Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock
or other conditions which may cause personal injury or
property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the
individual instructions package
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloths for brazing operations and have a fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult
local building codes and appropriate national electrical codes
(in USA, ANSI/NFPA70, National Electrical Code (NEC); in
Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the
safety-alert symbol . When you see this symbol on the unit
and in instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices,
which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or
operation.
Page 2
ELECTRICAL SHOCK HAZARD
LEGEND
TXV — Thermostatic Expansion Valve
Failure to follow this warning could cause personal injury
or death.
Before performing service or maintenance operations on
unit, always turn off main power switch to unit and install
lockout tag. Unit may have more than one power switch.
UNIT OPERA TION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
Puron® (R-410A) refrigerant systems operate at higher
pressures than standard R-22 systems. Do not use R-22
service equipment or components on Puron refrigerant
equipment.
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal injury
or death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing 40RU units.
4. This installation must conform with local building codes
and with the NEC (National Electrical Code) or ANSI
(American National Standards Institute)/NFPA (National
Fire Protection Association) latest revision. Refer to
provincial and local plumbing or wastewater codes and
other applicable local codes.
Moving and Storage — To transfer unit from truck to
storage site, use a fork truck. Do not stack units more than
2 high during storage. If unit is to be stored for more than
2 weeks before installation, choose a level, dry storage site free
from vibration. Do not remove plastic wrap or skid from unit
until final installation.
Rigging — All 40RU Series units can be rigged by using
the shipping skid. Units are shipped fully assembled. Do not
remove shipping skids or protective covering until unit is ready
for final placement; damage to bottom panels can result. Use
slings and spreader bars as applicable to lift unit.
INSTALLATION
General — Allow 2
clearance and airflow. For units equipped with an economizer,
refer to the accessory installation instructions for additional
clearance requirements. Be sure floor, wall, or ceiling can
support unit weight (T ables 1A – 1D). See Fig. 2A and Fig. 2B
for dimensions.
Uncrating — Move unit as near as possible to final loca-
tion before removing shipping skid.
Remove metal banding, top skid, and plastic wrap. Examine
unit for shipping damage. If shipping damage is evident, file
claim with transportation agency. Remove base skid just prior
to actual installation.
Check nameplate information against available power supply
and model number description in Fig. 3.
NOTE: Be sure to remove the styrofoam shipping pad from
the thermostatic expansion valve (TXV). Verify that it has
been removed. See Fig. 1.
1
/2 ft at front and side of unit for service
UNIT OPERA TION HAZARD
Failure to follow this caution could cause equipment
damage.
Ensure voltage listed on unit data plate agrees with
electrical supply provided for the unit.
PRE-INSTALLATION
1. The power supply (v, ph, and Hz) must correspond to that
specified on unit rating plate.
2. The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.
3. Refer to Installation, General section (page 2) and
Fig. 2A and Fig. 2B for locations of electrical inlets, condensate drain, duct connections, and required clearances
before setting unit in place.
Fig. 1 — Foam Block Location
Accessories — Refer to instructions shipped with each
Table 1A — 40RUA Physical Data, English — Cooling Units
UNIT 40RUA*252830
NOMINAL CAPACITY (Tons)202530
OPERATING WEIGHT (lb)
Base Unit with TXV73010501062
Plenum225325325
FANS
Qty...Diam. (in.)2...152...182...18
Nominal Airflow (cfm)8,00010,00012,000
Airflow Range (cfm)6,000 – 10,0007,500 – 12,5009,000 – 15,000
Nominal Motor Hp (Standard Motor)
208/230-3-60 and 460-3-605.07.510.0
575-3-605.07.510.0
Motor Speed (rpm)
208/230-3-60 and 460-3-60174517451745
575-3-60174517551755
REFRIGERANTR-410A
Operating charge (lb)
(approx per circuit)
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig)450
Face Area (sq ft)19.8824.8629.83
No. of Splits222
No. of Circuits per Split182024
Split Type...PercentageFace...50/50
Fins/in.171515
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)2...1
DX Coil — Liquid Refrigerant (ODF)2...5/
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...1/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (in.)
Access LocationEither Side
STEAM COIL
‡
Max Working Pressure (psig at 260°F)
Total Face Area (sq ft)13.3315.015.0
Rows...Fins/in.1...101...101...10
HOT WATER COIL
Max Working Pressure (psig)150
Total Face Area (sq ft)13.3315.015.0
Rows...Fins/in.2...8.52...12.52...12.5
Water Volume
Table 1B — 40RUA Physical Data, SI — Cooling Units
UNIT 40RUA*252830
NOMINAL CAPACITY (kW)7087105
OPERATING WEIGHT (kg)
Base Unit with TXV331477482
Plenum102148148
FANS
Qty...Diam. (mm)2...3812...4572...457
Nominal Airflow (L/s)377541195663
Airflow Range (L/s)2831 – 47193539 – 58994247 – 7079
Nominal Motor kW (Standard Motor)
208/230-3-60 and 460-3-603.735.607.46
575-3-603.735.607.46
Motor Speed (r/s)
208/230-3-60 and 460-3-6029.129.129.1
575-3-6029.129.329.3
REFRIGERANTR-410A
Operating charge (kg)
(approx per circuit)
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag)3102
Face Area (sq m)1.852.302.77
No. of Splits222
No. of Circuits per Split182024
Split Type...PercentageFace...50/50
Fins/m670591591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)2...1
DX Coil — Liquid Refrigerant (ODF)2...5/
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...1/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (mm.)
