This manual is issued to help all the CVM 96 users to install and use it in order
get the best from it. After receiving the unit, please check the following points:
(a) Does this device correspond to your order specifications?
(b) Check if any damage was done during the shipment process.
(c) Verify that it includes the correct instruction manual.
The manual you hold in your hands contains information and warnings
about the CVM 96 that the user should respect in order to guarantee a proper
operation of all the instrument functions and keep its safety conditions.
Before powering the instrument for the first time, verify following points:
(a) Power supply: see rear part of your CVM 96
Standard: 230 V a.c. Single-phase, Frequency: 50 ... 60 Hz
SDC Model : 24 .... 120 V c.c.
Other supply voltages, on request.
(b) Maximum measuring voltage:
Standard: 300 V a.c. phase-neutral / 520 V a.c. between phases
Other models: on request
CVM 96 – measuring 110V: 110 V a.c. phase-to-neutral / 190 V a.c. phase-to-phase
CVM 96 – measuring 500V: 500 V a.c. phase-to-neutral / 866 V a.c. phase-to-phase
(c) Maximum measurable current: Current transformer of In / 5 A a.c.
The CVM 96 power meter is a programmable measuring instrument, offering
several operation possibilities selectable in its SETUP option. Before power
supplying the instrument, read the CONNECTIONS and SETUP sections and
choose the most suitable operation mode for getting your desired data.
The CVM 96 is an instrument which measures, calculates and displays all the
main electrical parameters at any electrical network (balanced or not). The
measuring is true RMS value, through three a.c. voltage inputs and three a.c. current
inputs (from Current Transformers .../ 5A).
By means of an internal microprocessor it simultaneously measures:
Parameter Symbol L1L2 L3Average
Voltage (phase-neutral) V x x x
Voltage (phase-phase) V x x x
Current A x x x xx
Frequency Hz x
Active power kW x x x x
Reactive power L kvarL x x x x
Reactive power C kvarC x x x x
Apparent power xx
Power factor PF x x x x
Cos ϕ
Power demand Pd x
kW h energy x
kvarhL energy x
kvarhC energy x
Neutral current IN xx
Voltage THD % THD- V x x x
Current THD % THD- A x x x
Individual harmonic current
content (Up to the 15
Available: x: Display and communications xx: Communications
th
)
xx
xx xx xx
The CVM 96 delivers the visualization of above listed parameters by means of
three 4-digit, led type, displays. Up to 3 parameters can be simultaneously read in
the screen.
The manual you hold in your hands contains information and
warnings that the user should respect in order to guarantee a proper
operation of all the instrument functions and keep its safety
conditions. The instrument must not be powered and used until its
definitive assembly on the cabinet’s door.
Whether the instrument is not used as manufacturer’s specifications, the
protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents
external visible damages), the instrument must be immediately powered off. In this
case contact a qualified service representative.
3.1.- Installation.
Before powering the instrument for the first time, verify following points:
b.-Maximum voltage at the voltage measuring circuit:
Standard : 300 V a.c. phase-to-neutral / 520 V a.c. phase-to-phase
45 to 65 Hz
On request:
500 V a.c. phase-to-neutral / 866 V a.c. phase-to-phase
110 V a.c. phase-to-neutral / 190 V a.c. phase-to-phase
c.- Maximum allowable current : Current Transformer of In / 5 A a.c.
d.- Operation conditions :
- Operation temperature range: -10 to +50 ºC
- Humidity : 5 to 95 % R.H. non-condensing
e.- Safety : Designed to meet protection class III- 300 V a.c. as (EN 61010).
Mounting:
Instrument is to be mounted on panel (cut-out 92
+0.8
x 92
+0.8
mm, as per DIN
43 700). All connections keep inside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to
touching and cover opening actions or elements removal may allow accessing
dangerous parts. Therefore, the instrument must not be used until this is completely
installed.
The instrument must be connected to a power supply circuit protected with gl
type (IEC 269 ) or M type fuses rated between 0.5 and 2 A. This circuit should be
provided with a circuit breaker or any equivalent element to connect (ON) or
disconnect (OFF) the instrument from the power supply network. The supply and
measuring voltage circuits will be both connected through a wire with a minimum
cross-section of 1 mm2.
The line of the current transformer secondary will have a minimum crosssection of 2,5 mm2.
The instrument has three displays. Each one has also a LED type indicators
(red colour). Every led will be on according to the parameter presently shown in
screen.
When the CVM 96 is powered up, the display shows " xxxx ", so informing
about the program version and the SETUP. After some seconds, the analyzer is
ready for operation and shows one of the available screens. A led next to the shown
parameter is on.
Parameters on display can be switch by pressing the key. Leds on the
right or left indicate the parameters shown on screen at any moment.
When the first led (red) is on, it means that VOLTAGE values are shown on
screen, that is, the user can read the voltage of the phase L1 (V1), voltage of the
phase L2 (V2) and voltage of the phase L3 (V3).
Whether the key "" is press, the next led will be on, so indicating that for
this screen CURRENT values of each phase are now shown.
Pressing again the key "" , the next led will be on, and the screen will
shown following three parameters, and so successively.
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.