Follow the warnings described in this manual with the symbols shown below.
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a speci c point.
If you must handle the unit for its installation, start-up or maintenance, the following
should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage
to the unit. In particular, handling with voltages applied may result in electric shock, which may
cause death or serious injury to personnel. Defective installation or maintenance may also
lead to the risk of re.
Read the manual carefully prior to connecting the unit. Follow all installation and maintenance
instructions throughout the unit’s working life. Pay special attention to the installation standards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can
result in injury or damage to the unit and /or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior noti cation.
DISCLAIMER
CIRCUTOR, SA reserves the right to make modi cations to the device or the unit speci ca-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device
speci cations and the most updated manuals.
4�5�2� ALARM DATABASE �������������������������������������������������������������������������������������������������������������������������16
4�6�- WEB SERVER �����������������������������������������������������������������������������������������������������������������������������������������16
4�6�1� HOME SCREEN ��������������������������������������������������������������������������������������������������������������������������������16
4�6�2� MAIN SCREEN ��������������������������������������������������������������������������������������������������������������������������������� 18
5�1�- INSTALLATION OF THE UNIT ����������������������������������������������������������������������������������������������������������������� 73
5�1�1� PRELIMINARY RECOMMENDATIONS��������������������������������������������������������������������������������������������73
7�- CIRLAMP NODE DALI �����������������������������������������������������������������������������������������������������������������������������������82
7�1�- INSTALLATION OF THE UNIT ����������������������������������������������������������������������������������������������������������������� 82
9�- TECHNICAL FEATURES ��������������������������������������������������������������������������������������������������������������������������������90
10�- MAINTENANCE AND TECHNICAL SERVICE ����������������������������������������������������������������������������������������������99
11�- GUARANTEE �������������������������������������������������������������������������������������������������������������������������������������������������99
12�- CE CERTIFICATE ���������������������������������������������������������������������������������������������������������������������������������������� 100
Instruction Manual
5
REVISION LOG
DateRevisionDescription
09/14M029B01-03-14AInitial Version
01/15M029B01-03-15AIntroduction of the CirLAMP Nodo DALI
07/15M029B01-03-15BChanges in the following sections: 9.2. - 9.3. - 9.4.
CirLAMP system
Table 1: Revision log�
NB: The images of the units are solely for the purpose of illustration and may differ from the
original unit.
6
Instruction Manual
CirLAMP system
1�- VERIFICATION UPON RECEPTION
Check the following points upon receiving the unit:
a) The unit meets the specications described in your order.
b) The unit has not suffered any damage during transport.
c) Perform an external visual inspection of the unit prior to switching it on.
d) Check that it has been delivered with the following:
CirLAMP Manager unit:
- An installation guide.
- Anchors for DIN rail.
- Six fastening pins.
- Two connectors.
CirLAMP Node unit:
- An installation guide.
M8I8O unit:
- An installation guide.
- Anchors for DIN rail.
- Six fastening pins.
- Two connectors.
If any problem is noticed upon reception, immediately contact the transport
company and/or CIRCUTOR's after-sales service.
2�- PRODUCT DESCRIPTION
The CirLAMP system enables smart management of street lights, increasing efciency by reducing energy consumption and creating tools to help the user with problem diagnosis and light
maintenance.
The system comprises:
CirLAMP manager + CirLAMP node
CirLAMP Manager is the system manager; it communicates with the CirLAMP Nodes installed
at each light point of the public lighting system via low voltage cables using the DCSK PLC (Power Line Communication) protocol.
Instruction Manual
7
The unit features:
- A conguration web server, where the user can congure all the programming parameters for each light point.
- PLC (Power Line Communication) with the nodes on CENELEC Band B.
- A database for 1000 nodes, with capacity to store 1 million logs.
- An astronomical clock to switch each light point on and off (compatible with expansion
module M8I8O).
- 11 indicator LEDs.
CirLAMP Manager can be expanded with 1 expansion module:
M8I8O, expansion module with eight inputs and eight outputs.
