Carrier SYSTXCCUID01- B User Manual

SYSTXCCUID01-- B Infinityt Control
Installation Instructions
HEAT
HOLD
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 1...................................
INSTALLATION AND START--UP OVERVIEW 1..........
INSTALLATION 2....................................
INSTALLING INFINITY CONTROL 4....................
INITIAL POWER--UP 5................................
QUICK START 7.....................................
INSTALL / SERVICE MENUS 7.........................
EQUIPMENT SUMMARY MENU 8......................
INSTALL MENU 8....................................
SETUP MENU 8......................................
CHECKOUT MENUS 12...............................
SERVICE MENUS 12..................................
OPERATIONAL INFORMATION 14.....................
TROUBLESHOOTING 15..............................
SYSTEM MALFUNCTION SCREEN 16..................
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage the Infinity System.
Recognize safety information. This is the safety-- alert symbol When you see this symbol on the equipment and in the instruction
COOL
OFF
A03149
PAGE
manual, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION.
These words are used with the safety --alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies a hazard, which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
The Infinity System consists of several intelligent communicating components which includes the Infinity Control (or User Interface), variable speed furnace or FE fan coil, 2--stage AC or HP and Infinity Packaged Products, which continually communicate with each other via a four--wire connection called the ABCD bus. Commands, operating conditions, and other data are passed continually between components over the ABCD bus. The result is a new level of comfort, versatility, and simplicity.
All Infinity furnaces or fan coils are variable--speed and multi stage for maximum flexibility, efficiency, and comfort. They support controlled ventilation, humidification, dehumidification, and air quality control. Either an Infinity (communicating), or a standard 24VAC controlled outdoor unit may be used.
When using conventional outdoor units, the Infinity furnace or fan coil provides the 24 volt signals needed to control them. Also, the Infinity Network Interface Module (P/N SYSTXCCNIM01) allows connection of a Carrier HRV or ERV without the need for a separate wall control.
All system components are controlled through the wall mounted Infinity Control, which replaces the conventional thermostat and provides the homeowner with a single wall control for all features of the system.
INSTALLA TION AND START--UP
OVERVIEW
This instruction covers installation of the Infinity Control only. Physical installation instructions for the indoor and outdoor equipment, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the Infinity System are covered only in this installation instruction. It is the guide to connecting the system components and commissioning the system once all physical components are installed. Special screen prompts and start--up capabilities are provided in the Infinity System to simplify and automate the initial commissioning of the system.
S Install Infinity Control according to this instruction. S Install indoor unit, outdoor unit, and accessories according to
their instructions.
S Wire complete system according to this instruction. S Setup, commission, and operate system according to this
.
instruction to assure a smooth and trouble free start--up.
INSTALLATION
Check Equipment and Job Site
Inspect equipment. File claim with shipping company prior to installation if shipment is damaged or incomplete.
Infinity Control Location and Wiring Considerations
!
WARNING
S1
Sensor 1
Sensor 2
S2
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect power before routing control wiring.
All wiring must comply with national, local, and state codes.
Infinity Control Location
The Infinity Control User Interface is the command center for the Infinity System. It should be located where it is easily accessible and visible to the adult homeowner or end user.
CCUID01 -- B
For accurate temperature measurement, the following guidelines should be followed:
The Infinity Control and Room Sensors should be mounted:
S Approximately 5 feet (1.5 meters) from the floor.
S Close to or in a frequently used room, preferably on an inside
partitioning wall.
S On a section of wall without pipes or ductwork.
The Infinity Control and Room Sensors should NOT be mounted:
S Close to a window, on an outside wall, or next to a door leading
to the outside.
S Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature--radiating objects which could cause a false
reading.
S Close to or in direct airflow from supply registers.
S In areas with poor air circulation, such as behind a door or in an
alcove.
Remote Room Sensor Option
A Remote Room Sensor can be used with the Infinity Control to take the place of the User Interface internal temperature sensor. This allows the Infinity Control to be mounted in areas with less than optimal airflow (such as near an exterior door, window or in a closet). The remote sensor can be wired to the terminal block connectors labeled S1 and S2 at the User Interface backplate, or the OS1 and OS1C connection at the Damper Control Module. In either case, the Infinity Control will automatically detect the Remote Room Sensor and ignore its internal temperature sensor. Typically, one remote sensor is used but, multiple sensors may be used and averaged in some applications. Averaging requires a special series--parallel wiring method with a specific number of sensors. See Fig. 2. It is also important to note the humidity sensor cannot be remotely located, so do not locate the Infinity Control in an area where humidity sensing may not be accurate.
NOTE: S1 & S2 connection on User Interface backplate is now used for Remote Room Sensor, NOT for OAT Sensor hookup.
