CIRCUTOR CVM144 User Manual

SUPPLY NETWORK ANALYZER
CVM-144
(Ver 6.11 and higher)
SERIES
( M98170101-03 / 03C)

CIRCUTOR S.A.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 1
CONTENTS page
1.- DELIVERY SPOT CHECK .......................................................................................................... 2
2.- MAIN FEATURES ....................................................................................................................... 3
3.- MODELS ..................................................................................................................................... 5
4.- INSTALLATION AND START-UP............................................................................................... 6
4.1.- Installation. .................................................................................................................... 6
4.2.- CVM-144 connection terminal arrangement (power supply connection terminal) ............................. 8
4.3.- CVM-144 connection terminal arrangement (Expansion card) ..................................... 9
4.4.- Connection drawing for the CVM-144 : ....................................................................... 14
5.- OPERATION MODE ................................................................................................................. 18
6.- SET-UP PROCEDURE ............................................................................................................. 20
6.1.- Phase-to-Phase or Phase-to-Neutral voltages ............................................................ 21
6.2.- Voltage display mode .................................................................................................. 21
6.3.- Voltage transformation ratio ........................................................................................ 22
6.4.- Current Transformer Primary ...................................................................................... 23
6.5.- Transformation ratio for the measurement of neutral and residual current................. 24
6.6.- Setting power demand utility screens.......................................................................... 26
6.7.- Initial screen setting..................................................................................................... 27
6.8.- Setting of the display shutdown time........................................................................... 27
6.9.- Clearing energy counters ............................................................................................ 28
6.10.- THD or D setting........................................................................................................ 29
6.11.- Additional screens when RELAY OUTPUTS (2 relays) are equipped ...................... 30
6.12.- Additional screens with 4 - 20 mA outputs y inputs ................................................... 37
7.- SPECIFICATIONS .................................................................................................................... 42
8.- SAFETY CONSIDERATIONS................................................................................................... 44
9.- MAINTENANCE ........................................................................................................................ 44
10.- TECHNICAL SERVICE ............................................................................................................. 44
11.- CVM-144 COMMUNICATIONS ................................................................................................ 45
11.1.- To take into account !: .............................................................................................. 45
11.2.- RS-485 type connection to a RS-232 type input of a PC .......................................... 46
11.3.- RS-232 type connection to a RS-232 type input of a PC .......................................... 47
11.4.- MODBUS © protocol ................................................................................................ 48
12.- APPENDIX A: Second SET-UP of the CVM-144 ..................................................................... 54
12.1.- Communication setting.............................................................................................. 54
12.2.- SET-UP locking or unlocking .................................................................................... 55
13.- APPENDIX B: Insertion of an expansion module into a CVM-144 unit..................................... 56
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 2
1.- DELIVERY SPOT CHECK
This manual is issued to help all the CVM-144 (Version 6.11 and higher) users
to install and use it in order get the best from it. After receiving the unit, please check the following points:
(a) Does this device correspond to your order specifications?
(b) Check if any damage was done during the shipment process.
(c) Verify that it includes the correct instruction manual.
The manual you hold in your hands contains information and warnings about the CVM-144 that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions.
Before powering the instrument for the first time, verify following points:
(a)
Power supply: see rear part of your CVM-144
 Standard: 230 V a.c. Single-phase, Frequency: 50 ... 60 Hz
 SDC Model : 24 .... 120 V c.c.
 Other supply voltages, on request.
(b) Maximum measuring voltage:
 Standard: 300 V a.c. phase-neutral / 520 V a.c. between phases
 Other models: on request
CVM144 - measuring 110V: 110 V a.c. phase-to-neutral /190 V a.c. phase-to-phase CVM144 - measuring 500V: 500 V a.c. phase-to-neutral /866 V a.c. phase-to-phase
(c) Maximum measurable current: Current transformer of In / 5 A a.c.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 3
2.- MAIN FEATURES
The CVM-144 power meter is a programmable measuring instrument, offering
several operation possibilities selectable in its SET-UP option. Before power supplying the instrument, read the CONNECTIONS and SET-UP sections and choose the most suitable operation mode for getting your desired data.
reset
The CVM-144 is an instrument which measures, calculates and displays all the main electrical parameters at any electrical network (balanced or not). The measuring is true RMS value, through three a.c. voltage inputs and three a.c. current inputs (from Current Transformers .../ 5A).
