Carrier T-298 User Manual

Page 1
2P
1
2
BLK
BLU
Transport Air Conditioning
Transport Air Conditioning
R
R
BRN
WHT
GRN/YEL
WHT
F
EVAP.
RED
WHT
YEL
2
1
C
RED
R
BLU
S
BLU
PTC
SERVICE MANUAL
for
Rooftop Air Conditioning Systems
T--298 Rev D
MODEL AirV
Page 2
SERVICE MANUAL
For
AirV
AIR CONDITIONING AND
HEATING EQUIPMENT
MODELS
68RV11302A 68RV14102A 68RV14103A
68RV14112A 68RV15102A 68RV15103A
Page 3
SAFETY SUMMARY
GENERAL SAFETY NOTICES
The following general safety notices supplement the specific warnings and cautionsappearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and maintenanceoftheequipmentcoveredherein.Thegeneralsafety notices arepresentedinthefollowingthree sections labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warnings and cautions appearing elsewhere in the manual follows the general safety notices.
FIRST AID
An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately.
OPERATING PRECAUTIONS
Always wear safety glasses. Keep hands clear of the evaporator blower and condenser fan. No work should be performed on the unit until all circuit breakers and start--stop switches are turned off, and
power supply is disconnected. Always work in pairs. Never work alone. In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator blower & condenser fan. Do not remove the ceiling grill assembly or the upper unit coverassembly beforeturningthe power off, and disconnecting the power supply. Before disconnecting, discharge capacitors by shorting across the capacitors terminals. (See Paragraph
3.5.8) When disassembling wiring, use numbered stickers to identify wire leads and terminals. This aids in quick,
accurate reassembly. Besurepoweristurnedoffbeforeworkingonmotors,controllers, or electricalcontrolswitches.Taganycircuit
breakers and power supply to prevent accidental energizing of circuits. Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires.
Problems with the system should be diagnosed and any necessary repairs must be performed by qualified service personnel.
In case of electrical fire, open circuit switch and extinguish with CO Usedrynitrogentopressurizethesystemforleakchecking. Be careful not to exceed150psigtestpressurein
the hermetic compressor. Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury. Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when
brazing, and keep brazing cloth and fire extinguisher handy for emergency use. Disconnect power to the AirV unit before checking the capacitor.
(never use water).
2
Safety-- i
T-298
Page 4
SPECIFIC WARNING AND CAUTION STATEMENTS
The statements listed below are applicable to the refrigeration unit and appear elsewhere in this manual. These recommended precautions must be understood and applied during operation and maintenance of the equipment covered herein.
SPECIFIC WARNINGS AND CAUTIONS
WARNING
Be sure to observe warnings listed in the safetysummary in the front of this manualbefore performing maintenance on the AirV system
WARNING
Beforeworkingonthe unitbesuretofirstdisconnectall electricpowertotheunitto avoidthe possibilityof electrical shock and personalinjury. Before disconnecting, discharge capaci- tors by shorting across the capacitors terminals (Refer to paragraph 3.5.8)
WARNING
Shieldcoilswithcardboard to protecthandsagainstinjuryfromsharpmetaledgeswhen re­moving compressor and other components.
WARNING
Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise ex­treme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency use.
WARNING
Disconnect power to the AirV unit before checking the capacitor.
WARNING
Do not touch the metal of the screwdriver when discharging the capacitor.Y oucould receive a shock.
WARNING
Before installing thermostat, turn off all power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
CAUTION
Do not use carbon tetrachloride, solvents, or waxes containing solvents to clean plastic sec­tions.
T--298
Safety-- ii
Page 5
CAUTION
Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury.
CAUTION
ThechangefromFahrenheittoCelsiuswill bepermanent.Itcannotbechangedbackto Fahr­enheit.
CAUTION
When re--assembling, ensure the battery springs are correctly placed in the battery spring holders.
CAUTION
Improper wiring or installation may damage thermostat. Wiring must conform to local and national electrical codes.
Safety--iii
T-298
Page 6
TABLE OF CONTENTS
PARAGRAPH NUMBER Page
DESCRIPTION 1-1...............................................................................
1.1 INTRODUCTION 1-1.....................................................................
1.2 SERIAL NUMBER IDENTIFICATION 1-1....................................................
1.3 DESIGN CHANGE DESCRIPTIONS 1-1....................................................
1.4 AirV SYSTEM COMPONENT SPECIFICATIONS 1-9.........................................
1.4.1 Refrigerant Charge 1-9................................................................
1.4.2 Compressor - 115 Volts, 60 Cycles, 1 Phase 1-9..........................................
1.4.3 Compressor - 220 Volts, 50 Cycles, 1 Phase 1-9..........................................
1.4.4 Thermostat Range (All Free Blow Units) 1-9..............................................
1.5 START-UP 1-9...........................................................................
1.6 REFRIGERANT CYCLE-STANDARD SYSTEM 1-9...........................................
1.7 REFRIGERANT CYCLE - HEAT PUMP 1-10..................................................
1.7.1 Cooling 1-10..........................................................................
1.7.2 Heating 1-11..........................................................................
TROUBLESHOOTING 2-1.........................................................................
2.1 NO POWER TO UNIT 2-1.................................................................
2.2 DUCTED UNIT WILL NOT OPERATE 2-1...................................................
2.3 DUCTED UNIT WILL NOT COOL 2-1.......................................................
2.4 COMPRESSOR POWER SUPPLY OPEN 2-1...............................................
2.5 COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY 2-1....................
2.6 CYCLES ON COMPRESSOR OVERLOAD 2-2..............................................
2.7 INSUFFICIENT COOLING, COOLING AIR NOT ADEQUATE 2-2..............................
2.8 CONDENSER AIR NOT ADEQUATE 2-2....................................................
2.9 INSUFFICIENT COOLING 2-2.............................................................
2.10 COMPRESSOR FLOODING 2-2...........................................................
2.11 HEATERCYCLES ON LIMIT SWITCH (HEAT/ COOL VERSION ONLY) 2-2.....................
2.12 AIR SWEEP NOT WORKING (FREE BLOW VERSION ONLY) 2-2.............................
2.13 WATER LEAKAGE 2-2....................................................................
2.14 INADEQUATE HEAT (FREE-BLOW HEAT ONLY) 2-3........................................
2.15 INADEQUATE HEAT (HEAT-PUMP) 2-3....................................................
Clearing Diagnostic Alarms 2-3...................................................................
SERVICE AND MAINTENANCE 3-1................................................................
3.1 PREVENTATIVE MAINTENANCE 3-1......................................................
3.2 SERVICE - GENERAL 3-1................................................................
3.3 CEILING UNIT - FREE BLOW SYSTEMS 3-1...............................................
3.3.1 Filter Removal 3-1....................................................................
3.3.2 Ceiling Grill Removal 3-1..............................................................
3.3.3 Ceiling Panel Removal 3-2.............................................................
3.3.4 Master Control Switch 3-2.............................................................
3.3.5 Air Sweep Switch Removal 3-2.........................................................
3.3.6 Indoor Thermostat Removal 3-3........................................................
3.3.7 Air Sweep Removal
3.3.8 Heat Strip Assembly Removal 3-3......................................................
3-3...............................................................
i
T--298
Page 7
TABLE OF CONTENTS - Continued
3.4 CEILING UNIT - DUCTED SYSTEMS 3-4...................................................
3.4.1 Filter Removal 3-4....................................................................
3.4.2 Ceiling Grill Removal 3-4..............................................................
3.4.3 Control Box Assembly Removal 3-4.....................................................
3.4.4 Main PCB Board Removal 3-5..........................................................
3.4.5 PCB Display Removal 3-5.............................................................
3.4.6 Fuse Removal 3-5....................................................................
3.5 SERVICE - UPPER UNIT - STANDARD, HC & HP 3-5........................................
3.5.1 Exterior Cover Removal 3-5............................................................
3.5.2 Compressor Replacement 3-6..........................................................
3.5.3 Control Box Assembly Removal 3-6.....................................................
3.5.4 Upper Scroll Assembly Removal 3-7....................................................
3.5.5 Motor Assembly and Condenser Fan Removal 3-7........................................
3.5.6 Evaporator Blower Wheel Adjustment or Removal 3-8.....................................
3.5.7 Air Handling System Removal 3-8......................................................
3.5.8 Capacitor Troubleshooting 3-9..........................................................
3.5.9 Capacitor Testing and Replacement 3-9.................................................
3.5.10 Positive Temperature Coefficient Thermister (PTC) (Start Thermistor) Troubleshooting 3-9.....
3.5.11 Line Voltage - 10% 3-9................................................................
3.6 SERVICE - UPPER UNIT - LOW PROFILE 3-10..............................................
3.6.1 Exterior Cover Removal 3-10............................................................
3.6.2 Upper Scroll Assembly Removal 3-10....................................................
3.6.3 Condenser Fan Assembly Removal 3-11..................................................
3.6.4 Condenser Motor Removal 3-12.........................................................
3.6.5 Evaporator Motor/Blower Assembly Removal 3-12.........................................
3.6.6 Compressor Replacement 3-13..........................................................
3.6.7 Capacitor Removal 3-13................................................................
3.6.8 Remote Control (Fahrenheit to Celsius) 3-13..............................................
3.7 THERMOSTAT INSTALLATION AND STAR T-UP INSTRUCTIONS (WALL MOUNTED) 3-15........
3.7.1 Introduction 3-15......................................................................
3.7.2 Installation 3-15.......................................................................
3.7.3 Thermostat Location 3-15...............................................................
3.7.4 Install Thermostat - 12VDC 3-15.........................................................
3.8 LCD DISPLA Y 3-15.......................................................................
3.8.1 Cool Only Thermostat 3-15.............................................................
3.8.2 Heat/Cool Thermostat 3-15.............................................................
3.9 SET THERMOSTAT CONFIGURATION 3-15.................................................
3.9.1 Enter Configuration Mode 3-15..........................................................
3.10 CHECK THERMOSTAT OPERATION 3-16...................................................
3.10.1 Fan Operation (Cool Only) 3-16..........................................................
3.10.2 Fan Operation (Heat/Cool) 3-16.........................................................
3.10.3 Cooling Operation (Cool Only) 3-16......................................................
3.10.4 Cooling Operation (Heat/Cool) 3-16......................................................
3.10.5 Heating Operation (Heat/Cool) 3-16......................................................
T--298
ii
Page 8
TABLE OF CONTENTS - Continued
3.11 CHECK THERMOSTAT OPERATION 3-16...................................................
3.11.1 Temperature Display 3-16...............................................................
3.11.2 Timeguard Timer 3-17..................................................................
3.11.3 Cycle Timer 3-17......................................................................
3.11.4 Minimum On Timer 3-17................................................................
3.11.5 Error Messages 3-17...................................................................
WIRING SCHEMATICS 4-1........................................................................
4.1 INTRODUCTION 4-1.....................................................................
LIST OF FIGURES
FIGURE NUMBER Page
Figure 1-1 Model/Serial Number Plate (Typical) 1-1...................................................
Figure 1-2 Roof Unit Component Identification 1-3....................................................
Figure 1-3 Ceiling Unit Component Identification (Free-Blow) 1-4.......................................
Figure 1-4 Component Identification - Low Profile - Upper Unit 1-5......................................
Figure 1-5 Component Listing-Ceiling Unit For Ducted Systems 1-6....................................
Figure 1-6 Ducted System Air Flow Arrangement 1-7.................................................
Figure 1-7 Serial Number Locations 1-8.............................................................
Figure 1-8 Refrigerant Flow Schematic (Standard System) 1-9.........................................
Figure 1-9 Refrigerant Flow Schematic - Heat Pump - (Cool Mode) 1-10.................................
Figure 1-10 Refrigerant Flow Schematic - Heat Pump - (Heat Mode) 1-11................................
