CAT INV1250, INV2000, INV2250 User Manual

517–9204-04
Owner's Manual
INV1250, INV2000, INV2250
2
Important Safety Information
Most accidents that involve product operation, maintenance and repair are caused by failure to observe basic safety rules or precautions. An accident can often be avoided by recognizing potentially hazardous situations before an accident occurs. A person must be alert to potential hazards, including human factors that can affect safety. This person should also have the necessary training, skills and tools to perform these functions properly.
Safety precautions and warnings are provided in this manual and on the product. If these hazard warnings are not heeded, bodily injury or death could occur to you or to other persons. The hazards are
identified by the “Safety Alert Symbol” and followed by a “Signal Word” such as “DANGER”, “WARNING” or “CAUTION”.
Caterpillar cannot anticipate every possible circumstance that might involve a potential hazard. The warnings in this publication and on the product are, therefore, not all inclusive. You must not use this product in any manner different from that considered by this manual without first satisfying yourself that you have considered all safety rules and precautions applicable to the operation of the product in the location of use, including site-specific rules and precautions applicable to the worksite. If a tool, procedure, work method or operating technique that is not specifically recommended by Caterpillar is used, you must satisfy yourself that it is safe for you and for others. You should also ensure that you are authorized to perform this work, and that the product will not be damaged or become unsafe by the operation, lubrication, maintenance or repair procedures that you intend to use.
The information, specifications, and illustrations in this publication are on the basis of information that was available at the time that the publication was written. The specifications, torques, pressures, measurements, adjustments, illustrations, and other items can change at any time. These changes can affect the service that is given to the product. Obtain the complete and most current information before you start any job.
In the United States, the maintenance, replacement, or repair of the emission control devices and systems may be performed by any repair establishment or individual of the owner's choosing.
This manual contains safety, operation, and maintenance information. This manual should be stored near the product. Read, study and keep it with the literature and product information.
Consumer Arbitration Clause
The Limited Warranty included in this User Guide contains important legal terms including, but not limited to, a Consumer Arbitration Clause calling for mandatory individual arbitration and waiving the ability to bring a case as a class action. Please review this carefully.
California Proposition 65 Warning
3
Table of Contents
Consumer Arbitration Clause .................................................................................................................... 2
California Proposition 65 Warning ............................................................................................................... 2
SAFETY MESSAGES ................................................................................................................................... 5
Additional Messages ................................................................................................................................. 6
Special Requirements ............................................................................................................................... 6
COMPONENT IDENTIFICATION (INV2000 / INV2250) ............................................................................... 7
COMPONENT IDENTIFICATION (INV1250) ................................................................................................ 8
Engine Type & Serial Number ................................................................................................................... 9
FIRST USE INSTRUCTIONS ....................................................................................................................... 9
Oil .............................................................................................................................................................. 9
Fuel ........................................................................................................................................................... 9
Walk-Around Inspection ............................................................................................................................ 9
CONTROLS ................................................................................................................................................ 10
Display LEDs ........................................................................................................................................... 10
Generator Switch .................................................................................................................................... 10
CO DEFENSETM & Shut Off System (If equipped) ................................................................................ 10
Parallel Receptacles ............................................................................................................................... 11
Engine Smart Control Switch .................................................................................................................. 11
AC/DC Circuit Breakers .......................................................................................................................... 11
USB Receptacles .................................................................................................................................... 11
Low Oil Level Shutdown .......................................................................................................................... 11
GENERATOR OPERATION........................................................................................................................ 12
Optimal Generator Operating Conditions ................................................................................................ 12
Connection to Household Power Supply ................................................................................................. 12
Generator Grounding .............................................................................................................................. 12
AC Usage ................................................................................................................................................ 12
High Altitude Kits ..................................................................................................................................... 12
BEFORE STARTING ENGINE ................................................................................................................... 13
Engine Oil ................................................................................................................................................ 13
Fuel Level - Check .................................................................................................................................. 13
STARTING THE ENGINE ........................................................................................................................... 13
Recoil Start .............................................................................................................................................. 13
STOPPING THE ENGINE ........................................................................................................................... 13
MAINTENANCE .......................................................................................................................................... 14
Air Filter – Check ..................................................................................................................................... 14
Cylinder Head - Clean ............................................................................................................................. 14
Engine Oil Level – Check ........................................................................................................................ 15
Engine Oil – Change ................................................................................................................................ 15
Engine Valve Lash – Inspect/Adjust ....................................................................................................... 15
Fuel Line – Replace ................................................................................................................................ 16
4
Fuel Tank Cap and Strainer – Clean ...................................................................................................... 16
Generator - Inspect ................................................................................................................................. 16
Spark Arrestor - Inspect/Clean/Replace.................................................................................................. 16
Spark Plug – Inspect/Adjust/Replace ...................................................................................................... 17
Walk-Around Inspection .......................................................................................................................... 17
STORAGE ................................................................................................................................................... 18
Storage for 1 to 3 months ........................................................................................................................ 18
Storage for more than 3 months ............................................................................................................. 18
TROUBLESHOOTING ................................................................................................................................ 19
SPECIFICATIONS ...................................................................................................................................... 20
COMBINED EXHAUST AND EVAPORATIVE EMISSIONS CONTROLS WARRANTY STATEMENT ..... 21
Your Warranty Rights and Obligations .................................................................................................... 21
Manufacturer’s Warranty Coverage ........................................................................................................ 21
Owner’s Warranty Responsibilities ......................................................................................................... 21
Defects Warranty Requirements: ............................................................................................................ 21
WARRANTY ................................................................................................................................................ 23
CONSUMER ARBITRATION CLAUSE: MANDATORY BINDING INDIVIDUAL ARBITRATION
INSTEAD OF COURT; CLASS ACTION WAIVER ................................................................................. 23
5
SAFETY MESSAGES
There may be several specific safety messages on your generator. Please become familiar with all safety messages.
Ensure that all of the safety messages are legible. Clean the safety messages or replace the safety messages if the words cannot be read or if the illustrations are not visible. Use a cloth, water, and soap to clean the safety messages. Do not use solvents, gasoline, or other harsh chemicals. Solvents, gasoline, or harsh chemicals could loosen the adhesive that secures the safety messages.
Replace any safety message that is damaged or missing. If a safety message is attached to a part of the generator that is replaced, install a new safety message on the replacement part.
Read the Manual
Do not operate or work on this generator unless you have read and understand the instructions and warnings in the Owner’s Manual. Failure to follow the instructions or heed the warnings could result in injury or death. Proper care is your responsibility.
