Circutor CirCAMP-4DP, CirCAMP-2IP Instruction Manual

INSTRUCTION MANUAL
(M097B01-03-16A)
Multifunction multimeter
CirCAMP-4DP
CirCAMP-2IP
2
SAFETY PRECAUTIONS
DISCLAIMER
CIRCUTOR, SA reserves the right to make modi cations to the device or the unit speci ca-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device speci cations and the most updated manuals.
www.circutor.com
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a speci c point.
Follow the warnings described in this manual with the symbols shown below.
If you must handle the unit for its installation, start-up or maintenance, the following should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit. In particular, handling with voltages applied may result in electric shock, which may cause death or serious injury to personnel. Defective installation or maintenance may also lead to the risk of  re. Read the manual carefully prior to connecting the unit. Follow all installation and maintenance instructions throughout the unit’s working life. Pay special attention to the installation stan­dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result in injury or damage to the unit and /or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior noti cation.
3
CONTENTS
SAFETY PRECAUTIONS ���������������������������������������������������������������������������������������������������������������������������������������3 DISCLAIMER ���������������������������������������������������������������������������������������������������������������������������������������������������������� 3 CONTENTS ������������������������������������������������������������������������������������������������������������������������������������������������������������� 4 REVISION LOG �������������������������������������������������������������������������������������������������������������������������������������������������������6 1�- VERIFICATION UPON RECEPTION ����������������������������������������������������������������������������������������������������������������� 7 2�- PRODUCT DESCRIPTION �������������������������������������������������������������������������������������������������������������������������������� 7 3�- DEVICE INSTALLATION ����������������������������������������������������������������������������������������������������������������������������������� 9
3�1�- PRELIMINARY RECOMMENDATIONS ���������������������������������������������������������������������������������������������������� 9 3�2�- INSTALLATION ���������������������������������������������������������������������������������������������������������������������������������������10 3�3�- DEVICE TERMINALS ������������������������������������������������������������������������������������������������������������������������������ 10
3�3�1�- CirCAMP-4DP MODEL �����������������������������������������������������������������������������������������������������������������10 3�3�2�- CirCAMP-2IP MODEL ������������������������������������������������������������������������������������������������������������������� 11
3�4�- CONNECTION DIAGRAM ����������������������������������������������������������������������������������������������������������������������� 12
3�4�1�- CirCAMP-4DP MODEL ������������������������������������������������������������������������������������������������������������������12 3�4�2�- CirCAMP-2IP MODEL ��������������������������������������������������������������������������������������������������������������������13
3�5�- CONNECTIONS ���������������������������������������������������������������������������������������������������������������������������������������� 14
4�- OPERATION ��������������������������������������������������������������������������������������������������������������������������������������������������� 15
4�1�- KEY FUNCTIONS ������������������������������������������������������������������������������������������������������������������������������������� 15 4�2�- DISPLAY ��������������������������������������������������������������������������������������������������������������������������������������������������� 15 4�3�- LED INDICATORS ������������������������������������������������������������������������������������������������������������������������������������ 16
4�3�1�- CirCAMP-4DP MODEL ������������������������������������������������������������������������������������������������������������������16
4�3�2�- CirCAMP-2IP MODEL ��������������������������������������������������������������������������������������������������������������������17 4�4�- IMPULSE INPUTS ������������������������������������������������������������������������������������������������������������������������������������ 18 4�5�- RELAY OUTPUTS ������������������������������������������������������������������������������������������������������������������������������������ 19 4�6�- CIRCUIT BREAKER ��������������������������������������������������������������������������������������������������������������������������������� 19
4�6�1�- CirCAMP-4DP MODEL �������������������������������������������������������������������������������������������������������������������19
4�6�2�- CirCAMP-2IP MODEL ���������������������������������������������������������������������������������������������������������������������20 4�7�- REAL TIME CLOCK ���������������������������������������������������������������������������������������������������������������������������������21
5�- DISPLAY IMPROVEMENTS ��������������������������������������������������������������������������������������������������������������������������� 22
