland Convection
or fresh
4
pack 5
B
roccoli, flowerettes, frozen
1-2
Carrots, sliced, fre
sh 7-8
2
Potatoes, whole,
8
oz., with skin. no foil
30-35
SEAFOOD MINUTES
3
Cod, filets, frozen
3
Crab legs, king, frozen
4
-6
Prepare meats over a catch pan as juices
can be used for gravy, beef stock and
soups. The size of portion, thickness of cut,
etc., should be considered when selecting
Beef, 1 1/2" cubes
4
-5 min/lb Beef. 1 1/2" cubes, frozen
6
min/lb Beef, ground chuck, fresh or frozen
4
min/lb Beef, pot roas
t choice
8-12
min/lb Beef, rump roast, choice, boned,
rolled, tied
10
-12 min/lb
Beef, patties, chopped sirloin.
8
oz. portions, rare
-
2 min, medium
-
4 min,
well done
6
min *Beef, corned, brisket
18
-20 min/lb
Chicken, 1 1/2 Ib. pieces, frozen
26
-30
Liver, fresh or frozen
2
-4
Place pasta into 2 1/2" deep perforated pan
and nest into a solid
2 1/2"
deep pan. Cover
pasta with cold water, stir at least once
during steaming.
Macaroni, shells or elbow
12
Noodles,
1/2"
wide
10
Spa
ghetti, vermicelli
8
Cabbage rolls, stuffed, frozen, full
size pan. steam, then cover
with hot
tomato sauce and serve
20
Casserole dishes such as beef stew
etc.. Full size pan. Frozen
25-30 Lasagna, pre
-
cooked, refrigerated.
Hardcooked in shell for egg salad or
potato salad
10 Soft cooked, in shell
3
Soft yolk, for caesar salad
5
Steamer
TIMER SETTINGS
Timer settings are approximate due to the differences in food quality, age, shape and the degree of 'doneness" desired. It is not
necessary to add water. Perforated pans are recommended. Starred items (*) must be cooked in solid pans.
VEGETABLES MINUTES Asparagus, spears, frozen jumbo 6 Beans, green. 2" long, frozen-loose pack
Beans, green, french cut, frozen-solid Broccoli, spears, frozen 2-3
Broccoli, spears, fresh trimmed 3 Broccoli, flowerettes. fresh 2-3
Cabbage, fresh, slices or wedges 2-4 Cabbage, fresh, 4-6 Ib. head for cabbage
rolls, steam, peel, repeat as necessary 2-4 Carrots, baby whole, fresh or frozen 10
Carrots, sliced or krinkle cut. frozen 3 Carrots, diced, frozen 2 Cauliflower, floweretts, fresh 4-5 Cauliflower, flowerettes. frozen 2-3
Celery, 1-1 1/2" diagonal cut Celery, diced, for stuffing 2 Celery, minced Corn, yellow wh. kernel, frozen-loose pack 1 Corn on the cob, yellow, fresh 6 Corn on the cob, white, fresh 4
Corn on the cob, frozen 8-10 Eggplant. whole, fresh, to blanch 1
Mixed vegetables, frozen 2-3 Mushrooms, whole, fresh, 1/2" diameter 3 Onions, diced or sliced 2-3 Peas, green, frozen 2
Potato, sweet, whole 8 oz., with skin. no foil 30-35 Spinach, leaf. fresh or thawed 1 1/2 Spinach, frozen 3 Ib. block 15-17
Squash acorn, cut into halves, no seeds 15 Squash, cooked, frozen 4 Ib. block 18-20 Zucchini, diced, fresh or frozen 2-4
FRUIT
Apples, cored, blanch for peeling 1 Apricots, dried 10 Grapefruit. blanch for peeling 1
Oranges, blanch for peeling 1 Peaches, blanch for peeling 1
Pineapple, whole, for cutting 1-2 Prunes, dried 10
DEHYDRATED FOODS
*Potatoes, random sliced, use 5 cups cold water per Ib. 12
*Rice, long grain, use 4 cups cold water per Ib. 17
3
1/
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
Halibut, 6-8 oz. port ions, frozen 4-5 Lobster tails, 6-8 oz. portions, thawed 4-6 Red snapper, 8 oz. portions, frozen 4-5 Salmon steaks, 8 oz. portions, frozen 7 Shrimp, large, 10 count per Ib., frozen 4-6
MEATS
a timer setting.
6-8 Ib. cut with 1/2" water Chicken. 8 oz. pieces, frozen 18-20
Meat loaf, fresh or frozen 5 min/lb Weiners, frozen or thawed 2
PASTA
Lasagna noodles 12
Spaghetti, regular 10
PREPARED ENTREES
full size pan, 4" sq. servings 25-30
EGGS
CONVECTION STEAMER MECHANICAL COMPONENTS
REFERENCE NUMBER
PART NUMBER
DESCRIPTION
1 42063
Inner Door Assembly
2 44098
Gasket Retainer Plate
3
66556
Inner Gasket Retainer Plate
4
07138
Gasket
5
04171
Inner Door
6
14667
1/4-20 Knurled Finger Nut
(4
required)
7
19923
Inner Door Mounting Stud
(2
required)
8
40818
* Outer Door Assembly
9
52488
Outer Door Mounting Bracket
10
69635
Door Spring
11 44057
Outer Door Weldment
12
40746
Door Latch
13
58177
Door Handle
14
19577
Upper Door Spring
15
19578
Lower Door Spring
16
40817
Latch Pin
&
Retainer
(2
required)
17
02414
Hinge Bracket (upper or lower)
18
40816
Hinge Pin
&
Retainer
(2
required)
19
53061
Door Catch
20
40299
Steam Tube Assembly
21
15201
Tube
"0"
Ring 22 19574
Tube Spring
23
41423
Slide Rack
24
40417
Drain Cover Screen
Model "D" with Blue Control Panel and 30-Minute Timer
Date of Manufacture: July 1976 through December 1985
*Also available as part number 44056—
Replacement Outer Door Assembly with Latch and Handle, less Door Spring and Mounting Bracket. (Door latch # 08116 is no longer available. If this door latch breaks, the entire outer door must be replaced with #44055, using the door spring and mounting bracket from the original door. In addition, the door catch must be replaced with the replacement catch #53061, using the screws, nuts, and lockwashers from the original door catch.)
