Cla-Val PC-1 User Manual

Page 1
INSTALLATION / OPERATION / MAINTENANCE
INTRODUCTION
Thank you for purchasing Cla-Val Model PC-1 Pump Control Panel. The Cla-Val Model PC-1 Pump Control Panel (P/N 2444901K) pro­vides electrical interlock control between Cla-Val Pump Control Valve and pump with simple field hook-up and easily adjusted pump starting and stopping sequence steps. It is suitable for Booster Pump and Deep Well Pump appli­cations. For detailed operation information see Cla-Val engineering data sheet E-PC-1 included with this manual.
Personnel installing or using this equipment should read entire manual (and any other included documents) to become familiar with requirements for installing or operating the PC-1.
At a minimum, you should follow all applicable sections of the National Fire Code, National Electrical Code, and National Electrical Manufacturer’s Association Standards. There may be local regulatory or governmental offices that can also help deter­mine which codes and standards are necessary for safe installa­tion and operation.
MODEL
PC-1
Pump Control Panel
all applicable electrical wiring codes. Be sure to properly connect earth ground to green terminal.
Noise Suppression
AC power voltage spikes, electro-magnetic interference (EMI), lightning strikes, and AC-powered solenoids coil activation create electrical "noise" that can affect PC-1 controller operation. Noise suppressors are necessary for optimum PC-1 operation. MOV noise suppressors should be installed on PC-1 power input at ter­minals 1 and 2 and on power (red) wires of valve solenoid(s) as close to the solenoid coil as practical. Cla-Val offers an optional Noise Suppressor (p/n 2696336D) rated RC Snubber (MOV-type), 250 VAC, 70 Joules, one-piece with tinned leads.
FUSES
The PC-1 is supplied with four fuses for the powered output circuits. They are found in fuse holders marked F1, F2, F3, and F4. Prior to replacing any fuse all power to the PC-1 must be turned off. Replace fuses with 10 mm x 0.38 mm fuses of the proper current rating.
INSTALLATION
The installation should provide proper ventilation, spacing, and grounding techniques to help minimize the risk of potential prob­lems. Recommended mounting of the PC-1 is on vertical surface at a convenient location near pump motor panel. Conduit should be routed to the bottom of enclosure for easy hook-up to internal field wiring terminal strip. Use appropriate size hole saw to cut only the required number of holes in enclosure bottom. In order to maintain the watertight integrity of the enclosure, only watertight conduit connectors should be used.
WIRING
Consider the following wiring guidelines before you install any sys­tem or power wiring. For specific information on wiring, refer to product specification sheet or National Electrical Code require­ments. can also help determine which codes and standards are necessary for safe installation and operation.
There may be local regulatory or governmental offices that
Always use continuous length of wire. Do not combine wires
to attain a needed length.
Use the shortest practical cable length.
Avoid running wires near high energy wiring.
Avoid running input wiring in close proximity to output wiring
where possible.
Avoid creating sharp bends in the wires.
Input Power
Provide 5 amp fused 120/60 VAC input power for PC-1 at terminals 1 and 2. Provide protection from AC power voltage spikes, elec­tro-magnetic interference (EMI), and lightning strikes according to
Fuse F1 is rated 10 A and is on NON-POWERED Pump Motor
Start Command Circuit
Fuse F2 is rated 1A and is on Valve E-Stop Solenoid Output
Circuit
Fuse F3 is rated 1A and is on Valve Pilot Solenoid Output
Circuit
Fuse F4 is rated 1A and is on Loss of Power Restart Delay
Alarm Output Circuit
INPUTS
The PC-1 control inputs are:
MANUAL/LOCAL
To initiate a pump start, place the H-O-A switch in Hand position and press the green Start switch. Pump will continue to run until red Stop switch is pressed to initiate a normal pump shutdown. When H-O-A switch is in Off position the PC-1 will not initiate a start sequence manually (local) or automatically (remote).