Access LocationEither Side
STEAM COIL
‡
Max Working Pressure (kPag at 126°C)138
Total Face Area (sq m)1.241.391.39
Rows...Fins/m1...3941...3941...394
HOT WATER COIL
Max Working Pressure (kPag)1034
Total Face Area (sq m)1.241.391.39
Rows...Fins/m2...3352...3352...335
Water Volume
Table 1C — 40RUS Physical Data, English — Chilled Water Units
UNIT 40RUS*252830
NOMINAL CAPACITY (Tons)202530
OPERATING WEIGHT (lb)
Base Unit68310351042
Plenum225325325
FANS
Qty...Diam. (in.)2...152...182...18
Nominal Airflow (cfm)8,00010,00012,000
Airflow Range (cfm)6,000 – 10,0007,500 – 12,5009,000 – 15,000
Nominal Motor Hp (Standard Motor)
208/230-3-60 and 460-3-605.07.510.0
575-3-605.07.510.0
Motor Speed (rpm)
208/230-3-60 and 460-3-60174517451745
575-3-60174517551755
CHILLED WATER COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig)435
Face Area (sq ft) – Upper11.012.415.5
Face Area (sq ft) – Lower8.312.412.4
Rows...Fins/in.3...15
PIPING CONNECTIONS,
Quantity...Size (in.)
3
Chilled Water — In2...1
Chilled Water — Out2...1
Steam Coil, In (MPT)1...2
Steam Coil, Out (MPT)1...11/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (in.)
Access LocationEither Side
STEAM COIL
‡
Max Working Pressure (psig at 260°F)20
Total Face Area (sq ft)13.3315.015.0
Rows...Fins/in.1...101...101...10
HOT WATER COIL
‡
Max Working Pressure (psig)150
Total Face Area (sq ft)13.3315.015.0
Rows...Fins/in.2...8.52...12.52...12.5
Water Volume
(gal)13.914.3
3
)1.11.90
(ft
LEGEND
‡
Field installed accessory only.
/8 ODM2...21/8 ODM2...21/8 ODM
3
/8 ODM2...21/8 ODM2...21/8 ODM
1
/
2
2
1
/4 ODM/1 IDF
4...16 x 20 x 2
4...16 x 24 x 2
4...20 x 24 x 2
4...20 x 25 x 2
7
Page 8
Table 1D — 40RUS Physical Data, SI — Chilled Water Units
UNIT 40RUS*252830
NOMINAL CAPACITY (kW)7087105
OPERATING WEIGHT (kg)
Base Unit310469473
Plenum102148148
FANS
Qty...Diam. (mm)2...3812...4572...457
Nominal Airflow (L/s)377547195663
Airflow Range (L/s)2831 – 47193539 – 58994247 – 7079
Nominal Motor kW (Standard Motor)
208/230-3-60 and 460-3-603.735.607.46
575-3-603.735.607.46
Motor Speed (r/s)
208/230-3-60 and 460-3-6029.129.129.1
575-3-6029.129.329.3
CHILLED WATER COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag)2999
Face Area (sq m) – Upper1.021.151.44
Face Area (sq m) – Lower0.771.151.15
Rows...Fins/m3...5913...5913...591
PIPING CONNECTIONS,
Quantity...Size (in.)
3
Chilled Water — In2...1
Chilled Water — Out2...1
Steam Coil, In (MPT)1...2
Steam Coil, Out (MPT)1...11/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (mm.)
Access LocationEither Side
STEAM COIL
‡
Max Working Pressure (kPag at 125°C)138
Total Face Area (sq m)1.241.391.39
Rows...Fins/m1...3941...3941...394
HOT WATER COIL
‡
Max Working Pressure (kPag)1034
Total Face Area (sq m)1.241.391.39
Rows...Fins/m2...3352..4932...493
Water Volume
(L)52.654.1
3
)0.0520.054
(m
LEGEND
‡
Field installed accessory only.
/8 ODM2...21/8 ODM2...21/8 ODM
3
/8 ODM2...21/8 ODM2...21/8 ODM
1
/
2
2
1
/4 ODM/1 IDF
4...406 x 508 x 51
4...406 x 610 x 51
4...508 x 610 x 51
4...508 x 635 x 51
8
Page 9
Fig. 3 — Model Number Nomenclature
123456789 10 11 12 13 14 15 16 17 18
4 0 R U A A 2 5 A 1 A 6– 0 A 0 A 0
_________________
Model TypeBrand / Packaging
40RU = Carrier Fan Coil
Puronr R---410A Refrigerant
0=Standard
Typ e of C oil
Not Used
A=StandardDXCoil
A=PlaceHolder
S = Chilled Water Coil
Refrigerant Options
Service Options
C = Hot Water Coil
A=None
B = Steam Coil
0 = Non-Painted Cabinet
1=PaintedCabinet
Nominal Tonnage
25 = 20 Tons
28 = 25 Tons
Not Used
30 = 30 Tons
A=PlaceHolder
Not Used
0=PlaceHolder
Not Used
A=PlaceHolder
Design Rev
--- = Catalog Model Number
Indoor Fan Options
1 = Fan Drive and Motor - Low / Motor Efficiency - Standard
Voltage
2 = Fan Drive and Motor - Med / Motor Efficiency - Standard
1 = 575/3/60
3 = Fan Drive and Motor - High / Motor Efficiency - Standard
4 = Fan Drive and Motor - Low / Motor Efficiency - Premium
5 = Fan Drive and Motor - Med / Motor Efficiency - Premium
5 = 208/ 230/3/60
6 = 460/3/60
6 = Fan Drive and Motor - High / Motor Efficiency - Premium
Coil Options
A=Al/Cu
SETANGISEDNOITISOP
)radnelac lacsif( erutcafunam fo keeW1−2
)ASU ,saxeT ,PTE = G( noitacol gnirutcafunaM5
rebmun laitneuqeS6−10
12345678910
4808G12345
POSITION NUMBER
TYPICAL
Year of manufacture (”08” = 2008)3−4
LEGEND
Accessory Line
Alternate Air Intake and Discharge
Air Intake and Discharge
Note:
Maintain recommended clearances
per Figs. 2A–2B
Unit Positioning — The unit can be mounted on the
floor for vertical application with return air entering the face of
the unit and supply air discharging vertically through the top of
the unit. The unit can also be applied in a horizontal
arrangement with return air entering horizontally and the
supply air discharging horizontally. When applying the unit in
a horizontal arrangement, ensure the condensate drain pan is
located at the bottom center of the unit for adequate condensate
disposal. See Fig. 5 for condensate connections for each unit
position.
