CLA-VAL PC-22D Installation, Operation & Maintenance Manual

Page 1
PC-22D
Electronic Pump Controller
Installation
Maintenance
Manual
Operation
Page 2
All measures have been taken to ensure accuracy and completeness of this document. However, as errors can never be fully excluded, we always appreciate any information or suggestions for improving the document.
E-Mail: info@cla-val.com
We wish to point out that the software and hardware terms as well as the trademarks of companies used and/or mentioned in the present manual are generally protected by trademark or patent.
Page 3
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 1
LIMITED WARRANTY
Automatic valves and controls as manufactured by Cla-Val are warranted for one (1) year from the date of shipment against manufacturing defects in materials and workmanship which develop in the service for which they are designed, provided the products are installed and used in accordance with all applicable instructions and limitations as issued by Cla-Val.
We will repair or replace defective material, free of charge, which is returned to our factory, transportation charges prepaid, provided that, after inspection, the material is found to have been defective at time of shipment. This warranty is expressly conditioned on the purchaser’s giving Cla-Val immediate written notice upon discovery the defect. Components used by Cla-Val but manufactured by others are warranted only to the extent of that manufacturer’s guarantee.
This warranty shall not apply if the product has been altered or repaired by others, and Cla-Val shall make no allowance or credit for such repairs or alterations unless authorized in writing Cla-Val.
TERMS OF SALE
Acceptance of orders
All orders are subject to acceptance by our main office at Newport Beach, California.
Credit Terms
Credit Terms are net thirty (30) days from date of invoice.
Purchase Order Forms
Orders submitted on customer’s own purchase order forms will be accepted only with the express understanding the no statements, clauses, or conditions contained in said order form will be binding on the Seller if they in any way modify the Seller’s own terms and conditions of sales.
Product Changes
The right is reserved to make changes in pattern, design, or materials when deemed necessary, without prior notice.
Prices
All prices are F.O.B. Newport Beach, California, unless expressly stated otherwise on our acknowledgment of the order. Prices are subject to change without notice. The prices at which any order is accepted are subject to adjustment to the Seller’s price in effect at the time of shipment. Prices do not include sales, excise, municipal, state or any other Government taxes. Minimum order charge $75.00.
DISCLAIMER OF WARRANTIES AND LIMITATIONS OF LIABILITY
The foregoing warranty is exclusive and in lieu of all other warranties and representations, whether expressed, implied, oral or written, including but not limited to any implied warranties of merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled.
Cla-Val shall not be liable for any incidental or consequential loss, damage or expense arising directly or indirectly from the use of the product. Cla-Val shall not be liable for any damages or charges for labor or expense in making repairs or adjustments to the product. Cla-Val shall not be liable for any damages or charges sustained in the adaptation or use of its engineering data and services. No representative of Cla-Val may change any of the foregoing or assume any additional liability or responsibility in connection with the product. The liability of Cla-Val is limited to material replacements F.O.B. Newport Beach, California.
Responsibly
We will not be responsible for delays resulting from strikes, accidents, negligence of carriers, or other causes beyond our control. Also, we will not be liable for any unauthorized product alterations or changes accruing therefrom.
Risk
All goods are shipped at the risk of the purchaser, after they have been delivered by use to the carrier. Claims for error, shortages, etc., must be me upon receipt of goods.
Export Shipments
Export shipments are subject to an additional charge for export packing.
Returned Goods
1. Customers must obtain written approval from Cla-Val prior to returning any material.
2. Cla-Val reserves the right to refuse the return of any products.
3. Products more than six (6) months old cannot be returned for credit.
4. Specially produced, nonstandard models cannot be returned for credit.
5. Rubber goods such as diaphragms, discs, O-rings, etc., cannot be returned for credit, unless as part of an unopened vacuum sealed repair kit which is less than six months old.
6. Goods authorized for return are subject to a 35% ($75 minimum) restocking charge and a service charge for inspection, reconditioning, replacement of rubber parts, retesting, repainted and repackaging as required.