AUTOMATIC/REMOTE START
To initiate a pump start, the PC-1 receives a pump start signal from a remote source such as a SCADA controlled RTU panel or a pres­sure switch. With the H-O-A switch in Auto a contact closure will initiate a pump start. Pump will continue to run while contacts are closed. Contact opening or positioning the H-O-A switch to Off will initiate a normal pump shutdown.
VALVE LIMIT SWITCH
The Normally Open and Common contacts of pump control valve limit switch are used for signaling valve position to the PC-1. These contacts are closed when valve is closed (or when valve is
START
Page 2
open for deep well pumps). The valve limit switch is adjusted to actuate when the valve is in closed position (or open for deep well pumps). For valve switch adjustment procedure, see Cla-Val Model X105L Valve Limit Switch Assembly data sheet in technical manual for pump control valve.
DISCHARGE PRESSURE SWITCH
In order to use the pressure-related functions of the PC-1, an optional customer supplied pressure switch must be installed between pump discharge and control valve inlet. The Normally Open contacts of the pressure switch are used (contacts close when pressure setting is reached or exceeded). If a pressure switch is not used, a factory supplied jumper must be installed across terminals 9 and 10. Remove jumper when installing pres­sure switch.
ANTI-PLUGGING PUMP SWITCH
Some pumps have built-in contacts to indicate pump motor shaft is rotating (forward or backward) when no electric power is applied. These Anti-Plugging Pump Contacts are used for signaling to the PC-1 that pump is rotating. These contacts are closed when pump is rotating and keep PC-1 from initiating a start sequence and potentially causing pump damage.
LAMP TEST/ALARM RESET SWITCH
Momentarily pushing of this switch will test all indicator lamps when power is on (they will all light while the switch is depressed). A 5 to 10 second push of this switch will reset (or acknowledge) any alarm light signal and all lights will go off (white light remains on). If the alarm condition is not corrected after acknowledgment by this switch, the alarm will again trip.
EMERGENCY STOP SWITCH
This push-pull, snap-action switch will remove all power to PC-1 outputs when pushed IN. The internal PLC remains powered. When switch is pulled OUT the PC-1 will operate normally. The switch must "click" into place. Activating this switch requires a heavy manual force.
imer T1 is LOSS OF POWER AUTOMATIC RESTART DELAY
T
TIMER. After a loss of power, an automatic pump restart will occur upon the expiration of timer T1 provided that:
a. The H-O-A switch is in Automatic b. A signal is present to start the pump remotely (terminal 12 and 13) c. The valve indicates closed (via valve position switch at
terminals 10 and 11)
NOTE: Automatic restart is disabled by removing jumper from ter­minals 14 and 15.
Timer T2 is PRESSURE DELAY SEQUENCE TIMER (PDST). Upon initiation of a pump start command, the PDST is energized. The pilot valve solenoid is energized upon expiration of the PDST. In booster pump applications, this time maybe used to allow the pump to develop discharge pressure before opening the pump control valve. In deep well pump applications, the time may be used to flush the system prior to closing the valve and placing the pump on the system.
Timer T3 is VALVE SEQUENCE TIMER (VST).
The VST is energized when the pilot valve solenoid is energized. If the valve fails to open (close for deep well pumps) prior to the VST expiring, an automatic shutdown will occur.
OUTPUTS
The PC-1 control outputs are:
Valve Pilot Solenoid Output Control Circuit (120/60 VAC
1. powered)
2. Valve E-Stop Solenoid Output Control Circuit (120/60 VAC powered)
3. Pump Motor Start Command Circuit (non-powered but fused)
4. Failure to Develop Pressure Remote Alarm Output Circuit (non-powered)
5. Loss of Pressure Remote Alarm Output Circuit (non­powered)
6. Valve Failed to Open Remote Alarm Output Circuit (non­powered)
7. Valve Reclosed Remote Alarm Output Circuit (non-powered)
8. Loss of Power Restart Delay Alarm Output Circuit (120/60 VAC powered)
9. H-O-A Switch in Auto Position Remote Contacts Output Circuit (non-powered)
TIMERS
The PC-1 is supplied with three field adjustable timers. These timers provide easy-to-set adjustment of pump start sequence steps. In case of mechanical trouble with pump, control valve, or system, these timers keep PC-1 from completing a start sequence.