Figure 3-1 Filter Removal - Free Blow 3-1...........................................................
Figure 3-2 Ceiling Grill - Free Blow 3-2..............................................................
Figure 3-3 Ceiling Panel Assembly 3-2..............................................................
Figure 3-4 Ceiling Panel With Heat Option 3-2.......................................................
Figure 3-5 Control Box Assembly - Free Blow 3-2....................................................
Figure 3-6 Indoor Thermostat 3-3..................................................................
Figure 3-7 Air sweep motor 3-3....................................................................
Figure 3-8 Heat Strip Assembly 3-3................................................................
Figure 3-9 Filter Removal - Ducted Unit 3-4.........................................................
Figure 3-10 Ceiling Grill - Ducted 3-4...............................................................
Figure 3-11 Control Box & PCB Cover 3-4...........................................................
Figure 3-12 Control Box Assembly - Ducted 3-5......................................................
Figure 3-13 Main/Display PCB’s 3-5................................................................
Figure 3-14 Cover Assembly - Standard 3-5.........................................................
Figure 3-15 Control Box 3-6.......................................................................
Figure 3-16 Control Box Removal 3-6...............................................................
Figure 3-17 Water Cover Removal 3-6..............................................................
Figure 3-18 Upper Scroll Assembly 3-7.............................................................
Figure 3-19 Motor Assembly 3-7...................................................................
Figure 3-20 Spring Clamp Removal 3-7.............................................................
Figure 3-21 Motor Clip Removal 3-7................................................................
Figure 3-22 Condenser Fan Removal 3-8...........................................................
Figure 3-23 Blower Wheel 3-8.....................................................................
Figure 3-24 Condenser With Motor Assembly & Compressor 3-8.......................................
Figure 3-25 Set-Up For Discharging a Capacitor 3-9..................................................
iii
T--298
Page 9
LIST OF FIGURES
Figure 3-26 Cover Assembly - Low Profile 3-10.......................................................
Figure 3-27 Upper Scroll Assembly Locking T abs (b.) & Screw Locations (c.) 3-10.........................
Figure 3-28 Upper Scroll Assembly Keeper T ab Release 3-10...........................................
Figure 3-29 Upper Scroll & Control Box Cover Removed 3-11...........................................
Figure 3-30 Condenser Fan Assembly & Retaining Ring 3-11...........................................
Figure 3-31 Condenser Fan Motor & Fan Assembly Stop 3-11..........................................
Figure 3-32 Condenser Fan Motor & Fan Assembly Tab 3-11...........................................
Figure 3-33 Condenser Motor Ground 3-12...........................................................
Figure 3-34 Evaporator Motor Locking Tabs 3-12......................................................
Figure 3-35 Evaporator Motor/Blower Assembly In Cradle 3-12.........................................
Figure 3-36 Evaporator Blower Wheel (Flush With End Of Motor Shaft) 3-13..............................
Figure 3-37 Control Box Assembly With Capacitor 3-13................................................
Figure 3-38 Remote Control Components 3-14........................................................
Figure 3-39 Remote Control PCB (FR9 Location) 3-14.................................................
Figure 3-40 Wall Thermostat Wiring Diagram - Cool Only Model 3-17....................................
Figure 3-41 Wall Thermostat Wiring Diagram - Heat/Cool Model 3-18....................................
Figure 4-1 Upper Unit Schematic - Standard & HC 4-1................................................
Figure 4-2 Upper Unit Schematic - Low Profile 4-1...................................................
Figure 4-3 Ceiling Unit Schematic - Cooling Only 4-2.................................................
Figure 4-4 Ceiling Unit Schematic - Heat/Cool 4-2....................................................
Figure 4-5 Ceiling Unit, Standard - Ducted 4-2.......................................................
Figure 4-6 Heat Pump - Upper Unit - Free Blow 4-3..................................................
Figure 4-7 Heat Pump - Ceiling Unit - Free Blow 4-3..................................................
Figure 4-8 Heat Pump - Upper Unit - Ducted 4-4.....................................................
Figure 4-9 Heat Pump - Ceiling Unit - Ducted 4-4....................................................
LIST OF TABLES
TABLE NUMBER Page
Table 1-1 Model Chart 1-2.........................................................................
Table 1-2 Additional Support Manuals 1-3............................................................
Table 2-1 System Self-diagnostics Function (Ducted Remote) 2-4.......................................
T--298
iv
Page 10
SECTION 1
DESCRIPTION
1.1 INTRODUCTION
This manual contains service instructions and electrical data for the AirV, Carrier Transport Air Conditioning’s Recreational Vehicle air conditioning unit.
The AirV units are two piece systems, consisting of the UpperUnitandtheCeilingunit.TheUpperUnitcontains the refrigeration system while the Ceiling Unit contains thecontrols andvents. The Ceiling Units are availablein a free--blow or ducted configuration.
The free--blow units (see Figure 1-2) deliver air to the vehicle by means of front and rear end vents and one downward vent (air shower). The vents may all be opened or closed to direct air as desired. The front and rear vents are fitted with motorized dampers that oscillates to produce an “air--sweep” effect. These units may be fitted with optional electric heat.
Theductedunits(seeFigure 1-5andFigure 1-6)deliver air through ducting built in the vehicle ceiling. These units are fitted with a 12 VDC microprocessor control system, a display panel (PCB display) and a remote controller. These units may be wired to provide thermostatic control of the vehicle furnace.
Carrier’s AirV air conditioning models include cooling only units, heating/cooling units, and heat pump units. The cooling only units are available with free blow or ducted air delivery. Cooling units with heat strips are available for free blow only.
Operation of the AirV units is controlled automatically by the temperature controller (thermostat), which maintains the vehicle’s interior temperature at the desired set point. Free Blow, cool--only units are available with a wall mounted thermostat.
Table 1-1 lists model numbers and descriptions of the AirV units, and Table 1-2 lists additional support manuals that are available.
1.2 SERIAL NUMBER IDENTIFICATION
Separatepartnumbersandserialnumbersareprovided for the upper and lower unit assemblies The numbers may be found on a plate readable from inside the vehicle, See Figure 1-7.
The first two numbers of the serial number, see Figure 3-22, is theweektheunitwasmanufactured. For example, 01 would designate the first week of the year and 52 would designate the last week of the year.
The third and fourth numbers designate the year in which the unit was manufactured. For example, 99 would represent the year 1999, 00 the year 2000, and so on.
The letter Y and all the numbers after it designates the unit serial number. Example: Y43210
Aserialnumber of 1303Y12345 designates that the unit was manufactured the 13th week of 2003 and the serial number is Y12345.
Carrier
Air Conditioning
C
Division ofCarrier Corporation
USE AMP20
TIME DELAY FUSE OR
CIRCUIT BREAKER
COMPRESSOR
FAN MOTOR
USE CEILING ASSY/ANY
DATEOFMfg
DESIGN PSIG HIGH 350 LO 150
R--22
MODEL No.
Part No.
VOLTS
CAPACITY
AMPS
SERIAL No.
68RV14102A 99--00468-- 01
115
ph
1
13,500 3,955
13.5 05/03
1303Y12345
oz kg
RLA
FLA
99--00469-- 01
15.9
0.45
12.5
2.58
hz
V
60
Btu/h
W
A
Figure 1-1 Model/Serial Number Plate (Typical)
1.3 DESIGN CHANGE DESCRIPTIONS
The following list provides a description of changes in design and serial number breaks for those changes.
1400Y A diode was added to the Ducted Ceiling assembly control board to stop DC ripple from the converters,
2900Y Cover screw coating was changed in order to eliminate corrosion.
3400Y The plastic shroud was modified to improve drainage.
5100Y A new compressor and capacitor is introduced, improving stability and increasing capacity.
1201Y The temperature sensor was moved to the grill to improve temperature sensing during furnace mode,
2501Y The dual air sweep was added. 4501Y A switch was added to skip compressor
malfunction test. 4601Y Change in material was made in order to
strengthen the fan propeller. 4901Y The mounting bolt lengths were increased 3/4
inch.
4901Y The polar whiteducted ceiling color was cut--in. 0703Y & 1903Y Newstyle PCB -- Cool Mode -- Control
& Power Assembly (Fans shut off in auto mode). 0803Y & 2603Y Newstyle PCB -- Heat Pump -- Control
& Power Assembly (Fans shut off in auto mode). 4204Y Minimumfurnacesetpoint loweredfrom 63°Fto
45°F.
1-1
T--298
Page 11
Table 1-1. Model Chart
115VStandardSyste
m
220VStandardSyste
m
5.3Cool
y
HighCapacit
y
R
V
A
A
R
V
B
A
R
V
A
A
R
V
C
A
UPPER UNIT (ROOF)
Model Number Part Number Voltage Amps Color
115VStandard System
68RV14102A
220VStandard System
68RV11302A
HighCapacit
68RV15102A
Heat Pump
Systems
68RV14112A
LOW PROFILE
68RV15103A
LOW PROFILE
68RV14103A
(Free Blow -- High Capacity)
99--00468--00 1 15/1/60 12.8 White 99--00468--01 1 15/1/60 12.8 Ivory 99--00468--02 220/1/50 99--00468--03 220/1/50
5.3 Cool
6.7 Heat
99--00468--08 1 15/1/60 14.5 White 99--00468--09 1 15/1/60 14.5 Ivory 99--00468--04
(Free Blow)
99--00468--05
(Free Blow)
99--00468--06
(Ducted)
99--00468--07
(Ducted)
99--00468--10
99--00468--12
(Free Blow -- Standard)
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
1 15/1/60
12.7 Cool
10.9 Heat
12.7 Cool
10.9 Heat
12.7 Cool
10.9 Heat
12.7 Cool
10.9 Heat
15.1 Cool
13.8 Heat
15.0 Cool
13.7 Heat
White
Ivory
White
Ivory
White
Ivory
White
White
CEILING UNIT
Model Number Part Number Voltage Color Options Interface
68
68
0010
0010
99--00469--00 1 15/1/60 White Cool Only Free Blow 99--00469--01 1 15/1/60 Ivory Cool Only Free Blow 99--00469--02 1 15/1/60 White Heat/Cool Free Blow 99--00469--03 1 15/1/60 Ivory Heat/Cool Free Blow
68RV0010KA 99--00469--06 1 15/1/60 (12VDC) White Cool Only Ducted 68
0030
99--00469--04 220/1/50 White Cool Only Free Blow
99--00469--05 220/1/50 Ivory Cool Only Free Blow 68RV0030BA 99--00469--08 220/1/50 White Heat/Cool Free Blow 68RV0030KA 99--00469--10 220/1/50 White Cool Only Ducted
68
0012
99--00469--11 115/1/60 White Heat Pump Free Blow
99--00469--12 1 15/1/60 Ivory Heat Pump Free Blow
68RV0011LA 99--00469--13 1 15/1/60 (12VDC) White Heat Pump Ducted 68RV0010AB 99--00469--23 1 15/1/60 White Cool Only Free Blow 68RV0010AB 99--00469--24 1 15/1/60 Ivory Cool Only Free Blow 68RV0010BB 99--00469--25 1 15/1/60 White Heat/Cool Free Blow 68RV0010BB 99--00469--26 1 15/1/60 Ivory Heat/Cool Free Blow
68RV0040MA 99--00469--22 115/1/60 White Cool Only
68RV0010DB 99--00469--29 115/1/60 White Cool Only
Ducted
Wall Thermostat
Free Blow
Wall Thermostat
T--298
1-2
Page 12
Table 1-2 Additional Support Manuals
MANUAL--FORM NO.
