Circutor CVM-MINI SERIES, CVM-MINI-ITF-HAR-RS485-C2, CVM-MINI-ITF-Plus-RS485-C2, CVM-MINI-Shunt, CVM-MINI-ITF Instruction Manual

...
POWER ANALYZER
CVM-MINI SERIES
INSTRUCTION MANUAL
M98174001-03-19A
Page 2 of 26
CONTENTS
1 BASIC INSTRUCTIONS .............................................................................................................. 3
1.1 Checks on receipt. ............................................................................................................ 3
1.2 Main features ................................................................................................................... 3
1.3 Electrical parameters ........................................................................................................ 3
1.4 Other features .................................................................................................................. 4
1.5 Available models ............................................................................................................. 4
2 INSTALLATION AND START-UP ............................................................................................... 5
2.1 Installation ...................................................................................................................... 5
2.1.1 Power supply voltage .................................................................................................. 5
2.1.2 Maximum voltage in the voltage measurement circuit ................................................... 5
2.1.3 Maximum permanent current in the current circuit ........................................................ 5
2.1.4 Transistor output features ............................................................................................ 5
2.1.5 Temperature probe features ......................................................................................... 5
2.1.6 Operating conditions .................................................................................................. 6
2.1.7 Safety ........................................................................................................................ 6
2.2 Start-up ........................................................................................................................... 6
2.2.1 Description of terminals .............................................................................................. 6
2.2.2 Connection diagrams .................................................................................................. 7
3 OPERATING MODE .................................................................................................................... 7
3.1 Keypad ........................................................................................................................... 8
3.2 Default settings ................................................................................................................ 8
3.2.1 Default display ........................................................................................................... 9
3.2.2 LED Indicators......................................................................................................... 10
4 SETTING SET-UP ...................................................................................................................... 10
4.1 Measurement Set-up ....................................................................................................... 10
4.1.1 Transformation Ratios .............................................................................................. 11
4.1.1.1 Voltage primary value ........................................................................................ 11
4.1.1.2 Voltage secondary value ..................................................................................... 11
4.1.1.3 Current primary value ......................................................................................... 11
4.1.1.4 Current secondary value ..................................................................................... 12
4.1.2 Measurement in 2 or 4 quadrants ............................................................................... 12
4.1.3 Power demand meter parameterisation ....................................................................... 13
4.1.3.1 Integrated parameter ........................................................................................... 13
4.1.3.2 Integration period ............................................................................................... 13
4.1.3.3 Clearing power demand meter value .................................................................... 14
4.1.4 Display and backlight ............................................................................................... 14
4.1.4.1 Selection of screens to be displayed ..................................................................... 14
4.1.4.2 Selection of start page ........................................................................................ 14
4.1.4.3 Backlight (Backlit display).................................................................................. 15
4.1.5 Clearing energy meter values .................................................................................... 15
4.1.6 Setting THd or d ...................................................................................................... 15
4.1.7 Digital output for the transistor (2) ............................................................................. 15
4.1.7.1 Impulse per n KW·h or Kvar·h consumed or generated ......................................... 16
4.1.7.2 Alarm condition ................................................................................................. 16
4.2 Communication Set-up ................................................................................................... 19
4.2.1 Default settings ........................................................................................................ 19
4.2.2 Peripheral number .................................................................................................... 20
4.2.3 Transmission speed .................................................................................................. 20
4.2.4 Parity ...................................................................................................................... 20
4.2.5 Data bits .................................................................................................................. 21
4.2.6 Stop bits .................................................................................................................. 21
4.2.7 Protection of data Set-up using password ................................................................... 21
5 APPENDIX – CVM-MINI-ITF-HAR-RS485-C2 SERIES .............................................................. 22
6 MODBUS RTU PROTOCOL ...................................................................................................... 23
6.1 MODBUS memory map ................................................................................................. 23
6.2 RS485 Connection diagram ............................................................................................ 26
7 TECHNICAL SERVICE ............................................................................................................. 26
Page 3 of 26
1 BASIC INSTRUCTIONS
This manual is designed to familiarise the user with operating the CVM-MINI power analyzer in order to get the best from its features.
1.1 Checks on receipt.
Please check the following points on receipt of the analyzer:
The equipment delivered matches your order specifications.
Check that the equipment has not been damaged during delivery.
Check that it has the correct instruction manual.
This manual contains information and warnings about the CVM-MINI
analyzer which must be followed to guarantee the proper operation of all instrument functions and to maintain it in a safe condition.
Installing and maintenance for this analyzer must be carried out by a qualified person.
1.2 Main features
The CVM-MINI panel analyzer is a programmable measuring instrument; it offers a series of options for using it, which may be selected from configuration menus on the instrument itself. Before starting the analyzer carefully read sections: power supply, connection and setting and select the most suitable form of operation in order to obtain the required data.
The CVM-MINI measures, calculates and displays the main electrical
parameters for three-
phase, balanced or unbalanced industrial
systems.
Measurements are taken in true effective value using the three alternating and neutral voltage inputs and three current inputs to
measure IN /1A or IN
/5A secondaries from external measurement
transformers.
Figure 1. [CVM-MINI]
The CVM-MINI allows the display of all electrical parameters, using the backlit LCD display, showing three instant electrical parameters, maximum or minimum on each page jump.
1.3 Electrical parameters
By using its internal processor, the CVM-MINI shows on the screen and through communication (according to model), over 100 parameters, which may be either single­phase or three-phase. These parameters may or may not be displayed on the screen, according to the equipment’s preset values.
