CIRCUTOR CVM-BD User Manual

SUPPLY NETWORK ANALYZERS
CVM-BD-420-4 & CVM-BD-420-8
SERIES
INSTRUCTION MANUAL
( M98132301-20 / 03A )
(c)
CIRCUTOR S.A.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 1
CVM-BD-420-4 & CVM-BD-420-8 SUPPLY NETWORK ANALYZERS Page
1.- BASIC INSTRUCTIONS ............................................ 2
1.1.- Delivery spot check ......................................... 2
1.2.- Connection procedures .................................... 2
1.3.- CVM-BD-420 types ........................................ 3
2.- MAIN CHARACTERISTICS ....................................... 3
2.1.- Other characteristics ........................................ 6
3.- INSTALLATION AND STARTUP ................................ 6
3.1.- Installation ..................................................... 7
3.2.- CVM-BD-420-.. connection terminal ................... 9
3.3.- Connection drawing for the CVM-BD-420-.. ....... 10
4.- OPERATION MODE ................................................. 14
5.- SETUP .................................................................. 16
5.1.- Phase-to-Phase or Phase-to-Neutral voltages 16
5.2.- Voltage Transformer Primary ............................. 17
5.3.- Voltage Transformer Secondary ........................ 18
5.4.- Current Transformer Primary.............................. 18
5.5.- Parameter SETUP............................................. 19
5.6.- First Page SETUP............................................. 22
5.7.- Maximum power demand ................................. 23
5.8.- TIME / DATE SETUP......................................... 24
5.9.- Clearing Energy Counters ................................. 25
5.10.- 4 - 20 mA Type outputs................................. 26
6.- SPECIFICATIONS.................................................... 29
7.- SAFETY CONSIDERATIONS ..................................... 30
8.- MAINTENANCE ...................................................... 31
9.- TECHNICAL SERVICE ............................................. 31
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 2
1.- BASIC INSTRUCTIONS
1.1.- Delivery spot check
This manual is issued to help all the CVM-BD-420-4 & CVM-BD-420-8 users to install and use it in order to get the best from it. After receiving the unit please check the following points:
(a) Does this device corresponds to your order specifications? (b) Check if any damage was done during the shipment process. (c) Verify that it includes *One instruction manual .
1.2.- Connection procedures
Before connecting the instrument to the mains verify the following:
(a) Power supply :
 230 V a.c. Power supply Va.c. ( Single phase )
 Frequency: 50 ... 60 Hz
(b) Maximum measuring voltage:
 Standard : 500 V a.c. phase-neutral / 866 V a.c. between phases  A special model for 110 V measuring is available:
100 V a.c. phase-neutral / 173 V a.c. between phases
(c) Maximum measuring current: Transformer of In / 5 A a.c.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 3
1.3.- CVM-BD-420 types
Two CVM-BD-420 types are available according to the number of analog outputs that the analyzer equips:
Code Type Features
7 70 262 CVM-BD-420-4 4C + 4 analog outputs + display 7 70 263 CVM-BD-420-8 4C + 8 analog outputs + display
2.- MAIN CHARACTERISTICS
The CVM-BD-420-4 & CVM-BD-420-8 power meters are programmable measuring instruments, offering several operation possibilities selectable in their SETUP option.
Before power supplying the instrument, read the CONNECTIONS and SETUP
sections and choose the most suitable operation mode for getting your desired data.
4 or 8 user-programmable analog outputs are available. (Section 5.10)
The CVM-BD-420-.. is an instrument which measures, calculates and displays all the main electrical parameters at any electrical network (balanced or not). The measuring is true RMS value, through three a.c. Voltage inputs and three a.c. Current inputs (from Current Transformers .../ 5A).
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 4
By means of an internal microprocessor it simultaneously measures:
Parameter L1 L2 L3 Average Addition
Voltage (phase-neutral) x x x x Voltage (phase-phase) x x x x Current x x x x Active power x x x X Reactive power L x x x X Reactive power C x x x X Power factor x x x x Apparent power X Frequency x
Parameter CVM-BD-420-..