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 4
By means of an internal microprocessor it simultaneously measures:
Parameter Symbol L1 L2 L3 Average
Voltage (phase-neutral) V x x x Voltage (phase-phase) V x x x Current A x x x xx Frequency Hz x Active power kW x x x x Reactive power L kvarL x x x x Reactive power C
kvarL /(-C)
x x x x
Apparent power kVA xx Power factor PF x x x x
Cos ϕ
xx Power demand Pd x kW h energy x kvarhL energy x kvarhC energy x Neutral current IN x Voltage THD % THD- V x x x Current THD % THD- A x x x Individual harmonic
current content (Up to the 15
th
)
xx xx xx
Analog inputs Input xx Earth leakage (residual) current
Available: x: Display and communications xx: Communications
x
The CVM-144 delivers the visualization of above listed parameters by means of three 4-digit, led type, displays. Up to 3 parameters can be simultaneously read in the screen.
---------------------------------------------------------------------------------------------
OTHER FEATURES
- Low-size (144 x 144 mm), panel-mounting analyzer.
- True R.M.S. measuring system.
- Collection in memory of maximum and minimum values.
- Energy measurement (indication through a lighting led)
- RS-485 or RS-232 type communication to a PC (optional)
- Maximum demand determination: kW, kVA, AIII or line-current.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 5
3.- MODELS
Code Model
Current measurement
7 70 551 CVM-144 Shunts 7 70 552 CVM-144-ITF Isolated ITF
Code Expansion modules Card
7 70 570 Mod. CVM 144 C2 2 7 70 571 Mod. CVM 144 C2 Analogue 0571 2 7 70 572 Mod. CVM 144 C2-Currents 0572 2 7 70 569 Mod. CVM 144 C2 Digital 2 4 7 70 573 Mod. CVM 144 RS485-C2 0573 RS485 2 7 70 574 Mod. CVM 144 RS485-C2 Analogue 0574 RS485 2 7 70 575 Mod. CVM 144 RS485-C2-Currents 0575 RS485 2 7 70 579 Mod. CVM 144 RS485-C2 Digital 0579 RS485 2 4 7 70 576 Mod. CVM 144 RS232-C2 0576 RS232 2 7 70 577 Mod. CVM 144 RS232-C2 Analogue 0577 RS232 2 7 70 578 Mod. CVM 144 RS232-C2-Currents 0578 RS232 2 7 70 580 Mod. CVM 144 RS232-C2 Digital 0580 RS232 2 4
Communication
Relay outputs
Optionally 2 analog inputs and 2 analog outputs.
Digital inputs
Analogue inputs
3*
3*
3*
Analogue outputs
Measurement of
neutral and residual
currents
1*
X
1*
X
1*
X
Code Complete Kit Communications
7 70 591 CVM-144-ITF-RS485-C2 RS-485 2 Isolated ITF
Relay
Outputs
Current
inputs
Each CVM 144 supports as a maximum 1 expansion module
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 6
4.- INSTALLATION AND START-UP
The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered and used until its definitive assembly on the cabinet’s door.
If the instrument is not used as manufacturer’s specifications, the
protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents external visible damages), the instrument must be immediately powered off. In this case contact a qualified service representative.
4.1.- Installation.
Before powering the instrument for the first time, verify following points:
a.- Power supply: see rear part of your CVM-144
 Standard supply : Single-phase 230 V ∼ (a.c.)