CirLAMP system
The CirLAMP Nodes are regulating units that are installed at each light point.
They measure the main electrical parameters (voltage, current, active power, reactive power)
independently.
There are two CirLAMP Node models depending on the ballast:
CirLAMP Node DN, a regulating unit for lighting with electronic ballasts or bi-level
drivers.
CirLAMP Node 1 ��� 10V, a regulating unit for lighting with electronic ballasts or drivers
with a regulation range from 1 to 10V.
CirLAMP Node DALI, a regulating unit for lighting with electronic ballasts or drivers
with a DALI communications.
8
Instruction Manual
CirLAMP system
The units include:
- PLC (Power Line Communication) with the CirLAMP Manager on CENELEC Band B.
- Systems to detect a burnt out lamp, an open capacitor and a ashing lamp, and to generate an alarm.
- (CirLAMP Node DN model) Relay output with ON/OFF control.
- (CirLAMP Node DN model) Relay output to control the bi-level ballasts.
- ( CirLAMP Node 1 ��� 10V model) 1 to 10V output to control ballasts with a regulation
range from 1 to 10V.
- (CirLAMP Node DALI model) DALI communications protocol to control ballasts .
3�- OPERATING PRINCIPLE
With the CirLAMP system it is possible to detect lighting anomalies, for example, burnt out
light bulbs, a blinking lamp, open capacitor, or control the useful life of each lamp, to ensure
correct maintenance of installations. When the CirLAMP system detects an incident, it sends
an email with detailed information.
To control lighting maintenance, the CirLAMP Manager has:
PLC communication on CENELEC Band B with a DCSK system.
Light point management through access by location.
(CirLAMP NODE Location application)
Possibility of sending emails when a fault or incident is detected.
Management of tasks and conguration orders sent to the CirLAMP Nodes�
Regular reading of the status of alarms, voltage and powers.
Memory event log.Ability to automatically download event les
Astronomical clock to switch each light point on and off.
(M8I8O Expansion module)
Alarm management and external event control with the input and output module.
(M8I8O Expansion module).
Instruction Manual
9
CirLAMP system
4�- CirLAMP Manager
4.1.- INSTALLATION OF THE UNIT
4�1�1� PRELIMINARY RECOMMENDATIONS
In order to use the unit safely, it is critical that individuals who handle it follow
the safety measures set out in the standards of the country where it is being
used, use the necessary personal protective equipment, and pay attention to
the various warnings indicated in this instruction manual.
The CirLAMP Manager unit must be installed by authorised and qualied staff.
The power supply plug must be disconnected before handling, altering the connections or
replacing the unit. It is dangerous to handle the unit while it is powered.
Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal
injury and damage to installations.
The manufacturer of the unit is not responsible for any damage resulting from failure by the
user or installer to observe the warnings and/or recommendations set out in this manual, nor
for damage resulting from the use of non-original products or accessories or those made by
other manufacturers.
If an anomaly or malfunction is detected in the unit, do not use it to perform any operation.
The unit must be disconnected from any power supply before carrying out any
maintenance or repairs, or handling any of the unit's connections.
Please contact the after-sales service if you suspect that there is an operational
fault in the unit.
4�1�2� INSTALLATION
The CirLAMP Manager unit must be installed on an electric panel or enclosure, attached to a
DIN rail (IEC 60715).
10
Two DIN rail brackets are supplied with the unit and must be installed on the unit before insta-
lling it on the electric panel.
To do so, follow these steps:
Instruction Manual
CirLAMP system
1�- Insert the rst bracket, as shown in Figure 1�
Figure 1: DIN rail brackets installation ( step 1)�
2�- Insert the second bracket in the rst bracket, Figure 2.
Figure 2: DIN rail brackets installation ( step 2)�
3�- Push the brackets into the rail until fully installed,Figure 3.
Figure 3: DIN rail brackets installation ( step 3)�
Terminals, opening covers or removing elements can expose parts that are
hazardous to the touch while the unit is powered. Do not use the unit until it is
fully installed.
