Carrier T R-410A User Manual

Page 1
40RU
Packaged Air-Handling Units 60 Hz
®
with Puron
(R-410A) Refrigerant
Sizes 25, 28, 30
Installation, Start-Up and
Service Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 1
PRE-INST ALLA TION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Moving and Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rigging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–20
Uncrating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit Isolation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Refrigerant and Chilled Water Piping Access . . . . . . 11
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . . . . . 16
Power Supply and Wiring . . . . . . . . . . . . . . . . . . . . . . . 17
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SERVICE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21–34
Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fan Motor Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fan Shaft Position Adjustment. . . . . . . . . . . . . . . . . . . 22
Individual Fan Wheel Adjustment . . . . . . . . . . . . . . . . 22
Fan Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Pulley and Drive Adjustment . . . . . . . . . . . . . . . . . . . . 23
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Chilled Water Coil Freeze Protection . . . . . . . . . . . . 23
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Cleaning Cooling Coil. . . . . . . . . . . . . . . . . . . . . . . . . . 23
Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Replacing Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . CL-1, CL-2
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions package
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Page 2
ELECTRICAL SHOCK HAZARD
LEGEND
TXV — Thermostatic Expansion Valve
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
UNIT OPERA TION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puron® (R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing 40RU units.
4. This installation must conform with local building codes and with the NEC (National Electrical Code) or ANSI (American National Standards Institute)/NFPA (National Fire Protection Association) latest revision. Refer to provincial and local plumbing or wastewater codes and other applicable local codes.
Moving and Storage — To transfer unit from truck to
storage site, use a fork truck. Do not stack units more than 2 high during storage. If unit is to be stored for more than 2 weeks before installation, choose a level, dry storage site free from vibration. Do not remove plastic wrap or skid from unit until final installation.
Rigging — All 40RU Series units can be rigged by using
the shipping skid. Units are shipped fully assembled. Do not remove shipping skids or protective covering until unit is ready for final placement; damage to bottom panels can result. Use slings and spreader bars as applicable to lift unit.
INSTALLATION
General — Allow 2
clearance and airflow. For units equipped with an economizer, refer to the accessory installation instructions for additional clearance requirements. Be sure floor, wall, or ceiling can support unit weight (T ables 1A – 1D). See Fig. 2A and Fig. 2B for dimensions.
Uncrating — Move unit as near as possible to final loca-
tion before removing shipping skid. Remove metal banding, top skid, and plastic wrap. Examine
unit for shipping damage. If shipping damage is evident, file claim with transportation agency. Remove base skid just prior to actual installation.
Check nameplate information against available power supply and model number description in Fig. 3.
NOTE: Be sure to remove the styrofoam shipping pad from the thermostatic expansion valve (TXV). Verify that it has been removed. See Fig. 1.
1
/2 ft at front and side of unit for service
UNIT OPERA TION HAZARD
Failure to follow this caution could cause equipment damage.
Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.
PRE-INSTALLATION
1. The power supply (v, ph, and Hz) must correspond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be suf­ficient to handle load imposed by this unit.
3. Refer to Installation, General section (page 2) and Fig. 2A and Fig. 2B for locations of electrical inlets, con­densate drain, duct connections, and required clearances before setting unit in place.
Fig. 1 — Foam Block Location
Accessories — Refer to instructions shipped with each
accessory for specific information.
2
Page 3
LEGEND
TXV — Thermostatic Expansion Valve NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory-supplied and field-
installed.
UNIT
UNIT WEIGHT
lb (kg)
40RUA*25 730 (331) 40RUS*25 683 (310)
Fig. 2A — Dimensions – Size 25
3
Page 4
UNIT
UNIT WEIGHT
lb (kg)
40RUA*28 1050 (477) 40RUA*30 1062 (482) 40RUS*28 1035 (469) 40RUS*30 1042 (473)
LEGEND
TXV — Thermostatic Expansion Valve NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory-supplied and field-
installed.
6. 40RUS may require alternate or additional
field favricated poping access holes
Fig. 2B — Dimensions – Sizes 28 and 30
4
Page 5
Table 1A — 40RUA Physical Data, English — Cooling Units
UNIT 40RUA* 25 28 30 NOMINAL CAPACITY (Tons) 20 25 30 OPERATING WEIGHT (lb)
Base Unit with TXV 730 1050 1062 Plenum 225 325 325
FANS
Qty...Diam. (in.) 2...15 2...18 2...18 Nominal Airflow (cfm) 8,000 10,000 12,000 Airflow Range (cfm) 6,000 – 10,000 7,500 – 12,500 9,000 – 15,000 Nominal Motor Hp (Standard Motor)
208/230-3-60 and 460-3-60 5.0 7.5 10.0 575-3-60 5.0 7.5 10.0
Motor Speed (rpm)
208/230-3-60 and 460-3-60 1745 1745 1745 575-3-60 1745 1755 1755
REFRIGERANT R-410A
Operating charge (lb) (approx per circuit)
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 450 Face Area (sq ft) 19.88 24.86 29.83 No. of Splits 222 No. of Circuits per Split 18 20 24 Split Type...Percentage Face...50/50 Fins/in. 17 15 15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...1 DX Coil — Liquid Refrigerant (ODF) 2...5/ Steam Coil, In (MPT) 1...21/ Steam Coil, Out (MPT) 1...1/ Hot Water Coil, In (MPT) 1...2 Hot Water Coil, Out (MPT) 1...2 Condensate (PVC) 1...1
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) Access Location Either Side
STEAM COIL
Max Working Pressure (psig at 260°F) Total Face Area (sq ft) 13.33 15.0 15.0 Rows...Fins/in. 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150 Total Face Area (sq ft) 13.33 15.0 15.0 Rows...Fins/in. 2...8.5 2...12.5 2...12.5 Water Volume
(gal)
3
) 1.85 1.90
(ft
LEGEND
DX Direct Expansion TXV Thermostatic Expansion Valve
Units are shipped without refrigerant charge.
Field installed accessory only.
3.5 4.5 5.0
1
/
8
4...16 x 20 x 2
4...16 x 24 x 2
2...13/
8
8
2
2
1
/4 ODM/1 IDF
4...20 x 24 x 2
4...20 x 25 x 2
20
13.9
14.3
2...13/
8
5
Page 6
Table 1B — 40RUA Physical Data, SI — Cooling Units
UNIT 40RUA* 252830 NOMINAL CAPACITY (kW) 70 87 105 OPERATING WEIGHT (kg)
Base Unit with TXV 331 477 482 Plenum 102 148 148
FANS
Qty...Diam. (mm) 2...381 2...457 2...457 Nominal Airflow (L/s) 3775 4119 5663 Airflow Range (L/s) 2831 – 4719 3539 – 5899 4247 – 7079 Nominal Motor kW (Standard Motor)
208/230-3-60 and 460-3-60 3.73 5.60 7.46 575-3-60 3.73 5.60 7.46
Motor Speed (r/s)
208/230-3-60 and 460-3-60 29.1 29.1 29.1 575-3-60 29.1 29.3 29.3
REFRIGERANT R-410A
Operating charge (kg) (approx per circuit)
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag) 3102 Face Area (sq m) 1.85 2.30 2.77 No. of Splits 222 No. of Circuits per Split 18 20 24 Split Type...Percentage Face...50/50 Fins/m 670 591 591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...1 DX Coil — Liquid Refrigerant (ODF) 2...5/ Steam Coil, In (MPT) 1...21/ Steam Coil, Out (MPT) 1...1/ Hot Water Coil, In (MPT) 1...2 Hot Water Coil, Out (MPT) 1...2 Condensate (PVC) 1...1
FILTERS Throwaway — Factory Supplied
Quantity...Size (mm.) Access Location Either Side
STEAM COIL
Max Working Pressure (kPag at 126°C) 138 Total Face Area (sq m) 1.24 1.39 1.39 Rows...Fins/m 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034 Total Face Area (sq m) 1.24 1.39 1.39 Rows...Fins/m 2...335 2...335 2...335 Water Volume
(L) 52.6 54.1
3
) 0.052 0.054
(m
LEGEND
DX Direct Expansion TXV Thermostatic Expansion Valve
Units are shipped without refrigerant charge.
Field installed accessory only.