71LC6A54310 AirV 115 Volts--Free Blow (Cool Only) Owner’s Guide
71LH6A54070 AirV 115 Volts--Free Blow (Heat--Cool) Owner’s Guide 71LD6A54070 AirV 115 Volts--Ducted (Cool Only) Owner’s Guide 71LH6A54070 AirV 220 Volts--Free Blow (Heat--Cool) Owner’s Guide
71RQ6A5401A AirV 115 Volts--Free Blow (Heat Pump) Owner’s Guide 71DQ6A5401A AirV 115 Volts--Ducted (Heat Pump) Owner’s Guide
71DW6A54070 AirV 115 Volts--Ducted Wired Thermostat Owner’s Guide
71LC6A54310 AirV 115 Volts--Free Blow (Cool Only) Owner’s Guide
71LH6A54070 AirV 115 Volts--Free Blow (Heat--Cool) Owner’s Guide
71RW6A54310 AirV 115 Volts--Free Blow Wired Thermostat Owner’s Guide
T--298PL AirV Service Parts ALL
62--50455--00 Basic refrigeration Service Training ALL
EQUIPMENT COVERED TYPE OF MANUAL (For) PART NO.
99--00469--00 99--00469--01
99--00469--02 99--00469--03
99--00469--06 99--00469--08
99--00469--09 99--00469--11
99--00469--12 99--00469--13 99--00469--22 99--00469--23
99--00469--24 99--00469--25
99--00469--26 99--00469--29
1
2
3
4
5
1. Cover
2. Condenser
3. Evaporator
4. Compressor
5. Base Pan
Figure 1-2 Roof Unit Component Identification
1-3
T--298
Page 13
1
2
3
4
1. Ceiling Panel Assembly
2. Control Box Cover
Figure 1-3 Ceiling Unit Component Identification (Free--Blow)
T--298
3. Control Assembly
4. Ceiling Grill Assembly
1-4
Page 14
1
2
3
9
8
5
6
4
7
10
11
1. Cover Assembly
2. Scroll Assembly -- Upper
3. Condenser Fan
4. Condenser Motor
5. Evaporator Motor
6. Evaporator Blower Wheel
Figure 1-4 Component Identification -- Low Profile -- Upper Unit
7. Condenser Coil
8. Scroll Assembly -- Lower
9. Evaporator Coil
10. Compressor 1 1. Base Pan Assembly
See Figure 1-3 for Ceiling Package (Free--Blow)
1-5
T--298
Page 15
1
2
3
12
11
10
4
5
6
7
9
8
1. Telescoping Divider (3 different sizes available)
2. Divider Assembly
3. Frame Panel, Insulation Assembly
4. Control Box Assembly
5. Control Box Cover
6. Suction Packing Assembly
Figure 1-5 Component Listing--Ceiling Unit For Ducted Systems
T--298
7. Remote Control Assembly
8. Remote Control Bracket Assembly
9. Filter Assemblies (2)
10. PCB Cover 1 1. PCB Main Assembly
12. PCB Display
1-6
Page 16
1
4
5
SCHEMATIC VIEW
1
2
3
5
1
SUPPLY AIR
4
INSTALLED VIEW
1. Vehicle Duct System (Connection)
2. Telescoping Divider (3 different sizes available)
3. Return Air Suction Area
Figure 1-6 Ducted System Air Flow Arrangement
SUPPLY AIR
2
3
RETURN AIR
4. Control Box Assembly
5. Supply Air Discharge Area
1-7
T--298
Page 17
Serial number of Upper Unit
Serial Number of Ceiling Unit
Free Blow Type
Upper Unit
Ceiling Unit
(Cover Removed)
Bottom of Upper Unit
Serial Number of
Ceiling Unit
(Side of Control Box)
Ceiling Assembly Frame
Ducted Type
T--298
Serial Number of Upper Unit
Figure 1-7 Serial Number Locations
1-8
Bottom View After Installation
(With Grille Removed)
Page 18
1.4 AirV SYSTEM COMPONENT SPECIFI­CATIONS
1.4.1 Refrigerant Charge
Standard -- High Capacity -- Heat Pump
R--22 -- 15.9 Ounces
Low Profile (All)
R--22 -- 16.9 Ounces
1.4.2 Compressor -- 115 Volts, 60 Cycles, 1 Phase
a. Locked Rotor Amps -- Standard -- High
Capacity -- Heat Pump
64.5 AMPS6
b. Locked Rotor Amps -- Low Profile
High Capacity
59.0 AMPS
c. Fully Loaded Amps -- Standard
Cooling -- Approximate 12.8 AMPS Heating -- N/A
d.Fully Loaded Amps -- High Capacity
Cooling -- Approx. 14.5 AMPS Heating -- Approx. 11 AMPS
e. Fully Loaded Amps -- Low Profile
Cooling -- Approx. 14.1 AMPS Heating -- Approx. 13.8 AMPS
f. Fully Loaded Amps -- Heat Pump
Cooling -- Approx. 12.8 AMPS Heating -- Approx. 11 AMPS
1.4.3 Compressor -- 220 Volts, 50 Cycles, 1 Phase a. Locked Rotor Amps
23.6 AMPS
1.4.4 Thermostat Range (All Free Blow Units)
61° F(16° C) to 89° F(32° C)
1.5 ST ART--UP
Refer to operating instructions in Owners Guide (see Table 1-2) packaged with the vehicle system.
DISCHARGE LIQUID
SUCTION
COMPRESSOR
Figure 1-8 Refrigerant Flow Schematic (Standard System)
1.6 REFRIGERANT CYCLE--STANDARD SYSTEM
The cooling cycle is energized when the thermostat, located on the ceiling unit, calls for cooling. The main components of the system are the compressor, air-cooled condenser coil, strainer, capillary tube, evaporator coil and accumulator.
The compressor raises the pressure and the temperature of the refrigerant and forces it through the discharge line into the condenser coil. (See Figure 1-8.)
The condenser fan circulates surrounding air (which is at a temperature lower than the refrigerant) over the outside of the coil tubes. Heat transfer is established from the refrigerant (inside the tubes) to the air (flowing over the tubes). The tubes have fins designed to improve the transfer of heat from the refrigerant gas to the air. This removal of heat causes the refrigerant to liquefy, thus liquid refrigerant leaves the coil and flows through a strainer to the capillary tube. The strainer removes any impurities within the refrigerant system.
The capillary tube meters the flow of liquid refrigerant to the evaporator coil. As the refrigerant flows through the capillary tube, there is a reduction in pressure and temperature.
CAPILLARY TUBE
EVAPORATOR
ACCUMULATOR
CONDENSER
STRAINER
Theevaporator blower (fan)pullsvehicleairthroughthe filters, which remove particulate matter, and then pass the cleaned air through the evaporator coil.
The low pressure, low temperature liquid that flows into the evaporator coil tubes is colder than the air that is circulated over the tubes. Heat transfer is established from the vehicle air (flowing over the tubes) to the refrigerant (flowing inside the tubes). The evaporator coil tubes have aluminum fins to increase heat transfer from the air to the refrigerant; therefore the cooler air is circulated to the interior of the vehicle.
The transfer of heat from the air to the low temperature liquid refrigerant in the indoor coil causes the liquid to vaporize. This low temperature, low pressure vapor passes into the accumulator. The accumulator is designed with the inlet tube delivering refrigerant to the bottom of the tank and the outlet tube taking refrigerant form the top of the tank. This arrangement ensures that only vapor refrigerant is returned to the compressor, where the cycle repeats.
When ventilation only is selected, the indoor fan functions to circulate air throughout the vehicle. The refrigerant cycle will remain off.
1-9
T--298
Page 19
1.7 REFRIGERANT CYCLE -- HEAT PUMP
DISCHARGE LIQUID
SUCTION
ACCUMULATOR
COMPRESSOR
Figure 1-9 Refrigerant Flow Schematic -- Heat Pump -- (Cool Mode)
1.7.1 Cooling
The cooling cycle is energized when the thermostat, located in the ceiling unit, calls for cooling The system controls are positioned for “normal”refrigerant flow,with the compressor discharge delivered to the outdoor coil and liquid delivered to the indoor coil. (See Figure 1-9.)
The main components of the system are the compressor, reversing valve, air-cooled outdoor coil, strainer,capillary tube, indoor coil, and theaccumulator.
The compressor raises the pressure and the temperature of the refrigerant and forces it through the discharge line and reversing valve into the outdoor coil.
The outdoor fan circulates surrounding air (which is at a temperature lower than the refrigerant)over the outside of the coil tubes. Heat transfer is established from the refrigerant (inside the tubes) to the outdoor air (flowing over the tubes). The tubes have fins designed to improve the transfer of heat from the refrigerant gas to the air; this removal of heat causes the refrigerant to liquefy, thus liquid refrigerant leaves the coil and flows through the strainer to the capillary tube. The strainer removes any impurities within the refrigerant system.
The capillary tube meters the flow of liquid refrigerant to the indoor coil. As the refrigerant flows through the
CAPILLARY
INDOOR COIL
REVERSING VALVE
OUTDOOR COIL
TUBE
STRAINER
capillary tube, there is a reduction in pressure and temperature.
The indoor blower (fan) pulls inside air through the filters, which remove particulate matter, and then pass the cleaned air through the indoor coil.
The low pressure, low temperature liquid that flows into the indoor coil tubes is colder than the air that is circulated over the tubes. Heat transfer is established from the indoor air (flowing over the tubes) to the refrigerant (flowing inside the tubes). The indoor coil tubes have aluminum fins toincrease heat transfer from the air to the refrigerant; therefore the cooler air is circulated to the interior of the vehicle.
The transfer of heat from the air to the low temperature liquid refrigerant in the indoor coil causes the liquid to vaporize. This low temperature, low pressure vapor passes into the accumulator. The accumulator is designed with the inlet tube delivering refrigerant to the bottom of the tank and the outlet tube taking refrigerant form the top of the tank. This arrangement ensures that only vapor refrigerant is returned to the compressor, where the cycle repeats.
When ventilation only is selected, the indoor fan functions to circulate air throughout the vehicle. The refrigerant cycle will remain off.
T--298
1-10
Page 20
DISCHARGE LIQUID
SUCTION
CAPILLARY
INDOOR COIL
REVERSING VALVE
ACCUMULATOR
COMPRESSOR
OUTDOOR COIL
TUBE
Figure 1-10 Refrigerant Flow Schematic -- Heat Pump -- (Heat Mode)
STRAINER
1.7.2 Heating
The heating cycle is energized when the thermostat, located in the ceiling unit, calls for heat The system controls are positioned for “reverse” refrigerant flow, with the compressor discharge delivered to the indoor coil and liquid delivered to the outdoor coil. (See Figure 1-10.)
The main components of the system are the compressor, reversing valve, indoor coil, capillary tube, strainer, air-cooled outdoor coil, and the accumulator.
The compressor raises the pressure and the temperature of the refrigerant and forces it through the discharge line and reversing valve into the indoor coil.
The indoor blower (fan) pulls inside air through the filters, which remove particulate matter, and then pass the cleaned air through the indoor coil.
Thevehicle air (which is at a temperature lower than the refrigerant) passes over the outside of the coil tubes. Heat transfer is established from the refrigerant (inside thetubes) to thevehicleair(flowingoverthetubes).The tubes have fins designed to improve the transfer of heat from the refrigerant gas to the air; this removal of heat causes the refrigerant to liquefy, thus liquid refrigerant leaves the coil and flows through the strainer to the
outdoor coil. The strainer removes any impurities within the refrigerant system.
The capillary tube meters the flow of liquid refrigerant to the outdoor coil. As the refrigerant flows through the capillary tube, there is a reduction in pressure and temperature.
The low pressure, low temperature liquid that flows into the outdoor coil tubes is colder than the outdoor air that is circulated over thetubes. Heat transfer isestablished from the outdoor air (flowing over the tubes) to the refrigerant (flowing inside the tubes). The outdoor coil tubes have aluminum fins toincrease heat transfer from the air to the refrigerant.