Date/Time dd/mm/yy hh:mm:ss TIME Active energy ( two indep. meters: demanded energy (+) and generated energy (--) ) Reactive energy (inductive), two indep. meters kvarh.L (+) and (--) Reactive energy (capacitive), two indep. meters kvarh.C (+) and (--)
---------------------------------------------------
The CVM-BD-420-.. allows reading up to 54 electrical parameters in 18 screens, shown in a three line numerical display, where you can see:
(a) Phase-phase or phase-neutral voltage of the three phases (b) 51 user-selectable parameters according to the model (see attached table)
kWh (+) and (--)
And also the MAXIMUM POWER DEMAND: The power demand is integrated
during a prefixed period.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 5
You can select:
a) The parameter to be controlled (it can measure active power kW,
apparent power kVA or three phase average current AIII).
b) The demand period (1 to 60 min.).
This power demand function works with sliding window : shows the accumulated demand over the last period from "now".
---------------------------------------------------------------------------------------------
The CVM-BD-420-.. is a 4 quadrant analyzer, that is, this can automatically
detect the energy sign:
Example of the phase difference between voltage and current 30º kW + kvar L + + 300º kW + kvar C + -- 210º kW -- kvar L -- + 120º kW -- kvar C -- --
Active power kW or kW.h
Reactive power kvar or kvar.h
P.F.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 6
2.1- Other Characteristics
- DIN rail mounting device with low dimensions.
- True RMS value measurements.
- 4 or 8 user-programmable analog inputs.
- Measurements in all four quadrants (equivalent to CVMk-4C ).
- Power demand control.
- Memorizes Maximum and Minimum values.
- Two leds for indication of CPU and communication operation
- Incorporates the calculation of the harmonic distortion.
3.- INSTALLATION AND STARTUP
The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions.
The instrument must not be powered and used until its definitive assembly on the cabinet’s door.
Whether the instrument is not used as manufacturer’s specifications, the protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents external visible damages), the instrument must be immediately powered off. In this case contact a qualified service representative.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 7
3.1.- INSTALLATION
Before applying AC power to the, check following points :
a.- Supply voltage :
- Power supply V a.c. ( Single phase ) 50 ...60 Hz
230 V a.c.
- Frequency : 50 ... 60 Hz
- Supply tolerance : + 10 % / --15 %
- Connection terminals : Terminals 1 - 28
- Instrument burden : 6 VA
b.- Maximum voltage at the voltage measuring circuit:
Standard : 500 V a.c. phase-neutral / 866 V a.c. between phases
A special model CVM-BD-420-4 & CVM-BD-420-8 for 110 V measur ement is
also available:
100 V a.c. phase-neutral / 173 V a.c. between phases
c.- Maximum admissible current : Transformer of In / 5 A a.c.
d.- Operation conditions :
- Operating temperature : 0 to 50ºC
- Humidity : 25 to 80 % R.H. non-condensing
e.- Safety : Designed to meet protection class II as per EN 61010.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 8
Mounting:
Instrument is to be mounted on DIN rail mounting device with low dimensions. All connections keep inside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. Therefore, the instrument must not be used until this is completely installed.
The instrument must be connected to a power supply circuit protected with gl type (IEC 269 ) or M type fuses rated between 0.5 and 2 A. This circuit should be provided with an automatic switch or any equivalent element to disconnect the instrument from the power supply network. The supply and measuring voltage circuits will be both connected through a wire with a minimum cross-section of 1 mm2. The line of the current transformer secondary will have a minimum cross­section of 2,5 mm2.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 9
3.2.- CVM-BD-420-.. Connection terminal
Terminal No Designation Concept
1 - 28 A1 - A2 supply voltage : 230 V a.c.
17 Out 1 4-20 mA type output 1 18 Out 2 4-20 mA type output 2 19 GND Ground 20 Out 3 4-20 mA type output 3 21 Out 4 4-20 mA type output 4 22 Out 5 4-20 mA type output 5 23 Out 6 4-20 mA type output 6 24 GND Ground 25 Out 7 4-20 mA type output 7 26 Out 8 4-20 mA type output 8
15 N NEUTRAL 14 VL3 Voltage phase 3 13 VL2 Voltage phase 2 12 VL1 Voltage phase 1
11 - 10 I L3: s1 - s2 Current phase L3 .../ 5 A
9 - 8 I L2: s1 - s2 Current phase L2 .../ 5 A
7 - 6 I L1: s1 - s2 Current phase L1 .../ 5 A
NOTE: Current inputs are isolated
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 10
3.3.- Connection drawing for the CVM-BD-420-..
a.- Connection diagram of the CVM-BD-420-4 & CVM-BD-420-8 for a low voltage, three phase network.