1.59 2.04 2.27
1
/
8
4...406 x 508 x 51
4...406 x 610 x 51
2...13/
8
8
2
2
1
/4 ODM/1 IDF
4...508 x 610 x 51
4...508 x 635 x 51
2...13/
8
6
Page 7
Table 1C — 40RUS Physical Data, English — Chilled Water Units
UNIT 40RUS* 252830 NOMINAL CAPACITY (Tons) 20 25 30 OPERATING WEIGHT (lb)
Base Unit 683 1035 1042 Plenum 225 325 325
FANS
Qty...Diam. (in.) 2...15 2...18 2...18 Nominal Airflow (cfm) 8,000 10,000 12,000 Airflow Range (cfm) 6,000 – 10,000 7,500 – 12,500 9,000 – 15,000 Nominal Motor Hp (Standard Motor)
208/230-3-60 and 460-3-60 5.0 7.5 10.0 575-3-60 5.0 7.5 10.0
Motor Speed (rpm)
208/230-3-60 and 460-3-60 1745 1745 1745 575-3-60 1745 1755 1755
CHILLED WATER COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435 Face Area (sq ft) – Upper 11.0 12.4 15.5 Face Area (sq ft) – Lower 8.3 12.4 12.4 Rows...Fins/in. 3...15
PIPING CONNECTIONS,
Quantity...Size (in.)
3
Chilled Water — In 2...1 Chilled Water — Out 2...1 Steam Coil, In (MPT) 1...2 Steam Coil, Out (MPT) 1...11/ Hot Water Coil, In (MPT) 1...2 Hot Water Coil, Out (MPT) 1...2 Condensate (PVC) 1...1
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) Access Location Either Side
STEAM COIL
Max Working Pressure (psig at 260°F) 20 Total Face Area (sq ft) 13.33 15.0 15.0 Rows...Fins/in. 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150 Total Face Area (sq ft) 13.33 15.0 15.0 Rows...Fins/in. 2...8.5 2...12.5 2...12.5 Water Volume
(gal) 13.9 14.3
3
) 1.1 1.90
(ft
LEGEND
Field installed accessory only.
/8 ODM 2...21/8 ODM 2...21/8 ODM
3
/8 ODM 2...21/8 ODM 2...21/8 ODM
1
/
2 2
1
/4 ODM/1 IDF
4...16 x 20 x 2
4...16 x 24 x 2
4...20 x 24 x 2
4...20 x 25 x 2
7
Page 8
Table 1D — 40RUS Physical Data, SI — Chilled Water Units
UNIT 40RUS* 252830 NOMINAL CAPACITY (kW) 70 87 105 OPERATING WEIGHT (kg)
Base Unit 310 469 473 Plenum 102 148 148
FANS
Qty...Diam. (mm) 2...381 2...457 2...457 Nominal Airflow (L/s) 3775 4719 5663 Airflow Range (L/s) 2831 – 4719 3539 – 5899 4247 – 7079 Nominal Motor kW (Standard Motor)
208/230-3-60 and 460-3-60 3.73 5.60 7.46 575-3-60 3.73 5.60 7.46
Motor Speed (r/s)
208/230-3-60 and 460-3-60 29.1 29.1 29.1 575-3-60 29.1 29.3 29.3
CHILLED WATER COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag) 2999 Face Area (sq m) – Upper 1.02 1.15 1.44 Face Area (sq m) – Lower 0.77 1.15 1.15 Rows...Fins/m 3...591 3...591 3...591
PIPING CONNECTIONS,
Quantity...Size (in.)
3
Chilled Water — In 2...1 Chilled Water — Out 2...1 Steam Coil, In (MPT) 1...2 Steam Coil, Out (MPT) 1...11/ Hot Water Coil, In (MPT) 1...2 Hot Water Coil, Out (MPT) 1...2 Condensate (PVC) 1...1
FILTERS Throwaway — Factory Supplied
Quantity...Size (mm.) Access Location Either Side
STEAM COIL
Max Working Pressure (kPag at 125°C) 138 Total Face Area (sq m) 1.24 1.39 1.39 Rows...Fins/m 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034 Total Face Area (sq m) 1.24 1.39 1.39 Rows...Fins/m 2...335 2..493 2...493 Water Volume
(L) 52.6 54.1
3
) 0.052 0.054
(m
LEGEND
Field installed accessory only.
/8 ODM 2...21/8 ODM 2...21/8 ODM
3
/8 ODM 2...21/8 ODM 2...21/8 ODM
1
/
2 2
1
/4 ODM/1 IDF
4...406 x 508 x 51
4...406 x 610 x 51
4...508 x 610 x 51
4...508 x 635 x 51
8
Page 9
Fig. 3 — Model Number Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
4 0 R U A A 2 5 A 1 A 6 – 0 A 0 A 0
_____________ ____
Model Type Brand / Packaging
40RU = Carrier Fan Coil Puronr R---410A Refrigerant
0=Standard
Typ e of C oil
Not Used
A=StandardDXCoil
A=PlaceHolder
S = Chilled Water Coil
Refrigerant Options
Service Options
C = Hot Water Coil
A=None B = Steam Coil
0 = Non-Painted Cabinet 1=PaintedCabinet
Nominal Tonnage
25 = 20 Tons 28 = 25 Tons
Not Used
30 = 30 Tons
A=PlaceHolder
Not Used
0=PlaceHolder
Not Used
A=PlaceHolder
Design Rev
--- = Catalog Model Number
Indoor Fan Options
1 = Fan Drive and Motor - Low / Motor Efficiency - Standard
Voltage
2 = Fan Drive and Motor - Med / Motor Efficiency - Standard
1 = 575/3/60
3 = Fan Drive and Motor - High / Motor Efficiency - Standard
4 = Fan Drive and Motor - Low / Motor Efficiency - Premium
5 = Fan Drive and Motor - Med / Motor Efficiency - Premium
5 = 208/ 230/3/60 6 = 460/3/60
6 = Fan Drive and Motor - High / Motor Efficiency - Premium
Coil Options
A=Al/Cu
SETANGISEDNOITISOP
)radnelac lacsif( erutcafunam fo keeW1−2
)ASU ,saxeT ,PTE = G( noitacol gnirutcafunaM5
rebmun laitneuqeS6−10
12345678910 4808G12345
POSITION NUMBER TYPICAL
Year of manufacture (”08” = 2008)3−4
LEGEND
Accessory Line Alternate Air Intake and Discharge
Air Intake and Discharge
Note:
Maintain recommended clearances per Figs. 2A–2B
Unit Positioning — The unit can be mounted on the
floor for vertical application with return air entering the face of the unit and supply air discharging vertically through the top of the unit. The unit can also be applied in a horizontal arrangement with return air entering horizontally and the supply air discharging horizontally. When applying the unit in a horizontal arrangement, ensure the condensate drain pan is located at the bottom center of the unit for adequate condensate disposal. See Fig. 5 for condensate connections for each unit position.
T ypical positioning and alternate return air locations are shown in Fig. 5. Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air location. Refer to overhead suspension accessory drawing (Fig. 6) for preferred suspension technique. The unit needs support underneath to prevent sagging.
IMPORTANT: Do NOT attempt to install unit with return air entering top panel of unit. Condensate will not drain from unit.
Fig. 4 — Serial Number Nomenclature
9
Fig. 5 — Typical Unit Positioning
Page 10
OVERHEAD SUSPENSION ACCESSORY
UNIT SIZE 25
UNIT SIZES 28, 30
NOTE: Dimensions in [ ] are millimeters
Fig. 6 — Preferred Suspension Technique
10
Page 11
Unit Isolation — Where extremely quiet operation is
UNIT
USE HOLE NUMBERS
FIELD-FABRICATED HOLE DIAMETERS
in. (mm)
FIELD-FABRICATED HOLE POSITION
DIMENSIONS, in. (mm)
No. 5No. 6No. 7No.8ABCD
40RUA*25, 28, 30 1, 2, 3, 4————————
40RUS*25 4, 5, 6, 7 1
3
/4 (44.5) 13/4 (44.5) 13/4 (44.5) 3.0 (76.2) 6.0 (152.5) 10.5 (266.7)
40RUS*28, 30 5, 6, 7, 8 2
1
/2 (63.5) 21/2 (63.5) 21/2 (63.5) 21/2 (63.5) 6.0 (152.5) 9.625 244.5) 13.38 (339.9) 17.0 (431.8)
essential, install isolators between floor and base of unit, or between ceiling and top section of unit.
Be sure that unit is level and adequately supported. Use channels at front and sides of unit for reference points when leveling.
