The following general safety notices supplement the specific warnings and cautionsappearing elsewhere in
this manual. They are recommended precautions that must be understood and applied during operation and
maintenanceoftheequipmentcoveredherein.Thegeneralsafety notices arepresentedinthefollowingthree
sections labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific
warnings and cautions appearing elsewhere in the manual follows the general safety notices.
FIRST AID
An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention
immediately.
OPERATING PRECAUTIONS
Always wear safety glasses.
Keep hands clear of the evaporator blower and condenser fan.
No work should be performed on the unit until all circuit breakers and start--stop switches are turned off, and
power supply is disconnected.
Always work in pairs. Never work alone.
In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator blower & condenser fan. Do not remove the ceiling grill
assembly or the upper unit coverassembly beforeturningthe power off, and disconnecting the power supply.
Before disconnecting, discharge capacitors by shorting across the capacitors terminals. (See Paragraph
3.5.8)
When disassembling wiring, use numbered stickers to identify wire leads and terminals. This aids in quick,
accurate reassembly.
Besurepoweristurnedoffbeforeworkingonmotors,controllers, or electricalcontrolswitches.Taganycircuit
breakers and power supply to prevent accidental energizing of circuits.
Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires.
Problems with the system should be diagnosed and any necessary repairs must be performed by qualified
service personnel.
In case of electrical fire, open circuit switch and extinguish with CO
Usedrynitrogentopressurizethesystemforleakchecking. Be careful not to exceed150psigtestpressurein
the hermetic compressor.
Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury.
Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when
brazing, and keep brazing cloth and fire extinguisher handy for emergency use.
Disconnect power to the AirV unit before checking the capacitor.
(never use water).
2
Safety-- i
T-298
Page 4
SPECIFIC WARNING AND CAUTION STATEMENTS
The statements listed below are applicable to the refrigeration unit and appear elsewhere in this manual.
These recommended precautions must be understood and applied during operation and maintenance of the
equipment covered herein.
SPECIFIC WARNINGS AND CAUTIONS
WARNING
Be sure to observe warnings listed in the safetysummary in the front of this manualbefore
performing maintenance on the AirV system
WARNING
Beforeworkingonthe unitbesuretofirstdisconnectall electricpowertotheunitto avoidthe
possibilityof electrical shock and personalinjury. Before disconnecting, discharge capaci-tors by shorting across the capacitors terminals (Refer to paragraph 3.5.8)
WARNING
Shieldcoilswithcardboard to protecthandsagainstinjuryfromsharpmetaledgeswhen removing compressor and other components.
WARNING
Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency
use.
WARNING
Disconnect power to the AirV unit before checking the capacitor.
WARNING
Do not touch the metal of the screwdriver when discharging the capacitor.Y oucould receive
a shock.
WARNING
Before installing thermostat, turn off all power to unit. There may be more than one power
disconnect. Electrical shock can cause personal injury or death.
CAUTION
Do not use carbon tetrachloride, solvents, or waxes containing solvents to clean plastic sections.
T--298
Safety-- ii
Page 5
CAUTION
Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal
injury.
Figure 4-1 Upper Unit Schematic - Standard & HC4-1................................................
Figure 4-2 Upper Unit Schematic - Low Profile4-1...................................................
Figure 4-3 Ceiling Unit Schematic - Cooling Only4-2.................................................
Figure 4-4 Ceiling Unit Schematic - Heat/Cool4-2....................................................
Figure 4-5 Ceiling Unit, Standard - Ducted4-2.......................................................
Figure 4-6 Heat Pump - Upper Unit - Free Blow4-3..................................................
Figure 4-7 Heat Pump - Ceiling Unit - Free Blow4-3..................................................
Figure 4-8 Heat Pump - Upper Unit - Ducted4-4.....................................................
Figure 4-9 Heat Pump - Ceiling Unit - Ducted4-4....................................................
LIST OF TABLES
TABLE NUMBERPage
Table 1-1 Model Chart1-2.........................................................................
Table 1-2 Additional Support Manuals1-3............................................................
Table 2-1 System Self-diagnostics Function (Ducted Remote)2-4.......................................
T--298
iv
Page 10
SECTION 1
DESCRIPTION
1.1INTRODUCTION
This manual contains service instructions and electrical
data for the AirV, Carrier Transport Air Conditioning’s
Recreational Vehicle air conditioning unit.
The AirV units are two piece systems, consisting of the
UpperUnitandtheCeilingunit.TheUpperUnitcontains
the refrigeration system while the Ceiling Unit contains
thecontrols andvents. The Ceiling Units are availablein
a free--blow or ducted configuration.
The free--blow units (see Figure 1-2) deliver air to the
vehicle by means of front and rear end vents and one
downward vent (air shower). The vents may all be
opened or closed to direct air as desired. The front and
rear vents are fitted with motorized dampers that
oscillates to produce an “air--sweep” effect. These units
may be fitted with optional electric heat.
Theductedunits(seeFigure 1-5andFigure 1-6)deliver
air through ducting built in the vehicle ceiling. These
units are fitted with a 12 VDC microprocessor control
system, a display panel (PCB display) and a remote
controller. These units may be wired to provide
thermostatic control of the vehicle furnace.
Carrier’s AirV air conditioning models include cooling
only units, heating/cooling units, and heat pump units.
The cooling only units are available with free blow or
ducted air delivery. Cooling units with heat strips are
available for free blow only.
Operation of the AirV units is controlled automatically by
thetemperaturecontroller(thermostat),which
maintains the vehicle’s interior temperature at the
desired set point. Free Blow, cool--only units are
available with a wall mounted thermostat.
Table 1-1 lists model numbers and descriptions of the
AirV units, and Table 1-2 lists additional support
manuals that are available.
1.2SERIAL NUMBER IDENTIFICATION
Separatepartnumbersandserialnumbersareprovided
for the upper and lower unit assemblies The numbers
may be found on a plate readable from inside the
vehicle, See Figure 1-7.
The first two numbers of the serial number, see
Figure 3-22, is theweektheunitwasmanufactured. For
example, 01 would designate the first week of the year
and 52 would designate the last week of the year.
The third and fourth numbers designate the year in
which the unit was manufactured. For example, 99
would represent the year 1999, 00 the year 2000, and
so on.
The letter Y and all the numbers after it designates the
unit serial number. Example: Y43210
Aserialnumber of 1303Y12345 designates that the unit
was manufactured the 13th week of 2003 and the serial
number is Y12345.
Carrier
Air Conditioning
C
Division ofCarrier Corporation
USEAMP20
TIME DELAY FUSE OR
CIRCUIT BREAKER
COMPRESSOR
FAN MOTOR
USE CEILING ASSY/ANY
DATEOFMfg
DESIGN PSIG HIGH 350 LO 150
R--22
MODEL No.
Part No.
VOLTS
CAPACITY
AMPS
SERIAL No.
68RV14102A
99--00468-- 01
115
ph
1
13,500
3,955
13.5
05/03
1303Y12345
oz
kg
RLA
FLA
99--00469-- 01
15.9
0.45
12.5
2.58
hz
V
60
Btu/h
W
A
Figure 1-1 Model/Serial Number Plate (Typical)
1.3DESIGN CHANGE DESCRIPTIONS
The following list provides a description of changes in
design and serial number breaks for those changes.
1400Y A diode was added to the Ducted Ceiling
assembly control board to stop DC ripple from the
converters,
2900Y Cover screw coating was changed in order to
eliminate corrosion.
3400Y The plastic shroud was modified to improve
drainage.
5100Y A new compressor and capacitor is introduced,
improving stability and increasing capacity.
1201Y The temperature sensor was moved to the grill
to improve temperature sensing during furnace mode,
2501Y The dual air sweep was added.
