Circutor CVM-E3-MINI Instruction Manual

INSTRUCTION MANUAL
(M170B01-03-18B)
Power analyzer
CVM-E3-MINI
2
Instruction Manual
SAFETY PRECAUTIONS
DISCLAIMER
CIRCUTOR, SA reserves the right to make modi cations to the device or the unit speci ca-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device speci cations and the most updated manuals.
www.circutor.com
CIRCUTOR, recommends using the original cables and accessories that are supplied with the device.
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a speci c point.
Follow the warnings described in this manual with the symbols shown below.
If you must handle the unit for its installation, start-up or maintenance, the following should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit. In particular, handling with voltages applied may result in electric shock, which may cause death or serious injury to personnel. Defective installation or maintenance may also lead to the risk of  re. Read the manual carefully prior to connecting the unit. Follow all installation and maintenance instructions throughout the unit’s working life. Pay special attention to the installation stan­dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result in injury or damage to the unit and /or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior noti cation.
3
Instruction Manual
CONTENTS
SAFETY PRECAUTIONS ���������������������������������������������������������������������������������������������������������������������������������������3 DISCLAIMER ���������������������������������������������������������������������������������������������������������������������������������������������������������� 3 CONTENTS ������������������������������������������������������������������������������������������������������������������������������������������������������������� 4 REVISION LOG �������������������������������������������������������������������������������������������������������������������������������������������������������6 SYMBOLS ��������������������������������������������������������������������������������������������������������������������������������������������������������������� 6 1�- VERIFICATION UPON RECEPTION ����������������������������������������������������������������������������������������������������������������� 7 2�- PRODUCT DESCRIPTION �������������������������������������������������������������������������������������������������������������������������������� 7 3�- DEVICE INSTALLATION ����������������������������������������������������������������������������������������������������������������������������������� 8
3�1�- PRIOR RECOMMENDATIONS������������������������������������������������������������������������������������������������������������������� 8 3�2�- INSTALLATION ������������������������������������������������������������������������������������������������������������������������������������������9 3�3�- PANEL MOUNTING ACCESSORY (72 x 72 mm)��������������������������������������������������������������������������������������9 3�4�- DEVICE TERMINALS ������������������������������������������������������������������������������������������������������������������������������� 11 3�5�- CONNECTION DIAGRAM ������������������������������������������������������������������������������������������������������������������������ 12 3�5�1�- MEASURING THREE-PHASE NETWORKS WITH A 4-WIRE CONNECTION ������������������������������ 12
3�5�2�- MEASURING THREE-PHASE NETWORKS WITH A 3-WIRE CONNECTION� ���������������������������� 13 3�5�3�- MEASURING THREE-PHASE NETWORKS WITH A 3-WIRE CONNECTION AND TRANSFORMERS WITH AN ARON CONNECTION ��������������������������������������������������������������������������������� 14 3�5�4�- MEASURING TWO-PHASE NETWORKS WITH A 3-WIRE CONNECTION ��������������������������������� 15 3�5�5�- MEASURING SINGLE-PHASE NETWORKS, PHASE TO PHASE, WITH A 2-WIRE CONNECTION� ������������������������������������������������������������������������������������������������������������������������������������������� 16 3�5�6�- MEASURING SINGLE-PHASE NETWORKS, PHASE TO NEUTRAL, WITH A 2-WIRE CONNECTION� ������������������������������������������������������������������������������������������������������������������������������������������� 17
4�- OPERATION ���������������������������������������������������������������������������������������������������������������������������������������������������� 18
4�1�- MEASURING PARAMETERS ������������������������������������������������������������������������������������������������������������������ 19 4�2�- KEYBOARD FUNCTIONS ������������������������������������������������������������������������������������������������������������������������ 21 4�3�- DISPLAY ��������������������������������������������������������������������������������������������������������������������������������������������������� 22 4�4�- LED INDICATORS ������������������������������������������������������������������������������������������������������������������������������������ 23 4�5�- DIGITAL INPUT ���������������������������������������������������������������������������������������������������������������������������������������� 23 4�6�- DIGITAL OUTPUT ������������������������������������������������������������������������������������������������������������������������������������ 24
5�- DISPLAY ���������������������������������������������������������������������������������������������������������������������������������������������������������� 25
5�1�- ANALYZER PROFILE������������������������������������������������������������������������������������������������������������������������������25
5�1�1�- MAXIMUM VALUES ������������������������������������������������������������������������������������������������������������������������ 28 5�1�2�- MINIMUM VALUES �������������������������������������������������������������������������������������������������������������������������� 28 5�1�3�- MAXIMUM DEMAND ����������������������������������������������������������������������������������������������������������������������� 28 5�1�4�- HARMONICS ����������������������������������������������������������������������������������������������������������������������������������� 28
5�1�5�- DETECTION OF INCORRECT CONNECTION AND INCORRECT DIRECTION OF ROTATION ��29 5�2�- e3 PROFILE ���������������������������������������������������������������������������������������������������������������������������������������������� 30 5�3�- DEVICE INFORMATION SCREENS ������������������������������������������������������������������������������������������������������� 34 5�4�- DIGITAL INPUT AND OUTPUT STATUS SCREEN �������������������������������������������������������������������������������� 34
6�- CONFIGURATION ������������������������������������������������������������������������������������������������������������������������������������������� 35
6�1�- PRIMARY VOLTAGE ������������������������������������������������������������������������������������������������������������������������������� 36 6�2�- SECONDARY VOLTAGE ������������������������������������������������������������������������������������������������������������������������� 36 6�3�- PRIMARY CURRENT ������������������������������������������������������������������������������������������������������������������������������37 6�4�- SECONDARY CURRENT ������������������������������������������������������������������������������������������������������������������������38 6�5�- NUMBER OF QUADRANTS �������������������������������������������������������������������������������������������������������������������38 6�6�- MEASUREMENT CONVENTION ������������������������������������������������������������������������������������������������������������ 39 6�7�- MEASUREMENT SYSTEM ���������������������������������������������������������������������������������������������������������������������39 6�8�- MAXIMUM DEMAND INTEGRATION PERIOD��������������������������������������������������������������������������������������� 40
6�9�- DELETING MAXIMUM DEMAND ������������������������������������������������������������������������������������������������������������ 41
6�10�- DELETING MAXIMUM AND MINIMUM VALUES ��������������������������������������������������������������������������������� 41 6�11�- DELETING ENERGY VALUES �������������������������������������������������������������������������������������������������������������� 42 6�12�- ACTIVATING THE HARMONICS DISPLAY SCREEN� �������������������������������������������������������������������������42 6�13�- kgC02 CARBON EMISSION RATIO OF CONSUMED ENERGY ���������������������������������������������������������� 43 6�14�- kgC02 CARBON EMISSION RATIO OF GENERATED ENERGY ��������������������������������������������������������� 44 6�15�- COST RATIO OF CONSUMED ENERGY ��������������������������������������������������������������������������������������������� 44 6�16�- COST RATIO OF GENERATED ENERGY �������������������������������������������������������������������������������������������� 45 6�17�- PROGRAMMING ALARM : DIGITAL OUTPUT T1 ������������������������������������������������������������������������������� 46
6�17�1� MAXIMUM VALUE �������������������������������������������������������������������������������������������������������������������������� 48
6�17�2� MINIMUM VALUE ��������������������������������������������������������������������������������������������������������������������������� 48
4
Instruction Manual
6�17�3� CONNECTION TIME DELAY ���������������������������������������������������������������������������������������������������������� 49 6�17�4� HYSTERESIS VALUE ��������������������������������������������������������������������������������������������������������������������� 50 6�17�5� LATCH �������������������������������������������������������������������������������������������������������������������������������������������� 50 6�17�6� DISCONNECTION TIME DELAY ��������������������������������������������������������������������������������������������������� 51 6�17�7� CONTACT STATUS ������������������������������������������������������������������������������������������������������������������������ 51 6�17�8� KILOWATTS PER PULSE �������������������������������������������������������������������������������������������������������������� 52
6�17�9� PULSE WIDTH �������������������������������������������������������������������������������������������������������������������������������52 6�18�- OPERATING MODE OF DIGITAL INPUT ��������������������������������������������������������������������������������������������53 6�19�- BACKLIGHT, TURNING ON THE BACKLIT DISPLAY ������������������������������������������������������������������������ 54 6�20�- RS-485 COMMUNICATIONS����������������������������������������������������������������������������������������������������������������� 54
6�20�1�- MODBUS PROTOCOL: BAUD RATE ������������������������������������������������������������������������������������������� 55
6�20�2�- MODBUS PROTOCOL: PERIPHERAL NUMBER ������������������������������������������������������������������������ 56
6�20�3�- MODBUS PROTOCOL : PARITY �������������������������������������������������������������������������������������������������� 56
6�20�4�- MODBUS PROTOCOL : DATA BITS �������������������������������������������������������������������������������������������� 57
6�20�5�- MODBUS PROTOCOL : STOP BITS �������������������������������������������������������������������������������������������� 57
6�20�6�- BACnet PROTOCOL : BAUD RATE �������������������������������������������������������������������������������������������� 58
6�20�7�- BACnet PROTOCOL : ID ��������������������������������������������������������������������������������������������������������������58
6�20�8�- BACnet PROTOCOL : MAC ADDRESS ��������������������������������������������������������������������������������������� 59 6�21�- LOCKING THE PROGRAMMING ���������������������������������������������������������������������������������������������������������59
6�21�1�- PASSWORD ���������������������������������������������������������������������������������������������������������������������������������� 60
7�- COMMUNICATIONS ���������������������������������������������������������������������������������������������������������������������������������������� 62
7�1�- CONNECTIONS ��������������������������������������������������������������������������������������������������������������������������������������� 62 7�2�- MODBUS PROTOCOL ����������������������������������������������������������������������������������������������������������������������������63
7�2�1�- READING EXAMPLE : Funtion 0x04� �������������������������������������������������������������������������������������������� 63
7�2�2�- WRITING EXAMPLE : Funtion 0x05� ��������������������������������������������������������������������������������������������� 63 7�3�- MODBUS COMMANDS ��������������������������������������������������������������������������������������������������������������������������� 64
7�3�1� MEASUREMENT VARIABLES ��������������������������������������������������������������������������������������������������������� 64
7�3�2� ENERGY VARIABLES ���������������������������������������������������������������������������������������������������������������������� 67
7�3�3� VOLTAGE AND CURRENT HARMONICS� ��������������������������������������������������������������������������������������69
7�3�4� DELETING PARAMETERS� ������������������������������������������������������������������������������������������������������������� 72
7�3�5� POWER STATUS ����������������������������������������������������������������������������������������������������������������������������� 73
7�3�6� DETECTION OF INCORRECT DIRECTION OF ROTATION ����������������������������������������������������������� 73
7�3�7� DEVICE CONFIGURATION VARIABLES� ��������������������������������������������������������������������������������������73
7�4�- BACnet PROTOCOL �������������������������������������������������������������������������������������������������������������������������������78
7�4�1�- MAPA PICS ������������������������������������������������������������������������������������������������������������������������������������� 79
8�- TECHNICAL FEATURES �������������������������������������������������������������������������������������������������������������������������������� 82 9�- MAINTENANCE AND TECHNICAL SERVICE ������������������������������������������������������������������������������������������������ 85 10�- GUARANTEE �������������������������������������������������������������������������������������������������������������������������������������������������85 11�- CE CERTIFICATE ������������������������������������������������������������������������������������������������������������������������������������������ 86
5
Instruction Manual
REVISION LOG
Table 1: Revision log�
Date Revision Description
12/17 M170B01-03-17A Initial Version
02/18 M170B01-03-18A
Changes in the following sections:
3.3. - 6.17.- 10.
04/18 M170B01-03-18B
Changes in the following sections:
3.2.- 3.5. - 5.1.5 - 7.3.6.
Note : Devices images are for illustrative purposes only and may differ from the actual device.
SYMBOLS
Table 2: Symbols
Symbol Description
In compliance with the relevant European directive.
Device covered by European directive 2012/19/EC. At the end of its useful life, do not leave the unit in a household waste container. Follow local regulations on electronic equipment recycling.
DC current
~
AC current
6
Instruction Manual
1�- VERIFICATION UPON RECEPTION
Check the following points when you receive the device:
a) The device meets the specications described in your order. b) The device has not suffered any damage during transport. c) Perform an external visual inspection of the device prior to switching it on. d) Check that it has been delivered with the following:
- An installation guide,
- 1 retainer to secure the device to the DIN rail,
- 4 connectors.
- 2 terminal covers.
If any problem is noticed upon reception, immediately contact the transport company and/or CIRCUTOR's after-sales service.
2�- PRODUCT DESCRIPTION
The CVM-E3-MINI device measures, calculates and displays the main electrical parameters of the following networks: single-phase, two-phase, with and without neutral, balanced three­phase, with ARON measurements or unbalanced. The measurement will be taken in RMS with the three AC voltage inputs and three current inputs.
The device features:
- 3 keys that allow you to browse between the various screens and program the device.
- 2 indicator LEDs: CPU and ALARM.
- LCD display, displays all parameters,
- 1 digital inputs, used to select the tariff or detect the logic state of external signals.
- 1 digital outputs, fully programmable.
- RS-485 Communications, with two serial protocols: MODBUS RTU© and BACnet.
7
Instruction Manual
3�- DEVICE INSTALLATION
3.1.- PRIOR RECOMMENDATIONS
In order to use the device safely, it is critical that individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use the necessary personal protective equipment, and pay attention to the vari­ous warnings indicated in this instruction manual.