- Frequency : 50 - 60 Hz
- Supply voltage tolerance : - 10 % / + 15
- Connection terminal : Terminals 1 - 2 (Power supply)
- Burden : 5 VA
 SDC Model : 0.24.... 120 V c.c. ( continua )
- Supply voltage tolerance : - 20 % / + 15
- Connection terminal : Terminals 1 - 2 (Power supply)
- Burden : 2,2 W
 On request: other voltages
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 7
b.-Maximum voltage at the voltage measuring circuit:
 Standard : 300 V a.c. phase-to-neutral/520 V a.c. phase-to-phase
45 to 65 Hz
 Other models on request :
CVM-144-measuring 500 V: 500 Va.c. phase-to-neutral/866 Va.c. phase-to-phase CVM-144-measuring 110 V: 110 Va.c. phase-to-neutral/190 Va.c. phase-to-phase
c.- Maximum allowable current : Current Transformer of In / 5 A a.c.
d.- Operation conditions :
- Operation temperature range : -10 to +50 ºC
- Humidity : 5 to 95 % R.H. non-condensing
- Altitude : below 2000 m
e.- Safety :
- Designed to meet protection class III- 300 V a.c. as (EN 61010).
- Protection against electric shock by class II double-isolation
Mounting:
+1
Instrument is to be mounted on panel (cut-out 138
x 138+1 mm, as per DIN
43 700). All connections keep inside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. Therefore, the instrument must not be used until this is completely installed.
The instrument must be connected to a power supply circuit protected with gl type (IEC 269 ) or M type fuses rated between 0.5 and 2 A. This circuit should be provided with a circuit breaker or any equivalent element to connect (ON) or disconnect (OFF) the instrument from the power supply network. The supply and measuring voltage circuits will be both connected through a wire with a minimum cross-section of 1 mm2.
The line of the current transformer secondary will have a minimum cross­section of 2,5 mm2.
P-NP
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 8
4.2.- CVM-144 connection terminal arrangement (power supply connection terminal)
(see lable on the rear part)
300 V
P2 P1L3P2 P1
L2
56
83
7
-P
300V
NL1VL2VV
9
520V
L3
CAT III
230 V
Power Supply
12
5A
I
n
/
P2
P1
L1
S2 S1 S2 S1 S2 S1
4101112
No. Terminal description No. Terminal description
1 2 3 4 5 6
*Power supply AL1 *Power supply AL2 IL1 S2 Current measurement IL1 S1 Current measurement IL2 S2 Current measurement IL2 S1 Current measurement
7
IL3 S2 Current measurement
8
IL3 S1 Current measurement
9
Neutral
10
VL1 Measurement
11
VL2 Measurement
12
VL3 Measurement
NOTE: Terminals 3, 5, 7 are internally connected to the 9 terminal (Neutral)
... / 5 A current inputs are isolated for the ITF model.
* Lower connection terminal (SDC Model)
Nº Descripción Borne
1 2 Supply voltage (+) d.c.
Supply voltage (-) d.c.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 9
4.3.- CVM-144 connection terminal arrangement (Expansion card)
(see lable on the rear part)
4.3.1.- Basic card (770 570, 770 573 and 770 576)
Description Card connection terminal arrangement
Mod CVM 144 -C2
(Code: 7 70 570)
Mod CVM 144 RS485-C2
(Code: 7 70 573)
Mod CVM 144 RS232-C2
(Code: 7 70 576)
Mod CVM 144 -C2 (Código: 770 570)
No Terminal
Mod CVM 144 RS485-C2
Mod CVM 144 RS232-C2
(Código: 770 573)
No Terminal description No Terminal description
description
13
No used
14
No used
15
No used
16
No used
17
No used
18
No used
19
No used
20
No used
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
13
14 15 16 17 18 19 20 21 22 23 24
No used No used No used No used No used RS-485 ( GND ) RS-485 ( - ) RS-485 ( + ) Relay RL2 output Relay RL2 common Relay RL1 output Relay RL1 common