The transfer of heat from the air to the low temperature liquid refrigerant in the outdoor coil causes the liquid to vaporize. This low temperature, low pressure vapor passes into the accumulator. The accumulator is designed with the inlet tube delivering refrigerant to the bottom of the tank and the outlet tube taking refrigerant form the top of the tank. This arrangement ensures that only vapor refrigerant is returned to the compressor, where the cycle repeats.
When ventilation only is selected, the indoor fan functions to circulate air throughout the vehicle. The refrigerant cycle will remain off.
1-11
T--298
Page 21
SECTION 2
TROUBLESHOOTING
For ducted units, the green operation indicator LED (SeeFigure 3-9) will flash if there is a problem. Refer to Table 2--1 for diagnostic information.
SYMPTOM AND PROBABLE CAUSE
2.1 NO POWER TO UNIT
1. Master switch off
2. Open circuit breaker
3. Defective wiring
4. Loose electrical connections
5. Faulty switches, thermostat, or fan
6. 12 VDC not connected (Ducted System)
7. 12 VDC in--line fuse open (Ducted)
2.2 DUCTED UNIT WILL NOT OPERATE
1. Display not illuminated
2. Display illuminated
2.3 DUCTED UNIT WILL NOT COOL
1. Green LED light flashes 5 times
2. Unit cools for a few moments then stops cooling
2.4 COMPRESSOR POWER SUPPLY OPEN
1. Loose leads at compressor terminals
2. Defective motor overload switch
3. Defective capacitor
4. Open compressor windings
5. Seized compressor
6. Capacitor incorrectly wired
2.5 COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY
1. Loose lead at fan motor
2. Defective or burned out motor
3. Outdoor air restricted or recirculating
4. Overcharge or noncondensables in system
5. Restricted discharge line
6. Defective motor overload switch
1. Reset master switch
2. Reset circuit breaker
3. Replace wiring
4. Tighten connections
5. Replace defective components
6. Connect to 12 VDC power source
7. Replace fuse
1. Check 12 Volt DC in--line fuse
2. Check 1 15 Volt AC Connections
1. Check 1 15 volt AC power source Momentarily disconnect 12 VDC power source Disable compressor malfunction test switch.
Check AMP draw.
Check ∆ T
2. Remove grill, verify evaporator coil probe is inserted into coil.
Check AMP draw. Check ∆ T Replace unit
1. Tighten leads
2. Replace switch
3. Replace capacitor -- Refer to Paragraph 3.5.8
4. Replace compressor
5. Replace compressor
6. Verify capacitor wiring (Refer to wiring diagram)
1. Tighten lead.
2. Replace motor.
3. Check for dirty condenser coil, proper clearance around unit, remove any obstructions.
4. Check AMP draw
5. Check for obstruction in line. Check T. Replace unit.
6. Replace switch.
PROBABLE REMEDY
2-1
T--298
Page 22
SYSTEM AND PROBABLE CAUSE
PROBABLE REMEDY
2.6 CYCLES ON COMPRESSOR OVERLOAD
1. Defective run capacitor
2. Defective compressor bearings or valves
3. Greatly restricted evaporator air, iced evaporator
1. Replace capacitor -- Refer to Paragraph 3.5.8
2. Replace unit.
3. Defrost evaporator coil.
coil.
4. Low refrigerant charge
5. Evaporator capillary restricted
6. Liquid line restricted
7. Compressor hot
4. Replace unit.
5. Replace unit.
6. Replace unit.
7. Verify refrigerant charge. Check AMP draw. Check T.
8. Weak or inconsistent line power
8. Check line voltage at time of compressor start--up.
2.7 INSUFFICIENT COOLING, COOLING AIR NOT ADEQUATE
1. Dirty evaporator coil
2. Iced evaporator coil, slightly low refrigerant charge
3. Improper fan operation
4. Defective fan motor
5. Return air filter is dirty
1. Clean as required.
2. Defrost or Recharge.
3. Verify fan rotation (Refer to wiring diagram)
4. Replace fan motor.
5. Remove and clean filters (Refer to paragraphs 3.3.1
& 3.4.1)
2.8 CONDENSER AIR NOT ADEQUATE
1. Outside Air Restricted
2. Dirty coil
3. Defective fan motor
1. Check for obstruction at coil. Remedy as required.
2. Clean coil.
3. Replace fan motor.
2.9 INSUFFICIENT COOLING
1. Unit undersized
2. Capillary restricted
1. Re--evaluate unit for proper capacity.
2. Check AMP draw. Check T. Replace unit.
2.10 COMPRESSOR FLOODING
1. Unit overcharged
1. Check AMP draw. Check T. Replace unit.
2. Low evaporator airflow
3. Defective electrical connections
2. Clean filter and/or evaporator coil.
3. Check connections per wiring diagram and tighten any loose connections.
2.11 HEATER CYCLES ON LIMIT SWITCH (HEAT/ COOL VERSION ONLY)
1. Dirty filter
2. Blocked evaporator air inlet (indoor)
3. Low airflow due to fan motor speed
1. Clean or replace filter.
2. Remove blockage.
3. Check fan motor. Repair or replace as necessary.
2.12 AIR SWEEP NOT WORKING (FREE BLOW VERSION ONLY)
1. Ceiling grill not properly aligned
2. Linkage in upper control box stuck
3. Air sweep motor failure
1. Align ceiling grill.
2. Align and lubricate linkage.
3. Replace motor.
2.13 WATER LEAKAGE
1. Water dripping from ceiling unit. 1. Verify vehicle is level Tighten unit mounting bolts evenly or replace unit
gasket.
T--298
2-2
Page 23
SYSTEM AND PROBABLE CAUSE
2.14 INADEQUATE HEAT (FREE--BLOW HEAT ONLY)
1. No heat from heat strip. 1. Verify AMP draw . ( 13.8 AMP) Verify resistance through heating element. (9 OHM) Check bi--metal switch. If open, replace switch.
2.15 INADEQUATE HEAT (HEAT--PUMP)
NOTE: Allow unit to operate 15 minutes after switch-
ing from cooling mode.
1. Reversing valve not operating
2. Outdoor coil icing.
1. Check for 115 volts at reversing valve coil Check for reversing valve restriction Verify compressor operation
2. Check outdoor coil sensor
PROBABLE REMEDY
Clearing Diagnostic Alarms
When a repair has been accomplished due to a corresponding alarm, the alarm must be cleared. This is done by disconnecting the 12 VDC power to the ducted ceiling assembly for one or two seconds. Once the 12 VDC power is reconnected, the alarm should have been cleared.
2-3
T--298
Page 24
Table 2--1 System Self--diagnostics Function (Ducted Remote)
Flashes
2
Error Codes
(Priority)
1 ROOM AIR THERM-
Error Contents
(Malfunction)
ISTOR FAILURE
3 2 INDOOR COIL
THERMISTOR FAIL-
URE
4 3 OUTDOOR COIL
THERMISTOR
FAILURE
5 4 COMPRESSOR
DRIVE
MALFUNCTION
Display Pattern Allowed Modes
FAN Mode
FAN Mode
3sec .
0.5 sec (3 Times)
0.5 sec. (Twice)
3sec .
FURNACE Mode
3sec .
0.5 sec. (4 Times)
3sec.
FAN Mode
FURNACE Mode
3sec.
0.5 sec. (5 Times)
3sec .
FAN Mode
FURNACE Mode
6 5 REVERSING VALVE
DRIVE MAL--
FUNCTION
1
6 DISCHARGE AIR
THERMISTOR FAIL-
URE
Continuous 7 THERMISTOR
WIRING WRONG
(only in cooling
test mode)
3sec .
3sec .
3sec .
0.5 sec. (6Times)
0.5 sec. (Once)
3sec.3sec
.
0.5 sec. (Continu­ous)
3sec .
3sec .
FAN Mode
FURNACE Mode
FAN Mode
FURNACE Mode
FAN Mode
NOTE:
If more than two errors occur, the highest ranked code is displayed. If the highest ranked error is cleared, the next highest ranked error code is displayed.
T--298
2-4
Page 25
SECTION 3
SERVICE AND MAINTENANCE
3.1 PREVENTA TIVE MAINTENANCE Cleaning--Clean evaporator coil and condenser coil.
Hold flashlight behind coil to see if all spaces are clear. Dust accumulation obstructs or reduces airflow and results in loss of cooling capacity. Both coils may be vacuumed when dry. Coils may also be brushed with a stiff brush and then blown out with compressed air.
Thoroughly clean base pan, motors, fan wheels, and other components.
Clean cover and ceiling grill. Mild detergents reduce electrostatic charges on plastic sections of the grill and are good cleaners.
WARNING
Before working on the unit be sure to first disconnect all electric power to the unit to avoidthepossibilityofelectricalshockand personal injury. Before disconnecting, dis-
charge capacitors by shorting across the capacitors terminals (Refer to paragraph
3.5.8)
WARNING
CAUTION
Do not use carbon tetrachloride, solvents, or waxes containing solvents to clean plas­tic sections.
Painting--Paint any parts that show evidence of rust
with a good rust--prevention paint. Wiring-- Check all wiring for deterioration and all
electrical contacts for tightness or corrosion. Mounting--Make sure unit is secure on roof according
to installation instructions provided in Owner’s Guide. Checkfanstoinsurethatthey arecorrectly positionedin the center of the orifice, and tight on the shaft.
Leaks--Check any connections that show evidence of oil or leaks. When unit is properly installed (refer to Owner’sGuide) check gaskets for possible air leakage.
Controls--Check unit to ensure all controls are functioning correctly and unit operation is normal. Vibrations can cause unwanted noise.
NOTE
Check to ensure that piping is not vibrating against side of the unit.
Shield coils with cardboard to protect hands against injury from sharp metal edges when removing compressor and oth­er components.
3.3 CEILING UNIT -- FREE BLOW SYSTEMS
3.3.1 Filter Removal
The filters (Figure 3-1) are located in the ceiling grill. To remove the filters, do the following:
a. Grasp the edge of the filter at recess in the end of the
ceiling grill. b. Pull filter completely out of the filter slot. c. Vacuum filter or wash filter in luke--warm water.
Shake off excess water and dry thoroughly. d. Replace filter by sliding the filter into the filter slot in
the ceiling grill until the filter frame is flush with the in-
terior grill.
Filters
NOTE
For proper cleaning and flushing, use a UL approved refrigerant recovery/recycling system.
NOTE
Refrigerant removal must always include recovering the refrigerant, not allowing it to escape to the atmosphere.
3.2 SERVICE -- GENERAL General Notes—These Service Instructions are
provided to assist the trained and qualified Carrier service technician in repairing or replacing components of the AirV units.
Figure 3-1 Filter Removal -- Free Blow
3.3.2 Ceiling Grill Removal
To remove the ceiling grill (Figure 3-2) do the following: a. Before working on unit place the master switch in the
OFF position and disconnect all electrical power. b. Remove 4 screws located on the ceiling grill, making
sure to support the weight of the grill. c. Lower the ceiling grill from the ceiling panel.
3-1
T--298
Page 26
d. To replace the grill, place the grill up against the ceil-
ingpanelandalignthescrew holes in thegrill with the ceiling panel.
e. Replace 4 screws.
Mounting
Screws
Figure 3-2 Ceiling Grill -- Free Blow
3.3.3 Ceiling Panel Removal
To remove the ceiling panel (Figure 3-3) do the following:
a. Remove the ceiling grill. (Refer to paragraph 3.3.2.) b. Remove 5 screws securing the duct plate to the ceil-
ing panel.