Hot Surface / Do Not Touch /
Flammable Material
Hot parts or hot components can cause burns or personal injury. Do not allow hot parts or components to contact your skin. Use protective clothing or protective equipment to protect your skin. Hot exhaust presents a potential fire hazard. Be sure that nothing flammable is within 1.5 meters of the exhaust.
Carbon Monoxide
Operating a generator indoors can kill you in minutes. Generator exhaust contains carbon monoxide. Carbon monoxide is a poison that you cannot see or smell. Never operate a generator inside a home or garage, even if doors and windows are open. Only operate a generator outdoors and away from windows, doors, and
vents. Always direct engine exhaust away from occupied structures. If anyone experiences dizziness, headaches, nausea, or tiredness get to fresh air immediately and seek medical attention. Ventilate the area thoroughly before occupying again.
The carbon monoxide shutoff system (if equipped) is not a substitute for safe generator operation. Do Not adjust or modify the carbon monoxide shutoff system. Failure to follow instructions can cause the system to malfunction which can result in hazardous conditions.
DANGER
PELIGRO
Utiliser un générateur à
l’intérieur PEUT VOUS TUER EN
QUELQUES MINUTES. Les gaz
d’échappement du générateur
contiennent du monoxyde de
carbone. C’est un gaz toxique
invisible et inodore. NE JAMAIS utiliser à l’intérieur d’une maison ou d’un garage, MÊME SI les portes et les fenêtres sont ouvertes. Utiliser UNIQUEMENT à l’EXTÉRIEUR et loin des fenêtres, portes et ventilations.
Si usa un generador en
interiores, MORIRA EN POCOS MINUTOS. El escape del generador contiene monóxido de carbono. Es un veneno que no tiene olor ni se puede ver. NUNCA lo use dentro de una casa o garaje. AUN si las puertas y vantanas están abiertas. Sólo úselo en EXTERIORES
y lejos de ventanas, puertas y ductos de ventilación.
6
Electrocution
Shock/Electrocution Hazard: Do not operate this equipment or work on this equipment unless you have read and understand the instructions and warnings in the Owner’s Manual. Failure to follow the instructions or heed the warnings will result in serious injury or death.
Operation of this equipment may create sparks that can start fires around dry vegetation. A spark arrestor may be required. The operator should contact local fire agencies for laws or regulations relating to fire prevention requirements.
Electrical backfeed into a utility’s distribution system
can cause property damage, severe injury, or death.
Electrical backfeed warning. Do not connect
generator to a building’s electrical system unless
using an isolation (transfer) switch installed by a certified, licensed electrician. CA H&S Code 119075 & 119080.
Additional Messages
Do not operate in wet conditions
No smoking, no exposed flames, no sparks.
Maintain a minimum distance of 5 feet (1.5 meters) from other objects.
Ensure that the unit is properly grounded.
Earth ground connection
Special Requirements
Electrical equipment, including lines and plug connections should be covered and protected from moisture.
In any generator set installation, the frame of the generator must be connected to an earth ground. A ground terminal is provided.
The INV1250/INV2000/INV2250 has a permanent neutral conductor bonded to the frame.
For 120VAC, use extension cords rated for 125V at 20A or greater. Use the shortest extension cord that meets these requirements.
Wear a hard hat, protective glasses, and other protective equipment, as required.
When work is performed around an engine that is operating, wear protective devices for ears in order to help prevent damage to hearing.
Do not wear loose clothing or jewelry that can snag on controls or on other parts of the engine.
Ensure that all protective guards and all covers are secured in place on the engine.
Never put maintenance fluids into glass containers. Glass containers can break.
Use all cleaning solutions with care.
The circuit breakers should match the generator specifications. If the circuit breakers require replacement, they must be replaced with a circuit breaker of the same rating and performance characteristics.
7
COMPONENT IDENTIFICATION (INV2000 / INV2250)
1) Vacuum Relief Valve
2) Fuel Cap
3) Panel Light
4) Recoil Starter
5) Fuel Gauge
6) Spark Plug Cover
7) Spark Arrestor
8) Oil Gauge / Oil Fill / Oil Drain*
9) Air Filter Assembly*
10) Generator Switch
11) Engine Smart Control (ESC) Switch
12) Display LEDs
13) Receptacle – 120 VAC double GFCI
14) AC Circuit Breaker
15) Ground Terminal
16) Parallel Receptacles
17) Receptacle – USB double
18) Receptacle – 12VDC 8.3A
19) DC Circuit Breaker
20) CO DEFENSETM (If equipped)
*behind service access door
1
2
4
3
5
6
7
8
9
Panel without CO DEFENSE
TM
Panel with CO DEFENSE
TM
8
COMPONENT IDENTIFICATION (INV1250)
1) Vacuum Relief Valve
2) Fuel Cap
3) Panel Light
4) Oil Gauge / Oil Fill / Oil Drain*
5) Air Filter Assembly*
6) Fuel Gauge
7) Spark Plug Cover
8) Spark Arrestor
9) Recoil Starter
10) Generator Switch
11) Receptacle – USB double
12) Display LEDs
13) Parallel Receptacles
14) Engine Smart Control (ESC) Switch
15) AC Circuit Breaker
16) Receptacle – 120 VAC
17) CO DEFENSETM (If equipped)
18) Ground Terminal
*behind service access door
1
2
4
3
6 7 8
9
Panel without CO DEFENSE
TM
Panel with CO DEFENSE
TM
11
12
13
14
15
16
18
10
17
5
9
Engine Type & Serial Number
INV1250
INV2000 / INV2250
Cat® portable generators are identified with model numbers, serial numbers, and with performance specification numbers. The model number and performance specifications are located on the ratings plate (2). The serial number is located on the serial number plate (1).
FIRST USE INSTRUCTIONS
Oil
Follow the Engine Oil Level-Check procedure to add the proper amount of oil for the unit as described in the Specifications chart.
Note: The generator is shipped with no oil in the engine, add the proper amount before first use.
Fuel
Follow the Fuel Level – Check procedure to add the proper amount of fuel for the unit as described in the Specifications chart.
Walk-Around Inspection
Perform the Walk-Around Inspection before each use as described later in this manual.
1
2
2
10
CONTROLS
Display LEDs
This generator is equipped with 3 Display LEDs that indicate Low Oil (1), Overload (2), and Output Power (3). The low oil indicator will illuminate red when there is an insufficient amount of oil in the crankcase. The overload indicator will illuminate red when there is a short circuit in a connected load, or the generator is overloaded. The output power indicator will illuminate green when the generator is in normal operation.