4501Y A switch was added to skip compressor
malfunction test.
4601Y Change in material was made in order to
strengthen the fan propeller.
4901Y The mounting bolt lengths were increased 3/4
inch.
4901Y The polar whiteducted ceiling color was cut--in.
0703Y & 1903Y Newstyle PCB -- Cool Mode -- Control
& Power Assembly (Fans shut off in auto mode).
0803Y & 2603Y Newstyle PCB -- Heat Pump -- Control
& Power Assembly (Fans shut off in auto mode).
4204Y Minimumfurnacesetpoint loweredfrom 63°Fto
The cooling cycle is energized when the thermostat,
located on the ceiling unit, calls for cooling. The main
components of the system are the compressor,
air-cooled condenser coil, strainer, capillary tube,
evaporator coil and accumulator.
Thecompressorraisesthepressureandthe
temperature of the refrigerant and forces it through the
discharge line into the condenser coil. (See Figure 1-8.)
The condenser fan circulates surrounding air (which is
at a temperature lower than the refrigerant) over the
outside of the coil tubes. Heat transfer is established
from the refrigerant (inside the tubes) to the air (flowing
over the tubes). The tubes have fins designed to
improve the transfer of heat from the refrigerant gas to
the air. This removal of heat causes the refrigerant to
liquefy, thus liquid refrigerant leaves the coil and flows
through a strainer to the capillary tube. The strainer
removes any impurities within the refrigerant system.
The capillary tube meters the flow of liquid refrigerant to
the evaporator coil. As the refrigerant flows through the
capillary tube, there is a reduction in pressure and
temperature.
CAPILLARY
TUBE
EVAPORATOR
ACCUMULATOR
CONDENSER
STRAINER
Theevaporator blower (fan)pullsvehicleairthroughthe
filters, which remove particulate matter, and then pass
the cleaned air through the evaporator coil.
The low pressure, low temperature liquid that flows into
the evaporator coil tubes is colder than the air that is
circulated over the tubes. Heat transfer is established
from the vehicle air (flowing over the tubes) to the
refrigerant (flowing inside the tubes). The evaporator
coil tubes have aluminum fins to increase heat transfer
from the air to the refrigerant; therefore the cooler air is
circulated to the interior of the vehicle.
The transfer of heat from the air to the low temperature
liquid refrigerant in the indoor coil causes the liquid to
vaporize. This low temperature, low pressure vapor
passes into the accumulator. The accumulator is
designed with the inlet tube delivering refrigerant to the
bottom of the tank and the outlet tube taking refrigerant
form the top of the tank. This arrangement ensures that
only vapor refrigerant is returned to the compressor,
where the cycle repeats.
When ventilation only is selected, the indoor fan
functions to circulate air throughout the vehicle. The
refrigerant cycle will remain off.
The cooling cycle is energized when the thermostat,
located in the ceiling unit, calls for cooling The system
controls are positioned for “normal”refrigerant flow,with
the compressor discharge delivered to the outdoor coil
and liquid delivered to the indoor coil. (See Figure 1-9.)
The main components of the systemare the
compressor, reversing valve, air-cooled outdoor coil,
strainer,capillary tube, indoor coil, and theaccumulator.
Thecompressorraisesthepressureandthe
temperature of the refrigerant and forces it through the
discharge line and reversing valve into the outdoor coil.
The outdoor fan circulates surrounding air (which is at a
temperature lower than the refrigerant)over the outside
of the coil tubes. Heat transfer is established from the
refrigerant (inside the tubes) to the outdoor air (flowing
over the tubes). The tubes have fins designed to
improve the transfer of heat from the refrigerant gas to
the air; this removal of heat causes the refrigerant to
liquefy, thus liquid refrigerant leaves the coil and flows
through the strainer to the capillary tube. The strainer
removes any impurities within the refrigerant system.
The capillary tube meters the flow of liquid refrigerant to
the indoor coil. As the refrigerant flows through the
CAPILLARY
INDOOR COIL
REVERSING VALVE
OUTDOOR COIL
TUBE
STRAINER
capillary tube, there is a reduction in pressure and
temperature.
The indoor blower (fan) pulls inside air through the
filters, which remove particulate matter, and then pass
the cleaned air through the indoor coil.
The low pressure, low temperature liquid that flows into
the indoor coil tubes is colder than the air that is
circulated over the tubes. Heat transfer is established
from the indoor air (flowing over the tubes) to the
refrigerant (flowing inside the tubes). The indoor coil
tubes have aluminum fins toincrease heat transfer from
the air to the refrigerant; therefore the cooler air is
circulated to the interior of the vehicle.
The transfer of heat from the air to the low temperature
liquid refrigerant in the indoor coil causes the liquid to
vaporize. This low temperature, low pressure vapor
passes into the accumulator. The accumulator is
designed with the inlet tube delivering refrigerant to the
bottom of the tank and the outlet tube taking refrigerant
form the top of the tank. This arrangement ensures that
only vapor refrigerant is returned to the compressor,
where the cycle repeats.
When ventilation only is selected, the indoor fan
functions to circulate air throughout the vehicle. The
refrigerant cycle will remain off.
The heating cycle is energized when the thermostat,
located in the ceiling unit, calls for heat The system
controls are positioned for “reverse” refrigerant flow,
with the compressor discharge delivered to the indoor
coil and liquid delivered to the outdoor coil. (See
Figure 1-10.)
The main components of the systemare the
compressor, reversing valve, indoor coil, capillary tube,
strainer, air-cooled outdoor coil, and the accumulator.
Thecompressorraisesthepressureandthe
temperature of the refrigerant and forces it through the
discharge line and reversing valve into the indoor coil.
The indoor blower (fan) pulls inside air through the
filters, which remove particulate matter, and then pass
the cleaned air through the indoor coil.
Thevehicle air (which is at a temperature lower than the
refrigerant) passes over the outside of the coil tubes.
Heat transfer is established from the refrigerant (inside
thetubes) to thevehicleair(flowingoverthetubes).The
tubes have fins designed to improve the transfer of heat
from the refrigerant gas to the air; this removal of heat
causes the refrigerant to liquefy, thus liquid refrigerant
leaves the coil and flows through the strainer to the
outdoor coil. The strainer removes any impurities within
the refrigerant system.
The capillary tube meters the flow of liquid refrigerant to
the outdoor coil. As the refrigerant flows through the
capillary tube, there is a reduction in pressure and
temperature.
The low pressure, low temperature liquid that flows into
the outdoor coil tubes is colder than the outdoor air that
is circulated over thetubes. Heat transfer isestablished
from the outdoor air (flowing over the tubes) to the
refrigerant (flowing inside the tubes). The outdoor coil
tubes have aluminum fins toincrease heat transfer from
the air to the refrigerant.
The transfer of heat from the air to the low temperature
liquid refrigerant in the outdoor coil causes the liquid to
vaporize. This low temperature, low pressure vapor
passes into the accumulator. The accumulator is
designed with the inlet tube delivering refrigerant to the
bottom of the tank and the outlet tube taking refrigerant
form the top of the tank. This arrangement ensures that
only vapor refrigerant is returned to the compressor,
where the cycle repeats.
When ventilation only is selected, the indoor fan
functions to circulate air throughout the vehicle. The
refrigerant cycle will remain off.
1-11
T--298
Page 21
SECTION 2
TROUBLESHOOTING
For ducted units, the green operation indicator LED (SeeFigure 3-9) will flash if there is a problem.
Refer to Table 2--1 for diagnostic information.