13 14 15 16 17 18 19 20 21 22 23 24
(Código: 770 576)
No used No used No used No used No used RS-232 ( GND ) RS-232 (Rx) RS-232 (Tx) Relay RL2 output Relay RL2 common Relay RL1 output Relay RL1 common
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 10
4.3.2.- Card for analog Inputs/Outputs (7 70 571, 7 70574 and 7 70577)
Description Card connection terminal arrangement
Mod CVM 144 -C2-Analogue
(Code: 7 70 571)
Mod CVM 144 RS485-C2-Analogue
(Code: 7 70 574)
Mod CVM 144 RS232-C2-Analogue
(Code: 7 70 577)
Mod CVM 144
C2-Analogue
(Code: 7 70 571)
Mod CVM 144
RS485-C2-Analogue
(Code: 7 70 574)
Mod CVM 144
RS232-C2-Analogue
(Code: 7 70 577)
Terminal description Nº Terminal description Nº Terminal description
13
4-20 mA I/O common
14
4-20 mA D/A1 output
15
4-20 mA A/D3 input
16
4-20 mA A/D2 input
17
4-20 mA A/D1 input
18
No used
19
No used
20
No used
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
13
14 15 16 17 18 19 20 21 22 23 24
4-20 mA I/O common 4-20 mA D/A1 output 4-20 mA A/D3 input 4-20 mA A/D2 input 4-20 mA A/D1 input RS-485 (GND) RS-485 ( - ) RS-485 ( + ) Relay RL2 output Relay RL2 common Relay RL1 output Relay RL1 common
13
4-20 mA I/O common
14
4-20 mA D/A1 output
15
4-20 mA A/D3 input
16
4-20 mA A/D2 input
17
4-20 mA A/D1 input
18
RS-232 ( GND)
19
RS-232 ( Rx )
20
RS-232 ( Tx )
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 11
4.3.3.- Module for residual and neutral currents (770 572, 770 575 and 770578)
Description Lable in the expansion module connection terminal
13 14 15
Mod CVM 144 -C2-Currents
17 18 19 20
16
21 22
RL2
23 24
RL1
(Code: 7 70 572)
Mod CVM 144 RS485-C2-Currents
(Code: 7 70 575)
Mod CVM 144 RS232-C2-Currents
(Code: 7 70 578)
13 14 15
13 14 15
N
17 18 19 20
16
GND
I
N
17 18 19 20
16
I
N
(+)(-)
RS 485
250 V 3 A
21 22
250 V 3 A
21 22
RL2
250 V 3 A
23 24
RL1RL2
23 24
RL1
I
Mod CVM 144
C2-Currents
(Code: 7 70 572)
Mod CVM 144
RS485-C2-Currents
(Code: 7 70 575)
Mod CVM 144
RS232-C2-Currents
(Code: 7 70 578)
Nº Terminal description Nº Terminal description Nº Terminal description
13
Measur. residual current S1
14
Measur. residual current S2
15
Measur. residual current S2
16
Measur. neutral current S1
17
Measur. neutral current S2
18
Not used
19
Not used
20
Not used
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
(30 A)
(3 A)
13
14
15
16 17 18 19 20 21 22 23 24
Measur. residual current S1 Measur. residual current S2
(30 A)
Measur. residual current S2
(3 A)
Measur. neutral current S1 Measur. neutral current S2
RS-485 ( GND ) RS-485 ( - ) RS-485 ( + ) Relay RL2 output Relay RL2 common Relay RL1 output Relay RL1 common
13
Measur. residual current S1
14
Measur. residual current S2
15
Measur. residual current S2
16
Measur. neutral current S1
17
Measur. neutral current S2
18
RS-232 ( GND )
19
RS-232 ( Rx )
20
RS-232 ( Tx )
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
(30 A)
(3 A)
Notes:
For the measurement of the residual current (earth leakage current), the use of
transformers of the WG xx series is required. These transformers can be connected to the 3 A or 30 A rated input, depending on the needed measuring range.
For the measurement of the neutral current, the use of .../5A current transformers is
required.
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 12
Connection diagram of the WG transformer (for residual current purposes)
One single WG series transformer can be use for the measurement of residual currents within the range to 3 A or to 30 A, jut depending on the arranged connection diagram.