T ypical positioning and alternate return air locations are shown
in Fig. 5. Alternate return air locations can be used by moving
the unit panel from the alternate return air location to the
standard return air location. Refer to overhead suspension
accessory drawing (Fig. 6) for preferred suspension technique.
The unit needs support underneath to prevent sagging.
IMPORTANT: Do NOT attempt to install unit with return
air entering top panel of unit. Condensate will not drain
from unit.
Fig. 4 — Serial Number Nomenclature
9
Fig. 5 — Typical Unit Positioning
Page 10
OVERHEAD SUSPENSION ACCESSORY
UNIT SIZE 25
UNIT SIZES 28, 30
NOTE: Dimensions in [ ] are millimeters
Fig. 6 — Preferred Suspension Technique
10
Page 11
Unit Isolation — Where extremely quiet operation is
essential, install isolators between floor and base of unit, or
between ceiling and top section of unit.
Be sure that unit is level and adequately supported. Use
channels at front and sides of unit for reference points when
leveling.
Refrigerant and Chilled Water Piping
Access —
knockouts for refrigerant and chilled water piping. These
knockouts are located on both sides of the unit for installation
flexibility. The standard knockouts provide sufficient access to
the unit’s coils for all 40RUA*25, 28, and 30 units. RUS*25,
28, and 30 units require additional holes which must be fieldfabracated to accomodiate the piping. See Fig. 7 for the
positions and dimensions of the additional access holes
required for the RUS units. Recommended access hole use is
also listed for all units. Note that Fig. 7 shows the access holes
on the control-box side of the unit; this is the side of the unit
with the coil headers, so it is used most often for piping access.
IMPORTANT : Do not bury refrigerant piping underground.
The 40RU Series units come with standard
Refrigerant Piping — See Tables 1A–1D for refrigerant
pipe connection sizes. For ease in brazing, it is recommended
that all internal solder joints be made before unit is placed in
final position.
The 40RU direct-expansion units have internal
factory-installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R-410A. See Table 2
for part numbers. Knockouts are provided in the unit corner
posts for 40RU refrigerant piping. See Fig. 7, which also
lists recommended knockouts and access holes to use for
each 40RU unit size. Recommended fittings are listed in
Table 3.
The sensor bulb capillary tubes must be routed from the TXVs
inside the unit through one of the piping access holes. Clamp
the TXV sensor bulb on a vertical portion of the suction line,
outside the unit. See Fig. 8.
NOTE: Be sure to remove the styrofoam shipping pad from
the TXV. Verify that it has been removed. See Fig. 1.
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped portion
of the suction line.
The 40RU Series evaporator coils have a face-split design.
Ensure that lower circuit of coil is first on/last off when
connected to the condensing unit and/or system controls. See
Fig. 9.
External TXV equalizer connections are provided and
factory-brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction line at
least 45 degrees above bottom, at approximately the 4 o’clock
or 8 o’clock position. See Fig.10.
8
7
6
5
4
3
2
1
Fig. 7 — Refrigerant and Chilled Water Piping Access Holes
11
B
A
D
C
Page 12
LEGEND:
TXV – Thermostatic Expansion Valve
NOTE: Component location arrangemet shown for field installatio n of
sight glasses, solenoid valves, filter driers, and TXV sensin g bulbs.
The TXVs and equilizer lines are factory installed.
UPPER
– Not required when mated to units 38AP_025 - 060
*
FIRST ON/LAST OFF = B
VERT ICAL INSTALL ATION
FIRST ON/LAST OFF = A
HORIZONT AL INS TAL LATION
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: The 8 o’clock position is sho w n above.
SPLIT
AIRFLOW
LOWER
SPLIT
TXV
SENSING
BULB
15 DIAMS
MIN
TXV
SENSING
BULB
10
DIAMS
8 DIAMS
MIN
EQUALIZER LINE
TXV
EQUALIZER
LINE
FILTER
DRIER
SOLENOID*
VALV E
SIGHT
GLASS
8 DIAMS
MIN
TXV
INDOOR
COIL
AIRFLOW
15 DIAMS
MIN
10
DIAMS
Fig. 8 — Face-Split Coil Suction and Liquid Line Piping (Typical)
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.
TXV
Qty...Part No.
DISTRIBUTOR
Qty...Part No.
2...1135
2...1126
2...1126
Table 3 — Fitting Requirements
UNIT
40RUA25
40RUS25
ACCESS
HOLE NO.
‡
1SuctionLower
2LiquidLower
3LiquidUpper
4SuctionUpper
4SupplyLower
5ReturnLower
6ReturnUpper
7SupplyUpper
CONNECTION
TYPE
FEEDER TUBES
PER DISTRIBUTOR
CIRCUIT
Qty...S iz e (in.)
18...3/
16
3
20...
/
16
3
/
24...
16
1
1
/8 Street Elbow
1
/8 Nipple, 75/8 L
1
1
/8 Long Radius Elbow
1
5
/8 Street Elbow
5
/8 Nipple, 61/2 L
5
/8 Long Radius Elbow
5
/8 Street Elbow
5
/8 Nipple, 91/2 L
5
/8 Long Radius Elbow
1
/8 Nipple, 55/8 L
1
1
/8 Long Radius Elbow
1
1
/8 Nipple, 11 L
1
1
/8 Long Radius Elbow
1
3
1
/8 Long Radius Elbow
3
/8 Nipple, 33/4 L
1
3
/8 Long Radius Elbow
1
3
/8 Long Radius Elbow
1
3
/8 Nipple, 33/8 L
1
3
/8 Long Radius Elbow
1
3
/8 Long Radius Elbow
1
3
/8 Nipple, 7 L
1
3
1
/8 Long Radius Elbow
3
/8 Long Radius Elbow
1
3
/8 Nipple, 113/4 L
1
3
1
/8 Long Radius Elbow
†
NOZZLE
Qty...Part No.