SYMPTOM AND PROBABLE CAUSE
2.1NO POWER TO UNIT
1. Master switch off
2. Open circuit breaker
3. Defective wiring
4. Loose electrical connections
5. Faulty switches, thermostat, or fan
6. 12 VDC not connected (Ducted System)
7. 12 VDC in--line fuse open (Ducted)
2.2DUCTED UNIT WILL NOT OPERATE
1. Display not illuminated
2. Display illuminated
2.3DUCTED UNIT WILL NOT COOL
1. Green LED light flashes 5 times
2. Unit cools for a few moments then stops cooling
2.4 COMPRESSOR POWER SUPPLY OPEN
1. Loose leads at compressor terminals
2. Defective motor overload switch
3. Defective capacitor
4. Open compressor windings
5. Seized compressor
6. Capacitor incorrectly wired
2.5COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY
1. Loose lead at fan motor
2. Defective or burned out motor
3. Outdoor air restricted or recirculating
4. Overcharge or noncondensables in system
5. Restricted discharge line
6. Defective motor overload switch
1. Reset master switch
2. Reset circuit breaker
3. Replace wiring
4. Tighten connections
5. Replace defective components
6. Connect to 12 VDC power source
7. Replace fuse
1. Check 12 Volt DC in--line fuse
2. Check 1 15 Volt AC Connections
1. Check 1 15 volt AC power source
Momentarily disconnect 12 VDC power source
Disable compressor malfunction test switch.
Check AMP draw.
Check ∆ T
2. Remove grill, verify evaporator coil probe is
inserted into coil.
Check AMP draw.
Check ∆ T
Replace unit
1. Tighten leads
2. Replace switch
3. Replace capacitor -- Refer to Paragraph 3.5.8
4. Replace compressor
5. Replace compressor
6. Verify capacitor wiring (Refer to wiring diagram)
1. Tighten lead.
2. Replace motor.
3. Check for dirty condenser coil, proper clearance
around unit, remove any obstructions.
4. Check AMP draw
5. Check for obstruction in line.
Check ∆ T.
Replace unit.
5. Remove and clean filters (Refer to paragraphs 3.3.1
& 3.4.1)
2.8CONDENSER AIR NOT ADEQUATE
1. Outside Air Restricted
2. Dirty coil
3. Defective fan motor
1. Check for obstruction at coil. Remedy as required.
2. Clean coil.
3. Replace fan motor.
2.9INSUFFICIENT COOLING
1. Unit undersized
2. Capillary restricted
1. Re--evaluate unit for proper capacity.
2. Check AMP draw.
Check ∆ T.
Replace unit.
2.10 COMPRESSOR FLOODING
1. Unit overcharged
1. Check AMP draw.
Check ∆ T.
Replace unit.
2. Low evaporator airflow
3. Defective electrical connections
2. Clean filter and/or evaporator coil.
3. Check connections per wiring diagram and tighten
any loose connections.
2.11 HEATER CYCLES ON LIMIT SWITCH (HEAT/ COOL VERSION ONLY)
1. Dirty filter
2. Blocked evaporator air inlet (indoor)
3. Low airflow due to fan motor speed
1. Clean or replace filter.
2. Remove blockage.
3. Check fan motor. Repair or replace as necessary.
2.12 AIR SWEEP NOT WORKING (FREE BLOW VERSION ONLY)
1. Ceiling grill not properly aligned
2. Linkage in upper control box stuck
3. Air sweep motor failure
1. Align ceiling grill.
2. Align and lubricate linkage.
3. Replace motor.
2.13 WATER LEAKAGE
1. Water dripping from ceiling unit.1. Verify vehicle is level
Tighten unit mounting bolts evenly or replace unit
gasket.
T--298
2-2
Page 23
SYSTEM AND PROBABLE CAUSE
2.14 INADEQUATE HEAT (FREE--BLOW HEAT ONLY)
1. No heat from heat strip.1. Verify AMP draw . ( 13.8 AMP)
Verify resistance through heating element. (9 OHM)
Check bi--metal switch. If open, replace switch.
2.15 INADEQUATE HEAT (HEAT--PUMP)
NOTE: Allow unit to operate 15 minutes after switch-
ing from cooling mode.
1. Reversing valve not operating
2. Outdoor coil icing.
1. Check for 115 volts at reversing valve coil
Check for reversing valve restriction
Verify compressor operation
2. Check outdoor coil sensor
PROBABLE REMEDY
Clearing Diagnostic Alarms
When a repair has been accomplished due to a corresponding alarm, the alarm must be cleared. This is done by
disconnecting the 12 VDC power to the ducted ceiling assembly for one or two seconds. Once the 12 VDC power is
reconnected, the alarm should have been cleared.
2-3
T--298
Page 24
Table 2--1 System Self--diagnostics Function (Ducted Remote)
Flashes
2
Error Codes
(Priority)
1ROOM AIR THERM-
Error Contents
(Malfunction)
ISTOR FAILURE
32INDOOR COIL
THERMISTOR FAIL-
URE
43OUTDOOR COIL
THERMISTOR
FAILURE
54COMPRESSOR
DRIVE
MALFUNCTION
Display PatternAllowed Modes
FAN Mode
FAN Mode
3sec
.
0.5 sec (3
Times)
0.5 sec.
(Twice)
3sec
.
FURNACE Mode
3sec
.
0.5 sec. (4
Times)
3sec.
FAN Mode
FURNACE Mode
3sec.
0.5 sec. (5
Times)
3sec
.
FAN Mode
FURNACE Mode
65REVERSING VALVE
DRIVE MAL--
FUNCTION
1
6DISCHARGE AIR
THERMISTOR FAIL-
URE
Continuous7THERMISTOR
WIRING WRONG
(only in cooling
test mode)
3sec
.
3sec
.
3sec
.
0.5 sec.
(6Times)
0.5 sec.
(Once)
3sec.3sec
.
0.5 sec. (Continuous)
3sec
.
3sec
.
FAN Mode
FURNACE Mode
FAN Mode
FURNACE Mode
FAN Mode
NOTE:
If more than two errors occur, the highest ranked code is displayed. If the highest ranked error is cleared, the
next highest ranked error code is displayed.
T--298
2-4
Page 25
SECTION 3
SERVICE AND MAINTENANCE
3.1PREVENTA TIVE MAINTENANCE
Cleaning--Clean evaporator coil and condenser coil.
Hold flashlight behind coil to see if all spaces are clear.
Dust accumulation obstructs or reduces airflow and
results in loss of cooling capacity. Both coils may be
vacuumed when dry. Coils may also be brushed with a
stiff brush and then blown out with compressed air.
Thoroughly clean base pan, motors, fan wheels, and
other components.
Clean cover and ceiling grill. Mild detergents reduce
electrostatic charges on plastic sections of the grill and
are good cleaners.
WARNING
Before working on the unit be sure to first
disconnect all electric power to the unit to
avoidthepossibilityofelectricalshockand
personal injury. Before disconnecting, dis-
charge capacitors by shorting across the
capacitors terminals (Refer to paragraph
3.5.8)
WARNING
CAUTION
Do not use carbon tetrachloride, solvents,
or waxes containing solvents to clean plastic sections.
Painting--Paint any parts that show evidence of rust
with a good rust--prevention paint.
Wiring-- Check all wiring for deterioration and all
electrical contacts for tightness or corrosion.
Mounting--Make sure unit is secure on roof according
to installation instructions provided in Owner’s Guide.
Checkfanstoinsurethatthey arecorrectly positionedin
the center of the orifice, and tight on the shaft.
Leaks--Check any connections that show evidence of
oil or leaks. When unit is properly installed (refer to
Owner’sGuide) check gaskets for possible air leakage.
Controls--Check unit to ensure all controls are
functioning correctly and unit operation is normal.
Vibrations can cause unwanted noise.
NOTE
Check to ensure that piping is not vibrating
against side of the unit.