Generator Switch
Turn the generator switch to the choke position when starting the engine. Refer to Starting the Engine – Recoil Start. Turn the generator switch
to the on position “I” once it has been started. To
turn off the generator, turn the generator switch to the off “0” position.
CO DEFENSETM & Shut Off System (If equipped)
The (carbon monoxide) CO DEFENSETM system monitors the accumulation of CO gas while the generator is running and will shut off the engine if the levels become dangerously high. The CO DEFENSETM on this generator is not a substitute for an indoor CO alarm.
Whenever the CO DEFENSETM has shut off the engine there will be a light on the control panel that indicates the reason. Read the CO Action Label (shown above) for the next steps to take.
If the CO DEFENSETM light is flashing “red” you must leave the area immediately and relocate to an open outdoor area. Ventilate the area thoroughly before occupying again. Ensure the generator is located in an open outdoor area with the exhaust pointed away from occupied structures. If anyone
experiences dizziness, headaches, nausea, or tiredness get to fresh air immediately and seek medical attention.
If the CO DEFENSETM light is a constant “orange” then a system fault has occurred, or it is indicating that it has reached the end of its life. This fault can only be diagnosed and repaired by an Authorized Service Provider.
The CO DEFENSETM monitors the accumulation of CO gas from all sources in the area around the generator. If the CO DEFENSETM light is flashing
“red” this is not an error and safety measures must
be taken immediately. Note: Tampering with the CO DEFENSETM could result
in hazardous conditions and must be avoided. Note: The generator must not be operated in ambient
temperatures greater than 131oF (55oC) as this can damage the CO DEFENSETM.
11
Parallel Receptacles
Two parallel ready generators can be connected together to increase the total power available to a load by using the parallel receptacles. The system seamlessly matches frequency and automatically distributes the load to each generator so one is not overloaded. Follow the parallel kit (sold separately) instructions for connection and use of a parallel kit.
Engine Smart Control Switch
This generator is equipped with an engine smart control switch. When in the on position “I” the engine will vary speed to match the required power output to conserve fuel, and reduce wear and noise.
Note: If loads requiring intermittent power, or multiple large loads are connected, turn the
electronic speed control switch off “O” to avoid
possible engine stall. To avoid extended warm­up time, keep the electronic speed control off until normal operating temperatures have been reached.
AC/DC Circuit Breakers
The generator comes equipped with circuit breakers that protect the unit and the load from short circuit or overload conditions. If the circuit breaker opens, determine why the circuit breaker tripped before closing the circuit breaker.
USB Receptacles
The generator comes equipped with a double USB receptacle. The top is a 5V 1A USB port and the bottom is a 5V 2.1A USB port.
Low Oil Level Shutdown
The generator is equipped with a low oil level shutdown that is designed to protect the engine from damage caused by an insufficient amount of oil in the crankcase. When the oil level in the crankcase falls below the safe operating limit, the low oil level light will illuminate and the engine will automatically shutdown.
120 VAC, 20 Amp, Single or Duplex
The 120 VAC single or duplex receptacle is protected against overload by a 20 Amp push to reset circuit breaker. . It also provides protection via a Ground Fault Circuit Interruptor (GFCI) with press to Test and Reset buttons (INV2000/ INV2250). Use the receptacle to power a NEMA 5-20, 120 VAC, single phase, 60 Hz electrical load requiring 20 Amps of current.
Use only high quality, well insulated, 3-wire grounded cords rated for 125 V at 20 Amps (or greater). Keep extension cords as short as possible (less than 15 feet) to prevent voltage drop and overheating of wires.
12
GENERATOR OPERATION
Optimal Generator Operating Conditions
Temperature: 23oF to 104 oF
(-5oC to 40oC)
Humidity below 95%
Height above sea level: < 3000 feet (900
m). If the height of the operating area is over 900 m high, output power will be reduced.
Standard operating conditions are 77oF (25oC) and 40% humidity. Generator power may be reduced due to different ambient conditions and other factors such as fuel quality.
Connection to Household Power Supply
This generator must be installed in accordance with all applicable local laws and electrical codes. The generator must be isolated from the utility and the connection must be verified by a qualified electrician.
Generator Grounding
The National Electrical Code requires generators to be grounded to an approved earth ground.
Correct grounding for the generator is necessary for optimum engine performance and reduces the risk of electric shock. Use the ground terminal (1) to properly ground the generator.
Before using the ground terminal, consult a qualified electrician, electrical inspector, or local authority having jurisdiction for local codes or ordinances that apply for the intended use of the generator.
AC Usage
Do NOT overload the generator. Exceeding the rated power of the generator can damage the generator and the electrical devices connected to it.
Motor-driven devices require a large starting current. Make sure that the total power requirement of these types of loads does not exceed the rated power of the generator.
When the generator is used to power multiple loads or electric appliances, start by connecting the appliance with the highest starting power requirements, followed by the second highest and ending with the lowest.
High Altitude Kits
At higher altitudes, the standard air-fuel mixture is too rich and will cause decreased performance and increased fuel consumption. A rich mixture will also foul the spark plug and make starting difficult. Operation at higher altitudes for extended periods of time may increase emissions.
Proper operation can be ensured by installing an altitude kit when required. High altitude kits should be installed by a qualified technician. Contact an authorized service provider if the portable generator will be operated at altitudes greater than 3000 feet (0.9 km) above sea level.
Note: At elevations greater than 8000 feet above sea level, the engine may experience decreased performance even with the high altitude kit installed.
13
BEFORE STARTING ENGINE
Engine Oil
Check the oil level before each use. Refer to the Engine Oil Level - Check procedure in this manual.
Fuel Level - Check
1. Check the fuel level gauge (2).
2. If the fuel level is low, remove fuel cap (1).
3. Check the strainer. If the strainer is dirty, clean the strainer. Refer to Fuel Tank Cap and Strainer – Clean for instructions.
4. Add fuel. The use of a fuel stabilizer is highly recommended as the unit may sit for long periods of time before needed.
5. Install the fuel cap after fueling.
To avoid personal injury always use caution when you are adding fuel:
Fuel the generator in a well-ventilated area.
Always stop the engine before fueling.
Always fill with the generator on a level
surface.
Allow the engine to cool before fueling.
Do not smoke while you are fueling the
generator.
Do not fuel the generator near open flames or sparks.
Do not fill the fuel tank above the full line.
Avoid repeated or prolonged contact with
skin.
Avoid prolonged breathing of fuel vapor.