SETTING TIMERS T1, T2, and T3
The Cla-Val PC-1 Pump Control Panel is supplied with three field adjustable timers (time delay relays) marked setting desired time delay, during the pump start sequence power is applied to relay coil and control contacts remain open and power (PWR) light is on. After preset time has elapsed, relay shifts to close contacts and out (OUT) light is on. Reset occurs when power is removed by PLC inside PC-1.
There have been three different styles of time delay relays used for T1, T2, and T3. Each style of relay has different setting instruc­tions depending on date of PC-1 manufacture.
A. Prior to January 1998, the timers were an orange cube-style (Syrelec Model OAR2U delay on make) with an adjustable range of 0.1 sec to 10 hours and used these instructions for setting time delay.
1. Select Hours, Minutes, or Seconds with the Time Base Selection Switch on the lower right-hand front. Use a small screwdriver (4 mm maximum width) to move switch up or down and view desired setting in window above switch. Make sure switch clicks or snaps into place.
T1, T2, and T3. After
Page 3
2. Select desired multiplier (x0.1 or x1) by moving Scale Selection Switch located to the left of the time base switch. Make sure switch clicks or snaps into place.
2. Mode of Operation switch is located on lower left corner of relay top face. This switch must be kept in the ”A” mode position for "Delay on Make" operation.
3. Rotate Dial (for 0 to 10 units) to desired time delay setting within the Time Base range and Scale multiplier selected.
B. Between January 1998 and January 2004, the timers were a blue cube-style (IDEC Model RTE-P12) and used these instruc­tions for setting time delay.
1. Select desired maximum time range using only Time Range Group 2 relay. M = minutes, H = hours
Digital Switch
Position
0, (or 8) 1 S 1 M Blue 1, (or 9) 3 S 3 M Violet
2. Remove thin plastic dial faceplate. Use a small screwdriver (4 mm maximum width) under lip at bottom center to carefully pry faceplate off relay top. Do not remove knob.
3. Digital Switch is located on lower left corner of relay top face. Adjust digital switch up or down with a small screwdriver until desired time range number is displayed in window.
4. Mode of Operation switch is located on upper left corner of relay top face. This switch must be kept in the right-hand position for "Delay on Make" operation.
5. Rotate inner portion of plastic dial faceplate until desired time range and units show in faceplate windows. You may have to turn plastic dial over to find desired range and to match dial color. Refer to above chart. Reinstall plastic dial on top of relay by inserting top edge tabs into top slots. Bend the dial faceplate slightly as it is placed over knob and insert the bottom edge into the bottom slot of the timer. As dial faceplate "snaps" into place at the top, make sure that inner dial remains in place.
6. Use center knob to set amount of time delay desired within the range selected.
in following table. Table is also on bottom side of
Time Range Group
1 2
2 6 S 6 M Violet 3 10 S 10 M Blue 4 60 S 60 M Violet 5 30 S 30 M Violet 6 5 M 5 H Blue 7 10 M 10 H Blue
Dial Color
3. Use center knob to set amount of time delay desired within the range selected.
FIELD WIRING HOOKUP TERMINALS
The following describes the input and output terminals of PC-1 panels built since January 1996. Refer to Field Wiring Hookup dia­gram Cla-V
A.) Terminals 1, 2 and Ground are for connecting 120 Volt 60Hz
B.) Terminals 4 and 5 are dry-contacts (N.O. rated: 120 VAC, 10
C.) Terminals 6 and 7 have 120 Volt AC power (up to 1 Amp -
D.) Terminals 7 and 8 have 120 Volt AC power (up to 1 Amp -
E.) Terminals 9 and 10 are dry-contact type (24 volt DC, 10
F.) Terminals 10 and 11 are dry-contact type (24 volt DC, 10
al drawing 204377 included with this manual.
AC (5 Amp fused) power (customer supplied). This is for power to the PC-1 itself. Terminal 3 is NOT used.
