Carrier INFINITY ZONING CONTROL, SYSTXCCUIZ01-V, SYSTXCCUIZ01-B, Infinity SYSTXCCUIZ01-V Installation Instructions Manual

SYSTXCCUIZ01-- V Infinityt Control
Installation Instructions
ZONE
HEAT
HOLD
I
NFINITY™ SYSTEM
Fig. 1 -- Infinityt Zone Control
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 1...................................
INSTALLATION AND START--UP OVERVIEW 2..........
INSTALLATION 2....................................
INSTALLING INFINITY ZONE CONTROL 4..............
INITIAL POWER-- UP 6................................
QUICK START 8.....................................
INSTALL / SERVICE MENUS 9.........................
EQUIPMENT SUMMARY MENU 9......................
INSTALL MENU 9....................................
SETUP MENU 9......................................
CHECKOUT MENUS 14...............................
SERVICE MENUS 15..................................
OPERATIONAL INFORMATION 16.....................
TROUBLESHOOTING 19..............................
SYSTEM MALFUNCTION SCREEN 20..................
COOL
OFF
A04031
PAGE
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings and cautions included in literature and attached to the unit. Consult local building codes and the current edition of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING,andCAUTION. These words are used with the safety-- alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies hazards, which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
on
INTRODUCTION
The Infinity Zone System consists of several intelligent communicating components which includes the Infinity Zone Control (or User Interface), Smart Sensors, Damper Control Module, variable speed furnace or FE fan coil, 2--stage AC or HP and Infinity Packaged Products, which continually communicate with each other via a four--wire connection called the ABCD bus. Commands, operating conditions, and other data are passed continually between components over the ABCD bus. The result is a new level of comfort, versatility, and simplicity.
All Infinity furnaces or fan coils are variable--speed and multi--stage for maximum flexibility, efficiency, and comfort. They support controlled ventilation, humidification, dehumidification, and air quality control. Either an Infinity (communicating) or a standard 24VAC controlled outdoor unit may be used.
When using conventional outdoor units, the Infinity furnace or fan coil provides the 24 volt signals needed to control them. Also, the Infinity Damper Control Module (P/N SYSTXCC4ZC01) allows connection of a Carrier HRV or ERV without the need for a separate wall control.
All system components are controlled through the wall mounted Infinity Zone Control, which replaces the conventional thermostat and provides the homeowner with a single wall control for all features of the system.
Design Considerations
The Infinity Zone system is unique because a bypass damper must not be used. This is possible due to the intelligence of the system and variable speed motor technology. For trouble--free applications, the following parameters should always be met:
1. Zones should be sized so that each zone can deliver at least the minimum airflow for the system in both heating and cooling modes.
2. Oversize duct work by 25% to avoid excess noise at mini­mum zone airflow.
3. Be aware that heating airflow may be higher than cooling airflow depending on equipment combination.
INSTALLATION, ST ART--UP OVERVIEW
This instruction covers installation of the Infinity Zone Control only. Physical installation instructions for the indoor and outdoor equipment, Damper Control Module, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the Infinity Zone System are covered in this installation instruction. It is the guide to connecting the system components and
UIZ01--V
commissioning the system once all physical components are installed. Special screen prompts and start--up capabilities are provided in the Infinity System to simplify and automate the initial commissioning of the system.
S Install Infinity Zone Control according to this instruction.
S Install indoor unit, outdoor unit, and accessories according to
their instructions.
S Wire complete system according to this instruction.
S Setup, commission, and operate system according to this
instruction to assure a smooth and trouble free start--up.
INSTALLATION
Check Equipment and Job Site
Inspect equipment. File claim with shipping company prior to installation if shipment is damaged or incomplete.
Infinity Zone Control Location and Wiring Considerations
S Close to a window, on an outside wall, or next to a door leading
to the outside.
S Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature--radiating objects which could cause a false
reading.
S Close to or in direct airflow from supply registers.
S In areas with poor air circulation, such as behind a door or in an
alcove.
Remote Room Sensor Option
A Remote Room Sensor can be used with the Infinity Zone Control to take the place of the User Interface internal temperature sensor. This allows the Infinity Zone Control to be mounted in areas with less than optimal airflow (such as near an exterior door, window or in a closet). The remote sensor can be wired to the terminal block connectors labeled S1 and S2 at the User Interface backplate, or the ZS1 and ZS1C connection at the Damper Control Module. In either case, the Infinity Zone Control will automatically detect the Remote Room Sensor and ignore its internal temperature sensor. It is also important to note the humidity sensor cannot be remotely located, so do not locate the Infinity Zone Control in an area where humidity sensing may not be accurate.