2...G6
2...C15
2...C17
FITTINGS REQUIRED
(in.)
†
13
Page 14
Table 3 — Fitting Requirement (cont)
UNIT
ACCESS
HOLE NO.
‡
1SuctionLower
2LiquidLower
40RUA28
3LiquidUpper
4SuctionUpper
5SupplyLower
6ReturnLower
40RUS*28, 30
7ReturnUpper
8SupplyUpper
1SuctionLower
2LiquidLower
40RUA*30
3LiquidUpper
4SuctionUpper
‡
See Fig. 7 for access hole location by number.
† Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
CONNECTION
TYPE
CIRCUIT
FITTINGS REQUIRED
3
1
/8 Street Elbow
3
/8 Nipple, 11 L
1
3
/8 Long Radius Elbow
1
5
/8 Street Elbow
5
/8 Nipple, 11/2 L
5
/8 Long Radius Elbow
5
/8 Street Elbow
5
/8 Nipple, 191/2 L
5
/8 Long Radius Elbow
3
/8 Nipple, 43/16 L
1
3
/8 Long Radius Elbow
1
3
/8 Nipple, 231/4 L
1
3
/8 Long Radius Elbow
1
1
2
/8 Long Radius Elbow
1
/8 Nipple, 31/2 L
2
1
/8 Long Radius Elbow
2
1
/8 Long Radius Elbow
2
1
/8 Nipple, 3 L
2
1
/8 Long Radius Elbow
2
1
/8 Long Radius Elbow
2
1
/8 Nipple, 67/8 L
2
1
/8 Long Radius Elbow
2
1
/8 Long Radius Elbow
2
1
/8 Nipple, 117/8 L
2
1
/8 Long Radius Elbow
2
3
1
/8 Street Elbow
3
/8 Nipple, 3 L
1
3
/8 Long Radius Elbow
1
5
/8 Street Elbow
5
/8 Nipple, 73/4 L
5
/8 Long Radius Elbow
5
/8 Street Elbow
5
/8 Nipple, 181/2 L
5
/8 Long Radius Elbow
3
/8 Nipple, 43/16 L
1
3
1
/8 Long Radius Elbow
3
/8 Nipple, 191/4 L
1
3
/8 Long Radius Elbow
1
(in.)
†
14
Page 15
Chillled Water Piping — See Tables 1C and 1D for
chilled water connecton sizes. For ease in bazing, it it recommended that all internal solder joints be made before unit is
placed in final position.
Knockouts are provided in the unit corner posts for 40RUS refrigerant piping. Additional field-fabricated access holes are required for 40RUS chilled water piping. See Fig. 7, which lists
recommended knockouts and access holes to use for each
40RUS unit size.
To size, design, and install chilled water piping, consult the
Carrier System Design manual. See Fig. 11 for an example of a
typical installation. Recommended fittings are listed in T able 3.
To access 40RUS coil vents and drains, remove the unit side
panel over the coil header. Vent and drain plugs are on the top
and bottom of header, respectively. See the Service section for
information on preventing coil freeze-up during winter.
Fig. 11 — Typical 40RUS Chilled Water Piping
15
Page 16
Condensate Drain — Install a trapped condensate drain
3” MIN.
[76]
NOTE: Dimensions in [ ] are in millimeters
line to unit connection as shown in Fig. 12. The unit drain connection is a PVC stub. See Fig. 13. Some areas may require an
adapter to connect to either galvanized steel or copper pipe.
For these applications, install a field-supplied threaded PVC
adapter.
Fig. 12 — Condensate Drains
NOTE: A trap must be installed in the condensate drain
line to ensure that the static pressure of fans is balanced
with the water column in the drain line and that condensate
can drain completely from pan. Without a trap, air can be
drawn up drain line until water level in condensate pan
becomes equal to static pressure created by fans, preventing
complete drainage. Conditions will worsen as filters
become dirty .
Install clean-out plugs in trap. Pitch drain line downward to an
open floor drain or sump. Provide service clearance around
drain line to permit removal of unit panels. Observe all local
sanitary codes.
Fig. 13 — Drain Pan Slope Adjustment
As shipped, the unit’s condensate drain pan is NOT sloped towards the drain connection. The pan slope must be changed to
pitch towards the side of the unit with the drain connection. See
Fig. 13. Loosen the 2 screws next to the drain outlet at both
ends of the unit, push drain pan down in the slots near the drain
connection, and up in the slots on the opposite end. Retighten
screws. The pan should have a pitch of at least
1
/4-in. over its
length toward the drain connection.
Fan Motors and Drives — Motor and drive packages
are factory installed in all units. The motor and drive packages
consist of the following items:
1 — fan motor
1 — adjustable motor pulley
1 — fan pulley
2 — matched fan belts (40RUA*25-30, 40RUS*25-30 units)
For instructions on changing fan rotation, changing drive
speeds and adjusting drives, see Pulley and Drive Adjustment
in the Service section.
16
Page 17
Power Supply and Wiring — Check the unit data
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
A
LEGEND
TXV —
Th ermostatic Expans ion Valve
23
22
21
1
3
1
2
1
1
1
0
5
°
C
6
00
VR
J
A
W
FAN
CONTACTOR
24V
TERMINAL
BLOCK
POWER
WIRING
KNOCKOUT
plate to ensure that available power supply matches electrical
characteristics of the unit. Provide a disconnect switch with an
integrated lock-out feature of size required to provide adequate
fan motor starting current. See Tables 4-6 for unit electrical
data.