Page 4 of 26
PARAMETER
UNIT
L1
L2
L3
III
Phase-neutral voltage
V f-n
• • • Phase-phase voltage
V f-f
• • •
Current
A
• • •
••
Frequency
Hz
Active power
kW
• • •
Reactive power L
kvarL
• • •
Reactive power C
kvarC
• • •
Apparent power
kVA
• • • • Power factor
PF
• • • • Cos ϕ
Cos ϕ
Maximum demand
Pd
• • •
Neutral current
IN
Voltage THD
% THD - V
• • •
Current THD
% THD - A
• • •
kWh (consumption and generation)
W·h
kvarh.L (consumption and generation)
W·h
kvarh.C (consumption and generation)
W·h
kVAh (consumption and generation)
W·h
Harmonic content (V and A) *
%
• • •
15th
Temperature
ºC
( • ) Available through display and communications. ( •• ) Only available through communications. ( * ) Harmonic content in HAR model.
1.4 Other features
A small sized instrument with a 85x52x70mm (3 steps).
Measurement in true effective value (TRMS).
Instant, maximum, minimum values for each parameter.
Energy measurer function.
1 GW·h counter in consumed energy.
100 MW·h counter in generated energy.
Backlit LCD display.
Built in RS485 communications (Modbus RTU®).
Temperature probe built in the equipment.
1.5 Available models
CODE
REFERENCE
Ci r c ut or UER1 .0 0
M52000
CVM-MINI-Shunt
M52010
CVM-MINI-ITF
M52021
CVM-MINI-ITF-RS485-C2
M52031
CVM-MINI-ITF-HAR-RS485-C2
M52022
CVM-MINI-ITF-Plus-RS485-C2
Page 5 of 26
2 INSTALLATION AND START-UP
This manual contains information and warnings about the analyzer which must be followed to guarantee the proper operation of all instrument functions and to maintain it in a safe condition. The analyzer must not be switched on until it is finally connected to the electrical board.
If the equipment is handled in a way not specified by the manufacturer, the
equipment's protection may be compromised.
When it is likely that the equipment has lost its protection (i.e. with visible damage), it must be disconnected from the auxiliary supply. In this event, contact a qualified technical service representative.
2.1 Installation
The following features must be taken into consideration before supplying power to the equipment:
2.1.1 Power supply voltage
Standard model power supply: Single-phase 230 V AC. Plus model power supply: 85…265 V AC. / 95…300 V DC. Frequency: 50 Hz … 60 Hz Power supply tolerance: -15 % / +10% Connection terminals: 14 - 15 Equipment consumption: 3 VA
2.1.2 Maximum voltage in the voltage measurement circuit
Voltage: 300 V AC. phase-neutral
520 V AC. phase-phase
Frequency: 50 Hz … 60 Hz
2.1.3 Maximum permanent current in the current circuit
In scale IN /1A: 1.2 amperes In scale I
N
/5A: 6.0 amperes
2.1.4 Transistor output features
Type NPN transistor: Opto-insulated / Open Collector Maximum operating voltage: 24 V DC. Maximum operating current: 50 mA Maximum frequency: 5 impulses / second Impulse length: 100 ms
2.1.5 Temperature probe features
The CVM-MINI has a built in temperature sensor. The sensor has a ± 2ºC accuracy and a temperature measurement range of -10ºC +50ºC.
The interior temperature of the CVM-MINI has been estimated at 14.0 ºC above the interior of the cabinet where it has been installed, if the cabinet has no ventilation. If the cabinet has forced ventilation then the temperature of the CVM is 3.5 ºC higher.
Page 6 of 26
2.1.6 Operating conditions
Operating temperature: -10 ºC / +50ºC Relative humidity: 5 to 95 % RH (without condensation) Altitude: Up to 2000 metres
2.1.7 Safety
Designed for category III installations, 300 V AC (EN 61010). Class II double insulation against electric shock protection.
2.2 Start-up
The equipment is mounted on a DIN rail 46277 (EN 50022). All connections must remain inside the electrical board.
Note that when the instrument is switched on, the terminals may be dangerous
when touched and opening or removing parts may access dangerous areas.
Therefore, the equipment must not be used until it is properly installed.
The equipment must be connected to a power supply circuit protected with gl (IEC 269) or type M fuses between 0.5 and 2 A. It must have an overload/short circuit switch or equivalent device in order to disconnect the equipment from the power supply system. An earth leakage switch or similar device must be fitted to disconnect the equipment from the power supply system. The power supply circuit and the voltage measurement circuit are connected with a cable with a minimum diameter of 1 mm
2
. The secondary line for the current transformer shall have a minimum diameter of 2.5 mm
2
.
