This manual is issued to help all the CVM-BD-420-4 & CVM-BD-420-8 users to install
and use it in order to get the best from it. After receiving the unit please check the
following points:
(a) Does this device corresponds to your order specifications?
(b) Check if any damage was done during the shipment process.
(c) Verify that it includes *One instruction manual .
1.2.- Connection procedures
Before connecting the instrument to the mains verify the following:
(a) Power supply :
230 V a.c. Power supply Va.c. ( Single phase )
Frequency: 50 ... 60 Hz
(b) Maximum measuring voltage:
Standard : 500 V a.c. phase-neutral / 866 V a.c. between phases A special model for 110 V measuring is available:
100 V a.c. phase-neutral / 173 V a.c. between phases
(c) Maximum measuring current: Transformer of In / 5 A a.c.
The CVM-BD-420-4 & CVM-BD-420-8 power meters are programmable measuring
instruments, offering several operation possibilities selectable in their SETUP option.
Before power supplying the instrument, read the CONNECTIONS and SETUP
sections and choose the most suitable operation mode for getting your desired data.
4 or 8 user-programmable analog outputs are available. (Section 5.10)
The CVM-BD-420-.. is an instrument which measures, calculates and displays all the
main electrical parameters at any electrical network (balanced or not). The
measuring is true RMS value, through three a.c. Voltage inputs and three a.c.
Current inputs (from Current Transformers .../ 5A).
By means of an internal microprocessor it simultaneously measures:
Parameter L1 L2 L3 Average Addition
Voltage (phase-neutral) x x x x
Voltage (phase-phase) x x x x
Current x x x x
Active power x x x X
Reactive power L x x x X
Reactive power C x x x X
Power factor x x x x
Apparent power X
Frequency x
Parameter CVM-BD-420-..
Date/Time dd/mm/yy hh:mm:ss TIME
Active energy ( two indep. meters: demanded energy (+)
and generated energy (--) )
Reactive energy (inductive), two indep. meters kvarh.L (+) and (--)
Reactive energy (capacitive), two indep. meters kvarh.C (+) and (--)
- Measurements in all four quadrants (equivalent to CVMk-4C ).
- Power demand control.
- Memorizes Maximum and Minimum values.
- Two leds for indication of CPU and communication operation
- Incorporates the calculation of the harmonic distortion.
3.- INSTALLATION AND STARTUP
The manual you hold in your hands contains information and warnings that the
user should respect in order to guarantee a proper operation of all the instrument
functions and keep its safety conditions.
The instrument must not be powered and used until its definitive assembly on the
cabinet’s door.
Whether the instrument is not used as manufacturer’s specifications, the
protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents external
visible damages), the instrument must be immediately powered off. In this case
contact a qualified service representative.
Instrument is to be mounted on DIN rail mounting device with low dimensions.
All connections keep inside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to
touching and cover opening actions or elements removal may allow accessing
dangerous parts. Therefore, the instrument must not be used until this is completely
installed.
The instrument must be connected to a power supply circuit protected with gl type
(IEC 269 ) or M type fuses rated between 0.5 and 2 A. This circuit should be
provided with an automatic switch or any equivalent element to disconnect the
instrument from the power supply network. The supply and measuring voltage
circuits will be both connected through a wire with a minimum cross-section of 1
mm2. The line of the current transformer secondary will have a minimum crosssection of 2,5 mm2.
17 Out 1 4-20 mA type output 1
18 Out 2 4-20 mA type output 2
19 GND Ground
20 Out 3 4-20 mA type output 3
21 Out 4 4-20 mA type output 4
22 Out 5 4-20 mA type output 5
23 Out 6 4-20 mA type output 6
24 GND Ground
25 Out 7 4-20 mA type output 7
26 Out 8 4-20 mA type output 8
15 N NEUTRAL
14 VL3 Voltage phase 3
13 VL2 Voltage phase 2
12 VL1 Voltage phase 1
The instrument has a display with three lines (10 characters every line).
When you switch on the power supply of the CVM-BD-420-.. you will see on the
display "Circ CVM-BD-..." (program version) and following you will read "CARD TYPE
xxxx" (identification of the output options). After some seconds the instrument is
ready to work, showing one of the possible screens.
The display indicates the parameter presently shown.
display
The first display shows the voltage of phase L1 (V1), the voltage of phase L2 (V2)
and the voltage of phase L3 (V3).
220 V12
220 V23
220 V31
If you press the "display" key, we are now reading the CURRENT values for each
phase (A1, A2, A3). However, this screen can be configured in order to display other
different parameters.
When pressing again the "display" key, we will see on display the three previously
programmed parameters (see point 5.5. in the SET-UP section).
If you press the "display" key again you repeat the above mentioned process
( you can see 1 to 18 displays depending of the previous set-up ).
On the screen we read the word "SET U P" followed by 6 digits. They allow us
setting the primary of the voltage transformer.
SET U
P - - -
- - -
Last digit of the first display indicates "U" (Voltage) and first digit of the second
display indicates "P" (Primary). It means that we can set the primary of the voltage
transformer. To avoid mistakes the Voltage red LEDs remain lit on.
a.- To write or modify the value just repeatedly press the "max" key and the blinking
digit value will be increased.
b.- When the value on screen is the proper one, we can pass to the next digit by
pressing the "min" key in order to modify the other values.
c.- When the blinking digit is the last one, pressing the "min" key we go back to the
initial value: set values can be again modified.
d.- Press "display" to pass to the next setup option.
We can now set the value of the secondary of the voltage transformer. Only three
digits are available:
SET U
S
- - -
Same process as in point 5.2:
- "max" key: Allows us modifying the value of the blinking digit. Each time it is
pressed the value is increased.