The unit must be connected to a power circuit that is protected with gL fuses (IEC 269) or
M fuses, with a rating of 1 to 2 A. It must be tted with a circuit breaker or equivalent device
for disconnecting the unit from the power supply mains.
Instruction Manual
11
4�1�3� UNIT TERMINALS
1: L1, PLC connection L15: L, Auxiliary power supply
2: L2, PLC connection L26: N, Auxiliary power supply
PLC POWERPart of the connected PLC.
PLC>>CPUCommunication from the PLC to the CirLAMP Manager.
PLC<<CPUCommunication from the CirLAMP Manager to the PLC.
TX PLCSending frames.
RX PLCReceiving frames.
CPU POWERCirLAMP Manager connected.
ACTIVITYThe unit is performing a task.
ALARMAn alarm has been activated.
PLC DATAReceiving frames.
ETH�LINKThe Ethernet port is connected.
ETH�ACTEthernet port activity.
14
Instruction Manual
Restaurant
23
bakery
Restaurant
23
bakery
Restaurant
23
bakery
Restaurant
23
bakery
Restaurant
23
bakery
Restaurant
23
bakery
Restaurant
23
bakery23bakery
Restaurant
23
bakery
CirLAMP system
4.3.- PLC
The CirLAMP Manager uses PLC technology to communicate with the nodes (CirLAMP Nodes) through the electrical network.
PLC (Power Line Communications) transfers data via the electrical network using advanced
modulation technology.
The PLC frequency bands are dened by different committees: FCC for North America and
Canada, ARIB for Asia and Japan and CENELEC for Europe.
The CirLAMP Manager works on Band B, from 95kHz to 125kHz, dened by CENELEC.
(European Committee for Electrotechnical Standardization).
PC
CIRLAMP
Manager
Comunicaciones PLC
Figure 7:Connection of a CirLAMP system via PLC�
Bombilla
Balasto/Driver
CIRLAMP
Nodo
F N
Control
4.4.- ETHERNET
The unit has an Ethernet port (terminal 7 in Figure 4), which can exchange information bidirectionally through the web server and transfer les through FTP, using TCP/IP type communications.
Instruction Manual
15
4.5.- DATABASES
CirLAMP Manager has two databases:
4�5�1� MEASUREMENTS DATABASE
The measurements database comprises the following features:
A database for 1000 light points, with capacity to store 1 million logs.
Hardware: non-volatile memory without battery.
Non-volatile memory write policy to save maximum write cycles on FLASH memory.
Delete policy for oldest information.
Automatic node registration.
Automatic node withdrawal.
4�5�2� ALARM DATABASE
CirLAMP system
The alarm database comprises the following features:
Database for each light point with capacity for 50,000 logs.
Hardware: non-volatile memory without battery.
Non-volatile memory write policy to save maximum write cycles on FLASH memory.Delete policy for oldest information.
4.6.- WEB SERVER
CirLAMP Manager has a conguration web site where the user can fully congure the conguration parameters of each light point. Furthermore, the unit has an XML server, so that it can
be integrated into any global control and maintenance platform.
4�6�1� HOME SCREEN
CirLAMP Manager is accessed via an Ethernet connection.
The default IP address of the unit is: 192�168�42�30.
It can also be accessed from a local IP on the Ethernet port: 100�0�0�1�
16
The web site detects the browser language. If the browser’s language is Spanish, the web site
will be shown in Spanish. Otherwise, the language will be English.
You can also select the language using the buttons that appear on the upper left part of the web
site (Figure 8).
Instruction Manual
CirLAMP system
Figure 8: Homepage�
You must enter the correct username and password to enter the CirLAMP Manager web site.
CirLAMP Manager has two types of users:
1�- User with write access, admin:
With this access the user can read and write the CirLAMP Manager parameters as well
as those of the CirLAMP nodes installed.