Heat Strip Connection
Heater Assembly
Option
Figure 3-4 Ceiling Panel With Heat Option
3.3.4 Master Control Switch
To remove the master control switch, do the following: a. Remove ceiling grill. (Refer to paragraph 3.3.2.) b. Remove 5 screws that secure the control assembly
(Item 2, Figure 1-3) to the control box cover.
c. Remove the master control switch knob by grabbing
the outside edge of the knob and pulling it off of the switch stem.
d. Remove 2 screws securing the master control switch
to the control assembly.
e. Carefully disconnect wires from the master control
switch. Label wires to aid in reassembly.
f. Reverse above procedure for reassembly.
c. Remove 4 mounting bolts making sure to support the
weight of the ceiling panel.
d. Disconnect the unit harnesses and main power wires
from the ceiling panel. e. Lower the ceiling panel from the air conditioning unit. f. Reverse above procedure for reassembly.
Air Sweep Cam
Serial/Model Number Tag
Duct Plate & Mounting Holes
Mounting Bolts
Junction Box
Figure 3-3 Ceiling Panel Assembly
Junction Box
Air Sweep Switch
With Cover
Thermostat
Master Control
Switch
Figure 3-5 Control Box Assembly -- Free Blow
3.3.5 Air Sweep Switch Removal
To remove the air sweep switch, do the following: a. Remove ceiling grill. (Refer to paragraph 3.3.2.) b. Remove 5 screws securing the control assembly
(Item 2, Figure 1-3) to the control box cover. c. Disconnect wires from the air sweep switch. d. Pinch tabs on either end of the switch and slide out of
lower control box cover. e. Reverse above procedure for reassembly.
T--298
3-2
Page 27
3.3.6 Indoor Thermostat Removal
To remove the indoor thermostat (Figure 3-6) do the following:
a. Remove ceiling grille. (Refer to paragraph 3.3.2.) b. Remove 5 screws securing the control assembly
(item 3, Figure 1-3) to the control box cover.
c. Remove the indoor thermostat knob by grabbing the
outside edge of the knob and pulling it off of the ther­mostat stem.
d.Remove2screwsthatsecuretheindoorthermostatto
the lower control box cover.
e. Carefully disconnect the 2 wires from the indoorther-
mostat. f. Remove the sensing bulb from the plastic clip. g. Carefully slide the sensing bulb through the rubber
grommet. h. Remove the thermostat from the control assembly. i. Reverse above procedure for reassembly.
Thermostat
Air Sweep Motor
Figure 3-7 Air sweep motor
3.3.8 Heat Strip Assembly Removal
To remove the heat strip assembly (Figure 3-8) do the following:
a. Remove ceiling grille. (Refer to paragraph 3.3.2.) b. Unplug electrical connection at air sweep motor as-
sembly.
c. Remove two screws securing heat strip assembly to
the ceiling panel assembly.
d. Slide heat strip assembly away from air sweep motor
assembly and pull down, easing the the electrical connection through the access hole.
e. Reverse the procedures for reassembly.
Sensing Bulb
Figure 3-6 Indoor Thermostat
3.3.7 Air Sweep Removal
To remove the air sweep, do the following: a. Remove ceiling grille. (Refer to paragraph 3.3.2.) b. Remove cam (See Figure 3-3) from air sweep motor
shaft. c. Remove 4 screws securing air sweep motor bracket
to the ceiling panel assembly. d. Carefully disconnect air sweep motor wire termina-
tions. e. Remove 2 screws securing air sweep motor
(Figure 3-7) to control box and remove motor. f. Reverse above procedure for reassembly.
Heat Strip
Figure 3-8 Heat Strip Assembly
3-3
T--298
Page 28
3.4 CEILING UNIT -- DUCTED SYSTEMS
3.4.1 Filter Removal
The filters (Figure 3-9) are located in the ceiling grill. To remove the filters, do the following:
a. Grasp the edge of the filter at recess in the end of the
ceiling grill. b. Pull filter completely out of the filter slot. c. Vacuum filter or wash filter in luke--warm water.
Shake off excess water and dry thoroughly. d. Replace filter by sliding the filter into the filter slot in
the ceiling grill until the filter frame is flush with the in-
terior grill.
c. Remove two screws securing control box cover to
control box assembly. See Figure 3-11.
d. Remove control box assembly cover.
Mounting Screws
Filters
Operation Indicators
Figure 3-9 Filter Removal -- Ducted Unit
3.4.2 Ceiling Grill Removal
Toremovetheceilinggrill(Figure3--10)dothefollowing: a. Before working on unit place the master switch in the
OFF position and disconnect all electrical power. b. Remove filters (Refer to paragraph 3.4.1). c. Remove 4 screws located on the ceilinggrill, (two are
underthefilters) making sure to support the weightof
the grill. d. Lower the ceiling grill from the ceiling panel. e. To replace the grill, place the grill up against the ceil-
ingpanelandalignthescrew holes in thegrill with the
ceiling panel. f. Replace 4 screws and 2 filters.
3.4.3 Control Box Assembly Removal
To remove the control box assembly (Figure 3-11 & Figure 3-12) do the following:
a. Remove ceiling grill. Refer to paragraph 3.4.2. b. Disconnect 115 volt (AC) and 12 volt (DC) power
wires.
Figure 3-10 Ceiling Grill -- Ducted
e. Disconnect blue furnace wires. f. Unplug two connectors from upper unit. g. Unplug DC power plug #1 (red/yellow/black wires)
SeeFigure3-12
h. Unplug relay signal plug #2 (brown/red/orange/
yellow wires). See Figure 3-12
i. While supporting control box assembly remove two
screws securing control box assembly to ducted ceil-
ing unit. j. Pull controlboxassemblyfromtheductedceilingunit. k. Reverse above procedure to reassemble.
Control Box
Control Box Cover Screws
Fuse
PCB Cover
PCB Cover
Screws
Figure 3-11 Control Box & PCB Cover
T--298
3-4
Page 29
1 15V AC
3.4.5 PCB Display Removal
To remove the PCB display assembly (Figure 3-13) do
the following.
12V DC
a. Remove ceiling grill. Refer to paragraph 3.4.2. b. Push large clip away from PCB display assembly.
Fuse
Upper Unit Connectors
Figure 3-12 Control Box Assembly -- Ducted
3.4.4 Main PCB Board Removal
To remove the Main PCB board (Figure 3-13) do the following:
a. Remove ceiling grill. Refer to paragraph 3.4.2. b. Remove three screws securing the PCB cover to the
ducted ceiling unit.
c. Carefully turn over the PCB cover exposing the PCB
main and the PCB display assemblies.
d. Gentlypushholdingclipaway from PCB mainassem-
bly. e. Lift PCB main assembly from PCB cover assembly. f. Unplug display wiring plug #4. Figure 3-13
#2
#1
Furnace Wires (blue)
c. Push center clip towards large clip. d. Pull PCB display assembly from PCB cover. e. Unplug display wiring from PCB main assembly. f. Reverse above procedures of reassembly.
3.4.6 Fuse Removal
To remove the fuse (Figure 3-11) do the following: a. Remove ceiling grill. Refer to paragraph 3.4.2. b. Turnfuseholderindirectionofarrow(counter--clock--
wise). c. Pull fuse from fuse holder. d. Test and/or replace. e. Reverse above procedures for reassembly.
3.5 SERVICE -- UPPER UNIT -- STANDARD,
HC&HP
3.5.1 Exterior Cover Removal
CAUTION
g. Unplug thermistor/thermostat wiring plug #3.
Figure 3-13 h. Unplug power wiring plug #1. Figure 3-12 i. Unplug signal wiring plug #2. Figure 3-12 j. Reverse above procedures for reassembly.
Holding Clips
PCB Display
PCB Main
#4
Coil fins are sharp. Usecarewhenremoving the cover form the base pan to avoid per­sonal injury.
To remove the exterior cover, do the following: a. Before working on unit place the master switch in the
OFF position and disconnect all electrical power.
b. Remove 15 screws securing the unit cover to the
base pan assembly. See Figure 3-14.
c. Carefully lift the exterior cover off of theunit base pan
assembly.
d. Reverse above procedure for reassembly.
#3
Figure 3-13 Main/Display PCB’s
3-5
Cover Screws
Figure 3-14 Cover Assembly -- Standard
T--298
Page 30
3.5.2 Compressor Replacement
Observe the same procedures for rotary compressors as for reciprocating compressors.
a. Follow all safety codes. Reminder: use protective
goggles, work gloves, and water soaked quenching cloth.
b. Remove exterior cover.refer toparagraph 3.5.1.Dis-
connect all wiring from the compressor.
c. Apply field--supplied, line--tap--valves to the suction
and discharge lines as close to the compressor as possible.
d. Recover therefrigerant charge from the unit. Afterre-
covering,cut the discharge and suction line process tubes below the tube crimps. If you choose a good tubing location for cutting the refrigeration lines ini­tially, the location is easily accessible when making the final joints.
WARNING
Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exer­cise extreme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency use.
Control Box
Screws
Figure 3-15 Control Box
Water Cover
e. Connectanitrogen supply to theunitatoneoftheline
--tap--valve connectors (5--psig maximum flow), leav­ing the other connector open to the atmosphere.
Braze angle valves with stubs to each process tube. f. Remove compressor from unit (3 bolts). g. Remove line--tap--valves from suction and discharge
lines.Carefullybrazetheholesclosedfromwherethe
line--tap--valves were removed. h. Cleansystem:addorreplaceliquidlinefilter drier.For
proper cleaning and flushing use a UL approved re-
frigerant recycling system. i. Install new compressor and braze into place with
field--supplied copper slip couplings. j.Connect wiring: replace wire terminals if necessary. k. Proceed with evacuation and charging (15.9 OZ. --
.45 KG R22). Pinch off lines where angle valves were
added. Cut off angle valves above pinch--off , and
braze tubes. l. Start up unit.
3.5.3 Control Box Assembly Removal
To remove the control box assembly, do the following: a. Removeexterior cover assembly.Refertoparagraph
3.5.1.
b. Remove 2 screws securing control box assembly to
the lower scroll assembly. (SeeFigure 3-15.)
Figure 3-16 Control Box Removal
c. Slide control box out of the lower scroll assembly.
(See Figure 3-16.)
d. To open control box remove 2 screws securing the
water cover to the control box cover.
e. Gently lift the water cover off of the control box. (See
Figure 3-17.)
f. Reverse above procedure for reassembly.
Control Box Cover
Figure 3-17 Water Cover Removal
T--298
3-6
Page 31
3.5.4 Upper Scroll Assembly Removal
a. Removeexterior cover assembly.Refertoparagraph
3.5.1.
b. Remove 4 screws securing upper scroll assembly to
the lower scroll assembly. (See Figure 3-18)
c. Gently pry 4 snap clips open and lift the upper scroll
assembly off of the lower scroll assembly.
d. Reverse above procedure for reassembly.
Screws 4 Places
i. Remove condenser fan from motor shaft and lift fan
out through the top of the condenser orifice. (See
Figure 3-22) j. Remove motor assembly. k.Reverse above procedure for reassembly.
Ground screw
Motor Ground Lead
Figure 3-19 Motor Assembly
Snap Clip 4 Places
Figure 3-18 Upper Scroll Assembly
3.5.5 Motor Assembly and Condenser Fan Removal
a. Removeexterior cover assembly.Refertoparagraph
3.5.1.
b. Remove control box assembly. Refer to paragraph
3.5.3.
c. Remove upper scroll assembly. Refer to paragraph
3.5.4.
d. Remove 4 screws securing the condenser cover to
the condenser orifice. (See Figure 3-24.)
e. Carefully disconnect motor wire terminations from
within the control box.
f. Remove 1 screw securing the motor ground lead to
the motor bracket assembly. (See Figure 3-19)
g. Using flat--nosed pliers, depress the motor spring
clamp and slide it off of the condenser fan (See Figure 3-20).
h. Liftandslidemotortowardsevaporatorcoiltoremove
condenser fan from the motor shaft.