The CVM-E3-MINI device must be installed by authorised and qualied staff.
The power supply plug must be disconnected and measuring systems switched off before
handling, altering the connections or replacing the device. It is dangerous to handle the device
while it is powered.
Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal
injury and damage to installations.
The manufacturer of the device is not responsible for any damage resulting from failure by the
user or installer to heed the warnings and/or recommendations set out in this manual, nor for
damage resulting from the use of non-original products or accessories or those made by other
manufacturers.
If an anomaly or malfunction is detected in the device, do not use it to take any measurements.
Inspect the work area before taking any measurements. Do not take measurements in danger-
ous areas or where there is a risk of explosion.
Disconnect the device from the power supply (device and measuring system power supply) before maintaining, repairing or handling the device's connections. Please contact the after-sales service if you suspect that there is an operational fault in the device.
8
Instruction Manual
3.2.- INSTALLATION
The device must be installed on an electric panel or enclosure, attached to a DIN rail (IEC
60715).
Terminals, opening covers or removing elements can expose parts that are haz­ardous to the touch while the device is powered. Do not use the device until it is fully installed.
The device must be connected to a power circuit that is protected with gl (IEC 269) or M type fuses with a rating of 0.5 to 2 A. It must be tted with a circuit breaker or equivalent device, in order to be able to disconnect the device from the power supply network. The power and voltage measuring circuit must be connected with cables that have a minimum cross-section of 1mm2.
The secondary line of the current transformer will have a minimum cross-section of 2.5 mm2.
To guarantee the insulation of the device and its category, it is necessary to earth the S2 termi­nals of the transformers.
The temperature rating of insulation of wires connected to the device will be at minimum 62ºC.
3.3.- PANEL MOUNTING ACCESSORY (72 x 72 mm)
Note: The 72 x 72 mm panel mounting accessory is an accessory that is sold separately.
CIRCUTOR has a panel mounting accessory of the CVM-E3-MINI equipment so that it can be installed on 72 x 72 mm panels.
Figure 1: CVM-E3-MINI with panel mounting accessory�
Figure 2 shows the installation of the panel mounting accessory to the CVM-E3-MINI.
Disconnect all power supplies and measuring equipment from the device before carrying out the installation of the panel mounting accessory.
9
Instruction Manual
Figure 2: Installation of the panel mounting accessory�
Table 3: Technical features�
Technical features
Protection degree IP40
Enclosure Self-extinguishing V0 plastic
68 mm
68 mm
Figure 3: Panel cut-out�
10
Instruction Manual
3.4.- DEVICE TERMINALS
Table 4:Device terminals
Device terminals
A1: Auxiliary power supply 4: S2, L2 current input
A2: Auxiliary power supply 5: S1, L3 current input
10 : VL1, L1 voltage input 6: S2, L3 current input
11 : VL2, L2 voltage input
A : A+, RS485
12 : VL3, L3 voltage input
B : B-, RS485
13 : N, Neutral voltage input
S : S, GND for RS485 and digital inputs
1: S1
,
L1 current input
9: I1, Digital input 1 or selection rate
2: S2, L1 current input
8: O1, Digital output 1
3: S1, L2 current input
7: CO, Common digital outputs
A1
A2
10
11
12
13
10
11
12 13
Figure 4:CVM-E3-MINI terminals: Up�
1
2
S
9
8
7
3
4
5
6
A
B
2 3 4
5 6
A B S
9 8
7
1
Figure 5:CVM-E3-MINI terminals: down�
11
Instruction Manual
3.5.- CONNECTION DIAGRAM
3�5�1�- MEASURING THREE-PHASE NETWORKS WITH A 4-WIRE CONNECTION
Measurement system: 4-3Ph
VL1 VL2
VL3 N
L1
L2
L3
N
N
V
L3
L2
V
L1
V
VL1 VL2 VL3
a
b
A B
a
b
A B
CARGA / LOAD
13
12
11
10
Alimentación Auxiliar
Power Supply
S1 S2 S1
S2
S1
S2
S1
S2
P1
P2
S1 S2
P1
P2
S1
S2
P1
P2
1 2
3 4
5 6
Figure 6: Three-Phase measuring with a 4-wire connection�
To guarantee the insulation of the device and its category, it is nec­essary to earth the S2 terminals of the transformers.
12
Instruction Manual
3�5�2�- MEASURING THREE-PHASE NETWORKS WITH A 3-WIRE CONNECTION�
Measurement system: 3-3Ph
VL1 VL2
VL3
L1
L2
L3
V
L3
L2
V
L1
V
VL1 VL2 VL3
a
b
A
B
a
b
A B
CARGA / LOAD
12
11
10
S1 S2 S1
S2
S1
S2
S1
S2
P1
P2
S1 S2
P1
P2
S1
S2
P1
P2
1 2
3 4
5 6
Alimentación Auxiliar
Power Supply
Figure 7: Three-Phase measuring with a 3-wire connection�
To guarantee the insulation of the device and its category, it is nec­essary to earth the S2 terminals of the transformers.
13
Instruction Manual
3�5�3�- MEASURING THREE-PHASE NETWORKS WITH A 3-WIRE CONNECTION AND
TRANSFORMERS WITH AN ARON CONNECTION
Measurement system: 3-ArOn
VL1 VL2
VL3
L1
L2
L3
V
L3
L2
V
L1
V
VL1 VL2 VL3
a
b
A
B
a
b
A B
CARGA / LOAD
12
11
10
Alimentación Auxiliar
Power Supply
S1 S2 S1
S2
S1
S2
S1
S2
P1
P2
S1
S2
P1
P2
1 2
3 4
5 6
Figure 8: Three-Phase measuring with a 3-wire connection and transformers with an ARON connection�
To guarantee the insulation of the device and its category, it is nec­essary to earth the S2 terminals of the transformers.
14
Instruction Manual
3�5�4�- MEASURING TWO-PHASE NETWORKS WITH A 3-WIRE CONNECTION
Measurement system: 3-2Ph
VL1 VL2
N
L1
L2
N
N
L2
V
L1
V
VL1 N VL2
a
b
A
B
a
b
A B
CARGA / LOAD
13
11
10
Alimentación Auxiliar
Power Supply
S1 S2 S1
S2
S1
S2
S1 S2
P1
P2
S1
S2
P1
P2
1 2
3 4
5 6
Figure 9: Measuring Two-Phase Networks with a 3-wire connection�
To guarantee the insulation of the device and its category, it is nec­essary to earth the S2 terminals of the transformers.
15
Instruction Manual
3�5�5�- MEASURING SINGLE-PHASE NETWORKS, PHASE TO PHASE, WITH A 2-WIRE
CONNECTION�
Measurement system: 2-2Ph
VL1 VL2
L1
L2
L2
V
L1
V
VL1 VL2
a
b
A B
CARGA / LOAD
11
10
Alimentación Auxiliar
Power Supply
S1 S2 S1
S2
S1
S2
S1
S2
P1
P2
1 2
3 4
5 6
Figure 10: Measuring Single-Phase Networks, phase to phase, with a 2-wire connection�
To guarantee the insulation of the device and its category, it is nec­essary to earth the S2 terminals of the transformers.
16
Instruction Manual
3�5�6�- MEASURING SINGLE-PHASE NETWORKS, PHASE TO NEUTRAL, WITH A 2-WIRE CONNECTION�
Measurement system: 2-1Ph
VL1 N
L1
N
N
L1
V
VL1 N
a b
A B
CARGA / LOAD
13
10
Alimentación Auxiliar
Power Supply
S1 S2 S1
S2
S1
S2
S1
S2
P1
P2
1 2
3 4
5 6
Figure 11: Measuring Single-Phase Networks, phase to neutral, with a 2-wire connection�
To guarantee the insulation of the device and its category, it is nec­essary to earth the S2 terminals of the transformers.
17
Instruction Manual
4�- OPERATION
The CVM-E3-MINI is a four-quadrant power analyzer (consumption and generation).
The device can operate according to three different measurement conventions:
CIRCUTOR measurement convention.
IEC measurement convention.
IEEE measurement convention.
The measurement convention is congured in the setup menu, see “6.6. MEASUREMENT CON-
VENTION”.
CIRCUTOR. measurement convention
90º
180º
-90º
Capacitive
Capacitive
Inductive
Inductive
Generation
Power
Consumption
Power
Single-phaseThree-phase
Single-phase
Single-phase
Single-phase
Three-phase
Three-phase
Three-phase
k k
k k k
k k
k k k
k
k
k
k
k
k k
k
k
k
Figure 12: CIRCUTOR measurement convention�
IEC measurement convention
Q
P
Q1Q2
Q3
Q4
P < 0 Q > 0 PF < 0
Capacitive
Capacitive
Inductive
Inductive
P < 0 Q < 0 PF < 0 P > 0 Q < 0 PF > 0
P > 0 Q > 0 PF > 0
Operation in the 4 quadrants (Q1, Q2, Q3, Q4)
0 +
0 +
cos φ > 0
cos φ > 0
Q1
Q4
+ 1 + 1
cos φ values in the receiver operating mode (Q1,Q4)
Figure 13:IEC measurement convention�
18
Instruction Manual
IEEE measurement convention
Q
P
Q1Q2
Q3
Q4
P < 0 Q > 0 PF > 0
Capacitive
Capacitive
Inductive
Inductive
P < 0 Q < 0 PF < 0 P > 0 Q < 0 PF > 0
P > 0 Q > 0 PF < 0
Operation in the 4 quadrants (Q1, Q2, Q3, Q4)
0 -
0 +
cos φ < 0
cos φ > 0
Q1
Q4
- 1 + 1
cos φ values in the receiver operating mode (Q1,Q4)
Figure 14:IEEE measurement convention�
4.1.- MEASURING PARAMETERS
The device displays the electrical parameters shown in Table 5.
Table 5: Measuring parameters of the CVM-E3-MINI
Parameter Units
Phases
L1-L2-L3
Total
III
Maxim�
value
Minim�
value
Phase-neutral voltage Vph-N
Phase-phase voltage Vph-ph
Current A
Frequency Hz
Active power M/kW
Apparent power M/kVA
Total Reactive Power M/kvar
Total Reactive Power - Consumption M/kvar
Total Reactive Power - Generation M/kvar
Total Inductive Reactive Power M/kvarL
Inductive Reactive Power - Consumption M/kvarL
Inductive Reactive Power - Generation M/kvarL
Total Capacitive Reactive Power M/kvarC
Capacitive Reactive Power - Consumption M/kvarC
Capacitive Reactive Power - Generation M/kvarC
Power factor PF
Cos φ φ
THD % Voltage % THD V
THD % Current % THD A
Harmonic Breakdown - Voltage (up to the 31st order harmonic)
harm V
19
Instruction Manual
Table 5 (Continuation) : Measuring parameters of the CVM-E3-MINI�
Parameter Units
Phases
L1-L2-L3
Total
III
Maxim�
value
Minim�
value
Harmonic Breakdown - Current (up to the 31st order harmonic)
harm V
Total Active Energy (Consumption and Generation)
M/kWh
(1)
Total Inductive Reactive Energy (Consumption and Generation)
M/kvarLh
(1)
Total Capacitive Reactive Energy (Consumption and Generation)
M/kvarCh
Total Apparent Energy (Consumption and Generation)
M/kVAh
Active Energy Tariff 1 (Consumption and Generation)
M/kWh
(1)
Inductive Reactive Energy Tariff 1 (Consumption and Generation)
M/kvarLh
(1)
Capacitive Reactive Energy Tariff 1 (Consumption and Generation)
M/kvarCh
Apparent Energy Tariff 1 (Consumption and Generation)
M/kVAh
Active Energy Tariff 2 (Consumption and Generation)
M/kWh
(1)
Inductive Reactive Energy Tariff 2 (Consumption and Generation)
M/kvarLh
(1)
Capacitive Reactive Energy Tariff 2 (Consumption and Generation)
M/kvarCh
Apparent Energy Tariff 2 (Consumption and Generation)
M/kVAh
Maximum Current Demand A
Maximum Demand of Active power M/kW
Maximum Demand of Apparent Power M/kVA
Maximum Demand of Inductive Power M/kvarL
Maximum Demand of Capacitive Power M/kvarC
Parameter Units Tariff: T1-T2 Total
No. of hours hours
Cost COST
CO2 Emissions kgCO
2
(1)
These variables are only displayed through communications, see Table 21�
20
Instruction Manual
4.2.- KEYBOARD FUNCTIONS
The CVM-E3-MINI has 3 keys that allow you to browse between the various screens and pro­gram the device.
Key functions on measuring screens (Table 6):
Table 6: Key functions on measuring screens�
Key Short keystroke Long keystroke (2 s)
Previous screen Display of minimum value
Next screen Display of maximum value
Browsing the different proles (analyzer, e3)
Accessing the programming menu
Display of the Maximum Demand
Unlocks the active alarm
Visualization of the status of the digi­tal input and output.
Display of device information screens.
Key functions on harmonics screens (Table 7):
Table 7: Key functions on harmonics screens�
Key Short keystroke Long keystroke (2 s)
Output of the harmonics screens
Next screen
Browsing the different types of harmonics Accessing the programming menu
Key functions on the programming menu, query mode (Table 8):
Table 8: Key functions on the programming menu, query mode�
Key Short keystroke Long keystroke (2 s)
Previous screen Programming output
Next screen Programming output
Entering and exiting the edit mode of the pro­gramming menu
21
Instruction Manual
Key functions on the programming menu, edit mode (Table 9):
Table 9: Key functions on the programming menu, edit mode�
Key Keystroke
Skips to the previous digit that can be edited (ashing)
Increases the digits (0-9) or rotates between the different options.