Refrigerant and Chilled Water Piping Access —
knockouts for refrigerant and chilled water piping. These knockouts are located on both sides of the unit for installation flexibility. The standard knockouts provide sufficient access to the unit’s coils for all 40RUA*25, 28, and 30 units. RUS*25, 28, and 30 units require additional holes which must be field­fabracated to accomodiate the piping. See Fig. 7 for the positions and dimensions of the additional access holes required for the RUS units. Recommended access hole use is also listed for all units. Note that Fig. 7 shows the access holes on the control-box side of the unit; this is the side of the unit with the coil headers, so it is used most often for piping access.
IMPORTANT : Do not bury refrigerant piping underground.
The 40RU Series units come with standard
Refrigerant Piping — See Tables 1A–1D for refrigerant
pipe connection sizes. For ease in brazing, it is recommended that all internal solder joints be made before unit is placed in final position.
The 40RU direct-expansion units have internal factory-installed thermostatic expansion valves (TXVs), distributors, and nozzles for use with R-410A. See Table 2 for part numbers. Knockouts are provided in the unit corner posts for 40RU refrigerant piping. See Fig. 7, which also lists recommended knockouts and access holes to use for each 40RU unit size. Recommended fittings are listed in Table 3.
The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit. See Fig. 8.
NOTE: Be sure to remove the styrofoam shipping pad from the TXV. Verify that it has been removed. See Fig. 1.
IMPORTANT: Never attach the sensor to the suction manifold. Do NOT mount the sensor on a trapped portion of the suction line.
The 40RU Series evaporator coils have a face-split design. Ensure that lower circuit of coil is first on/last off when connected to the condensing unit and/or system controls. See Fig. 9.
External TXV equalizer connections are provided and factory-brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately the 4 o’clock or 8 o’clock position. See Fig.10.
8 7 6 5
4
3 2
1
Fig. 7 — Refrigerant and Chilled Water Piping Access Holes
11
B
A
D
C
Page 12
LEGEND:
TXV – Thermostatic Expansion Valve
NOTE: Component location arrangemet shown for field installatio n of
sight glasses, solenoid valves, filter driers, and TXV sensin g bulbs. The TXVs and equilizer lines are factory installed.
UPPER
– Not required when mated to units 38AP_025 - 060
*
FIRST ON/LAST OFF = B
VERT ICAL INSTALL ATION
FIRST ON/LAST OFF = A
HORIZONT AL INS TAL LATION
LEGEND TXV — Thermostatic Expansion Valve NOTE: The 8 o’clock position is sho w n above.
SPLIT
AIRFLOW
LOWER SPLIT
TXV SENSING BULB
15 DIAMS
MIN
TXV SENSING BULB
10
DIAMS
8 DIAMS
MIN
EQUALIZER LINE
TXV
EQUALIZER
LINE
FILTER
DRIER
SOLENOID*
VALV E
SIGHT
GLASS
8 DIAMS
MIN
TXV
INDOOR COIL
AIRFLOW
15 DIAMS
MIN
10
DIAMS
Fig. 8 — Face-Split Coil Suction and Liquid Line Piping (Typical)
Fig. 9 — Typical Evaporator Coil Connections (40RU)
Fig. 10 — TXV Sensing Bulb Location
12
Page 13
Table 2 — Factory-Installed Nozzle and Distributor Data
UNIT
COIL TYPE
STD
40RU*25 4 Row 2...BBIZE-8-GA 40RU*28 4 Row 2...BBIZE-15-GA 40RU*30 4 Row 2...BBIZE-15-GA
Feeder tube size is 1/4 in. (6.35 mm).
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.
TXV
Qty...Part No.
DISTRIBUTOR
Qty...Part No.
2...1135
2...1126
2...1126
Table 3 — Fitting Requirements
UNIT
40RUA25
40RUS25
ACCESS
HOLE NO.
1 Suction Lower
2 Liquid Lower
3 Liquid Upper
4 Suction Upper
4 Supply Lower
5 Return Lower
6 Return Upper
7 Supply Upper
CONNECTION
TYPE
FEEDER TUBES
PER DISTRIBUTOR
CIRCUIT
Qty...S iz e (in.)
18...3/
16
3
20...
/
16
3
/
24...
16
1
1
/8 Street Elbow
1
/8 Nipple, 75/8 L
1
1
/8 Long Radius Elbow
1
5
/8 Street Elbow
5
/8 Nipple, 61/2 L
5
/8 Long Radius Elbow
5
/8 Street Elbow
5
/8 Nipple, 91/2 L
5
/8 Long Radius Elbow
1
/8 Nipple, 55/8 L
1
1
/8 Long Radius Elbow
1
1
/8 Nipple, 11 L
1
1
/8 Long Radius Elbow
1
3
1
/8 Long Radius Elbow
3
/8 Nipple, 33/4 L
1
3
/8 Long Radius Elbow
1
3
/8 Long Radius Elbow
1
3
/8 Nipple, 33/8 L
1
3
/8 Long Radius Elbow
1
3
/8 Long Radius Elbow
1
3
/8 Nipple, 7 L
1
3
1
/8 Long Radius Elbow
3
/8 Long Radius Elbow
1
3
/8 Nipple, 113/4 L
1
3
1
/8 Long Radius Elbow
NOZZLE
Qty...Part No.
2...G6
2...C15
2...C17
FITTINGS REQUIRED
(in.)
13
Page 14
Table 3 — Fitting Requirement (cont)
UNIT
ACCESS
HOLE NO.
1 Suction Lower
2 Liquid Lower
40RUA28
3 Liquid Upper
4 Suction Upper
5 Supply Lower
6 Return Lower
40RUS*28, 30
7 Return Upper
8 Supply Upper
1 Suction Lower
2 Liquid Lower
40RUA*30
3 Liquid Upper
4 Suction Upper
See Fig. 7 for access hole location by number.
† Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
CONNECTION
TYPE
CIRCUIT
FITTINGS REQUIRED
3
1
/8 Street Elbow
3
/8 Nipple, 11 L
1
3
/8 Long Radius Elbow
1
5
/8 Street Elbow
5
/8 Nipple, 11/2 L
5
/8 Long Radius Elbow
5
/8 Street Elbow
5
/8 Nipple, 191/2 L
5
/8 Long Radius Elbow
3
/8 Nipple, 43/16 L
1
3
/8 Long Radius Elbow
1
3
/8 Nipple, 231/4 L
1
3
/8 Long Radius Elbow
1
1
2
/8 Long Radius Elbow
1
/8 Nipple, 31/2 L
2
1
/8 Long Radius Elbow
2
1
/8 Long Radius Elbow
2
1
/8 Nipple, 3 L
2
1
/8 Long Radius Elbow
2
1
/8 Long Radius Elbow
2
1
/8 Nipple, 67/8 L
2
1
/8 Long Radius Elbow
2
1
/8 Long Radius Elbow
2
1
/8 Nipple, 117/8 L
2
1
/8 Long Radius Elbow
2
3
1
/8 Street Elbow
3
/8 Nipple, 3 L
1
3
/8 Long Radius Elbow
1
5
/8 Street Elbow
5
/8 Nipple, 73/4 L
5
/8 Long Radius Elbow
5
/8 Street Elbow
5
/8 Nipple, 181/2 L
5
/8 Long Radius Elbow
3
/8 Nipple, 43/16 L
1
3
1
/8 Long Radius Elbow
3
/8 Nipple, 191/4 L
1
3
/8 Long Radius Elbow
1
(in.)
14
Page 15
Chillled Water Piping — See Tables 1C and 1D for
chilled water connecton sizes. For ease in bazing, it it recom­mended that all internal solder joints be made before unit is placed in final position.
Knockouts are provided in the unit corner posts for 40RUS re­frigerant piping. Additional field-fabricated access holes are re­quired for 40RUS chilled water piping. See Fig. 7, which lists recommended knockouts and access holes to use for each 40RUS unit size.
To size, design, and install chilled water piping, consult the Carrier System Design manual. See Fig. 11 for an example of a typical installation. Recommended fittings are listed in T able 3.
To access 40RUS coil vents and drains, remove the unit side panel over the coil header. Vent and drain plugs are on the top and bottom of header, respectively. See the Service section for information on preventing coil freeze-up during winter.
Fig. 11 — Typical 40RUS Chilled Water Piping
15
Page 16
Condensate Drain — Install a trapped condensate drain
3” MIN.
[76]
NOTE: Dimensions in [ ] are in millimeters
line to unit connection as shown in Fig. 12. The unit drain con­nection is a PVC stub. See Fig. 13. Some areas may require an adapter to connect to either galvanized steel or copper pipe. For these applications, install a field-supplied threaded PVC adapter.
