CIRCUTOR CVM144 User Manual

SUPPLY NETWORK ANALYZER
CVM-144
(Ver 6.11 and higher)
SERIES
( M98170101-03 / 03C)

CIRCUTOR S.A.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 1
CONTENTS page
1.- DELIVERY SPOT CHECK .......................................................................................................... 2
2.- MAIN FEATURES ....................................................................................................................... 3
3.- MODELS ..................................................................................................................................... 5
4.- INSTALLATION AND START-UP............................................................................................... 6
4.1.- Installation. .................................................................................................................... 6
4.2.- CVM-144 connection terminal arrangement (power supply connection terminal) ............................. 8
4.3.- CVM-144 connection terminal arrangement (Expansion card) ..................................... 9
4.4.- Connection drawing for the CVM-144 : ....................................................................... 14
5.- OPERATION MODE ................................................................................................................. 18
6.- SET-UP PROCEDURE ............................................................................................................. 20
6.1.- Phase-to-Phase or Phase-to-Neutral voltages ............................................................ 21
6.2.- Voltage display mode .................................................................................................. 21
6.3.- Voltage transformation ratio ........................................................................................ 22
6.4.- Current Transformer Primary ...................................................................................... 23
6.5.- Transformation ratio for the measurement of neutral and residual current................. 24
6.6.- Setting power demand utility screens.......................................................................... 26
6.7.- Initial screen setting..................................................................................................... 27
6.8.- Setting of the display shutdown time........................................................................... 27
6.9.- Clearing energy counters ............................................................................................ 28
6.10.- THD or D setting........................................................................................................ 29
6.11.- Additional screens when RELAY OUTPUTS (2 relays) are equipped ...................... 30
6.12.- Additional screens with 4 - 20 mA outputs y inputs ................................................... 37
7.- SPECIFICATIONS .................................................................................................................... 42
8.- SAFETY CONSIDERATIONS................................................................................................... 44
9.- MAINTENANCE ........................................................................................................................ 44
10.- TECHNICAL SERVICE ............................................................................................................. 44
11.- CVM-144 COMMUNICATIONS ................................................................................................ 45
11.1.- To take into account !: .............................................................................................. 45
11.2.- RS-485 type connection to a RS-232 type input of a PC .......................................... 46
11.3.- RS-232 type connection to a RS-232 type input of a PC .......................................... 47
11.4.- MODBUS © protocol ................................................................................................ 48
12.- APPENDIX A: Second SET-UP of the CVM-144 ..................................................................... 54
12.1.- Communication setting.............................................................................................. 54
12.2.- SET-UP locking or unlocking .................................................................................... 55
13.- APPENDIX B: Insertion of an expansion module into a CVM-144 unit..................................... 56
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 2
1.- DELIVERY SPOT CHECK
This manual is issued to help all the CVM-144 (Version 6.11 and higher) users
to install and use it in order get the best from it. After receiving the unit, please check the following points:
(a) Does this device correspond to your order specifications?
(b) Check if any damage was done during the shipment process.
(c) Verify that it includes the correct instruction manual.
The manual you hold in your hands contains information and warnings about the CVM-144 that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions.
Before powering the instrument for the first time, verify following points:
(a)
Power supply: see rear part of your CVM-144
 Standard: 230 V a.c. Single-phase, Frequency: 50 ... 60 Hz
 SDC Model : 24 .... 120 V c.c.
 Other supply voltages, on request.
(b) Maximum measuring voltage:
 Standard: 300 V a.c. phase-neutral / 520 V a.c. between phases
 Other models: on request
CVM144 - measuring 110V: 110 V a.c. phase-to-neutral /190 V a.c. phase-to-phase CVM144 - measuring 500V: 500 V a.c. phase-to-neutral /866 V a.c. phase-to-phase
(c) Maximum measurable current: Current transformer of In / 5 A a.c.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 3
2.- MAIN FEATURES
The CVM-144 power meter is a programmable measuring instrument, offering
several operation possibilities selectable in its SET-UP option. Before power supplying the instrument, read the CONNECTIONS and SET-UP sections and choose the most suitable operation mode for getting your desired data.
reset
The CVM-144 is an instrument which measures, calculates and displays all the main electrical parameters at any electrical network (balanced or not). The measuring is true RMS value, through three a.c. voltage inputs and three a.c. current inputs (from Current Transformers .../ 5A).
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 4
By means of an internal microprocessor it simultaneously measures:
Parameter Symbol L1 L2 L3 Average
Voltage (phase-neutral) V x x x Voltage (phase-phase) V x x x Current A x x x xx Frequency Hz x Active power kW x x x x Reactive power L kvarL x x x x Reactive power C
kvarL /(-C)
x x x x
Apparent power kVA xx Power factor PF x x x x
Cos ϕ
xx Power demand Pd x kW h energy x kvarhL energy x kvarhC energy x Neutral current IN x Voltage THD % THD- V x x x Current THD % THD- A x x x Individual harmonic
current content (Up to the 15
th
)
xx xx xx
Analog inputs Input xx Earth leakage (residual) current
Available: x: Display and communications xx: Communications
x
The CVM-144 delivers the visualization of above listed parameters by means of three 4-digit, led type, displays. Up to 3 parameters can be simultaneously read in the screen.
---------------------------------------------------------------------------------------------
OTHER FEATURES
- Low-size (144 x 144 mm), panel-mounting analyzer.
- True R.M.S. measuring system.
- Collection in memory of maximum and minimum values.
- Energy measurement (indication through a lighting led)
- RS-485 or RS-232 type communication to a PC (optional)
- Maximum demand determination: kW, kVA, AIII or line-current.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 5
3.- MODELS
Code Model
Current measurement
7 70 551 CVM-144 Shunts 7 70 552 CVM-144-ITF Isolated ITF
Code Expansion modules Card
7 70 570 Mod. CVM 144 C2 2 7 70 571 Mod. CVM 144 C2 Analogue 0571 2 7 70 572 Mod. CVM 144 C2-Currents 0572 2 7 70 569 Mod. CVM 144 C2 Digital 2 4 7 70 573 Mod. CVM 144 RS485-C2 0573 RS485 2 7 70 574 Mod. CVM 144 RS485-C2 Analogue 0574 RS485 2 7 70 575 Mod. CVM 144 RS485-C2-Currents 0575 RS485 2 7 70 579 Mod. CVM 144 RS485-C2 Digital 0579 RS485 2 4 7 70 576 Mod. CVM 144 RS232-C2 0576 RS232 2 7 70 577 Mod. CVM 144 RS232-C2 Analogue 0577 RS232 2 7 70 578 Mod. CVM 144 RS232-C2-Currents 0578 RS232 2 7 70 580 Mod. CVM 144 RS232-C2 Digital 0580 RS232 2 4
Communication
Relay outputs
Optionally 2 analog inputs and 2 analog outputs.
Digital inputs
Analogue inputs
3*
3*
3*
Analogue outputs
Measurement of
neutral and residual
currents
1*
X
1*
X
1*
X
Code Complete Kit Communications
7 70 591 CVM-144-ITF-RS485-C2 RS-485 2 Isolated ITF
Relay
Outputs
Current
inputs
Each CVM 144 supports as a maximum 1 expansion module
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 6
4.- INSTALLATION AND START-UP
The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered and used until its definitive assembly on the cabinet’s door.