Skips to the next digit that can be edited (ashing)
4.3.- DISPLAY
The device has a backlit LCD display showing all the parameters listed in Table 5.
The display is divided into two areas (Figure 15):
Data area
States area
Figure 15: CVM-E3-MINI Display areas
The data area displays the values measured or calculated by the device.
The device states area shows the different states, profiles and information about the
unit (Table 10).
Table 10: Icons in the display�
Icon Description Icon Description
Facility status: ▼Facility consuming. ▲ Facility generating.
Instantaneous value
Operation prole e
3
Minimum value
Tariff : T1 Tariff 1, T2 Tariff 2 Programming screen
Maximum demand value
Programming menu:
Locked with a password. Unlocked.
Maximum value Communications activated
22
Instruction Manual
4.4.- LED INDICATORS
The CVM-E3-MINI device has 2 LEDs:
- CPU, indicates that the device is on, ashing each second.
- ALARM / ENERGY PULSES; if this is on, it indicates that an alarm or an energy pulses
output has been activated. In the case of the energy pulses, the LED will be lit and ash with the rate of these pulses.
CPU ALARM / ENERGY PULSES
Figure 16:LED Indicators of the CVM-E3-MINI�
4.5.- DIGITAL INPUT
The CVM-E3-MINI has one digital input (terminals S and 9 on Table 4) that can be programmed to operate as a logic or tariff selection input.
If congured as a logic input, the device displays the status of that input. See “6.18. OPERATING
MODE OF DIGITAL INPUT”
The selected tariff can be determined in accordance with the status of the inputs, as shown in
Table 11.
Table 11: Selecting the tariff in accordance with the input status�
IN1, Input 1
Tariff
Logic input Tariff selection
x T1
0 T1 1 T2
23
Instruction Manual
4.6.- DIGITAL OUTPUT
The device has one digital output, optoisolated NPN transistors (terminals 8 and 7 on Table 4),
fully programmable, see “6.17. PROGRAMMING ALARM : DIGITAL OUTPUT T1”
Press the keys to access the digital output status screen, see “5.4.- DIGITAL INPUT
AND OUTPUT STATUS SCREEN”
24
Instruction Manual
5�- DISPLAY
The CVM-E3-MINI has 2 operation proles. The display screens will be opened for the corre­sponding prole:
Analyzer prole, analyzer, Electrical energy efciency prole, e3,
Press the key to change from one operating prole to another.
5.1.- ANALYZER PROFILE
The device displays 15 different screens for the analyzer prole (Table 12) and the voltage and current harmonics, up to the 31st order harmonic, for each one of the lines, L1, L2 and L3. (“5.1.4.- HARMONICS”)
Use keys and to browse the different screens.
The inst symbol on the left of the screen indicates that the values being displayed are of the instantaneous type.
Table 12: Analyzer prole screens.
Screen Parameters (units)
phase-neutral Voltage L1 (V
ph-N
)
phase-neutral Voltage L2 (V
ph-N
)
phase-neutral Voltage L3 (V
ph-N
)
phase-phase Voltage L1-L2 (V
ph-ph
)
phase-neutral Voltage L2-L3 (V
ph-ph
)
phase-neutral Voltage L3-L1 (V
ph-ph
)
Medium phase-neutral Voltage
Medium phase-phase Voltage
Frequency (Hz)
25
Instruction Manual
Table 12 (Continuation) : Analyzer profile screens�
Screen Parameters (units)
Current L1 (A) Current L2 (A) Current L3 (A)
Active Power L1 (M/kW) Active Power L2 (M/kW) Active Power L3 (M/kW)
Apparent Power L1 (M/kVA) Apparent Power L2 (M/kVA) Apparent Power L3 (M/kVA)
Inductive Reactive Power L1 (M/kvarL) Inductive Reactive Power L2 (M/kvarL) Inductive Reactive Power L3 (M/kvarL)
Capacitive Reactive Power L1 (M/kvarC) Capacitive Reactive Power L2 (M/kvarC) Capacitive Reactive Power L3 (M/kvarC)
Active Power III (M/kW)
Apparent Power III (M/kVA)
Inductive Reactive Power III (M/kvarL)
26
Instruction Manual
Table 12 (Continuation) : Analyzer profile screens�
Screen Parameters (units)
Active Power III (M/kW)
Apparent Power III (M/kVA)
Capacitive Reactive Power III (M/kvarC)
Cos φ L1 (cos φ) Cos φ L2 (cos φ) Cos φ L3 (cos φ)
Power factor L1 (PF) Power factor L2 (PF) Power factor L3 (PF)
Power factor III (PF)
Cos φ III (cos φ)
THD % Voltage L1 (V THD %) THD % Voltage L2 (V THD %) THD % Voltage L3 (V THD %)
THD % Current L1 (A THD %) THD % Current L2 (A THD %) THD % Current L3 (A THD %)
Also displayed on these screens are:
Maximum values Minimum values Maximum Demand Harmonics
27
Instruction Manual
5�1�1�- MAXIMUM VALUES
To see the maximum values of the screen being displayed, press the key for 2 seconds.
These are displayed for 10 seconds.
Press the and keys to display all other maximum values.
The max symbol is shown on the display.
The maximum and minimum values are reset on the programming menu.(“6.10.- DELETING
MAXIMUM AND MINIMUM VALUES”)
5�1�2�- MINIMUM VALUES
To see the minimum values of the screen being displayed, press the key for 2 seconds.
These are displayed for 30 seconds.
Press the and . keys to display all other maximum values.
The min symbol is shown on the display.
The maximum and minimum values are reset on the programming menu. (“6.10.- DELETING
MAXIMUM AND MINIMUM VALUES”)
5�1�3�- MAXIMUM DEMAND
The device calculates the maximum demand of the following:
The Current of each phase.
Three-Phase Active Power.
Three-Phase Apparent Power.
Three-Phase inductive Power.
Three-Phase capacitive Power.
This value can be displayed on the display screen of the parameter by pressing the and
keys at the same time.
The dem symbol appears on the display.
Press keys or to stop displaying the maximum demand values.
The maximum demand values are reset on the programming menu: “6.9.- DELETING MAXIMUM
DEMAND”
5�1�4�- HARMONICS
The device can display the voltage and current harmonics, up to the 31st order harmonic, for
each one of the lines, L1, L2 and L3.
A minimum signal level is required to measure harmonics correctly, i.e., a signal level of at least
20 V is required to measure the voltage harmonics and of at least 200 mA to measure the cur-
rent harmonics. If the levels are lower, the unit will not calculate them and will display a value
of 0.
28
Instruction Manual
The harmonics display screens can be displayed by pressing the key shown after the last prole screen.
Harmonics are represented as shown in Figure 17. The gure shows the 15th voltage harmonic (H15).
Figure 17: 15th voltage harmonic�
The key jumps to the next harmonics screen.
Press the key to jump from the voltage harmonics to the current harmonics, and from the current harmonics to the home screen of the instantaneous values.
5�1�5�- DETECTION OF INCORRECT CONNECTION AND INCORRECT DIRECTION OF RO­TATION
Incorrect connection or disconnection
The device has a system for detecting the incorrect connection or disconnection of the voltage lines. If this error occurs, the device displays 0 on the lines with a voltage value of less than 50% of the line with the highest voltage value.
Incorrect direction of rotation
The device has a system for detecting the incorrect direction of rotation of the voltages. In other words, if each of the voltages has been correctly connected to the appropriate terminal, L1 to terminal 10, L2 to terminal 11 and L3 to terminal 12.
If there is an error in the direction of rotation, the icons L1, L2 and L3 ash on the display.
The device has a RS-485 communications parameter, which indicates whether an incorrect direction of rotation has been detected (7.3.6. DETECTION OF INCORRECT DIRECTION OF
ROTATION”)
Note: The detection of the direction of rotation is only enabled for measurement systems:
Three-phase network measurement (4-3Ph, 3-3Ph y 3-ArOn) and two-phase network meas­urement with 3-wire connection (3-2Ph).
29
Instruction Manual
5.2.- e3 PROFILE
The installation’s consumed and generated energy are displayed on the e3 prole of the device.
The installation status is also displayed:
Installation is consuming energy.
Installation is generating energy.
Long press (3 sec.) the or keys to jump from the generated values to the consumed
values displayed.
The generation values are identied with the negative sign on the screen, which appears in
front of each parameter.
Note : If the 2 quadrant option has been configured, only the consumed values can be
displayed.
This prole is identied with the e3 symbol on the left of the screen.
Use keys and to browse the different screens (short keystroke).
Table 13: Screens of the e3 prole.
Screen Parameters (units)
Total three-phase active Energy
(2)
(kWh)
Total three-phase Apparent Energy
(2)
(kVAh)
Total three-phase Inductive Reactive Energy
(2)
(kvarLh)
30
Instruction Manual
Table 13 (Continuation) : Screens of the e3 profile�
Screen Parameters (units)
Total three-phase Capacitive Reactive Energy
(2)
(kvarCh)
Total Cost
(2)
(cost)
Total CO2 Emissions
(2)
(kgCO2)
Total No. of hours
(2)
(hours)
Three-phase Active Energy Tariff 1 (kWh)
Three-phase Apparent Energy Tariff 1 (kVAh)
31
Instruction Manual
Table 13 (Continuation) : Screens of the e3 profile�
Screen Parameters (units)
Three-phase Inductive Reactive Energy Tariff 1
(kvarLh)
Three-phase Capacitive Reactive Energy Tariff 1
(kvarCh)
Cost Tariff 1 (cost)
CO2 Emissions Tariff 1 (kgCO2)
No. of hours Tariff 1 (hours)
Three-phase Active Energy Tariff 2 (kWh)
32
Instruction Manual
Table 13 (Continuation) : Screens of the e3 profile�
Screen Parameters (units)
Three-phase Apparent Energy Tariff 2 (kVAh)
Three-phase Inductive Reactive Energy Tariff 2
(kvarLh)
Three-phase Capacitive Reactive Energy Tariff 2
(kvarCh)
Cost Tariff 2 (cost)
CO2 Emissions Tariff 2 (kgCO2)
No. of hours Tariff 2 (hours)
(2)
Total = Tariff 1 + Tariff 2.
Symbols T1 and T2 on the display indicate the two tariffs available on the device. The symbol will flash if the current tariff is displayed. If the Total tariff is displayed ( = Tariff 1 + Tariff 2), symbols T1 and T2 will remain disabled.
33
Instruction Manual
5.3.- DEVICE INFORMATION SCREENS
Press the keys at the same time on any display screen to open the device infor-
mation screens, with the version and serial number of the device (Figure 18).
. .
Figure 18: Device information screens�
5.4.- DIGITAL INPUT AND OUTPUT STATUS SCREEN
Press the keys at the same time on any display screen to show the status of the de-
vice’s digital inputs and outputs (Figure 19)
Figure 19: Digital input and output status screen�
The Out parameter indicates the status of the digital output: 0: Output not activated
1: Output activated.
The In parameter indicates the status of the digital input.
If it has been congured as a logical input: 0: Input not activated
1: Input activated.
If it has been congured as a tariff selection: T1: Tariff 1 selected.
T2: Tariff 2 selected.
34
Instruction Manual
6�- CONFIGURATION
To enter the conguration menu press the key for 3 seconds.
If the icon appears on the conguration screen, the conguration parameters can be edited. If the icon appears, the conguration of the unit will be locked with a password (“6.21.-
LOCKING THE PROGRAMMING”); when the user tries to edit the value using the , key, the
screen in Figure 20 ill be displayed, in which the user must enter the password to unlock.
Figure 20: Password screen�
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the password, press the key if you are on the last digit or the key if you are on the rst digit.
Default password: 1234.
The conguration parameters can be modied after entering the correct password.
35
Instruction Manual
6.1.- PRIMARY VOLTAGE
On this screen the voltage transformer primary is programmed.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed
value will be deleted and the system will restore it to the last saved value.
Maximum programming value: 99999.
Minimum programming value: 1.
Voltage ratio ≤ 1000.
Voltage ratio x Primary Current ≤ 300000.
Note: The ratio is the relation between the primary and the secondary.
Press key to access the next programming step.
6.2.- SECONDARY VOLTAGE
On this screen the voltage transformer secondary is programmed.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
36
Instruction Manual
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed value will be deleted and the system will restore it to the last saved value.
Maximum programming value: 999. Minimum programming value: 1. Voltage ratio ≤ 1000. Voltage ratio x Primary Current ≤ 300000.
Press key to access the next programming step.
6.3.- PRIMARY CURRENT
The current transformer primary is programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed value will be deleted and the system will restore it to the last saved value.
Maximum programming value: 10000. Minimum programming value: 1. Voltage ratio x Current ratio ≤ 300000.
Note: The ratio is the relation between the primary and the secondary.
Press key to access the next programming step.
37
Instruction Manual
6.4.- SECONDARY CURRENT
On this screen the current transformer secondary is selected.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Voltage ratio x Primary Current ≤ 300000.
Use the key to browse the available options: 1A o 5A.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
6.5.- NUMBER OF QUADRANTS
The quadrant number on which the device takes the measurement is selected on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Use the key to browse the available options: 2 or 4 quadrants.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
38
Instruction Manual
6.6.- MEASUREMENT CONVENTION
You can select the measurement convention of the device from this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
The key is used to browse the different options:
Cir Circutor measurement convention.