Page 4
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 2
Table of Contents
1 Notes about this Documentation……………………………………………….
3
1.1 Validity of this Document………………….………………………………...….
3
1.2 Copyright………………...……………….……..………………………………..
3
1.3 Symbols………………….……………......………….…………...……………..
3
2 Important Notes………………………………………..……….………………….
4
2.1 Legal Bases……………..……………………………….…………………...….
4
2.1.1 Subject to Changes………………...………………………….….………..
4
2.1.2 Personnel Qualifications………………………......……..….……………..
4
2.2 Safety Advice……………..……………………………………………..…...….
4
3 Product Description……………..………………………………………….…….
6
3.1 Specifications……………..……………………………………………….....….
6
4 Installation……………..……………….……………………………………….….
9
4.1 Unpacking……………..……..…………………………………………….....….
9
4.2 Mounting the Enclosure....……………………………………………….....….
9
4.3 Component Layout…...…..……………………………………………….....….
11
4.4 Wiring Connections……....……………………………………………….....….
12
4.5 Grounding & Shielding…...……………………………………………….....….
14
4.6 Cabinet Wiring………..…………………………..……………………….....….
16
5 Software Setup and Operation…..….……………………………………….….
18
5.1 System Timers…………..……..………………………………………….....….
19
5.2 Normal Pump Start....…………………………………………………….....….
20
5.3 Pump Malfunction…...…..………….…………………………………….....….
20
5.4 Valve Malfunction…...…..…………..…………………………………….....….
21
5.5 Normal Stopping of Pump.……………………………………………….....….
21
5.6 Power Failure…...…..……………….…………………………………….....….
21
5.7 Alarms…...…..……………………………………………………………......….
22
6 Modbus Communication……...…..….……………………………………….….
23
7 Pump Control Applications…..…..….……………………………………….….
26
8 Troubleshooting………………..…..….……………………………………….….
28
Page 5
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 3
1 Notes about this Documentation
! !
Keep this documentation!
The operating instructions are part of the product and shall be kept for the entire lifetime of the device. They shall be transferred to each subsequent owner or user of the device. Care must also be taken to ensure that any supplement to these instructions are included, if applicable.
1.1 Validity of this Document
This documentation is only applicable to the device: “Cla-Val PC-22D Electronic Pump Control Panel”.
The Cla-Val PC-22D shall only be installed and operated according to the instructions in this manual and the system description.
1.2 Copyright
This Manual, including all figures and illustrations, is copyright-protected. Any further use of this Manual by third parties that violate pertinent copyright provisions is prohibited. Reproduction, translation, electronic and photo technical filing/archiving (e.g., photocopying) as well as any amendments require the written consent of Cla-Val. Non-observance will involve the right to assert damage claims.
1.3 Symbols
Personal Injury!
Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury.
Personal Injury Caused by Electric Current!
Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury.
Personal Injury!
Indicates a moderate-risk, potentially hazardous situation which, if not avoided, could result in death or serious injury.
Note
!
DANGER
DANGER
WARNING
Page 6
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 4
2 Important Notes
This section includes an overall summary of the most important safety requirements and notes that are mentioned in each individual section. To protect your health and prevent damage to devices as well, it is imperative to read and carefully follow the safety guidelines.
2.1 Legal Bases
2.1.1 Subject to Changes
Cla-Val reserves the right to provide for any alterations or modifications that serve to increase the efficiency of technical progress. Cla-Val owns all rights arising from the granting of patents or from the legal protection of utility patents. Third-party products are always mentioned without any reference to patent rights. Thus, the existence of such rights cannot be excluded.
2.1.2 Personnel Qualifications
All sequences implemented on the Cla-Val PC-22D Valve Controller may only be carried out by electrical specialist with sufficient knowledge in automation. The specialists must be familiar with the current norms and guidelines for the devices and automated environments.
All changes to the controller should always be carried out by qualified personnel with sufficient skills in PLC programming.
2.2 Safety Advice (Precautions)
For installing and operating purposes of the relevant device to your system the following safety precautions shall be observed:
Do not work on components while energized!
All power sources to the device shall be switched off prior to performing any installation, repair or maintenance work.
Installation only in appropriate housings, cabinets or in electrical operation rooms!
The Cla-Val VC-22D Valve Controller are an open system. As such, install the system and its components exclusively in appropriate housings, cabinets or in electrical operation rooms. Allow access to such equipment and fixtures to authorized, qualified staff only by means of specific keys or tools.