IMPORTANT REMARK! If power = 0 is shown for any of the phases (codes 03, 09
and 15) and voltage and current are not zero for this phase, check out following points:
- Assure that L1, L2 and L3 phases coincide in voltage and current.
- Correct polarity? Reverse the current transformer placed at this phase.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 11
b.- CVM-BD-420-4 & CVM-BD-420-8: 3 current transformers + two voltage
transformer :
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 12
c.- CVM-BD-420-4 & CVM-BD-420-8 : Two current transformers + 2 voltage
transformers.
S2 of the current transformer grounded to earth
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 13
S1 of the current transformer grounded to earth
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 14
4.- OPERATION MODE
The instrument has a display with three lines (10 characters every line).
When you switch on the power supply of the CVM-BD-420-.. you will see on the display "Circ CVM-BD-..." (program version) and following you will read "CARD TYPE xxxx" (identification of the output options). After some seconds the instrument is ready to work, showing one of the possible screens. The display indicates the parameter presently shown.
display
The first display shows the voltage of phase L1 (V1), the voltage of phase L2 (V2) and the voltage of phase L3 (V3).
220 V12 220 V23 220 V31
If you press the "display" key, we are now reading the CURRENT values for each
phase (A1, A2, A3). However, this screen can be configured in order to display other different parameters.
When pressing again the "display" key, we will see on display the three previously
programmed parameters (see point 5.5. in the SET-UP section).
If you press the "display" key again you repeat the above mentioned process
( you can see 1 to 18 displays depending of the previous set-up ).
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 15
max
Pressing the "max" key, the maximum values for the parameters being shown
appear in the displays.
xxxx MAX xxxx MAX xxxx MAX
This function is only valid while you keep pressing the "max" key. If you stop
pressing the key the instantaneous values appear again.
min
Pressing the "min" key, the minimum values for the parameters being shown
appear in the displays.
xxxx MIN xxxx MIN xxxx MIN
This function is only valid while you keep pressing the "min" key. If you stop
pressing the key the instantaneous values appear again.
Reset
Pressing the "reset" key the system is reset. This is equivalent to switch off the
power supply of the instrument. The stored maximum and minimum values will be automatically deleted from the internal memory.
If you are in the setup process and press the "reset" key, you exit it without saving
any modification that you have done and making a reset of the system.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 16
5.- SETUP
To access into the setup menu just follow these steps:
(a) Connect (supply) the instrument.
(b) Press the two green buttons (max, min) simultaneously. You will see during a few seconds the word "set". It means that we are in the setup
process. Then we go along the different options, step by step:
5.1.- Phase-to-Phase or Phase-to-Neutral voltages
After the word "set" you will see on the three displays the voltages of the phases
L1, L2, L3.
U1 U12 U2 or U23 U3 U31
Phase to Neutral Voltages: U1 , U2 , U3 Phase to Phase Voltages : U12 , U23 , U31
a.- To select one of the voltage options just press the green key "max" and both
options will appear alternately.
b.- When you get in the display the wished option just press the "display" key to
validate it and access to the next setup option.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 17
5.2.- Voltage Transformer Primary
On the screen we read the word "SET U P" followed by 6 digits. They allow us setting the primary of the voltage transformer.
SET U P - - -
- - -
Last digit of the first display indicates "U" (Voltage) and first digit of the second display indicates "P" (Primary). It means that we can set the primary of the voltage transformer. To avoid mistakes the Voltage red LEDs remain lit on.
a.- To write or modify the value just repeatedly press the "max" key and the blinking
digit value will be increased.
b.- When the value on screen is the proper one, we can pass to the next digit by
pressing the "min" key in order to modify the other values. c.- When the blinking digit is the last one, pressing the "min" key we go back to the
initial value: set values can be again modified.
d.- Press "display" to pass to the next setup option.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 18
5.3.- Voltage Transformer Secondary
We can now set the value of the secondary of the voltage transformer. Only three digits are available:
SET U S
- - -
Same process as in point 5.2:
- "max" key: Allows us modifying the value of the blinking digit. Each time it is
pressed the value is increased.