Shield coils with cardboard to protect
hands against injury from sharp metal
edges when removing compressor and other components.
3.3 CEILING UNIT -- FREE BLOW SYSTEMS
3.3.1 Filter Removal
The filters (Figure 3-1) are located in the ceiling grill. To
remove the filters, do the following:
a. Grasp the edge of the filter at recess in the end of the
ceiling grill.
b. Pull filter completely out of the filter slot.
c. Vacuum filter or wash filter in luke--warm water.
Shake off excess water and dry thoroughly.
d. Replace filter by sliding the filter into the filter slot in
the ceiling grill until the filter frame is flush with the in-
terior grill.
Filters
NOTE
For proper cleaning and flushing, use a UL
approvedrefrigerantrecovery/recycling
system.
NOTE
Refrigerant removal must always include
recovering the refrigerant, not allowing it to
escape to the atmosphere.
3.2SERVICE -- GENERAL
General Notes—These Service Instructions are
provided to assist the trained and qualified Carrier
service technician in repairing or replacing components
of the AirV units.
Figure 3-1 Filter Removal -- Free Blow
3.3.2 Ceiling Grill Removal
To remove the ceiling grill (Figure 3-2) do the following:
a. Before working on unit place the master switch in the
OFF position and disconnect all electrical power.
b. Remove 4 screws located on the ceiling grill, making
sure to support the weight of the grill.
c. Lower the ceiling grill from the ceiling panel.
3-1
T--298
Page 26
d. To replace the grill, place the grill up against the ceil-
ingpanelandalignthescrew holes in thegrill with the
ceiling panel.
e. Replace 4 screws.
Mounting
Screws
Figure 3-2 Ceiling Grill -- Free Blow
3.3.3 Ceiling Panel Removal
To remove the ceiling panel (Figure 3-3) do the
following:
a. Remove the ceiling grill. (Refer to paragraph 3.3.2.)
b. Remove 5 screws securing the duct plate to the ceil-
ing panel.
Heat Strip
Connection
Heater Assembly
Option
Figure 3-4 Ceiling Panel With Heat Option
3.3.4 Master Control Switch
To remove the master control switch, do the following:
a. Remove ceiling grill. (Refer to paragraph 3.3.2.)
b. Remove 5 screws that secure the control assembly
(Item 2, Figure 1-3) to the control box cover.
c. Remove the master control switch knob by grabbing
the outside edge of the knob and pulling it off of the
switch stem.
d. Remove 2 screws securing the master control switch
to the control assembly.
e. Carefully disconnect wires from the master control
switch. Label wires to aid in reassembly.
f. Reverse above procedure for reassembly.
c. Remove 4 mounting bolts making sure to support the
weight of the ceiling panel.
d. Disconnect the unit harnesses and main power wires
from the ceiling panel.
e. Lower the ceiling panel from the air conditioning unit.
f. Reverse above procedure for reassembly.
Air Sweep Cam
Serial/Model
Number Tag
Duct Plate &
Mounting Holes
Mounting Bolts
Junction Box
Figure 3-3 Ceiling Panel Assembly
Junction Box
Air Sweep Switch
With Cover
Thermostat
Master Control
Switch
Figure 3-5 Control Box Assembly -- Free Blow
3.3.5 Air Sweep Switch Removal
To remove the air sweep switch, do the following:
a. Remove ceiling grill. (Refer to paragraph 3.3.2.)
b. Remove 5 screws securing the control assembly
(Item 2, Figure 1-3) to the control box cover.
c. Disconnect wires from the air sweep switch.
d. Pinch tabs on either end of the switch and slide out of
lower control box cover.
e. Reverse above procedure for reassembly.
T--298
3-2
Page 27
3.3.6 Indoor Thermostat Removal
To remove the indoor thermostat (Figure 3-6) do the
following:
a. Remove ceiling grille. (Refer to paragraph 3.3.2.)
b. Remove 5 screws securing the control assembly
(item 3, Figure 1-3) to the control box cover.
c. Remove the indoor thermostat knob by grabbing the
outside edge of the knob and pulling it off of the thermostat stem.
d.Remove2screwsthatsecuretheindoorthermostatto
the lower control box cover.
e. Carefully disconnect the 2 wires from the indoorther-
mostat.
f. Remove the sensing bulb from the plastic clip.
g. Carefully slide the sensing bulb through the rubber
grommet.
h. Remove the thermostat from the control assembly.
i. Reverse above procedure for reassembly.
Thermostat
Air Sweep Motor
Figure 3-7 Air sweep motor
3.3.8 Heat Strip Assembly Removal
To remove the heat strip assembly (Figure 3-8) do the
following:
a. Remove ceiling grille. (Refer to paragraph 3.3.2.)
b. Unplug electrical connection at air sweep motor as-
sembly.
c. Remove two screws securing heat strip assembly to
the ceiling panel assembly.
d. Slide heat strip assembly away from air sweep motor
assembly and pull down, easing the the electrical
connection through the access hole.
e. Reverse the procedures for reassembly.
Sensing Bulb
Figure 3-6 Indoor Thermostat
3.3.7 Air Sweep Removal
To remove the air sweep, do the following:
a. Remove ceiling grille. (Refer to paragraph 3.3.2.)
b. Remove cam (See Figure 3-3) from air sweep motor
shaft.
c. Remove 4 screws securing air sweep motor bracket
to the ceiling panel assembly.
d. Carefully disconnect air sweep motor wire termina-
tions.
e. Remove 2 screws securing air sweep motor
(Figure 3-7) to control box and remove motor.
f. Reverse above procedure for reassembly.
Heat Strip
Figure 3-8 Heat Strip Assembly
3-3
T--298
Page 28
3.4CEILING UNIT -- DUCTED SYSTEMS
3.4.1 Filter Removal
The filters (Figure 3-9) are located in the ceiling grill. To
remove the filters, do the following:
a. Grasp the edge of the filter at recess in the end of the
ceiling grill.
b. Pull filter completely out of the filter slot.
c. Vacuum filter or wash filter in luke--warm water.
Shake off excess water and dry thoroughly.
d. Replace filter by sliding the filter into the filter slot in
the ceiling grill until the filter frame is flush with the in-
terior grill.
c. Remove two screws securing control box cover to
control box assembly. See Figure 3-11.
d. Remove control box assembly cover.
Mounting Screws
Filters
Operation Indicators
Figure 3-9 Filter Removal -- Ducted Unit
3.4.2 Ceiling Grill Removal
Toremovetheceilinggrill(Figure3--10)dothefollowing:
a. Before working on unit place the master switch in the
OFF position and disconnect all electrical power.
b. Remove filters (Refer to paragraph 3.4.1).
c. Remove 4 screws located on the ceilinggrill, (two are
underthefilters) making sure to support the weightof
the grill.
d. Lower the ceiling grill from the ceiling panel.
e. To replace the grill, place the grill up against the ceil-
ingpanelandalignthescrew holes in thegrill with the
ceiling panel.
f. Replace 4 screws and 2 filters.
3.4.3 Control Box Assembly Removal
To remove the control box assembly (Figure 3-11 &
Figure 3-12) do the following:
a. Remove ceiling grill. Refer to paragraph 3.4.2.
b. Disconnect 115 volt (AC) and 12 volt (DC) power
wires.
Figure 3-10 Ceiling Grill -- Ducted
e. Disconnect blue furnace wires.
f. Unplug two connectors from upper unit.
g. Unplug DC power plug #1 (red/yellow/black wires)
SeeFigure3-12
h. Unplug relay signal plug #2 (brown/red/orange/
yellow wires). See Figure 3-12
i. While supporting control box assembly remove two
screws securing control box assembly to ducted ceil-
ing unit.
j. Pull controlboxassemblyfromtheductedceilingunit.
k. Reverse above procedure to reassemble.