DANGER
!
DANGER
Page 7
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 5
Replace defective or damaged devices!
Replace defective or damaged controllers, since the long-term functionality of the device can no longer be ensured.
Protect the components against materials having seeping and insulating properties!
The components are not resistant to materials having seeping and insulating properties such as: aerosols, silicones and triglycerides (found in some hand creams). If you cannot exclude that such materials will appear in the component environment, then install the components in an enclosure being resistant to the above-mentioned materials. Clean tools and materials are imperative for handling the controller.
Cleaning only with permitted materials!
Clean the Cla-Val VC22-D using oil-free compressed air or with ethyl alcohol and leather cloths. Do not use any contact spray.
Do not reverse the polarity of connection lines!
Avoid reverse polarity of data and power supply lines, as this may damage the devices involved.
Avoid electrostatic discharge!
The controller is equipped with electronic components that may get destroy by electrostatic discharge when you touch. Pay attention while handling the devices to good grounding of the environment (person, job and packing).
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
Page 8
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 6
3 Product Description
The Electronic Pump Control Panel shall provide control between the pump control valve and the pump, to prevent surges in the system when the pump starts or stops. The control panel shall properly sequence and control the pump start-up and pump shut-down procedure, providing both visual and electronic status outputs for operating personnel. Panel shall protect the pumping system from damage due to mechanical, hydraulic or power failure. Panel shall be pre-wired and include an integral programmable valve controller to sequence the pump and pump control valve during all modes of operation. Controller shall be pre-programmed for most common pump control applications. Controller shall be easy to wire and adjust. Controller to include the following features:
Sequence timers
Local visual indication of pump and control valve status.
Displays time for system to build pressure and for valve to open
Contacts for remote or automatic start signal
Local pump start & pump stop buttons
Local emergency stop button
Automatic shutdown of pump in emergency situations
Terminal block connections for solenoid controls, valve limit switch, pump starter relay, remote
automatic contact, pressure switch
HOA switch for remote or local operation
Custom application programming is available upon request. The control panel shall include automatic recognition of common fault conditions and shall provide proper fault response sequencing to the pump control valve and pump starter as well as visual and electronic fault notification to operating personnel.
The integral programmable valve controller shall be housed in a NEMA 4X fiberglass enclosure with polycarbonate window, gasketed door, continuous stainless steel hinge, stainless steel twist/latch door fasteners, and pad lockable door hasp.
ORDERING INFORMATION
Cla-Val Part
Number
Description
20977406F
PC-22D Electronic Pump Control Panel
Figure 1. PC-22D Electronic Pump Control Panel
Page 9
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 7
3.1 Specifications
Material Specification for the Electronic Pump Control Panel as follows:
Panel Enclosure Material Flame retardant UL rated PC/ABS plastic Enclosure Panel Dimensions 20.0” (508 mm) H x 18.0” (457 mm) W x 9.0” (228 mm) D
The enclosure panel shall be provided with all necessary mounting brackets.