If the instrument is not used as manufacturer’s specifications, the
protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents external visible damages), the instrument must be immediately powered off. In this case contact a qualified service representative.
4.1.- Installation.
Before powering the instrument for the first time, verify following points:
a.- Power supply: see rear part of your CVM-144
 Standard supply : Single-phase 230 V ∼ (a.c.)
- Frequency : 50 - 60 Hz
- Supply voltage tolerance : - 10 % / + 15
- Connection terminal : Terminals 1 - 2 (Power supply)
- Burden : 5 VA
 SDC Model : 0.24.... 120 V c.c. ( continua )
- Supply voltage tolerance : - 20 % / + 15
- Connection terminal : Terminals 1 - 2 (Power supply)
- Burden : 2,2 W
 On request: other voltages
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 7
b.-Maximum voltage at the voltage measuring circuit:
 Standard : 300 V a.c. phase-to-neutral/520 V a.c. phase-to-phase
45 to 65 Hz
 Other models on request :
CVM-144-measuring 500 V: 500 Va.c. phase-to-neutral/866 Va.c. phase-to-phase CVM-144-measuring 110 V: 110 Va.c. phase-to-neutral/190 Va.c. phase-to-phase
c.- Maximum allowable current : Current Transformer of In / 5 A a.c.
d.- Operation conditions :
- Operation temperature range : -10 to +50 ºC
- Humidity : 5 to 95 % R.H. non-condensing
- Altitude : below 2000 m
e.- Safety :
- Designed to meet protection class III- 300 V a.c. as (EN 61010).
- Protection against electric shock by class II double-isolation
Mounting:
+1
Instrument is to be mounted on panel (cut-out 138
x 138+1 mm, as per DIN
43 700). All connections keep inside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. Therefore, the instrument must not be used until this is completely installed.
The instrument must be connected to a power supply circuit protected with gl type (IEC 269 ) or M type fuses rated between 0.5 and 2 A. This circuit should be provided with a circuit breaker or any equivalent element to connect (ON) or disconnect (OFF) the instrument from the power supply network. The supply and measuring voltage circuits will be both connected through a wire with a minimum cross-section of 1 mm2.
The line of the current transformer secondary will have a minimum cross­section of 2,5 mm2.
P-NP
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 8
4.2.- CVM-144 connection terminal arrangement (power supply connection terminal)
(see lable on the rear part)
300 V
P2 P1L3P2 P1
L2
56
83
7
-P
300V
NL1VL2VV
9
520V
L3
CAT III
230 V
Power Supply
12
5A
I
n
/
P2
P1
L1
S2 S1 S2 S1 S2 S1
4101112
No. Terminal description No. Terminal description
1 2 3 4 5 6
*Power supply AL1 *Power supply AL2 IL1 S2 Current measurement IL1 S1 Current measurement IL2 S2 Current measurement IL2 S1 Current measurement
7
IL3 S2 Current measurement
8
IL3 S1 Current measurement
9
Neutral
10
VL1 Measurement
11
VL2 Measurement
12
VL3 Measurement
NOTE: Terminals 3, 5, 7 are internally connected to the 9 terminal (Neutral)
... / 5 A current inputs are isolated for the ITF model.
* Lower connection terminal (SDC Model)
Nº Descripción Borne
1 2 Supply voltage (+) d.c.
Supply voltage (-) d.c.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 9
4.3.- CVM-144 connection terminal arrangement (Expansion card)
(see lable on the rear part)
4.3.1.- Basic card (770 570, 770 573 and 770 576)
Description Card connection terminal arrangement
Mod CVM 144 -C2
(Code: 7 70 570)
Mod CVM 144 RS485-C2
(Code: 7 70 573)
Mod CVM 144 RS232-C2
(Code: 7 70 576)
Mod CVM 144 -C2 (Código: 770 570)
No Terminal
Mod CVM 144 RS485-C2
Mod CVM 144 RS232-C2
(Código: 770 573)
No Terminal description No Terminal description
description
13
No used
14
No used
15
No used
16
No used
17
No used
18
No used
19
No used
20
No used
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
13
14 15 16 17 18 19 20 21 22 23 24
No used No used No used No used No used RS-485 ( GND ) RS-485 ( - ) RS-485 ( + ) Relay RL2 output Relay RL2 common Relay RL1 output Relay RL1 common
13 14 15 16 17 18 19 20 21 22 23 24
(Código: 770 576)
No used No used No used No used No used RS-232 ( GND ) RS-232 (Rx) RS-232 (Tx) Relay RL2 output Relay RL2 common Relay RL1 output Relay RL1 common
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 10
4.3.2.- Card for analog Inputs/Outputs (7 70 571, 7 70574 and 7 70577)
Description Card connection terminal arrangement
Mod CVM 144 -C2-Analogue
(Code: 7 70 571)
Mod CVM 144 RS485-C2-Analogue
(Code: 7 70 574)
Mod CVM 144 RS232-C2-Analogue
(Code: 7 70 577)
Mod CVM 144
C2-Analogue
(Code: 7 70 571)
Mod CVM 144
RS485-C2-Analogue
(Code: 7 70 574)
Mod CVM 144
RS232-C2-Analogue
(Code: 7 70 577)
Terminal description Nº Terminal description Nº Terminal description
13
4-20 mA I/O common
14
4-20 mA D/A1 output
15
4-20 mA A/D3 input
16
4-20 mA A/D2 input
17
4-20 mA A/D1 input
18
No used
19
No used
20
No used
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
13
14 15 16 17 18 19 20 21 22 23 24
4-20 mA I/O common 4-20 mA D/A1 output 4-20 mA A/D3 input 4-20 mA A/D2 input 4-20 mA A/D1 input RS-485 (GND) RS-485 ( - ) RS-485 ( + ) Relay RL2 output Relay RL2 common Relay RL1 output Relay RL1 common
13
4-20 mA I/O common
14
4-20 mA D/A1 output
15
4-20 mA A/D3 input
16
4-20 mA A/D2 input
17
4-20 mA A/D1 input
18
RS-232 ( GND)
19
RS-232 ( Rx )
20
RS-232 ( Tx )
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 11
4.3.3.- Module for residual and neutral currents (770 572, 770 575 and 770578)
Description Lable in the expansion module connection terminal
13 14 15
Mod CVM 144 -C2-Currents
17 18 19 20
16
21 22
RL2
23 24
RL1
(Code: 7 70 572)
Mod CVM 144 RS485-C2-Currents
(Code: 7 70 575)
Mod CVM 144 RS232-C2-Currents
(Code: 7 70 578)
13 14 15
13 14 15
N
17 18 19 20
16
GND
I
N
17 18 19 20
16
I
N
(+)(-)
RS 485
250 V 3 A
21 22
250 V 3 A
21 22
RL2
250 V 3 A
23 24
RL1RL2
23 24
RL1
I
Mod CVM 144
C2-Currents
(Code: 7 70 572)
Mod CVM 144
RS485-C2-Currents
(Code: 7 70 575)
Mod CVM 144
RS232-C2-Currents
(Code: 7 70 578)
Nº Terminal description Nº Terminal description Nº Terminal description
13
Measur. residual current S1
14
Measur. residual current S2
15
Measur. residual current S2
16
Measur. neutral current S1
17
Measur. neutral current S2
18
Not used
19
Not used
20
Not used
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
(30 A)
(3 A)
13
14
15
16 17 18 19 20 21 22 23 24
Measur. residual current S1 Measur. residual current S2
(30 A)
Measur. residual current S2
(3 A)
Measur. neutral current S1 Measur. neutral current S2
RS-485 ( GND ) RS-485 ( - ) RS-485 ( + ) Relay RL2 output Relay RL2 common Relay RL1 output Relay RL1 common
13
Measur. residual current S1
14
Measur. residual current S2
15
Measur. residual current S2
16
Measur. neutral current S1
17
Measur. neutral current S2
18
RS-232 ( GND )
19
RS-232 ( Rx )
20
RS-232 ( Tx )
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
(30 A)
(3 A)
Notes:
For the measurement of the residual current (earth leakage current), the use of
transformers of the WG xx series is required. These transformers can be connected to the 3 A or 30 A rated input, depending on the needed measuring range.