2.2.1 Description of terminals
TERMINAL
TERMINAL DESCRIPTION
1
Current input AL1 - S1
2
Current input AL1 - S2
3
Current input AL2 - S1
4
Current input AL2 - S2
5
Current input AL3 - S1
6
Current input AL3 - S2
7
Transistor output RL2
8
Common transistor output
9
Transistor output RL1
10
Measurement VL3
11
Measurement VL2
12
Measurement VL1
13
Neutral V measurement
14
Power supply voltage input
15
Power supply voltage input
A
RS-485 (+)
S
RS-485 (GND)
B
RS-485 (-)
Page 7 of 26
2.2.2 Connection diagrams
S2
P2
S1
P1
L1
L2
L3
N
S2
P2
S1
P1
S2
P2
S1
P1
N
Alimentacion
Power Supply
S2
P2
S1
P1
L1
L2
L3
S2
P2
S1
P1
S2
P2
S1
P1
b
B
a
A
b
B
a
A
L1
L2
L3
b
B
a
A
b
B
a
A
S2
P2
S1
P1
S2
P2
S1
P1
Alimentacion
Power Supply
Figure 2. [4-wire / 3-wire - Low Voltage]
Figure 3. [2 voltage transformers -
3 current transformers]
Figure 4. [2 voltage transformers -
2 current transformers]
3 OPERATING MODE
When power is supplied to the CVM-MINI, the equipment will start its software interface on the screen showing the version of the firmware and its setting. After a few seconds the equipment is ready to operate and shows all available screens. Once started the power analyzer will display the programmable electrical parameters via the measurement Set-up. If there is no previous setting, the analyzer will display the voltage between phase and neutral for L1, L12 and L1
Ci r c ut or UER1 .0 0
Figure 5. CVM-MINI
-
-
-
8 .8 .8 .8 8 .8 .8 .8
8.8.8.8.88
L1
L2
L3
THD
PF
OS
C
I
N
Pd
kvVArCh
Hz
Figure 6. CVM-MINI display - LCD SEGMENTS
Page 8 of 26
3.1 Keypad
The keypad comprises a total of seven silicon buttons which are used to set the equipment. Some buttons have a rapid access function, i.e. entering the Set Up interface is not required. Only the rapid access key needs to be pressed to run the function. Only three of the seven buttons may be pressed when the upper cover is down. This is because the remaining five keys have a high risk factor if they were to be accidentally pressed.
KEY
FUNCTION
resetN
Starting the equipment and clearing maximum and minimum values
for all instant parameters. Pressing the Reset
key is equivalent to
starting the equipment in the absence of voltage.
Nsetup
Using a long press, after starting the equipment (in the absence of
voltage, or after pressing the Reset key), Communication Set-up is accessed. Here the
RS485 port parameters may be set and all
communication and measurement parameters may be blocked
using a password. Using a long press, after starting the equipment (runtime mode), Measurement Set-up
is accessed. Each and every parameter for
measurement may be changed.
clear
energy
Rapid access function; using a long press (pressed for 5 seconds),
all enabled energy counters are cleared (kW·h / kvarL·h / kvarC·h /
kVA·h in power consumption or consumption and generation).
max Pd
clear
Rapid access function; using a long press (pressed for 5 seconds),
the Power demand parameter previously set in Measurement Set-
up is cleared (Power demand) (kW III / kV·A III / A III / A ph).
Displaying all electrical variables by repeated presses, in runtime
mode. In Set-up
mode has the function of advancing the setting
screens.
min
Pressing in runtime mode, displays the minimum value of displayed
variable/s. In Set-up
mode it has the function of moving 1 digit
sideways.
max
Pressing in runtime mode, maximum variable values are displayed.
In Set-up
mode it has the function of increasing 1 digit cyclically
(from 0 to 9
), or selecting between two possible preset
configurations (for example: yes or no).
3.2 Default settings
The CVM-MINI Analyzer has a factory setting for display, communication and measurement. For this reason and due to the fact that this default setting is not valid in nearly all cases, the user must properly set-up the display, measurement and communication in accordance with the installation’s requirements.
Page 9 of 26
3.2.1 Default display
Figure 7. Phase-neutral
voltage
(1)
Figure 8. Phase-phase voltage
(1)
503,2
570.9
550.8
L1
L2
L3
A
Figure 9. Current per phase
117,2 132,5 128,5
L1
L2
L3
kvV
Figure 10. Active power per
phase
7 .6
14.1 7 .6
L1
L2
L3
K VAr
Figure 11. Reactive power per
phase
117.9
133.4
128.5
L1
L2
L3
K VA
Figure 12. Apparent power per
phase
0.
99
0
.
9
9
0.99
L1
L2
L3
Pd
PF
Figure 13. Power factor per
phase
1 .3 1 .3 1 .0
L1
L2
L3
THD
V
Figure 14. % harmonic
distortion in voltage per phase
6 ,4 5 .0 4 ,9
L1
L2
L3
THD
A
Figure 15. % harmonic
distortion in current per phase
0.99
377.9
PF
kvV
Figure 16. PF III / Active power
III
0.99
29.2
PF
K VArL
Figure 17. PF III / Inductive
reactive power III
0.99 0
PF
K VArC
Figure 18. PF III / Capacitive
reactive power III
0.99 379,4
OS
C
K VA
Figure 19. Cos ϕ III / Apparent
power III
96,2
50.0 24,6oC
I
N
Hz
Figure 20. Neutral current /
Frequency / Temperature
375,5
Pd
kvV
Figure 21. Maximum demand
52349.1
kvV h
Figure 22. Imported / Consumed
active energy
1246.4
K VArLh
Figure 23. Imported / Consumed
inductive reactive energy
253.2
K VArCh
Figure 24. Imported / Consumed
capacitive reactive energy
52668.6
K VA h
Figure 25. Imported / Consumed
apparent energy
2349.1-
kvV h
Figure 26. Exported / Generated
active energy
- 1246.4
K VArLh
Figure 27. Exported / Generated
inductive reactive energy
- 253.2
K VArCh
Figure 28. Exported / Generated
capacitive reactive energy
- 2668.6
K VA h
Figure 29. Exported / Generated
apparent energy
(1)
The device display voltage as:
0 … 999 V :  … . V The dot indicates 1 decimal, 1000 … 9999 V :  V without decimal. 10000 … 99999 V : .. V , the dot indicates a multiplying factor of 100.