Wiring Considerations
Ordinary thermostat wire is recommended. Use 22 AWG or larger for normal wiring applications. Continuous wire lengths over 100 ft. should use 20 AWG or larger.
Sensor 3
Fig. 2 -- Remote Room Sensor -- Parallel Wiring
NOTE: ABCD bus wiring only requires a four--wire connection;
however, it is good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during installation.
Each communicating device in the Infinity System has a four--pin connector labeled ABCD. It is recommended that the following color code be used when wiring each device:
A — Green = Data A
B — Yellow = Data B C — White = 24VAC (Com)
D — Red = 24VAC (Hot) It is not mandatory that the above color code be used, but each
ABCD connector in the system MUST be wired consistently.
Sensor 4
A07116
Mounting Infinity Control
There are two options for mounting the Infinity Control to the wall. First, become familiar with all plastic assembly pieces shown in Fig. 3 through 10. The User Interface will snap together with either the Recess Mount or the Surface Mount backplate.
Recess Mount
This provides the thinnest mounting configuration (see Fig. 4). The backplate containing the recessed terminal block can be mounted directly to the wall by cutting a hole 1 1/2” (38.1 mm) wide by 2 1/8” (54 mm) high. Mark location and cut hole in wall.
NOTE: Always ensure the Infinity Control location is acceptable before cutting any holes in wall.
Surface Mount
This provides surface mounting configuration, which allows use of a small hole in the wall. A surface mount backplate is supplied (see Fig. 5). Attach backplate as shown in Fig. 8, and the assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through.
NOTE: Once Infinity Control is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs when removing. Gently remove Infinity Control by rocking up/down until interlocking tabs release.
Decorative Backplate
Supplied is a thin decorative backplate (see Fig. 6) to hide any marks/screw holes left from the previous thermostat. This decorative backplate (or beauty ring) can be used in either the recess or surface mount installation by snapping it onto back of recessed mount backplate or surface mount backplate before securing to wall. See Fig. 9 and 10 for a larger decorative backplate P/N SYSTXXOLBP01 (5.75”/146 mm wide x 6”/152 mm high), which can be ordered separately.
2
A03185
A04017
Fig. 6 -- Thin Decorative Backplate
Fig. 4 -- Recessed Mount Backplate
Fig. 5 -- Surface Mount Backplate
A03186
A03187
Recessed terminal block in wall 1 wide by 2
Recessed Mount
1
1
/8˝ high
Interlocking Tabs (4)
Fig. 7 -- Recessed Mount Assembly
Surface Mount Backplate to wall
Interlocking Tabs (4)
Fig. 8 -- Surface Mount Assembly
/2˝
A03190
A03191
CCUID01 -- B
Fig. 9 -- Large Decorative Backplate
3
A03188
Fig. 10 -- Decorative Backplate Assembly
INSTALLING INFINITY CONTROL
!
WARNING
ELECTRICAL OPERATION HAZARD
CCUID01 -- B
Failure to follow this warning could result in personal injury, death or equipment damage.
Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
A03192
Variable-Speed
User Interface
A
B
C
D
S1
S2
Green
Yellow
White
Red
Optional Remote
Room Sensor
Furnace/ Fan Coil
Humidifier
Connection
A
B
C
D
HUM
COM 24V
OAT
Green
Yellow
White
Red
ABCD
Connections
OAT
Sensor
(Optional)
Communicating
AC or HP
A
B
C
D
Fig. 11 -- Universal Four--Wire Connection Diagram
Variable-Speed
User Interface
A
B
C
D
S1
S2
Optional Remote
Room Sensor
Furnace/Fan Coil
Green
Yellow
White
Red
Humidifier
Connection
Y/Y2
HUM
COM
A
B
C
D
24V
ABCD
Connection
1-Spd. Non-Communicating AC
C
Y
A03146
1. Turn off all power to equipment.
2. If an existing User Interface or control is being replaced: a. Remove existing control from wall.
b. Disconnect wires from existing control.
c. Discard or recycle old control.
NOTE: Mercury is a hazardous waste, if existing control contains any mercury, it MUST be disposed of properly. The User Interface does not contain mercury.
3. Select Infinity Control mounting plastic (recess mount or
surface mount and decorative backplate if desired).
4. Route wires through large hole in mounting plastic. Level
rear plastic against wall (for aesthetic value only -- Infinity Control need not be level to operate properly) and mark wall through two mounting holes.
5. Drill two 3/16” (4.8 mm) mounting holes in wall where
marked.
6. Secure mounting plastic to wall using two screws and an-
chors provided.
7. Adjust length and routing of each wire to reach each wire
entry on the connector backplate. Strip 1/4” (6.4 mm) of in­sulation from each wire.