To avoid damaging the generator:
Use unleaded gasoline with an octane rating greater than or equal to 86.
Do not mix oil with the gasoline.
Do not use gasoline with greater than
10% ethanol content.
Do not use old gasoline.
Avoid getting dirt or water into the fuel
tank.
STARTING THE ENGINE
Recoil Start
1. Isolate the generator from the utility.
2. Unplug any electrical devices from the receptacles.
3. Turn the Engine Smart Control Switch to the off “0” position.
4. Open the vacuum relief valve on top of the fuel cap by rotating clockwise to the on “I” position.
5. Turn the generator switch to the choke position.
6. Slowly pull the starter handle until resistance is felt, then quickly pull the starter handle the rest of the way. If the engine does not start, repeat step 6 until the engine does start.
7. After the engine has started, turn the generator switch to the on “I” position.
STOPPING THE ENGINE
1. Disconnect the generator / unplug all electrical devices.
2. Turn the generator switch to the off “0” position.
3. Close the vacuum relief valve on top of the fuel cap by rotating counter­clockwise to the off “0” position.
NOTE: To stop the engine in an emergency, turn the generator switch to the off “0” position.
2
1
14
MAINTENANCE
Ensure that all safety information, warnings, and instructions are read and understood before any maintenance procedures are performed.
Use service hours or calendar time, WHICH EVER OCCURS FIRST, to determine the correct maintenance intervals.
Stop the engine before servicing. Put the generator on a level surface and remove the spark plug cap to prevent the engine from starting. Do not operate the engine in an unventilated room or other enclosed area.
When Required:
Fuel Tank Cap and Strainer – Clean Every Use:
Engine Oil Level – Check Walk-Around Inspection
First 20 Service Hours or 1 Month: Engine Oil – Change
Every Month: Generator – Inspect
Every 50 Service Hours or 3 Months:
Spark Arrester – Inspect/Clean/Replace Every 100 Service Hours or 6 Months:
Engine Oil – Change Air Filter – Check Spark Plug – Inspect/Adjust/Replace
Every 300 Service Hours or 1 Year:
Cylinder Head – Clean Engine Valve Lash – Check
Every 2 Years:
Fuel Line – Check/Replace if necessary
NOTE: Only use Caterpillar genuine parts.
Air Filter – Check
A dirty air filter will restrict air flow into the carburetor, will cause poor fuel economy, and may damage the engine. To keep the generator in good operating condition, service the air filter regularly. Service more frequently when operating the generator in extremely dusty areas.
Note: Never operate the generator without the
air filter in place. Operating the generator without the air filter in place will result in rapid engine wear.
Open the left service door (1). Remove the air filter cover bolt (2) and remove the air filter cover (3) by lifting out the service door opening. Make sure that the air filter is clean and not damaged. If the air filter is dirty, wash the filter. If the air filter is damaged, replace the air filter.
Use a nonflammable solvent or a mixture of household detergent and warm water to wash the filter. Rinse the filter thoroughly to remove all of the cleaning solution. After the filter has dried, pour a small amount of engine oil into the filter and squeeze to distribute the oil throughout. Remove excess oil and replace the filter.
Note: Do not wring out the filter. Wringing out the filter may damage the filter.
Use a damp rag to wipe dirt from the case and cover. Install the filter into the housing. Place the air filter cover over the filter and reinstall the air filter cover bolt. Reinstall the service door.
Cylinder Head - Clean
Only qualified service personnel should perform this maintenance procedure. Contact your local service center to schedule this maintenance.
1
2
3 1
2
3
INV1250
INV2000 / INV2250
15
Engine Oil Level – Check
Always check the engine oil with the generator on a level surface and with the engine stopped.
1.
Open the service door (1). Remove the oil level gauge (2) and wipe clean.
2.
Check the oil level by re-inserting the oil level gauge (do not screw in tight).
3.
If the oil level is low (4), add the recommended engine oil, using the funnel supplied, until the oil level reaches the upper mark (3) on the oil level gauge. Use the chart below to determine which viscosity oil to use.
4.
After adding oil, install and tighten the oil level gauge (2), and close the service door (1).
Note: Non-detergent and 2-stroke engine oils will
damage the engine and must not be used.
Engine Oil – Change
1. Operate the engine until it reaches normal operating temperature. Stop the engine and use a suitable container to collect the used oil.
2. Close the vacuum relief valve on top of the fuel cap by rotating counter­clockwise to the off “0” position.
3. Open the service door (1). Remove the oil level gauge (2), wipe clean, and set aside.
4. Attach the oil funnel supplied, and tilt the generator so the used oil flows from the engine into the container and fully tilt the generator until the crankcase is empty. Wipe the funnel clean.
5. Refill the oil, using the funnel supplied, and check the oil level. Refer to Engine Oil Level – Check.
6. Install and tighten the oil level gauge. Close the service door (1).
7. Dispose of the used oil properly.
8. Start the engine for a brief period and check for leaks.
9. Stop the engine and check the oil level. Refer to Engine Oil Level – Check.
Engine Valve Lash – Inspect/Adjust
Only qualified service personnel should perform this maintenance procedure. Contact your local service center to schedule this maintenance.
Recommended Lubricant Viscosities for
Ambient Temperature
Oil Viscosities
oC o
F
Min
Max
Min
Max
SAE 0W-40
-40
40
-40
104
SAE 5W-40
-30
50
-22
122
SAE 10W-30
-18
40 0 104
SAE 15W-40
-10
50
14
122
2
3
4
2
1 2 1
16
Fuel Line – Replace
Only qualified service personnel should perform this maintenance procedure. Contact your local service center to schedule this maintenance.
Fuel Tank Cap and Strainer – Clean
Wipe off the fuel cap (1) and surrounding area before removing the fuel cap. Wiping off the fuel cap and surrounding area before removing the fuel cap helps to reduce the amount of contaminants allowed into the fuel system.
If there is a build-up of debris in the fuel strainer (2), remove the strainer and rinse out the strainer. Allow the strainer to dry before installing the strainer.
Generator - Inspect
Once a month start the engine and run the engine until it reaches normal operating temperature (about 10 minutes). Plug in a corded device and turn on the device to ensure that the generator is providing power. Once you have verified that the generator is providing power, turn off the device and unplug it. Then turn the generator off.
Spark Arrestor ­Inspect/Clean/Replace
This unit has a spark arrestor fitted to the exhaust outlet of the muffler. The spark arrestor should be cleaned with a soft wire brush after every 50 hours or 3 months of use. The spark arrestor should be replaced after every 100 hours of operation or if it becomes damaged.