389.5
390.1
V
229.5
229.8
230.1
L1
L2
L3
V
Page 10 of 26
3.2.2 LED Indicators
The CVM-MINI power analyzer is supplied with two LED indicators which give information on the status of:
LED
FUNCTION
CPU
The slow flashing of the LED CPU shows that the equipment has
auxiliary power supply and is operative. The rapid flashing of the LED CPU shows that there is an internal
problem with the start up software.
CO MM
The slow flashing of the COMM LED shows that the equipment is communicating with a master peripheral via its RS485
communications port. The CVM-MINI power analyzer’s
communications protocol is Modbus RTU.
4 SETTING SET-UP
The CVM-MINI power analyzer has two very different Set-up configurations which can set the parameters for all the measurement and communication settings.
Measurement set-up: All parameterisation of the equipment’s measurements are carried out from this menu; voltage display (phase-neutral or phase-phase voltages and current transformer ratios, setting the power demand meter, setting the start page, backlight setting, returning the energy counters to zero and maximum demand, type of harmonic distortion and setting the transistor outputs.
Communication set-up: All of the analyzer’s RS485 RTU Modbus communications are parameterised from this set-up menu. Also the option to enter a password to protect previous data settings in both Set-ups is possible from this menu.
4.1 Measurement Set-up
The measurement parameters for the CVM-MINI and all its functions are changed from this menu (according to type); it may start the eight energy meters and reset maximum demand (Pd), maximums and minimums recorded. The analyzer does not store the setting changes until all of the setting has been finished; the analyzer does not store the changes to the settings until the whole setting
program has been completed. If
resetN
is pressed before the end of the setting, the
setting entered is not stored in the memory.
To access MEASUREMENT Set-Up the SETUP key has to be pressed with a
long press with the equipment started until setting mode is entered.
On entering setting mode, the message "SETUP loc", or as a default "SETUP unlo" is displayed for a few seconds indicating that it is in setting and is informing of their status (locked or unlocked respectively).
SETUP unlo: on entering setting mode it is possible to view and change the setting. SETUP loc: on entering setting mode it is possible to view the parameterisation but it is not possible to change it.
Page 11 of 26
4.1.1 Transformation Ratios
This menu accesses the voltage and current ratios and the voltage and current primary and secondary may be changed.
4.1.1.1 Voltage primary value
The display shows ”set PriU” followed by six digits; these allow the setting of the transformer voltage primary. To write or change the voltage transformer primary value, repeatedly press the
max
key increasing the value of the digit which is flashing at the time. When the required value is on the screen, move on to the following digit by pressing
min
, to change the remaining values.
When the last digit has been changed, press
min
to move back to the first
digit, allowing the previously set values to be changed again. To enter the data and access the next setting process, press
.
set Pr i U 000001
Figure 30. Voltage primary ratio
4.1.1.2 Voltage secondary value
The display shows ”set SecU” followed by three digits; these allow the setting of the transformer voltage secondary. To write or change the voltage transformer secondary value, repeatedly press the
max
key increasing the value of the digit which is flashing at the time. When the required value is on the screen, move on to the following digit by pressing
min
, to change the remaining values.
When the last digit has been changed, press
min
to move back to the first
digit, allowing the previously set values to be changed again. To enter the data and access the next setting step, press
.
set Sec U 001
Figure 31. Secondary voltage ratio
4.1.1.3 Current primary value
The display shows ”set PrIA” followed by five digits; these allow the setting of the transformer current primary. To write or change the current primary value, repeatedly press the
max
key increasing the value of the digit which is flashing at the time. When the required value is on the screen, move on to the following digit by pressing
min
, to change the remaining values.
Page 12 of 26
When the last digit has been changed, press
min
to move back to the first
digit, allowing the previously set values to be changed again. To enter the data and access the next setting step, press
.
set pr i a 00005
Figure 32. Current primary ratio
4.1.1.4 Current secondary value
Due to the fact that the CVM-MINI analyzer has a double scale for measuring the current secondary, the secondary to be measured by the analyzer must be set (I
N
/1A or IN /5A).
To select one of the two display measurement options, press the
max
key and
the two options will alternate. Once the required secondary of current has been selected, press the
key to enter the data and access the next setting step.
set Sec a 5
set Sec a 1
Figure 33. Current secondary value IN /5A
Figure 34. Current secondary value IN /1A
4.1.2 Measurement in 2 or 4 quadrants
The CVM-MINI power analyzer may measure in two quadrants (power consumption), or in four quadrants (power consumption and generation). If measurements are only to be taken in power consumption, the two quadrant option is recommended to avoid exported or generated energies being displayed (-kW·h / -kvarL·h / -kvarC·h / -kVA·h).
90º
180º
-90º
Capacitive
Capacitive
Inductive
Inductive
Page 13 of 26
To select one of the two display options (2 or 4 measurement quadrants), press the
max
key and the two options will alternate. Once the required option is
selected, press the
key to enter the data and access the next setting step.
set quad 4
set quad 2
Figure 35. Measurement in 4 quadrants
Figure 36. Measurement in 2 quadrants
4.1.3 Power demand meter parameterisation
The CVM-MINI power demand meter is the integration in the time of a preset instant parameter. The amplitude of this window is preset by the integration time.
4.1.3.1 Integrated parameter
The display shows ”Pd Code” followed by two digits which identify the code or variable to be integrated as Maximum Demand.
To select one of the four integration parameters available, press the
max
key
and the four options will alternate in turn. Once the required option is selected, press the
key to enter the data and access the next setting step.