Control Box
Control Box
Cover Screws
Fuse
PCB Cover
PCB Cover
Screws
Figure 3-11 Control Box & PCB Cover
T--298
3-4
Page 29
1 15V AC
3.4.5 PCB Display Removal
To remove the PCB display assembly (Figure 3-13) do
the following.
12V DC
a. Remove ceiling grill. Refer to paragraph 3.4.2.
b. Push large clip away from PCB display assembly.
Fuse
Upper Unit
Connectors
Figure 3-12 Control Box Assembly -- Ducted
3.4.4 Main PCB Board Removal
To remove the Main PCB board (Figure 3-13) do the
following:
a. Remove ceiling grill. Refer to paragraph 3.4.2.
b. Remove three screws securing the PCB cover to the
ducted ceiling unit.
c. Carefully turn over the PCB cover exposing the PCB
main and the PCB display assemblies.
d. Gentlypushholdingclipaway from PCB mainassem-
bly.
e. Lift PCB main assembly from PCB cover assembly.
f. Unplug display wiring plug #4. Figure 3-13
#2
#1
Furnace
Wires (blue)
c. Push center clip towards large clip.
d. Pull PCB display assembly from PCB cover.
e. Unplug display wiring from PCB main assembly.
f. Reverse above procedures of reassembly.
3.4.6 Fuse Removal
To remove the fuse (Figure 3-11) do the following:
a. Remove ceiling grill. Refer to paragraph 3.4.2.
b. Turnfuseholderindirectionofarrow(counter--clock--
wise).
c. Pull fuse from fuse holder.
d. Test and/or replace.
e. Reverse above procedures for reassembly.
3.5SERVICE -- UPPER UNIT -- STANDARD,
HC&HP
3.5.1 Exterior Cover Removal
CAUTION
g. Unplugthermistor/thermostatwiringplug#3.
Figure 3-13
h. Unplug power wiring plug #1. Figure 3-12
i. Unplug signal wiring plug #2. Figure 3-12
j. Reverse above procedures for reassembly.
Holding Clips
PCB Display
PCB Main
#4
Coil fins are sharp. Usecarewhenremoving
the cover form the base pan to avoid personal injury.
To remove the exterior cover, do the following:
a. Before working on unit place the master switch in the
OFF position and disconnect all electrical power.
b. Remove 15 screws securing the unit cover to the
base pan assembly. See Figure 3-14.
c. Carefully lift the exterior cover off of theunit base pan
assembly.
d. Reverse above procedure for reassembly.
#3
Figure 3-13 Main/Display PCB’s
3-5
Cover Screws
Figure 3-14 Cover Assembly -- Standard
T--298
Page 30
3.5.2 Compressor Replacement
Observe the same procedures for rotary compressors
as for reciprocating compressors.
a. Follow all safety codes. Reminder: use protective
goggles, work gloves, and water soaked quenching
cloth.
b. Remove exterior cover.refer toparagraph 3.5.1.Dis-
connect all wiring from the compressor.
c. Apply field--supplied, line--tap--valves to the suction
and discharge lines as close to the compressor as
possible.
d. Recover therefrigerant charge from the unit. Afterre-
covering,cut the discharge and suction line process
tubes below the tube crimps. If you choose a good
tubing location for cutting the refrigeration lines initially, the location is easily accessible when making
the final joints.
WARNING
Oil vapor in piping stubs can ignite from
torch flame and cause serious injury. Exercise extreme care when brazing, and keep
brazing cloth and fire extinguisher handy
for emergency use.
Control Box
Screws
Figure 3-15 Control Box
Water
Cover
e. Connectanitrogen supply to theunitatoneoftheline
--tap--valve connectors (5--psig maximum flow), leaving the other connector open to the atmosphere.
Braze angle valves with stubs to each process tube.
f. Remove compressor from unit (3 bolts).
g. Remove line--tap--valves from suction and discharge
lines.Carefullybrazetheholesclosedfromwherethe
line--tap--valves were removed.
h. Cleansystem:addorreplaceliquidlinefilter drier.For
proper cleaning and flushing use a UL approved re-
frigerant recycling system.
i. Install new compressor and braze into place with
field--supplied copper slip couplings.
j.Connect wiring: replace wire terminals if necessary.
k. Proceed with evacuation and charging (15.9 OZ. --
.45 KG R22). Pinch off lines where angle valves were
added. Cut off angle valves above pinch--off , and
braze tubes.
l. Start up unit.
3.5.3 Control Box Assembly Removal
To remove the control box assembly, do the following:
a. Removeexterior cover assembly.Refertoparagraph
3.5.1.
b. Remove 2 screws securing control box assembly to
the lower scroll assembly. (SeeFigure 3-15.)
Figure 3-16 Control Box Removal
c. Slide control box out of the lower scroll assembly.
(See Figure 3-16.)
d. To open control box remove 2 screws securing the
water cover to the control box cover.
e. Gently lift the water cover off of the control box. (See
Figure 3-17.)
f. Reverse above procedure for reassembly.
Control Box
Cover
Figure 3-17 Water Cover Removal
T--298
3-6
Page 31
3.5.4 Upper Scroll Assembly Removal
a. Removeexterior cover assembly.Refertoparagraph
3.5.1.
b. Remove 4 screws securing upper scroll assembly to
the lower scroll assembly. (See Figure 3-18)
c. Gently pry 4 snap clips open and lift the upper scroll
assembly off of the lower scroll assembly.
d. Reverse above procedure for reassembly.
Screws
4 Places
i. Remove condenser fan from motor shaft and lift fan
out through the top of the condenser orifice. (See
Figure 3-22)
j. Remove motor assembly.
k.Reverse above procedure for reassembly.
Ground screw
Motor Ground
Lead
Figure 3-19 Motor Assembly
Snap Clip
4 Places
Figure 3-18 Upper Scroll Assembly
3.5.5 Motor Assembly and Condenser Fan
Removal
a. Removeexterior cover assembly.Refertoparagraph
3.5.1.
b. Remove control box assembly. Refer to paragraph
3.5.3.
c. Remove upper scroll assembly. Refer to paragraph
3.5.4.
d. Remove 4 screws securing the condenser cover to
the condenser orifice. (See Figure 3-24.)
e. Carefully disconnect motor wire terminations from
within the control box.
f. Remove 1 screw securing the motor ground lead to
the motor bracket assembly. (See Figure 3-19)
g. Using flat--nosed pliers, depress the motor spring
clamp and slide it off of the condenser fan (See
Figure 3-20).
h. Liftandslidemotortowardsevaporatorcoiltoremove
condenser fan from the motor shaft.
Spring Clamp
Figure 3-20 Spring Clamp Removal
Motor Clip
Figure 3-21 Motor Clip Removal
3-7
T--298
Page 32
Condenser Fan
3.5.7 Air Handling System Removal
a. Removeexterior cover assembly.Refertoparagraph
3.5.1.
b. Remove control box assembly. Refer to paragraph
3.5.3.
c. Remove upper scroll assembly. Refer to paragraph
3.5.4.
d. Remove motor assembly. Refer to paragraph 3.5.5.
e. Remove 8 screws securing lower scroll assembly to
the base pan assembly.
f. Remove 1 screw from clamp securing suction tubeto
the base pan assembly.
g. Remove 3 nuts securing the compressor to the base
pan assembly.
h. Remove 2 screws securing the condenser orifice to
the base pan assembly.