FAN SCROLL
MOTOR
ND DRIVE
FAN
CONTACTOR
BOX
WIRE
ACCESS
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit cabinet
must have an uninterrupted, unbroken electrical ground to
minimize the possibility of personal injury if an electrical
fault should occur. This ground may consist of electrical
wire connected to unit ground lug in control compartment,
or conduit approved for electrical ground when installed in
accordance with NEC (National Electrical Code); ANSI/
NFPA 70, latest edition (in Canada, Canadian Electrical
Code CSA [Canadian Standards Association] C22.1), and
local electrical codes.
FIRE HAZARD
Failure to follow this warning could result in intermittent
operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch
and condensing unit. Use only copper wire.
(See Fig. 14)
CONDENSATE
DRAIN
CONNECTION
(HORIZONTAL)
FILTER
ELEMENTS
FILTER
RETAINER
CLIP
FAN DRIVE
PULLEY
COIL
TXV BULB
ACCESS
REFRIGERANT
PIPING ACCESS
CONDENSATE
DRAIN
CONNNECTION
(VERTICAL)
Fig. 15 — Wiring and Service Access
(Side Panel Removed)
Fan motors are factory-installed on all units. Indoor-fan
contactors are located in the fan contactor box behind the side
access panel (see Fig. 15 and 16). Wire the thermostat to the
24-v control circuit terminal block located in the side of the fan
contactor control box, according to Fig. 17 or the unit label
diagram. If the air handler is part of a split system, complete the
wiring from the condensing unit to the thermostat shown in
Fig. 17.
Install disconnect switch and power wiring in accordance with
all applicable local codes. See Fig. 15-17 and the unit label
diagram. Connect power wiring with
Fig. 14 — Disconnect Switch and Unit
1
/4-in. ring terminal.
Fig. 16 — Fan Contactor Box and Terminal Block
(Cover Removed) (Typical)
17
Page 18
Table 4 — Electrical Data, Standard Motors
LEGEND
†
Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in accordance with NEC (National Electrical Code), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters’
Laboratories) Standard 1995.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percentage of
voltage imbalance.
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
Determine maximum deviation from average voltage
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
Maximum deviation is 6 v.
Determine percent voltage imbalance.
This amount of phase imbalance is satisfactory because it is below the maximum allowable 2%.
FLA— Full Load Amps
MOCP
—
Maximum Overcurrent Protection
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
393 + 403 + 396
3
=
119 2
3
=
397
% Voltage Imbalance = 100 x
6
397
=1.5%
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
EQUIP—Equipment
GND—Ground
HC—Heating Contactor
HTR—Electric Heater
IFC—Indoor-Fan Contactor
IFM—Indoor-Fan Motor
TB—Te rmin a l B l ock
T’STAT—Thermostat
Factory Wiring
Field Control Wiring
19
Page 20
Table 6 — Fan Contactor Coil Data
UNIT
40RU**
25, 28, 302410
VOLTAGE
(vac)
MAXIMUM
HOLDING
VA
Connecting Ductwork — Refer to the Carrier System
Design Manual for the recommended design and layout of
ductwork. Fig. 18 shows recommended duct connection to
units with 2 fans.
UNIT OPERA TION HAZARD
Failure to follow this caution could cause equipment
damage.
Do not operate unit without ductwork or discharge plenum
unless fan speed has been adjusted for external static
pressure of zero in. wg. Failure to do so may result in
motor overload.
DISCHARGE CONNECTIONS — Duct flanges are
factory-supplied; they are shipped inside the unit attached to
the hairpin end of the coil tube sheet for field installation.
Using the existing screws, install the duct flanges on the unit’s
fan deck. Each fan discharge requires 2 flanges; each flange
must be bent in the middle to conform to the discharge
opening. See Fig. 19. After flanges are installed, connect them
to the supply duct using a canvas connection to prevent
vibration. It is important that this connection be properly
fabricated to prevent high air friction losses and air noise.
RETURN CONNECTION — When usin g return-air
ductwork, route return-air duct to the unit’s return air inlet near
the filter rack, using a canvas connection to prevent
transmission of unit vibration. If the duct blocks off the unit’s
access panel, provide a slip joint in the ductwork to permit
removal for servicing.
OUTDOOR-AIR INLET CONNECTION — Connect outdoorair inlet to field-installed accessory economizer. Refer to
Economizer Installation Instructions.
Return-Air Filters — Type and size of filters are shown
in Tables 1A – 1D and are factory-supplied and factoryinstalled. In all units with 2 fans, a filter replacement tool
(hook) is shipped inside the unit for field use when replacing
filters. See the Service section for instructions on filter element
replacement.
Fig. 18 — Typical Fan Discharge Connections for Multiple Fan Units
20
Page 21
Fig. 19 — Duct Flange Installation
START-UP
Before starting unit, check the following and correct as
necessary:
• Is unit solidly supported?
• Is fan adjusted for speed and pulley alignment?
• Are pulleys, motor, and bearings securely mounted?
• Are there any loose parts that will rattle or vibrate?
• Is condensate drain pan pitched for correct drainage?
• Are coil baffle plates tight against coil to prevent air
bypass?
• Are all panels securely fastened?
• Are all electrical connections correct and tight?
Also refer to condensing unit instructions before starting a split
system. A split system start-up checklist is provided at the end
of these instructions.
SERVICE
Inspection and maintenance should be performed at regular intervals and should include the following:
• Complete cleaning of cabinet, fan wheel, cooling coil,
condensate pan and drain, heating coils, and return-air
grille (if present).
• Inspection of panels and sealing of unit against air
leakage.
• Adjustment of fan motor, belt, bearings, and wheels.
• Cleaning or replacement of filters.
• Testing for cooling/heating system leaks.