Hot Surface
Hot parts or hot components can cause burns or personal injury. Do not allow hot parts or components to contact your skin. Use protective clothing or protective equipment to protect your skin.
DO NOT perform this maintenance procedure until the muffler has cooled.
Remove screws (1). Remove spark arrestor (2) Check the spark arrestor. Carefully clean the spark arrestor with a soft wire brush. If the spark arrestor is damaged, replace the spark arrestor.
To install the spark arrestor, align the mounting holes in the spark arrestor with the mounting holes on the muffler. Insert screws (1) and tighten securely.
2
1
1
2
17
Spark Plug – Inspect/Adjust/Replace
Refer to the Specifications section of this manual to determine the proper spark plug part number and spark plug gap for your product.
INV2000/ INV2250
INV1250
1. DO NOT perform this maintenance procedure with the engine running.
2. Turn the generator switch to the off “O” position.
3. Remove the screws (5) to remove the outer side panel by pushing up and out to access the engine.
4. Remove the spark plug boot by lifting it off the top of the spark plug and remove the spark plug access cover (2) by rotating and pulling out.
5. Use the plug wrench (4) or a spark plug socket to remove the spark plug (3).
6. Visually check the spark plug to see if it is damaged. If the insulator is cracked, replace the spark plug. If the electrode is damaged, replace the spark plug.
7. Measure the plug gap (1) with a feeler gauge. Adjust the gap as necessary by carefully bending the side electrode. Refer to Specifications for the correct gap for your product.
8. Check the spark plug washer to ensure proper working condition. If the washer is damaged, replace the washer.
9. Install spark plug and tighten to 9 ± 2 lb ft (12.5 ± 2 Nm). DO NOT overtighten as this may damage the engine.
10. Re-attach the spark plug boot, spark plug cover (2), and outer side panel.
Walk-Around Inspection
Before starting the engine perform a visual inspection of the unit. Look for:
Proper oil level
Proper fuel level
Good quality fuel
Fluid leaks
Loose clamps
Loose bolts
Cracked fuel line
Loose or frayed wiring
Built up debris
In addition, make sure that:
The ground terminal is properly connected
1
4
5
3
2
18
STORAGE
When a generator is in storage, air may condense and moisture may appear on the windings. In order to minimize condensation, always store the generator in a dry area. Cover the generator with a protective cover that extends to the ground. The cover should remain loose around the generator in order to allow proper ventilation.
The generator must not be stored in ambient temperatures greater than 131oF (55oC) as this can damage the CO DEFENSETM (if equipped).
Wait until the generator has cooled before covering it. NEVER operate the generator with the cover installed. It could ignite and cause damage.
Storage for 1 to 3 months
Remove any dirt, rust, grease, and oil from the generator. DO NOT use a pressure washer to clean the generator. Inspect the exterior. Make any necessary repairs.
Add fuel stabilizer to the fuel tank to prevent the gasoline from going bad. Start and run the engine for 5 minutes to ensure that the fuel stabilizer has been pulled in to the carburetor. Shut off the engine and allow the engine to cool.
Turn the generator switch to the off “O” position. Move the generator to the storage place. Cover the generator.
Storage for more than 3 months
Remove any dirt, rust, grease, and oil from the generator. DO NOT use a pressure washer to clean the generator. Inspect the exterior. Make any necessary repairs.
Gasoline is extremely flammable and is explosive under certain conditions. Drain the fuel in a well-ventilated area with the engine stopped and cool. Never smoke or allow flames or sparks in the area during this procedure.
Remove the fuel cap and carefully turn the generator over to pour the gasoline into an appropriate container. Reinstall the fuel cap and start and run the engine until the engine stops, to allow the fuel to drain from the fuel lines, carburetor, and engine system.
Change the engine oil. Refer to Engine Oil – Change.
Remove the spark plug and pour a small amount of oil into the cylinder. Install the spark plug but do not install the spark plug boot.
Turn the generator switch to the off “O” position. Move the generator to the storage place. Cover the generator.
19
TROUBLESHOOTING
Issue:
Possible Cause:
Solution:
Check:
Engine Will
Not Start
Generator switch in the off “0”
position
Turn the generator switch to the correct
position.
Start the engine.
Generator inclined
Move generator to a level position.
No fuel
Fill the fuel tank.
Bad or contaminated fuel
Check the fuel.
Not enough oil in the engine
Check the oil level. If low, add the
recommended oil.
Dirty air filter
Clean the air filter.
No spark
Replace the spark plug.
Oil in the combustion chamber
Remove spark plug, turn generator switch
to off “O” position, pull recoil starter four
times to remove oil from combustion
chamber.
If the engine still will not start:
Take the unit to an authorized service provider.
Engine
Runs
Rough (no
load)
Dirty air filter
Stop the engine and check the air filter.
Clean if needed.
Start the engine /
check if it runs
rough.
Generator inclined
Move generator to a level position.
If the engine still runs rough:
Take the unit to an authorized service provider.
Engine
Shuts
Down
Out of fuel
Check the fuel. Fill the tank if necessary.
Start the engine /
check if it shuts
down.
Not enough oil in the engine
Check the oil level. If low, add the
recommended oil.
Dirty air filter
Clean the air filter.
Shut off due to CO accumulation &
flashing red indicator
Follow all safety instructions on CO Action
Label
Generator overloaded
Unplug some of the devices.
Vacuum relief valve in off “O” position
Turn vacuum relief valve to on “I” position.
Shut off due to CO DEFENSETM system
fault & constant orange indicator
System fault or end of life indication. Take the unit to an
authorized service provider.
If the engine still shuts down:
Engine
Runs
Rough
(with load)
Dirty air filter
Stop the engine and check the air filter.
Clean if needed.
Start the engine /
check if it runs
rough.
Generator overloaded
Unplug some of the devices.
Defective device plugged in
Unplug defective device.
If the engine still runs rough:
Take the unit to an authorized service provider.
Engine Runs, But Generator
Does Not
Provide
Power
Generator overloaded, overload light is
on
Turn off and unplug all electrical devices,
shut down the engine, wait 10 minutes & start the engine, connect fewer or lighter
electrical loads.
Start the engine /
check for power.
Bad connection
Stop the engine and check the
connections.
Defective power cord
Replace the cord.
Defective device plugged in
Unplug defective device.
If there is still no power:
Take the unit to an authorized service provider.