For the measurement of the neutral current, the use of .../5A current transformers is
required.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 12
Connection diagram of the WG transformer (for residual current purposes)
One single WG series transformer can be use for the measurement of residual currents within the range to 3 A or to 30 A, jut depending on the arranged connection diagram.
The current input used for the
2S2 2S1
1S2 1S1
residual current measurement must agree with the input selected in the pertinent a Setup section (6.5.-)
The appropriate connection mode to execute the measurement of the residual current with the CVM-144 is shown in the below tables:
Measurement of residual current with a maximum value of 3 A (30 mA ... 3 A)
WG Transformer Mod CVM 144 ... -Currents
Terminal No. Description Terminal No. Description
1S1 1S2 2S1 2S2
Measuring winding S1 Measuring winding S2
Not used Not used
13 15
Residual current measur. S1 Residual current measur. S2
(3 A)
Measurement of residual current with a maximum value of 30 A (300 mA ... 30 A)
WG Transformer Mod CVM 144 ... -Currents
Terminal No. Description Terminal No. Description
1S1 1S2 2S1 2S2
Measuring winding S1 Measuring winding S2
Not used Not used
13 14
Residual current measur. S1 Residual current measur. S2
(30 A)
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 13
4.3.4.- Card for digital Inputs (7 70 579 and 7 70580)
Description Card connection terminal arrangement
Mod CVM 144 -C2-Digital
(Code: 770 569)
Mod CVM 144 RS485-C2-Digital
(Code: 7 70 579)
Mod CVM 144 RS232-C2-Digital
(Code: 7 70 580)
Mod CVM 144
C2-Digital
(Code: 7 70 569)
No Terminal description No Terminal description No Terminal description 13
digital inputs common
14
digital input IN4
15
digital input IN3
16
digital input IN2
17
digital input IN1
18
no used
19
no used
20
no used
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
Mod CVM 144
RS485-C2-Digital
(Code: 7 70 579)
13
digital inputs common
14
digital input IN4
15
digital input IN3
16
digital input IN2
17
digital input IN1
18
RS-485 ( GND)
19
RS-485 ( - )
20
RS-485 ( + )
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
Mod CVM 144
RS232-C2-Digital
(Code: 7 70 580)
13
digital inputs common
14
digital input IN4
15
digital input IN3
16
digital input IN2
17
digital input IN1
18
RS-232 ( GND)
19
RS-232 (Rx)
20
RS-232 (Tx)
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 14
4.4.- Connection drawing for the CVM-144 :
a.- Three-phase network.- 4 wires (low voltage) :
S1
P1
P2
S2
S1
P1
P2
S2
S1
L1
L2
P1
L3
N
P2
S2
1 2 3 4 5 6 7 8 9 10 11 12
A.C. POWER SUPPLY
PowerSupply (SDC Model)
Te rm i na l
1
2
Description + V d.c.
- V d.c.
VL3
VL2
VL1
N
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 15
b.-Three-phase network – 3 wires (low voltage):
P2
P1
L1
S2
1 2 3 4 5 6 7 8 9 10 11 12
S1
P2
S2
S1
P1
P2
S2
L2
P1
L3
S1
A.C. POWER SUPPLY
PowerSupply (SDC Model)
Te rm i na l
1
2
Description + V d.c.
- V d.c.
VL3
VL2
VL1
A
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 16
c.- Three-phase network - 3 wires (2 P.T. and 3 C.T.):
S1
P1
P2
S2
S1
P1
P2
S2
S1
P1
L1
L2
L3
B
A
a
a
b
B
b
P2
S2
A
a
B
b
1 2 3 4 5 6 7 8 9 10 11 12
VL3
VL2
A.C. POWER SU PPLY
PowerSupply (SDC Model)
Ter m in al
1 2
Description + V d.c.
- V d.c.
VL1
A
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 17
d.- Three-phase network - 3 wires (2 P.T. and 2 C.T.):
P2
S2
P1
S1
L1
L2
S1
P1
B
A
a
a
b
L3
B
b
P2
S2
A
a
B
b
1 2 3 4 5 6 7 8 9 10 11 12
VL3
VL2
A.C. POWER SUPPLY
PowerSupply (SDC Model)
Terminal
1 2
Description + V d.c.
- V d.c.
VL1
IMPORTANT REMARK! If power = -0.01 is shown for any of the phases
(codes 03, 09 and 15) and voltage and current are not zero for this phase, check out following points:
- Assure that L1, L2 and L3 phases coincide in voltage and current.
- Correct polarity? Reverse the current transformer placed at this phase.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 18
5.- OPERATION MODE
The instrument has three displays. Each one has also a LED type indicators (red colour). Every led will be on according to the parameter presently shown in screen.
When the CVM-144 is powered on, 2 screens with the indication of the program version and the hardware configuration.
If the message “EEPr Err.” is shown by display, it means that any problem on the hardware configuration has been detected. If this happens, please contact to the technical service.
After some seconds, the analyzer is ready for operation and shows one of the available screens. A led next to the shown parameter is on.
Parameters on display can be switch by pressing the key . Leds on the right or left indicate the parameters shown on screen at any moment.
When the first led (red) is on, it means that VOLTAGE values are shown on screen, that is, the user can read the voltage of the phase L1 (V1), voltage of the phase L2 (V2) and voltage of the phase L3 (V3).
Whether the key " " is press, the next led will be on, so indicating that for this screen CURRENT values of each phase are now shown.
Pressing again the key " " , the next led will be on, and the screen will shown following three parameters, and so successively.
Max
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 19
min
Pressing the "max" or "min" key, maximum or minimum values for the parameters being shown by display, respectively, appear in screen.
This function is only valid while you keep pressing the "max" or "min" key. If you stop pressing the key the instantaneous values will appear again after 5 seconds.
While showing maximum or minimum values the LED indicators will keep blinking.
reset
Pressing the "reset" key the system is reset. This is equivalent to switch off the power supply of the instrument. The maximum and minimum values recorded will be automatically deleted from the internal memory.
If you are in the set-up process and press the "reset" key, you exit it without saving any modification that you might have done (this event will depend on the set­up section that is accessed when the reset action is carried out) and reset of the system occurs.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 20
6.- SET-UP PROCEDURE
The set-up procedure of the CVM-144 is performed by means of several SET­UP options.
For accessing the set-up menu the keys max & min must be
simultaneously pressed once the instrument is at the main screen.
