Before performing any maintenance operations,
suspect an operational fault in the unit or in its
0- 1200, 1- 2400, 2- 4800,
3- 9600, 4- 19200
0024 – Three-phase current
0 to 270F (9,999
Decimal)
00 (See table of
variables)
0 to 270F (9,999
Decimal)
00 (See table of
variables)
CVM-
POWER ANALYZER
/ 5 A) .
n
www.circutor.com
, and, while holding
CVM-NET is an instrument that measures and
calculates the primary electric parameters in threephase industrial power grids (balanced or unbalanced).
It is measured in true RMS values, using three AC
voltage inputs, and three AC current inputs (through
current transformers I
The measured and calculated parameters are shown in
the table of variables.
You can find this manual in electronic format on th e website
protection system, remove the unit from service. The design of
the unit makes it easy to replace in the event of a fault.
of CIRCUTOR:
connection modifications, repairs, etc., you must
disconnect the unit from the power supply. If you
1.- KEYPAD
CVM-NET has a single button; it can be used to
functionally reset the unit or to restore default
communication parameters.
To functionally reset the unit, press the button
for at least one second, and the unit will reset its
system within 5 s.
To restore the default communication parameters
(19200/8N/1 see section 2.1.-), disconnect the auxiliary
power, then press the button
the button down, switch the unit back on. After 5 s, the
unit restores its factory settings.
2.- CONFIGURATION
As the unit has no keypad, the configuration settings
must be sent to the device via Modbus/RTU©
commands, or using the CIRCUTOR PowerStudio
Software, which can be downloaded for free from the
website:
www.circutor.com
2.1.- Configuration of configurati on s e t t ings
Two options are available for this:
2.1.1.- Using the peripheral number
By default, the unit has the following parameters:
3/19200/8/N/1. The following records are available for
changing the peripheral number or speed of
communications:
Example of a write command. Changing the peripheral
number. From 03 (3 decimal) to 0F (15 decimal), at 9600 bps.
TX: NP 10 03E8000306 000F 0300 0100 CRC
RX: NP 10 03E80003 CRC
After editing the registers with the new communications
parameters, must be reset the device with the next sentence,
entering in the peripheral number the original slave address (in
this case the number 03).
TX: NP 05 07D01100 CRC
RX: NP 05 07D01100 CRC
2.1.2.- Using the serial number (broadcast)
The serial number of the unit can be found on t he side
label of the device (e.g.:3104200679). This number
must be translated into hexadecimal l anguage so that
the sentence can be sent to the unit:
3104200679 (Decimal) B90657E7 (Hexadecimal)
The parameters to be set us ing the “broadcast” format
to the 00 peripheral are restricted, as they are only for
configuring the communication settings:
Example of a write command. Changing the peripheral number.
From 03 (3 decimal) to 0F (15 decimal), at 9600 bps.
TX: 00 10 0BB8000306 B90657E7 0F 00 CRC
RX: Time Out
2.2.- Transform a t ion ratio settings
The CVM-NET analyzer can perform indirect
measurements (using voltage and current t ransformers).
For this reason, it has an input table for setting the
voltage and current transformation ratios. If the voltage
measurement is performed directly, the ratio is 1/1.
Example of programming voltage ratios; Direct voltage
measurement (230 ph-N), and current transformers with
primary ratio of 400 A.
Primary voltage 1(Dec) 00000001 (Hex)
Secondary voltage 1(Dec) 0001 (Hex)
Primary current 400 (Dec) 0190 (Hex)
Calculating harmonics 00 with regard to the Effective Value
TX: NP 10 044C00060C 000000010001019000000000 CRC
RX: NP 10 044C00060C CRC
Next, reset the unit (see section 2.1.1.-).
2.2.1.- Reading transformation ratios settings
As additional information, the user has a Modbus
command, for reading the transformation ratios setting in
th device:
TX: NP 04 044C0006 CRC
RX: NP 04 0C 00000001 0001 0190 00000000 CRC
2.3.- Maximum de m a nd s et t ings
The power analyzer can calculate the maximum value,
using the sliding window method. This calculat ion can be
associated to one of the three available variables, as
shown below.
variable
Example of maximum demand programming by three-phase
power, with a 15 minute period:
TX: NP 10 04E2000204 0010 000F CRC
RX: NP 10 04E20002 CRC
Next, reset the unit (see section 2.1.1.-).