IEC IEC measurement convention.
IEEE IEEE measurement convention.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
6.7.- MEASUREMENT SYSTEM
The measurement system is selected on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
The key is used to browse the different options
4-3Ph Three-phase network measurement with a 4-wire connection. 3-3Ph Three-phase network measurement with a 3-wire connection.
3-ArOn Three-phase network measurement with a 3-wire connection and transformers with an ARON connection .
3-2Ph Two-phase network measurement with a 3-wire connection. 2-2Ph Single-phase network measurement, phase to phase, with a 2-wire connection. 2-1Ph Single-phase network measurement, phase to neutral, with a 2-wire connection.
39
Instruction Manual
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
6.8.- MAXIMUM DEMAND INTEGRATION PERIOD
The maximum demand integration period is programmed in minutes on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed
value will be deleted and the system will restore it to the last saved value.
Maximum programming value: 60.
Minimum programming value: 0.
Note: Programming the value 0 disables the calculation of the maximum demand.
Press key to access the next programming step.
40
Instruction Manual
6.9.- DELETING MAXIMUM DEMAND
On this screen you select whether or not to delete the maximum demand.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Use the key to browse the available options: Yes or No.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Select Yes to force the device to automatically delete all maximum demand data; the No option will be displayed again on the screen.
Press key to access the next programming step.
6.10.- DELETING MAXIMUM AND MINIMUM VALUES
On this screen you select whether or not to delete the maximum and minimum values
Ç
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Use the key to browse the available options: Yes or No.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Select Yes to force the device to automatically delete all maximum and minimum values; the No option will be displayed again on the screen.
Press key to access the next programming step.
41
Instruction Manual
6.11.- DELETING ENERGY VALUES
On this screen you select whether or not to delete the energy, cost, CO2 emissions and No. of
hours values
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Use the key to browse the available options: Yes or No.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Select Yes to force the device to automatically delete all values; the No option will be displayed
again on the screen.
Press key to access the next programming step.
6.12.- ACTIVATING THE HARMONICS DISPLAY SCREEN.
This screen is used to select whether harmonics are displayed or not.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Use the key to browse the available options: Yes or No.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
42
Instruction Manual
6.13.- kgC02 CARBON EMISSION RATIO OF CONSUMED ENERGY
The carbon emissions ratio is the amount of emissions released into the atmosphere to produce a unit of electricity (1 kWh). The ratio for the European mix is approximately 0.65 kgCO2 per kWh.
This screen is used to programme the carbon emissions ratio for consumed energy, using the 2 tariffs congured for the device: T1 on the top line and T2 on the bottom line.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed value will be deleted and the system will restore it to the last saved value.
Maximum programming value: 1.9999. Minimum programming value: 0.
Press key to access the next programming step.
43
Instruction Manual
6.14.- kgC02 CARBON EMISSION RATIO OF GENERATED ENERGY
The carbon emissions ratio is the amount of emissions released into the atmosphere to produce
a unit of electricity (1 kWh).
The ratio for the European mix is approximately 0.65 kgCO2 per kWh.
This screen is used to programme the carbon emissions ratio for generated energy, using the
2 tariffs congured for the device: T1 on the top line and T2 on the bottom line.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed
value will be deleted and the system will restore it to the last saved value.
Maximum programming value: 1.9999.
Minimum programming value: 0.
Press key to access the next programming step.
6.15.- COST RATIO OF CONSUMED ENERGY
This screen is used to programme the cost per kWh of electricity for consumed energy, using
the 2 tariffs congured for the device: T1 on the top line and T2 on the bottom line.
44
Instruction Manual
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed value will be deleted and the system will restore it to the last saved value.
Maximum programming value: 1.9999. Minimum programming value: 0.
Press key to access the next programming step.
6.16.- COST RATIO OF GENERATED ENERGY
This screen is used to programme the cost per kWh of electricity for generated energy, using the 2 tariffs congured for the device: T1 on the top line and T2 on the bottom line.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed value will be deleted and the system will restore it to the last saved value.
Maximum programming value: 1.9999. Minimum programming value: 0.
Press key to access the next programming step.
45
Instruction Manual
6.17.- PROGRAMMING ALARM : DIGITAL OUTPUT T1
The values corresponding to digital output T1 are programmed in this step.
The code of the variable is selected on this screen, according to Table 14, Table 15 and Table
16, which will control digital output T1.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
Set the value to 00 if you do not wish to program a variable.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
If an incorrect code has been entered, the value will be deleted and the device will restore the
last value saved.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Table 14: Parameter codes used to program the digital output (Table 1)�
Parameter Phase Code Phase Code Phase Code Phase Code
Phase-Neutral Voltage L1 01 L2 09 L3 17 - ­Current L1 02 L2 10 L3 18 - ­Active power L1 03 L2 11 L3 19 III 25 Inductive Reactive Power L1 04 L2 12 L3 20 III 26 Capacitive Reactive Power L1 05 L2 13 L3 21 III 27 Apparent power L1 06 L2 14 L3 22 III 28 Power factor L1 07 L2 15 L3 23 III 29 Cosine φ L1 08 L2 16 L3 24 III 30 % THD V L1 36 L2 37 L3 38 - ­% THD A L1 39 L2 40 L3 41 - ­Phase-Phase Voltage L1/2 32 L2/3 33 L3/1 34 - ­Frequency - 31 - - - - - ­Maximum current demand L1 45 L2 46 L3 47 - ­Active Power Maximum
Demand
- - - - - - III 42
46
Instruction Manual
Table 14 (Continuation) : Parameter codes used to program the digital output (Table 1)�
Parameter Phase Code Phase Code Phase Code Phase Code
Apparent Power Maximum Demand
- - - - - - III 43
Inductive Power Maximum Demand
- - - - - - III 132
Capacitive Power Maximum Demand
- - - - - - III 133
In addition, there are some parameters (Table 14) that refer to the three phases at the same time (OR function). If you have selected one of these variables, the alarm will be activated when any of the three phases meets the programmed conditions.
Table 15:Parameter codes used to program the digital output (Table 2)�
Types of parameters Code
Phase-Neutral Voltage 200 Current 201 Active power 202 Inductive Reactive Power 203 Capacitive Reactive Power 204 Power factor 205 Phase-Phase Voltage 206 % THD V 207 % THD A 208 Apparent Power 209
Table 16: Parameter codes used to program the digital output (energy pulses) (Table 3)�
Parameter Tariff Code Tariff Code Tariff Code
Consumed active energy T1 49 T2 70 total 112 Generated active energy T1 59 T2 80 total 122 Consumed inductive reactive energy T1 51 T2 72 total 114 Generated inductive reactive energy T1 61 T2 82 total 124 Consumed capacitive reactive energy T1 53 T2 74 total 116 Generated capacitive reactive energy T1 63 T2 84 total 126 Consumed apparent energy T1 55 T2 76 total 118 Generated apparent energy T1 65 T2 86 total 128
Press key to access the next programming step.
If a parameter has been selected from Table 14 or Table 15, the next setup screen will be shown in section “6.17.1. MAXIMUM VALUE”
If a parameter has been selected from Table 16, the next setup screen will be shown in section
“6.17.8. KILOWATTS PER PULSE”
47
Instruction Manual
6�17�1� MAXIMUM VALUE
This screen is used to programme the maximum value, i.e., the value above which the alarm
will be activated.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
Note: The device allows the user to congure negative values. To do so, increase the rst digit
to a value higher than 9.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
Note: Pay special attention when programming the Generation Power (displayed with
negative values).
Example: If you wish to enter a generation power alarm with limits between 2 kW and 1 kW,
program the following as the maximum value : - 1 kW and the following as the minimum
value : - 2 kW.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
6�17�2� MINIMUM VALUE
This screen is used to programme the minimum value, i.e., the value under which the alarm
will be activated.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
Note: The device allows the user to congure negative values. To do so, increase the rst digit
48
Instruction Manual
to a value higher than 9.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
Note: Pay special attention when programming the Generation Power (displayed with negative values). Example: If you wish to enter a generation power alarm with limits between 2 kW and 1 kW, program the following as the maximum value : - 1 kW and the following as the minimum value : - 2 kW.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
6�17�3� CONNECTION TIME DELAY
The alarm connection delay is programmed on this screen in seconds.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Maximum programming value: 999. Minimum programming value: 0.
Press key to access the next programming step.
49
Instruction Manual
6�17�4� HYSTERESIS VALUE
The hysteresis value, i.e., difference between the alarm connection and disconnection value,
in %, is programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Maximum programming value: 99.
Minimum programming value: 0.
Press key to access the next programming step.
6�17�5� LATCH
The interlocking is selected on this screen, i.e., if the alarm is interlocked after it has been
tripped, even when the condition that triggered it has disappeared.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Use the key to browse the available options: Yes or No.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
Note: If the device is reset, the status of alarms is deleted and all alarms will return to the
programmed standby status, provided that the condition that triggered them has been resolved.
50
Instruction Manual
6�17�6� DISCONNECTION TIME DELAY
The alarm disconnection delay is programmed on this screen in seconds.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Maximum programming value: 999. Minimum programming value: 0.
Press key to access the next programming step.
6�17�7� CONTACT STATUS
The status of relay contacts is selected on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press key to browse the two options:
nO Normally open contact. nC Normally closed contact.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
51
Instruction Manual
6�17�8� KILOWATTS PER PULSE
Note: This screen is displayed if the alarm parameter has been selected from an energy value,
see Table 16.
This screen is used to programme the kilowatts per pulse.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
Maximum programming value: 999.99 kWh
Minimum programming value: 000.01 kWh
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed
value will be deleted and the system will restore it to the last saved value.
Press key to access the next programming step.
6�17�9� PULSE WIDTH
Note: This screen is displayed if the alarm parameter has been selected from an energy value,
see Table 16.
The width of the pulse is selected on this screen in ms.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
52
Instruction Manual
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
Maximum programming value: 500 ms. Minimum programming value: 30 ms.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed value will be deleted and the system will restore it to the last saved value.
Press key to access the next programming step.
6.18.- OPERATING MODE OF DIGITAL INPUT
The function of digital input 1 is selected on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press key to browse the two options:
lOGIC Logic input
tARIF Tariff selection.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
53
Instruction Manual
6.19.- BACKLIGHT, TURNING ON THE BACKLIT DISPLAY
This screen is used to programme the maximum brightness time of the display since the device
was last used with the keypad. After this time, the display will reduce the brightness level.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
Maximum programming value: 999 seconds.
Minimum programming value: 1 second.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed
value will be deleted and the system will restore it to the last saved value.
Press key to access the next programming step.
6.20.- RS-485 COMMUNICATIONS
The RS-485 communications protocol is selected on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
54
Instruction Manual
Press key to browse the two options:
nodb Modbus bacn BACnet.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
Note: The device will restart after exiting the setup menu if the RS-485 communications
parameters have been modied.
If the Modbus protocol has been selected, the next setup screen will be shown in section
“6.20.1. MODBUS PROTOCOL: BAUD RATE”
If the BACnet protocol has been selected, the next setup screen will be shown in section
“6.20.6.- BACnet PROTOCOL: BAUD RATE”
6�20�1�- MODBUS PROTOCOL: BAUD RATE
The baud rate of modbus communications is programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press key to browse the options: 9600, 19200, 38400 or 57600 bps.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
55
Instruction Manual
6�20�2�- MODBUS PROTOCOL: PERIPHERAL NUMBER
The peripheral number is programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
Maximum programming value: 255.
Minimum programming value: 1.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed
value will be deleted and the system will restore it to the last saved value.
Press key to access the next programming step.
6�20�3�- MODBUS PROTOCOL : PARITY
The type of parity of Modbus communications is selected on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press key to browse the options:
nonE no parity
Even even parity
odd odd parity
56
Instruction Manual
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
6�20�4�- MODBUS PROTOCOL : DATA BITS
The number of data bits of Modbus communications are programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press key to browse the options: 7 or 8 bits
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
6�20�5�- MODBUS PROTOCOL : STOP BITS
The number of Stop bits of Modbus communications are programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press key to browse the options: 1 or 2 bits
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
57
Instruction Manual
6�20�6�- BACnet PROTOCOL : BAUD RATE
The baud rate of BACnet communications is programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press key to browse the options: 9600, 19200 or 38400 bps.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Press key to access the next programming step.
6�20�7�- BACnet PROTOCOL : ID
The device ID is programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left
of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
Maximum programming value: 99999.
Minimum programming value: 0.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed
value will be deleted and the system will restore it to the last saved value.
Press key to access the next programming step.
58
Instruction Manual
6�20�8�- BACnet PROTOCOL : MAC ADDRESS
The MAC address is programmed on this screen.
Press the key for 3 seconds to enter the edit mode. The prog icon will ash on the left of the screen.
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit cursor.
Maximum programming value: 127. Minimum programming value: 0.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
If the value entered by the user is out of the range of programming values, the programmed value will be deleted and the system will restore it to the last saved value.
Press key to access the next programming step.
6.21.- LOCKING THE PROGRAMMING
This screen is for protecting the data congured in the programming menu.
Press the key for 3 seconds to enter the edit mode. The screen shown in Figure 21 will be displayed, in which the user must enter the locking password.
59
Instruction Manual
Figure 21: Password screen�
Press the key to modify the value of the ashing digit.
When the desired value is shown on the screen, use the and keys to move the edit
cursor.
To validate the value, press the key for 3 seconds; the prog icon will stop ashing.
Password value: 1234
The programming lock parameters can be modied after entering the correct password.