When accessing the SET-UP, the message "SET-UP unlo " (1) is shown for some seconds on screen, or, otherwise, the message "SET-UP loc" (2).
(1) Set-up UNLO (SET-UP unlocked ) : when the SET-UP is
accessed, configuration parameters can be either visualized and modified.
(2) Set-up LOC (SET-UP locked ) : when the SET-UP is accessed,
configuration parameters can be visualized but cannot be modified .
Once into the SET-UP, use the keyboard to select different options and enter required variables:
- The key
- The key MAX permits to select among different options in a menu, or to
increase a digit when a variable is being entered.
- The key MIN permits to move the cursor along the digits.
Different options are following shown in a sequential mode:
1. Choice of visualization of phase-to-neutral or phase-to-phase voltages
2. Voltage displaying format
3. Voltage transformation ratio.
4. Value of the current transformer primary : 1 a 10000 A
5. Value of the current primary value for the measurement of neutral and residual currents.
6. Power demand meter setting
7. Choice of default initial screen
8. Time for display shutdown
9. Deleting energy counters
10. Choice of harmonic distortion determination mode: d% or THD%
11. Alarms setting : RELAY 1 (OUT 1) & RELAY 2 (OUT 2)
12. Analog outputs and inputs setting
validates de value and pass to the next menu.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 21
6.1.- Phase-to-Phase or Phase-to-Neutral voltages
After the word "set" you will see on the three displays the voltages of the
phases L1, L2, L3.
U1 U12 U2 or U23 U3 U31
- Phase to Neutral Voltages: U1, U2, U3
- Phase to Phase Voltages : U12, U23, U31
a) To select one of the voltage options just press the green key "max" and
both options will appear alternately.
b) When you get in the display the desired option just press the "
" key to
validate it and access to the next set-up option.
6.2.- Voltage display mode
This option permits the user to select the voltage display mode. That way, the choice between viewing the voltage with one decimal digit or without decimals is user-programmable.
SEt SEt
Udec ó Udec
no YES
No decimals 1 decimal digit
c) To select one of the voltage options just press the green key "max" and
both options will appear alternately.
d) When you get in the display the desired option just press the " " key to
validate it and access to the next set-up option.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 22
6.3.- Voltage transformation ratio
6.3.1.- Voltage Transformer Primary
On the screen we read the word "SET U P" followed by 5 digits. They allow us setting the primary of the voltage transformer.
SET U P - -
- - -
a.- To write or modify the value just repeatedly press the "max" key and the blinking digit value will be increased.
b.- When the value on screen is the proper one, we can pass to the next digit by pressing the "min" key in order to modify the other values.
c.- When the blinking digit is the last one, pressing the "min" key we go back to the initial value: set values can be again modified.
d.- Press"
" to pass to the next setup option.
Note:
Maximum values of transformation ratios which are allowable to be set,
depend on the full-scale value of the measuring instrument. (see indications on the
rear side lable).
FULL-SCALE
VALUE
MAXIMUM ALLOWABLE
VALUE
110 V~ 99,999
300 V~ 70,000
500 V~ 40,000
- In case that a value higher than the maximum allowable value is validated
"
", the screen will blink and the previous set value will be kept in memory.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 23
6.3.2.- Voltage Transformer Secondary
We can now set the value of the secondary of the voltage transformer. Only three digits are available:
SET U S
- - -
Same process than in point 6.2.-:
- "max" key: Allows us modifying the value of the blinking digit. Each time it
is pressed the value is increased.
- "min" key: Allows us the validation of the blinking digit and going to the
next one.
- Press "
" to pass to the next setup option.
If the CVM144 is directly connected to the mains (without voltage transformer) the values of primary and secondary must be the same, for instance 00001/001.
6.4.- Current Transformer Primary
"SET A P" and five digits appear on screen allowing us to set the primary of the current transformer.
SET A P - -
- - -
1 A ... 10.000 A
a) To enter or modify the value of the C.T.'s primary, just repeatedly press "max" to
increase the value of the blinking digit.
b) When the value in screen is the required, pass to the next digit by pressing "min",
so that the whole value can be set.
c) When the last digit blinks, pressing then "min" the first digit is again accessed, so
that set value can be modified if required.
d) To access next set-up option press " ".
NOTES:
- The secondary of the current transformers is not programmable. It is
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 24
automatically set at 5 A (... / 5 A ac)
- The primary current value to be set is also limited by the following condition: The maximum allowable primary current value which can be set is defined by the fact that the multiplication of the primary voltage value by this primary current value cannot exceed 20,000,000.
6.5.- Transformation ratio for the measurement of neutral and residual current
This section is only applicable for the CVM-144 units equipped with the
module for residual and neutral current measurement (7 70 572, 7 70 575 & 7
70578)
6.5.1.- Primary of the current transformer for neutral current measur. (IN)
The screen shows the message "A_n P" and fixe numeric digits that permit the user to set the value of the current transformer for the neutral current measurement.
A_n P - -
- - -
1 A ... 10.000 A
a) To enter or modify the value of the C.T.'s primary, just repeatedly press "max" to
increase the value of the blinking digit.
b) When the value in screen is the required, pass to the next digit by pressing "min",
so that the whole value can be set.
c) When the last digit blinks, pressing then "min" the first digit is again accessed, so
that set value can be modified if required.
d) To access next set-up option press " ".
NOTES:
- The secondary of the current transformers is not programmable. It is automatically set at 5 A (... / 5 A a.c.)
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 25
6.5.2.- Residual current measuring range: 3 A or 30 A
You will view in screen the message "SET A_L". Set then the right measuring range of the residual current input to which the WG transformer has been connected..
Two possible values are available (the choice must coincide with the measuring transformer wiring): 3 A or 30 A.
SEt A_L
- - -
3 A or 30 A
a) To select the appropriate input / range just press the key "max", the value will
switch from one option to the other one.
b) To pass to the next option press "
".
NOTE :
For the measurement of the residual current (earth leakage current), the use of
transformers of the WG xx series is required. These transformers can be connected to the 3 A or 30 A rated input, depending on the needed measuring range.
For the measurement of the neutral current, the use of .../5A current transformers
is required.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 26
6.6.- Setting power demand utility screens.
Push the key " " and the following screens will appear by display:
1.- PARAMETER TO CONTROL ("Pd Code xx")
None Three phase active power kW III Three phase apparent power kVA III Average three-phase current AIII Single line current A1 – A2 – A3
00 16 34 36 A-PH
Value of power integrated during the programmed demand period.
2.- DEMAND PERIOD ( 1 to 60 min.) ("Pd Per xx")
3.- CLEAR MAXIMUM VALUE IN MEMORY
("CLr Pd xx") no or YES
Programming mode:
- "max" key: allows choosing the different available options.
- "min" key: allows the validation of the blinking digit and go forward to the
next digit (only for the "Pd Per xx" option).
- To pass to the next option press " ".
If you don't want to modify anything, just press the " " key three times without modifying any value.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 27
6.7.- Initial screen setting
This option allows choice among fixed or rotary screen:
a) Fixed screen (choice is switch just pressing
): choice the initial screen to be
shown when the CVM-144 is powered (or when the CVM-144 is reset).
b) Rotary screens: all screens are successively shown at intervals of 5 s.
This option is noticed by means of some leds:
SET dEF PAGE
- The key "max": permits to modify the selected page. The led of the selected
option will be on. Whether rotary screens option is selected, then all leds will be on.