Amp - fused at F1) for connection to customer supplied pump motor starter circuit.
fused at F2) present (the PC-1 will energize these when needed) and are to be connected to the Emergency Closing Solenoid on the control valve (if present).
fused at F3) present (the PC-1 will energize these when needed) and are to be connected to the Pilot Valve Solenoid on the control valve.
Milliamp) for connection to customer supplied no-voltage circuit to Pressure Switch (N. O. contact and Common contact) located between pump output and valve inlet (if present).
Milliamp) for connection to customer supplied no-voltage circuit to Cla-Val Model X105L Valve Limit Switch (N. O. contact and Common contact) mounted on the valve.
C. Starting in January 2004, the timers were changed to a blue cube-style (IDEC Model RTE-P1AF20) and use these instructions for setting time delay.
1. Select desired time range using following table. Set Time Range Selector and Dial Selector at bottom of relay face to corresponding positions for desired time range. Use a small screwdriver (4 mm maximum width) to turn selectors. Make sure switch clicks or snaps into place. DO NOT FORCE BEYOND END POSITION.
Range
s 0.1 s-1 s 0.1 s-3 s 0.2 s-10 s 0.6 s-30 s 1.2 s-60 s
min 1.2 s-1 m 3.6 s-3 m 12 s-10 m 36 s-30 m 1.2 m-60 m
h 1.2 m-1 h 3.6 m-3 h 12 m-10 h 36 m-30 h 1.2 h-60 h
10 h 12 m-10 h 36 m-30 h 2 h-100 h 6 h-300 h 12 h-600 h
0 - 1
scale
s = seconds, m = minutes, h = hours
0 - 3
scale
0 - 10 scale
0 - 30 scale
0 - 60 scale
G.)Terminals 12 and 13 are dry-contact type (24 volt DC, 10
Milliamp) for connection to customer supplied no-voltage circuit to provide Remote/Automatic Start with the PC-1. When these contacts are "made" and with the H-O-A switch in Automatic, the PC-1 will initiate a start of the pump and continue to allow the pump to run until this contact is broken.
H.) Terminals 14 and 15 are for allowing automatic Loss of
Power Restart with the jumper installed (standard). PC-1 will automatically initiate a pump start after power is restored. If the jumper is not present, the PC-1 will not initiate a pump start when power is restored after a loss of power. A manual reset with the Lamp Test/Reset switch (30-sec. minimum) will be needed to restart the pump after power is restored.
J.) Terminals 16 and 17 are dry-contact type (N.O. rated: 1
Amp, 120 VAC) for connection to customer supplied circuit
Page 4
for remote signal alarm of Failure To Develop Pressure.
CLA-VAL
Copyright Cla-Val 2008 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
K.) Terminals 18 and 19 are dry-contact type (N.O. rated: 1
Amp, 120 VAC) for connection to customer supplied circuit for remote signal alarm of Loss Of Pressure.
L.) Terminals 20 and 21 are dry-contact type (N.O. rated: 1
Amp, 120 VAC) for connection to customer supplied circuit for remote signal alarm of Valve Fail To Open.
M.)Terminals 22 and 23 are dry-contact type (N.O. rated: 1
Amp, 120 VAC) for connection to customer supplied circuit for remote signal alarm of Valve Re-Closed during start sequence.
N.) Terminals 24 and 25 have 120/60 AC power (N.O. up to 1
Amp - fused at F4) present when an alarm condition exists and are for connection to customer supplied circuit for remote signal alarm of Loss Of Power Restart Delay. Typically, this would activate a relay for the alarm signal.
O.)Terminals 26 and 27 are dry-contact type (N.O. rated: 1
Amp, 120 VAC) for connection to customer supplied circuit for remote signaling of the H-O-A switch being in the "Auto" position. When the H-O-A switch is in the "Auto" position,
no power contact is "made" at these terminals.
3. On the inside, the Input module red indicators A0, A7, and B0 go on (use A/B selector switch to switch between A and B series).
4. On the inside, the TR1 relay ON and OUT lights are on.
NOTE: If the white panel light does not go on, then the E-STOP switch is depressed. Lifting the E-STOP switch will turn on white panel light. The switch must "click" into place.