Panel Integral Controller
Display Type 4.3” Color TFT-LCD, 480 x 272 pixels Display Update Rate 100ms Programming Method Mechanical Push Button VNC Password 5 digit
Enclosure Environmental NEMA 4X
Controller Mass Data Storage Type 4GB SD Card Language English Temperature Range 14°F to 158°F (-10°C to 70° C) Humidity 90% RH, non-condensing Memory Protection 10 year life lithium battery
Power Requirement Power 120VAC @ 60Hz protected with 5 Amp Fuse & Circuit Breaker Motor Starter Contacts: 10 amp maximum Valve Solenoid Contacts: 10 amp maximum Remote Alarm: 1 amp maximum
Controller Inputs Analog 4-20mA; (6) Inputs Available (0-5 V / 0-10 V) Resolution 10 bit Digital (6) digital inputs (Dry contact) Units Configurable Decimal Point 0 / 0.0 / 0.00 / 0.000 Signal Filter Configurable 1 to 60 seconds Totalizer Configurable Input and Units Totalizer Reset Yes I/O Connection Screw Terminals
Controller Outputs Pump Relay 10 Amp Max Control Valve Relays 120VAC @ 60Hz Output (double chamber valves)
24VDC Solid State Relay Output (single chamber valves) Alarm Relay (2) Available and Configurable Analog 4-20mA; (4) Outputs available Resolution 10 bit Solenoid (2) Solid State Relay, Zero Switching Voltage Relay (2) Mechanical Relay, Rated Voltage 250VAC,
Rated Current 6A
Page 10
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 8
Controller Input Logging Configurable Yes Logging Speed 1 minute Event Memory 128 Mbytes rolling memory up to 80,000,000 values capacity Output CSV format suitable for exporting to MS Excel
Controller Parameters Control Input 4-20mA full scale / 0-5 V / 0-10V / digital (dry contact) Proportional Band 0-100% (50% default) adjustable in 1% increments
Independently for opening and closing Dead band Adjustable 0 to full scale of set-point signal Cycle Time 0 to 60 seconds in 1 sec. increments Integral Band Adjustable 0 to 60 seconds Derivative Band Adjustable 0 to 60 seconds Loop Zoning Adjustable up to (4) zones PID Loops 4 Configurable Control Curves 4 Retransmission 4 Analog (4-20mA signal) Actions (Alarms) Triggering conditions
Controller Communication Local Mechanical Push Button Remote VNC Server Interfaces GPRS Modem Quad Band / Ethernet / RJ-45 / RS-232 / RS-485 Protocols Modbus TCP / ModbusRTU / VNC
Conntroller Approvals Conformity Marking CE marking
Controller Optional Features /Accessories Fan / Heater with integral thermostat
Page 11
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 9
4 Installation
For Installation in USA: The Cla-Val VC-22D must be installed in accordance with the National Electrical Code (NEC) NFPA 70.
For Installation in Canada: The Cla-Val VC-22D must be installed in accordance with the Canadian Electrical Code CSA 22.1. All input circuits must be derived from a CSA approved Class 2 source.
For European Community: The Cla-Val VC-22D must be installed in accordance with the ATEX directive 94/9/EC.
4.1 Unpacking
Remove enclosure from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier.
If any part is missing or the control malfunctions, please contact your supplier or the factory for assistance.
4.2 Mounting the Enclosure
The PC-22D Electronic Pump Control Panel is NEMA 4X rated. Molded fiberglass polyester with enhanced UV inhibitors protect against outdoor weathering. Stainless steel mounting brackets and hardware are provided for mounting to the rear of the enclosure.
1. PC-22D Enclosure Physical Dimensions:
Figure 2. PC-22D Enclosure Footprint Dimensions.
Page 12
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 10
2. PC-22D Enclosure Mounting Dimensions:
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Figure 3. PC-22D Enclosure Mounting Dimensions.
Page 13
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 11
!
!
!
!
4.3 Component Layout
List of Components:
1. NEMA 4X Enclosure
2. Cla-Val VC-22D Controller
3. Power Supply 24VDC @ 40Watts
4. 5A Circuit Breaker
5. 5A Fuse Protection
6. (2) Mechanical Relays
7. Din Rail
8. Wiring Ducting
9. 3-Position Switch
10. Start Pump Switch – Green
11. Stop Pump Switch – Red
12. Emergency Stop Button
Figure 4. PC-22D Component Layout.
Page 14
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 12
4.4 Wiring Connections
Customer connections shall be made to the provided numbered terminal blocks located near the bottom portion of the enclosure.
Stripped solid conductors, stranded conductors, or ultrasonically “bonded” conductors are easily connected using a screwdriver.
Maximum Conductor Size: 12 AWG
1. System Supply
The PC-22D requires 110VAC @ 60Hz alternating current supplied to the enclosure. The product is powered via terminal block 4 & 5 with CAGE CLAMP connections. The provided power supply generates the necessary voltage to power the integral controller and valve solenoid/s.
Do not use an incorrect voltage/frequency!
The use of an incorrect supply voltage or frequency can cause severe damage to the product.!
NOTICE
Wire Removal
The conductor is removed using a screwdriver.
Figure 5. Terminal Block installation & removal.
110V
AC
The$110V$AC$supplies$p o wer$to$ system$controller$and$valve$ solenoid.$
Figure 6. Supply Voltage Connections.