- Press " " to validate the choice.
6.8.- Setting of the display shutdown time
Setting of the period of time to go by, from the moment that the CVM keyboard is not touched anymore, before the CVM display is automatically shut down (low consumption mode):
dISP OFF 05
Time to shutdown (Minutes)
When the display is shut down, a point at the bottom left corner of the CVM will keep blinking. The display will be automatically turned on when any CVM key is pressed.
- "max" key: to modify the value of the blinking value.
- "min" key: to validate the blinking value and go to the next digit.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 28
6.9.- Clearing energy counters
On display we see "CLR ENER no" (Clear energy counters).
- "max": To select "YES" or "no"
- " ": To validate the choice and pass to the following set-up option.
Display:
If any of the energies is programmed (kWh, kvarhL or kvarhC), it is displayed as follows:
Example : If the accumulated energy is 32.534,810 kWh, it will be displayed as follows:
max min
kWh MWh
Wh
3 2 MWh 2 5 3 4 kWh 8 1 0 Wh
max min
2534 kWh 32 MWh
810 Wh
Note : the energy counter range is limited at 999.999.999 Wh , that is, when the value of 1 GWh is reached, the counter is reset to zero.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 29
6.10.- THD or D setting
SET SET dHAR or dHAR
d
Thd
Two modes for the harmonic distortion calculation can be selected:
a) d % : total value of the harmonic distortion referred to the fundamental value.
b) Thd % : total value of the harmonic distortion referred to the R.M.S. value.
The selected option will be the one shown on screen.
- To select any option just press "max" to switch between the two available
options.
- Press "
" to validate the choice. Since all set-up options have been completed, the set-up is exited, all modifications are saved in memory, and the running mode automatically starts up.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 30
6.11.- Additional screens when RELAY OUTPUTS (2 relays) are equipped
With these outputs the CVM-144...C2 can be set to deliver:
A.- Pulse every certain kWh or kvarh (ENERGY). You can define the
value corresponding to the energy consumed for generating a pulse (0.5 s long): kWh / 1 pulse or kvarh / 1 pulse
B.- ALARM conditions: the parameter to be controlled, the maximum value,
the minimum value and the delay are user-definable for each relay output.
----------------------------------------------------------------------------------
On the CVM-144 screen following messages appear at this SET-UP option:
OUT 1 RELAY 1 CODE 00
Parameter No. (1)
Depending on the selected variable we will pass to a.- or b.- sections
In case that no parameter is wanted to be programmed set par. No. = 00.
Parameter Symbol
phase L1
Single voltage V 1 01 V 2 06 V 3 11 Current A 1 02 A 2 07 A 3 12 Active power kW 1 03 kW 2 08 kW 3 13 Reactive power Inductive/ Capacitive Power factor PF 1 05 PF 2 10 PF 3 15 % THD V THD V1 25 THD V2 26 THD V3 27 % THD A THD A1 28 THD A2 29 THD A3 30
kvarL 1
kvarC 1
Code Symbol
phase L2
04 kvarL 2
kvarC 2
Code Symbol
phase L3
09 kvarL 3
kvarC 3
Code
14
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 31
Parameter Symbol Code Parameter Symbol Code Three-phase active power kW III 16 Three-phase inductive power kvarL III 17 Three-phase power factor PF III 20
Three-phase capacitive power kvarC III 18 Frequency Hz 21 Active energy kWh 31 Ph-Ph voltage L1- L2 V 12 22 Reactive energy (inductive) kvarh. L 32 Ph-Ph voltage L2 - L3 V 23 23 Reactive energy (capacitive) kvarh. C 33 Ph-Ph voltage L3 - L1 V 31 24 Three phase apparent power kVA III 34 Power demand Pd 35 Power demand (L1) Pd 35* Three-phase current AIII 36 Power demand (L2) Pd 42* Neutral current IN 37 Power demand (L3) Pd 43* Analog input 1 Input 1 38 Analog input 2 Input 2 39 Analog input 3 Input 3 40
Residual (earth leakage)
Three-phase cos ϕ Cos ϕ
41
19
current
* This parameters are only enabled if the maximum demand by line current has been programmed
There are, besides, some parameters that refer to 3 phases at once. In case that any of these parameter is selected, then the alarm will be activated always one phase complies with alarm settings.
Parameter Symbol Code
Line-to-neutral voltages V1 or V2 or V3 90 Currents I1 or I2 or I3 91 Active powers kW1 or kW2 or kW3 92 Reactive powers kvar1 or kvar2 or kvar3 93 Power factors PF1 or PF2 or PF3 94 Line-to-line voltages V12 or V23 or V31 95 % THD V THDV1 or THDV2 or THDV3 96 % THD I THDI1 or THDI2 or THDI3 97
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 32
a.- If an ENERGY parameter is chosen: kWh (31), kvarhL (32) or kvarhC(33)
OUT 1 RELAY 1 PULS xxxx
kW / pulse (1)
(1) Value of energy in kW : four digits with floating decimal point
Set-up procedure:
- "max" key: to modify the value of the blinking value. Every time it is pressed the
value is increased.
- "min" key: to validate the blinking value and go to the next digit.
NOTE : When the last digit is reached, the position of the decimal can be move point with the "max" key.
Example for setting a 500 W / 1 pulse:
Firstly we enter the value, 0500, and following we place the decimal point at the right position with the "max" key 0.500 kW.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 33
- For accessing to the next option, press " ": set-up options for the second
relay will appear.
OUT 2 RELAY 2 CODE 00
Parameter value (2)
Act as before. Pressing again " " the set-up mode is exited.
b.- ALARM conditions (1 condition for each relay): If any other parameter (excepts for energies) is selected at (1), two outputs can be configured as alarms. For each output it is possible to set:
Any of the parameters measured by the CVM-144 MAXIMUM value MINIMUM value Delay for the conditions
These screens are successively displayed by the CVM-144 once the parameter has been selected ( for the set-up of each option proceed as in the Section a.-):
b.1.- Programming the maximum value to be controlled:
OUT 1 RELAY 1 AL hI
0.000
Maximum value
The key "max" will increase the value of the blinking digit (0,1...9, sign -- ). Use the key "min" to pass to the following digit.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 34
b.2.- Programming the minimum value to be controlled:
OUT 1 RELAY 1 AL LO
0.000
Minimum value
b.3.- Programming the delay:
OUT 1 RELAY 1 SEC Delay in seconds
0.000
maximum 9999 s
- Press " " to pass to the next option: the set-up for the second relay is
then shown:
OUT 2 RELAY 2 CODE 00
Parameter No. (1)
Proceed as before. Pressing again " " the set-up option exited.
---------------------------------------------------------------------------
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 35
ALARM ACTIVATION: Alarms operation depend on the set values of MAXIMUM and MINIMUM.
MIN +
MIN +
MIN --
MIN +
MIN --
MIN --
MAX + max > min
MAX + max < min
MAX +
MAX --
MAX -- max > min
MAX -- max < min
ON OFF ON
======
0 Min Max
OFF ON OFF
==============
0 Max Min
ON OFF ON
=======
Min 0 Max
OFF ON OFF
=============
Max 0 Min
ON OFF ON
=====
Min Max 0
OFF ON OFF
================
Max Min 0
ON = alarm activated ----------> relay closed
OFF = alarm deactivated ------> relay open
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 36
The DELAY set value is applied either to the connection or the disconnection when the alarm conditions occur.