• Checking of all electrical connections.
Most unit service can be performed by removing one or both of
the unit’s side panels. Coil cleaning or removal or insulation
cleaning may require removal of a rear, top, or bottom panel,
depending on the unit’s orientation. When service is
completed, replace unit panels.
Panels — Panels are fastened to unit frame with sheet metal
screws. Fan and coil compartment must be sealed tightly after
service to prevent air from bypassing the cooling coil.
Fan Motor Lubrication — Fan motor supplied with
unit is permanently lubricated and requires no further
lubrication.
Fan Shaft Bearings — Size 25-30 units have pillow-
block bearings (Fig. 20) that must be lubricated with suitable
bearing grease approximately every 3 months. See Table 7 for
suitable lubricants.
Table 7 — Lubricant Data
MANUFACTURERLUBRICANT
MobilMobilplex EP No. 2
SunocoPrestige 42
TexacoMultifak 2
TexacoRegal AFB-2*
*Preferred lubricant, contains rust and oxidation inhibitors.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury
or death.
Before performing service or maintenance operations on
unit, always turn off main power switch to unit and install
lockout tag. Unit may have more than one power switch.
Fig. 20 — Fan Shaft, Bearings, and Fan Wheel (Typical)
21
Page 22
Centering Fan Wheel — If fan and fan shaft assembly
are not properly centered, blades may scrape against the blower
side scroll plate or may create an objectionable whistling noise.
It may be necessary to adjust individual fan wheels or move entire fan shaft. See the following two sections.
Fan Shaft Position Adjustment — Loosen set-
screw or locking collar of each fan shaft bearing. Slide shaft
into correct position and replace locking collar (Fig. 21). To replace locking collar, push collar up against inner face of bearing. Turn collar in direction of fan rotation until tight, and tighten setscrew. Tightening locking collar in direction of fan rotation results in further tightening of collar should setscrew work
itself loose.
Individual Fan Wheel Adjustment — Loosen the
2 locking bolts holding fan wheel hub to shaft. See Fig. 20.
Position fan wheel in center of the fan housing and tighten
locking bolts. Clearance between wheel and housing should be
the same on both sides.
Fan Belts — Motor mounting plate and motor support
angles are slotted to permit both vertical and horizontal
adjustment. Adjust belt(s) for correct deflection by loosening
motor plate mounting bolts, moving motor/plate assembly
forward or back, and retightening bolts. Press down on belt
with one finger midway between fan and motor pulleys to
check deflection. The correct deflection is
Fig. 22.
If complete belt replacement is required during servicing,
loosen the motor plate mounting bolts (Fig. 22), move motor/
plate assembly towards fan pulley, and pull belt(s) off pulleys.
Reverse the procedure with new bolts and readjust deflection.
1
/8-in. (3.2 mm). See
Fan Rotation — Correct fan rotation with respect to fan
outlet is shown in Fig. 23.
To reverse the direction of rotation of a 3-phase fan motor,
reverse any 2 of the power leads. Refer to the connection
diagram on the inside of motor terminal box cover for proper
reversing procedure of single-phase motor.
Fig. 21 — Fan Shaft Bearing
Fig. 22 — Fan Motor Mounting
22
Page 23
Fig. 23 — Fan Rotation
Fan Pulley Alignment — Align as follows:
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan pulley
to lock it in place.
3. Use the methods shown in Fig. 24 to check proper pulley
alignment.
4. If pulleys are not in correct alignment, loosen the motor
holddown bolts and slide the motor axially until the
pulleys are aligned.
5. Tighten motor holddown bolts.
Pulley and Drive Adjustment — To obtain desired
fan speed, refer to the fan motor and drive data in Tables
8A-11D and adjust fan motor pulley as follows:
1. Remove belt from fan motor pulley after loosening motor
from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw
moveable flange toward fixed flange to increase the fan
speed and away from fixed flange to reduce speed.
Before tightening setscrew, make certain that setscrew is
over nearest flat surface of pulley hub (Fig. 24).
UNIT OPERA TION HAZARD
Failure to follow this caution could cause equipment
damage.
Increasing fan speed produces a greater load on motor. Do
not exceed rated capacity of motor.
Condensate Drains — Keep condensate drains free of
dirt and foreign matter.
Return-Air Filters — Refer to Replacing Filters section
for filter accessibility and removal. Replace with clean filters of
the sizes listed in Tables 1A-1D.
Chilled Water Coil Freeze Protection — Shut off
water supply to unit. Remove side panel of unit and remove
vent and drain plugs in top and bottom of coil header. Drain
coil and blow out remaining water. Reinstall plugs and side
panel.
Fig. 24 — Fan Pulley Adjustments
Alternative freeze protection methods follow:
• Circulate hot water within the water coil’s supply main
or supplementary space heating.
• Close off supply lines to unit and open a union or fieldsupplied drain valve in the return line.
IMPORTANT: Draining from return line will not completely drain water from coils.
• After draining as much water as possible from coils, add
sufficient antifreeze to prevent residual water in the coil
from freezing.
• Add a sufficient quantity of non-corrosive antifreeze to
the entire system to prevent all water within the system
from freezing.
Coil Removal — Remove unit panels and corner posts as
required. Disconnect coil connections and remove fastening
screws. Remove coil through end or side sections of unit.
Remove any heavy dirt that may have accumulated on underside of coil. Coil can be cleaned more easily with a stiff brush,
vacuum cleaner, or compressed air when coil is dry. If coil is
wet or if water is to be used for cleaning, guard against splashing water on electrical components or damaging surrounding
area. Clean coil baffles as applicable and check for tight fit to
be sure air does not bypass coil.
Cleaning Insulation — The insulation contains an im-
mobilized antimicrobial agent that helps prevent the growth of
bacteria and fungi. Clean the inner surface of the insulation
according to the separate maintenance instructions shipped
with the unit.