Fig. 12 — Condensate Drains
NOTE: A trap must be installed in the condensate drain line to ensure that the static pressure of fans is balanced with the water column in the drain line and that condensate can drain completely from pan. Without a trap, air can be drawn up drain line until water level in condensate pan becomes equal to static pressure created by fans, preventing complete drainage. Conditions will worsen as filters become dirty .
Install clean-out plugs in trap. Pitch drain line downward to an open floor drain or sump. Provide service clearance around drain line to permit removal of unit panels. Observe all local sanitary codes.
Fig. 13 — Drain Pan Slope Adjustment
As shipped, the unit’s condensate drain pan is NOT sloped to­wards the drain connection. The pan slope must be changed to pitch towards the side of the unit with the drain connection. See Fig. 13. Loosen the 2 screws next to the drain outlet at both ends of the unit, push drain pan down in the slots near the drain connection, and up in the slots on the opposite end. Retighten screws. The pan should have a pitch of at least
1
/4-in. over its
length toward the drain connection.
Fan Motors and Drives — Motor and drive packages
are factory installed in all units. The motor and drive packages consist of the following items:
1 — fan motor 1 — adjustable motor pulley 1 — fan pulley 2 — matched fan belts (40RUA*25-30, 40RUS*25-30 units) For instructions on changing fan rotation, changing drive
speeds and adjusting drives, see Pulley and Drive Adjustment in the Service section.
16
Page 17
Power Supply and Wiring — Check the unit data
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
A
LEGEND
TXV —
Th ermostatic Expans ion Valve
23
22
21
1
3
1
2
1
1
1
0
5
°
C
6
00
VR
J
A
W
FAN CONTACTOR
24V TERMINAL BLOCK
POWER WIRING KNOCKOUT
plate to ensure that available power supply matches electrical characteristics of the unit. Provide a disconnect switch with an integrated lock-out feature of size required to provide adequate fan motor starting current. See Tables 4-6 for unit electrical data.
FAN SCROLL
MOTOR
ND DRIVE
FAN CONTACTOR BOX
WIRE ACCESS
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/ NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch and condensing unit. Use only copper wire.
(See Fig. 14)
CONDENSATE DRAIN CONNECTION (HORIZONTAL)
FILTER ELEMENTS
FILTER RETAINER CLIP
FAN DRIVE PULLEY
COIL
TXV BULB ACCESS
REFRIGERANT PIPING ACCESS
CONDENSATE DRAIN CONNNECTION (VERTICAL)
Fig. 15 — Wiring and Service Access
(Side Panel Removed)
Fan motors are factory-installed on all units. Indoor-fan contactors are located in the fan contactor box behind the side access panel (see Fig. 15 and 16). Wire the thermostat to the 24-v control circuit terminal block located in the side of the fan contactor control box, according to Fig. 17 or the unit label diagram. If the air handler is part of a split system, complete the wiring from the condensing unit to the thermostat shown in Fig. 17.
Install disconnect switch and power wiring in accordance with all applicable local codes. See Fig. 15-17 and the unit label diagram. Connect power wiring with
Fig. 14 — Disconnect Switch and Unit
1
/4-in. ring terminal.
Fig. 16 — Fan Contactor Box and Terminal Block
(Cover Removed) (Typical)
17
Page 18
Table 4 — Electrical Data, Standard Motors
LEGEND
Motors are designed for satisfactory operation within 10% of nominal voltages shown. Voltages should not exceed the limits shown in the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in accor­dance with NEC (National Electrical Code), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters’ Laboratories) Standard 1995.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of
voltage imbalance.
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v BC = 403 v AC = 396 v
Determine maximum deviation from average voltage
(AB) 397 – 393 = 4 v (BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v
Maximum deviation is 6 v. Determine percent voltage imbalance.
This amount of phase imbalance is satisfactory because it is below the maxi­mum allowable 2%.
FLA Full Load Amps MOCP
Maximum Overcurrent Protection
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
393 + 403 + 396
3
=
119 2
3
=
397
% Voltage Imbalance = 100 x
6
397
=1.5%
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
UNIT V-PH-Hz
208/230-3-60 187-253 5.0 (3.73) 14.6/12.8 18.3/16.0 30/25
40RUA*25 40RUS*25
208/230-3-60 187-253 7.5 (5.59) 21.4/19.4 26.9/24.3 45/40
40RUA*28 40RUS*28
208/230-3-60 187-253 10.0 (7.46) 28.2/26.8 35.3/33.5 60/60
40RUA*30 40RUS*30
See Legend and Notes below.
UNIT V-PH-Hz
208/230-3-60 187-253 7.5 (5.59) 21.4/19.4 26.9/24.3 45/40
40RUA*25 40RUS*25
40RUA*28 40RUA*30 40RUS*28
208/230-3-60 187-253 10.0 (7.46) 28.2/26.8 35.3/33.5 60/60
40RUS*30
VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA
Minimum
Circuit Amps
MOCP
460-3-60 414-506 5.0 (3.73) 6.4 8.0 15 575-3-60 518-632 5.0 (3.73) 5.1 6.4 15
460-3-60 414-506 7.5 (5.59) 9.7 12.1 20 575-3-60 518-632 7.5 (5.59) 7.8 9.8 15
460-3-60 414-506 10.0 (7.46) 13.4 16.8 30 575-3-60 518-632 10.0 (7.46) 10.3 12.9 20
Table 5 — Electrical Data, Alternate Mot or s
VOLTAGE
LIMITS
460-3-60 414-506 7.5 (5.59) 9.7 12.1 20 575-3-60 518-632 7.5 (5.59) 7.8 9.8 15
460-3-60 414-506 10.0 (7.46) 13.4 16.8 30 575-3-60 518-632 10.0 (7.46) 10.3 12.9 20
FAN MOTOR POWER SUPPLY
Hp (kW) FLA
Minimum
Circuit Amps
MOCP
See Legend and Notes below.
Legend and Notes For Tables 4 and 5
18
Page 19
Fig. 17 — Unit Wiring
LEGEND
NOTE: Use copper conductors only.
EQUIP Equipment GND Ground HC Heating Contactor HTR Electric Heater IFC Indoor-Fan Contactor IFM Indoor-Fan Motor TB Te rmin a l B l ock T’STAT Thermostat
Factory Wiring Field Control Wiring
19
Page 20
Table 6 — Fan Contactor Coil Data
UNIT
40RU**
25, 28, 30 24 10
VOLTAGE
(vac)
MAXIMUM
HOLDING
VA
Connecting Ductwork — Refer to the Carrier System
Design Manual for the recommended design and layout of ductwork. Fig. 18 shows recommended duct connection to units with 2 fans.
UNIT OPERA TION HAZARD
Failure to follow this caution could cause equipment damage.
Do not operate unit without ductwork or discharge plenum unless fan speed has been adjusted for external static pressure of zero in. wg. Failure to do so may result in motor overload.
DISCHARGE CONNECTIONS — Duct flanges are factory-supplied; they are shipped inside the unit attached to the hairpin end of the coil tube sheet for field installation. Using the existing screws, install the duct flanges on the unit’s fan deck. Each fan discharge requires 2 flanges; each flange must be bent in the middle to conform to the discharge opening. See Fig. 19. After flanges are installed, connect them to the supply duct using a canvas connection to prevent vibration. It is important that this connection be properly fabricated to prevent high air friction losses and air noise.
RETURN CONNECTION — When usin g return-air ductwork, route return-air duct to the unit’s return air inlet near the filter rack, using a canvas connection to prevent transmission of unit vibration. If the duct blocks off the unit’s access panel, provide a slip joint in the ductwork to permit removal for servicing.
OUTDOOR-AIR INLET CONNECTION — Connect outdoor­air inlet to field-installed accessory economizer. Refer to Economizer Installation Instructions.
Return-Air Filters — Type and size of filters are shown
in Tables 1A – 1D and are factory-supplied and factory­installed. In all units with 2 fans, a filter replacement tool (hook) is shipped inside the unit for field use when replacing filters. See the Service section for instructions on filter element replacement.
Fig. 18 — Typical Fan Discharge Connections for Multiple Fan Units
20
Page 21
Fig. 19 — Duct Flange Installation
START-UP
Before starting unit, check the following and correct as necessary:
• Is unit solidly supported?
• Is fan adjusted for speed and pulley alignment?
• Are pulleys, motor, and bearings securely mounted?
• Are there any loose parts that will rattle or vibrate?
• Is condensate drain pan pitched for correct drainage?
• Are coil baffle plates tight against coil to prevent air bypass?
• Are all panels securely fastened?
• Are all electrical connections correct and tight?