Table 4: Default username and password for a user with write access�
Default username and password
Usernameadmin
Passwordadmin
2�- User with read access, user:With this access, the user can only access certain read elds in CirLAMP Manager�
Table 5: Default username and password for a user with read access�
Default username and password
Usernameuser
Passworduser
Instruction Manual
17
CirLAMP system
4�6�2� MAIN SCREEN
Figure 9 shows the web server's main screen, where you can access all the information relating
to the CirLAMP Manager and the CirLAMP Nodes installed.
Figure 9: Main screen�
The screen is divided into three areas of information (Figure 10):
CirLAMP Manager information area. Menu for accessing all web screens. Central area.
CirLAMP manager
information area
18
MenuCentral area
Figure 10: Areas on the main screen�
Instruction Manual
CirLAMP system
4�6�2�1 CirLAMP Manager information area�
Figure 11: CirLAMP Manager information area�
This area of the main screen shows all the information relating to CirLAMP Manager:
Identier: The unit identier is displayed (Example: CIR0000000001).Name: Name given to the CirLAMP Manager. (Example:CirLamp Manager)
PLC version: PLC modem version.
Connected: Number of units connected/units detected.
Version: Firmware version of the CirLAMP Manager�
4�6�2�2 Menu
The CirLAMP Nodes and CirLAMP Manager screens can be accessed from the menu. The
unit status can also be viewed.
4�6�2�2�1� Menu: Nodes
Figure 12: Node selection menu�
The following screens can be accessed via the Nodes menu:
Equipments table: Accesses the table of nodes logged in the CirLAMP Manager� (“4.6.3. NODES MENU: EQUIPMENTS TABLE”)
Orders: (“4�6�4� NODES MENU: ORDERS”)
Read access user: Cannot access the Orders screen.
Node map: Access the nodes map with the units connected at that instant.
(“4.6.5. NODES MENU: NODE MAP”)
Intruder list: Allows you to add the nodes that you do not wish to connect to CirLAMP
Manager to a list using the serial number of each node.
(“4.6.7. NODES MENU: INTRUDER LIST”)
Read access user: Cannot access the Intrusion list screen.
Instruction Manual
19
4�6�2�2�2� Menu: CIRLAMP Manager
Figure 13:CirLAMP Manager selection menu�
The following screens can be accessed from the CirLAMP Manager:
Reports: Accesses documents containing information on CirLAMP Manager�
(“4.6.8. CirLAMP MANAGER MENU: REPORTS”)
CirLAMP system
Inputs and outputs: (If the M8I8O expansion module is not connected, this option
does not appear ). Up to 8 inputs and outputs can be congured.
(“4.6.9. CirLAMP MANAGER MENU: INPUTS AND OUTPUTS”)
Read access user: This option does not appear in the selection menu.
Parameters: Provides access to the conguration of the CirLamp�
Manager (“4.6.10. CirLAMP MANAGER MENU: PARAMETERS”)
Read access user: This option does not appear in the selection menu.
Geolocation: Accesses the unit geolocation screen.
(“4.6.11. CirLAMP MANAGER MENU: GEOLOCATION”).
Read access user: This option does not appear in the selection menu.
Tasks: Accesses the unit tasks conguration screen.
( “4.6.12. CirLAMP MANAGER MENU: TASKS”)
Read access user: This option does not appear in the selection menu.
Task status: This button accesses the status screen for the
CirLAMP Manager tasks.
(“4.6.13. CirLAMP MANAGER MENU: TASK STATUS”)
Read access user: This option does not appear in the selection menu.
Update: Accesses the unit update screen.
(“4.6.14. CirLAMP MANAGER MENU: UPDATE”)
Read access user: This option does not appear in the selection menu.
20
Modem update: Accesses the screen for updating the unit's modem driver.
(“4.6.15. CirLAMP MANAGER MENU: MODEM UPDATE”)
Read access user: This option does not appear in the selection menu.
Reboot: Accesses the unit restart screen.
(“4.6.16. CirLAMP MANAGER MENU: REBOOT”)
Read access user: This option does not appear in the selection menu.