5�1�- DISPLAY IN STANDBY MODE ����������������������������������������������������������������������������������������������������������������22
5�1�1�- CirCAMP-4DP MODEL ������������������������������������������������������������������������������������������������������������������23
5�1�2�- CirCAMP-2IP MODEL ��������������������������������������������������������������������������������������������������������������������24 5�2�- DISPLAY IN READING MODE ����������������������������������������������������������������������������������������������������������������� 25
5�2�1�- CirCAMP-4DP MODEL �������������������������������������������������������������������������������������������������������������������25
5�2�2�- CirCAMP-2IP MODEL ���������������������������������������������������������������������������������������������������������������������27
6�- CONFIGURATION ������������������������������������������������������������������������������������������������������������������������������������������ 29 7�- COMMUNICATIONS ��������������������������������������������������������������������������������������������������������������������������������������� 29
7�1�- OPTICAL COMMUNICATIONS PORT ����������������������������������������������������������������������������������������������������� 29 7�2�- PLC COMMUNICATIONS������������������������������������������������������������������������������������������������������������������������� 29 7�3�- RS-485 COMMUNICATIONS (according to version) ����������������������������������������������������������������������������� 30
7�3�1� CONNECTIONS ������������������������������������������������������������������������������������������������������������������������������� 30 7�4�- DLMS PROTOCOL �����������������������������������������������������������������������������������������������������������������������������������31
7�4�1�- ABSTRACT OBJECTS: SAP ASSIGNMENT, LN ASSOCIATIONS, COSEM �������������������������������31
7�4�2�- IDENTIFICATION NUMBERS ��������������������������������������������������������������������������������������������������������� 35
7�4�3�- CLOCK ��������������������������������������������������������������������������������������������������������������������������������������������36
7�4�4�- ERRORS ������������������������������������������������������������������������������������������������������������������������������������������ 37
7�4�5�- EVENTS ������������������������������������������������������������������������������������������������������������������������������������������� 37
7�4�6�- CONTROLLING THE CIRCUIT BREAKER ������������������������������������������������������������������������������������ 45
7�4�7�- FIRMWARE UPDATE ���������������������������������������������������������������������������������������������������������������������� 46
7�4�8�- METERING POINT ID ���������������������������������������������������������������������������������������������������������������������47
7�4�9�- FIRMWARE VERSION ��������������������������������������������������������������������������������������������������������������������47
7�4�10�- OPTICAL PORT CONFIGURATION ��������������������������������������������������������������������������������������������� 47
7�4�11�- RS-485 PORT CONFIGURATION ������������������������������������������������������������������������������������������������� 48
7�4�12�- TIMEOUT ��������������������������������������������������������������������������������������������������������������������������������������� 48
7�4�13�- RESETTING THE DEVICE ������������������������������������������������������������������������������������������������������������ 49
7�4�14�- ACTIVE ENERGY �������������������������������������������������������������������������������������������������������������������������� 49
7�4�15�- IMPULSE INPUTS ������������������������������������������������������������������������������������������������������������������������ 50
7�4�16�- INSTANTANEOUS VALUES �������������������������������������������������������������������������������������������������������� 50
7�4�17�- TRANSFORMER RATIO ��������������������������������������������������������������������������������������������������������������� 54
4
7�4�18�- OBJECTS RELATED TO PRE-PAYMENT ������������������������������������������������������������������������������������ 55
7�4�19�- LOAD PROFILES �������������������������������������������������������������������������������������������������������������������������� 61 8�- TECHNICAL FEATURES �������������������������������������������������������������������������������������������������������������������������������� 63 9�- MAINTENANCE AND TECHNICAL SERVICE ������������������������������������������������������������������������������������������������ 67 10�- GUARANTEE �������������������������������������������������������������������������������������������������������������������������������������������������67 11�- CE CERTIFICATE ������������������������������������������������������������������������������������������������������������������������������������������ 68
5
REVISION LOG
Table 1: Revision log�
Date Revision Description
07/16 M097B01-03-15A Initial Version
02/17 M097B01-03-16A
Changes in the following sections:
2. - 3.3.2. - 3.4.2. - 3.5. - 4. - 4.3.2. - 4.4. - 4.3.2. - 4.4.-
4.5. - 4.6.2. - 5.1.2. - 5.2.2. - 7.4.2. - 7.4.5.6. - 7.4.14. -
7.4.15. - 7.4.16. - 7.4.17. - 7.4.18.1. - 7.4.19. - 8
Note: The images of the devices are for illustrative purposes only and may differ from the orig-
inal device.