Page 15
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 13
2. Pump Start & Valve Solenoid Connections
The pump start signal shall be terminated on terminal block 10 & 11. This contact is pre-wired as a dry­contact output. If the contact requires power, the maximum current is 10 amps.
The control valve solenoid shall be terminated on terminal block 12 & 13. This contact is pre-wired with an output of 110VAC. Typically when wiring AC solenoids, polarity is irrelevant.
Terminals 6, 7, 8, & 9 are reserved for optional alarms. See the Software Programming section of this manual for further explanation.
3. Remote Pump Start, Valve Pressure & Limit Switch Connections
Terminal block 14, 15, & 16 are reserved for a valve position transmitter or another type of 4-20mA device. If using a standard pump control valves, these terminals will not be used.
The remote start signal from SCADA shall be terminated on terminal block 17 & 18. This contact is pre­wired as a dry-contact input. When the contact is closed and the 3-position switch is set to remote, the controller will interpret this as a pump run command.
The valve limit switch shall be terminated on terminal block 19 & 20. This contact is pre-wired as a dry­contact input. When the contact is open, the controller will interpret as “valve open”. When the contact is closed, the controller will interpret as “valve closed”.
110V
AC
Figure 7. Pump Start & Solenoid Terminals
!Alarms!
Activate in software menus!
Figure 8. Valve Limit Switch Connections.
Page 16
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 14
The pressure switch signal shall be terminated on terminal block 21 & 22. This contact is pre-wired as a dry-contact input. When the contact is open, the controller will interpret as “minimum pressure not met”. When the contact is closed, the controller will interpret as “minimum pressure met”.
If a pressure switch is not used!
If a pressure switch is not used, a jumper must be inserted across terminal block 21 & 22.
4.5 Grounding & Shielding Function
Grounding increases the resistance against disturbances from electromagnetic interferences. From the field side, the ground wire shall be connected to any ground potential (green terminal block). The terminal block is internally connect to the carrier rail.
NOTICE
Figure 9. Remote Start, Valve Limit Switch, & Pressure Switch Connections.
Figure 10. Grounding Connection Terminal Block.
Page 17
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 15
The use of shielded cables reduces electromagnetic interference and thus increases signal quality. Measurement errors, data transmission errors and interference due to excessive voltage can be prevented.
Shielded signal lines only required for analog signals connected to the Cla-Val Controller.
Connect the cable shield to the ground potential!
Integrated shielding is mandatory to meet the technical specifications in regards to measuring accuracy. Connect the cable shield to the ground potential (green terminal block). This allows induced interference to dissipate and to be kept away from devices in the cabinet.
Improve shielding performance by placing the shield over a large area!
Higher shielding performance is achieved via low-impedance connection between shield and ground. For this purpose, connect the shield over a large surface area.
Keep data and signal lines away from sources of interference!
Route data and signal lines separately from all high voltage cables and other sources of high electromagnetic emission (e.g. power supplies).
NOTE
NOTE
NOTE
Page 18
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 16
4.6 Cabinet Wiring
Provided wiring diagrams are intended to be used as reference only.
Figure 11. Panel Wiring Diagram.
Page 19
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 17
Figure 12. Panel Wiring Diagram.
Page 20
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 18
5 Software Setup and Operation
The PC-22D Electronic Pump Control Panel powers on after switching the circuit breaker to the on position. An indicator light illuminates on the power supply indicating power to controller and accessory components. It takes approximately 40 seconds for the controller to complete its boot up procedure.
Once the controller has completed the boot up process, the home screen will appear with system indicators and status.
1. Visual Indicators:
Indicator
Color Red
Color Green
Pump Status
Pump OFF
Pump ON
Pressure Switch
Pressure minimum not met
Pressure above minimum
Valve Open
Valve Closed
Valve Open
2. Status Indicators:
Time – Pressure = Time it takes for the pressure switch contact to close once the pump has been started. This timer is displayed in seconds.
Time – Valve = Time it takes for valve to open once valve solenoid has been energized. This timer is displayed in seconds.
Valve Solenoid = Displays whether the valve solenoid is energized or not.
Figure 13. PC-22D Controller Home Screen.