The current input used for the
2S2 2S1
1S2 1S1
residual current measurement must agree with the input selected in the pertinent a Setup section (6.5.-)
The appropriate connection mode to execute the measurement of the residual current with the CVM-144 is shown in the below tables:
Measurement of residual current with a maximum value of 3 A (30 mA ... 3 A)
WG Transformer Mod CVM 144 ... -Currents
Terminal No. Description Terminal No. Description
1S1 1S2 2S1 2S2
Measuring winding S1 Measuring winding S2
Not used Not used
13 15
Residual current measur. S1 Residual current measur. S2
(3 A)
Measurement of residual current with a maximum value of 30 A (300 mA ... 30 A)
WG Transformer Mod CVM 144 ... -Currents
Terminal No. Description Terminal No. Description
1S1 1S2 2S1 2S2
Measuring winding S1 Measuring winding S2
Not used Not used
13 14
Residual current measur. S1 Residual current measur. S2
(30 A)
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 13
4.3.4.- Card for digital Inputs (7 70 579 and 7 70580)
Description Card connection terminal arrangement
Mod CVM 144 -C2-Digital
(Code: 770 569)
Mod CVM 144 RS485-C2-Digital
(Code: 7 70 579)
Mod CVM 144 RS232-C2-Digital
(Code: 7 70 580)
Mod CVM 144
C2-Digital
(Code: 7 70 569)
No Terminal description No Terminal description No Terminal description 13
digital inputs common
14
digital input IN4
15
digital input IN3
16
digital input IN2
17
digital input IN1
18
no used
19
no used
20
no used
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
Mod CVM 144
RS485-C2-Digital
(Code: 7 70 579)
13
digital inputs common
14
digital input IN4
15
digital input IN3
16
digital input IN2
17
digital input IN1
18
RS-485 ( GND)
19
RS-485 ( - )
20
RS-485 ( + )
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
Mod CVM 144
RS232-C2-Digital
(Code: 7 70 580)
13
digital inputs common
14
digital input IN4
15
digital input IN3
16
digital input IN2
17
digital input IN1
18
RS-232 ( GND)
19
RS-232 (Rx)
20
RS-232 (Tx)
21
Relay RL2 output
22
Relay RL2 common
23
Relay RL1 output
24
Relay RL1 common
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 14
4.4.- Connection drawing for the CVM-144 :
a.- Three-phase network.- 4 wires (low voltage) :
S1
P1
P2
S2
S1
P1
P2
S2
S1
L1
L2
P1
L3
N
P2
S2
1 2 3 4 5 6 7 8 9 10 11 12
A.C. POWER SUPPLY
PowerSupply (SDC Model)
Te rm i na l
1
2
Description + V d.c.
- V d.c.
VL3
VL2
VL1
N
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 15
b.-Three-phase network – 3 wires (low voltage):
P2
P1
L1
S2
1 2 3 4 5 6 7 8 9 10 11 12
S1
P2
S2
S1
P1
P2
S2
L2
P1
L3
S1
A.C. POWER SUPPLY
PowerSupply (SDC Model)
Te rm i na l
1
2
Description + V d.c.
- V d.c.
VL3
VL2
VL1
A
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 16
c.- Three-phase network - 3 wires (2 P.T. and 3 C.T.):
S1
P1
P2
S2
S1
P1
P2
S2
S1
P1
L1
L2
L3
B
A
a
a
b
B
b
P2
S2
A
a
B
b
1 2 3 4 5 6 7 8 9 10 11 12
VL3
VL2
A.C. POWER SU PPLY
PowerSupply (SDC Model)
Ter m in al
1 2
Description + V d.c.
- V d.c.
VL1
A
----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 17
d.- Three-phase network - 3 wires (2 P.T. and 2 C.T.):
P2
S2
P1
S1
L1
L2
S1
P1
B
A
a
a
b
L3
B
b
P2
S2
A
a
B
b
1 2 3 4 5 6 7 8 9 10 11 12
VL3
VL2
A.C. POWER SUPPLY
PowerSupply (SDC Model)
Terminal
1 2
Description + V d.c.
- V d.c.
VL1
IMPORTANT REMARK! If power = -0.01 is shown for any of the phases
(codes 03, 09 and 15) and voltage and current are not zero for this phase, check out following points:
- Assure that L1, L2 and L3 phases coincide in voltage and current.
- Correct polarity? Reverse the current transformer placed at this phase.
Loading...
+ 40 hidden pages