20
SPECIFICATIONS
INV1250
INV2000 / INV2250
Engine Type
Single Cylinder, 4-Stroke, Forced
Air Cooling
Single Cylinder, 4-Stroke,
Forced Air Cooling
Displacement (cc)
60
79.7
Ignition System
Electronic
Electronic
Spark Plug Gap
.024 - .032 inches (0.6 – 0.8mm)
.024 - .032 inches (0.6 – 0.8mm)
Fuel Volume
0.8 U.S. gallon (3L)
1.05 U.S. gallon (4L)
Fuel Consumption
(g/(kW·h)
≤ 450
≤ 450
100% load continuous
4.9
3.5
running time (hr)
50% load continuous
7.9
6
running time (hr)
Oil Capacity
0.33 quart (0.31L)
0.40 quart (0.38L)
Rated Output (DC)
N/A
12V 8.3A
Rated Frequency (Hz)
60
60
Rated Voltage (V)
120
120
Rated Output Power (kW)
1.0
1.8
Surge Output Power (kW)
1.25
2.25
Phase
Single
Single
Total Harmonic Distortion
< 3%
< 3%
21
COMBINED EXHAUST AND EVAPORATIVE EMISSIONS CONTROLS WARRANTY STATEMENT
Your Warranty Rights and Obligations
The California Air Resources Board (CARB), the United States Environmental Protection Agency (EPA), and Caterpillar Inc. are pleased to explain the exhaust and evaporative emissions control system warranty on your 2020 model year small off-road engine/equipment. In the United States and California, new equipment that use small off-road engines must be designed, built, and equipped to meet stringent emissions standards. Caterpillar must warrant the emission control system on your small off­road engine/equipment for the periods of time listed below provided there has been no abuse, neglect, or improper maintenance of your small off-road engine/equipment leading to the failure of the emissions control system.
Your emissions control system may include parts such as the carburetor or fuel injection system, the ignition system, catalytic converter, fuel tanks, fuel lines (for liquid fuel and fuel vapors), fuel caps, valves, canisters, filters, clamps, and other associated components. Also included may be hoses, belts, connectors, and other emission-related assemblies.
Where a warrantable condition exists, Caterpillar will repair your small off-road engine/equipment at no cost to you including diagnosis, parts, and labor.
Manufacturer’s Warranty Coverage
This emissions control system is warranted for three years. If any emission-related part on your small off-road engine/equipment is defective, the part will be repaired or replaced by Caterpillar.
Owner’s Warranty Responsibilities
As the small off-road engine/equipment owner, you are responsible for the performance of the required maintenance listed in your owner's manual. Caterpillar recommends that you retain all receipts covering maintenance on your small off-road engine/equipment, but Caterpillar cannot deny warranty coverage solely for the
lack of receipts or for your failure to ensure the performance of all scheduled maintenance.
As the small off-road engine/equipment owner, you should however be aware that Caterpillar may deny you warranty coverage if your small off-road engine/equipment or a part has failed due to abuse, neglect, improper maintenance or unapproved modifications.
You are responsible for presenting your small off-road engine/equipment to a Caterpillar distribution center or service center as soon as a problem exists. The warranty repairs shall be completed in a reasonable amount of time, not to exceed 30 days.
If you have any questions regarding your warranty rights and responsibilities, you should contact Caterpillar at 1-844-797-6387 or E-mail:
homeandoutdoorpower@cat.com
Defects Warranty Requirements:
(a) The warranty period begins on the date the
engine/equipment is delivered to an ultimate purchaser.
(b) General Emissions Warranty Coverage.
Caterpillar warrants to the ultimate purchaser and each subsequent owner that the engine or equipment is:
(1) Designed, built, and equipped so as to
conform with all applicable regulations adopted by the Air Resources Board; and
(2) Free from defects in materials and workmanship
that causes the failure of a warranted part for a period of three years
(c) The warranty on emission-related parts will be
interpreted as follows:
(1) Any warranted part that is not scheduled for
replacement as required maintenance in the written instructions must be warranted for the warranty period defined in Subsection (b)(2). If any such part fails during the period of warranty coverage, it must be repaired or replaced by Caterpillar according to Subsection (4) below. Any such part repaired or replaced under the warranty must be warranted for the remaining warranty period.
(2) Any warranted part that is scheduled only for
regular inspection in the written instructions must be warranted for the warranty period defined in Subsection (b)(2). A statement in
such written instructions to the effect of “repair
or replace as necessary” shall advise owners of the warranty coverage for emissions related parts. Replacement within the warranty period is covered by the warranty and will not reduce
22
the period of warranty coverage. Any such part repaired or replaced under warranty must be warranted for the remaining warranty period.
(3) Any warranted part that is scheduled for
replacement as required maintenance in the written instructions must be warranted for the period of time prior to the first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part must be repaired or replaced by Caterpillar according to Subsection (4) below. Any such part repaired or replaced under warranty must be warranted for the remainder of the period prior to the first scheduled replacement point for the part.
(4) Repair or replacement of any warranted part
under the warranty provisions must be performed at no charge to the owner at a warranty station.
(5) Notwithstanding the provisions of Subsection
(4) above, warranty services or repairs must be provided at distribution centers that are franchised to service the subject engine/equipment.
(6) The owner must not be charged for diagnostic
labor that leads to the determination that a warranted part is in fact defective, provided that such diagnostic work is performed at a warranty station.
(7) Caterpillar is liable for damages to other
engine/equipment components proximately caused by a failure under warranty of any warranted part.
(8) Throughout the emissions control system's
warranty period set out in subsection (b)(2), Caterpillar must maintain a supply of warranted parts sufficient to meet the expected demand for such parts and must obtain additional parts if that supply is exhausted.
(9) Manufacturer-approved replacement parts that
do not increase the exhaust or evaporative emissions of the engine or emissions control system must be used in the performance of any warranty maintenance or repairs and must be provided without charge to the owner. Such use will not reduce the warranty obligations of Caterpillar.
(10) Add-on or modified parts that are not
exempted by the Air Resources Board may not be used. The use of any non-exempted add-on or modified parts will be grounds for disallowing a warranty claim. Caterpillar will not be liable to warrant failures of warranted parts caused by the use of a non-exempted add-on or modified part.
(11) Caterpillar issuing the warranty shall provide
any documents that describe that warranty procedures or policies within five working days of request by the Executive Officer.