6
1�- VERIFICATION UPON RECEPTION
Check the following points when you receive the device:
a) The device meets the specications described in your order. b) The device has not suffered any damage during transport. c) Perform an external visual inspection of the device prior to switching it on. d) Check that it has been delivered with the following:
- An installation guide.
If any problem is noticed upon reception, immediately contact the transport company and/or CIRCUTOR's after-sales service.
2�- PRODUCT DESCRIPTION
CirCAMP-xxP units are a range of multichannel compact energy meters, with additional inputs
for metering the impulses of other devices, such as water and gas meters.
The system consists of two models:
El CirCAMP-4DP is a static energy meter that can manage 4 single-phase measurements independently, all sharing the same neutral terminal.
El CirCAMP-2IP is a static energy meter that can manage 2 three-phase measurements, indirectly /5A and independently in current, all sharing the same voltage.
Active energy is measured in compliance with Class B, according to European Directive 22/2004 EC.
The device features:
- 2 keys that allow you to browse the different screens and program the device.
- Indicator LEDs: 13 CirCAMP-4DP model y 7 CirCAMP-2IP model.
- Verication LEDs: 4 CirCAMP-4DP model y 2 CirCAMP-2IP model.
- LCD display, displays all parameters,
- 2 connection seals,
- 2 terminal covers, to cover the measuring terminals of the device and the xing screws.
7
- Communications via an optical port.
- RS-485 communications (according to version).
- PLC OFDM communications.
The CirCAMP-xxP is offered in different versions, Table 2 shows all of the possible options of
the device.
Table 2: CirCAMP-xxP options�
Options CirCAMP-4DP Code
Connection mode 4 single-phase measurements with shared neutral 1
Accuracy Class B active / Does not measure reactive energy 10
Measurement voltage
230 V
E
Current measurement system Transformer D
Current measurement 5(32) A 7
Frequency
50 Hz
A
60 Hz
B
Automatic (50/60Hz) C
Communications
PLC OFDM / RS-485 8 PLC OFDM B
Expansion 4 potential free outputs / 4 inputs 3
Model Pre-payment P
Number of quadrants Storage in both directions 2
Additional features With circuit breaker on the phase lines 2
Options CirCAMP-2IP Code
Connection mode
2 three-phase measurements with common volt-
ages
6
Accuracy Class B active / Does not measure reactive energy 10
Measurement voltage
3 x 127/220 V N 3 x 230/400 V Q 3 x 127/220 V ... 3 x 230/400 V U
Current measurement system Transformer T
Current measurement 5(10) A 8
Frequency
50 Hz
A
60 Hz B Automatic (50/60Hz) C
Communications
PLC OFDM / RS-485 8 PLC OFDM B
Expansion 4 potential free outputs / 4 inputs 3
Model Pre-payment P
Number of quadrants Storage in both directions 2
Additional features No additional features 0
8
3�- DEVICE INSTALLATION
3.1.- PRELIMINARY RECOMMENDATIONS
In order to use the device safely, it is critical that individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use the personal protective equipment necessary, and pay attention to the vari­ous warnings indicated in this instruction manual.
The CirCAMP-xxP device must be installed by authorised and qualied staff.
The power supply plug must be disconnected and measuring systems switched off before handling, altering the connections or replacing the device. It is dangerous to handle the device while it is powered.
Also, it is critical to keep the cables in perfect condition to avoid accidents, personal injury and damage to installations.
The manufacturer of the device is not responsible for any damage resulting from failure by the user or installer to heed the warnings and/or recommendations set out in this manual, nor for damage resulting from the use of products or accessories that did not come with the device or that were made by other manufacturers.
If an anomaly or malfunction is detected in the device, do not use the device to take any meas­urements.
Inspect the work area before taking any measurements. Do not take measurements in danger­ous areas or where there is a risk of explosion.
Disconnect the device from the power supply (device and measuring system power supply) before maintaining, repairing or handling the device's connections. Please contact the after-sales service if you suspect that there is an operational fault in the device.
9
3.2.- INSTALLATION
On the side of the device are all of the indications adjusted to the CEI 62052-11 standard.
The device is installed on a DIN rail. All connections are located inside the electric panel.
Terminals, opening roofs or removing elements can expose parts that are haz­ardous to the touch while the device is powered. Do not use the device until it is fully installed.