Instruction Manual
CirLAMP system
4�6�2�2�3� Equipment status
Figure 14:Unit status�
This section displays the CirLAMP Manager status or task in progress, as well as the current
time on the unit.
4�6�3� NODES MENU: EQUIPMENTS TABLE
Figure 15:Table of units�
This screen shows a table with all the CirLAMP Nodes logged in the CirLAMP Manager�
As seen in Figure 15, the table includes the following elds:
#: This column correlatively lists the units logged in the CirLAMP Manager�
Node identier: unit's serial number.
Status: current status of the unit. Two states are possible, see Table 6:
Table 6: Possible node states�
Status
AActive
PFPermanent fault
Reference: reference assigned to a node to help identify it.
Latitude: latitude assigned to the node.
Longitude: longitude assigned to the node.
Instruction Manual
21
CirLAMP system
Alarms: current status of the node. Two states are possible, see Table 7:
Table 7: Alarms�
Status
OKNo alarms
FAILNode fault
NB: There is an application for iOS and Androids for positioning the nodes.(CirLAMP NODE
Location)
There are two buttons in the lower part of the table, with the following functions (Table 8):
Table 8: Buttons on the table of units�
ButtonFunction
UpdateUpdates the current content of the table of units.
Removes all nodes that are not active (Status: PF)
Clean the nodes table
from the CirLAMP Manager database.
If the nodes reconnect to the network at a later date,
they will automatically appear in the table of units.
To access all the information available relating to a node, click on the row for the selected unit.
See “4.6.3.1. Node information menu”
4�6�3�1� Node information menu
All the parameters of a CirLAMP Node can be viewed and congured from this screen.
The menu varies depending on the type of user used to enter the web site (Figure 16 and
Figure 17).
Figure 16:Node information menu (Write access user)�
22
Instruction Manual
CirLAMP system
Figure 17:Node information menu (Read access user)�
4�6�3�1�1� Database values
On this screen Figure 18 you can view the node data for the last 24 hours. You can select any
time on the graph and see instantaneous values for the unit at that time.
Figure 18:Database values screen�
Instruction Manual
23
CirLAMP system
4�6�3�1�2� Instant values
On this screen, Figure 19, you can view the instantaneous consumption values and congure
the work time interval and memory work interval for each node.
NB: If the node is stopped the CirLAMP Manager cannot provide the data.
24
Figure 19:Instant values screen�
General parameters:
This section displays the identier and rmware version for the node selected.
Electric values:
This section displays the following electrical parameters:
Instruction Manual
CirLAMP system
Table 9: Electrical parameters�
ParameterUnits
Voltage: VoltageV
Current: CurrentA
pActive: Active powerW
pReactive: Reactive powervar
Times:
This section displays:
minOn: Time from the last switch on.
minTotalOn: The total useful life of the node.
Clicking on the Delete time button resets the two parameters.
Current power:
Is the power (in %) of the node at the moment when the instantaneous values are read.
Temporal lamp interval:
In this section you can congure:
pWork: Value of the power (in %) during the period determined by tWork�
tWork: Time interval in minutes for which we want the power value dened in pWork�
Click on the Send button to send the data to the unit.
NB: The parameters for the work time interval are not saved when the power supply is dis-
connected from the node.
Memory lamp interval:
In this section four different power intervals can be congured. The remaining time starts to
count down when the power supply is connected to the node.
power1: Power value in % during interval 1.
time1: Duration in minutes of interval 1.
power2: Power value in % during interval 2.
time2: Duration in minutes of interval 2.
power3: Power value in % during interval 3.
time3: Duration in minutes of interval 3.
power4: Power value in % during interval 4.
time4: Duration in minutes of interval 4.
Click on the Send button to send the data to the unit.
NB: The parameters for the memory work interval are not saved when the power supply is
disconnected from the node.
Read access user: The Delete time button is not enabled and the work time interval or the
work memory interval cannot be modied.