Figure 3-22 Condenser Fan Removal
3.5.6 Evaporator Blower Wheel Adjustment or
Removal
a. Remove exterior cover assembly. Refer to Exterior
Cover Assembly Removal instructions 3.5.1
b. Remove control box assembly. Refer to Control Box
Assembly Removal instructions 3.5.3
c. Remove upper scrollassembly.Refer to Upper Scroll
Assembly Removal instructions 3.5.4
d. Loosen motor assembly. Refer to Motor Assembly
Removal instructions 3.5.5.
e. Mark shaft at a point where wheel hub and motor
shaft meet to aid in reassembly.(See Figure 3-23.)
f. Remove 1 set screw holding the blower wheel to the
motor shaft. (See Figure 3-23)
g. Slide off blower wheel from motor shaft
h. Reverse above procedure for reassembly.
Set Screw
i. Remove 2 screws securing the condenser coil as-
sembly to the base pan assembly.
j. Carefully lift the entire assembly off of the base pan
assembly.
k. Reverse the above procedure for reassembly,ensur-
ing that the air handling system is positioned correctly. Tighten all screws.
Compressor
Condenser Cover
Condenser
Cover Screws
Motor Assembly
T--298
Figure 3-23 Blower Wheel
Base Pan
Base Pan
Figure 3-24 Condenser With Motor Assembly &
Compressor
3-8
Page 33
3.5.8 Capacitor Troubleshooting
WARNING
WARNING
Disconnect power to the AirV unit before
checking the capacitor.
To test capacitor to determine if good, open or shorted,
an ohm meter can be used. Todetermine a capacitor’s
capacitance, a capacitor meter is required.
Capacitors showing signs of leaks or bulging should be
replaced immediately.
3.5.9 Capacitor Testing and Replacement
Capacitors must be discharged properly before testing.
a. Place a 20,000 ohm, 2 watt resistor across the termi-
nals of the capacitor for approximately 30 seconds
(See Figure 3-25 for a suggested tool).
INSULATED SCREWDRIVER
Do not touch the metal of the screwdriver
when discharging the capacitor. You could
receive a shock.
b. After the capacitor has been dischargedand all wires
removed from the capacitor terminals, use an ohm-meter to test its resistance.
c. Set the scale to R x 1K or 10K ohm and place the
ohmmeter leads across the capacitor terminals.
d. Iftheohmmeterfirst reads 0, then rises towardinfinity
or some higher resistance, the capacitor is good.
e. If the ohmmeter goes to 0 or a low resistance and
stays there, the capacitor is shorted and needs to be
replaced.
f. If the ohmmeter reads infinity (OL) the capacitor is
open and needs to be replaced.
20,000 -- OHM
2 -- WATTRESISTOR
CLIP TO
SCREWDRIVER
Figure 3-25 Set--Up For Discharging a Capacitor
3.5.10 Positive Temperature Coefficient Thermister
(PTC) (Start Thermistor) Troubleshooting
a. Disconnect power from the AirV unit.
b. Disconnect the wires to the PTC.
c. Using an ohm meter, check for continuity across the
PTC.
If the PTC does not havecontinuity, it must bereplaced.
If continuity exists, reconnect the wires to the PTC.
d. Reconnect power to the AirV unit.
e. Turn on the AirV unit to start.
f. Use a clamp--on amp probe to monitor the amp draw
of the compressor during its start--up.
ATTACH TO CLEAN UNPAINTED
METAL PART OF UNIT FRAME
TOUCH TO CAPACITOR TERMINALS
TO DISCHARGE CAPACITOR
When the compressor starts, an amp draw will be
indicated for almost a second.
If no amp draw is indicated or if the amp draw occurs for
much longer than a second, the PTC is defective and
must be replaced.
3.5.11 Line Voltage -- 10%
Line voltage should be checked during peak electrical
load periods.
With the AirV unit onandthecompressoroperating,use
a voltmeter to check the voltage being supplied to the
AirV unit. The voltage must be within 10% of the units
required voltage. A voltage drop greater than 10% will
cause a premature compressor failure and needs to be
corrected immediately.
3-9
T--298
Page 34
3.6 SERVICE -- UPPER UNIT -- LOW PROFILE
3.6.1 Exterior Cover Removal
CAUTION
b.b.
Coil fins are sharp. Usecarewhenremoving
the cover form the base pan to avoid personal injury.
To remove the exterior cover, do the following:
a. Before working on unit place the master switch in the
OFF position and disconnect all electrical power.
b. Remove (8) screws securing the unit cover to the
base pan assembly. See Figure 3-26.
c. Carefully lift the exterior cover off of theunit base pan
assembly.
d. Reverse above procedure for reassembly.
Screws
Screws
b.
b.
c.
b.
Figure 3-27 Upper Scroll Assembly
Locking Tabs (b.) & Screw Locations (c.)
b.
Figure 3-26 Cover Assembly -- Low Profile
3.6.2 Upper Scroll Assembly Removal
To remove the upper scroll assembly, do the following:
a. Removeexterior cover assembly.Refertoparagraph
3.6.1.
b. Releasethe(2)front,(2)rear,(1) left sideand(1)right
sidelockingtabs(SeeFigure 3-27) bypullingbackon
the tabs (See Figure 3-28).
c. Remove the screw (1) from the control box cover
(See Figure 3-27).
d. With all (6) locking tabs released and control box
screw removed, lift the upper scroll assembly off of
the lower scroll assembly.
e. Reverse above procedure for reassembly.Ensure all
(6) locking tabs snap shut & lock.
Figure 3-28 Upper Scroll Assembly
Keeper Tab Release
T--298
3-10
Page 35
Evaporator Coil
Condenser Coil
Retaining
Ring
Figure 3-30 Condenser Fan Assembly
& Retaining Ring
Fan Stop
Figure 3-29 Upper Scroll & Control Box
Cover Removed
3.6.3 Condenser Fan Assembly Removal
To remove condenser fan assembly, do the following:
a. Perform steps outlined in Section 3.6.2.
b. DepressandremoveRetainingRing(See
Figure 3-30).
c. Using both hands, carefully pull up on fan assembly
until it is free of the motor shaft.
d. When replacing the fan assembly make sure the fan
assembly is against the stop on the shaft (See
Figure 3-31)
13MM
Bolt
Condenser Motor
Grommet
Figure 3-31 Condenser Fan Motor
& Fan Assembly Stop
Tab
13MM
Bolt
e. Push back on tab to allow fan assembly to rest
against stop (See Figure 3-32). Fan assembly will
now be flush with the end of the motor shaft.
f. Reverse above procedure for reassembly.
3-11
Figure 3-32 Condenser Fan Motor
& Fan Assembly Tab
T--298
Page 36
3.6.4 Condenser Motor Removal
To remove condenser fan motor, do the following:
a. Perform steps outlined in Section 3.6.2.
b. Remove (3) 13MM bolts (See Figure 3-31).
c. Remove (3) Grommets. Inspect, replace or reuse.
d. Cut Tie--Wraps & discard (2 locations). When re-
assembling, tie--wrap at same 2 locations.
e. Remove ground wire from compressor bracket (See
Figure 3-33).
f. Un--plug (yellow/brown/white) from control box as-
sembly.
g. Reverse above procedure for reassembly.
Cond. Motor
Ground Screw
Blower Side Locking T abs
Outside Locking T abs
Comp. Mounting Bolt
Figure 3-33 Condenser Motor Ground
3.6.5 Evaporator Motor/Blower Assembly
Removal
To remove the evaporator motor, do the following:
a. Perform steps outlined in Section 3.6.2.
b. Pull back on and release the (4) locking tabs. There
are 2 on each side of the control box assembly. (See
Figure 3-34).
c. Lift control box assembly from lower scroll assembly,
exposing evaporator motor.
d. Un--plug (black/blue/white/brown) evaporator motor
from control box assembly.
e. Remove ground wire (green/yellow) from motor
housing.
f. Lift motor/blower assembly from lower scroll assem-
bly cradle.
g. Carefully remove the blower wheelfrom theevapora-
tor motor shaft by pushing out from the motor side.