- "min" key: Allows us the validation of the blinking digit and going to the next one.
- Press "display" to pass to the next setup option.
If the CVM-BD-420-.. is directly connected to the mains (without voltage
transformer) the values of primary and secondary must be the same, for instance
000001/001.
5.4.- Current Transformer Primary
"SET A P" and five digits appear on screen allowing us to set the primary of the
current transformer. The current green LEDs light on to avoid mistakes.
The procedure is the same one done at the previous sections with the "max", "min"
and "display" keys.
NOTES:
- The maximum programmable value is 10.000
- The secondary of the current transformers is not programmable. It is automatically
taken as 5 A (... / 5 A ac)
5.5.- Parameter SETUP
This option allows to program until 51 optional parameters that you can see on the
display through 17 possible pages (3 parameters per each page). The CVM-BD-420.. firstly inquires whether you want the default parameter selection.
"max" key : you can select YES or NO. The “display” key allows the validation
of the selected option.
dEF
PAGE
YES
5.5.1.-Select “YES” to program the default parameters. In this case , it pass to the
next option (5.6.- First Page SET-UP )
5.5.2.-If you select “NO” , it allows programming the parameters that you want to
see on the display. Every new page, it asks if you want to continue this set-up .
- If you select “SET PAGE YES” , you can program the desired parameters in this
page :
xx A1
xx A2
xx A3
Parameter code ( set-up ) / Parameter symbol
SET-UP
:
- "max" key : Allows us modifying the value of the blinking digit. Each time it is
pressed the value is increased.
- "min" key : Allows us the validation of the blinking digit and going to the next one.
Each display has two digits to select the desired parameters among the ones in the
attached code chart:
Parameter Symbol
phase L1
Single voltage V 1
Current A 1
Active power kW 1
Inductive power kvarL 1
Capacitiva power kvarC 1
Power factor PF 1
Three phase single voltage Vav III
Three phase current Aav III
Three phase active power kW III
Three. ph. inductive power. kvarL III
Three ph. capacitive power kvarC III
Three ph. power factor. PF III
Code Symbol
phase L2
01
02
03
04
05
06
19
20
21
22
23
24
V 2
A 2
kW 2
kvarL 2
kvarC 2
PF 2
Frequency Hz
Three ph. apparent power kVA III
Ph-Ph voltage L1- L2 V 12
Ph-Ph voltage L2 - L3 V 23
Ph-Ph voltage L3 - L1 V 31
Three ph. Ph-Ph voltage Vc III
5.10.- 4 - 20 mA outputs: CVM-BD-420-4 (4 analog outputs) and
CVM-BD-420-8 (8 analog outputs)
With these outputs we can configure the CVM-BD420 to give an output of 4 - 20
mA d.c. or of 0 - 20 mA d.c. ( resolution of 4.000 points ) proportional to any of the parameters measured by the CVM-BD, with the ability of setting the scale
(offset and full scale).
On the CVM-BD-420-.. screen following messages appear at this SET-UP point
(provided the right module is connected to the equipment):
a.- Parameter choice:
dA 1 OUTPUT D/A No.1
Code xx
- "max" -- "min" keys: allow the selection of any parameter from 1 to 30, the 35, or
from 54 to 59.
- “display” key: validates the selected option and passes to the next setup screen.
b.- Selection of 0 - 20 mA or 4 - 20 mA :
dA 1 OUTPUT D/A Nr.1
Scal Scale :
4 - 20
- "display": to validate the selected option and pass to the next setup screen.
Value of the parameter that we assign as the zero of the scale.
dA 1 OUTPUT D/A No.1
Zero Zero of the scale:
x.xxx
(four digits with floating decimal point)
allows choosing the zero of the scale
- "max" key: it allows modifying the value of the blinking value.
Every time it is pressed the number is increased.
- "min" key: it allows validating the blinking value and go to the next digit.
NOTE : When you arrive at the last digit, you can move the position of the decimal
point with the "max" key.
- "display": to validate the selected option and pass to the next setup screen.
d.- Full scale: Value of the parameter to which we assign the 20 mA.
dA 1 OUTPUT D/A No.1
F.ESC Full scale:
x.xxx
allows choosing the full scale (20 mA)
(four digits with floating decimal point)
Proceed as in the previous section.
- To access the next option, press "display": setup options for the rest of analog
outputs will appear up. Setup procedure is similar for any output.
Terminals : IP 20
Dimensions 140 x 70 x 110 mm ( 8 modules relay as per DIN 43 880)
Safety Category II , as perEN-61010
Standards EN 60664, EN 61010-1, EN 61036, IEC 60801 , IEC 60571-1,
All installation specification described at the previous chapters named
INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Note that with the instrument powered on, the terminals could be dangerous to
touching and cover opening actions or elements removal may allow accessing
dangerous parts. This instrument is factory-shipped at proper operation condition.
The CVM-BD-420-.. does not require any special maintenance. No adjustment,
maintenance or repairing action should be done over the instrument open and
powered and, should those actions are essential, high-qualified operators must
perform them.
Before any adjustment, replacement, maintenance or repairing operation is carried
out, the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be
immediately put out of service. The instrument’s design allow a quick replacement in
case of any failure.
9.- TECHNICAL SERVICE
For any inquiry about the instrument performance or whether any failure happens,
contact to CIRCUTOR’s technical service.
CIRCUTOR S.A. - Aftersales Service
Vial Sant Jordi, s/n
08232 - Viladecavalls
tel - +34 - 93-745 29 00
fax - +34 - 93-745 29 14
e-mail: central@circutor.es
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.