3.3.- DEVICE TERMINALS
3�3�1�- CirCAMP-4DP MODEL
Table 3:List of CirCAMP-4DP terminals
Device terminals
1 : Input channel 1 25,26 : Channel 3 relay output
3 : Output channel 1 27,28 : Channel 4 relay output
4 : Input channel 2 / Power supply 31 : Impulse input common
6 : Output channel 2 32 : Channel 1 impulse input
7 : Input channel 3 33 : Channel 2 impulse input
9 : Output channel 3 34 : Channel 3 impulse input
10: Input channel 4 35 : Channel 4 impulse input
11 : Neutral connection 36,37 : Reclose input
12 : Output channel 4 38 : B, RS-485 communications (according to version)
21,22 : Channel 1 relay output 39 : S, RS-485 communications (according to version)
23,24 : Channel 2 relay output 40 : A, RS-485 communications (according to version)
1 3
4 6 11
7
9
10
12
31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28
Figure 1:CirCAMP-4DP terminals�
10
3�3�2�- CirCAMP-2IP MODEL
Table 4:List of CirCAMP-2IP terminals
Device terminals
1 : S1, Current input L1 (CH1 y CH2) 23,24 : Channel 2 relay output
3 : S2, Current output L1 (CH1 y CH2) 25,26 : Circuit breaker control 1
4 : S1, Current input L2 (CH1 y CH2) 27,28 : Circuit breaker control 2
6 : S2, Current output L2 (CH1 y CH2) 31 : Impulse input common
7 : S1, Current input L3 (CH1 y CH2) 32 : Channel 1 impulse input
9 : S2, Current output L3 (CH1 y CH2) 33 : Channel 2 impulse input
2: VL1, Voltage input L1 34,35 : Not used
5 : VL2, Voltage input L2 36,37 : Reclose input
8 : VL3, Voltage input L3 38 : B, RS-485 communications (according to version)
11 : Neutral connection 39 : S, RS-485 communications (according to version)
21,22 : Channel 1 relay output 40 : A, RS-485 communications (according to version)
1
3 4
6 7 9
21 22 23 24 252627 28
CH1
2 5 8 11
31 32
33 343536 37 383940
1
3
4
6
7 9
CH2
Figure 2:CirCAMP-2IP terminals�
11
3.4.- CONNECTION DIAGRAM
3�4�1�- CirCAMP-4DP MODEL
1 3 4 6 11
7 9 10 12
31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28
L
N
LOAD
Channel 1 Channel 2 Channel 3 Channel 4
CH1
Channel 2
Channel 3 Channel 4
LOAD
LOAD LOAD
Utilizar cualquiera de las 3 fases / Use any line
Channel 1
CH2*
CH3 CH4
Figure 3: Connection diagram, CirCAMP-4DP�
* CH2: The power supply of the device and the PLC communications occur via channel 2.
12
3�4�2�- CirCAMP-2IP MODEL
1
3 4
6 7 9
21 22 23 24 252627 28
CH1
2 5 8 11
31 32
33 343536 37 383940
1
3
4
6
7 9
CH2
L1
N
L2
L3
L1
N
L2
L3
S1 S2
P1
P2
S1 S2
P1
P2
S1 S2
P1
P2
S1 S2
P1
P2
S1 S2
P1
P2
S1 S2
P1
P2
VL1
VL2
VL3
N
Figure 4: Connection diagram, CirCAMP-2IP�
Note: The power supply of the unit is through phase 2
13
3.5.- CONNECTIONS
The CirCAMP-xxP has terminal covers that cover the measuring terminals of the device and
the xing screws (Figure 5).
Figure 5: CirCAMP-xxP terminal covers�
The xing screws are of the mixed type, allowing the use of PZ1 and at head screwdrivers.
Table 5:CirCAMP-xxP connection features
Connection
Model CirCAMP-4DP CirCAMP-2IP
Terminals
1, 3, 4, 6, 7, 9, 10,11,12 1, 3, 4, 6, 7, 9, 2, 5, 8, 11
8 mm 16 mm
2
1.2 Nm 8 mm 16 mm
2
1.2 Nm
Screwdriver head PZ1 PZ1
Terminals
21 ��� 28 , 31 ��� 40 21 ��� 28 , 31 ��� 40
8 mm 1.5 mm
2
0.6 Nm 8 mm 1.5 mm
2
0.6 Nm
Screwdriver head Flathead ( 3 x 0.5 mm) Flathead ( 3 x 0.5 mm)
Once connected, the device can be protected with two connection seals (Figure 6).