Figure 3-34 Evaporator Motor Locking Tabs
Lower Scroll
Assembly
Capacitor
Cradle
Figure 3-35 Evaporator Motor/Blower Assembly
In Cradle
T--298
3-12
Page 37
NOTE
When reassembling the blower wheel on to
the motor shaft ensure that the blower
wheel is flush with the end of the motor
shaft (SeeFigure 3-36).
h. Reverse above procedure for reassembly.
NOTE
When placing the evaporator motor/blower
assembly back into the lower scroll assembly cradle, make sure that the assembly is
seated securely in the cradle.
(See Figure 3-35).
3.6.6 Compressor Replacement
Perform the procedures outlined in Section 3.5.2
There are 4 bolts with the Low Profile Compressor.
The system charge for the Low Profile unit is 16.9 OZ.
3.6.7 Capacitor Removal
To remove the capacitor, do the following:
Wheel Flush With Motor Shaft
Figure 3-36 Evaporator Blower Wheel
(Flush With End Of Motor Shaft)
Upper Scroll Assembly
a. Perform steps a., b. & c. as outlined in Section 3.6.5.
b. Perform steps outlined in Sections 3.5.8 & 3.5.9.
c. The Low Profile Capacitor is removed from the con-
trol box assembly by pushing on the capacitor from
under the control box assembly (See Figure 3-35).
Control Box Assembly
Capacitor
Terminal Block
Figure 3-37 Control Box Assembly With Capacitor
3.6.8 Remote Control (Fahrenheit to Celsius)
All Remote Control Assemblies in the United States are
pre--setto display inFahrenheit degrees (see
Figure 3-38). To change from a Fahrenheit display to a
Celsius display do the following:
3-13
CAUTION
The change from Fahrenheit to Celsiuswill
bepermanent.Itcannotbechangedbackto
Fahrenheit.
T--298
Page 38
a. Remove the batteries from the remote control.
b. Carefully remove the remotecover by insertinganar-
row flat object between the cover and remote body
and prying apart.
c. Remove the brass screw holding the PCB in place.
d. Carefully remove the PCB board from the remote
body, making sure the battery springs release from
their holders.
e. Locate FR9 on the PCB board (see Figure 3-39).
f. Carefully cut the FR9 jumper wire.
g. Reverse above procedure for reassembly.
CAUTION
When re--assembling, ensure the battery
springs are correctly placed in the battery
spring holders.
BATTERIES
&
COVER
Battery Springs
PCB
COVER
Figure 3-38 Remote Control Components
Spring Holders
BODY
T--298
PCB
FR9
Figure 3-39 Remote Control PCB (FR9 Location)
3-14
Page 39
3.7THERMOSTAT INSTALLATION AND START-UP INSTRUCTIONS (WALL MOUNTED)
3.7.1 Introduction
The thermostat is a wall mounted, low--voltage
thermostat which maintains room temperature by
controlling the operation ofa heating and air
conditioning system. Batteries are not required;
temperature and mode settings are preserved with the
power off.
2.Disconnect wires from existing thermostat, one at
a time. Be careful not to allow wires to fall back into
the wall.
3.As each wire is disconnected, record wire color
and terminal marking.
4.Discard or recycle old thermostat.
NOTE
Mercuryisahazardouswasteandmustbedesposed of properly.
CAUTION
Improperwiring orinstallationmaydamage
thermostat. Wiring must conform to local
and national electrical codes.
WARNING
Before installing thermostat, turn off all
power to unit. There may be more than one
power disconnect. Electrical shock can
cause personal injury or death.
The thermostat requires no batteries. The thermostat is not a power stealing device and
MUST have both R and C connected.
c. Seperate the front and back pieces of plastic.
d. Route thermostat wires through hole in back piece of
plastic. Level plastic against wall (for aesthetic value
only -- thermostat need not be leveled for proper operation) and mark wall through 2 mounting holes.
e. Drill two 3/16 inch mounting holes in wall where
marked.
NOTE
Mounting holes on thermostat are designed to
fit on a horizontal J--Box.
g. Connect wires to proper terminal of the connector
block in the front piece of plastic.
h. Pusr any excess wire back into wall. Excess wire in-
side the thermostat plastic case can interfere with
proper air flow across the temperature sensor. Seal
hole in wall to prevent air leaks. Leaks can effect op-
eration.
i. Snap front and back pieces of plastic together.
j. Turn on power to the unit.
3.8LCD DISPLAY
3.7.3 Thermostat Location
The thermostat should be mounted:
Approximately 5 foot (1.5m) from the floor.
Close to or in a frequently used room, preferably on
an inside partitioning wall.
On a section of wall without pipes or duct work.
The thermostat should NOT be mounted:
Closetoawindow,oranoutsidewall,ornexttoadoor
leading to the outside.
Exposedtodirectlightandheatfromalamp,sun,fireplace, or other temperature--radiating object which
may cause a false reading.
Close to or in direct airflow from supply registers and
return--air grilles.
In areas with poor air circulation, such as behind a
door or in an alcove.
3.7.4 Install Thermostat -- 12VDC
a. Turn off all power to unit.
b. If an existing thermostat is being replaced:
1.Remove existing thermostat from wall.
3.8.1 Cool Only Thermostat (Part No. 11 10--421)
On power up, the LCD readout will display C (Cool
Only).
3.8.2 Heat/Cool Thermostat (Part No. 1110--420)
On power up, the LCD readout will display HC (Heat/
Cool).
3.9 SET THERMOSTAT CONFIGURATION
While in configuration mode, three option choices can be
made.
A -- Anticipator Value Adjustment
d -- Display Temperature Fahrenheit/Celcius Selection
oF -- Offset Adjustment For Room Temperature
3.9.1 Enter Configuration Mode
EnterandholdtheFANbuttonforapproximately 10 secondsuntilroom temperaturedisappears and the display
reads A. You are now in the configuration mode.
3-15
T--298
Page 40
NOTE
IftheFANbuttonispressedagainorif nobutton
is pressed for two minutes, the thermostat will
exit the configuration mode and return to normal operation. To re--enter the configuration
mode, the FAN button must be pressed and
held for 10 seconds again.
While in the configuration mode, the following options
are available:
A. ANTICIPATOR -- Value Adjustment
Thisadjustmentcontrolsthesensitivityandcyclerate of
thethermostst.Highernumbersdecreasethe
sensitivity and slow the cycle rate. Lower numbers
increase the sensitivity and increase the cycle rate.
However, a limiting feature will not allow more than 4
equipmentcyclesperhour,regardlessofsetting.Values
can range from 1 to 3. Factory default setting is 2. This
default selection will provide optimum performance in
nearlyallinstallations.Tryitfirst. Donotchangesettings
unless there is evidence of need to do so. Unlike
conventional anticipators, this setting is not determined
by current draw. There is no need to measure, know,or
compensate for current.
To Adjust:
a. Enter configuration mode (if not already there).
b. Use UP & DOWN buttons to display A.
c.Press MODE button once to display current value.
d. Use UP & DOWN buttons to move betweenvalues.
e. Press MODE buttonto return to A.UP &DOWN
buttons now move between option choices A, d, oF or
press FAN button to exit configuration mode.
d. Fahrenheit/Celsius Selection
This selection operates the thermostat in either
Fahrenheit or Celsius.
To Select:
a. Enter configuration mode (if not already there).
b. Use UP & DOWN buttons to display d.
c.Press MODE button once to display current
selection of F or C.
d. Use UP &DOWNbuttonstochangebetweenF&C.
e. Press MODE buttonto return to d.UP &DOWN
buttons now move between option choices; or press
FAN button to exit configuration mode.
oF. Room Temperature Offset Adjust Selection
The selected number is the number of degrees, plus or
minus, which will be added to the actual temperature.