Pd Code 16
Figure 37. Active power III
Pd Code 34
Figure 38. Apparent power III
Pd Code 36
Figure 39. Current III
Pd Code a- ph
Figure 40. Current per phase
If “Pd Code 00” is selected, the instant integration of the power demand meter will be deactivated.
4.1.3.2 Integration period
The Integration Period of the power demand meter may vary between a minimum of 1 minute up to a maximum of 60 minutes. To write or change the integration time value, repeatedly press the
max
key increasing the value of the digit which is flashing at the time. When the required value is on the screen, move on to the following digit by pressing
min
, to allow the remaining values to be changed.
When the last digit has been changed, press
min
to move back to the first
digit, allowing the previously set values to be changed again. To enter the data and access the next setting step, press
.
Page 14 of 26
4.1.3.3 Clearing power demand meter value
To clear or save maximum demand, press the
max
key and the two options will
alternate. Once the required option is selected, press the
key to enter the
data and access the next setting step.
Cl r pd no
Cl r pd yes
Figure 41. No-clearing power demand meter value
Figure 42. Clearing power demand meter value
4.1.4 Display and backlight
4.1.4.1 Selection of screens to be displayed
Due to the fact that the CVM-MINI power analyzer has a large number of default screens (as shown in section 3.2.1 Default display), the user has the option of setting a personalised display by selecting screens to be displayed.
The display shows as default “def page yes”; the
max
key has to be pressed to
proceed to the personalised display option. The analyzer will show “def page no” on the screen; to enter the data and proceed to this setting, press
.
Once the personalisation option has been entered, by using
key the screens shown in section 3.2.1 Default display will be displayed in turn. By using the
max
button, the screen to be displayed is selected. Select “yes” or
“no” respectively.
4.1.4.2 Selection of start page
In order to select the equipment’s preferred start up screen, repeatedly press the
max
key up to display the screen to be selected. Once the required option
is selected, press the
key to enter the data and access the next setting
step.
set init page
L1
L2
L3
V
Figure 43. Select preferred page
Rotating function: Using the rotating display function, the Power analyzer automatically displays every available screen for five seconds each.
The
must be used to enter the rotating display function when all electrical
parameters are flashing at the same time.
Page 15 of 26
4.1.4.3 Backlight (Backlit display)
The time in which the back lighting will be on after the last use is set by using the keypad in this menu. The display is permanently on if 00 is set.
4.1.5 Clearing energy meter values
Clearing energy meters refers to the four consumed or imported energy meters. To select clear these meters of kw·h, press the
max
key and the two options will
alternate. Once the required option is selected, press the
key to enter the
data and access the next setting step.
cl r ener no
cl r ener yes
Figure 44. No-clearing energy meters
Figure 45. Clearing energy meters
4.1.6 Setting THd or d
Harmonic distortion rate measurements may be made using two measurement options: the effective value or the fundamental value. To select one of the two calculation options, press the
max
key and the two
options will alternate. Once the required option is selected, press the
key to
enter the data and access the next setting step.
set HAR THD
set HAR D
Figure 46. Harmonic distortion value for the
effective value (RMS)
Figure 47. Harmonic distortion value for the
fundamental value
4.1.7 Digital output for the transistor (2)
Two types of setting may be made using the CVM-MINI’s digital transistor outputs:
Impulse per n kW·h or kvar·h (Energy): the value for the energy consumed
or generated may be set to generate an impulse.
Alarm condition: associates a parameter to a digital output, setting a
maximum, minimum and delay (delay) for the trip condition.
In the event that no condition needs to be set, the 00 code is typed and entered using the
key.
Page 16 of 26
4.1.7.1 Impulse per n KW·h or Kvar·h consumed or generated
In order to generate an impulse for consumed n kW·h, the energy meter to be used has to be selected:
PARAMETER
SYMBOL
CODE
Active energy III
kW·h III
31
Inductive reactive energy III
KvarL·h III
32
Capacitive reactive energy III
KvarC·h III
33
Apparent energy III
kVA·h III
44
Active energy generated III
kW·h III (-)
45
Inductive reactive energy generated III
KvarL·h III (-)
46
Capacitive reactive energy generated III
KvarC·h III (-)
47
Apparent energy generated III
kVA·h III (-)
48
Once the energy code has been selected and entered using the key, the watts·time per impulse is entered or as a default, kilowatts·time per impulse.
For entering the watts·time rate per impulse, repeatedly press the
max
key increasing the value of the digit which is flashing at the time. When the required value is on the screen, move on to the following digit by pressing
min
, to allow the remaining values to be changed.
When the last digit has been changed, press
min
to move back to the first
digit, allowing the previously set values to be changed again. To enter the data and access the next setting step, press
.
Ou t 1 Pul s
000.000
Figure 48. Watts / impulse
4.1.7.2 Alarm condition
In order to link an alarm condition to an energy parameter, the code for the selected parameter has to be entered. A list of electrical parameters and their codes is shown below.