Figure 6: CirCAMP-xxP seal�
14
4�- OPERATION
The CirCAMP-4DP is a static meter capable of:
Measuring and managing 4 single-phase measurements, independent phase mode. ( CirCAMP-4DP model) Measuring and managing 1 three-phase measurement, two-phase, etc. , polyphase mode.( CirCAMP-4DP model)
 Measure and manage 2 three-phase measurements independently in current, sharing
the same voltage ( CirCAMP-2IP model)
The device measures:
Active energy stored in both directions.
The active, reactive and apparent power.
Effective voltage and current. The internal temperature of the unit, CirCAMP-2IP model.
4.1.- KEY FUNCTIONS
The CirCAMP-xxP has 2 keys that allow you to browse the different screens (Table 6):
Table 6: Key functions�
Key Keystroke
For the cyclic movement. Next screen.
Enters reading mode.
4.2.- DISPLAY
The device features an LCD display where all parameters are displayed (Figure 7):
CirCamp v01.01 s/n: 123456789 Model: 110ED7A83B22 CRC:12341234h
Figure 7:CirCAMP-4DP display�
15
4.3.- LED INDICATORS
4�3�1�- CirCAMP-4DP MODEL
The device features 17 LEDs:
Active Energy pulses
Pulse input
Cutting element
Relay outputs
PLC
CirCAMP-4DP
Figure 8:CirCAMP-4DP LED indicators�
 4 to verify the active energy, one for each measurement element. The weight of the LEDs is 10,000 imp/kWh.
The LEDs will remain lit when the current is lower than the energy meter start-up current. Once the start-up current is exceeded the LEDs are turned off and emit impulses that are proportional to the measured energy.
 4 to indicate the impulse input of other supplies.
 4 to indicate the circuit breaker status.
 4 to indicate the relay output status.
 1 to indicate the PLC communications status.
Table 7: Status LEDs: CirCAMP-4DP�
LEDs
Cutting element
Power on
The power supply is connected to the electrical network
Power off
The power supply is disconnected from the electrical network
Pulse input Calculation of impulses of other supplies: water, gas, etc.
Relay outputs
Power on
Relay connected.
Power off
Relay disconnected.
16
Table 7 (Cont�): Status LEDs: CirCAMP-4DP�
LEDs
PLC
Power on Red: It detects other PLC devices but it does not detect the presence of a
concentrator or transducer in the network.
Yellow: After start-up, the recording process can take up to a few hours. Green: Device recording and fully operational.
Power off
The device does not detect other devices in the PLC network.
4�3�2�- CirCAMP-2IP MODEL
The device features 8 LEDs :
PLC
CirCAMP-2IP
Active Energy pulses
Cutting element
Relay outputs
Pulse input
Figure 9:CirCAMP-2IP LED indicators�
 2 to verify the active energy, one for each measurement element. The weight of the LEDs is 20.000 imp/kWh.
The LEDs will remain lit when the current is lower than the energy meter start-up current. Once the start-up current is exceeded the LEDs are turned off and emit impulses that are proportional to the measured energy.
 2 to indicate the impulse input of other supplies.  2 to indicate the circuit breaker status.  2 to indicate the relay output status.  1 to indicate the PLC communications status.
Table 8: Status LEDs: CirCAMP-2IP�
LEDs
Cutting element
Power on
The power supply is connected to the electrical network
Power off
The power supply is disconnected from the electrical network
Pulse input Calculation of impulses of other supplies: water, gas, etc.
17
Table 8 (Cont�): Status LEDs: CirCAMP-2IP�
LEDs
Relay outputs
Power on
Relay connected.
Power off
Relay disconnected.
PLC
Power on Red: It detects other PLC devices but it does not detect the presence of a
concentrator or transducer in the network.
Yellow: After start-up, the recording process can take up to a few hours. Green: Device recording and fully operational.
Power off
The device does not detect other devices in the PLC network.
4.4.- IMPULSE INPUTS
The device features:
CirCAMP-4DP model: 4 impulse inputs (terminals 31 ... 35 in Table 3), according to UNE EN
62053-31:1999 class B, for the calculation of other supplies.
CirCAMP-2IP model: 2 impulse inputs (terminals 31, 32 and 35 in Table 4), according to UNE
EN 62053-31:1999 class B, for the calculation of other supplies.
