CIRCUTOR CVM-NET User Manual

CVM-NET
NET
Before performing any maintenance operations,
suspect an operational fault in the unit or in its
RESET
RESET
Modbus Address
Variable
Valid data window
03E8 Hi
Protocol
0 - Modbus
03E8 Lo
Peripheral number
00 to FF ( 0 to 255 dec)
03E9 Hi
Speed (Baud)
0- 1200, 1- 2400, 2- 4800, 3- 9600, 4- 19200
03E9 Low
Parity
0- No
03EA Hi
Length in bits
1- 8 bits
03EA Low
Stop bits
0- 1 bit
Modbus Address
Variable
Valid data window
0BB8,0BB9
Unit serial number
0 to FFFFFFFF (N)
0BBA Hi
Peripheral number
0 to FF (P)
0BBA Low
Port speed
0- 9600, 1-19200 (V)
Modbus Address
Variable
Valid data window
044C,044D
Primary voltage
0 to 000186A0 (100.000)
044E
Secondary voltage
0 to 03E7 (999)
044F
Primary current
0 to 2710 (10,000)
0450 Hi
Not used
00
0450 Low
Not used
00
0451 Hi
Harmonic calculation
00 – THD / 01- D
0451 Low
Not used
00
Modbus Address
Variable
Valid data window
04E2
PD calculation
0000 – No Pd
0024 – Three-phase current
04E3
Integration time
0 to 003C (0-60 minutes)
Digital output 1
Modbus Address
Variable
Valid data window
047E, 047F
MAX value or W·h imp
Hexadecimal value
0480, 0481
MIN value
Hexadecimal value
0482
Delay
0 to 270F (9,999 Decimal)
0483 Hi
Variable number
00 (See table of variables)
0483 Low
Not used
00
Digital output 2
Modbus Address
Variable
Valid data window
04B0, 04B1
MAX value or W·h imp
Hexadecimal value
04B2, 04B3
MIN value
Hexadecimal value
04B4
Delay
0 to 270F (9,999 Decimal)
04B5 Hi
Variable number
00 (See table of variables)
04B5 Low
Not used
00
CVM-
POWER ANALYZER
/ 5 A) .
n
www.circutor.com
, and, while holding
CVM-NET is an instrument that measures and calculates the primary electric parameters in three­phase industrial power grids (balanced or unbalanced). It is measured in true RMS values, using three AC voltage inputs, and three AC current inputs (through current transformers I The measured and calculated parameters are shown in the table of variables.
You can find this manual in electronic format on th e website
protection system, remove the unit from service. The design of the unit makes it easy to replace in the event of a fault.
of CIRCUTOR:
connection modifications, repairs, etc., you must disconnect the unit from the power supply. If you

1.- KEYPAD

CVM-NET has a single button; it can be used to
functionally reset the unit or to restore default communication parameters.
To functionally reset the unit, press the button
for at least one second, and the unit will reset its system within 5 s.
To restore the default communication parameters
(19200/8N/1 see section 2.1.-), disconnect the auxiliary power, then press the button the button down, switch the unit back on. After 5 s, the unit restores its factory settings.

2.- CONFIGURATION

As the unit has no keypad, the configuration settings must be sent to the device via Modbus/RTU© commands, or using the CIRCUTOR PowerStudio Software, which can be downloaded for free from the website:
www.circutor.com

2.1.- Configuration of configurati on s e t t ings

Two options are available for this:

2.1.1.- Using the peripheral number

By default, the unit has the following parameters: 3/19200/8/N/1. The following records are available for changing the peripheral number or speed of communications:
Example of a write command. Changing the peripheral number. From 03 (3 decimal) to 0F (15 decimal), at 9600 bps.
TX: NP 10 03E8000306 000F 0300 0100 CRC RX: NP 10 03E80003 CRC
After editing the registers with the new communications parameters, must be reset the device with the next sentence, entering in the peripheral number the original slave address (in this case the number 03).
TX: NP 05 07D01100 CRC RX: NP 05 07D01100 CRC

2.1.2.- Using the serial number (broadcast)

The serial number of the unit can be found on t he side label of the device (e.g.:3104200679). This number must be translated into hexadecimal l anguage so that the sentence can be sent to the unit:
3104200679 (Decimal)  B90657E7 (Hexadecimal)
The parameters to be set us ing the “broadcast” format to the 00 peripheral are restricted, as they are only for configuring the communication settings:
Example of a write command. Changing the peripheral number. From 03 (3 decimal) to 0F (15 decimal), at 9600 bps.
TX: 00 10 0BB8000306 B90657E7 0F 00 CRC
RX: Time Out

2.2.- Transform a t ion ratio settings

The CVM-NET analyzer can perform indirect measurements (using voltage and current t ransformers). For this reason, it has an input table for setting the voltage and current transformation ratios. If the voltage measurement is performed directly, the ratio is 1/1.
Example of programming voltage ratios; Direct voltage measurement (230 ph-N), and current transformers with primary ratio of 400 A.
Primary voltage 1(Dec) 00000001 (Hex) Secondary voltage 1(Dec) 0001 (Hex) Primary current 400 (Dec) 0190 (Hex) Calculating harmonics 00 with regard to the Effective Value
TX: NP 10 044C00060C 000000010001019000000000 CRC
RX: NP 10 044C00060C CRC
Next, reset the unit (see section 2.1.1.-).