- "min" key: Allows us the validation of the blinking digit and going to the next one.
- Press "display" to pass to the next setup option.
If the CVM-BD-420-.. is directly connected to the mains (without voltage transformer) the values of primary and secondary must be the same, for instance 000001/001.
5.4.- Current Transformer Primary
"SET A P" and five digits appear on screen allowing us to set the primary of the current transformer. The current green LEDs light on to avoid mistakes.
SET A P - -
- - -
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 19
The procedure is the same one done at the previous sections with the "max", "min" and "display" keys.
NOTES:
- The maximum programmable value is 10.000
- The secondary of the current transformers is not programmable. It is automatically taken as 5 A (... / 5 A ac)
5.5.- Parameter SETUP
This option allows to program until 51 optional parameters that you can see on the display through 17 possible pages (3 parameters per each page). The CVM-BD-420­.. firstly inquires whether you want the default parameter selection.
 "max" key : you can select YES or NO. The “display” key allows the validation
of the selected option.
dEF PAGE YES
5.5.1.- Select “YES” to program the default parameters. In this case , it pass to the
next option (5.6.- First Page SET-UP )
5.5.2.- If you select “NO” , it allows programming the parameters that you want to
see on the display. Every new page, it asks if you want to continue this set-up .
SET PAGE NUMBER YES xx <--- page Nº
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 20
- If you select “SET PAGE YES” , you can program the desired parameters in this page :
xx A1 xx A2 xx A3
Parameter code ( set-up ) / Parameter symbol
SET-UP
:
- "max" key : Allows us modifying the value of the blinking digit. Each time it is
pressed the value is increased.
- "min" key : Allows us the validation of the blinking digit and going to the next one.
Each display has two digits to select the desired parameters among the ones in the attached code chart:
Parameter Symbol
phase L1
Single voltage V 1 Current A 1 Active power kW 1 Inductive power kvarL 1 Capacitiva power kvarC 1 Power factor PF 1
Three phase single voltage Vav III Three phase current Aav III Three phase active power kW III Three. ph. inductive power. kvarL III Three ph. capacitive power kvarC III Three ph. power factor. PF III
Code Symbol
phase L2
01 02 03 04 05 06
19 20 21 22 23 24
V 2 A 2 kW 2 kvarL 2 kvarC 2 PF 2
Frequency Hz Three ph. apparent power kVA III Ph-Ph voltage L1- L2 V 12 Ph-Ph voltage L2 - L3 V 23 Ph-Ph voltage L3 - L1 V 31 Three ph. Ph-Ph voltage Vc III
Code Symbol
phase L3
07 08 09 10 11 12
V 3 A 3 kW 3 kvarL 3 kvarC 3 PF 3
Code
13 14 15 16 17 18
25 26 27 28 29 30
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 21
Date/ TIME dd/mm/yy hh:mm:ss
Active energy kW.h Reactive energy (inductive) kvarh.L Reactive energy (capacitive) kvarh.C
Demand power ( kW, kVA, AIII) Pd
Active energy generated kW.h -­ Reactive energy (inductive) gen. kvarh.L -­ Reactive energy (capacitive) gen. kvarh.C --
TIME
31
32 33 34 35
36 37 38
Parameter Symbol
phase L1
Voltage harmonic
distortion
Current harmonic
distortion
THD V1
THD A1
Code Symbol
phase L2
54
57
THD V2
THD A2
Code Symbol
phase L3
55
58
THD V3
THD A3
56
59
- For passing to the next page , press "display". In this case the CVM-BD-420-..
inquires again:
SET PAGE NUMBER
YES xx
- If you select “SET PAGE YES” , you can set-up a next page.
- If you don’t want to set-up more pages, select “SET PAGE No”, and it pass to the
next set-up option (5.6.- First Page SET-UP ). You can see the first page of voltages and all the programmed pages .
Code
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 22
5.6.- First Page SET-UP
This option allows selecting among fixed or rotary page: a.- Fixed page : the page is changed pressing the "display" key. The page among
the available ones that we want to see when the CVM-BD-420-.. is powered (or a reset is made) can be selected.
b.- Rotary pages : the page changes to the next one automatically every 5 seconds. ( “SET AUTO PAGE : Rotate page select “ option ).