Use the key to browse the available options:
unLoC When you enter the programming menu you can view and modify the
programming. Icon on the display indicates the permanently locked status.
LoC When you enter the programming you can view the programming but not modify
it. Icon indicates the locking status. Enter the password to modify the programming values.
To validate the data, press for 3 seconds and the prog icon will disappear from the
display.
Press the key to enter the password for locking and unlocking the programming:
6�21�1�- PASSWORD
On this screen you enter the password for locking and unlocking the programming.
Press the key to modify the value of the ashing digit.
60
Instruction Manual
When the desired value is shown on the screen, use the and keys to move the edit cursor.
To validate the password, press the key if you are on the last digit or the key if you are on the rst digit.
Password value : 1234
This value may only be modied through communications. See “7.3.6.14. Password congura-
tion.”
61
Instruction Manual
7�- COMMUNICATIONS
The CVM-E3-MINI devices have one RS-485 communications port.
The device has as standard two communications protocols: MODBUS RTU ® and BACnet.
The protocol and conguration parameters are selected in the setup menu. (6.20.- RS-485
COMMUNICATIONS)
7.1.- CONNECTIONS
The RS -485 cable must be wired with twisted pair cable with mesh shield (minimum 3 wires),
with a maximum distance between the CVM-E3-MINI and the master device of 1200 metres.
A maximum of 32 CVM-E3-MINI devices can be connected to this bus.
Use an intelligent RS-232 to RS-485 network protocol converter to establish the
communications with the master device.
B(-)
A(+)
S
RS-232 / USB / Ethernet / Profibus ...
PC
RS-485
RS-485
RS-232 USB Ethernet Profibus ...
A(+)
B(-)
S
A(+) B(-)
S
A B S
A B S
Figure 22: RS-485 Connection diagram�
62
Instruction Manual
7.2.- MODBUS PROTOCOL
In the Modbus protocol, the CVM-E3-MINI device uses the RTU (Remote Terminal Unit) mode. The Modbus functions implemented in the device are as follows:
Function 0x03 and 0x04. Reading integer registers. Function 0x05. Writing a relay. Function 0x10. Writing multiple registers.
7�2�1�- READING EXAMPLE : Funtion 0x04�
Question: Instantaneous value of the phase voltage of L1
Address Function
Initial
register
No� of
registers
CRC
0A 04 0000 0002 70B0
Address: 0A, Peripheral number: 10 in decimals. Function: 04, Read function. Initial Register: 0000, register on which the reading will start. No� of registers: 0002, number of registers read. CRC: 70B0, CRC Character.
Response:
Address Function
No� of Bytes
Register
No� 1
Register
No� 2
CRC
0A 04 04 0000 084D 8621
Address: 0A, Responding peripheral number: 10 in decimals. Function: 04, Read function. No� of bytes: 04, No. of bytes received. Register: 0000084D, value of the phase voltage of L1: VL1 x 10 : 212.5V CRC: 8621, CRC Character.
Note : Every Modbus frame has a maximum limit of 20 variables (40 logs).
7�2�2�- WRITING EXAMPLE : Funtion 0x05�
Question: Deleting maximum and minimum values.
Address Function
Initial
Register
Value CRC
0A 05 0834 FF00 CEEF
Address: 0A, Peripheral number: 10 in decimal.
Function: 05, Read function.
Initial register: 0834, register of the parameter for deleting maximum and minimum
values.
Value: FF00, we indicate that we want to delete the maximum and minimum values.
CRC: CEEF, CRC character.
63
Instruction Manual
Response:
Address Function
Initial
register
Value CRC
0A 05 0834 FF00 CEEF
7.3.- MODBUS COMMANDS
Two different memory maps have been implemented for the Measurement, Energy and Voltage
and Current harmonics variables. However, they have the same functions:
Map 1, uses the addresses of the CVM-MINI device, entering the addresses of the new parameters measured by this new device.
Map 2, uses the addresses of the CVM-C10 device (adding 0x1000 to all addresses). Except for 3 parameters, the CVM-C10 and the CVM-E3-MINI use the same parameters.
Map 2 should be used if a Modbus map is going to be implemented from scratch. However,
if the map is already being used in another device, use Map 1 for CVM-MINI and Map 2 for
CVM-C10.
7�3�1� MEASUREMENT VARIABLES
All the adresses of Modbus memory are in Hexadecimal.
For these variables is implemented the Function 0x03 and 0x04�
Table 17: Modbus memory Map 1: Measurement variables
Map 1
Parameter Symbol Instantaneous Maximum Minimum Units
L1 Phase voltage V 1 00-01 60-61 C0-C1 V x 10
L1 Current A 1 02-03 62-63 C2-C3 mA L1 Active Power kW 1 04-05 64-65 C4-C5 W L1 Inductive Power kvarL 1 12C-12D 13E-13F 150-151 var L1 Capacitive Power kvarC 1 12E-12F 140-141 152-153 var
L1 Apparent Power kVA 1 4A-4B AA-AB 10A-10B VA
L1 Power Factor PF 1 08-09 68-69 C8-C9 x 100
Cos φ L1 Cos φ 1 130-131 142-143 154-155 x 100
L2 Phase voltage V 2 0A-0B 6A-6B CA-CB V x 10
L2 Current A 2 0C-0D 6C-6D CC-CD mA L2 Active Power kW 2 0E-0F 6E-6F CE-CF W L2 Inductive Power kvarL 2 132-133 144-145 156-157 var L2 Capacitive Power kvarC 2 134-135 146-147 158-159 var
L2 Apparent Power kVA 2 4C-4D AC-AD 10C-10D VA
L2 Power Factor PF 2 12-13 72-73 D2-D3 x 100
Cos φ L2 Cos φ 2 136-137 148-149 15A-15B x 100
L3 Phase voltage V 3 14-15 74-75 D4-D5 V x 10
L3 Current A 3 16-17 76-77 D6-D7 mA L3 Active Power kW 3 18-19 78-79 D8-D9 W L3 Inductive Power kvarL 3 138-139 14A-14B 15C-15D var
64
Instruction Manual
Table 17 (Continuation) : Modbus memory Map 1: Measurement variables
Mapa 1
Parameter Symbol Instantaneous Maximum Minimum Units
L3 Capacitive Power kvarC 3 13A-13B 14C-14D 15E-15F var
L3 Apparent Power kVA 3 4E-4F AE-AF 10E-10F VA
L3 Power Factor PF 3 1C-1D 7C-7D DC-DD x 100
Cos φ L3 Cos φ 3 13C-13D 14E-14F 160-161 x 100 Three-phase Active Power kW III 1E-1F 7E-7F DE-DF W Three-phase Inductive power kvarL III 20-21 80-81 E0-E1 var
Three-phase Capacitive Power kvarC III 22-23 82-83 E2-E3 var
Three-phase Apparent power kVA III 42-43 A2-A3 102-103 VA
Three-phase Power Factor PF III 24-25 84-85 E4-E5 x100
Three-phase Cos φ Cos φ III 26-27 86-87 E6-E7 x100
L1 Frequency Hz 28-29 88-89 E8-E9 Hz x100
L1-L2 Voltage V12 2A-2B 8A-8B EA-EB V x 10
L2-L3 Voltage V23 2C-2D 8C-8D EC-ED V x 10
L3-L1 Voltage V31 2E-2F 8E-8F EE-EF V x 10
Neutral Current N A N 48-49 A8-A9 108-109 mA
% L1 voltage THD %THDV1 30-31 90-91 F0-F1 % x 10
% L2 voltage THD %THDV2 32-33 92-93 F2-F3 % x 10
% L3 voltage THD %THDV3 34-35 94-95 F4-F5 % x 10
% L1 current THD %THDI1 36-37 96-97 F6-F7 % x 10
% L2 current THD %THDI2 38-39 98-99 F8-F9 % x 10
% L3 current THD %THDI3 3A-3B 9A-9B FA-FB % x 10 Maximum demand kW III Md(Pd) 162-163 16A-16B - W
Maximum demand kVA III Md(Pd) 164-165 16C-16D - VA Maximum demand kvarL III Md(Pd) 166-167 16E-16F - var Maximum demand kvarC III Md(Pd) 168-169 170-171 - var
Maximum demand I L1 Md(Pd) 44-45 A4-A5 - mA
Maximum demand I L2 Md(Pd) 52-53 B2-B3 - mA
Maximum demand I L3 Md(Pd) 54-55 B4-B5 - mA
Table 18: Modbus memory Map 2: Measurement variables
Map 2
Parameter Symbol Instantaneous Maximum Minimum Units
L1 Phase voltage V 1 1000-1001 1106-1107 1164-1165 V x 10
L1 Current A 1 1002-1003 1108-1109 1166-1167 mA L1 Active Power kW 1 1004-1005 110A-110B 1168-1169 W L1 Inductive Power kvarL 1 1006-1007 110C-110D 116A-116B var L1 Capacitive Power kvarC 1 1008-1009 110E-110F 116C-116D var
L1 Apparent Power kVA 1 100A-100B 1110- 1111 116E-116F VA
L1 Power Factor PF 1 100C-100D 1112-1113 1170-1171 x 100
Cos φ L1 Cos φ 1 100E-100F 1114 -1115 1172-1173 x 100
L2 Phase voltage V 2 1010-1011 1116- 111 7 1174-1175 V x 10
L2 Current A 2 1012-1013 1118 - 1119 1176-1177 mA L2 Active Power kW 2 1014-1015 111A-111B 1178-1179 W L2 Inductive Power kvarL 2 1016-1017 111C- 111 D 117A-117B var L2 Capacitive Power kvarC 2 1018-1019 111 E - 111F 117C-117D var
65
Instruction Manual
Tabla 18 (Continuation) : Modbus memory Map 2: Measurement variables
Map 2
Parameter Symbol Instantaneous Maximum Minimum Units
L2 Apparent Power kVA 2 101A-101B 1120-1121 117E-117F VA
L2 Power Factor PF 2 101C-101D 1122-1123 1180-1181 x 100
Cos φ L2 Cos φ 2 101E-101F 1124-1125 1182-1183 x 100
L3 Phase voltage V 3 1020-1021 1126-1127 1184-1185 V x 10
L3 Current A 3 1022-1023 1128-1129 1186-1187 mA L3 Active Power kW 3 1024-1025 112A-112B 1188-1189 W L3 Inductive Power kvarL 3 1026-1027 112C-112D 118A-118B var L3 Capacitive Power kvarC 3 1028-1029 112E-112F 118C-118D var
L3 Apparent Power kVA 3 102A-102B 1130-1131 118E-118F VA
L3 Power Factor PF 3 102C-102D 1132-1133 1190-1191 x 100
Cos φ L3 Cos φ 3 102E-102F 1134-1135 1192-1193 x 100 Three-phase Active Power kW III 1030-1031 1136-1137 1194-1195 W Three-phase Inductive power kvarL III 1032-1033 1138-1139 1196-1197 var
Three-phase Capacitive Power kvarC III 1034-1035 113A-113B 1198-1199 var
Three-phase Apparent power kVA III 1036-1037 113C-113D 119A-119B VA
Three-phase Power Factor PF III 1038-1039 113E-113F 119C-119D x100
Three-phase Cos φ Cos φ III 103A-103B 1140-1141 119E-119F x100
L1 Frequency Hz 103C-103D 1142-1143 11A0-11A1 Hz x100
L1-L2 Voltage V12 103E-103F 1144-1145 11A2-11A3 V x 10
L2-L3 Voltage V23 1040-1041 1146-1147 11A4-11A5 V x 10
L3-L1 Voltage V31 1042-1043 1148-1149 11A6-11A7 V x 10
Neutral Current N A N 1044-1045 114A-114B 11A8-11A9 mA
% L1 voltage THD %THDV1 1046-1047 114C-114D 11AA-11AB % x 10
% L2 voltage THD %THDV2 1048-1049 114E-114F 11AC-11AD % x 10
% L3 voltage THD %THDV3 104A-104B 1150-1151 11AE-11AF % x 10
% L1 current THD %THDI1 104C-104D 1152-1153 11B0-11B1 % x 10
% L2 current THD %THDI2 104E-104F 1154-1155 11B2-11B3 % x 10
% L3 current THD %THDI3 1050-1051 1156-1157 11B4-11B5 % x 10 Maximum demand kW III Md(Pd) 1052-1053 1158-1159 - W
Maximum demand kVA III Md(Pd) 1054-1055 115A-115B - VA Maximum demand kvarL III Md(Pd) 1200-1201 1204-1205 - var Maximum demand kvarC III Md(Pd) 1202-1203 1206-1207 - var
Maximum demand I L1 Md(Pd) 1058-1059 115E-115F - mA
Maximum demand I L2 Md(Pd) 105A-105B 1160-1161 - mA
Maximum demand I L3 Md(Pd) 105C-105D 1162-1163 - mA
66
Instruction Manual
7�3�2� ENERGY VARIABLES
All the adresses of Modbus memory are in Hexadecimal. For these variables is implemented the Function 0x03 and 0x04�
Table 19: Modbus memory Map 1: Energy variables
Map 1
Parameter Symbol Tariff 1 Tariff 2 Total Units
Consumed active energy III (kWh) kWh III 18C-18D 1B6-1B7 3C-3D kWh Consumed active energy III (Wh) kWh III 18E-18F 1B8-1B9 172-173 Wh Consumed inductive reactive energy III
(kvarhL)
kvarhL III 190-191 1BA-1BB 3E-2F kvarh
Consumed inductive reactive energy III (varhL)