2.2.1.- Reading transformation ratios settings

As additional information, the user has a Modbus command, for reading the transformation ratios setting in th device:
TX: NP 04 044C0006 CRC RX: NP 04 0C 00000001 0001 0190 00000000 CRC

2.3.- Maximum de m a nd s et t ings

The power analyzer can calculate the maximum value, using the sliding window method. This calculat ion can be associated to one of the three available variables, as shown below.
variable
Example of maximum demand programming by three-phase power, with a 15 minute period:
TX: NP 10 04E2000204 0010 000F CRC RX: NP 10 04E20002 CRC
Next, reset the unit (see section 2.1.1.-).
0010 – Active power III 0022 – Apparent power III

2.3.1.- Reading maximum demand setting

As additional information, the user has a Modbus command, for reading the maximum demand setting:
TX: NP 04 04E20002 CRC RX: NP 04 04 0010 000F CRC

2.4.- Deleting m a x imum and minimum v a lues

The power analyzer records all the maximum and minimum values for eac h parameter measured in the Modbus/RTU variables table. A command is avai lable for resetting these records:
TX: NP 05 0836 FF 00 CRC RX: NP 05 0836 FF 00 CRC

2.5.- Deleting m a x imum demand

The maximum demand parameter, when calculated using the sliding window, can be reset, allowing the calculation to be restarted.
TX: NP 05 0838 FF 00 CRC RX: NP 05 0838 FF 00 CRC

2.6.- Configuration and use of digital outputs

2.6.1.- Forcing digital outputs

The unit is fitted with two digital outputs, that can be remotely managed in both their opening and closing functions.
Forcing Digital Output number 1:
TX: NP 05 0000 XX 00 CRC RX: NP 05 0000 XX 00 CRC
(Where XX  FF Close / 00 Open)
Forcing Digital Output number 2:
TX: NP 05 0001 XX 00 CRC RX: NP 05 0001 XX 00 CRC
(Where XX  FF Close / 00 Open)

2.6.2.- Reading the digital output status

The user can request a reading of the digital output status via Modbus/RTU using the following sentence:
TX: NP 01 0000 0008 CRC RX: NP 01 01 XX CRC
Where XX  04 Both outputs open 05 Output 1 closed 06 Output 2 closed 07 Both outputs closed

2.6.3.- Digital output settings

Digital outputs, in addition to being remotely managed, can be used as alarm elements, associated with an electric variable by a maxim um or minimum value, or fulfil the power pulse function associated with any power consumption parameter (active or reactive). The following input table is provided for programming them:
*When a power variable is selected, the analyzautomatically recognises the power pulse function and applies the w·h value of the first record.
Example of alarm programming by maximum and minimum value with voltage VL1. A maximum value of 240 V, a minimum value of 200 V (the voltage value must be sent multiplied by 10 (as shown in the enclosed variables table), and delay of 10 s are programmed.
Maximum value 2400 (Decimal) 00000960 (Hexadecimal) Minimum value 2000 (Decimal) 000007D0 (Hexadecimal) Delay 10 (Decimal) 000A (Hexadecimal) Var number 01 (Decimal) 01 (Hex) Not used 00 (Decimal) 00 (Hexadecimal)
TX: NP10047E00060C 00000960 000007D0 000A 0100 CRC RX: 03 10 047E0006 CRC
Next, reset the unit (see section 2.1.1.-).
*When a power variable is selected, the analyzer automatically recognises the power pulse function and applies the w·h value of the first record.
Example of alarm programming by maximum and minimum value with voltage VL1. Maximum value: 240 V, minimum value: 200 V (Vx10), and a delay of 10 s.
Maximum value 2400 (Decimal) 00000960 (Hexadecimal) Minimum value 2000 (Decimal) 000007D0 (Hexadecimal) Delay 10 (Decimal) 000A (Hexadecimal) Var number 01 (Decimal) 01 (Hex) Not used 00 (Decimal) 00 (Hexadecimal)
TX: NP1004B000060C 00000960 000007D0 000A 0100 CRC RX: 03 10 04B00006 CRC
2.6.4.- Next, reset the unit (see 2.1.1.-).Reading digital
output settings
TX: NP 04 04 047X 0006 CRC RX: NP 04 0C 00000960 000007D0 000A 01 00 CRC
(X: value of the inicial register for each digital output ).
M98229901-03-14A
CVM-NET
90º
180º
-90º
Capacitivo
Capacitivo
Inductivo
Inductivo
Power circuit:
AC version
DC version
Plus version: C. & DC
Metering circuit: Mechanical characteristics:
- Weight:
0.210 kg
Features of the output transistors
- Pulse duration:
100 ms
Precisions Class:
Maximum altitude operating:
2000 meters
Safety:
EN 61000-4-4, EN 61000-4-5, EN 55011, CE
4 wires / 3 wires ( low voltage )
3 wires (2 voltage and 3 current transformers)
3 wires (2 voltage and 2 current transformers)
S2
P2
S1
P1
L1
L2
L3
N
S2
P2
S1
P1
S2
P2
S1
P1
N
V
L1
V
L2
V
L3
min
max Pd
max
clear
COMM
CPU
CVM-MINI
reset reset energy
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
Alimentación
Power Supply
S2
P2
S1
P1
L1
L2
L3
S2
P2
S1
P1
S2
P2
S1
P1
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
b
B
aAbBa
A
V
L1
V
L2
V
L3
Alimentación
Power Supply
L1
L2
L3
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
b
B
a
A
b
B
a
A
V
L1
V
L2
V
L3
S2
P2
S1
P1
S2
P2
S1
P1
Alimentación
Power Supply
FOUR CVM -NE T Q UADRANTS