Page 21
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 19
5.1 System Timers
The PC-22D Electronic Pump Control Panel is equipped with (2) timers; the time allowed for pressure to build once the pump has been turned on and the time allowed for the valve to open. Both timers have a default value of 30 seconds.
The system timers are access using the 5 button keypad on the controller.
From the home screen, click the down arrow to access the timer menu.
To toggle between timers, use the buttons on the keypad.
Timers are selected using the button. The text box will highlight red and the value can be changed.
Figure 14. PC-22D Controller Timer Menu.
Page 22
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 20
5.2 Normal Pump Start (Local or Remote)
A local pump start command shall be initiated by turning the 3-position selector switch to the “local” position and pressing the pump start green button. A remote pump start command shall be initiated by turning the 3-position selector switch to the “remote” position and sending a remote start command to the enclosure.
The pump shall immediately turn on and shall be seen by the indicator on the pump controller home screen. The valve solenoid will not energize until the pressure switch contact has been made, notifying the controller system pressure has been met. Once the opening sequence is complete and the system is in normal operation, all system indicators can be seen in green.
5.3 Pump Malfunction
Anytime during the pumping operating when the pump discharge pressure is not capable of satisfying the pressure switch setting, the visual indicator will turn red. This indicates a loss of pressure, the control valve will close and the pump start contacts will open, turning the pump off. A “System Fault” indicator will display on the screen. A manual reset of the emergency stop switch is required to clear the fault and restart the pump.
Figure 15. PC-22D Controller Home Screen, Normal Operation.
Figure 16. PC-22D Controller Home Screen, Fault Indicator.
Page 23
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 21
To Reset a System Fault!
A system fault must be cleared using the emergency stop button. If the fault is not cleared, the pump will not be able to start.
5.4 Valve Malfunction
If the solenoids of the pump control valve fail, or if any other event should cause the valve to close without a normal pump shutdown command, the pump start contacts will open, turning off the pump. A “System Fault” indicator will display on the screen. A manual reset of the emergency stop switch is required to clear the fault and restart the pump.
5.5 Normal Stopping of Pump (Local and Remote)
A local pump stop command shall be initiated by pressing the stop pump button or by opening the remote start contact. By initiating this command the pump control valve solenoid will de-energize and the valve will start to close. Once the control valve is fully closed, the pump start contacts will open, shutting down the pump.
5.6 Power Failure
In the event of a power failure, even momentary, it will take approximately one minute for the controller to boot up. During the boot up process, it shall not be possible to have an automatic pump restart. After the boot up process has been completed, a normal pump start sequence shall be initiated by using a local or remote pump start command.
Valve Must be closed to prior to Pump Start!
A local or remote pump start will not be initiated unless the control valve is closed.
NOTE
WARNING
Page 24
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 22
5.7 Alarms
Various alarms can be programmed sending indication to SCADA there is a system failure. The alarms/actions menu is accessed by using the 5 button keypad.
From the home screen, hold down the up arrow for more than 2 seconds to access the alarms menu.
Select the “Actions” icon by using the button.
Various conditions can be programmed and sent to SCADA. To send a “fault” condition, program an alarm as in figure 18. If the fault alarm is off, the variable fault equals 0, if a fault existed the fault variable will equal 1. Outputs can be sent to SO1 (terminals 6 & 7) or SO2 (terminals 8 & 9).
Figure 17. PC-22D Controller, Alarms/Actions.
Figure 18. PC-22D Controller, fault alarm programming.
Page 25
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 23
6 Modbus Communication
The PC-22D Electronic Pump Control Panel comes standard with Modbus protocol. This protocol defines a message structure that PLC’s will recognize and use, regardless of the type of networks over which they communicate. The pump controller can be configured to communicate on standard Modbus networks using either of two transmission modes: TCP/IP or RTU. Users shall have the ability to select the desired mode, along with communication parameters (IP address, subnet mask, baud rate, etc). The electronic valve controller shall have a built in VNC server. A viewer/client uses TCP port 5900 to connect to a server (or 5800 for browser access), but can also be set to use any other port.
Supports Modbus TCP/IP and Modbus RTU simultaneously, as a server (slave) only.
Modbus RTU: requires UID (Modbus address, 1-255) and baud rate.