Page 17 of 26
PARAMETER
PHASE
SYMBOL
CODE
Phase-neutral voltage
L1
V 1
01
Current
L1
A 1
02
Active power
L1
kW 1
03
Reactive power L/C
L1
KvarL/C 1
04
Apparent power
L1
kV·A
38
Power factor
L1
PF 1
05
% THD V
L1
THD V1
25
% THD A
L1
THD A1
28
Phase-neutral voltage
L2
V 2
06
Current
L2
A 2
07
Active power
L2
kW 2
08
Reactive power L/C
L2
KvarL/C 2
09
Apparent power
L2
kV·A
39
Power factor
L2
PF 2
10
% THD V
L2
THD V2
26
% THD A
L2
THD A2
29
Phase-neutral voltage
L3
V 3
11
Current
L3
A 3
12
Active power
L3
kW 3
13
Reactive power L/C
L3
KvarL/C 3
14
Apparent power
L3
kV·A
40
Power factor
L3
PF 3
15
% THD V
L3
THD V3
27
% THD A
L3
THD A3
30
Temperature
-
ºC
41
PARAMETER
SYMBOL
CODE
PARAMETER
SYMBOL
CODE
Active power III
kW III
16
cos ϕ three-phase
cos ϕ
19
Inductive power III
kvarL III
17
Power factor III
PF III
20
Capacitive power III
kvarC III
18
Frequency
Hz
21
Active energy
kW·h
31
L1- L2 Voltage
V 12
22
Inductive reactive energy
Kvarh·L
32
L2- L3 Voltage
V 23
23
Capacit. reactive energy
Kvarh·C
33
L3- L1 Voltage
V 31
24
Apparent power III
kV·A III
34
Temperature
ºC
41
Maximum demand
Md (Pd)
35
Maximum demand L1
Md (Pd)
35*
Current III
AIII
36
Maximum demand L2
Md (Pd)
42*
Neutral current
IN
37
Maximum demand L3
Md (Pd)
43*
* Variables only valid if the Maximum Demand for current has been set per phase.
There are also some codes which refer to the three-phases at the same time (Function OR). If one of these variables has been selected, the alarm will go off when any of the three-phases, or all three at the same time, match the preset conditions.
Page 18 of 26
PARAMETER
SYMBOL
CODE
Phase-neutral voltage
V1 / V2 / V3
90
Current
A1 / A2 / A3
91
Active power
kW1 / kW2 / kW3
92
Reactive power
Kvar1 / kvar2 / kvar3
93
Apparent power
kV·A1 / kV·A2 / kV·A3
98
Power factor
PF1 / PF2 / PF3
94
Phase-phase voltage
V12 / V23 / V31
95
% THD V
Thd1 / Thd2 / Thd3 V
96
% THD I
Thd1 / Thd2 / Thd3 A
97
Once the Alarm Condition code has been selected and the data entered using the
key, the maximum value, minimum value and the delay in seconds
(hysteresis) for the alarm condition must be entered.
For entering the maximum, minimum and hysteresis values, repeatedly press the
max
key increasing the value of the digit which is flashing at the time. When the required value is on the screen, move on to the following digit by pressing
min
, to allow the remaining values to be changed.
When the last digit has been changed, press
min
to move back to the first
digit, allowing the previously set values to be changed again. In order to enter one of the pieces of data, press the
key. Once the delay has been set,
press the
key entering the data and ending the setting.
Ou t 1 HI
000.0
Ou t 1 lo
000.0
Ou t 1 del a 0000
Figure 49. Maximum value
Figure 50. Minimum value
Figure 51. Hysteresis / Delay
Setting the number 2 digital output is shown on the display as “Out 2”. This must be set by using the settings shown below.
MIN +
MAX + max > min
ON OFF ON
======
0 Min Max
MIN +
MAX + max < min
OFF ON OFF
==============
0 Max Min
MIN -- MAX +
ON OFF ON
=======
Min 0 Max
MIN + MAX --
OFF ON OFF
=============
Max 0 Min
MIN --
MAX -­max > min
ON OFF ON
=====
Min Max 0
MIN --
MAX -­max < min
OFF ON OFF
================
Max Min 0
Activating the outputs of the programmable values as Maximums and Minimums.
Page 19 of 26
4.2 Communication Set-up
One or more CVM-MINI instruments may be connected to a computer or PLC in order to automate a production process or an energy control system. As well as the usual operation of each instrument, this system may centralize data at one single point; for this reason the CVM-MINI has an RS-485 communication output. If more than one instrument is connected to one single series line (RS-485), it is necessary to assign to each a number or address (from 01 to 255) so that the central computer or PLC sends the appropriate requests to these addresses for each peripheral.
From communication Set-up, the CVM-MINI's communication parameters may be displayed and/or changed; this may match these parameters to the requirements of the system topologies and/or applications. The analyzer does not store the setting changes until all of the setting has been finished. If it is Reset before the end of the setting, the setting entered is not stored in the memory.
To access the COMMUNICATION Set-up, first press the Reset key and
immediately press the Set-up key for a long time to enter a setting.
On entering setting mode the message "SETUP inic" appears for a few seconds, informing the user that the equipment has entered communications display or setting mode.
set pr ot bus
Figure 52. Protocol information
Using this information screen, the equipment is informing the user that the Communication protocol via the RS-385 series port is standard MODBUS©.
To enter setting mode, press the
key.
4.2.1 Default settings
This menu option allows the automatic selection of a predefined communication parameter; the default preset parameters are: Peripheral number 1, speed 9,600 bps, parity NO, data bits 8 and stop bit 1.
If a different preset communication setting is not required, “no” should be selected.
To select one of the two options, just press the
max
key and the two options will
alternate. Once the required option is selected, press the
key to enter the
data and access the next setting step.
Page 20 of 26
set Cdef no
set Cdef yes
Figure 53. Non-standard communication
parameters
Figure 54. Predefined communication
parameters
4.2.2 Peripheral number
The peripheral number varies between 0 and 255 (0 and FF in hexadecimal). To write or change the number of the peripheral, repeatedly press the
max
key increasing the value of the digit which is flashing at the time. When the required value is on the screen, move on to the following digit by pressing
min
, to allow the remaining values to be changed.