0010 – Active power III
0022 – Apparent power III
2.3.1.- Reading maximum demand setting
As additional information, the user has a Modbus
command, for reading the maximum demand setting:
TX: NP 04 04E20002 CRC
RX: NP 04 04 0010 000F CRC
2.4.- Deleting m a x imum and minimum v a lues
The power analyzer records all the maximum and
minimum values for eac h parameter measured in the
Modbus/RTU variables table. A command is avai lable
for resetting these records:
TX: NP 05 0836 FF 00 CRC
RX: NP 05 0836 FF 00 CRC
2.5.- Deleting m a x imum demand
The maximum demand parameter, when calculated
using the sliding window, can be reset, allowing the
calculation to be restarted.
TX: NP 05 0838 FF 00 CRC
RX: NP 05 0838 FF 00 CRC
2.6.- Configuration and use of digital outputs
2.6.1.- Forcing digital outputs
The unit is fitted with two digital outputs, that can be
remotely managed in both their opening and closing
functions.
Forcing Digital Output number 1:
TX: NP 05 0000 XX 00 CRC
RX: NP 05 0000 XX 00 CRC
(Where XX FF Close / 00 Open)
Forcing Digital Output number 2:
TX: NP 05 0001 XX 00 CRC
RX: NP 05 0001 XX 00 CRC
(Where XX FF Close / 00 Open)
2.6.2.- Reading the digital output status
The user can request a reading of the digital output
status via Modbus/RTU using the following sentence:
TX: NP 01 0000 0008 CRC
RX: NP 01 01 XX CRC
Where XX 04 Both outputs open
05 Output 1 closed
06 Output 2 closed
07 Both outputs closed
2.6.3.- Digital output settings
Digital outputs, in addition to being remotely managed,
can be used as alarm elements, associated with an
electric variable by a maxim um or minimum value, or
fulfil the power pulse function associated with any
power consumption parameter (active or reactive). The
following input table is provided for programming them:
*When a power variable is selected, the analyzautomatically recognises the
power pulse function and applies the w·h value of the first record.
Example of alarm programming by maximum and minimum
value with voltage VL1. A maximum value of 240 V, a minimum
value of 200 V (the voltage value must be sent multiplied by 10
(as shown in the enclosed variables table), and delay of 10
s are programmed.
Maximum value 2400 (Decimal) → 00000960 (Hexadecimal)
Minimum value 2000 (Decimal) → 000007D0 (Hexadecimal)
Delay 10 (Decimal) → 000A (Hexadecimal)
Var number 01 (Decimal) → 01 (Hex)
Not used 00 (Decimal) → 00 (Hexadecimal)
TX: NP10047E00060C 00000960 000007D0 000A 0100 CRC
RX: 03 10 047E0006 CRC
Next, reset the unit (see section 2.1.1.-).
*When a power variable is selected, the analyzer automatically recognises
the power pulse function and applies the w·h value of the first record.
Example of alarm programming by maximum and minimum
value with voltage VL1. Maximum value: 240 V, minimum value:
200 V (Vx10), and a delay of 10 s.
Maximum value 2400 (Decimal) → 00000960 (Hexadecimal)
Minimum value 2000 (Decimal) → 000007D0 (Hexadecimal)
Delay 10 (Decimal) → 000A (Hexadecimal)
Var number 01 (Decimal) → 01 (Hex)
Not used 00 (Decimal) → 00 (Hexadecimal)
TX: NP1004B000060C 00000960 000007D0 000A 0100 CRC
RX: 03 10 04B00006 CRC
2.6.4.- Next, reset the unit (see 2.1.1.-).Reading digital
output settings
TX: NP 04 04 047X 0006 CRC
RX: NP 04 0C 00000960 000007D0 000A 01 00 CRC
(X: value of the inicial register for each digital output ).