(d) Emission Warranty Parts List for exhaust
(1) Fuel Metering System
(i) Carburetor and internal parts (and/or
pressure regulator or fuel injection system)
(ii) Air/fuel ratio feedback and control system (iii) Cold start enrichment system
(2) Air Induction System
(i) Controlled hot air intake system (ii) Intake manifold (iii) Air filter
(3) Ignition System
(i) Spark plugs (ii) Magneto or electronic ignition system (iii) Spark advance/retard system
(4) Exhaust Gas Recirculation (EGR) System
(i) EGR valve body, and carburetor spacer if
applicable
(ii) EGR rate feedback and control system
(5) Air Injection System
(i) Air pump or pulse valve (ii) Valves affecting distribution of flow (iii) Distribution manifold
(6) Catalyst or Thermal Reactor System
(i) Catalytic converter (ii) Thermal reactor (iii) Exhaust manifold
(7) Particulate Controls
(i) Traps, filters, precipitators, and any other
device used to capture particulate emissions
(8) Miscellaneous Items Used in Above Systems
(i) Electronic controls (ii) Vacuum, temperature, and time sensitive
valves and switches
(iii) Hoses, belts, connectors, and assemblies.
(e) Emissions Warranty Parts List for
Evaporative Emissions
(1) Fuel Tank (2) Fuel Cap (3) Fuel Lines (for liquid fuel and fuel vapors) (4) Fuel Line Fittings (5) Clamps* (6) Pressure Relief Valves* (7) Control Valves* (8) Control Solenoids* (9) Electronic Controls* (10) Vacuum Control Diaphragms* (11) Control Cables* (12) Control Linkages* (13) Purge Valves* (14) Gaskets* (15) Liquid/Vapor Separator (16) Cabon Canister (17) Canister Mounting Brackets (18) Carburetor Purge Port Connector
*Note: As they relate to the evaporative emission control system
23
WARRANTY
CATERPILLAR LIMITED WARRANTY
FOR INVERTER GENERATOR MODEL:
INV1250, INV2000, INV2250
Purchased in the United States and Canada
Caterpillar (Newberry) LLC. (Caterpillar) warrants to the original purchaser that any new Cat® branded portable generator products purchased in the United States and Canada are free from defects in materials and workmanship for the warranty period set forth below, provided that the product is operated and maintained in accordance with Caterpillar's instructions and manuals. Caterpillar will, at its option, repair or replace any part which, upon inspection by Caterpillar or a Caterpillar authorized service representative, is found to be defective during the warranty period as set forth below. Any product that the purchaser claims to be defective must be returned to and examined by the nearest Caterpillar authorized service representative
located in the United States or Canada. Transportation and associated costs and risk of loss are the responsibility of the purchaser.
Warranty Period:
All new inverter generator products are warranted under normal use for a period of two (2) years from the date of original purchase or under commercial use for a period of (6) months from the date of original purchase. If proof of original purchase is not presented, the manufacturer's shipping date will be used to determine the start of the warranty period. To help with any warranty claims, the original purchaser should register the product on www.cat.com/homeandoutdoorpower-support immediately following the purchase.
By means of registering the product on www.cat.com/homeandoutdoorpower-support within thirty (30) days from the date of purchase, original purchasers have the option to extend the Warranty Period by one additional year for a total of three (3) years calculated from the date of original purchase of the product.
This Warranty shall NOT apply to the following:
1. Damage or deterioration caused by normal wear and tear.
2. Failures caused by any external cause or act of God, such as accident, collision, theft, vandalism, riots, wars, fire, freezing, lightning, earth-quakes, windstorms, hail, volcanic eruptions, floods, tornados or hurricanes.
3. Failures due to alterations, adjustments, unauthorized fuel setting changes, neglect or improper storage, repair and/or maintenance.
4. Failures due to abuse or application of the product for uses other than for which it is designed or intended to by the manufacturer, including but not limited to, improper installation or location in a contaminated, harsh, corrosive or saltwater environment.
5. Failures resulting from attachments, accessory items, and parts not sold, issued or approved by Caterpillar.
6. Failures caused by contaminated or improper fuels, fuels, oils or other operating media or improper fluid levels.
7. Failures resulting from user’s delay in making the product available after being notified of a potential product problem.
8. Cosmetic damage, discolorations, rusting, corrosion or scratches to applied paint.
9. Replacement of consumables such as, but not limited to, fuses, lamps, filters, etc.
10. Repair by any party other than a Caterpillar authorized service representative.
11. Additional expenses for repair after normal business hours, i.e. overtime or holiday labor rates.
12. Expenses for rental of equipment during downtime and/or performance of warranty repairs.
13. Expenses related to investigating performance complaints and/or troubleshooting where no manufacturing defect is found.
14. Starting batteries are NOT covered under this warranty but will be covered under the portable generator parts warranty.
To obtain warranty service or if you have questions concerning this warranty or its applications, please call 1-844-797-6387 or visit
www.cat.com/homeandoutdoorpower-support, where you can also search for your nearest authorized Cat service representative.
CONSUMER ARBITRATION CLAUSE: MANDATORY BINDING INDIVIDUAL ARBITRATION INSTEAD OF COURT; CLASS ACTION WAIVER
a. You and Caterpillar both agree that, to the extent permitted by
applicable law, any and all disputes or claims arising out of or relating in any way to Cat Branded portable generator products or services related thereto, or from any advertising for any such products or services, including any question regarding the existence, validity, or termination of this Caterpillar Limited Warranty, as well as any issue regarding the interpretation of the terms and conditions of this Consumer Arbitration Clause will be resolved by binding arbitration before a sole arbitrator, rather than in court, except that you may assert claims in small claims court if your claims qualify. This also includes any claims that arose before you accepted this Caterpillar Limited Warranty, regardless of whether prior versions of the Limited Warranty required arbitration. In the US, The Federal Arbitration Act (9 U.S.C. § 1 et seq.) and federal arbitration law apply to the Caterpillar Limited Warranty and the terms and conditions of this Consumer Arbitration Clause.
b. Arbitration uses a neutral arbitrator instead of a judge and jury. An
arbitrator can award on an individual basis the same damages and relief as a court (including injunctive and declaratory relief or statutory damages) and must follow theterms of this Limited Warranty (including the terms and conditions of this Consumer Arbitration Clause) as a court would. Arbitration procedures allow
for more limited discovery, and court review of an arbitration award is limited.
c. If you have a dispute and elect to seek arbitration or file a claim in
small claims court, you must first send to Caterpillar, by certified mail, a written notice of your claim that (a) describes the nature and basis of the claim or dispute; (b) sets forth the specific relief sought and (c) includes a physical address and email address where you may be reached ("Notice"). The Notice must be addressed to: General Counsel, Caterpillar Inc., 100 N.E. Adams
St. Peoria Illinois 61629 (“Notice Address”) and reference a “Notice of Claim under Caterpillar Limited Warranty.” If Caterpillar
and you do not reach an agreement to resolve the claim within 60 days after the Notice is received, you or Caterpillar may commence an arbitration proceeding or file a claim in small claims court.
d. You may download or copy a form to initiate arbitration at
www.adr.org. If you are required to pay a filing fee, after
Caterpillar receives notice at the Notice Address that you have commenced arbitration, Caterpillar will reimburse you for your payment of the filing fee, unless your claim is for greater than US$25,000, in which case you will be responsible for filing fees.