Also refer to condensing unit instructions before starting a split system. A split system start-up checklist is provided at the end of these instructions.
SERVICE
Inspection and maintenance should be performed at regular in­tervals and should include the following:
• Complete cleaning of cabinet, fan wheel, cooling coil, condensate pan and drain, heating coils, and return-air grille (if present).
• Inspection of panels and sealing of unit against air leakage.
• Adjustment of fan motor, belt, bearings, and wheels.
• Cleaning or replacement of filters.
• Testing for cooling/heating system leaks.
• Checking of all electrical connections.
Most unit service can be performed by removing one or both of the unit’s side panels. Coil cleaning or removal or insulation cleaning may require removal of a rear, top, or bottom panel, depending on the unit’s orientation. When service is completed, replace unit panels.
Panels — Panels are fastened to unit frame with sheet metal
screws. Fan and coil compartment must be sealed tightly after service to prevent air from bypassing the cooling coil.
Fan Motor Lubrication — Fan motor supplied with
unit is permanently lubricated and requires no further lubrication.
Fan Shaft Bearings — Size 25-30 units have pillow-
block bearings (Fig. 20) that must be lubricated with suitable bearing grease approximately every 3 months. See Table 7 for suitable lubricants.
Table 7 — Lubricant Data
MANUFACTURER LUBRICANT
Mobil Mobilplex EP No. 2 Sunoco Prestige 42 Texaco Multifak 2 Texaco Regal AFB-2*
*Preferred lubricant, contains rust and oxidation inhibitors.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
Fig. 20 — Fan Shaft, Bearings, and Fan Wheel (Typical)
21
Page 22
Centering Fan Wheel — If fan and fan shaft assembly
are not properly centered, blades may scrape against the blower side scroll plate or may create an objectionable whistling noise. It may be necessary to adjust individual fan wheels or move en­tire fan shaft. See the following two sections.
Fan Shaft Position Adjustment — Loosen set-
screw or locking collar of each fan shaft bearing. Slide shaft into correct position and replace locking collar (Fig. 21). To re­place locking collar, push collar up against inner face of bear­ing. Turn collar in direction of fan rotation until tight, and tight­en setscrew. Tightening locking collar in direction of fan rota­tion results in further tightening of collar should setscrew work itself loose.
Individual Fan Wheel Adjustment — Loosen the
2 locking bolts holding fan wheel hub to shaft. See Fig. 20. Position fan wheel in center of the fan housing and tighten locking bolts. Clearance between wheel and housing should be the same on both sides.
Fan Belts — Motor mounting plate and motor support
angles are slotted to permit both vertical and horizontal adjustment. Adjust belt(s) for correct deflection by loosening motor plate mounting bolts, moving motor/plate assembly forward or back, and retightening bolts. Press down on belt with one finger midway between fan and motor pulleys to check deflection. The correct deflection is Fig. 22.
If complete belt replacement is required during servicing, loosen the motor plate mounting bolts (Fig. 22), move motor/ plate assembly towards fan pulley, and pull belt(s) off pulleys. Reverse the procedure with new bolts and readjust deflection.
1
/8-in. (3.2 mm). See
Fan Rotation — Correct fan rotation with respect to fan
outlet is shown in Fig. 23. To reverse the direction of rotation of a 3-phase fan motor,
reverse any 2 of the power leads. Refer to the connection diagram on the inside of motor terminal box cover for proper reversing procedure of single-phase motor.
Fig. 21 — Fan Shaft Bearing
Fig. 22 — Fan Motor Mounting
22
Page 23
Fig. 23 — Fan Rotation
Fan Pulley Alignment — Align as follows:
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan pulley to lock it in place.
3. Use the methods shown in Fig. 24 to check proper pulley alignment.
4. If pulleys are not in correct alignment, loosen the motor holddown bolts and slide the motor axially until the pulleys are aligned.
5. Tighten motor holddown bolts.
Pulley and Drive Adjustment — To obtain desired
fan speed, refer to the fan motor and drive data in Tables 8A-11D and adjust fan motor pulley as follows:
1. Remove belt from fan motor pulley after loosening motor from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw moveable flange toward fixed flange to increase the fan speed and away from fixed flange to reduce speed. Before tightening setscrew, make certain that setscrew is over nearest flat surface of pulley hub (Fig. 24).
UNIT OPERA TION HAZARD
Failure to follow this caution could cause equipment damage.
Increasing fan speed produces a greater load on motor. Do not exceed rated capacity of motor.
Condensate Drains — Keep condensate drains free of
dirt and foreign matter.
Return-Air Filters — Refer to Replacing Filters section
for filter accessibility and removal. Replace with clean filters of the sizes listed in Tables 1A-1D.
Chilled Water Coil Freeze Protection — Shut off
water supply to unit. Remove side panel of unit and remove vent and drain plugs in top and bottom of coil header. Drain coil and blow out remaining water. Reinstall plugs and side panel.
Fig. 24 — Fan Pulley Adjustments
Alternative freeze protection methods follow:
• Circulate hot water within the water coil’s supply main or supplementary space heating.
• Close off supply lines to unit and open a union or field­supplied drain valve in the return line.
IMPORTANT: Draining from return line will not com­pletely drain water from coils.
• After draining as much water as possible from coils, add sufficient antifreeze to prevent residual water in the coil from freezing.
• Add a sufficient quantity of non-corrosive antifreeze to the entire system to prevent all water within the system from freezing.
Coil Removal — Remove unit panels and corner posts as
required. Disconnect coil connections and remove fastening screws. Remove coil through end or side sections of unit.
Cleaning Cooling Coil — Remove return-air filters.
Remove any heavy dirt that may have accumulated on under­side of coil. Coil can be cleaned more easily with a stiff brush, vacuum cleaner, or compressed air when coil is dry. If coil is wet or if water is to be used for cleaning, guard against splash­ing water on electrical components or damaging surrounding area. Clean coil baffles as applicable and check for tight fit to be sure air does not bypass coil.
Cleaning Insulation — The insulation contains an im-
mobilized antimicrobial agent that helps prevent the growth of bacteria and fungi. Clean the inner surface of the insulation according to the separate maintenance instructions shipped with the unit.
23
Page 24
Replacing Filters — Filters can be removed and in-
FILTER RETAINE CLIP
SLIDE
stalled from either side of the unit. Install new filters in units that have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 25).
3. Remove old filters by lifting and tilting them out of the filter track. See Fig. 15 and 26. Use the factory-supplied filter hook to slide filters within reach for removal. The filter hook is shipped inside the unit in the filter track
4. Reverse the procedure to install new filters.
UNIT OPERA TION HAZARD
Failure to follow this caution could cause equipment damage. Do not operate unit without air filters.