In addition, the Remote Room Sensor is a temperature sensor only, having no additional user inputs. This sensor is typically connected to the Damper Control Module and used to sense and control temperature in each zone.
Remote Sensor Averaging
Typically, one Remote Room Sensor is used per zone, but multiple sensors may be used and averaged in some applications. Averaging requires a special series-- parallel wiring method with a specific number of sensors. See Fig. 2 in this manual for wiring diagram.
Damper Control
Module
ZS_
Sensor 1 Sensor 2
Damper Control
Module
ZS_C
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect power before routing control wiring.
All wiring must comply with national, local, and state codes.
Infinity Zone Control Location
The Infinity Zone Control User Interface is the command center for the Infinity Zone System and is typically located in Zone 1 to sense and control temperature in this zone. It should be located where it is easily accessible and visible to the adult homeowner or end user.
For accurate temperature measurement, the following guidelines should be followed:
The Infinity Zone Control and Room Sensors should be mounted:
S Approximately 5--ft (1.5 meters) from the floor.
S Close to or in a frequently used room, preferably on an inside
partitioning wall.
S On a section of wall without pipes or ductwork.
The Infinity Zone Control and Room Sensors should NOT be mounted:
Sensor 3 Sensor 4
A03233
Fig. 2 -- Remote Room Sensor -- Parallel Wiring
Smart Sensor
Any zone may use a Smart Sensor. It provides a temperature display and buttons to adjust the desired temperature in that zone only. It also displays outdoor temperature and indoor humidity sensed at the User Interface. Only one Smart Sensor may be used per zone. They cannot be averaged like Remote Room Sensors. If a Smart Sensor is used in a zone, a Remote Room Sensor may also be used in the same zone. The Remote Room Sensor has priority over the Smart Sensor. The Smart Sensor will display the Remote Room Sensor temperature.
NOTE: Smart Sensors must be addressed to identify which zone it will control. See Smart Sensor Installation Instructions for details.
Wiring Considerations
Ordinary thermostat wire is recommended. Use 22 AWG or larger for normal wiring applications. Continuous wire lengths over 100--ft. (3 m) should use 20 AWG or larger.
NOTE: ABCD bus wiring only requires a four--wire connection; however, it is good practice to run thermostat cable having more
2
than four wires in the event of a damaged or broken wire during installation.
Each communicating device in the Infinity Zone System has a four--pin connector labeled ABCD. It is recommended that the following color code be used when wiring each device:
A — Green = Data A B — Yellow = Data B C — White = 24VAC (Com) D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each ABCD connector in the system MUST be wired consistently.
If the thermostat wiring will be located near or in parallel with high voltage wiring, cable TV, or Ethernet wiring, then shielded thermostat wire can be used to reduce or eliminate potential interference. The shield wire should be connected to the C terminal, or ground, at the indoor unit. The shield wire should NOT be connected to any terminal at the user interface. Connecting the shield to ground at both ends can cause current loops in the shield, reducing shield effectiveness.
Shielded Wire
If the thermostat wiring will be located near or in parallel with high voltage wiring, cable TV, Ethernet wiring, or radio frequency equipment, then shielded thermostat wire can be used to reduce or eliminate potential interference. The shield wire should be connected to the C terminal, or ground, at the indoor unit. The shield wire should NOT be connected to any terminal at the user interface. Connecting the shield to ground at both ends can cause current loops in the shield, reducing shield effectiveness.
Locating Damper Control Module
All wiring is run back to the Damper Control Module. Select a location near the furnace or fan coil where wiring from the User Interface, each Remote Room Sensor or Smart Sensor, each damper actuator, and the equipment itself can come together easily.
The Damper Control Module is approved for indoor use only and should never be installed with any of its components exposed to the elements. The Damper Control Module (and zone dampers) may be installed in any area where the temperature remains between --4_F to 158_F(--20_Cto70_C), and there is no condensation. The cover must be installed to prevent damage from other sources. Do not locate where it will be accessible to children. It may be mounted in either vertical or horizontal position. Remember that wiring access is likely the most important consideration.
!