8. Match and connect thermostat wires to proper terminals on
User Interface backplate. See wiring diagram Fig. 11, 12, and 13.
OAT
OAT
Sensor
A07022
Fig. 12 -- Connection Diagram for Furnace or FE Fan Coil
w/1--Stage AC
Variable-Speed
Humidifier
Connection
Fan Coil
A
B
C
D
HUM
C
G
R
O
W
Y
OAT
ABCD
Connection
1-Spd. Non-communicating HP
W2
Y
C
R
O
OAT
Sensor
A07023
User Interface
A
B
C
D
S1
S2
Green
Yellow
White
Red
Optional Remote
Room Sensor
Fig. 13 -- Connection Diagram for FE Fan Coil with
Non-- Communicating 1--stage HP
A — Green = Data A
B — Yellow = Data B C — White = 24VAC (Com)
D — Red = 24VAC (Hot) NOTE: It is not mandatory that the above color code be used, but
each ABCD connection in the system MUST be wired consistently. A separate ABCD Connector comes inside packaging and should
4
be used when connecting to furnace (or fan coil). Ensure connector is inserted properly into circuit board. (See Fig. 14.)
automatically energize the HUM output during a call for humidification. The N.O. relay contacts will be used to energize the humidifier. See fan powered humidifier installation instructions for more details.
ABCD
A03193
Fig. 14 -- Wire ABCD Connector
!
CAUTION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Improper wiring of the ABCD connector will cause the Infinity System to operate improperly. Check to make sure all wiring is correct before proceeding with installation or turning on power.
9. Push any excess wire into the wall. Seal hole in wall to pre-
vent any air leaks. Leaks can affect operation.
10. Attach Infinity Control to the mounting plastic by lining up the plastic guides on the back of the control with the open­ing on the mounting plastic and push on.
11. Perform installation of all other system equipment (i.e. dampers, humidifier, ventilator, UV lights, etc.)
12. Turn on power to equipment.
See wiring diagram, Fig. 11, which includes an indoor communicating furnace or FE fan coil, with a communicating outdoor unit. No additional OAT (outdoor air temperature) sensor is required because the Infinity Control will use the temperature sensor inside the outdoor unit.
See wiring diagram, Fig. 12, for connecting an indoor communicating furnace or FE fan coil with a 1 --stage air conditioning unit (non-- communicating outdoor). An Outdoor Air Temperature (OAT) sensor may be installed (but is not required) at the indoor furnace or fan coil OAT terminals. When OAT sensor is applied, the Infinity System will provide enhanced system features and benefits.
See wiring diagram, Fig. 13, for connecting an FE fan coil with a 1-- stage heat pump (non--communicating outdoor unit). When OAT is applied, the Infinity System will provide enhanced system features and benefits.
NOTE: For other applications not listed, refer to the Network Interface Module (NIM) Installation Instructions.
Humidifier Connection
A 24VAC bypass or fan powered humidifier may be installed.
NOTE: Do Not Use a traditional humidistat to control humidifier operation. If a humidifier is installed, let the Infinity Control operate humidifier.
Bypass Humidifiers
A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24VAC COM terminals. The Infinity Control will automatically energize the HUM output during a call for humidification.
Fan Powered Humidifiers
Most fan powered humidifiers produce internal 24VAC in order to energize upon a switch or contact closure. For this application, a 24VAC N.O. Isolation Relay (DPST) MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer. Applying 24VAC isolation relay coil to furnace or fan coil HUM and COM terminals will allow the Infinity Control to
!
CAUTION
EQUIPMENT HAZARD
Failure to follow this caution may result in equipment damage.
Do not apply 24VAC fan powered humidifier (with internal power supply) direct to indoor unit HUM and COM terminals.
Humidity/OAT Button
Left-Side Button
Time (+/-) Button
Hold Button
Schedule & Vacation Program Buttons
Up/Down Scroll Buttons
HOLD
SCHEDULE VACATION
Schedule
to program temperature
schedule
PROGRAM
Vacation
to start/end
vacation
SCROLL
Scroll
up & down
BASIC
Basic
to set time,
humidity
SETUPS
ADVANCED
Advanced
for all other
settings
HEAT
COOL
Fan Button
Display Screen (LCD)
Right-Side Button
Heat Button
Cool Button
Temperature (+/-) Button
System On/Off Button
Basic & Advanced Setup Buttons
Flip Down Door
A03194
Fig. 15 -- Functional Overview
INITIAL POWER--UP
NOTE: Refer to Functional Overview (see Fig. 15) to become
familiar with key function buttons such as “System On/Off,” “Fan,” “Left--Side” and “Right--Side” buttons, etc. These function buttons will be used frequently during setup.