User-definable units for the different parameters are:
Parameter Format Example
Voltage V 220.5 = 220.5 V
0220 = 220 V Current A 0150 = 150 A Powers kW, kvarL, kvarC 0.540 = 540 W
250.5 = 250.5 kW Energies kWh, kvarLh, kvarCh 0.500 kWh Power factor +/- x.xx - 0.70 Frequency xx.x 50.0 = 50 Hz
Output relay connection lay-out CVM-144...-C2 (2 relays ) :
Out1 Terminals Signal Out2 Terminals Signal
RELAY 1
23 - 24 N.O.
RELAY 2
21- 22 N.O.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 37
6.12.- Additional screens with 4 - 20 mA outputs y inputs
CVM-144 equipped with an “Analogue” type module provides 4 - 20 mA d.c.
or 0 - 20 mA d.c. inputs and outputs (inputs can also optionally be 0-10 V type).
6.12.1.- Additional screen with the 4 - 20 mA output
These can be programmed to obtain an output signal proportional to any of
the parameters measured by the CVM-144, including the ability of setting the
scale (offset and full-scale values).
On the CVM screen following messages appear at this SET-UP point
(provided the right module is connected to the equipment):
a.- Parameter choosing:
dA 1 OUTPUT D/A Nr.1 Code xx
Parameter No.
- "max" -- "min" keys: permits the user to choose any parameter measured by the
CVM-144 but the parameters referred to energies..
- "display" key: validates the selected option and passes to the next setup screen.
b.- Election of 0 - 20 mA or 4 - 20 mA
:
dA 1 OUTPUT D/A Nr.1
Scal Scale :
4 - 20
allows choosing a 0 - 20 mA
or 4 - 20 output ("max" or "min" key)
- "display": to validate the selected option and pass to the next setup screen.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 38
c.- Scale offset:
Value of the parameter that we assign as the zero of the scale.
dA 1 OUTPUT D/A Nr.1 Zero zero of the scale: x.xxx
allows choosing the zero of the scale
(four digits with floating decimal point)
- "max" key: it allows modifying the value of the blinking value.
- Every time it is pressed the number is increased.
- "min" key: it allows validating the blinking value and go to the next digit.
NOTE : When you arrive at the last digit, you can move the position of the
decimal point with the "max" key.
- "display": to validate the selected option and pass to the next setup screen.
d.- Full scale: Value of the parameter to which we assign the 20 mA.
dA 1
OUTPUT D/A Nr.1 F.ESC Full scale: x.xxx
allows choosing the full scale (20 mA)
(four digits with floating decimal point)
Proceed as in the previous section.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 39
- For passing to the next option, press "display": the setup for the second output
will appear (only if this output is available).
dA 2 OUTPUT D/A Nr.2 code xxxx
Proceed as in the previous sections.
1.- Output calculation:
Re
solution
=
OffsetscaleF
()
mV = mA x ohms mV
- Maximum load is of 500 (10 V - 20 mA)
Output of the power factor parameter ( PF):
).(
ZeroOffsetMesuresolutionmA += *Re
)20(
Zero
Offset & f. scale = defined by the user Zero = 0 mA or 4 mA
(100 ohms)
= mA x 100
0/4 mA ----------------------------------------------------- 20 mA
+0.00 Ind. / 1.00 / Cap. – 0.00
ó
–0.00 Cap. / 1.00 / Ind. + 0.00
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 40
6.12.2.- Additional screens with 4 - 20 mA inputs
The 4-20 mA analog inputs (which can also be optionally 0-10 V type) can be
set to obtain the processed signal either by display or through communications. To complete the analog inputs management, the user must program the scale values
(offset and full-scale value).
On the CVM screen following messages appear at this SET-UP point
(provided the right module is connected to the equipment):
b.- Election of 0 - 20 mA or 4 - 20 mA :
In 1 INPUT A/D Nr.1
Scal Scale :
4 - 20
allows choosing a 0 - 20 mA
or 4 - 20 input ("max" or "min" key)
* This choice is disable in case of 0-10 V type input card
- "display": to validate the selected option and pass to the next setup screen.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 41
c.- Scale offset:
Value of the parameter that we assign as the zero of the scale.
In 1 INPUT A/D Nr.1 Zero zero of the scale: x.xxx
allows choosing the zero of the scale
(four digits with floating decimal point)
- "max" key: it allows modifying the value of the blinking value.
- Every time it is pressed the number is increased.
- "min" key: it allows validating the blinking value and go to the next digit.
NOTE : When you arrive at the last digit, you can move the position of the
decimal point with the "max" key.
- "display": to validate the selected option and pass to the next setup screen.
d.- Full scale: Value of the parameter to which we assign the 20 mA.
In 1
INPUT A/D Nr.1 F.ESC Full scale: x.xxx
allows choosing the full scale (20 mA)
(four digits with floating decimal point)
Proceed as in the previous section.
- For passing to the next option, press "display": the setup for the second output
will appear (
only if this output is available).
Proceed similarly for all analog inputs.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 42
7.- SPECIFICATIONS
Power supply : see specifications on the rear part of the CVM-144
- CVM-144 : Single-phase 230 V a.c.
Voltage tolerance: +10 % / -15 %
Frequency: 50 ... 60 Hz
Burden ................................... 5 VA
- CVM-144.... SDC : Direct current 24 V ....... 120 V d.c.
Voltage tolerence: -20 % / +15 %
Burden .................................. 2.2 W
Operation temperature ......... -10 to 50 ºC
Humidity ……………………… 5 to 95 % R.H. non-condensing
Measuring Circuits :
Rated voltage .... 300 V a.c. Phase-to-Neutral / 520 V a.c. Phase-to-Phase
Frequency .................. 45 to 65 Hz
Rated current .............. In / 5 A (isolated inputs in the CVM-144-ITF... model)
Permanent overload .....1.2 In
Current input burden .....0.75 VA
Accuracy :
Voltage ...................................... 0.5 % of full scale ± 1 digits
Current ...................................... 0.5 % of full scale ± 1 digits
Powers ...................................... 1 % of full scale ± 1 digits
Test conditions :
- Errors due to C.T. are not included and direct voltage measurement
- Temperature between + 5 ºC and + 45 ºC
- Power factor between 0.5 and 1
- Full scale measure range 5 % ... 100 %
Mechanical Characteristics :
- Connection : pluggable connection terminal
- Case material Self-extinguishable, V0 plastic
- Protection Assembled unit (frontal ) : IP 55 Un-assembled unit (side and rear covers) : IP 31
- Dimensions 144 x 144 mm - depth: 84 mm
- Weight 0.400 kg
3
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 43
Relays characteristics: according to model
- Maximum switching load : 750 VA
- Maximum switching voltage : 250 V a.c.