Instruction Manual
25
CirLAMP system
4�6�3�1�3� Scheduling time intervals in hours
If the CirLAMP Manager has theinput and output module (M8I8O Expansion module) the
work intervals can be programmed automatically from Sunrise (Sunrise time).
Figure 20:Screen for scheduling time intervals in hours�
The parameters are:
Cnt: Node identier.
inTime: Interval 1 activation time. This parameter cannot be modied; it coincides
with the Sunrise value (Sunrise time).
power1: Power value in % during interval 1.
rstTime: Interval 2 activation time. power2: Power value in % during interval 2.secondTime: Interval 3 activation time. power3: Power value in % during interval 3.
thirdTime: Interval 4 activation time.
power4: Power value in % during interval 4. Interval 4 will last until the node has
no power supply.
Click on the Send button to send the data to the unit.
Read access user: The programming of intervals in hours cannot be modied.
26
Instruction Manual
CirLAMP system
4�6�3�1�4� Alarms
Read access user: Cannot access the Alarms screen.
On this screen, Figure 21, you can view and congure the node alarms.
Figure 21:Alarm screen�
Status alarms:
Each CirLAMP node has the following alarms:
Detection of burnt out lamp (alBroken)
Each CirLAMP node detects the anomalous operation of each light. If the lamp is burnt
out the node detects this and generates an alarm.
Open capacitor detection and alert (alCapacity)
A malfunction or anomalous operation may be due to a deteriorated PFC capacitor. This
causes high consumption of inductive reactive power, which is detected after it has remained active for 1 hour.
Blinking lamp detection and alert (alIntermi)
Depending on the type of lamp, once it has reached the end of its useful life, it does not
switch off but starts to switch on intermittently, the CirLAMP detects this anomalous
situation and activates the alIntermi alarm if the lamp switches off more than a program-
mable number of times over a period of 2 hours.
Value 1 in the alarm status column indicates that the alarm is activated.
Conguration alarms:
The conguration parameters for the alarm are:
powerLamp, lamp power in W.timeAlarm, alarm detection time.
percentageAlarm, value of the percentage of power under which the alarm will be
activated.
factorPower, node power factor value.blinkTime, bulb blinking time to activate the alIntermi alarm.blinkTimes, number of bulb blinks toactivate the alIntermi alarm.
Instruction Manual
27
CirLAMP system
4�6�3�1�5� Reference node
Read access user: Cannot access the Reference node screen.
On this screen, Figure 22, you can view and modify the node reference, i.e, the identifying text
to differentiate it from the other nodes in the installation.
Figure 22:Reference node
4�6�3�1�6� Remove node from the table
Read access user: Cannot access the Remove node from the table screen.
Clicking on this button deletes the node from the table of units and the database.
If the node reconnects to the network at a later date, it will automatically appear in the table of
units.
Figure 23:Remove node from the table�
4�6�3�1�7� Add node from blackList
Read access user: Cannot access the Add node from blackList screen.
Clicking on this button deletes the node from the table of units and database and adds it to the
intrusion list.
Units which are included in the intrusion list will not be registered in the nodes table again until
they are deleted from the intrusion list.
Figure 24:Add node from blackList�
28
Instruction Manual
CirLAMP system
4�6�4� NODES MENU: ORDERS
On this screen, Figure 25, you can select the orders le that you want to send to the unit.
Figure 25:Orders screen�
The orders les are in .xml format.
The orders les that can be created in CirLAMP Manager are detailed in Table 10.
Table 10: Orders available for CirLAMP Manager�
Code
Write le
E01L01Conguration of parameters
E02
E03-Update rmware.
E04L04Nodes references.
E05L05Work time interval.
E06L06Memory interval.
E07L07Alarm adjustment.
E08L08Delete nodes from list.
E09-Manage the nodes black list.
E11L11Set the total useful life for node lamps to 0.
E12L12Delete all nodes from the network.
E13L13Manage the inputs/outputs module.
-L14List of spontaneous events.
E17L17Memory time interval, via time conguration.
C06-Modication of date in CirLAMP Manager.