When the last digit has been changed, press
min
to move back to the first digit,
allowing the previously set values to be changed again. To enter the data and access the next setting step, press
.
set nper 001
Figure 55. Peripheral number
4.2.3 Transmission speed
The transmission speed of RS485 communication bus may be: 1,200 bps, 2,400 bps, 4,800 bps, 9,600 bps or 19,200 bps. To select one of the transmission speeds available, press the
max
key and the four options will alternate in turn.
Once the required option is selected, press the
key to enter the data and
access the next setting step.
set baud 19200
Figure 56. Transmission speed
4.2.4 Parity
Parity may be selected, even or odd; to select the type of parity, press the
max
key and the three options will alternate in turn. Once the required option is selected, press the
key to enter the data and access the next setting step.
Page 21 of 26
set Pa r i no
Figure 57. Parity
4.2.5 Data bits
7 or 8 data bits may be selected; to select the number of bits, press the
max
key
and the two options will alternate in turn. Once the required option is selected, press the
key to enter the data and access the next setting step.
Figure 58. Data bits
4.2.6 Stop bits
1 or 2 stop bits may be selected; to select the number of bits, press the
max
key
and the two options will alternate in turn. Once the required option is selected, press the
key to enter the data and access the next setting step.
set st op 1
Figure 59. Stop bits
4.2.7 Protection of data Set-up using password
This menu option aims to protect the data set in Measurement Set-up. As a default the equipment does NOT protect data with the “unlo” option. By
pressing the
key the data is entered and setting the equipment is finalised.
If, on the other hand, the parameters in Measurement Set-up are to be protected, the option “Loc” has to be selected using the
max
key and then the key pressed. The protection password as a default will always be 1234; any other password code entered will be incorrect.
set pass 0000
set pass 1234
Figure 60. Password request to protect Set-up data
Figure 61. Enter password to protect Set-up data
For entering the password, repeatedly press the
max
key increasing the value of
the digit which is flashing at the time.
Page 22 of 26
When the required value is on the screen, move on to the following digit by pressing
min
, to allow the remaining values to be changed.
When the last digit has been changed, press
min
to move back to the first digit,
allowing the previously set values to be changed again. In order to enter the password, press the
key. Once the password has been set, press the
key entering the data and ending the setting.
In the event that the measurement SETUP parameters are to be changed again, the equipment has to be first unlocked by the same procedure (position “unlo”), and the appropriate changes are made.
5 APPENDIX – CVM-MINI-ITF-HAR-RS485-C2 SERIES
The CVM-MINI Series has an analyzer for the harmonic content up to the 15th harmonic in voltage and current, showing the content on the LCD display. Therefore, the HAR has a high number of display screens, where the value of the current and voltage fundamental and the content of each harmonic may be seen. The equipment’s display diagram is obtained by using the following procedure:
Figure 62. Display of Harmonic Content in Voltage and Current
Page 23 of 26
6 MODBUS RTU PROTOCOL
The CVM-MINI power analyzer communicates using the MODBUS© protocol. In the MODBUS protocol the RTU (Remote terminal Unit) mode is used; each 8-bit per byte in a message contains two 4-bits hexadecimal characters.
The format for each byte in RTU mode is:
Code 8 bit binary, hexadecimal 0-9, A-F.
2 hexadecimal characters contained in each 8-bit field in
the message. Bits per byte 8 data bits. Field Check-Error CRC Type (Cyclical Redundancy Check).
Modbus functions used:
Function 01 Reading the status of the relays.
Function 03 and 04 Reading n Words (16 bits-2 bytes). Function used for
reading the electrical parameters that the CVM-MINI is measuring. All electrical parameters are long with 32 bits, because of this two Words are required to request each parameter.
(4 bytes - XX XX XX XX)
Function 05 Writing a relay.