M98229901-03-14A
0º
90º
180º
-90º
Capacitivo
Capacitivo
Inductivo
Inductivo
Metering circuit:
Mechanical characteristics:
Features of the output transistors
Maximum altitude operating:
EN 61000-4-4, EN 61000-4-5, EN 55011, CE
4 wires / 3 wires ( low voltage )
3 wires (2 voltage and 3 current transformers)
3 wires (2 voltage and 2 current transformers)
S2
P2
S1
P1
L1
L2
L3
N
S2
P2
S1
P1
S2
P2
S1
P1
N
V
L1
V
L2
V
L3
min
max Pd
max
clear
COMM
CPU
CVM-MINI
reset reset energy
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
Alimentación
Power Supply
S2
P2
S1
P1
L1
L2
L3
S2
P2
S1
P1
S2
P2
S1
P1
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
b
B
aAbBa
A
V
L1
V
L2
V
L3
Alimentación
Power Supply
L1
L2
L3
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
b
B
a
A
b
B
a
A
V
L1
V
L2
V
L3
S2
P2
S1
P1
S2
P2
S1
P1
Alimentación
Power Supply
FOUR CVM -NE T Q UADRANTS
2.7.- CVM-NET COMMUNICATIONS
One or several CVM-NET analyzers can be connected to a computer or PLC. This system
makes it possible to centralise the data in a single record point, in addition to the normal
operation of each of them (PowerStudio® System). The CVM-NET has an RS-485 serial
communication output. If more than one analyzer is connected to a serial communication bus
(RS-485), each analyzer must be assigned a peripheral number or address (from 01 to 255),
with a maximum of 32 units per communication bus, so that the central computer sends the
queries from the various records measured or calculated to these addresses.
The CVM-NET power analyzer communicates using the MODBUS RTU© protocol (Pulling
Question / Answer).
3.- TECHNICAL SPECIFICATIONS
- Single-phase:
- Voltage tolerance:
- Frequency:
- Maximum consumption:
- Working temperature:
- Humidity (non-condensing):
- Case material:
- Protection titted unit (frontal):
- Protection non-fitted unit (sides and rear cover):
- Dimensions (mm):
- Voltage:
- Current:
- Power / Energy:
Measurement sensors: Current / Voltage
Power factor:
Full-scale measurement margin: ITF / Shunt
Temperature sensor: Precision / Working window
- Temperature measurement: with forced ventilation
- Temperature measurement: without forced ventilation
4.- CONNECTIONS
230 V AC
-15% / +10%
50 - 60 Hz
3.0 V·A
-10 …..+ 50 ºC
5 ….. 95%
20…120V DC
1,2…2 W
-10 …..+ 50 ºC
5 ….. 95%
85..265V AC /95..300V DC
50 - 60 Hz (AC mode.)
3.0 V·A/ 3W
-10 …..+ 50 ºC
5 ….. 95%
V0 self-extinguishing plastic
IP 51
IP 31
85 x 52 x 70 mm (3 modules)
0.5% ± 1 digit
0.5% ± 1 digit
1% ± 1 digit
External transformers / direct voltage
0.5 to 1
0.2 ..... 120% / 2 ..... 120%
± 2 ºC / -10 ….. +50 ºC
+ 14.0 ºC
+ 3.5 ºC
- Nominal voltage: phase-neutral / between phases
- Frequency:
- Nominal current:
- Permanent overload:
- Voltage consumption of the circuit:
- Current consumption of the circuit: ITF / Shunt
- Type: Opto-isolated transistor (commutator open).
- Maximum switching voltage:
- Maximum switching current:
- Maximum frequency:
300 V AC / 520 V AC
45 ~ 65 Hz
I
/ 5 A
n
1.2 I
n
0.7 V·A
0.9 V·A / 0.75 V·A
NPN
24 V DC
50 mA
5 pulse / s
Category III - 300 V AC / 520 V AC E N-61010 Class II double-insulated electric shock
protection.
The system should be c onnec ted t o a power supply circuit pr otec t ed by fuses gl or M type,
with current ratings between 0.5 and 1 A. It shoul d be prov ided with a MCCB or equiv al ent
device to switch off the system from the power supply circuit. The power supply and
voltage measuring circuit is connected with cable minimum cross section of 1 mm2
Standards:
IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3,
EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3,
5.- TECHNICAL SERVICE
In the event of any equipment failure or any operational queries please contact the technical service of CIRCUTOR S.A.
CIRCUTOR S.A. - After sales service
Vial Sant Jordi, s/n
08232 -Viladecavalls (Barcelona)
tel - (+34) 93 745 29 00 & fax - (+34) 93 745 29 14
E-mail :
sat@circutor.es www.circutor.com
M98229901-03-14A