Fig. 26 — Filter Removal/Replacement
Fig. 25 — Remove Filter Retainer Clip
24
Page 25
Table 8A — Fan Motor Data, Standard Motor — English
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
208/230-3-60 and 460-3-60
Speed (rpm) 1745 1745 1745 Hp 5.0 7.5 10.0 Frame (NEMA) S184T S213T S215T Shaft Dia (in.) 1
1
/
8
13/
8
575-3-60
Speed (rpm) 1745 1755 1755 Hp 5.0 7.5 10.0 Frame (NEMA) 184T S213T D215T Shaft Dia (in.) 1
LEGEND NEMA — National Electrical Manufacturers Association
1
/
8
13/
8
Table 8B — Fan Motor Data, Alternate Motor — English
UNIT
40RUA*25 40RUS*25
208/230-3-60 and 460-3-60
Speed (rpm) 1745 1745 1745 Hp 7.5 10.0 10.0 Frame (NEMA) S213T S215T S215T Shaft Dia (in.) 1
3
/
8
575-3-60
Speed (rpm) 1755 1750 1750 Hp 7.5 10.0 10.0 Frame (NEMA) S213T D215T D215T Shaft Dia (in.) 1
LEGEND NEMA — National Electrical Manufacturers Association
3
/
8
40RUA*28 40RUS*28
13/
8
13/
8
40RUA*30 40RUS*30
13/
13/
13/
13/
8
8
8
8
25
Page 26
Table 8C — Fan Motor Data, Standard Motor — SI
UNIT
208/230-3-60 and 460-3-60
Speed (r/s) 29.08 29.08 29.08 Shaft kW 3.73 5.60 7.46 Frame (NEMA) S184T S213T S215T Shaft Dia (mm) 28.634.934.9
575-3-60
Speed (r/s) 29.08 29.25 29.25 Shaft kW 3.73 5.60 7.46 Frame (NEMA) 184T S213T S215T Shaft Dia (mm) 28.634.934.9
LEGEND
NEMA — National Electrical Manufacturers Association
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
Table 8D — Fan Motor Data, Alternate Motor — SI
UNIT
208/230-3-60 and 460-3-60
Speed (r/s) 29.08 29.17 29.17 Shaft kW 5.60 7.46 7.46 Frame (NEMA) S213T S215T S215T Shaft Dia (mm) 34.934.934.9
575-3-60
Speed (r/s) 29.25 29.17 29.17 Shaft kW 5.60 7.46 7.46 Frame (NEMA) S213T D215T D215T Shaft Dia (mm) 34.934.934.9
LEGEND
NEMA — National Electrical Manufacturers Association
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
26
Page 27
Table 9A — Standard Drive Data, 60 Hz — English
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 3.7-4.7 4.3-5.3 4.3-5.3 Pulley Factory Setting
Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 9.4 11.0 11.0 Pulley Bore (in.) 1 Belt No. — Section 2—B 2—B
Belt Pitch (in.) 41.8
7
/
16
115/
16
(2) 42.8 (2) 43.8
115/
2—B
(2) 42.8 (2) 43.8
FAN SPEEDS (rpm)
Factory Setting 771 752 752 Range 679-863 682-841 674-831 Max Allowable Speed (rpm) 1200 1100 1100 Change per
Moveable Motor Pulley Flange
MAX FULL TURNS FROM CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
1
/2 Turn of
15.3 13.1 13.1
666
9.12-
10.99
6.67-
9.43
16
6.67-
9.43
Table 9B — Medium-Static Drive Data, 60 Hz — English
UNIT
40RUA*25 40RUS*25
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 4.3-5.3 4.3-5.3 4.3-5.3 Pulley Factory Setting
Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 9.4 9.4 9.4 Pulley Bore (in.) 1
7
/
16
Belt No. — Section 1—B 2—B Belt Pitch (in.) 41.8
FAN SPEEDS (rpm)
Factory Setting 881 881 881 Range 798-984 798-984 798-984 Max Allowable Speed (rpm) 1200 1100 1100 Change per
Moveable Motor Pulley Flange
MAX FULL TURNS FROM CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
1
/2 Turn of
15.3 15.3 15.3
666
9.16-
10.99
40RUA*28 40RUS*28
115/
16
(2) 38.8 (2) 39.8
6.67-
9.43
40RUA*30 40RUS*30
115/
2—B
(2) 38.8 (2) 39.8
6.67-
9.43
16
27
Page 28
Table 9C — High-Static Drive Data, 60 Hz — English
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 4.3-5.3 4.3-5.3 4.3-5.3 Pulley Factory Setting
Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 7.4 8.6 8.6 Pulley Bore (in.) 1
7
/
16
115/
16
115/
Belt No. — Section 2—B 2—B 2—B Belt Pitch (in.) 36.8 378 37.8
FAN SPEEDS (rpm)
Factory Setting 1118 1024 1024 Range
1014­1200
873-
1075
873-
1075
Max Allowable Speed (rpm) 1200 1100 1100 Change per
Moveable Motor Pulley Flange
MAX FULL TURNS FROM CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.
1
/2 Turn of
19.416.716.7
666
8.16-
10.02
6.67-
9.43
6.67-
9.43
16
Table 9D — Standard Drive Data, 60 Hz — SI
UNIT
40RUA*25 40RUS*25
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm) Pulley Factory Setting
Full Turns Open
94.0-
119.4
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 239 279 279 Pulley Bore (mm) 36.549.249.2 Belt No. — Section 2—B 2—B
Belt Pitch (mm) 1062
FAN SPEEDS (r/s)
Factory Setting 12.912.512.5 Range 11.3-14.4 11.4-14.0 11.2-13.9 Max Allowable Speed (r/s) 20.018.318.3 Change per
Moveable Motor Pulley Flange
MAX FULL TURNS FROM CLOSED POSITION
1
/2Turn of
0.255 0.218 0.218
666
SHAFTS CENTER DISTANCE (mm) 232-279 169-240 169-240
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
40RUA*28 40RUS*28
109.2-
134.6
(2) 1987 (2) 1113
40RUA*30 40RUS*30
109.2-
134.6
2—B
(2) 1987 (2) 1113
28
Page 29
Table 9E — Medium-Static Drive Data, 60 Hz — SI
UNIT
40RUA*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30 40RUS830
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm) Pulley Factory Setting
Full Turns Open
109.2-
134.6
3.0 3.0 3.0
109.2-
134.6
109.2-
134.6
FAN DRIVE
Pulley Pitch Dia (mm) 239 239 239 Pulley Bore (mm) 36.5 49.2 49.2
(2) 986
(2) 1011
2—B
(2) 986
(2) 1011
Belt No. — Section 1—B 2—B Belt Pitch (mm) 1062
FAN SPEEDS (r/s)
Factory Setting 14.7 14.7 14.7 Range 13.3-16.4 13.3-16.4 13.3-16.4 Max Allowable Speed (r/s) 20.0 18.3 18.3 Change per
Moveable Motor Pulley
1
/2 Turn of
0.255 0.255 0.255
Flange
MAX FULL TURNS FROM CLOSED POSITION
666
SHAFTS CENTER DISTANCE (mm) 232-279 169-240 169-240
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully se tting.
Table 9F — High-Static Drive Data, 60 Hz — SI
UNIT
40RUA*25 40RUS*25
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm) Pulley Factory Setting
Full Turns Open
109.2-
134.6
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 188 203 Pulley Bore (mm) 36.5 49.2 49.2 Belt No. — Section 2—B 2—B 2—B Belt Pitch (mm) 935 935 960
FAN SPEEDS (r/s)
Factory Setting 18.6 17.1 17.1 Range
16.9-
20.0
Max Allowable Speed (r/s) 20.0 18.3 18.3 Change per
Moveable Motor Pulley Flange
MAX FULL TURNS FROM CLOSED POSITION
1
/2 Turn of
0.323 0.278 0.278
666
SHAFTS CENTER DISTANCE (mm) 207-255 169-240 169-240
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.
40RUA*28 40RUS*28
109.2-
134.6
14.6-
17.9
40RUA*30
40RUS*30
109.2-
134.6
203
14.6-
17.9
29
Page 30
Table 10A — 40RU Standard Fan Performance Data —
0.0-2.4 in. wg External Static Pressure — English
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
See Legend and Notes on page 34.
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
AIRFLOW
(Cfm)
6,000 532 1.25 569 1.39 639 1.69 711 2.06 781 2.48 846 2.93 905 3.60 7,000 608 1.93 641 2.09 702 2.42 763 2.08 824 3.23 885 3.71 943 4.23 8,000 686 2.83 716 3.01 770 3.38 823 3.77 876 4.21 930 4.70 983 5.24 9,000 764 3.97 791 4.18 841 4.59 888 5.02 935 5.47 982 5.96 1030 6.51
10,000 843 5.38 868 5.62 914 6.09 957 6.55 1000 7.02 1042 7.53 1084 8.08
7,500 456 1.29 490 1.47 556 1.85 621 2.25 678 2.64 729 3.06 778 3.60
8,750 521 1.98 551 2.18 608 2.61 664 3.07 720 3.53 770 3.99 816 4.45 10,000 587 2.88 614 3.11 664 3.59 714 4.09 763 4.62 812 5.15 857 5.68 11,250 653 4.03 678 4.29 724 4.82 768 5.37 812 5.95 856 6.54 899 7.14 12,500 720 5.46 743 5.75 785 6.33 825 6.93 865 7.55 904 8.20 944 8.86 15,000 829 8.84 850 9.19 888 9.88 924 10.57 958 11.27 991 11.99 1024 12.73
9,000 521 1.99 550 2.25 616 2.77 676 3.23 731 3.72 782 4.20 829 4.70 10,500 596 3.16 623 3.40 672 3.89 720 4.40 767 4.94 814 5.50 859 6.05 12,000 673 4.63 698 4.90 743 5.45 785 6.02 826 6.62 867 7.23 908 7.87 13,500 751 6.51 773 6.82 815 7.44 853 8.06 890 8.71 927 9.38 963 10.07 15,000 829 8.84 850 9.19 888 9.88 924 10.57 958 11.27 991 11.99 1024 12.73
AIRFLOW
(Cfm)
6,000 954 3.83 1005 4.27 1052 4.72 1098 5.22 1142 5.67 7,000 990 4.74 1040 5.24 1090 5.80 1135 6.30 1176 6.84 8,000 1028 5.79 1078 6.38 1130 7.00 1173 7.60 9,000 1073 7.11 1120 7.72 1169 8.37
10,000 1126 8.75 1166 9.37
7,500 831 4.41 870 5.10 913 5.90 950 6.88 985 7.70
8,750 859 4.97 901 5.59 944 6.42 980 7.20 1020 8.10 10,000 900 6.20 939 6.74 976 7.33 1013 8.00 1050 8.82 11,250 941 7.73 980 8.32 1017 8.90 1052 9.51 1088 10.16 12,500 984 9.53 1022 10.19 1058 10.84 1093 11.49 15,000 1057 13.49 1090 14.28
9,000 866 5.20 899 5.85 950 6.65 989 7.38 1029 8.32 1077 9.74 10,500 902 6.60 942 7.14 980 7.70 1016 8.31 1051 8.99 1085 9.77 12,000 949 8.50 988 9.14 1026 9.76 1062 10.38 1095 11.01 13,500 1000 10.78 1036 11.49 1073 12.21 15,000 1057 13.49 1090 14.28
0.0 0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
EXTERNAL STATIC PRESSURE (in. wg)
Table 10A — 40RU Standard Fan Performance Data —
0.0-2.4 in. wg External Static Pressure — English (cont)
EXTERNAL STATIC PRESSURE (in. wg)
1.41.61.82.02.22.4
See Legend and Notes on page 34.