The numbers can range between --5 and +5. Factory
default is 0. This adjusted value will be used as actual
temperature for both display and control action. The
effect is that a positive number selection will make the
room temperaturelower, andvice versa.The
thermostat is calibrated within an accuracy of plus or
minus 2 degrees when shipped from the factory; this
adjustment will provide thebestaccuracy whenset to o.
To Select:
a. Enter configuration mode (if not already there).
b. Use UP & DOWN buttons to display oF .
c.Press MODE button once to display offset value.
d. Use UP & DOWN buttons toselect a value between
--5 and 5.
e. Press MODE buttonto return to oF.UP &DOWN
buttons now move between option choices; or press
FAN button to exit configuration mode.
3.10 CHECK THERMOSTAT OPERATION
3.10.1 Fan Operation (Cool Only)
1. Press FAN button, starting fan operation. FAN annunciator turns on; Lo is displayed in the room temperature area for 5 seconds indicating Fan Low
Speed.
2. Press FAN button, FAN annunciator remains on; Hi
is displayed in room temperature area for 5 seconds
indicating Fan High Speed.
3. Press FAN button, stopping fan operation. FAN annunciator turns off.
3.10.2 Fan Operation (Heat/Cool)
1. Press FAN button, starting low fan (Lo) operation.
FAN annunciator turns on.
2. Press FAN button, starting high fan (Hi) operation.
FAN annunciator remains on.
3. Press FAN button, stopping fan operation. FAN annunciator turns off.
3.10.3 Cooling Operation (Cool Only)
1. Press and release MODE button until COOL is displayed.
2. Press DOWN button until LCD readout reads 10degrees below room temperature. Cooling and High
Fan system should begin to operate within 5 minutes.
3.10.4 Cooling Operation (Heat/Cool)
1. Press and release MODE button until COOL is displayed.
2. Press DOWN button until LCD readout reads 10degrees below room temperature. Cooling and High
Fan system should begin to operate within 5 minutes.
3.10.5 Heating Operation (Heat/Cool)
1. Press and release MODE button until HEAT is displayed.
2. PressUPbuttonuntilLCDreadoutreads10degrees
above room temperature. Heating system should
begin to operate within 1 minute.
3.11 CHECK THERMOSTAT OPERATION
3.11.1 Temperature Display
The thermostat will display room temperature until the
UPorDOWN buttonispressed. The word SETappears
when these buttons are pressed and the current set
point is displayed. If no buttons are pressed for 5
seconds, the display will change back to show room
temperature.
T--298
3-16
Page 41
3.11.2 Timeguard Timer
A 3--minute timeguard is built into the thermostat
immediately upon power up, and any time the
compressor (output “Y”) turns off. The compressor will
notturn on until the timeguardhasexpired. Pressing UP
and FAN buttons simultaneously will override the
timeguard for 1 cycle.
3.11.3 Cycle Timer
Innormal cooling(and heating)operation the
thermostat will not allow more than 4 equipment cycles
per hour (or 1 cycle every 15 minutes). Both the “Y”
(cooling) and “W” (heating) outputs have a 15--minute
timer that starts counting down when the output is
turned on, (e.g., if “Y” output is turned on for 9 minutes
and then satisfies, it cannout turn back on for another 6
minutes regardless of demand). However, pressing UP
and F AN buttons simultaneously or changing the set
point will override the timer for 1 cycle.
3.11.4 Minimum On Timer
Oncetheequipmenthasturnedon,itwillremainonfora
minimum of 2 minutes regardless of demand. However,
the equipment can turn off in less than 2 minutes if a
change in set point, or a changein mode occurs.
3.11.5 Error Messages
E4 will be displayed if the thermostat has an internal
memory failure. If E4 appears, replace the thermostat.
---- (two dashes) will be displayed if the thermostat
cannot properly read the room temperature. If ---appears, replace the thermostat.
UPPER UNIT
MotorComp.
12342
1234
POWERBOX
ASSEMBLY
Factory WiringField Wiring
1
115V AC High V oltage
J
Power Supply
L
N2
N1
THERMOSTAT
1
2
3
4
5
W
Y
GH
GL
C
COOL (Compressor)
Y
FAN (High)
GH
GL
FAN (Low)
R
12VDC LowVoltage
Power Supply
C
CEILING UNIT
Figure 3-40 Wall Thermostat Wiring Diagram -- Cool Only Model
3-17
T--298
Page 42
UPPER UNIT
MotorComp.
123421
Factory WiringField Wiring
1234
POWERBOX
ASSEMBLY
J
115V AC High V oltage
Power Supply
L
N2
N1
THERMOSTAT
1
2
3
4
5
Blue
1
Blue
2
W
Y
GH
GL
C
TB
COOL (Compressor)
Y
FAN (High)
GH
GL
FAN (Low)
R
C
+ 12VDC
12VDC LowVoltage
Power Supply
12 VDC (Gnd)
T--298
CEILING UNIT
FURNACE
Figure 3-41 Wall Thermostat Wiring Diagram -- Heat/Cool Model
3-18
Page 43
SECTION 4
WIRING SCHEMATICS
4.1INTRODUCTION
This Section contains wiring schematics for the AirV units.
Figure 4--1 is the schematic for the standard upper unit assembly and it is applicable to all standard units.
Figure 4--2 is the schematic for the Low Profile upper unit assembly.
Figure 4--3 is the schematic for a free blow ceiling unit without heat while Figure 4--4 is a free blow unit with heat.
Figure 4--5 is for a ducted unit with microprocessor control.
Figure 4--6 is for an Upper Unit Heat Pump with free blowapplication and Figure 4--7 is the matching free blowceiling
unit.
Figure 4--8 is for the Upper Unit Heat Pump ducted application and Figure 4--9 is the matching ducted ceiling unit.
Notethat the ductedunits have 115VACpowerforthecomponents and 12 VDC power for themicroprocessorcontrol
system.
Figure 4--10is for the ductedorfreeblowapplicationthatusesawall--mounted thermostat, with or without thefurnace
option.
Where applicable, diagrams that designate 115Volt, 60 H, 1 Phase, arealsoavailableusing220Volts,50H,1Phase.
Most noteably Figure 4--1 and Figure 4--5.
4P
11
22
PLUG CONNECTS
TO CEILINGUNIT
SEE FIG> 4--3
OR 4--4
For proper wiring of Wall Mounted Thermostats as an accessory, refer to Figure 3-40 (Wall Thermostat Wiring
Diagram -- Cool Only Model) or Figure 3-41 (Wall Thermostat Wiring Diagram -- Heat/Cool Model).
4-5
T--298
Page 48
INDEX
A
Air Handling System , 3-8
Air Sweep Removal, 3-3
Air Sweep Switch , 3-2
C
Capacitor Testing, 3-9
Capacitor Testing and Replacement, 3-9
Ceiling Grill -- Ducted, 3-4
Ceiling Grill -- Free Blow, 3-1
Ceiling Panel -- Free Blow, 3-2
CEILING UNIT -- DUCTED SYSTEMS, 3-4
CEILING UNIT -- FREE BLOW , 3-1
Cleaning, 3-1
Compressor , 3-6, 3-13
Condenser Fan, 3-7
Control Box -- Ducted, 3-4
Control Box -- Upper Unit, 3-6
I
Indoor Thermostat , 3-3
INTRODUCTION, 1-1, 4-1
L
LCD DISPLAY, 3-15, 3-16
Leaks, 3-1
M
Main Pcb Board, 3-5
Master Control Switch, 3-2
Motor , 3-7
Mounting, 3-1