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
To prevent possible damage to the Damper Control Module, DO NOT mount on plenum, ductwork, or flush against furnace or fan coil.
CAUTION
Mounting Infinity Zone Control
There are two options for mounting the Infinity Zone Control to the wall. First, become familiar with all plastic assembly pieces shown in Fig. 3 through 10. The User Interface will snap together with either the Recess Mount or the Surface Mount backplate.
Recess Mount
This provides the thinnest mounting configuration (See Fig. 4). The backplate containing the recessed terminal block can be mounted directly to the wall by cutting a hole 1 1/2” (38.1 mm) wide by 2 1/8” (54 mm) high. Mark location and cut hole in wall.
NOTE: Always ensure the Infinity Zone Control location is acceptable before cutting any holes in wall.
Surface Mount
This provides surface mounting configuration, which allows use of a small hole in the wall. A surface mount backplate is supplied (See Fig. 5). Attach backplate as shown in Fig. 8, and the assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through.
NOTE: Once Infinity Zone Control is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs when removing. Gently remove Infinity Zone Control by rocking up/down until interlocking tabs release.
Decorative Backplate
Supplied is a thin decorative backplate (see Fig. 6) to hide any marks/screw holes left from the previous thermostat. This decorative backplate (or beauty ring) can be used in either the recess or surface mount installation by snapping it onto back of recessed mount backplate or surface mount backplate before securing to wall. See Fig. 9 and 10 for a larger decorative backplate P/N SYSTXXOLBP01 (5.75” / 146 mm wide x 6” / 1 52 mm high), which can be ordered separately.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing Infinity Zone Control, turn off all power to equipment. There may be more than one power source to disconnect.
1. Turn off all power to equipment.
2. If an existing User Interface or control is being replaced:
a. Remove existing control from wall.
b. Disconnect wires from existing control.
c. Discard or recycle old control.
NOTE: Mercury is a hazardous waste, if existing control contains any mercury, it MUST be disposed of properly. The User Interface does not contain mercury.
3. Select Infinity Zone Control mounting plastic (recess mount or surface mount and decorative backplate if desired).
4. Route wires through large hole in mounting plastic. Level rear plastic against wall (for aesthetic value only -- Infinity Zone Control need not be level to operate properly) and mark wall through two mounting holes.
5. Drill two 3/16--in. (4.8 mm) mounting holes in wall where marked.
6. Secure mounting plastic to wall using two screws and an­chors provided.
7. Adjust length and routing of each wire to reach each wire entry on the connector backplate. Strip 1/4--in. (6.4 mm) of insulation from each wire.
8. Match and connect thermostat wires to proper terminals on User Interface backplate. See wiring diagram Fig. 11, 12, and 13.
UIZ01--V
3
Recessed terminal block in wall 1
1
wide by 2
/8" (54 mm) high
Recessed Mount
Interlocking Tabs (4)
1
" (38.1 mm)
/
2
A03185
Fig. 3 -- Infinityt Zone Control
UIZ01--V
A03186
Fig. 4 -- Recessed Mount Backplate
Fig. 7 -- Recessed Mount Assembly
Surface Mount Backplate to wall
Interlocking Tabs (4)
Fig. 8 -- Surface Mount Assembly
A07150
A03191
Fig. 5 -- Surface Mount Backplate
Fig. 6 -- Thin Decorative Backplate
A03187
A04017
A03188
Fig. 9 -- Large Decorative Backplate
A03192
Fig. 10 -- Decorative Backplate Assembly
4
Zone Control
User Interface &
Smart Sensor(s)
A B C D
A B C D A B C D
Damper
Control module
Green
Yellow
White
Red
Humidifier
Connection
Indoor
Unit
HUM
COM 24V
OAT
A
B
C
D
Communicating
AC or HP
A
B
C
D
OAT
Sensor
(Optional)
A04018
Fig. 11 -- Communicating Indoor Unit w/2--Stage Puron
Refrigerant Communicating Outdoor Unit
Indoor
Zone Control
User Interface &
Smart Sensor(s)
A B C D
A B C D A B C D
Damper
Control module
Green
Yellow
White
Red
Humidifier
Connection
Unit
HUM
COM 24V
Y/Y2
OAT
A
B
C
D
1-Stage AC.