30
Page 31
Table 10B — 40RU Standard Fan Performance Data —
0-600 kPa External Static Pressure — SI
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
See Legend and Notes on page 34.
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
AIRFLOW
(L/s)
2830 8.86 0.94 9.48 1.04 10.65 1.26 11.84 1.53 13.01 1.85 14.10 2.19 15.08 2.53 3300 10.14 1.44 10.69 1.56 11.70 1.81 12.71 2.08 13.73 2.41 14.74 2.77 15.71 3.15 3780 11.43 2.11 11.93 2.25 12.84 2.52 13.71 2.81 14.60 3.14 15.49 3.51 16.39 3.91 4250 12.74 2.96 13.119 3.12 14.02 3.43 14.81 3.74 15.59 4.08 16.37 4.45 17.17 4.85 4720 14.05 4.01 14.47 4.19 15.23 4.54 15.96 4.88 16.66 5.24 17.36 5.62 18.07 6.03
3540 7.60 0.96 8.16 1.09 9.27 1.38 10.34 1.68 11.30 1.97 12.15 2.28 12.97 2.68 4130 8.68 1.47 9.18 1.62 10.13 1.94 11.07 2.29 11.99 2.63 12.84 2.97 13.60 3.32 4720 9.78 2.15 10.23 2.32 11.07 2.67 11.89 3.05 12.72 3.45 13.53 3.84 14.29 4.23 5310 10.89 3.01 11.30 3.20 12.06 3.59 12.80 4.00 13.53 4.43 14.27 4.88 14.99 5.33 5900 12.00 4.07 12.38 4.29 13.09 4.72 13.75 5.17 14.41 5.63 15.07 6.11 15.74 6.61
4250 8.68 1.48 9.17 1.68 10.27 2.07 11.27 2.41 12.19 2.77 13.03 3.13 13.81 3.50 4960 9.93 2.35 10.38 2.53 11.21 2.90 11.99 3.28 12.78 3.68 13.56 4.10 14.32 4.51 5660 11.21 3.45 11.63 3.66 12.38 4.07 13.08 4.49 13.76 4.93 14.45 5.39 15.14 5.87 6370 12.51 4.85 12.89 5.08 13.58 5.54 14.22 6.01 14.83 6.49 15.44 6.99 16.05 7.51 7080 13.82 6.59 14.17 6.85 14.81 7.36 15.40 7.88 15.97 8.40 16.52 8.94 17.06 9.49
AIRFLOW
(L/s)
2830 15.90 2.86 16.75 3.18 17.53 3.52 18.30 3.89 19.03 4.23 3300 16.50 3.53 17.33 3.91 18.17 4.32 18.92 4.70 19.60 5.10 3780 17.13 4.32 17.97 4.76 18.83 5.22 19.55 5.67 4250 17.88 5.30 18.67 5.76 19.48 6.24 4720 18.77 6.52 19.43 6.99
3540 13.85 3.29 14.50 3.80 15.22 4.40 15.83 5.13 16.42 5.74 4130 14.31 3.71 15.01 4.17 15.74 4.79 16.33 5.37 17.00 6.04 4720 14.99 4.62 15.65 5.02 16.27 5.46 16.88 5.97 17.50 6.57 5310 15.68 5.77 16.34 6.20 16.95 6.64 17.53 7.09 18.09 7.58 5900 16.39 7.10 17.03 7.60 17.64 8.08 18.22 8.57
4250 14.43 3.88 14.98 4.36 15.84 4.96 16.48 5.50 17.16 6.21 17.96 7.26 4960 15.04 4.92 15.71 5.32 16.33 5.74 16.93 6.20 17.51 6.70 18.09 7.29 5660 15.81 6.34 16.47 6.81 17.10 7.28 17.69 7.74 18.26 8.21 6370 16.66 8.04 17.27 8.57 17.88 9.10 7080 17.61 10.06 18.16 10.64
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
EXTERNAL STATIC PRESSURE (kPa)
0 50 100 150 200 250 300
Table 10B — 40RU Standard Fan Performance Data —
0-600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
350 400 450 500 550 600
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
See Legend and Notes on page 34.
31
Page 32
Table 10C — 40RU High-Capacity Fan Performance Data —
0.0-2.4 in. wg External Static Pressure — English
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
See Legend and Notes on page 34.
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
AIRFLOW
(Cfm)
6,000 542 1.29 577 1042 646 1.72 716 2.09 785 2.51 849 2.95 907 3.40 7,000 620 1.99 652 2.15 711 2.48 771 2.85 831 3.28 890 3.76 947 4.27 8,000 700 2.92 728 3.10 781 3.46 833 3.85 885 4.29 938 4.78 990 5.32 9,000 781 4.10 806 4.30 854 4.71 900 5.13 946 5.58 993 6.08 1039 6.62
10,000 862 5.56 885 5.79 929 6.24 971 6.70 1012 7.18 1054 7.69 1096 8.24
7,500 476 1.39 510 1.58 579 1.99 644 2.40 701 2.81 752 3.29 804 3.96
8,750 545 2.14 574 2.35 633 2.81 691 3.29 747 3.77 797 4.25 842 4.76 10,000 615 3.12 641 3.36 692 3.87 743 4.41 794 4.96 843 5.51 888 6.05 11,250 685 4.37 709 4.64 754 5.20 800 5.79 845 6.40 891 7.02 935 7.64 12,500 756 5.92 778 6.22 819 6.83 860 7.47 901 8.14 942 8.83 983 9.52
9,000 539 2.18 569 2.39 626 2.85 683 3.34 739 3.83 791 4.32 837 4.82 10,500 620 3.37 646 3.62 695 4.13 744 4.68 793 5.25 842 5.83 888 6.41 12,000 701 4.94 724 5.22 769 5.80 811 6.40 854 7.04 897 7.69 940 8.36 13,500 783 6.95 804 7.27 844 7.91 883 8.57 920 9.26 958 9.97 996 10.71 15,000 865 9.45 884 9.81 921 10.52 956 11.24 991 11.98 1025 12.75 1059 13.54
AIRFLOW
(Cfm)
6,000 961 3.86 1011 4.31 1058 4.77 1104 5.24 1147 5.71 7,000 1000 4.79 1050 5.32 1097 5.85 1142 6.38 1184 6.91 8,000 1041 5.88 1090 6.47 1137 7.07 1181 7.67 9,000 1086 7.21 1133 7.82 1178 8.47 ——————
10,000 11388.8311809.46————————
7,500 874 5.33 897 5.91 940 6.80 990 7.50
8,750 886 5.36 930 6.13 982 7.32 1020 8.10 10,000 930 6.60 969 7.20 1007 7.89 1045 8.71 11,250 976 8.25 1014 8.86 1051 9.49 1086 10.17 12,500 1023 10.20 1061 10.88 1097 11.56 ——————
9,000 881 5.37 923 6.03 967 6.89 1020 8.25 10,500 930 6.97 970 7.55 1008 8.17 1045 8.86 12,000 981 9.02 1021 9.67 1058 10.32 1094 10.97 13,500 1035 11.45 1072 12.20 ———————— 15,000 1093 14.35 —————————
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
Table 10C — 40RU High-Capacity Fan Performance Data —
0.0-2.4 in. wg External Static Pressure — English (cont)
EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
See Legend and Notes on page 34.