24
e. The arbitration will be governed by the AAA’s then current
Consumer Arbitration Rules, as modified by the terms set forth in this Limited Warranty (including the terms and conditions of this Consumer Arbitration Clause), and will be administered by the AAA. The AAA Rules and Forms are available online at www.adr.org or by calling the AAA at 1-800-778-7879. In the event of any conflict between the terms set forth herein and the AAA Consumer Arbitration Rules, these terms will apply.
f. If your claim totals less than US$25,000, Caterpillar will pay for all
administrative and arbitration fees, including the arbitrator’s
compensation, and will reimburse you for any administrative and arbitration fees that you incur. If your claim exceeds US$25,000, the parties will pay equal shares of any administrative and
arbitration fees, including the arbitrator’s compensation, except for
such fees that the AAA Consumer Arbitration Rules require Caterpillar to pay in full. Each party will bear the expense of its own counsel, experts, witnesses, and preparation and presentation of evidence at any arbitration hearing.
g. If your claim is for US$25,000 or less, you and Caterpillar agree that
you may choose whether the arbitration will be conducted solely on the basis of documents or through a telephonic hearing. You may also request an in-person hearing, which the arbitrator may grant at his or her discretion. If the arbitrator grants an in-person hearing, such hearing will be conducted either at a mutually agreed location or a location determined by the AAA or the arbitrator. In such an in­person hearing, the parties, or any of their witnesses, have the right to participate remotely by way of videoconference or some similar means. If your claim exceeds US$25,000, the right to a hearing will be determined by the arbitrator.
h. You and Caterpillar agree that, to the extent permitted by applicable
law, any dispute resolution proceedings, whether in court or before an arbitrator, will be conducted only on an individual basis and not in a class, representative, consolidated, or mass action. Neither you nor Caterpillar may join or consolidate claims by or against a third party, or arbitrate or otherwise participate in any claim as a class representative, class member or in a private attorney general capacity. If this provision is found to be unenforceable, then the entirety of the terms and conditions of these Dispute Resolution and Arbitration paragraphs (other than paragraph (k)) shall be null and void.
i. Any arbitration will be confidential. Neither you, Caterpillar, the AAA,
nor the arbitrator may disclose the existence, content (including any oral or written submissions), or results of any arbitration, except as may be required by law or for purposes of enforcing or challenging of the arbitration award.
j. You may opt out of this dispute resolution procedure by providing
written notice to Caterpillar at the Notice Address no later than 30 calendar days from the date of your purchase of Caterpillar products or services (or date of first use, in the case of free products or services) covered by this Limited Warranty. Opting out of this dispute resolution procedure will not otherwise affect the coverage or applicability of the Limited Warranty, or your ability to purchase or use Cat branded portable generator products or services, in any way.
k. If for any reason a claim proceeds in court rather than in arbitration
or small claims court, including if you opt out under paragraph (j), to the extent permitted by applicable law, we each waive any right to a jury trial and agree that any such proceeding shall be conducted only on an individual basis and not in a class, representative, consolidated, or mass action. Under such circumstances, you and Caterpillar agree that, to the extent any dispute arises out of a Cat branded portable generator sold in the US, the federal and state courts of the State of Illinois have exclusive jurisdiction to hear and determine any such claim, consent to the personal jurisdiction of any federal or state court in the State of Illinois, and acknowledge that venue is proper in any judicial district within the State of Illinois. If any part of these Dispute Resolution and Arbitration provisions or this paragraph (k) is found to be unenforceable, the remainder of these Dispute Resolution and Arbitration Provisions and this paragraph (k) shall still be given full force and effect.
l. In the event that any provision of this agreement is found to be
invalid or unenforceable in a particular case or jurisdiction, that provision will be severable in that case or jurisdiction, as the case may be, without affecting the validity and enforceability of the remaining provisions of the agreement, and shall not affect the validity and enforceability of the agreement in other cases and jurisdictions.
Applicable Law
m. By purchasing or using any Cat branded portable generator product
or service related thereto, you agree that, to the degree permitted by applicable law, the Federal Arbitration Act, applicable federal law, and laws of the State of Illinois, without regard to its conflict of laws rules, will govern the terms of this Limited Warranty, as well as any dispute of any sort that might arise between you and Caterpillar relating to such products or services.
n. If a dispute arises out of a Cat branded portable generator sold in
Canada the foregoing dispute resolution and arbitration terms will apply to the extent permitted by applicable law. If the foregoing
terms are not binding upon you under the applicable law of your jurisdiction, and the dispute is within the jurisdiction of the small claims court in your province, you may choose to take your claim to that court. If the dispute exceeds the jurisdiction of the small claims court in your province, you agree to submit to the jurisdiction of the courts within your province for the purpose of litigating all claims, disputes, actions or causes of action, issues or requests for relief arising out of or relating to this Limited Warranty, which courts shall have exclusive jurisdiction over all such claims, disputes, actions or causes of action, issues or requests for relief.
Limitations
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, CATERPILLAR MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. CATERPILLAR'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL CATERPILLAR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF CATERPILLAR'S NEGLIGENCE.
This warranty is subject to and shall not apply in contravention of the laws or other legal compliance requirements of the United States or any other applicable jurisdiction, without recourse or liability with respect to Caterpillar.Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you. This warranty gives you specific legal rights. You may also have other rights from state to state, or territory.
In USA and Canada: Caterpillar Newberry LLC, Electric Power Division, 40 Mawsons Way, SC 29108-6400, Attention:Customer Service Manager, Telephone (844)-797-6387. Outside the USA and Canada: Contact your Authorized Service Representative
www.cat.com/homeandoutdoorpower-support or email
homeandoutdoorpower@cat.com.
© 2020 Caterpillar. All Rights Reserved. CAT, CATERPILLAR,
LET’S DO THE WORK, their respective logos, "Caterpillar Yellow", the "Power Edge" and Cat “Modern Hex” trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission. www.cat.com/homeandoutdoorpower