C
Y
OAT
Sensor
A04019
Fig. 12 -- Connection Diagram for Furnace or FE Fan Coil
with Non --Communicating 1--Stage AC
Green
Yellow
White
Red
Humidifier Connection
Variable-Speed
Fan Coil
A
B
C
D
HUM
C
G
R
O
W
Y
OAT
1-Spd. HP
C
R
O
W2
Y
OAT
Sensor
A07149
Zone Control
User Interface &
Smart Sensor(s)
A B C D
A B C D A B C D
Damper
Control module
Fig. 13 -- Connection Diagram for FE Fan Coil with
Non-- Communicating 1-- stage HP
A — Green = Data A B — Yellow = Data B
C — White = 24VAC (Com) D — Red = 24VAC (Hot)
NOTE: It is not mandatory that the above color code be used, but each ABCD connection in the system MUST be wired consistently. A separate ABCD Connector comes inside packaging and should be used when connecting to furnace (or fan coil). Ensure connector is inserted properly into circuit board. (See Fig. 14.)
ABCD
A03193
Fig. 14 -- Wire ABCD Connector
!
CAUTION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Improper wiring of the ABCD connector will cause the Infinity Zone System to operate improperly. Check to make sure all wiring is correct before proceeding with installation or turning on power.
9. Push any excess wire into the wall. Seal hole in wall to pre­vent any air leaks. Leaks can affect operation.
10. Attach Infinity Zone Control to the mounting plastic by lin­ing up the plastic guides on the back of the control with the opening on the mounting plastic and push on.
11. Perform installation of all other system equipment (i.e. dampers, humidifier, ventilator, UV lights, etc.).
12. Turn on power to equipment.
See wiring diagrams Fig. 11, 12, and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Module. More information regarding Damper Control set-- up and wiring can be found in Damper Control Module Installation Instructions.
See wiring diagram, Fig. 11, which includes an indoor communicating furnace or FE fan coil, with a 2 --stage Puron refrigerant communicating outdoor unit. No additional OAT (outdoor air temperature) sensor is required because the Infinity Zone Control will use the temperature sensor inside the outdoor unit.
See wiring diagram, Fig. 12, for connecting an indoor communicating furnace or FE fan coil with a 1 --stage air conditioning unit (non--communicating outdoor). An Outdoor Air Temperature (OAT) sensor may be installed (but is not required) at the indoor furnace or fan coil OAT terminals. When OAT sensor is applied, the Infinity System will provide enhanced system features and benefits.
In a hybrid heat installation with a non--communicating heat pump, an OAT sensor must be installed or the heat pump will not run.
See wiring diagram Fig. 13 for connecting an FE fan coil with a 1--stage heat pump (non--communicating outdoor unit). When OAT is applied, the Infinity System will provide enhanced system features and benefits.
NOTE: For other applications not listed, refer to the Network Interface Module (NIM) Installation Instructions.
Humidifier Connection
A 24VAC bypass or fan powered humidifier may be installed. NOTE: Do Not Use a traditional humidistat to control humidifier
operation. If a humidifier is installed, let the Infinity Zone Control operate humidifier.
Bypass Humidifiers
A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24VAC COM terminals. The Infinity Zone Control will automatically energize the HUM output during a call for humidification.
Fan Powered Humidifiers
Most fan powered humidifiers produce internal 24VAC in order to energize upon a switch or contact closure. For this application, a 24VAC N.O. Isolation Relay (DPST) MU ST be used to prevent mixing the internal humidifier power with the indoor equipment
5
UIZ01--V
transformer. Applying 24VAC isolation relay coil to furnace or fan coil HUM and COM terminals will allow the Infinity Zone Control to automatically energize the HUM output during a call for humidification. The N.O. relay contacts will be used to energize the humidifier. See fan powered humidifier installation instructions for more details.
ESTABLISHING
COMMUNICATIONS
WITH EQUIPMENT
PLEASE WAIT
SOFTWARE
VERSION
INDOOR UNIT
SEARCHING FOR
INDOOR EQUIPMENT
WORKING
OUTDOOR UNIT
SEARCHING FOR
OUTDOOR EQUIPMENT
WORKING
!
CAUTION
EQUIPMENT HAZARD
Failure to follow this caution may result in equipment damage.
Do not apply 24VAC fan powered humidifier (with internal power supply) direct to indoor unit HUM and COM terminals.
INITIAL POWER--UP
NOTE: Refer to Functional Overview (Fig. 15) to become
familiar with key function buttons such as “System On/Off”, “Zone”, “Fan”, “Left--Side” and “Right--Side” buttons, etc. These function buttons will be used frequently during setup.