6.1 MODBUS memory map
PARAMETER
SYMBOL
Instant
Maximum
Minimum
Units
Voltage phase
V L1
00-01
60-61
C0-C1
V x10
Current
A L1
02-03
62-63
C2-C3
mA
Active power
kW L1
04-05
64-65
C4-C5
w
Reactive power
Kvar L1
06-07
66-67
C6-C7
w
Apparent power
kV·A L1
4A-4B
AA-AB
10A-10B
Power factor
PF L1
08-09
68-69
C8-C9
x 100
Voltage phase
V L2
0A-0B
6A-6B
CA-CB
V x10
Current
A L2
0C-0D
6C-6D
CC-CD
mA
Active power
kW L2
0E-0F
6E-6F
CE-CF
w
Reactive power
Kvar L2
10-11
70-71
D0-D1
w
Apparent power
kV·A L2
4C-4D
AC-AD
10C-10D
w
Power factor
PF L2
12-13
72-73
D2-D3
x 100
Voltage phase
V L3
14-15
74-75
D4-D5
V x10
Current
A L3
16-17
76-77
D6-D7
mA
Active power
kW L3
18-19
78-79
D8-D9
W
Reactive power
Kvar L3
1A-1B
7A-7B
DA-DB
W
Apparent power
kV·A L3
4E-4F
AE-AF
10E-10F
w
Power factor
PF L3
1C-1D
7C-7D
DC-DD
x 100
Temperature
ºC
50-51
B0-B1
110-111
ºC x 10
Page 24 of 26
PARAMETER
SYMBOL
Instant
Maximum
Minimum
Units
Active power III
kW III
1E-1F
7E-7F
DE-DF
w
Inductive power III
KvarL III
20-21
80-81
E0-E1
w
Capacitive power III
KvarC III
22-23
82-83
E2-E3
w
Cos φ III
Cos φ III
24-25
84-85
E4-E5
x 100
Power factor III
PF III
26-27
86-87
E6-E7
x 100
Frequency
Hz
28-29
88-89
E8-E9
Hz x 10
Voltage line L1-L2
V12
2A-2B
8A-8B
EA-EB
V x10
Voltage line L2-L3
V23
2C-2D
8C-8D
EC-ED
V x10
Voltage line L3-L1
V31
2E-2F
8E-8F
EE-EF
V x10
% THD V L1
%THD VL1
30-31
90-91
F0-F1
% x 10
% THD V L2
%THD VL2
32-33
92-93
F2-F3
% x 10
% THD V L3
%THD VL3
34-35
94-95
F4-F5
% x 10
% THD A L1
%THD AL1
36-37
96-97
F6-F7
% x 10
% THD A L2
%THD AL2
38-39
98-98
F8-F9
% x 10
% THD A L3
%THD AL3
3A-3B
9A-9B
FA-FB
% x 10
Apparent power III
KvaIII
42-43
A2-A3
102-103
w
Maximum demand
Md (Pd)
44-45
A4-A5
104-105
w/VA/mA
Three-phase current (average)
A_AVG
46-47
A6-A7
106-107
mA
Neutral current
In
48-49
A8-A9
108-109
mA
Maximum demand A2
Md (Pd)
52-53
B2-B3
112-113
mA
Maximum demand A3
Md (Pd)
54-55
B4-B5
114-115
mA
PARAMETER
SYMBOL
Instant
Units
Active energy
kW·h III
3C-3D
w·h
Inductive reactive energy
kvarL·h III
3E-3F
w·h
Capacitive reactive energy
kvarC·h III
40-41
w·h
Apparent energy
kVA·h III
56-57
w·h
Active energy generated
kW·h III (-)
58-59
w·h
Inductive energy generated
kvarL·h III (-)
5A-5B
w·h
Capacitive energy generated
kvarC·h III (-)
5C-5D
w·h
Apparent energy generated
kVA·h III (-)
5E-5F
w·h
Page 25 of 26
* Recordings available in HAR model
MODBUS VARIABLES
PARAMETER
SYMBOL
L1
L2
L3
Units
Harmonic content in VOLTAGE
RMS current
V
2AE-2AF
2CC-2CD
2EA-2EB
Vx10
Harmonic 2
2B0-2B1
2CE-2CF
2EC-2ED
%
Harmonic 3
2B2-2B3
2D0-2D1
2EE-2EF
%
Harmonic 4
2B4-2B5
2D2-2D3
2F0-2F1
%
Harmonic 5
2B6-2B7
2D4-2D5
2F2-2F3
%
Harmonic 6
2B8-2B9
2D6-2D7
2F4-2F5
%
Harmonic 7
2BA-2BB
2D8-2D9
2F6-2F7
%
Harmonic 8
2BC-2BD
2DA-2DB
2F8-2F9
%
Harmonic 9
2BE-2BF
2DC-2DD
2FA-2FB
%
Harmonic 10
2C0-2C1
2DE-2DF
2FC-2FD
%
Harmonic 11
2C2-2C3
2E0-2E1
2FE-2FF
%
Harmonic 12
2C4-2C5
2E2-2E3
300-301
%
Harmonic 13
2C6-2C7
2E4-2E5
302-303
%
Harmonic 14
2C8-2C9
2E6-2E7
304-305
%
Harmonic 15
2CA-2CB
2E8-2E9
306-307
%
* Recordings available in HAR model
MODBUS VARIABLES
PARAMETER
SYMBOL
L1
L2
L3
Units
Harmonic content in CURRENT
RMS current
A
1F4-1F5
212-213
230-231
mA
Harmonic 2
1F6-1F7
214-215
232-233
%
Harmonic 3
1F8-1F9
216-217
234-235
%
Harmonic 4
1FA-1FB
218-219
236-237
%
Harmonic 5
1FC-1FD
21A-21B
238-239
%
Harmonic 6
1FE-1FF
21C-21D
23A-23B
%
Harmonic 7
200-201
21E-21F
23C-23D
%
Harmonic 8
202-203
220-221
23E-23F
%
Harmonic 9
204-205
222-223
240-241
%
Harmonic 10
206-207
224-225
242-243
%
Harmonic 11
208-209
226-227
244-245
%
Harmonic 12
20A-20B
228-229
246-247
%
Harmonic 13
20C-20D
22A-22B
248-249
%
Harmonic 14
20E-20F
22C-22D
24A-24B
%
Harmonic 15
210-211
22E-22F
24C-24D
%
Page 26 of 26
6.2 RS485 Connection diagram
A1
A
2
5
1
2
B ( - )
A ( + )
S GND
5
1
2
7
5
2
3
5
7
3
2
RS-485
RS-232
CONVERTIDOR
DB-9
RS-232 / RS-485
PC
7 TECHNICAL SERVICE
In the event of any equipment failure or any operational queries please contact the technical service of CIRCUTOR S.A. CIRCUTOR S.A. - After sales service. Vial Sant Jordi, s/n 08232 - Viladecavalls. Tel. – 902 449 459 (Spain) / +34 937 452 919 ( Out of Spain) E-mail - sat@circutor.com
RS-232 / RS-485 CONVERTER
Loading...