LITHO IN U.S.A.
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted. 1286
1283 LITHO IN U.S.A Manufacturer reserves right of design improvement or modification, as warranted
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
CONVECTION STEAMER ELECTRICAL COMPONENTS
Model "D" with Blue Control Panel and 30-Minute Timer Date of
Manufacture: July 1976 thru December 1985
REFERENCE NUMBER PART NUMBER DESCRIPTION 1 41350 Buzzer 2 14860 Terminal Block Label 3 02195 Terminal Block 4 43904 Timer
19996 Micro-Switch (2 required) 5 20477 Timer, Solid State 6 19972 Thermal Switch 7 100635 Instrument Panel 8 19978 Illuminated Push Button Switch (Timer By -Pass) 9 12159 Neon Indicator Light 10 19285 Instrument Panel Screw
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
LITHO IN U.S.A.
CONVECTION STEAMER PIPING COMPONENTS
1 63172
Drain Pipe, Upper Compartment Only
Model "D" with Blue Control Panel and 30-Minute Timer Date of Manufacture: January 1975 thru December 1985
Data Sheet 261-DU (R3)
REFERENCE NUMBER DESCRIPTION
2 63171 Drain Pipe, Lower Compartment Only 3 22202* Safety Relief Valve — NO LONGER REQUIRED - NOT AVAILABLE 4 20559 Thermostatic Trap — Compact 5 22201 3/8" Solenoid Valve — Steam 6 06216 1/4" Tube x 1/4" Pipe Connector 7 02549 Condenser Bushing 8 14498 Nozzle — Steam Condenser (K-5) 9 22215 1/4" Solenoid Valve — Water 10 22131 3/4" Safety Valve — 15 psi 11 22140 Air Vent — NOT REQUIRED ON DIRECT CONNECT UNITS 12 63170 Steam Manifold 13 15455 Row Controller (regulator), 0.5 gpm 14 22099** Needle Valve 15 63162 Drain Manifold 16 03058 1-1/2" Cap
*Used until November 1982, then deleted from the steamer. **Optional
after November 4, 1982.
CLEVELAND RANGE CO., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
1086 LITHO IN U.S.A.
CONVECTION STEAMER PARTS ELECTRICAL
1 47007
Divider Panel Electrical Assembly
2
03511
Relay, By
-
Pass 3 41350
Buzzer
4
03510
Rel
ay, Safety Circuit
5
02195
Terminal Block
- 7
Pole
(2
required)
6
14860
Terminal Block Label
7
47006
Instrument Panel Assembly (Not Available)
8
42236
Instrument Panel Sub
-
Assembly (Not Available)
9
14858
Instrument Panel Label (Not Available)
10
19975
Switch Illuminated Push Button (Red,
3
Terminal)
11
19974
Switch Illuminated Push Button (Amber,
3
Terminal)
12
19973
Switch Illuminated Push Button (White,
4
Terminal)
13
43904
Timer Assembly
14
02482
Bulb, 3W
-
120V 15 41351
Bulb Socket
16
19285
Instrument Panel Screw
17
19971
Pressure Switch
18
19972
Thermal Switch
REFERENCE
PART
DESCRIPTION
STYLE A DATE OF MANUFACTURE: JANUARY 1975 TO JUNE 1975
Data Sheet 261-DT
NUMBER
NUMBER
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Manufacturer reserves right of design improvement or modification, as warranted.
LITHO IN U.S.A.
CONVECTION STEAMER PARTS ELECTRICAL
2 03511
Relay, By
-
Pass 3 41350
Buzzer
5 14860
Terminal Block Label
6
47006
Instrument Panel Assembly (Not Available)
7
42236
Instrument Panel Sub
-
Assembly (Not Available)
8
14858
Instrument Panel Label (Not Available)
9
19974
Switch Illuminated Push Button (Amber,
3
Terminal)
10
19973
Switch Illuminated Push Button (White,
4
Terminal)
11
43904
Timer Assembly
12
02482
Bulb, 3W
-
120V 13 41351
Bulb Socket
14
19285
Instrument Panel Screw
15
19972
Thermal Switch
REFERENCE
PART
DESCRIPTION
STYLE B DATE OF MANUFACTURE: JULY 1975 TO JUNE 1976
NUMBER
1 47007 Divider Panel Electrical Assembly
4 02195 Terminal Block - 7 Pole (2 required)
Manufacturer reserves right of design improvement or modification, as warranted. LITHO IN U.S.A.
NUMBER
CLEVELAND RANGE, INC., 1333 EAST 179th ST., CLEVELAND, OHIO 44110
Loading...
+ 25 hidden pages