Spring Clamp
Figure 3-20 Spring Clamp Removal
Motor Clip
Figure 3-21 Motor Clip Removal
3-7
T--298
Page 32
Condenser Fan
3.5.7 Air Handling System Removal
a. Removeexterior cover assembly.Refertoparagraph
3.5.1.
b. Remove control box assembly. Refer to paragraph
3.5.3.
c. Remove upper scroll assembly. Refer to paragraph
3.5.4. d. Remove motor assembly. Refer to paragraph 3.5.5. e. Remove 8 screws securing lower scroll assembly to
the base pan assembly.
f. Remove 1 screw from clamp securing suction tubeto
the base pan assembly.
g. Remove 3 nuts securing the compressor to the base
pan assembly.
h. Remove 2 screws securing the condenser orifice to
the base pan assembly.
Figure 3-22 Condenser Fan Removal
3.5.6 Evaporator Blower Wheel Adjustment or Removal
a. Remove exterior cover assembly. Refer to Exterior
Cover Assembly Removal instructions 3.5.1
b. Remove control box assembly. Refer to Control Box
Assembly Removal instructions 3.5.3
c. Remove upper scrollassembly.Refer to Upper Scroll
Assembly Removal instructions 3.5.4
d. Loosen motor assembly. Refer to Motor Assembly
Removal instructions 3.5.5.
e. Mark shaft at a point where wheel hub and motor
shaft meet to aid in reassembly.(See Figure 3-23.)
f. Remove 1 set screw holding the blower wheel to the
motor shaft. (See Figure 3-23) g. Slide off blower wheel from motor shaft h. Reverse above procedure for reassembly.
Set Screw
i. Remove 2 screws securing the condenser coil as-
sembly to the base pan assembly.
j. Carefully lift the entire assembly off of the base pan
assembly.
k. Reverse the above procedure for reassembly,ensur-
ing that the air handling system is positioned correct­ly. Tighten all screws.
Compressor
Condenser Cover
Condenser
Cover Screws
Motor Assembly
T--298
Figure 3-23 Blower Wheel
Base Pan
Base Pan
Figure 3-24 Condenser With Motor Assembly &
Compressor
3-8
Page 33
3.5.8 Capacitor Troubleshooting
WARNING
WARNING
Disconnect power to the AirV unit before checking the capacitor.
To test capacitor to determine if good, open or shorted, an ohm meter can be used. Todetermine a capacitor’s capacitance, a capacitor meter is required.
Capacitors showing signs of leaks or bulging should be replaced immediately.
3.5.9 Capacitor Testing and Replacement
Capacitors must be discharged properly before testing. a. Place a 20,000 ohm, 2 watt resistor across the termi-
nals of the capacitor for approximately 30 seconds (See Figure 3-25 for a suggested tool).
INSULATED SCREWDRIVER
Do not touch the metal of the screwdriver when discharging the capacitor. You could receive a shock.
b. After the capacitor has been dischargedand all wires
removed from the capacitor terminals, use an ohm-­meter to test its resistance.
c. Set the scale to R x 1K or 10K ohm and place the
ohmmeter leads across the capacitor terminals.
d. Iftheohmmeterfirst reads 0, then rises towardinfinity
or some higher resistance, the capacitor is good.
e. If the ohmmeter goes to 0 or a low resistance and
stays there, the capacitor is shorted and needs to be replaced.
f. If the ohmmeter reads infinity (OL) the capacitor is
open and needs to be replaced.
20,000 -- OHM 2 -- WATTRESISTOR
CLIP TO SCREWDRIVER
Figure 3-25 Set--Up For Discharging a Capacitor
3.5.10 Positive Temperature Coefficient Thermister (PTC) (Start Thermistor) Troubleshooting
a. Disconnect power from the AirV unit. b. Disconnect the wires to the PTC. c. Using an ohm meter, check for continuity across the
PTC. If the PTC does not havecontinuity, it must bereplaced. If continuity exists, reconnect the wires to the PTC. d. Reconnect power to the AirV unit. e. Turn on the AirV unit to start. f. Use a clamp--on amp probe to monitor the amp draw
of the compressor during its start--up.
ATTACH TO CLEAN UNPAINTED METAL PART OF UNIT FRAME
TOUCH TO CAPACITOR TERMINALS TO DISCHARGE CAPACITOR
When the compressor starts, an amp draw will be indicated for almost a second.
If no amp draw is indicated or if the amp draw occurs for much longer than a second, the PTC is defective and must be replaced.
3.5.11 Line Voltage -- 10%
Line voltage should be checked during peak electrical load periods.
With the AirV unit onandthecompressoroperating,use a voltmeter to check the voltage being supplied to the AirV unit. The voltage must be within 10% of the units required voltage. A voltage drop greater than 10% will cause a premature compressor failure and needs to be corrected immediately.
3-9
T--298
Page 34
3.6 SERVICE -- UPPER UNIT -- LOW PROFILE
3.6.1 Exterior Cover Removal
CAUTION
b. b.
Coil fins are sharp. Usecarewhenremoving the cover form the base pan to avoid per­sonal injury.
To remove the exterior cover, do the following: a. Before working on unit place the master switch in the
OFF position and disconnect all electrical power.
b. Remove (8) screws securing the unit cover to the
base pan assembly. See Figure 3-26.
c. Carefully lift the exterior cover off of theunit base pan
assembly.
d. Reverse above procedure for reassembly.
Screws
Screws
b.
b.
c.
b.
Figure 3-27 Upper Scroll Assembly
Locking Tabs (b.) & Screw Locations (c.)
b.
Figure 3-26 Cover Assembly -- Low Profile
3.6.2 Upper Scroll Assembly Removal
To remove the upper scroll assembly, do the following: a. Removeexterior cover assembly.Refertoparagraph
3.6.1.
b. Releasethe(2)front,(2)rear,(1) left sideand(1)right
sidelockingtabs(SeeFigure 3-27) bypullingbackon the tabs (See Figure 3-28).
c. Remove the screw (1) from the control box cover
(See Figure 3-27).
d. With all (6) locking tabs released and control box
screw removed, lift the upper scroll assembly off of the lower scroll assembly.
e. Reverse above procedure for reassembly.Ensure all
(6) locking tabs snap shut & lock.
Figure 3-28 Upper Scroll Assembly
Keeper Tab Release
T--298
3-10
Page 35
Evaporator Coil
Condenser Coil
Retaining
Ring
Figure 3-30 Condenser Fan Assembly
& Retaining Ring
Fan Stop
Figure 3-29 Upper Scroll & Control Box
Cover Removed
3.6.3 Condenser Fan Assembly Removal
To remove condenser fan assembly, do the following: a. Perform steps outlined in Section 3.6.2. b. Depress and remove Retaining Ring (See
Figure 3-30). c. Using both hands, carefully pull up on fan assembly
until it is free of the motor shaft. d. When replacing the fan assembly make sure the fan
assembly is against the stop on the shaft (See
Figure 3-31)
13MM
Bolt
Condenser Motor
Grommet
Figure 3-31 Condenser Fan Motor
& Fan Assembly Stop
Tab
13MM
Bolt
e. Push back on tab to allow fan assembly to rest
against stop (See Figure 3-32). Fan assembly will
now be flush with the end of the motor shaft. f. Reverse above procedure for reassembly.
3-11
Figure 3-32 Condenser Fan Motor
& Fan Assembly Tab
T--298
Page 36
3.6.4 Condenser Motor Removal
To remove condenser fan motor, do the following: a. Perform steps outlined in Section 3.6.2. b. Remove (3) 13MM bolts (See Figure 3-31). c. Remove (3) Grommets. Inspect, replace or reuse. d. Cut Tie--Wraps & discard (2 locations). When re-
assembling, tie--wrap at same 2 locations.
e. Remove ground wire from compressor bracket (See
Figure 3-33).
f. Un--plug (yellow/brown/white) from control box as-
sembly.
g. Reverse above procedure for reassembly.
Cond. Motor Ground Screw
Blower Side Locking T abs
Outside Locking T abs
Comp. Mounting Bolt
Figure 3-33 Condenser Motor Ground
3.6.5 Evaporator Motor/Blower Assembly Removal
To remove the evaporator motor, do the following: a. Perform steps outlined in Section 3.6.2. b. Pull back on and release the (4) locking tabs. There
are 2 on each side of the control box assembly. (See Figure 3-34).
c. Lift control box assembly from lower scroll assembly,
exposing evaporator motor.
d. Un--plug (black/blue/white/brown) evaporator motor
from control box assembly.
e. Remove ground wire (green/yellow) from motor
housing.
f. Lift motor/blower assembly from lower scroll assem-
bly cradle.
g. Carefully remove the blower wheelfrom theevapora-
tor motor shaft by pushing out from the motor side.
Figure 3-34 Evaporator Motor Locking Tabs
Lower Scroll
Assembly
Capacitor
Cradle
Figure 3-35 Evaporator Motor/Blower Assembly
In Cradle
T--298
3-12
Page 37
NOTE
When reassembling the blower wheel on to the motor shaft ensure that the blower wheel is flush with the end of the motor shaft (SeeFigure 3-36).
h. Reverse above procedure for reassembly.
NOTE
When placing the evaporator motor/blower assembly back into the lower scroll assem­bly cradle, make sure that the assembly is seated securely in the cradle. (See Figure 3-35).
3.6.6 Compressor Replacement
Perform the procedures outlined in Section 3.5.2 There are 4 bolts with the Low Profile Compressor. The system charge for the Low Profile unit is 16.9 OZ.
3.6.7 Capacitor Removal
To remove the capacitor, do the following:
Wheel Flush With Motor Shaft
Figure 3-36 Evaporator Blower Wheel
(Flush With End Of Motor Shaft)
Upper Scroll Assembly
a. Perform steps a., b. & c. as outlined in Section 3.6.5. b. Perform steps outlined in Sections 3.5.8 & 3.5.9. c. The Low Profile Capacitor is removed from the con-
trol box assembly by pushing on the capacitor from under the control box assembly (See Figure 3-35).
Control Box Assembly
Capacitor
Terminal Block
Figure 3-37 Control Box Assembly With Capacitor
3.6.8 Remote Control (Fahrenheit to Celsius)
All Remote Control Assemblies in the United States are pre--set to display in Fahrenheit degrees (see Figure 3-38). To change from a Fahrenheit display to a Celsius display do the following:
3-13
CAUTION
The change from Fahrenheit to Celsiuswill bepermanent.Itcannotbechangedbackto Fahrenheit.
T--298
Page 38
a. Remove the batteries from the remote control. b. Carefully remove the remotecover by insertinganar-
row flat object between the cover and remote body
and prying apart. c. Remove the brass screw holding the PCB in place. d. Carefully remove the PCB board from the remote
body, making sure the battery springs release from
their holders. e. Locate FR9 on the PCB board (see Figure 3-39).
f. Carefully cut the FR9 jumper wire. g. Reverse above procedure for reassembly.
CAUTION
When re--assembling, ensure the battery springs are correctly placed in the battery spring holders.
BATTERIES
&
COVER
Battery Springs
PCB
COVER
Figure 3-38 Remote Control Components
Spring Holders
BODY
T--298
PCB
FR9
Figure 3-39 Remote Control PCB (FR9 Location)
3-14
Page 39
3.7 THERMOSTAT INSTALLATION AND START-­UP INSTRUCTIONS (WALL MOUNTED)
3.7.1 Introduction
The thermostat is a wall mounted, low--voltage thermostat which maintains room temperature by controlling the operation of a heating and air conditioning system. Batteries are not required; temperature and mode settings are preserved with the power off.
2.Disconnect wires from existing thermostat, one at a time. Be careful not to allow wires to fall back into the wall.
3.As each wire is disconnected, record wire color and terminal marking.
4.Discard or recycle old thermostat.
NOTE
Mercuryisahazardouswasteandmustbedes­posed of properly.
CAUTION
Improperwiring orinstallationmaydamage thermostat. Wiring must conform to local and national electrical codes.