23
Page 24
Replacing Filters — Filters can be removed and in-
FILTER
RETAINE
CLIP
SLIDE
stalled from either side of the unit. Install new filters in units
that have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 25).
3. Remove old filters by lifting and tilting them out of the
filter track. See Fig. 15 and 26. Use the factory-supplied
filter hook to slide filters within reach for removal. The
filter hook is shipped inside the unit in the filter track
4. Reverse the procedure to install new filters.
UNIT OPERA TION HAZARD
Failure to follow this caution could cause equipment
damage.
Do not operate unit without air filters.
Fig. 26 — Filter Removal/Replacement
Fig. 25 — Remove Filter Retainer Clip
24
Page 25
Table 8A — Fan Motor Data, Standard Motor — English
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
208/230-3-60 and 460-3-60
Speed (rpm)174517451745
Hp5.07.510.0
Frame (NEMA)S184TS213TS215T
Shaft Dia (in.)1
1
/
8
13/
8
575-3-60
Speed (rpm)174517551755
Hp5.07.510.0
Frame (NEMA)184TS213TD215T
Shaft Dia (in.)1
LEGEND
NEMA — National Electrical Manufacturers Association
1
/
8
13/
8
Table 8B — Fan Motor Data, Alternate Motor — English
UNIT
40RUA*25
40RUS*25
208/230-3-60 and 460-3-60
Speed (rpm)174517451745
Hp7.510.010.0
Frame (NEMA)S213TS215TS215T
Shaft Dia (in.)1
3
/
8
575-3-60
Speed (rpm)175517501750
Hp7.510.010.0
Frame (NEMA)S213TD215TD215T
Shaft Dia (in.)1
LEGEND
NEMA — National Electrical Manufacturers Association
3
/
8
40RUA*28
40RUS*28
13/
8
13/
8
40RUA*30
40RUS*30
13/
13/
13/
13/
8
8
8
8
25
Page 26
Table 8C — Fan Motor Data, Standard Motor — SI
UNIT
208/230-3-60 and 460-3-60
Speed (r/s)29.0829.0829.08
Shaft kW3.735.607.46
Frame (NEMA)S184TS213TS215T
Shaft Dia (mm)28.634.934.9
575-3-60
Speed (r/s)29.0829.2529.25
Shaft kW3.735.607.46
Frame (NEMA)184TS213TS215T
Shaft Dia (mm)28.634.934.9
LEGEND
NEMA — National Electrical Manufacturers Association
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
Table 8D — Fan Motor Data, Alternate Motor — SI
UNIT
208/230-3-60 and 460-3-60
Speed (r/s)29.0829.1729.17
Shaft kW5.607.467.46
Frame (NEMA)S213TS215TS215T
Shaft Dia (mm)34.934.934.9
575-3-60
Speed (r/s)29.2529.1729.17
Shaft kW5.607.467.46
Frame (NEMA)S213TD215TD215T
Shaft Dia (mm)34.934.934.9
LEGEND
NEMA — National Electrical Manufacturers Association
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
26
Page 27
Table 9A — Standard Drive Data, 60 Hz — English
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)3.7-4.74.3-5.34.3-5.3
Pulley Factory Setting
Full Turns Open
3.03.03.0
FAN DRIVE
Pulley Pitch Dia (in.)9.411.011.0
Pulley Bore (in.)1
Belt No. — Section2—B2—B
Belt Pitch (in.)41.8
7
/
16
115/
16
(2) 42.8
(2) 43.8
115/
†
2—B
(2) 42.8
(2) 43.8
FAN SPEEDS (rpm)
Factory Setting771752752
Range679-863682-841674-831
Max Allowable Speed (rpm)120011001100
Change per
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
1
/2 Turn of
15.313.113.1
666
9.12-
10.99
6.67-
9.43
16
†
6.67-
9.43
Table 9B — Medium-Static Drive Data, 60 Hz — English
UNIT
40RUA*25
40RUS*25
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)4.3-5.34.3-5.34.3-5.3
Pulley Factory Setting
Full Turns Open
3.03.03.0
FAN DRIVE
Pulley Pitch Dia (in.)9.49.49.4
Pulley Bore (in.)1
7
/
16
Belt No. — Section1—B2—B
Belt Pitch (in.)41.8
FAN SPEEDS (rpm)
Factory Setting881881881
Range798-984798-984798-984
Max Allowable Speed (rpm)120011001100
Change per
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
1
/2 Turn of
15.315.315.3
666
9.16-
10.99
40RUA*28
40RUS*28
115/
16
†
(2) 38.8
(2) 39.8
6.67-
9.43
40RUA*30
40RUS*30
115/
2—B
(2) 38.8
(2) 39.8
6.67-
9.43
16
†
27
Page 28
Table 9C — High-Static Drive Data, 60 Hz — English
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)4.3-5.34.3-5.34.3-5.3
Pulley Factory Setting
Full Turns Open
3.03.03.0
FAN DRIVE
Pulley Pitch Dia (in.)7.48.68.6
Pulley Bore (in.)1
7
/
16
115/
16
115/
Belt No. — Section2—B2—B2—B
Belt Pitch (in.)36.837837.8
FAN SPEEDS (rpm)
Factory Setting111810241024
Range
10141200
†
873-
1075
873-
1075
Max Allowable Speed (rpm)120011001100
Change per
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
†
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.