32
Page 33
Table 10D — 40RU High-Capacity Fan Performance Data —
0-600 kPa External Static Pressure — SI
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
See Legend and Notes on page 34.
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
AIRFLOW
(L/s)
2830 9.03 0.96 9.62 1.06 10.77 1.29 11.94 1.56 13.08 1087 14.15 2.20 15.12 2.54 3330 10.34 1.48 10.86 1.60 11.85 1.85 12.84 2.12 13.85 2.45 14.84 2.80 15.78 3.18 3780 11.67 2.17 12.14 2.31 13.02 2.58 13.88 2.87 14.75 3.20 15.63 3.56 16.50 3.96 4250 13.01 3.05 13.44 3.21 14.23 3.51 15.00 3.82 15.77 4.16 16.54 4.53 17.32 4.94 4720 14.36 4.15 14.75 4.32 15.48 4.66 16.18 4.99 16.87 5.35 17.56 5.73 18.26 6.14
3540 7.94 1.04 8.51 1.18 9.65 1.48 10.73 1.79 11.68 2.10 12.53 2.46 13.40 2.95 4130 9.08 1.59 9.57 1.75 10.55 2.10 11.52 2.46 12.45 2.81 13.28 3.17 14.04 3.55 4720 10.24 2.33 10.68 2.51 11.53 2.88 12.39 3.29 13.24 3.70 14.05 4.11 14.80 4.51 5310 11.42 3.26 11.81 3.46 12.57 3.88 13.33 4.32 14.09 4.77 14.85 5.24 15.58 570 5900 12.60 4.42 12.96 4.64 13.65 5.09 14.33 5.57 15.01 6.07 15.40 6.58 16.38 7.10
4250 8.99 1.62 9.49 1.78 10.44 2.12 11.39 2.49 12.32 2.86 13.18 3.22 13.95 3.59 4960 10.33 2.51 10.77 2.70 11.59 3.08 12.40 3.49 13.22 3.92 14.03 4.35 14.79 4.78 5660 11.68 3.68 12.07 3.90 12.81 4.33 13.52 4.77 14.23 5.25 14.95 5.74 15.66 6.23 6370 13.04 5.18 13.40 5.42 14.07 5.90 14.71 6.39 15.34 6.90 15.97 7.44 16.61 7.98 7080 14.42 7.05 14.74 7.31 15.36 7.84 15.94 8.38 16.51 8.93 17.08 9.51 17.65 10.10
AIRFLOW
(L/s)
2830 16.01 2.88 16.85 3.22 17.64 3.56 18.39 3.91 19.12 4.26 3300 16.67 3.57 17.50 3.96 18.28 4.36 19.03 4.75 19.73 5.15 3780 17.35 4.39 18.17 4.82 18.95 5.27 19.68 5.72 4250 18.11 5.37 18.88 5.83 19.63 6.31 4720 18.96 6.58 19.67 7.05
3540 14.57 3.97 14.95 4.41 15.67 5.07 16.50 5.59 4130 14.76 3.99 15.51 4.57 16.36 5.46 17.00 6.04 4720 15.49 4.92 16.15 5.37 16.78 5.88 17.42 6.50 5310 16.26 6.15 16.91 6.61 17.51 7.08 18.10 7.58 5900 17.04 7.61 17.68 8.11 18.28 8.62
4250 14.68 4.00 15.38 4.49 16.12 5.14 17.00 6.15 4960 15.51 5.20 16.17 5.63 16.80 6.09 17.41 6.61 5660 16.35 6.72 17.01 7.21 17.64 7.69 18.23 8.18 6370 17.24 8.54 17.87 9.10 7080 18.2210.70——————————
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
EXTERNAL STATIC PRESSURE (kPa)
0 50 100 150 200 250 300
Table 10D — 40RU High-Capacity Fan Performance Data —
0-600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
350 400 450 500 550 600
r/skWr/skWr/skWr/skWr/skWr/skW
See Legend and Notes on page 34.
33
Page 34
Legend and Notes for Tables 10A and 10C
LEGEND
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure
NOTES:
1. Maximum allowable fan speed for size 25 units is 1200 rpm . Maximum allowable fan speed for size 28 and 30 units is 1100 rpm.
2. Fan performance is based on deductions for wet coil, clean 2-in. filters, and unit casing. See table at right for factory-supplied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
Legend and Notes for Tables 10B and 10D
LEGEND
ESP — External Static Pressure NOTES:
1. Maximum allowable fan speed for size 25 units is 20 r/s. Maximum allowable fan speed for size 28 and 30 units is 18.3 r/s.
2. Fan performance is based on deductions for wet coil, clean 51-mm filters, and unit casing. See table at right for factory-sup­plied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
AIRFLOW
(Cfm) 6,000 0.12
8,000 0.19
10,000 0.26
7,500 0.15 10,000 0.22 12,500 0.30
9,000 0.19 12,000 0.29 15,000 0.40
PRESSURE DROP
(in. wg)
FACTORY-SUPPLIED PRESSURE DROP — SI
UNIT
40RUA*25 40RUS*25
40RUA*28 40RUS*28
40RUA*30 40RUS*30
AIRFLOW
(L/s)
2900 32 3800 47 4700 64
3500 36 4700 55 5900 76
4250 47 5650 71 7050 98
PRESSURE DROP
(Pa)
Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in Mexico Edition Date: 09/09 Catalog No: 40RU-03SI Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
34
Page 35
I. PRELIMINARY INFORMATION
START-UP CHECKLIST
(SPLIT SYSTEMS WITH 40RU UNITS)
OUTDOOR: MODEL NO. _________________________ SERIAL NO. ___________________________________ ADDITIONAL ACCESSORIES ______________________________________________________________________________
INDOOR: MODEL NO. ___________________________ SERIAL NO. ___________________________________
II. PRE-START-UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? _______________ (Y/N) ____ IF SO, WHERE: _________________________________________________________________________________________
_______________________________________________________________________________________________________ WILL THIS DAMAGE PREVENT UNIT ST ART-UP? (Y/N) _____ CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) _____ HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) _____ HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) _______ ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) _______ HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N) _____
CONTROLS
ARE THERMOST AT(S) AND INDOOR FAN CONTROL WIRING CONNECTIONS MADE AND CHECKED? (Y/N) _____
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) _____ HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N) ______
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN P AN T O CONFIRM PROPER DRAINAGE? (Y/N) _____ ARE PROPER AIR FIL TERS IN PLACE? (Y/N) _____ HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) ______ DO THE FAN BELTS HAVE PROPER TENSION? (Y/N) _____
PIPING
40RUA HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? (Y/N) ______ ARE LIQUID LINE SOLENOID VALVES LOCA TED AT THE INDOOR UNIT COILS AS REQUIRED? (Y/N) _____ HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion V alves) SOLE NOID VAL VES, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N) _____
LOCATE, REPAIR, AND REPORT ANY LEAKS. _______________________________________________________________ HAVE ALL COMPRESSOR SER VICE VAL VES BEEN FULLY OPENED (BACKSEA TED) (Y/N) ____ ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N) _____ 40RUS HAS AIR BEEN BLED FROM SYSTEM? (Y/N) ___________________________________________ HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, AND INDOOR COILS? (Y/N) LOCATE, REPAIR, AND REPORT ANY LEAKS. _______________________________________________________________
CL-1
Page 36
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOL TS: AB ________ V AC ______ V BC ______ V (AB + AC + BC)/3 = A VERAGE VOLT AGE = _______ V MAXIMUM DEVIA TION FROM AVERAGE VOLTAGE = _______ V VOL TAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = __________ % IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START-UP
CHECK INDOOR FAN MOT OR SPEED AND RE CORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP OUTDOOR UNIT ENTERING WATER TEMP
(40RUS ONLY) OUTDOOR UNIT LEAVING WATER TEMP
(40RUS ONLY) INDOOR UNIT ENTERING WATER TEMP
(40RUS ONLY) INTDOOR UNIT LEAVING WATER TEMP
(40RUS ONLY)
COMPRESSOR AMPS (L1/L2/L3) ____/____/____ ____/____/____
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING OIL LEVEL AT
1
/8 to 1/3 FULL? (Y/N) ______
COMP A1 COMP B1
NOTES:
______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________
Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in Mexico Edition Date: 09/09 Catalog No: 40RU-03SI Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Pg CL-2 Replaces: New
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...