Set-up :
- The "max" key allows modifying the selected page. The display shows the different
possible pages.
SET xx AUTO xx
PAGE xx <-- set-up parameters
- The "display" key allows the validation of the chosen option.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 23
5.7.- Maximum power demand
Push the key "display" and the following screens will appear by display:
1.- DEMAND PERIOD ( 1 to 60 min.) ("SET Per xx")
2.- PARAMETER TO CONTROL ("SET Pd xx")
Three phase active power kW III Three phase apparent power kVA III Three phase average current AavIII
21 26 20
Value of power integrated during the programmed demand period.
3.- CLEAR MAXIMUM VALUE IN MEMORY
("CLr Pd xx") no or YES
PROGRAMMING MODE:
- "max" key: allows choosing the different available options.
- "min" key: allows the validation of the blinking digit and go forward to the
next digit (only for the "SET Per xx" option).
- To pass to the next option press "display". If you don't want to modify anything, just press the "display" key three times without
modifying any value.
- Display: If you program the MAXIMUM POWER DEMAND option, parameter
35, the following appears by display (depending on the pressed key):
display
Present value of the demand power meter (Sliding Window, according to the set demand period) updated every second.
max
min
MAXIMUM integrated value (since last reset) HOUR : MINUTE DAY : MONTH (“”HH.MM DD/MM”) when this maximum has occurred
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 24
5.8.- DATE / TIME SETUP
Pressing the "display" key we will see in the CVM-BD-420-.. screen the following:
1.- DAY : MONTH ("SET day dd:mm")
2.- YEAR ("SET YEAR xxxx " ) 4 digits
3.- HOURS : MINUTES ("SET HOUR hh:mm")
For their setup:
- "max" key: Allows modifying the value of the blinking digit.
- "min" key: Allows the validation of the blinking digits and go to the next one.
- To pass to the next option press "display". If you don't want to modify the time, just press three times "display" without making
any modification.
- Display: If you select the parameter 31, following appears by display:
display max min
HOUR .MINUTES DAY. MONTH MINUTES . SEC.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 25
5.9.- Clearing energy counters
On display we see "CLR ENER no" (Clear energy counters).
- "max" : To select "YES" or "no"
- "display" : To validate the selected option. Once finishing this option, all the
modifications that we have done are saved in memory and the setup process is finished.
- Display : If any of the energies is programmed (kWh, kvarhL or kvarhC), it is
displayed as follows:
[display]
[max]
[min]
XXXX kW.h 4 counter digits (more significant ) / units XXX XXX. XXX complete counter
XXXX (1 )
4 digits / Tariff type ( 1, 2 or 3 )
Example : If the accumulated energy is 32.534,810 kWh, it will be displayed as follows:
[display]
[max]
[min]
2534 kW.h
32534. 810 2534 ( 1 )
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 26
5.10.- 4 - 20 mA outputs: CVM-BD-420-4 (4 analog outputs) and CVM-BD-420-8 (8 analog outputs)
With these outputs we can configure the CVM-BD420 to give an output of 4 - 20 mA d.c. or of 0 - 20 mA d.c. ( resolution of 4.000 points ) proportional to any of the parameters measured by the CVM-BD, with the ability of setting the scale (offset and full scale).
On the CVM-BD-420-.. screen following messages appear at this SET-UP point (provided the right module is connected to the equipment):
a.- Parameter choice:
dA 1 OUTPUT D/A No.1 Code xx
- "max" -- "min" keys: allow the selection of any parameter from 1 to 30, the 35, or
from 54 to 59.
- “display” key: validates the selected option and passes to the next setup screen.
b.- Selection of 0 - 20 mA or 4 - 20 mA :
dA 1 OUTPUT D/A Nr.1
Scal Scale :
4 - 20
- "display": to validate the selected option and pass to the next setup screen.
allows choosing a 0 - 20 mA
or 4 - 20 output ("max" or "min" key)
Parameter No.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 27
c.- Scale offset:
Value of the parameter that we assign as the zero of the scale.
dA 1 OUTPUT D/A No.1 Zero Zero of the scale: x.xxx
(four digits with floating decimal point)
allows choosing the zero of the scale
- "max" key: it allows modifying the value of the blinking value.