kvarhL III 192-193 1BC-1BD 174-175 varh
Consumed capacitive reactive energy III (kvarhC)
kvarhC III 194-195 1BE-1BF 40-41 kvarh
Consumed capacitive reactive energy III (varhC)
kvarhC III 196-197 1C0-1C1 176-176 varh
Consumed apparent energy III (kVAh) kVAh III 198-199 1C2-1C3 56-57 kVAh
Consumed apparent energy III (VAh) kVAh III 19A-19B 1C4-1C5 178-179 VA h
Consumed CO2 emissions KgCO
2
19C-19D 1C6-1C7 182-183 x10
Consumption cost $ 19E-19F 1C8-1C9 184-185 x10 Generated active energy III (kWh) kWh III 1A0-1A1 1CA-1CB 58-59 kWh Generated active energy III (Wh) kWh III 1A2-1A3 1CC-1CD 17A-17B Wh Generated inductive reactive energy III
(kvarhL)
kvarhL III 1A4-1A5 1CE-1CF 5A-5B kvarh
Generated inductive reactive energy III (varhL)
kvarhL III 1A6-1A7 1D0-1D1 17C-17D varh
Generated capacitive reactive energy III (kvarhC)
kvarhC III 1A8-1A9 1D2-1D3 5C-5D kvarh
Generated capacitive reactive energy III (varhC)
kvarhC III 1AA-1AB 1D4-1D5 17E-17F varh
Generated apparent energy III (kVAh) kVAh III 1AC-1AD 1D6-1D7 5E-5F kVAh
Generated apparent energy III (VAh) kVAh III 1AE-1AF 1D8-1D9 180-181 VAh
Generated CO2 emissions KgCO
2
1B0-1B1 1DA-1DB 186-187 x10
Generation Cost $ 1B2-1B3 1DC-1DD 188-189 x10 Hours per tariff Hours 1B4-1B5 1DE-1DF 18A-18B seg
Table 20: Modbus memory Map 2: Energy variables
Map 2
Parameter Symbol Tariff 1 Tariff 2 Total Units
Consumed active energy III (kWh) kWh III 105E-105F 1088-1089 10DC-10DD kWh Consumed active energy III (Wh) kWh III 1060-1061 108A-108B 10DE-10DF Wh Consumed inductive reactive energy III
(kvarhL)
kvarhL III 1062-1063 108C-108D 10E0-10E1 kvarh
Consumed inductive reactive energy III (varhL)
kvarhL III
1064-1065 108E-108F 10E2-10E3 varh
Consumed capacitive reactive energy III (kvarhC)
kvarhC III
1066-1067 1090-1091 10E4-10E5 kvarh
Consumed capacitive reactive energy III (varhC)
kvarhC III
1068-1069 1092-1093 10E6-10E7 varh
Consumed apparent energy III (kVAh) kVAh III 106A-106B 1094-1095 10E8-10E9 kVAh
67
Instruction Manual
Table 20 (Continuation) : Modbus memory Map 2: Energy variables
Map 2
Parameter Símbolo Tariff 1 Tariff 2 Total Units
Consumed apparent energy III (VAh) kVAh III 106C-106D 1096-1097 10EA-10EB VA h
Consumed CO2 emissions KgCO
2
106E-106F 1098-1099 10EC-10ED x10
Consumption cost $ 1070-1071 109A-109B 10EE-10EF x10 Generated active energy III (kWh) kWh III 1072-1073 109C-109D 10F0-10F1 kWh Generated active energy III (Wh) kWh III 1074-1075 109E-109F 10F2-10F3 Wh Generated inductive reactive energy III
(kvarhL)
kvarhL III
1076-1077 10A0-10A1 10F4-10F5 kvarh
Generated inductive reactive energy III (varhL)
kvarhL III
1078-1079 10A2-10A3 10F6-10F7 varh
Generated capacitive reactive energy III (kvarhC)
kvarhC III
107A-107B 10A4-10A5 10F8-10F9 kvarh
Generated capacitive reactive energy III (varhC)
kvarhC III
107C-107D 10A6-10A7 10FA-10FB varh
Generated apparent energy III (kVAh) kVAh III 107E-107F 10A8-10A9 10FC-10FD kVAh
Generated apparent energy III (VAh) kVAh III 1080-1081 10AA-10AB 10FE-10EF VAh
Generated CO2 emissions KgCO
2
1082-1083 10AC-10AD 1100-1101 x10
Generation Cost $ 1084-1085 10AE-10AF 1102-1103 x10 Hours per tariff Hours 1086-1087 10B0-10B1 1104-1105 seg
Table 21: Modbus memory Map 1 and Map 2 (energy variables per phase)�
Map 1 and Map 2
Parameter Symbol L1 L2 L3 Units
Consumed active energy (kWh) T1 kWh 1400-1401 1460-1461 14C0-14C1 kWh Consumed active energy (Wh) T1 kWh 1402-1403 1462-1463 14C2-14C3 Wh
Consumed inductive reactive energy T1 (kvarhL)
kvarhL 1404-1405 1464-1465 14C4-14C5 kvarh
Consumed inductive reactive energy T1 (varhL)
kvarhL
1406-1407 1466-1467 14C6-14C7 varh
Generated active energy T1 (kWh) kWh 1410-1411 1470-1471 14D0-14D1 kWh Generated active energy T1 (Wh) kWh 1412-1413 1472-1473 14D2-14D3 Wh
Generated inductive reactive energy T1 (kvarhL)
kvarhL
1414-1415 1474-1475 14D4-14D5 kvarh
Generated inductive reactive energy T1 (varhL)
kvarhL
1416-1417 1476-1477 14D6-14D7 varh
Consumed active energy (kWh) T2 kWh 1420-1421 1480-1481 14E0-14E1 kWh Consumed active energy (Wh) T2 kWh 1422-1423 1482-1483 14E2-14E3 Wh
Consumed inductive reactive energy T2 (kvarhL)
kvarhL 1424-1425 1484-1485 14E4-14E5 kvarh
Consumed inductive reactive energy T2(varhL)
kvarhL
1426-1427 1486-1487 14E6-14E7 varh
Generated active energy T2 (kWh) kWh 1430-1431 1490-1491 14F0-14F1 kWh Generated active energy T2 (Wh) kWh 1432-1433 1492-1493 14F2-14F3 Wh
Generated inductive reactive ener­gyT2(kvarhL)
kvarhL 1434-1435 1494-1495 14F4-14F5 kvarh
Generated inductive reactive energy T2 (varhL)
kvarhL 1436-1437 1496-1497 14F6-14F7 varh
Consumed active energy (kWh) Total kWh 1440-1441 14A0-14A1 1500-1501 kWh
68
Instruction Manual
Table 21 (Continuation) : Modbus memory Map 1 and Map 2 (energy variables per phase)
Map 1 and Map 2
Parameter Symbol L1 L2 L3 Units
Consumed active energy (Wh) Total kWh 1442-1443 14A2-14A3 1502-1503 Wh
Consumed inductive reactive energy To­tal (kvarhL)
kvarhL 1444-1445 14A4-14A5 1504-1505 kvarh
Consumed inductive reactive energy To ­tal (varhL)
kvarhL 1446-1447 14A6-14A7 1506-1507 varh
Generated active energy Total (kWh) kWh 1450-1451 14B0-14B1 1510-1511 kWh Generated active energy Total (Wh) kWh 1452-1453 14B2-14B3 1512-1513 Wh
Generated inductive reactive energy To ­tal (kvarhL)
kvarhL 1454-1455 14B4-14B5 1514-1515 kvarh
Generated inductive reactive energy To ­tal (varhL)
kvarhL 1456-1457 14B6-14B7 1516-1517 varh
7�3�3� VOLTAGE AND CURRENT HARMONICS�
All the adresses of Modbus memory are in Hexadecimal. For these variables is implemented the Function 0x03 and 0x04�
Table 22: Modbus memory Map 1: Voltage Harmonics
Map 1
Parameter Voltage L1 Voltage L2 Voltage L3 Units
Fundamental Harm. 2AE-2AF 2CC-2CD 2EA-2EB V x 10
2nd Order harmonic 2B0-2B1 2CE-2CF 2EC-2ED % x 10
3rd Order harmonic 2B2-2B3 2D0-2D1 2EE-2EF % x 10
4th Order harmonic 2B4-2B5 2D2-2D3 2F0-2F1 % x 10
5th Order harmonic 2B6-2B7 2D4-2D5 2F2-2F3 % x 10
6th Order harmonic 2B8-2B9 2D6-2D7 2F4-2F5 % x 10
7th Order harmonic 2BA-2BB 2D8-2D9 2F6-2F7 % x 10
8th Order harmonic 2BC-2BD 2DA-2DB 2F8-2F9 % x 10
9th Order harmonic 2BE-2BF 2DC-2DD 2FA-2FB % x 10
10th Order harmonic 2C0-2C1 2DE-2DF 2FC-2FD % x 10
11th Order harmonic 2C2-2C3 2E0-2E1 2FE-2FF % x 10
12th Order harmonic 2C4-2C5 2E2-2E3 300-301 % x 10
13th Order harmonic 2C6-2C7 2E4-2E5 302-303 % x 10
14th Order harmonic 2C8-2C9 2E6-2E7 304-305 % x 10
15th Order harmonic 2CA-2CB 2E8-2E9 306-307 % x 10
16th Order harmonic 308-309 328-329 348-349 % x 10
17th Order harmonic 30A-30B 32A-32B 34A-34B % x 10
18th Order harmonic 30C-30D 32C-32D 34C-34D % x 10
19th Order harmonic 30E-30F 32E-32F 34E-34F % x 10
20th Order harmonic 310-311 330-331 350-351 % x 10
21st Order harmonic 312-313 332-333 352-353 % x 10
22nd Order harmonic 314-315 334-335 354-355 % x 10
23rd Order harmonic 316-317 336-337 356-357 % x 10
24th Order harmonic 318-319 338-339 358-359 % x 10
25th Order harmonic 31A-31B 33A-33B 35A-35B % x 10
26th Order harmonic 31C-31D 33C-33D 35C-35D % x 10
69
Instruction Manual
Table 22 (Continuation) : Modbus memory Map 1: Voltage Harmonics
Map 1
Parameter Voltage L1 Voltage L2 Voltage L3 Units
27th Order harmonic 31E-31F 33E-33F 35E-35F % x 10
28th Order harmonic 320-321 340-341 360-361 % x 10
29th Order harmonic 322-323 342-343 362-363 % x 10
30th Order harmonic 324-325 344-345 364-365 % x 10
31st Order harmonic 326-327 346-347 366-367 % x 10
Table 23:Modbus memory Map 2: Voltage Harmonics
Map 2
Parameter Voltage L1 Voltage L2 Voltage L3 Units
Fundamental Harm. 1A28-1A29 1A48-1A49 1A68-1A69 V x 10
2nd Order harmonic 1A2A 1A4A 1A6A % x 10
3rd Order harmonic 1A2B 1A4B 1A6B % x 10
4th Order harmonic 1A2C 1A4C 1A6C % x 10
5th Order harmonic 1A2D 1A4D 1A6D % x 10
6th Order harmonic 1A2E 1A4E 1A6E % x 10
7th Order harmonic 1A2F 1A4F 1A6F % x 10
8th Order harmonic 1A30 1A50 1A70 % x 10
9th Order harmonic 1A31 1A51 1A71 % x 10
10th Order harmonic 1A32 1A52 1A72 % x 10
11th Order harmonic 1A33 1A53 1A73 % x 10
12th Order harmonic 1A34 1A54 1A74 % x 10
13th Order harmonic 1A35 1A55 1A75 % x 10
14th Order harmonic 1A36 1A56 1A76 % x 10
15th Order harmonic 1A37 1A57 1A77 % x 10
16th Order harmonic 1A38 1A58 1A78 % x 10
17th Order harmonic 1A39 1A59 1A79 % x 10
18th Order harmonic 1A3A 1A5A 1A7A % x 10
19th Order harmonic 1A3B 1A5B 1A7B % x 10
20th Order harmonic 1A3C 1A5C 1A7C % x 10
21st Order harmonic 1A3D 1A5D 1A7D % x 10
22nd Order harmonic 1A3E 1A5E 1A7E % x 10
23rd Order harmonic 1A3F 1A5F 1A7F % x 10
24th Order harmonic 1A40 1A60 1A80 % x 10
25th Order harmonic 1A41 1A61 1A81 % x 10
26th Order harmonic 1A42 1A62 1A82 % x 10
27th Order harmonic 1A43 1A63 1A83 % x 10
28th Order harmonic 1A44 1A64 1A84 % x 10
29th Order harmonic 1A45 1A65 1A85 % x 10
30th Order harmonic 1A46 1A66 1A86 % x 10
31st Order harmonic 1A47 1A67 1A87 % x 10
70
Instruction Manual
Table 24: Modbus memory Map 1: Current Harmonics
Map 1
Parameter Current L1 Current L2 Current L3 Units
Fundamental Harm. 1F4-1F5 212-213 230-231 mA x 10
2nd Order harmonic 1F6-1F7 214-215 232-233 % x 10
3rd Order harmonic 1F8-1F9 216-217 234-235 % x 10
4th Order harmonic 1FA-1FB 218-219 236-237 % x 10
5th Order harmonic 1FC-1FD 21A-21B 238-239 % x 10
6th Order harmonic 1FE-1FF 21C-21D 23A-23B % x 10
7th Order harmonic 200-201 21E-21F 23C-23D % x 10
8th Order harmonic 202-203 220-221 23E-23F % x 10
9th Order harmonic 204-205 222-223 240-241 % x 10
10th Order harmonic 206-207 224-225 242-243 % x 10
11th Order harmonic 208-209 226-227 244-245 % x 10
12th Order harmonic 20A-20B 228-229 246-247 % x 10
13th Order harmonic 20C-20D 22A-22B 248-249 % x 10
14th Order harmonic 20E-20F 22C-22D 24A-24B % x 10
15th Order harmonic 210-211 22E-22F 24C-24D % x 10
16th Order harmonic 24E-24F 26E-26F 28E-28F % x 10
17th Order harmonic 250-251 270-271 290-291 % x 10
18th Order harmonic 252-253 272-273 292-293 % x 10
19th Order harmonic 254-255 274-275 294-295 % x 10
20th Order harmonic 256-257 276-277 296-297 % x 10
21st Order harmonic 258-259 278-279 298-299 % x 10
22nd Order harmonic 25A-25B 27A-27B 29A-29B % x 10
23rd Order harmonic 25C-25D 27C-27D 29C-29D % x 10
24th Order harmonic 25E-25F 27E-27F 29E-29F % x 10
25th Order harmonic 260-261 280-281 2A0-2A1 % x 10
26th Order harmonic 262-263 282-283 2A2-2A3 % x 10
27th Order harmonic 264-265 284-285 2A4-2A5 % x 10
28th Order harmonic 266-267 286-287 2A6-2A7 % x 10
29th Order harmonic 268-269 288-289 2A8-2A9 % x 10
30th Order harmonic 26A-26B 28A-28B 2AA-2AB % x 10
31st Order harmonic 26C-26D 28C-28D 2AC-2AD % x 10