- Maximum switching current : 3 A (Resistive)
7
- Mechanical endurance : 3 x 10
- Energy / alarms pulses : max. 1 pulse / s
operations
At full load: (250 V a.c. / 3 A )
- Electrical endurance : 1 x 10
5
operations
- Maximum operation cadence : 450 operations / hour
Analog output features: according to the model
- Output type : 0/4-20 mA
- Resolution : 4096 points (12 bits)
- Maximum impedance: 500
Analog input features: according to the model
0-20 mA inputs
- Resolution : 4000 points (12 bits)
- Input impedance : 200
Characteristics of residual currents measuring input: acc. to the model
- Transformer type: WG Series
- Current measuring range: Depending on used input. Input: 3A 30 mA - 3 A 30 A (300 mA – 30 A)
- Resolution: 4000 points (12 bits)
Safety .......... Category III - 300 V a.c. / 520 a.c., as per EN-61010
Protection against electric shock by class II double-isolation
Standards : IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 50081-1
EN 50082-1 , EN-61010-1
Dimensions :
144
78,5
5,
144
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 44
8.- SAFETY CONSIDERATIONS
All installation specification described at the previous chapters named INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.
9.- MAINTENANCE
The CVM-144 does not require any special maintenance. No adjustment, maintenance or repairing action should be done over the instrument open and powered and, should those actions are essential, high-qualified operators must perform them.
Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be immediately put our of service. The instrument’s design allow a quick replacement in case of any failure.
10.- TECHNICAL SERVICE
For any inquiry about the instrument performance or whether any failure happens, contact to CIRCUTOR’s technical service.
CIRCUTOR S.A. - After-sales service Vial Sant Jordi, s/n 08232 – Viladecavalls (SPAIN) Tel - + 34 93 745 29 00 fax - + 34 93 745 29 14
E-mail : central@circutor.es
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 45
11.- CVM-144 COMMUNICATIONS
One or some CVM-144... can be connected to a P.C.. With this system we can get all the parameters in one central point of reading. The CVM-144..., has a serial RS-485 or RS-232 type output (according to the model). If we connect more than one device to the same communication line (RS-485), we have to assign to each of them a different code or direction (from 01 to 255), since the P.C. needs the identification of every measuring point.
11.1.- To take into account !:
- PROTOCOL: MODBUS © (Question / Answer)
- CVM-144 DEFAULT CONFIGURATION : 001 / 9.600 / 8 bits / N / 1 bit
- Available baud rates: 1.200 - 2.400 - 4.800 - 9.600 - 19.200 bauds
- RS-485 type output:
-RS-485 connection will be carried out by means of a twisted and
screened cable, with a minimum of 3 wires, with a maximum distance
between the CVM-144 and the last peripheral of 1.200 m. The CVM-144 uses
a RS-485 communication bus allowing up to a maximum of 32 devices in
parallel (Multi-point bus) per port used in the PC.
----
- RS-232 type output:
-RS-232 connection will be carried out by means of a twisted and
screened cable, with a minimum of 3 wires, with a maximum distance
between the CVM-144 and the P.C. of 15 m.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 46
11.2.- RS-485 type connection to a RS-232 type input of a PC
RS-232
5
DB-9
7
A1
RS-485
7
2
512
3
5
A2
20 ( + )
19 ( - )
18 GND
CONVERTER RS-232 / RS-485
CVM-144
3
5
2
1
CVM-144
2
PC
*If the RS485/232 converter with RTS control ability (code 770208) is used, then
the pin 7 connection in the 232 side is not necessary to be done.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 47
11.3.- RS-232 type connection to a RS-232 type input of a PC
RS-232
RS-232
20 Tx
19 Rx
CVM-144
5
5
8
8
3
3
CVM-96
CVM-144
DB-9
DB-9
7
7
2
2
PC
PC
18 GND
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 48
11.4.- MODBUS © protocol
The CVM-144 analyzer can communicate by means of the MODBUS © protocol, as it is following described:
When the CVM-144 communicates with MODBUS protocol, it uses the RTU mode (Remote Terminal Unit ). Each 8-bits byte in a message contains two 4-bits hexadecimal characters.
The format for each byte in RTU mode is :
* Code : 8-bits binary, hexadecimal 0-9, A-F
Two hexadecimal characters
contained in each 8-bits field of the
message.
* Bits per Byte : 8 data bits
* Error Check Field : Cyclical Redundancy Check ( CRC ) .
MODBUS FUNCTIONS:
FUNCTION 01 Reading of relay state
FUNCTION 3 or 4 Reading of n Words (16 bits-2 bytes). This function
permits to read all the electrical parameters of the CVM-144. Each parameters is a 32-bits long, hence two words are required to inquiry for a parameter.
FUNCTION 05 Writing one relay
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 49
a.- Registers assigned to different parameters measured by the CVM-144:
MODBUS REGISTERS
PARAMETER
Phase voltage - V 1 V x 10 00-01 60-61 C0-C1 Current - A 1 mA 02-03 62-63 C2-C3 Active power - kW1 W 04-05 64-65 C4-C5 Reactive power - kvar 1 var 06-07 66-67 C6-C7 Power factor - PF1 PF x 100 08-09 68-69 C8-C9 Phase voltage - V 2 V x 10 0A-0B 6A-6B CA-CB Current - A 2 mA 0C-0D 6C-6D CC-CD Active power - kW2 W 0E-0F 6E-6F CE-CF Reactive power - kvar 2 var 10-11 70-71 D0-D1 Power factor - PF2 PF x 100 12-13 72-73 D2-D3 Phase voltage - V 3 V x 10 14-15 74-75 D4-D5 Current - A 3 mA 16-17 76-77 D6-D7 Active power - kW3 W 18-19 78-79 D8-D9 Reactive power - kvar 3 var 1A-1B 7A-7B DA-DB Power factor - PF3 PF x 100 1C-1D 7C-7D DC-DD
Three-phase active power-kWIII W 1E-1F 7E-7F DE-DF Three-phase inductive power-kvarL III var 20-21 80-81 E0-E1 Three-phase capacitive power-kvarC III var 22-23 82-83 E2-E3
Cos ϕ III Cos ϕx100
Three-phase power factor - PF III P.F.x100 26-27 86-87 E6-E7
Units
HEXA-DECIMAL (longs)
PRESENT
Value
MAXIMUM
Value
MINIMUM
Value
24-25 84-85 E4-E5
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 50
MODBUS REGISTERS
PARAMETER
Units
HEXA-DECIMAL (longs)
PRESENT
Value
MAXIMUM
Value
MINIMUM
Value
Frequency (L1) - Hz Hz x 10 28-29 88-89 E8-E9 Line voltage L1-L2 - V12 V x 10 2A-2B 8A-8B EA-EB Line voltage L2-L3 - V23 V x 10 2C-2D 8C-8D EC-ED Line voltage L3-L1 - V31 V x 10 2E-2F 8E-8F EE-EF %THD V 1 % x 10 30-31 90-91 F0-F1 %THD V 2 % x 10 32-33 92-93 F2-F3 %THD V 3 % x 10 34-35 94-95 F4-F5 %THD I 1 % x 10 36-37 96-97 F6-F7 %THD I 2 % x 10 38-39 98-99 F8-F9 %THD I 3 % x 10 3A-3B 9A-9B FA-FB
Active energy – kWh Wh 3C-3D Inductive reactive energy - kvarh L varLh 3E-3F Capacitive reactive energy - kvarh C varCh 40-41