31 35
5 V DC
470 Ω
COMM
470 Ω
...
CirCAMP-4DP
31
33
5 V DC
470 Ω
COMM
470 Ω
CirCAMP-2IP
Figure 10:Impulse inputs�
18
4.5.- RELAY OUTPUTS
The device features:
CirCAMP-4DP model: 4 relay outputs (terminals 21 ... 28 in Table 3).
CirCAMP-2IP model: 2 relay outputs (terminals 21 ... 24 in Table 4).
21
28
CirCAMP-4DP
Relay
Channel 1Channel2Channel 3Channel
4
21 24
CirCAMP-2IP
Relay
Channel 1Channel
2
Figure 11:Impulse inputs�
4.6.- CIRCUIT BREAKER
4�6�1�- CirCAMP-4DP MODEL
The CirCAMP-4DP features 4 circuit breakers, one for each of the measurement channels located inside the device, with no parts being accessible from the exterior.
Cut off occurs only on the phase line and can be generated:
By an order� The manager can send a command to open a circuit breaker via any communications port. These orders are usually used for:
● Cut offs or Reclosures for managing unpaid accounts.
● Commencing or terminating supply service.
The circuit breaker can only be reclosed via another communications command.
Depending on the contracted power. A different power threshold can be congured for each circuit breaker, which opens the circuit breaker in the case that the power demanded by the customer is exceeded.
The circuit breaker is reclosed automatically after 2n minutes have passed, with n being the number of attempted retries. Or automatically, via the reclose input of the CirCAMP- 4DP.
The reclose input is located in terminals 36 and 37 of the device, see Table 3�
19
36
37
5 V DC
470 Ω
COMM
Figure 12:Circuit breaker�
4�6�2�- CirCAMP-2IP MODEL
The CirCAMP-2IP model does not have circuit breakers located inside the unit.
It has two relays (terminals 25... 28 of Table 4) for controlling the external circuit breakers.
The cut-off can be generated:
By an order� The manager can send a command to open a circuit breaker via any communications port. These orders are usually used for:
● Cut offs or Reclosures for managing unpaid accounts.
● Commencing or terminating supply service.
The circuit breaker can only be reclosed via another communications command.
Depending on the contracted power. A different power threshold can be congured for each circuit breaker, which opens the circuit breaker in the case that the power demanded by the customer is exceeded.
The circuit breaker is reclosed automatically after 2n minutes have passed, with n being the number of attempted retries. Or automatically, via the reclose input of the CirCAMP- 2IP.
The reclose input is located in terminals 36 and 37 of the device, see Table 4 and Figure 12�
20
4.7.- REAL TIME CLOCK
The device has a real time clock capable of maintaining the date and time with a drift of less than 0.5 s/day, in accordance with the UNE EN 62054-21 Standard.
The CirCAMP-4DP is capable of maintaining the time during 12 hours, without being powered from the electrical network, via a Supercap. Provided that the device was previously connected to the electrical network during 1 hour. The device automatically makes the daylight saving time change.
Table 9: Real time clock�
Real Time Clock
Source Quartz crystal oscillator
Drift < 0.5 seconds / day at 25ºC
Supercap 12 hrs of autonomy, after 1 hour of charging
21
5�- DISPLAY IMPROVEMENTS
The device's home screen, Figure 13, appears for a few seconds when the device connects
to the network. It displays the rmware version, model and CRC of the DLNS version that it is
running.
CirCamp v01.01 s/n: 123456789 Model: 110ED7A83B22 CRC:12341234h
Figure 13: Home screen�
The CirCAMP-xxP has 2 display modes:
Display in standby mode
 Display in reading mode
5.1.- DISPLAY IN STANDBY MODE
With the display in standby mode, all of the information is presented in cyclic form without any
need to perform any action on the CirCAMP-xxP keypad.
In CirCAMP-4DP model, 6 different parameters are viewed in this mode, see Table 10, in
which they alternate every 6 seconds.
In CirCAMP-2IP model, 3 different parameters are viewed in this mode, see Table 11, in
which they alternate every 6 seconds.
The device is in this mode by default when none of the keys are pressed.
Short press the key to stop the cyclic movement of the parameter being shown at the time.
From then on, short press the key to browse all the parameters dened in Table 10 or
Table 11
Press the key to jump to reading mode.
22