Every time it is pressed the number is increased.
- "min" key: it allows validating the blinking value and go to the next digit. NOTE : When you arrive at the last digit, you can move the position of the decimal
point with the "max" key.
- "display": to validate the selected option and pass to the next setup screen.
d.- Full scale: Value of the parameter to which we assign the 20 mA.
dA 1 OUTPUT D/A No.1 F.ESC Full scale: x.xxx
allows choosing the full scale (20 mA)
(four digits with floating decimal point)
Proceed as in the previous section.
- To access the next option, press "display": setup options for the rest of analog
outputs will appear up. Setup procedure is similar for any output.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 28
1.- Output calculation:
Resolution = 20 Zero .
F. scale - offset
MA = (( F. scale - offset ) x Resolution) + Zero MV = mA x ohms
- Maximum load is:
CVM-BD-420-4: ................400
CVM-BD-420-8: ................300
- The maximum allowable offset is a value equal to the 90% of the full scale.
-
Output of the power factor parameter ( P.F.):
0/4 mA ---------------------------- -------------------------20 mA
+0.00 Ind. 1.00 Cap. – 0.00
2.- Default full scale:
Offset & f. scale = defined by the
user
Zero = 0 mA or 4 mA
mV
(100 ohms)
= mA x 100
Parameter Condition Full scale ( 20 mA )
Voltages Primary < 500 Primary x 500 /secondary
(V) Primary > 500 Voltage primary
Currents (A) Current primary
Powers For one phase voltage primary x current primary / 1000
(kW) Three phase value voltage primary x current primary x 3 / 1000
Frequency (Hz) 65
P.F. 0.00
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 29
6.- TECHNICAL FEATURES
Power supply : see specifications on the CVM-BD-420-.. rear
- CVM-BD-420-..: Single phase 230 V a.c.
Voltage tolerance: +10 % / -15 % Frequency: 50 ... 60 Hz
Power consumption ..................... 6 VA
Operation temperature ................ 0 to 50º C
Measuring Circuits :
Rated voltage .... 500 V a.c. Phase - Neutral / 866 V a.c. between phases
Other voltages ............With appropriate voltage transformers
Rated current ..............In / 5 A (isolated input like ITF types)
Permanent overload .....1.2 In
Current input power .....0.6 VA
Maximum burden per 20 mA channel :
CVM-BD-420-4: ................400
CVM-BD-420-8: ................300
Accuracy class:
Voltage ...................................... 0.5 % of readout ± 2 digits
Current ...................................... 0.5 % of readout ± 2 digits
Power ......................................... 1 % of readout ± 2 digits
Test conditions :
- Errors due to Voltage T. and Current T. are not included
- Temperature between + 5 ºC and + 45 ºC
- Power factor between 0.5 and 1
- Measured values between 5 % ... 100 %
Constructive characteristics :
Box type : Self-extinguishing, plastic casing Connection : Metallic terminals with "posidraft" screws Fixing : Fitted onto symmetrical DIN 46277 (EN 50022) rail
Screw fixing (Passing hole 4,2 mm).
Frontal cover : Lexan Protection : Built-in relay : IP 41
Terminals : IP 20 Dimensions 140 x 70 x 110 mm ( 8 modules relay as per DIN 43 880) Safety Category II , as perEN-61010 Standards EN 60664, EN 61010-1, EN 61036, IEC 60801 , IEC 60571-1,
EN 50081-1, EN 50082-1, VDE 110 , UL 94
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 30
Dimensions :
45
140
110
70
7.- SAFETY CONSIDERATIONS
All installation specification described at the previous chapters named INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.
-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 31
8.- MAINTENANCE
The CVM-BD-420-.. does not require any special maintenance. No adjustment, maintenance or repairing action should be done over the instrument open and powered and, should those actions are essential, high-qualified operators must perform them. Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be immediately put out of service. The instrument’s design allow a quick replacement in case of any failure.
9.- TECHNICAL SERVICE
For any inquiry about the instrument performance or whether any failure happens, contact to CIRCUTOR’s technical service.
CIRCUTOR S.A. - Aftersales Service Vial Sant Jordi, s/n 08232 - Viladecavalls
tel - +34 - 93-745 29 00 fax - +34 - 93-745 29 14
e-mail: central@circutor.es
Loading...