Table 25:Modbus memory Map 2: Current Harmonics
Map 2
Parameter Current L1 Current L2 Current L3 Units
Fundamental Harm. 1A88-1A89 1AA8-1AA9 1AC8-1AC9 mA x 10
2nd Order harmonic 1A8A 1AAA 1ACA % x 10
3rd Order harmonic 1A8B 1AAB 1ACB % x 10
4th Order harmonic 1A8C 1AAC 1ACC % x 10
5th Order harmonic 1A8D 1AAD 1ACD % x 10
6th Order harmonic 1A8E 1AAE 1ACE % x 10
7th Order harmonic 1A8F 1AAF 1ACF % x 10
8th Order harmonic 1A90 1AB0 1AD0 % x 10
9th Order harmonic 1A91 1AB1 1AD1 % x 10
10th Order harmonic 1A92 1AB2 1AD2 % x 10
71
Instruction Manual
Table 25 (Continuation) : Modbus memory Map 2: Current Harmonics
Map 2
Parameter Current L1 Current L2 Current L3 Units
11th Order harmonic 1A93 1AB3 1AD3 % x 10
12th Order harmonic 1A94 1AB4 1AD4 % x 10
13th Order harmonic 1A95 1AB5 1AD5 % x 10
14th Order harmonic 1A96 1AB6 1AD6 % x 10
15th Order harmonic 1A97 1AB7 1AD7 % x 10
16th Order harmonic 1A98 1AB8 1AD8 % x 10
17th Order harmonic 1A99 1AB9 1AD9 % x 10
18th Order harmonic 1A9A 1ABA 1ADA % x 10
19th Order harmonic 1A9B 1ABB 1ADB % x 10
20th Order harmonic 1A9C 1ABC 1ADC % x 10
21st Order harmonic 1A9D 1ABD 1ADD % x 10
22nd Order harmonic 1A9E 1ABE 1ADE % x 10
23rd Order harmonic 1A9F 1ABF 1ADF % x 10
24th Order harmonic 1AA0 1AC0 1AE0 % x 10
25th Order harmonic 1AA1 1AC1 1AE1 % x 10
26th Order harmonic 1AA2 1AC2 1AE2 % x 10
27th Order harmonic 1AA3 1AC3 1AE3 % x 10
28th Order harmonic 1AA4 1AC4 1AE4 % x 10
29th Order harmonic 1AA5 1AC5 1AE4 % x 10
30th Order harmonic 1AA6 1AC6 1AE6 % x 10
31st Order harmonic 1AA7 1AC7 1AE7 % x 10
7�3�4� DELETING PARAMETERS�
All the Modbus map addresses are hexadecimal.
The Function 0x05 is implemented for these variables.
Table 26:Modbus memory map: Deleting parameters�
Parameters
Address Valid data margin
Deleting maximum values 849 FF00
Deleting minimum values 84A FF00
Maximum demand initialization 852 FF00
Deleting the hour counters (Tariff 1) 837 FF00
Deleting the hour counters (Tariff 2) 83A FF00
Deleting energies per phase (L1, L2, L3) and three-phase energies
874 FF00
Deleting three-phase energies 834 FF00
Deleting energies per phase (L1, L2, L3) 873 FF00
Deleting energies per phase (L1) 870 FF00
Deleting energies per phase (L2) 871 FF00
Deleting energies per phase (L3) 872 FF00
Deleting all of the previous parameters 898 FF00
72
Instruction Manual
7�3�5� POWER STATUS
All the Modbus map addresses are hexadecimal. The function 0x04 is implemented for this variable. This variable indicates the quadrant in which the device is operating.
Table 27:Modbus memory map: Power status
Power status
Variable Address Default value
Power status 7D1 -
The variable format is shown in Table 28:
Table 28:Variable format: Power status�
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 1: Capacitive 1: Inductive 1: Generated 1: Consumed
7�3�6� DETECTION OF INCORRECT DIRECTION OF ROTATION
All the Modbus map addresses are hexadecimal. The function 0x04 is implemented for this variable. This variable indicates whether an incorrect direction of rotation has been detected in the voltages.
Table 29:Modbus memory map: Detection of incorrect direction of rotation�
Detection of incorrect direction of rotation
Variable Address Value
Detección del sentido de giro inco­rrecto
7D5 0: No fault has been detected
1: Fault detected
7�3�7� DEVICE CONFIGURATION VARIABLES�
All the Modbus map addresses are hexadecimal. The functions 0x04 and 0x10 are implemented for this variable.
The device’s Modbus function does not check whether the variables recorded are within the correct margins, they are only checked when they are read from the EEPROM. So if any parameter is recorded with an incorrect value the device will be congured with its default value. The Modbus conguration will not take effect until the device is reset.
7�3�7�1� Transformation ratios�
Table 30:Modbus memory map: Transformation ratios�
Transformation ratios
Configuration variable
(3)
Address Valid data margin
Default
value
Voltage primary 2710 - 2711 1 - 599999 1 Voltage secondary 2712 1 - 999 1
73
Instruction Manual
Table 30 (Continuation) : Modbus memory map: Transformation ratios�
Transformation ratios
Configuration variable
(3)
Address Valid data margin
Default
value
Current primary 2713 1 - 10000 5
Current secondary 2714
0: .../1A
1: ../5 A
1
(3)
Voltage ratio x Current ratio ≤ 300000.
Voltage ratio ≤ 1000.
Note: The ratio is between the primary and the secondary.
Note: The 5 registers must be written or read at once (as a group); otherwise. the system will
respond with an error.
7�3�7�2� Number of quadrants
Table 31:Modbus memory map: Number of quadrants
Numberof quadrants
Configuration variable Address Valid data margin Default value
Number of quadrants 2B64
0: 4 quadrants 1: 2 quadrants
0
7�3�7�3� Measurement convention
Table 32:Modbus memory map: Measurement convention�
Measurement convention
Configuration variable Address Valid data margin Default value
Measurement convention 2B86
0: Circutor
1: IEC
2: IEEE
0
7�3�7�4� Measurement system
Table 33:Modbus memory map: Measurement system
Measurement system
Configuration
variable
Address Valid data margin
Default
value
Measurement system 2B5C
0: 4-3Ph Three-phase network with 4 wires� 1: 3-3Ph Three-phase network with 3 wires. 2: 3-ArOM Three-phase network with 3 wires, Aron. 3: 3-2Ph Two-phase network with 3 wires. 4: 2-2Ph Single-phase network with 2 wires, phase-to-phase. 5: 2-1Ph Single-phase network with 2 wires, phase-to-neutral.
0
7�3�7�5� Maximum demand
Table 34:Modbus memory map: Maximum demand
Maximum demand
Configuration variable Address Valid data margin
Default
value
Integration period 274C
0: The maximum demand will not be calculated
1 - 60 minutes
0
74
Instruction Manual
7�3�7�6� Display backlight
Table 35:Modbus memory map: Backlight
Backlight
Configuration variable Address Valid data margin Default value
Backlight 2B5E 1 - 999 seconds 300 s
7�3�7�7� Activating the harmonics display screen
Table 36:Modbus memory map: Display of harmonics
Display of harmonics
Configuration variable Address Valid data margin Default value
Display of harmonics 2B62
0: No
1: Yes
1
7�3�7�8� CO2 consumption and generation emissions�
Table 37:Modbus memory map: CO2 consumption and generation emissions�
CO2 emissions
Configuration variable
(4)
Address Valid data margin
Default
value
Tariff 1 consumption emissions ratio 2724 0 - 1�9999 0
Tariff 2 consumption emissions ratio 2725 0 - 1�9999 0
Tariff 1 generation emissions ratio 2728 0 - 1�9999 0
Tariff 2 generation emissions ratio 2729 0 - 1�9999 0
(4)
They have 1 decimal place.
7�3�7�9� Cost of energy consumption and generation�
Table 38:Modbus memory map: Cost of energy consumption and generation�
Cost per kWh
Configuration variable
(5)
Address Valid data margin
Default
value
Cost per kWh of tariff 1 consumption 272C 0 - 1�9999 0
Cost per kWh of tariff 2 consumption 272D 0 - 1�9999 0
Cost per kWh of tariff 1 generation 2730 0 - 1�9999 0
Cost per kWh of tariff 2 generation 2731 0 - 1�9999 0
(5)
They have 1 decimal place.
7�3�7�10� Programming Digital Output T1
Table 39:Modbus memory map: Programming Digital Output T1 (Alarm)
Programming Digital Output : Alarm
Configuration variable Address Valid data margin Default value
Maximum value 2AF8-2AF9 depending on the variable 0
Minimum value 2AFA-2AFB depending on the variable 0
Variable code 2AFC Table 13 and Table 15 0
Connection delay 2AFD 0 - 9999 seconds 0
Hysteresis 2AFE 0 - 99 % 0
Latch 2AFF
0 : No
1: Yes
0
Disconnection delay 2B00 0 - 9999 seconds 0
75
Instruction Manual
Table 39 (Continuation) : Modbus memory map: Programming Digital Output T1 (Alarm)
Programming Digital Output : Alarm
Configuration variable Address Valid data margin Default value
Contacts status 2B01
0 : Normally open
1: Normally closed
0
Table 40:Modbus memory map: Programming Digital Output T1 (pulses output)
Programming Digital Output : Pulses output
Configuration variable Address Valid data margin Default value
Kilowatts per impulse 2B20-2B21 0.001 - 999.99 kWh 1.00 kWh
Variable code 2AFC Table 16 0 Pulse width 2B22 30 - 500 ms 100 ms
7�3�7�11� Digital inputs
Table 41:Modbus memory map: Conguration of digital inputs.
Configuration variable
Address
Valid data margin Default value
Operating mode 2B66
0: Tariff
1: Logic state
0
We can also read the status of the digital inputs when they are in logic mode:
The Function 0x04 is implemented for this variable.
Table 42:Modbus memory map: Status of the digital inputs (Logic state mode)
Status of digital inputs
Variable Address Default value
Status of digital inputs 4E20 -
The variable format is shown in Table 43:
Table 43:Variable format: Status of digital inputs�
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 0 0 0
Input 1 0: OFF
1: ON
7�3�7�12� Digital outputs
Reading the status of the digital outputs.
The Function 0x04 is implemented for this variable.
Table 44:Modbus memory map: Status of the digital outputs
Status of the digital outputs
Variable Address Default value
Status of the digital outputs 4E21 -
The variable format is shown in Table 45:
76
Instruction Manual
Table 45:Variable format: Status of the digital outputs�
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 0 0 0
Output 1
0: OFF
1: ON
7�3�7�13� Communications
Table 46:Modbus memory map: Communications
Communications
Configuration variable Address Valid data margin
Default
value
Protocol 2742
0 : Modbus
1: Bacnet
0
Modbus and BACnet: Peripheral number 2743 0 - 255 1
Modbus : Baud rate 2744
0: 9600 - 1:19200 - 2:38400
3:57600
0
Modbus : Parity 2745
0: No parity
1: Odd parity
2: Even parity
0
Modbus : Data bits 2746
0 : 8 bits
1: 7 bits
0
Modbus : Stop bits 2747
0 : 1 stop bit
1: 2 stop bits
0
BACnet: Device ID 2EE0- 2EE1 0- 99999 2 BAcnet: MAC 2EE2 0- 127 1 BAcnet: Baud rate 2744 0: 9600 - 1:19200 - 2:38400 1
7.3.7.14. Password conguration
These variables allow you to lock or unlock access to the programming menu, and also allow you to change the password code. The password code may only be changed through this com­mand. The device does not need you to enter the old password in order for it to record the new one; it records the new one directly without any verication.
Table 47:Modbus memory map: Password conguration
Password
Configuration variable Address Valid data margin Default value
Password value
(6)
2B70 0 - 9999 1234
Lock-Unlock 2B71
0: Unlock
1: Lock
0
(6)
The password value is read and written in hexadecimal.