2.7.- CVM-NET COMMUNICATIONS

One or several CVM-NET analyzers can be connected to a computer or PLC. This system makes it possible to centralise the data in a single record point, in addition to the normal operation of each of them (PowerStudio® System). The CVM-NET has an RS-485 serial communication output. If more than one analyzer is connected to a serial communication bus (RS-485), each analyzer must be assigned a peripheral number or address (from 01 to 255), with a maximum of 32 units per communication bus, so that the central computer sends the queries from the various records measured or calculated to these addresses.
The CVM-NET power analyzer communicates using the MODBUS RTU© protocol (Pulling Question / Answer).

3.- TECHNICAL SPECIFICATIONS

- Single-phase:
- Voltage tolerance:
- Frequency:
- Maximum consumption:
- Working temperature:
- Humidity (non-condensing):
- Case material:
- Protection titted unit (frontal):
- Protection non-fitted unit (sides and rear cover):
- Dimensions (mm):
- Voltage:
- Current:
- Power / Energy:
Measurement sensors: Current / Voltage Power factor: Full-scale measurement margin: ITF / Shunt Temperature sensor: Precision / Working window
- Temperature measurement: with forced ventilation
- Temperature measurement: without forced ventilation

4.- CONNECTIONS

230 V AC
-15% / +10% 50 - 60 Hz
3.0 V·A
-10 …..+ 50 ºC 5 ….. 95%
20…120V DC
1,2…2 W
-10 …..+ 50 ºC 5 ….. 95%
85..265V AC /95..300V DC 50 - 60 Hz (AC mode.)
3.0 V·A/ 3W
-10 …..+ 50 ºC 5 ….. 95%
V0 self-extinguishing plastic IP 51 IP 31 85 x 52 x 70 mm (3 modules)
0.5% ± 1 digit
0.5% ± 1 digit 1% ± 1 digit External transformers / direct voltage
0.5 to 1
0.2 ..... 120% / 2 ..... 120%
± 2 ºC / -10 ….. +50 ºC + 14.0 ºC + 3.5 ºC
- Nominal voltage: phase-neutral / between phases
- Frequency:
- Nominal current:
- Permanent overload:
- Voltage consumption of the circuit:
- Current consumption of the circuit: ITF / Shunt
- Type: Opto-isolated transistor (commutator open).
- Maximum switching voltage:
- Maximum switching current:
- Maximum frequency:
300 V AC / 520 V AC 45 ~ 65 Hz
I
/ 5 A
n
1.2 I
n
0.7 V·A
0.9 V·A / 0.75 V·A
NPN 24 V DC 50 mA 5 pulse / s
Category III - 300 V AC / 520 V AC E N-61010 Class II double-insulated electric shock protection. The system should be c onnec ted t o a power supply circuit pr otec t ed by fuses gl or M type, with current ratings between 0.5 and 1 A. It shoul d be prov ided with a MCCB or equiv al ent device to switch off the system from the power supply circuit. The power supply and voltage measuring circuit is connected with cable minimum cross section of 1 mm2 Standards: IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3,

5.- TECHNICAL SERVICE

In the event of any equipment failure or any operational queries please contact the technical service of CIRCUTOR S.A.
CIRCUTOR S.A. - After sales service Vial Sant Jordi, s/n 08232 -Viladecavalls (Barcelona) tel - (+34) 93 745 29 00 & fax - (+34) 93 745 29 14 E-mail :
sat@circutor.es www.circutor.com
M98229901-03-14A
Loading...