Modbus TCP/IP: requires allowed client IP address range (for access control) and IP port number (default 502)
All data accessible with Modbus requests is mapped into the Holding Register address space (40000 to
65535). The commands supported are
• 03 – read multiple holding registers
• 16 – write multiple holding registers
Initially, only the physical inputs and outputs are available to a client. All share a common format, in which an input or output is accessible as three consecutive 16-bit words. Remember that Modbus word data is transmitted in Motorola format i.e. high-order byte: low-order byte.
Each input/output is represented as follows:
• Status/control word
• Input/output value (IEEE 32-bit float, high-order word:low-order word)
The status of the status/control word is common to all, but certain bits may never be set if they are not applicable. Unused bits are read as zeros.
b0 signal lost/out of range (AIx and DIx_F only) read-only b1 local override applied read-only b2 alarm active (AOx, DOx only) read-only b3 recopy active (AOx, DOx only) read-only b14 clear Modbus override write-only, always reads as 0 b15 Modbus override active/set Modbus override read/write
Input/output values are expressed as natural units, so that if a 4-20 mA analog input is configured as flow, where 4 mA = 10 l/s and 20 mA = 200 l/s, for an input value of 12 mA the client will read 95.
Space is reserved for 32 each of the analog inputs, digital inputs, analog outputs and digital outputs. Reading an input/output which does not, physically, exist will return all zeros: writing has no effect. Note that input values are supplied after any filtering, scaling and special handling. So reading the value of a 4-20 mA input which has no signal (defined as input < 3.6 mA) may return
• an out-of-range value
• the last-known good value
• a default value depending on the configuration of the input. An input/output with a local override applied will return the override value, not the current physical value.
Page 26
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 24
Address mapping is as follows:
Analog Inputs
40000
Status/control word 40001
input value, high-order word 40002
AI1
Input value, low-order word 40003
Status/control word 40004
input value, high-order word 40005
AI2
Input value, low-order word 40006 . .
AI3 . . 40015
Status/control word 40016
input value, high-order word 40017
AI6
Input value, low-order word 40018-40099
Read as zeros
Digital Inputs
40100
Status/control word 40101
input value, high-order word 40102
DI1 (digital state 1/0)
Input value, low-order word 40103
Status/control word 40104
input value, high-order word 40105
DI1_C (counter value)
Input value, low-order word 40106
Status/control word 40107
input value, high-order word 40108
DI1_F (flow value i.e. counter value over time)
Input value, low-order word 40109 . .
DI2 . . 40145-40147
DI6 40148-40150
DI6_C 40151-40153
DI6_F 40154-40199
Read as zeros
Analog Outputs
40200
Status/control word 40201
input value, high-order word 40202
AO1
Input value, low-order word 40203
Status/control word 40204
input value, high-order word 40205
AO2
Input value, low-order word 40206 . .
AO3 . . 40209
Status/control word 40210
input value, high-order word 40211
AO4
Input value, low-order word 40212-40299
Read as zeros
Page 27
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 25
Digital Outputs
40300
Status/control word 40301
input value, high-order word 40302
DO1
Input value, low-order word 40303
Status/control word 40304
input value, high-order word 40305
DO2
Input value, low-order word 40306 . .
DO3 . . 40309
Status/control word 40310
input value, high-order word 40311
DO4
Input value, low-order word 40312-40399
Read as zeros
To override an input/output value, the client must perform a single write operation to all three words of the input(s)/output(s) concerned. Any number of inputs/outputs may be overridden in the same write operation, but the above condition must be respected.
To override a value the client must write
• status/control word, with b15 set to 1 (other bits will NOT be changed)
• high-order word of the new value
• low-order word of the new value
To clear an override the client must write at least the status/control word for the input/output concerned, with b14 set to 1.
This means that with a single 18-word (6 x 3) write operation the client can override the values of selected analog inputs (by setting b15 of the status/control word to 1), clear an override on others (set b14 to 1), and leave the state of the rest unchanged (b14, b15 = 0).
NOTE that an override will have no effect if
• the write operation is incomplete (writing only 5 words to address 40200, for example, may
override AO1 but will have no effect on AO2)
• the supplied value is outside the permitted range
• a local override, an alarm, or a recopy is active
• if an override is applied and subsequently a local override, an alarm or a recopy become active,
the override is removed.