1
/2 Turn of
19.416.716.7
666
8.16-
10.02
6.67-
9.43
6.67-
9.43
16
Table 9D — Standard Drive Data, 60 Hz — SI
UNIT
40RUA*25
40RUS*25
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
94.0-
119.4
3.03.03.0
FAN DRIVE
Pulley Pitch Dia (mm)239279279
Pulley Bore (mm)36.549.249.2
Belt No. — Section2—B2—B
Belt Pitch (mm)1062
FAN SPEEDS (r/s)
Factory Setting12.912.512.5
Range11.3-14.411.4-14.011.2-13.9
Max Allowable Speed (r/s)20.018.318.3
Change per
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
1
/2Turn of
0.2550.2180.218
666
SHAFTS CENTER DISTANCE (mm)232-279169-240169-240
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
40RUA*28
40RUS*28
109.2-
134.6
†
(2) 1987
(2) 1113
40RUA*30
40RUS*30
109.2-
134.6
†
2—B
(2) 1987
(2) 1113
28
Page 29
Table 9E — Medium-Static Drive Data, 60 Hz — SI
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS830
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
109.2-
134.6
3.03.03.0
109.2-
134.6
109.2-
134.6
FAN DRIVE
Pulley Pitch Dia (mm)239239239
Pulley Bore (mm)36.549.249.2
(2) 986
(2) 1011
†
2—B
(2) 986
(2) 1011
Belt No. — Section1—B2—B
Belt Pitch (mm)1062
FAN SPEEDS (r/s)
Factory Setting14.714.714.7
Range13.3-16.413.3-16.413.3-16.4
Max Allowable Speed (r/s)20.018.318.3
Change per
Moveable Motor Pulley
1
/2 Turn of
0.2550.2550.255
Flange
MAX FULL TURNS FROM
CLOSED POSITION
666
SHAFTS CENTER DISTANCE (mm)232-279169-240169-240
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully se tting.
†
Table 9F — High-Static Drive Data, 60 Hz — SI
UNIT
40RUA*25
40RUS*25
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
109.2-
134.6
3.03.03.0
FAN DRIVE
Pulley Pitch Dia (mm)188203
Pulley Bore (mm)36.549.249.2
Belt No. — Section2—B2—B2—B
Belt Pitch (mm)935935960
FAN SPEEDS (r/s)
Factory Setting18.617.117.1
Range
16.9-
20.0
†
Max Allowable Speed (r/s)20.018.318.3
Change per
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
1
/2 Turn of
0.3230.2780.278
666
SHAFTS CENTER DISTANCE (mm)207-255169-240169-240
†
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.
Table 10D — 40RU High-Capacity Fan Performance Data —
0-600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
350400450500550600
r/skWr/skWr/skWr/skWr/skWr/skW
See Legend and Notes on page 34.
33
Page 34
Legend and Notes for Tables 10A and 10C
LEGEND
Bhp— Brake Horsepower Input to Fan
ESP— External Static Pressure
NOTES:
1. Maximum allowable fan speed for size 25 units is 1200 rpm .
Maximum allowable fan speed for size 28 and 30 units is 1100
rpm.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. Refer to fan motor and drive tables for additional data.
Legend and Notes for Tables 10B and 10D
LEGEND
ESP — External Static Pressure
NOTES:
1. Maximum allowable fan speed for size 25 units is 20 r/s.
Maximum allowable fan speed for size 28 and 30 units is 18.3 r/s.
2. Fan performance is based on deductions for wet coil, clean
51-mm filters, and unit casing. See table at right for factory-supplied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
AIRFLOW
(Cfm)
6,0000.12
8,0000.19
10,0000.26
7,5000.15
10,0000.22
12,5000.30
9,0000.19
12,0000.29
15,0000.40
PRESSURE DROP
(in. wg)
FACTORY-SUPPLIED PRESSURE DROP — SI
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
AIRFLOW
(L/s)
290032
380047
470064
350036
470055
590076
425047
565071
705098
PRESSURE DROP
(Pa)
Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231Printed in MexicoEdition Date: 09/09Catalog No: 40RU-03SIManufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.Replaces: New
34
Page 35
I. PRELIMINARY INFORMATION
START-UP CHECKLIST
(SPLIT SYSTEMS WITH 40RU UNITS)
OUTDOOR: MODEL NO. _________________________
SERIAL NO. ___________________________________
ADDITIONAL ACCESSORIES ______________________________________________________________________________
INDOOR: MODEL NO. ___________________________
SERIAL NO. ___________________________________
II. PRE-START-UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? _______________(Y/N) ____
IF SO, WHERE: _________________________________________________________________________________________
_______________________________________________________________________________________________________
WILL THIS DAMAGE PREVENT UNIT ST ART-UP? (Y/N) _____
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) _____
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) _____
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) _______
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) _______
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N) _____
CONTROLS
ARE THERMOST AT(S) AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N) _____
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) _____
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N) ______
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN P AN T O CONFIRM PROPER DRAINAGE? (Y/N) _____
ARE PROPER AIR FIL TERS IN PLACE? (Y/N) _____
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) ______
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N) _____
PIPING
40RUA
HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? (Y/N) ______
ARE LIQUID LINE SOLENOID VALVES LOCA TED AT THE INDOOR UNIT COILS AS REQUIRED?(Y/N) _____
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion V alves) SOLE NOID VAL VES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR?(Y/N) _____
LOCATE, REPAIR, AND REPORT ANY LEAKS._______________________________________________________________
HAVE ALL COMPRESSOR SER VICE VAL VES BEEN FULLY OPENED (BACKSEA TED)(Y/N) ____
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N) _____
40RUS
HAS AIR BEEN BLED FROM SYSTEM?(Y/N) ___________________________________________
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, AND INDOOR COILS? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS._______________________________________________________________
CL-1
Page 36
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOL TS:AB ________ V AC ______ V BC ______ V
(AB + AC + BC)/3 = A VERAGE VOLT AGE = _______ V
MAXIMUM DEVIA TION FROM AVERAGE VOLTAGE = _______ V
VOL TAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = __________ %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START-UP
CHECK INDOOR FAN MOT OR SPEED AND RE CORD.
AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP
Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231Printed in MexicoEdition Date: 09/09Catalog No: 40RU-03SIManufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.Pg CL-2Replaces: New