NEXT, turn the H-O-A switch from OFF to HAND, then push green (Start) button. Watch for:
1. On the lid, the blue panel light (Pressure) goes on and about three seconds later the green panel light (Valve Open) goes on.
2. On the inside, the Input module red indicator lights A3, A5, A6, A7, B0, and B4 go on.
3. On the inside, the TR1, TR2, and TR3 relay ON and OUT lights go on.
4. On the inside, the CR1 relay red indicator light goes on.
P.) Terminals 28 and 29 are dry-contact type (24 volt DC, 10
Milliamp) for connection to customer supplied no-voltage circuit to provide an "Anti-Plugging" input signal from the pump (if so equipped) when the pump is coasting or spinning in reverse. When these contacts are "made" from the pump, a start sequence will not be allowed.
OPERATION CHECK OUT AND BENCH TEST
The following steps are for a PC-1 operation check out and bench
This test is for newer PC-1 panels built since January 1998
test. and that have on the lid face the following: a) Lamp-test/Reset switch, b) H-O-A switch mounted to the left-of-center, c) lid has red and blue color markings on white background, and d) inside the PC-1 is an Automation-Direct brand modular-style PLC. PC-1’s built before September 1996 used an Omron brand dedicated PLC for internal control sequencing and does not follow this sequence exactly.
NOTE:
a) To verify that panel lamps are functionary properly, depress
and hold Lamp Test/RESET button. All five panel lights go on for about three to five seconds and then go off.
b) If the amber panel light (Restart/Delay) flashes, then
depress the Lamp Test/RESET button for at least 30 seconds to reset the PC-1. You may hear some relay clicking from inside the PC-1, this is normal. If AC power to terminals 1, 2, and ground are removed for 30 seconds, the PC-1 will also reset.
c) If the Lamp Test/RESET button is released before complete
reset, then when the HOA switch is turned from OFF to HAND (or if it was already in HAND), AND then Start button is pushed, the amber panel light will flash. A complete 30 second reset will turn off flashing amber panel light.
d) If the Lamp Test/RESET button is released before complete
reset and the amber panel is flashing, THEN when the E­STOP switch is depressed and then lifted, the red panel light goes on and the amber panel light will continue to flash. A complete 30 second reset will turn off red panel light and flashing amber panel light.
Preparation:
A.) PC-1 hooked up to 120/60 VAC at terminals 1, 2, and Ground. B.) No other inputs or outputs hooked up to the PC-1. C.) Set Time Delay Relays TR1, TR2, and TR3 to zero time. D.) H-O-A switch is in OFF position.
The following steps occur when power is applied:
1. On the lid, the white panel light (Power) goes on.
2. On the inside, the CPU module PWR and RUN green indicators go on.
N-PC-1 (R-1/08)
Page 5
Water Flow to System
(
)
Cla-Val PC-1
H-O-A
Page 2Prepared by Bob Haines 3/30/2007
2 4 5 7 8 10 11 1312
1
G
Check Valve
V1
V2
N.O.
S1
S2 (COM)
61
Series
Control
Valve
To
Waste
120 VAC
Relay
Well
PUMP
1
2
Pump
Typical Deep Well Pump Application and PC-1 Wiring
MOTOR
STARTER
1R
1 2
120 VAC
Radio
RTU
Radio I/O
Center
SCADA
H-O-A
L
H
N
Pump Panel
Page 6
SCADA
Center
Pump Panel
N
H
L
H-O-A
Typical Booster Pump Application and PC-1 Wiring
Prepared by Bob Haines 3/30/2007 Page 1
Radio I/O
RTU
Radio
Relay
120 VAC
2
1R
1
120 VAC
STARTER
1
MOTOR
Pump
2
Booster
PUMP
S1 (N.O.)
Control Valve
S2 (COM)
60 Series
G
1
2 4 5 7 8
H-O-A
Cla-Val PC-1
V1
V2
10
11
Water Flow to System
1312
Page 7
Page 8
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
CLA-VAL
©
Copyright Cla-Val 2008 Printed in USA Specifications subject to change without notice.
N-PC-1 (R-1/08)
Loading...