WARNING
Before installing thermostat, turn off all power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
3.7.2 Installation
NOTE
Readallinstructionsbeforestarting theinstalla­tion.
NOTE
The thermostat requires no batteries. The ther­mostat is not a power stealing device and MUST have both R and C connected.
c. Seperate the front and back pieces of plastic. d. Route thermostat wires through hole in back piece of
plastic. Level plastic against wall (for aesthetic value only -- thermostat need not be leveled for proper op­eration) and mark wall through 2 mounting holes.
e. Drill two 3/16 inch mounting holes in wall where
marked.
NOTE
Mounting holes on thermostat are designed to fit on a horizontal J--Box.
f. Securebackplasticto wallwith2anchorsandscrews
provided,makingsureallwiresextendthroughholein plastic.
g. Connect wires to proper terminal of the connector
block in the front piece of plastic.
h. Pusr any excess wire back into wall. Excess wire in-
side the thermostat plastic case can interfere with proper air flow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can effect op-
eration. i. Snap front and back pieces of plastic together. j. Turn on power to the unit.
3.8 LCD DISPLAY
3.7.3 Thermostat Location
The thermostat should be mounted:
Approximately 5 foot (1.5m) from the floor. Close to or in a frequently used room, preferably on
an inside partitioning wall. On a section of wall without pipes or duct work.
The thermostat should NOT be mounted:
Closetoawindow,oranoutsidewall,ornexttoadoor leading to the outside.
Exposedtodirectlightandheatfromalamp,sun,fire­place, or other temperature--radiating object which may cause a false reading.
Close to or in direct airflow from supply registers and return--air grilles.
In areas with poor air circulation, such as behind a door or in an alcove.
3.7.4 Install Thermostat -- 12VDC
a. Turn off all power to unit. b. If an existing thermostat is being replaced:
1.Remove existing thermostat from wall.
3.8.1 Cool Only Thermostat (Part No. 11 10--421)
On power up, the LCD readout will display C (Cool Only).
3.8.2 Heat/Cool Thermostat (Part No. 1110--420)
On power up, the LCD readout will display HC (Heat/ Cool).
3.9 SET THERMOSTAT CONFIGURATION
While in configuration mode, three option choices can be made.
A -- Anticipator Value Adjustment d -- Display Temperature Fahrenheit/Celcius Selection oF -- Offset Adjustment For Room Temperature
3.9.1 Enter Configuration Mode
EnterandholdtheFANbuttonforapproximately 10 sec­ondsuntilroom temperaturedisappears and the display reads A. You are now in the configuration mode.
3-15
T--298
Page 40
NOTE
IftheFANbuttonispressedagainorif nobutton is pressed for two minutes, the thermostat will exit the configuration mode and return to nor­mal operation. To re--enter the configuration mode, the FAN button must be pressed and held for 10 seconds again.
While in the configuration mode, the following options are available:
A. ANTICIPATOR -- Value Adjustment
Thisadjustmentcontrolsthesensitivityandcyclerate of the thermostst. Higher numbers decrease the sensitivity and slow the cycle rate. Lower numbers increase the sensitivity and increase the cycle rate. However, a limiting feature will not allow more than 4 equipmentcyclesperhour,regardlessofsetting.Values can range from 1 to 3. Factory default setting is 2. This default selection will provide optimum performance in nearlyallinstallations.Tryitfirst. Donotchangesettings unless there is evidence of need to do so. Unlike conventional anticipators, this setting is not determined by current draw. There is no need to measure, know,or compensate for current.
To Adjust:
a. Enter configuration mode (if not already there). b. Use UP & DOWN buttons to display A. c. Press MODE button once to display current value. d. Use UP & DOWN buttons to move betweenvalues. e. Press MODE buttonto return to A.UP &DOWN
buttons now move between option choices A, d, oF or press FAN button to exit configuration mode.
d. Fahrenheit/Celsius Selection
This selection operates the thermostat in either Fahrenheit or Celsius.
To Select:
a. Enter configuration mode (if not already there). b. Use UP & DOWN buttons to display d. c. Press MODE button once to display current
selection of F or C. d. Use UP &DOWNbuttonstochangebetweenF&C. e. Press MODE buttonto return to d.UP &DOWN
buttons now move between option choices; or press FAN button to exit configuration mode.
oF. Room Temperature Offset Adjust Selection
The selected number is the number of degrees, plus or minus, which will be added to the actual temperature. The numbers can range between --5 and +5. Factory default is 0. This adjusted value will be used as actual temperature for both display and control action. The effect is that a positive number selection will make the room temperature lower, and vice versa. The thermostat is calibrated within an accuracy of plus or minus 2 degrees when shipped from the factory; this adjustment will provide thebestaccuracy whenset to o.
To Select:
a. Enter configuration mode (if not already there). b. Use UP & DOWN buttons to display oF .
c. Press MODE button once to display offset value. d. Use UP & DOWN buttons toselect a value between
--5 and 5. e. Press MODE buttonto return to oF.UP &DOWN
buttons now move between option choices; or press FAN button to exit configuration mode.
3.10 CHECK THERMOSTAT OPERATION
3.10.1 Fan Operation (Cool Only)
1. Press FAN button, starting fan operation. FAN an­nunciator turns on; Lo is displayed in the room tem­perature area for 5 seconds indicating Fan Low Speed.
2. Press FAN button, FAN annunciator remains on; Hi is displayed in room temperature area for 5 seconds indicating Fan High Speed.
3. Press FAN button, stopping fan operation. FAN an­nunciator turns off.
3.10.2 Fan Operation (Heat/Cool)
1. Press FAN button, starting low fan (Lo) operation. FAN annunciator turns on.
2. Press FAN button, starting high fan (Hi) operation. FAN annunciator remains on.
3. Press FAN button, stopping fan operation. FAN an­nunciator turns off.
3.10.3 Cooling Operation (Cool Only)
1. Press and release MODE button until COOL is dis­played.
2. Press DOWN button until LCD readout reads 10de­grees below room temperature. Cooling and High Fan system should begin to operate within 5 min­utes.
3.10.4 Cooling Operation (Heat/Cool)
1. Press and release MODE button until COOL is dis­played.
2. Press DOWN button until LCD readout reads 10de­grees below room temperature. Cooling and High Fan system should begin to operate within 5 min­utes.
3.10.5 Heating Operation (Heat/Cool)
1. Press and release MODE button until HEAT is dis­played.
2. PressUPbuttonuntilLCDreadoutreads10degrees above room temperature. Heating system should begin to operate within 1 minute.
3.11 CHECK THERMOSTAT OPERATION
3.11.1 Temperature Display
The thermostat will display room temperature until the UPorDOWN buttonispressed. The word SETappears when these buttons are pressed and the current set point is displayed. If no buttons are pressed for 5 seconds, the display will change back to show room temperature.
T--298
3-16
Page 41
3.11.2 Timeguard Timer
A 3--minute timeguard is built into the thermostat immediately upon power up, and any time the compressor (output “Y”) turns off. The compressor will notturn on until the timeguardhasexpired. Pressing UP and FAN buttons simultaneously will override the timeguard for 1 cycle.
3.11.3 Cycle Timer
In normal cooling (and heating) operation the thermostat will not allow more than 4 equipment cycles per hour (or 1 cycle every 15 minutes). Both the “Y” (cooling) and “W” (heating) outputs have a 15--minute timer that starts counting down when the output is turned on, (e.g., if “Y” output is turned on for 9 minutes and then satisfies, it cannout turn back on for another 6
minutes regardless of demand). However, pressing UP and F AN buttons simultaneously or changing the set point will override the timer for 1 cycle.
3.11.4 Minimum On Timer
Oncetheequipmenthasturnedon,itwillremainonfora minimum of 2 minutes regardless of demand. However, the equipment can turn off in less than 2 minutes if a change in set point, or a changein mode occurs.
3.11.5 Error Messages
E4 will be displayed if the thermostat has an internal memory failure. If E4 appears, replace the thermostat.
---- (two dashes) will be displayed if the thermostat cannot properly read the room temperature. If ---­appears, replace the thermostat.
UPPER UNIT
Motor Comp.
1234 2
1234
POWERBOX
ASSEMBLY
Factory Wiring Field Wiring
1
115V AC High V oltage
J
Power Supply
L
N2
N1
THERMOSTAT
1 2 3 4 5
W
Y
GH
GL
C
COOL (Compressor)
Y
FAN (High)
GH
GL
FAN (Low)
R
12VDC LowVoltage
Power Supply
C
CEILING UNIT
Figure 3-40 Wall Thermostat Wiring Diagram -- Cool Only Model
3-17
T--298
Page 42
UPPER UNIT
Motor Comp.
1234 21
Factory Wiring Field Wiring
1234
POWERBOX ASSEMBLY
J
115V AC High V oltage
Power Supply
L
N2
N1
THERMOSTAT
1 2 3
4
5
Blue
1
Blue
2
W
Y
GH
GL
C
TB
COOL (Compressor)
Y
FAN (High)
GH
GL
FAN (Low)
R
C
+ 12VDC
12VDC LowVoltage
Power Supply
12 VDC (Gnd)
T--298
CEILING UNIT
FURNACE
Figure 3-41 Wall Thermostat Wiring Diagram -- Heat/Cool Model
3-18
Page 43
SECTION 4
WIRING SCHEMATICS
4.1 INTRODUCTION
This Section contains wiring schematics for the AirV units. Figure 4--1 is the schematic for the standard upper unit assembly and it is applicable to all standard units. Figure 4--2 is the schematic for the Low Profile upper unit assembly. Figure 4--3 is the schematic for a free blow ceiling unit without heat while Figure 4--4 is a free blow unit with heat. Figure 4--5 is for a ducted unit with microprocessor control. Figure 4--6 is for an Upper Unit Heat Pump with free blowapplication and Figure 4--7 is the matching free blowceiling
unit. Figure 4--8 is for the Upper Unit Heat Pump ducted application and Figure 4--9 is the matching ducted ceiling unit. Notethat the ductedunits have 115VACpowerforthecomponents and 12 VDC power for themicroprocessorcontrol
system. Figure 4--10is for the ductedorfreeblowapplicationthatusesawall--mounted thermostat, with or without thefurnace
option. Where applicable, diagrams that designate 115Volt, 60 H, 1 Phase, arealsoavailableusing220Volts,50H,1Phase.
Most noteably Figure 4--1 and Figure 4--5.
4P
11
22
PLUG CONNECTS TO CEILINGUNIT SEE FIG> 4--3 OR 4--4
3
4
2P
1
2
(UNIT -- 99--00468--10)
4P
2P
1 2
PLUG CONNECTS TO CEILING UNIT.
WIRING.
SEE DIAGRAM SUPPLIED WITH
CEILING UNIT FOR ADDITIONAL
OLP: OVERLOAD PROTECTION PTC: STARTTHERMISTER JTB: JOINT TERMINAL BLOCK FMC: INDOORFAN MOTOR CAPACITOR
1 2 3 4
FAN MOTOR
2P
BLK
BLU
WHT
WHT
YEL
2
1
C
GRN/YEL
BLK
BLU
CONTROL
BOX
YEL
GRN/YEL
EVAP.