UIZ01--V
Zone Button
Left-Side Button
Time (+/-) Button
Hold Button
Schedule & Vacation Program Buttons
Up/Down Scroll Buttons
ZONE
HOLD
SCHEDULE VACATION
PROGRAM
Schedule
to program
temperature
schedule
Vacation
to start/end
vacation
SCROLL
Scroll
up & down
BASIC
Basic
to set time,
humidity
SETUPS
ADVANCED
Advanced
for all other
settings
HEAT
COOL
Fig. 15 -- Functional Overview
Power Up Sequence
This section addresses initial power up (or commissioning) of a new Infinity Zone Control. The User Interface will communicate and identify all Infinity components in the system. The following is a typical example for a communicating Variable--Speed Furnace / Fan Coil with a 2--stage Air Conditioner / Heat Pump (including Hybrid Heat).
The User Interface display will light up and indicate that it is now “ESTABLISHING COMMUNICATIONS WITH EQUIPMENT PLEASE W AIT”. The User Interface will automatically continue by “SEARCHING FOR EQUIPMENT”, followed by “SEARCHING FOR OUTDOOR EQUIPMENT” (See Fig. 16). Once the indoor and outdoor equipment has been found, the Installer will be asked to select Accessories. Packaged Products will be automatically identified and the Installer will be asked to select Accessories. Proceed to Selecting Accessories.
Fan Button
Display Screen (LCD)
Right-Side Button
Heat Button
Cool Button
Temperature (+/-) Button
System On/Off Button
Basic & Advanced Setup Buttons
Flip Down Door
A04038
A03195
Fig. 16 -- Power Up Sequence
NOTE: If the variable-- speed indoor equipment (furnace or fan
coil) cannot be found, the User Interface will display “CANNOT COMMUNICATE WITH INDOOR UNIT”. This MUST be corrected before the initial power up sequence can continue. If indoor unit is found, but outdoor unit is not found, “OUTDOOR UNIT NOT IDENTIFIED” will appear. Proceed to the next section for Outdoor Unit Identification.
Selecting Outdoor Unit
If there is no communicating outdoor unit, the screen, shown in Fig. 17, will appear. Press either Left or Right Up/Down button to select AC (air conditioner), HP (heat pump), or None (no unit installed). Press right--side button to continue to next screen.
OUTDOOR UNIT
NOT IDENTIFIED
SELECT TYPE: NONE, AC, HP
PRESS +/- TO MAKE
SELECTION
CONTINUE
NONE
OUTDOOR UNIT
ENTER HEAT PUMP SIZE
18000 TO 60000 BTU
PRESS +/- TO MAKE
BACK CONTINUE
36000 BTU
SELECTION
OUTDOOR UNIT
HEAT PUMP
ENTER NUMBER OF SPEEDS, 1 or 2:
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
A03196
1
Fig. 17 -- Selecting Outdoor Unit
If either AC or HP has been selected as the outdoor unit type, the middle screen will appear (See Fig. 17). Press either Left or Right Up/Down button to select appropriate Btu size of outdoor unit, then press right side button to continue. If a NIM (Network Interface Module) is applied for non--communicating two-- stage outdoor equipment, select 1 or 2--stage compressor operation, and press right--side button to continue.
NOTE: Range of outdoor unit Btu selection is limited by model number of indoor unit installed. The Infinity Zone Control will not allow an outdoor unit size that is not supported by the installed indoor unit.
NOTE: On new system installations, the model and serial number will be recognized and displayed. On any indoor/outdoor board replacements, the equipment will be recognized but the exact model/serial number will not be displayed.
Selecting Indoor Evaporator Coil
If a furnace is installed with a variable capacity heat pump, a screen will appear to select the installed indoor evaporator coil. This selection is used to adequately calculate refrigerant charge required while in the Heat Pump Charging screens under the Heat Pump Checkout menu. Select “other” for non--Carrier evaporators.
Selecting Electric Heater
If the equipment is a fan coil, packaged heat pump, or packaged AC and the electric heater is not self--identifying, “ELECTRIC HEATER NOT IDENTIFIED” will appear (See Fig. 18). Press either Left or Right Up/Down button to select appropriate size of electric heater installed, then press right--side button to continue. An asterisks (*) will appear next to electric heater sizes that may cause excessive airflow.
6