Page 28
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 26
7 Pump Control Applications
The PC-22D Electronic Pump Control Panel is supplied with a pre-loaded pump control application on the controller. This particular application uses both a pressure switch and valve limit switch.
There are many applications which do not require a pressure switch. If this is the case, the supplied USB stick has an application with the pressure switch removed.
Pressure Switch!
If the alternative program is used, a jumper is still required across the pressure switch contacts.
To load an alternative program, using the 5 button keypad.
From the home screen, hold down the down arrow for more than 2 seconds. Select “Application Management” icon.
Next, select the “Import Application” icon and load the appropriate application. The controller will restart.
NOTE
Figure 19. PC-22D Controller, settings menu.
Page 29
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 27
8 Troubleshooting
1. Verify Input Connections
Note: All digital inputs are dry contact, 0 = Open Contact, 1 = Closed Contact
a. Before checks are made, remove both ice cube relays from socket to disconnect outputs.
b. From the home screen, click the “left arrow” button to view the input status.
c. Verify Local Start is recognized by controller – Put the HOA switch in “local” mode & press the
“Start Pump” button. When pressed, DI4 (Start Pump) should change from 0 to 1. This is a momentary switch, when the “Start Pump” button is released the input will change back to 0.
d. Verify Local Stop is recognized by controller – Put the HOA switch in “local” mode & press the
“Stop Pump” button. When pressed, DI5 (Stop Pump) should change from 0 to 1. This is a momentary switch, when the “Stop Pump” button is released the input will change back to 0.
e. Verify Pressure Switch Contact is Closed – Since a pressure switch is not being used, a jumper is
required across the contact. Verify the controller recognizes the closed contact (DI3 = 1).
f. Verify Limit Switch Contact Closure is Working Correctly – When the valve is closed, DI2 should
read 0 (open contact). When the valve is open, DI2 should read 1 (closed contact). Using a jumper, verify the controller interprets a closed & open contact correctly.
g. Verify Emergency Stop is Working Correctly – Press in and out the emergency stop button & verify
DI6 is responding to each change.
h. Verify Remote Start is Working Correctly – Put the HOA switch in “remote” mode & close the
remote start contact. Verify DI1 (Pump Start) switches from 0 to 1.
Figure 21. PC-22D Controller, input status.
Page 30
!
!
Cla-Val PC-22D Electronic Pump Control Panel
Installation, Operation & Maintenance Manual
Page | 28
2. Verify Output Connections
i. Insert both ice cube relays back into sockets.
j. When the pump starts, verify there is a contact closure between 10 & 11. This is a non-powered
output from the factory.
k. When the valve solenoid energizes there should be 120VAC across 12 & 13.
Page 31
Page 32
GLOBAL HEADQUARTERS
1701 Placentia Avenue Costa Mesa , CA 92627 Phone: (949) 722-4800
(800) 942-6326
E-mail: info@cla-val.com
CLA-VAL EUROPE
Chemin des Mésanges 1 CH-1032 Romanel/ Lausanne, Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50 E-mail: cla-val@cla-val.ch
CLA-VAL UK
Dainton House, Goods Station Road Tunbridge Wells Kent TN1 2 DH England Phone: 44-1892-514-400 Fax: 44-1892-543-423 E-mail: info@cla-val.co.uk
CLA-VAL FRANCE
Porte du Grand Lyon 1 ZAC du Champ du Périer France - 01700 Neyron Phone: 33-4-72-25-92-93 Fax: 33-4-72-25-04-17 E-mail: cla-val@cla-val.fr
EASTERN REGION
6911 Richmond Highway, Suite 444
Alexandria, VA 22306
Phone: (800) 451-3030
CENTRAL REGION
8707 Forney Road
Dallas, TX 75227
Phone: (214) 388-3493
Fax: (214) 381-9579
WESTERN REGION
1701 Placentia Avenue
Costa Mesa, CA 92627
Phone: (949) 722-4800
CLA-VAL PACIFIC
45 Kennaway Road
Woolston, Christchurch
8023 New Zealand
Phone: 64-39644860 info@cla-vapacific.com www.cla-valpacific.com
CLA-VAL LATIN AMERICA
CLA-VAL CANADA