1. Always check that the circuit breaker in the
electrical panel is in the OFF position, and that
all high voltage circuits (more than 42.4V) are
completely isolated from the mains supply
before doing any work.
2. Ensure that all low voltage systems (less than 42.4V) are
suitably protected from damage, by disconnecting all
sources of power such as chargers and batteries before
doing any work.
3. All electrical work must be carried out according to the
requirements of all applicable local electrical codes. (It is
recommended that a licensed electrical contractor perform
such work).
Connect all wiring
Connect the controller to the required input and output devices as per
the wiring diagram on the right hand side.
Safety Open Opening beam safety input. (A normally-closed
potential-free input)
Light/Light Pillar light connection. (A normally-open
potential-free input)
Safe Common Used for switching the power supply to the safety
beams, if automatic beam testing is required
Aux 12V Out Auxiliary power connection. Provides +12V DC
supply for auxiliary equipment such as a radio
receiver, photo cells, etc. It is electronically limited
to 300mA
Safety Close Closing beam safety input. (A normally-closed
potential-free input)
Lck/Stp Holiday Lockout or emergency stop input.
(A normally-closed potential-free input)
Trg Trigger input. (A normally-open potential-free
input)
FRX Free-exit input. (A normally-open potential-free
input)
Aux Activates the pillar light relay. (A normally-open
potential-free input).
Ped Pedestrian opening input. (A normally-open
potential-free input)
Com Common termination point. All trigger signals,
etc. have their return path to one of the Com
terminals
Status External gate status indicator. (A low current
output signal). An output terminal which provides a
low current, drive (approx. 4,5V DC, 20mA) to a
LED which can be used to indicate the gate status
remotely)
Aux IO The Aux IO terminal provides an open collector
output which can be used for alarm or auto function
purposes