Three phase apparent power kVA III 42-43 A2-A3 102-103 Power demand (L1) Pd 44-45 A4-A5 Three-phase current mA 46-47 A6-A7 106-107 Neutral current mA 48-49 A8-A9 108-109
Analog input 1* Analog input 2* Analog input 3*
Real value Real value Real value
4A-4B AA-AB 10A-10B 4C-4D AC-AD 10C-10D
4E-4F AE-AF 10E-10F Residual (earth leakage) current** mA 50-51 B0-B1 110-111 Power demand (L2) *** Pd 52-53 B2-B3 Power demand (L3)*** Pd 54-55 B4-B5
* Modbus addresses valid only for the analogue input modules (770574 & 770577)
** Modbus addresses valid only for the ”currents” module (770575 and 770578)
*** This parameters are only enabled if the maximum demand by line current has been
programmed
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 51
PARAMETER
Units
MODBUS REGISTERS
HEXA-DECIMAL (longs)
L1 L2 L3
Fundamental mA 1F4-1F5 212-213 230-231 Harmonic 2 % 1F6-1F7 214-215 232-233 Harmonic 3 % 1F8-1F9 216-217 234-235 Harmonic 4 % 1FA-1FB 218-219 236-237 Harmonic 5 % 1FC-1FD 21A-21B 238-239 Harmonic 6 % 1FE-1FF 21C-21D 23A-23B Harmonic 7 % 200-201 21E-21F 23C-23D Harmonic 8 % 202-203 220-221 23E-23F Harmonic 9 % 204-205 222-223 240-241 Harmonic 10 % 206-207 224-225 242-243 Harmonic 11 % 208-209 226-227 244-245 Harmonic 12 % 20A-20B 228-229 246-247 Harmonic 13 % 20C-20D 22A-22B 248-249 Harmonic 14 % 20E-20F 22C-22D 24A-24B Harmonic 15 % 210-211 22E-22F 24C-24D
NOTE: The maximum number of parameters (1 parameter = 1 word of 32 bits) that can be
read in one transmission is 20.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 52
EXAMPLE
INQUIRY 0A 04 00 00 00 0A 71 76
0A CVM-144 peripheral number, 10 in decimal 04 Reading function 00 00 Initial address (first register) 00 0A Number of registers to be read 7176 CRC character
ANSWER 0A 04 14 00 00 08 4D 00 00 23 28 00 00 0F A0 00 00 00
90 00 00 00 60 CB 2E 0A CVM-144 number , 10 in decimal 04 Reading function – the one use for the inquiry 14 Bytes received (20) 00 00 08 4D V 1x10 (register 00 Hex), in decimal 212.5 V 00 00 23 28 mA 1, in decimal 9000 mA 00 00 0F A0 W 1, in decimal 4000 W 00 00 00 90 varL 1, in decimal 144 varL 00 00 00 60 PF 1 x 100, in decimal 96 PF CB 2E CRC character
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 53
b.- Reading of digital inputs and outputs
Inquiry
Answer
Relay outputs Digital inputs
PP0100000008 CRC PP0100100004 CRC PP0101XXCRC
Where:PP peripheral No. XX (hexadecimal byte) translated to binary
b7 b6 b5 b4 b3 b2
bit Relay outputs Digital inputs
(770 579 y 770 580)
bo relay 1 Digital input 1 b1 relay 2 Digital input 2 b2 No used Digital input 3 b3 No used Digital input 4
c.- Write of digital outputs
This function is used to force the status of the CVM-144 digital outputs.
Output No. Message Answer
Relay 1 Relay 2
PP050000xx00 CRC PP050001xx00 CRC
PP050000xx00 CRC PP050001xx00 CRC
Where: PP peripheral No.
xx 00 Deactivate FF Activate
b1 b0
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 54
12.- APPENDIX A: Second SET-UP of the CVM-144
A second SET-UP menu is accessible in order to perform the configuration of
the CVM-144 with other features different from factory-supplied ones.
To access this menu proceed as follows:
- Being the CVM-144 powered off, simultaneously press " ", "max" and
"min" keys.
- Holding these keys pressed, powered the CVM-144 on.
When this option of the 2nd Setup menu is accessed, the following message
will be shown in screen during some seconds
Set
UP
Inic
12.1.- Communication setting
a.- Communication protocol: MODBUS
SET
PROT Protocol:
BUS
MODBUS (c) (BUS) protocol
- " " key: to validate the choice and pass to the next set-up screen:
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 55
b.- SETTING COMMUNICATION PARAMETERS
SET Cdef Default configuration NO
"max" key to switch from NO / YES
If YES is chosen: the configuration is 001 / 9600 / 8 bits / N / 1 bit
If NO is chosen, pressing " " following options successively appear:
- n PER : Peripheral No. 001 to 255
- Baud 1 : baud rate 1.200 – 2.400 – 4.800 – 9.600 – 19.200
- Parity : No, even, odd
- LEN : (length) 8 bits
- Stop bits : 1 or 2
12.2.- SET-UP locking or unlocking
SET Up Unlo
Loc (locked SET-UP) or Unloc (unlocked SET-UP)
Use the key "max" to modify the choice.
- Whether LOC is set, when the SET-UP is accessed, configuration
parameters can be visualized but cannot be modified.
- To modify the previously set option, a 4-figure password is required to be
entered (in case that this password is not correct, this blinks and the previous menu is again accessed).
PASSWORD : 1234
To exit this set-up mode, the key RESET can be pressed at any moment
(WARNING: if the set-up is exited by pressing the key RESET some last modifications might not be saved in memory) or reach the end of this set-up mode.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 56
13.- APPENDIX B: Insertion of an expansion module into a CVM-144 unit
The installation of an extension card into a CVM-144 unit must be accomplished just following below enumerated steps:
Checking the card acknowledgement
1. Check that the expansion card to be inserted into the CVM-144 will be acknowledged by the power meter.
Code Expansion module Board 5.xx 6.xx
7 70 570 Mod. CVM 144 C2 x 7 70 571 Mod. CVM 144 C2 Analogue 0571 x x 7 70 572 Mod. CVM 144 C2-Currents 0572 x 7 70 569 Mod. CVM 144 C2-Digital x 7 70 573 Mod. CVM 144 RS485-C2 0573 x x 7 70 574 Mod. CVM 144 RS485-C2-Analogue 0574 x x 7 70 575 Mod. CVM 144 RS485-C2-Currents 0575 x 7 70 579 Mod. CVM 144 RS485-C2-Digital 0579 x x 7 70 576 Mod. CVM 144 RS232-C2 0576 x x 7 70 577 Mod. CVM 144 RS232-C2 Analogue 0577 x x 7 70 578 Mod. CVM 144 RS232-C2-Currents 0578 x 7 70 580 Mod. CVM 144 RS232-C2 Digital 0580 x x
Removing the rear cover
Ranuras
2. Disconnect the meter out from the electric network.
3. Pull the connection terminals out.
4. Insert a plain-edge screwdriver into the bottom gaps (see right picture) and pull up the holding pieces until these are released.
5. Now, the cover should be easily removable with the hand.
Ranuras
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 57
Insertion of a new module
6. Place the expansion card into the side rail (The 2nd one from the top) checking that the components keep under the card.
7. Smoothly insert the card, checking that the frontal pins correctly fit into the connector, until the card keeps firmly fixed.
8. Cut the necessary removable pieces out from the rear cover to permit it to be properly hold.
9. Place the CVM-144 rear cover back.
Detection of a new expansion module
10. For versions 6.xx and later ones, the expansion module detection process is
automatically performed by the power meter.
Loading...