OVERLOAD PROTECTOR
(IfUsed)
COMPRESSOR
Figure 4--1 Upper Unit Schematic -- Standard & HC
WHT BRN
YEL
(IF USED)
1
OLP
4P
1
1
2
2
3
3
4
4
3P
1 2 3
(3)
YEL
1
WHT
2 3
BRN
YEL
2
COMPRESSOR
LEGEND
BLK BLU WHT
GRN/YEL
FMC
WHT
YEL
YEL
GRN/YEL
BRN
WHT
WHT
RED
R
S
BLK
BLU WHT BRN
S
BRN
RED
BLU
F
CAPACITOR
BLU
PTC
INDOOR FANMOTOR
OUTDOOR FANMOTOR
F
WHT
RED
BLU
PTC
(IF USED)
CAPACITOR
BLURED
GRN/YEL
Figure 4--2 Upper Unit Schematic -- Low Profile
4-1
T--298
Page 44
{
115 VAC SUPPLY WIRE
BLK
SW
GRN/YEL
4
BLK
4P
2
BLU
ASW
ORN
61
YEL
8
2
C
IT
ORN
1
12
2P
ORN
L
WHT
ASM
WHT
GRN/YEL
1
2
3
4
2P
WHT
YEL
1
2
Figure 4--3 Ceiling Unit Schematic -- Cooling Only
SWITCH
POSITION
HIGH FAN LOW FAN
OFF LOW COOL HIGH COOL
ASW
CONTACTS MADE
1--4 . 1--6 1--2 . 1--6
NONE
1--2 . 1--6 . 1--8
1--4 . 1--6 . 1--8
O (OFF)
I(ON)22--1
LEGEND
ASM : AIR SWEEPMOTOR
ASW :AIR SWEEPSWITCH
SEE DIAGRAM SUPPLIED WITH
SW : SWITCH
UPPER UNIT FOR ADDITIONAL WIRING.
IT : INDOORTHERMOSTAT
PLUG CONNECTS TO UPPER UNIT.
SW
H
L
L1
B
L2
WHT
GRN/YEL
A
YEL
RED
1
3
BLU
BLK WHT
1
1
3
HT
C
CEC
115 VAC SUPPLY WIRE
{
BLK
BLK
LEGEND
IDC Th : INDOoR COIL THERMISTER
RA Th : ROOM AIR THERMISTER
KY : RELAY
DI:DIODE
RATh
IDC Th
BLK
BRN
CN1
1 2 3 4
CONTROL
PCB
ASS’Y
24
135786
CN9
CN9
24135786
DISPLAYPCB AS
ORN
IT
2P
2
BLK
2
BLK
21
ASW
HEATER--ASSY
HEATER
BT
WHT
YEL
BLU
ORN
2P
ORN
112
WHT
ASM
WHT
WHT
GRN/YEL
4P
2P
1
2
3
4
1
PLUG CONNECTS TOUPPER UNIT.
UPPER UNIT FOR ADDITIONAL
2
SEE DIAGRAM SUPPLIEDWITH
Figure 4--4 Ceiling Unit Schematic -- Heat/Cool
23412
BLK
WHT
FUSE
250V 3.15A
D1
CN4
11
2 3 4
5 6
8
11 2 3
CN4
1 2 3 4 5 6 7 8 8
1 2 3
2 3 4
RY3
5 6 77
2 3
GRN/YEL
BLU
WHT
BLK
CN3
213
1Y
RY2
RY4
2
1
CN2
BLU
BLU
SWITCH
POSITION CONTACTS MADE
OFF
LOW FAN HIGH FAN
LOW COOL
HIGH COOL
HEAT
ASW
LEGEND
WIRING.
RY1
L N2 N1
2 1
CN1
L1--L .L1--A L1--H .L1--A
L2--C .L1--L. L1--A. B--3
L2--C .L1--H. L1--A. B--3
L2--HT.L1--L.L1--A.B--1
O (OFF)
1(ON)
ASM AIRSWEEP MOTOR ASW AIRSWEEP SWITCH SW SWITCH
IT INDOOR THERMOSTAT CEC CLOSED END CONNECTOR
BT BIMETAL
BLK
WHT
GRN/YEL
RED BLK
NONE
2
2--1
115 VAC POWER
12 VDC POWER
(+) (--)
T--298
Figure 4--5 Ceiling Unit, Standard -- Ducted
4-2
Page 45
4P 1
2 3 4
BLK BLU
WHT
GRN/YEL GRN/YEL
4P
1
1
2
2
3
3
4
4
FAN MOTOR
BLK
BLU
WHT
BRN
OLP: OVERLOAD PROTECTION PTC: STARTTHERMISTER RVC: REVERSING VALVECOIL
GRN/YEL
BRN
{
PLUG CONNECTS TO CEILING UNIT.
SEE DIAGRAM SUPPLIED WITH
115 VAC SUPPLY WIRE
BLK
BRN
EVAP.
BLK
2P
1
212
(IF USED)
1
BLK(BLU)
YEL
2
(3)
WHT
RVC
F
WHT
WHT
S
REDOLP
BLU
PTC
CAPACITOR
BLURED
CONTROL
2P 1
2
2P
1
WIRING.
CEILING UNIT FOR ADDITIONAL
2
BOX
RED
FREEZE
SWITCH
COMPRESSOR
Figure 4--6 Heat Pump -- Upper Unit -- Free Blow
BLK
BLK
BLK
SW
L1
L2
B
GRN/YEL
21
2
IT
ASW
BLK
BLU
BLK
WHT
ORN
11
2P
BLK
22
WHT
YEL
CEC
2P
ORN
WHT
112
2
WHT
GRN/YEL
ASM
BRN
WHT
L
ORN
A
HT
WHT
YEL
RED
HEATER AS
HEATER BT
1
33
L
1
4P
1
2
3
4
2P 1
2
PLUG CONNECTS TOUPPER UNIT.
2P
1
2
SWITCH
POSITION
OFF LOW FAN HIGH FAN
WIRING.
LOW COOL HIGH COOL
HEATING
ASM: AIRSWEEP MOTOR
UPPER UNIT FOR ADDITIONAL
SEE DIAGRAM SUPPLIEDWITH
ASW: AIRSWEEP SWITCH
SW: SWITCH
IT: INDOOR THERMOSTAT CEC: CLOSED END CONNECTO R
BT: BIMETAL
ASW
O (OFF)
LEGEND
L1--L .L1--A
L1--H .L1--A
L2--C .L1--L. L1--A. B--3
L2--C .L1--H. L1--A. B--3
L2--HT.L1--L.L1--A.B--1
1(ON)22--1
CONTACTSMADE
NONE
Figure 4--7 Heat Pump -- Ceiling Unit -- Free Blow
4-3
T--298
Page 46
1
2
3
1
2
3
4
1
2
1
PLUG CONNECTS TO CEILINGUNIT.
SEE DIAGRAM SUPPLIED WITH
2
WIRING.
CEILING UNITFORADDITIONAL
BRN
BLK
BLK
BLU
RED
GRN/YEL
CONTROL
BOX
BLK(BLU)
EVAP.
WHT
YEL
ODC Th
ODA Th
RVC
CN
BLK
1
BLU
2
RED
3
5
6
FAN MOTOR
GRN/YEL
WHT
BRN
BRN
WHT
COMPRESSOR
OLP
(IF USED)
1
YEL
C
2
(3)
CN
LEGEND
CN :HOUSING CONNECTOR PTC :STARTTHERMISTOR
OLP :OVERLOAD PROTECTOR
RVC :REVERSING VALVE COIL ODA Th :OUTDOOR AIR THERMISTOR ODC Th :OUTDOOR COIL THERMISTOR
C
RED
R
S
RED
BLU
PTC
F
H
CAPACITOR
BLU
Figure 4--8 Heat Pump -- Upper Unit -- Ducted
LEGEND
IDC Th: INDOOR COIL THERMISTER RA Th: ROOM AIR THERMISTER ODC Th: OUTDOOR COIL THERMISTER
ODA Th :OUTDOOR AIR THERMISTOR
RVC: REVERSING VALVE COIL D1: DIODE K: RELAY
RA Th
IDC Th
BLK
BRN
CN1
1
CONTROL PCB
2 3 4
1133576
CN9
CN9
DISPLAYPCBAS
ASS’Y
224
4
8
578
6
PLUG CONNECTS TOUPPER UNIT.
SEE DIAGRAM SUPPLIEDWITH UPPER UNIT
FORADDITIONAL WIRING.
GRN/YEL
CN3CN5
K4K3
FUSE
250V 3.15A
COMPRESSOR
BLK
Y
D1
FURNACE SIGNAL
ODC ODA
BLK
CN5 1
2 3
22 33 44 55 66 7
CN4
1 2 3
CN6
RED
BRN
7
CN4
1 2 33
CN6
RVC MOTOR
WHT
BLK
111 2 3
K7
4 5 6 7 888
POWER PCB ASS’Y
1
K6
2
12
CN2
BLU
11
22
33
41221
BLU
BLK
RED
11
22
34
K2
BLUBLU
Figure 4--9 Heat Pump -- Ceiling Unit -- Ducted
NOTE
*
FACTORY WIRING FIELD WIRING
*
(115VACHIGHVOLT.)
*
FIELD WIRING
WHT
L
K1
N2 N1
RED
2 1
BLK
CN1
(12VDC LOWVOLT.)
BLK
WHT
GRN/YEL
115VAC POWER
(+)
12VDC POWER
(--)
T--298
4-4
Page 47
Figure 4--10 Ceiling Unit -- Wall Thermostat -- Ducted & Free Blow
4.2 WALL MOUNTED THERMOSTA TS
For proper wiring of Wall Mounted Thermostats as an accessory, refer to Figure 3-40 (Wall Thermostat Wiring Diagram -- Cool Only Model) or Figure 3-41 (Wall Thermostat Wiring Diagram -- Heat/Cool Model).
4-5
T--298
Page 48
INDEX
A
Air Handling System , 3-8 Air Sweep Removal, 3-3 Air Sweep Switch , 3-2
C
Capacitor Testing, 3-9 Capacitor Testing and Replacement, 3-9 Ceiling Grill -- Ducted, 3-4 Ceiling Grill -- Free Blow, 3-1 Ceiling Panel -- Free Blow, 3-2 CEILING UNIT -- DUCTED SYSTEMS, 3-4 CEILING UNIT -- FREE BLOW , 3-1 Cleaning, 3-1 Compressor , 3-6, 3-13 Condenser Fan, 3-7 Control Box -- Ducted, 3-4 Control Box -- Upper Unit, 3-6
I
Indoor Thermostat , 3-3 INTRODUCTION, 1-1, 4-1
L
LCD DISPLAY, 3-15, 3-16 Leaks, 3-1
M
Main Pcb Board, 3-5 Master Control Switch, 3-2 Motor , 3-7 Mounting, 3-1
P
Painting, 3-1 PCB Display , 3-5 PREVENTATIVE MAINTENANCE, 3-1
Controls, 3-1 Cool Only Thermostat, 3-15
D
Design Change, 1-1
E
Evaporator Blower Wheel, 3-8 Exterior Cover, 3-5, 3-10, 3-15
F
Filter Removal -- Free Blow, 3-1 Filter Removal -- Ducted, 3-4 Fuse Removal -- Ducted, 3-5
H
R
REFRIGERANT CYCLE, 1-9, 1-10
S
Serial Number, 1-1 SERVICE -- GENERAL, 3-1 SERVICE -- UPPER UNIT -- LOW PROFILE, 3-10 SERVICE AND MAINTENANCE, 3-1 START--UP, 1-9
T
THERMOSTAT INSTALLATION AND START--UP IN-
STRUCTIONS (WALL MOUNTED), 3-15
TROUBLESHOOTING, 2-1, 2-3
U
Upper Scroll Assembly, 3-7, 3-10, 3-11, 3-12, 3-13
Heat Strip, 3-3 Heat/Cool Thermostat, 3-15
Index -1
W
WIRING SCHEMATICS, 4-1
T--298
Page 49
Carrier Transport Air Conditioning 50 Grumbacher Road York PA 17402 USA Tel: 1--800--673--2431 Fax: 1--717--764--0401
A member of the United Technologies Corporation family. Stock symbol UTX ©2006 Carrier Corporation D Printed in U. S. A. 0606
Carrier Transicold Division, Carrier Corporation Transport Air Conditioning Group P.O. Box 4805 Syracuse, N.Y. 13221 U.S A
www.carrier.transicold.com
Loading...