77
Instruction Manual
7.4.- BACnet PROTOCOL
BACnet is a communications protocol for Building Automation and Control NETworks. This
protocol replaces the proprietary communications of each device, making it a set of common
communication rules that enables the complete integration of the building automation and
control devices of different manufacturers.
The device features BACNet MS/TP communications, following the specications of ANSI/
ASHRAE 135 (ISO 16484-5).
Using a RS485 connection, the device can connect to a BACnet and include all of the objects
and services defined in the attached PICS map (Protocol Implementation Conformance
Statement). ( 7.4.1. PICS MAP”)
The default speed is 19200 bps and the MAC is 2 (node number), and can be changed on the
conguration screen or by entering the BaudRate and MAC_Address variables. The identier
(Device_ID) can be changed on the conguration screen using the writing property over the
variable or through the Device_ID variable.
Another option is to overwrite the Object_Name in the Device object:
a) #Baud x – where x can be: 9600, 19200, 38400
b) #MAC x – where x can be: 0 ... 127
c) #ID x – where x can be: 0 ... 99999
For further information on the protocol: www.bacnet.org.
78
Instruction Manual
7�4�1�- MAPA PICS
PICS Vendor Name: CIRCUTOR Product Name: CVM-E3-MINI Product Model Number: 837 Application Software Version: 1.0 Firmware Revision: 0.7.1 BACnet Protocol Revision: 10
Product Description:
Electrical energy meter
BACnet Standardized Device Prole (Annex L)
x BACnet Application Specic Controller (B-ASC)
List all BACnet Interoperability Building supported (see Annex K in BACnet Addendum 135d):
DS-RP-B Read Property DS-WP-B Write Propery DS-RPM-B Read Property Multiple DM-DDB-B Dynamic Device Binding DM-DOB-B Dynamic Object Binding DM-DCC-B Device Communication Control DM-RD-B Reinitialize Device
Which of the following device binding methods does the product support? (check one or more)
x Recive Who-Is, send I-Am (BIBB DM-DDB-B)
x Recive Who-Has, send I-Have (BIBB DM-DOB-B)
Standard Object Types Supported:
Analog Input Object Type
1. Dynamically creatable using BACnet’s CreateObject service? No
2. Dynamically deleatable using BACnet’s DeleteObject service? No
3. List of optional properties supported: max_pres_value min_pres_value
4. List of all properties that are writable where not otherw is a required by this standard
5. List of proprietary properties:
6. List of any property value range restrictions:
Properly Identier
Object_Name max 32 characters
DESCRIPTION SYMBOL ID OBJECTS OBJECT NAME UNITS
Tensión fase-neutro
Voltage phase to neutral
V 1 AI0 Ph2NU1 V
Corriente Current A 1 AI1 Ph1Current A Potencia activa Active power kW 1 AI2 ActPwrPh1 kW Potencia reactiva Reactive power kvar 1 AI3 ReactPwrPh1 kvar
Factor de potencia Power factor PF 1 AI4 PwrFactPh1 PF
Tensión fase-neutro Voltage phase to
neutral
V 2 AI5 Ph2NU2 V
Corriente Current A 2 AI6 Ph2Current A
79
Instruction Manual
DESCRIPTION SYMBOL ID OBJECTS OBJECT NAME UNITS
Potencia activa Active power kW 2 AI7 ActPwrPh2 kW Potencia reactiva Reactive power kvar 2 AI8 ReactPwrPh2 kvar
Factor de potencia Power factor PF 2 AI9 PwrFactPh2 PF
Tensión fase-neutro Voltage phase to
neutral
V 3 AI10 Ph2NU3 V
Corriente Current A 3 AI11 Ph3Current A Potencia activa Active power kW 3 AI12 ActPwrPh3 kW Potencia reactiva Reactive power kvar 3 AI13 ReactPwrPh3 kvar
Factor de potencia Power factor PF 3 AI14 PwrFactPh3 PF
Potencia activa trifá­sica
Three phase active power
kW III AI15 ActPwOn3Ph kW
Potencia inductiva trifásica
Three phase reactive inductive power
kvarL III AI16 InductPwOn3Ph kvarL
Potencia capacitiva trifásica
Three phase capacitive inductive power
kvarC III AI17 CapPwOn3Ph kvarC
Cos φ trifásico Three phase cos φ Cos φ III AI18 Cosphi Cos φ
Factor de potencia trifásico
Three phase power factor
PFIII AI19 PwFactOn3Ph PF
Frecuencia (L2) Frequency Hz AI20 Frequency Hz
Tensión fase-fase Voltage phase to phase V12 AI21 Ph2PhU12 V
Tensión fase-fase Voltage phase to phase V23 AI22 Ph2PhU23 V
Tensión fase-fase Voltage phase to phase V31 AI23 Ph2PhU31 V
%THD V %THD V %THD V1 AI24 THDVal_U1 %THD
%THD V %THD V %THD V2 AI25 THDVal_U2 %THD
%THD V %THD V %THD V3 AI26 THDVal_U3 %THD
%THD A %THD A %THD A1 AI27 THDVal_I1 %THD
%THD A %THD A %THD A2 AI28 THDVal_I2 %THD
%THD A %THD A %THD A3 AI29 THDVal_I3 %THD Energía activa Active energy kW•h III AI30 ActEnergy kW•h
Energía reactiva in­ductiva
Reactive inductive energy
kvarL•h III AI31 InductEnergy kvarL•h
Energía reactiva capa­citiva
Reactive capacitive energy
kvarC•h III AI32 CapEnergy kvarC•h
Energía Aparente trifásica
Three phase aparent energy
kVA•h III AI33 AppEnergy kVA•h
Energía activa gene-
rada
Three phase generated active energy
kW•h III (-) AI34 ActEnergy_exp kW•h
Energía inductiva generada
Three phase genera­ted reactive inductive energy
kvarL•h III (-) AI35 IndEnergy_exp kvarL•h
Energía capacitiva generada
Three phase genera­ted reactive capacitive energy
kvarC•h III(-) AI36 CapEnergy_exp kvarC•h
Energía aparente generada
Three phase generated aparent energy
kVA•h III (-) AI37 AppEnergy_exp kVA•h
Corriente trifásica (media)
Three phase average current
I_AVG AI38 AvgValCurr3Ph I_AVG
Corriente de neutro Neutral current In AI39 NeutralCurrent In
Potencia aparente L1 Aparent power L1 kVA AI40 AppPwrPh1 kVA
Potencia aparente L2 Aparent power L2 kVA AI41 AppPwrPh2 kVA
80
Instruction Manual
DESCRIPTION SYMBOL ID OBJECTS OBJECT NAME UNITS
Potencia aparente L3 Aparent power L3 kVA AI42 AppPwrPh3 kVA
Potencia aparente trifásica
Three phase aparent power
kVAIII AI43 AppPw3Ph kVA
Máxima demanda I1 Maximum demand I1 Md (A1) AI44 MaxDemand_A1 A
Máxima demanda I2 Maximum demand I2 Md(A2) AI45 MaxDemand_A2 A
Máxima demanda I3 Maximum demand I3 Md(A3) AI46 MaxDemand_A3 A
Máxima demanda A Maximum demand A A III AI47 MaxDemand_A A Máxima demanda kW Maximum demand kW kW III AI48 MaxDemand_kW kW
Máxima demanda kVA Maximum demand kVA kVA III AI49
MaxDemand_
kVA
kVA
Analog Value Object Type
1. Dynamically creatable using BACnet’s CreateObject service? No
2. Dynamically deleatable using BACnet’s DeleteObject service? No
3. List of optional properties supported:
4. List of all properties that are writable where not otherwise required by this standard
5. List of propietary properties:
Property Identier Property Datatype Meaning
5. List of object identiers and their meaning in this device
Object ID Object Name Description
AV1 MAC_Address MAC
AV2 BaudRate BAUD RATE
AV3 Device_ID DEVICE ID
Device Object Type
1. Dynamically creatable using BACnet’s CreateObject service? No
2. Dynamically deleatable using BACnet’s DeleteObject service? No
3. List of optional properties supported: Description, Protocolo_Conformance_Class
4. List of all properties that are writable where not otherwise required by this standard
Object_Name Max_Master Max_Info_Frames Object_Identier
5. List of propietary properties:
5. List of any property value range restrictions
Property Identier Restrictions
Object_Name < 32 bytes
Object_Identier Device Type only
Number_Of_APDU_Retries 0-255
APDU_Timeout 0-65535 miliseconds
Vendor_Identier 0-65535
Data Link Layer Options (check all that supported):
X MS/TP master (Clause 9), baud rate(s): 9.6, 19.2kB/s
Character Sets Supported (check all that apply):
Indicating support for multiple character set does not imply that they can all be supported simulta­neously.
X ANSI X3.4
81
Instruction Manual
8�- TECHNICAL FEATURES
AC Power supply
Rated voltage
207 ... 253 V ~
Frequency 50 ... 60 Hz
Consumption 3.5 VA
Installation category CAT III 300 V
Voltage measurement circuit
Rated voltage (Un) 300 V Ph-N, 520 V Ph-Ph
Voltage measurement margin 5 ... 120% Un
Frequency measurement margin 45 ... 65Hz
Input impedance 400 kΩ Min� voltage measurement (Vstart) 11 V Ph-N
Installation category CAT III 300 V
Current measurement circuit
Nominal current (In) .../5A o .../1 A
Current measurement margin 2 ... 120% In
Min� current measurement (Istart) 10 mA
Consumption 0.9 VA
Installation category CAT III 300 V
Measurement accuracy
Voltage measurement 0.5% ± 1 digit
Current measurement 0.5% ± 1 digit
Frequency measurement 0.5%
Active power measurement 0.5% ± 2 digits
Reactive power measurement 1% ± 2 digits
Active energy measurement
I < 0�1In I > 0�1In
Class 1 Class 0.5
Reactive energy measurement Class 2
Pulse outputs
Quantity 1
Type NPN ouput
Maximum voltage 24 V
Maximum current 50 mA
Maximum frequency 16 impulses / sec
Pulse width 30 ms to 500 ms (Programmable)
Digital inputs
Quantity 1
Type NPN Potential free contact
Insulation optoisolated
82
Instruction Manual
Communications
Modbus RTU BACnet
Bus RS-485 MS/TP
Protocol Modbus RTU BACnet
Baud rate 9600 - 19200 - 38400 - 57600 bps 9600 - 19200 - 38400 bps Stop bits 1 - 2 1
Parity without - even - odd without
User interface
Display LCD Custom COG high contrast
Keyboard Capacitive, 3 keys
LED 2 LED
Environmental features
Operating temperature -5ºC... +45ºC
Storage temperature -10ºC ... +50ºC
Relative humidity (non-condensing) 5 ... 95%
Maximum altitude 2000 m
Protection degree
IP30, Front: IP40
Mechanical features
Dimensions (Figure 23) 52.5 x 118 x 74 mm
Weight 300 g
Surround Self-extinguishing V0 plastic
Attachment DIN rail
Standards
Safety requirements for electrical equipment for measurement, con­trol and laboratory use -- Part 1: General requirements
EN 61010-1: 2010
Safety requirements for electrical equipment for measurement, con­trol and laboratory use -- Part 2-030: Particular requirements for test­ing and measuring circuits
EN 61010-2-030: 2010
Electrical equipment for measurement, control and laboratory use ­EMC requirements - Part 1: General requirements (Endorsed by AE­NOR in March of 2013�)
EN 61326-1:2013
Test for ammability of plastic materials for parts in devices and appliances
UL 94
Electrical safety in low voltage distribution systems up to 1 000 V a�c� and 1 500 V d�c� - Equipment for testing, measuring or monitoring of protective measures -- Part 12: Performance measuring and monito­ring devices (PMD)
EN 61557-12:2008
83
Instruction Manual
90
45
44
52.5 74
118
Figure 23: Dimensions of the CVM-E3-MINI�
84
Instruction Manual
9�- MAINTENANCE AND TECHNICAL SERVICE
10�- GUARANTEE
No returns will be accepted and no unit will be repaired or replaced if it is not ac-
companied by a report indicating the defect detected or the reason for the return.
•The guarantee will be void if the units has been improperly used or the stora­ge, installation and maintenance instructions listed in this manual have not been followed. “Improper usage” is de ned as any operating or storage condition con­trary to the national electrical code or that surpasses the limits indicated in the technical and environmental features of this manual.
CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the installation, nor will it cover any possible sanctions derived from a pos­sible failure, improper installation or “improper usage” of the unit. Consequently, this guarantee does not apply to failures occurring in the following cases:
- Overvoltages and/or electrical disturbances in the supply;
- Water, if the product does not have the appropriate IP classi cation;
- Poor ventilation and/or excessive temperatures;
- Improper installation and/or lack of maintenance;
- Buyer repairs or modi cations without the manufacturer’s authorisation.
CIRCUTOR guarantees its products against any manufacturing defect for two years after the delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee period.
In the case of any query in relation to unit operation or malfunction, please contact the
CIRCUTOR, SA Technical Support Service.
Technical Assistance Service
Vial Sant Jordi, s/n, 08232 - Viladecavalls (Barcelona) Tel: 902 449 459 ( España) / +34 937 452 919 (outside of Spain) email: sat@circutor.es
85
Instruction Manual
11�- CE CERTIFICATE
86
Instruction Manual
87
Instruction Manual
88
Instruction Manual
89
Instruction Manual
CIRCUTOR, SA
Vial Sant Jordi, s/n 08232 -Viladecavalls (Barcelona) Tel.: (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14 www.circutor.com central@circutor.com
Loading...