Power Up Sequence
INDOOR UNIT
ESTABLISHING
COMMUNICATIONS
WITH EQUIPMENT
PLEASE WAIT
SOFTWARE
VERSION
SEARCHING FOR
INDOOR EQUIPMENT
WORKING
Fig. 16 -- Power Up Sequence
This section addresses initial power up (or commissioning) of a new Infinity Control. The User Interface will communicate and identify all Infinity components in the system. The following is a typical example for a communicating Variable--Speed Furnace / Fan Coil with a 2--stage Air Conditioner / Heat Pump (including Hybrid Heat).
The User Interface display will light up and indicate that it is now “ESTABLISHING COMMUNICATIONS WITH EQUIPMENT PLEASE W AIT”. The User Interface will automatically continue by “SEARCHING FOR EQUIPMENT”, followed by “SEARCHING FOR OUTDOOR EQUIPMENT” (see Fig. 16). Once the indoor and outdoor equipment has been found, the
OUTDOOR UNIT
SEARCHING FOR
OUTDOOR EQUIPMENT
WORKING
A03195
CCUID01 -- B
5
Installer will be asked to select Accessories. Packaged Products will be automatically identified and the Installer will be asked to select Accessories. Proceed to Selecting Accessories.
NOTE: If the variable--speed indoor equipment (furnace or fan coil) cannot be found, the User Interface will display “CANNOT COMMUNICATE WITH INDOOR UNIT”. This MUST be corrected before the initial power up sequence can continue. If indoor unit is found, but outdoor unit is not found, “OUTDOOR UNIT NOT IDENTIFIED” will appear. Proceed to the next section for Outdoor Unit Identification.
Selecting Outdoor Unit
OUTDOOR UNIT
NOT IDENTIFIED
CCUID01 -- B
SELECT TYPE: NONE, AC, HP
PRESS +/- TO MAKE
SELECTION
CONTINUE
NONE
Fig. 17 -- Selecting Outdoor Unit
If there is no communicating outdoor unit, the screen, shown in Fig. 17, will appear. Press either Time or Temp +/-- buttons to select AC (air conditioner), HP (heat pump), or None (no unit installed). Press right--side button to continue to next screen.
If either AC or HP has been selected as the outdoor unit type, the middle screen will appear (see Fig. 17). Press either Time or Temp +/-- buttons to select appropriate BTU size of outdoor unit, then press right side button to continue. If a NIM (Network Interface Module) is applied for non --communicating two--stage outdoor equipment, select 1 or 2--stage compressor operation, and press right--side button to continue.
NOTE: Range of outdoor unit BTU selection is limited by model number of indoor unit installed. The Infinity Control will not allow an outdoor unit size that is not supported by the installed indoor unit.
NOTE: On new system installations, the model and serial number will be recognized and displayed. On any indoor/outdoor board replacements, the equipment will be recognized but the exact model/serial number will not be displayed.
OUTDOOR UNIT
ENTER HEAT PUMP SIZE
18000 TO 60000 BTU
PRESS +/- TO MAKE
BACK CONTINUE
36000 BTU
SELECTION
OUTDOOR UNIT
HEAT PUMP
ENTER NUMBER OF SPEEDS, 1 or 2:
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
Selecting Electric Heater
ELECTRIC HEATER
NOT IDENTIFIED
ENTER SIZE: NONE, 5,10,15 KW
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
Fig. 18 -- Selecting Electric Heater
5 KW
1
A03196
A03197
An asterisks (*) will appear next to electric heater sizes that may cause excessive airflow.
NOTE: Range of electric heaters available is limited by model number of the equipment installed. The Infinity Control will not allow an electric heater size that is not supported by the installed equipment.
Hydronic Heat Applications
The --B non--zoned model of the Infinity Control supports 2 types of Hydronic Heat applications:
1. Hot water coil in combination with an FE fan coil and heat pump, or hot water coil as sole heat source with an FE fan coil.
2. Non--zoned FE fan coil combined with radiant hot water heat.
In either application, a Hydronic Heat kit should be installed in place of an electric heater. See FE fan coil Product Data for accessory part number. The system will identify that Hydonic Heat has been installed during the initial commissioning process. The system will treat the hot water coil as either auxiliary heat in a heat pump application, or the sole heat source. Setup options for Hydronic Heat applications are described in the Setup section of this instruction.
Selecting Accessories
ACCESSORIES
AIR FILTER TYPE: EAC MEDIA MEDIA + EAC
PRESS +/- TO MAKE
SELECTION
CONTINUE
AIR FILTER MEDIA TYPE HUMIDIFIER INSTALLED? U.V. LIGHTS INSTALLED?
EAC
ACCESSORIES
HUMIDIFIER INSTALLED?
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
YES
Fig. 19 -- Accessories —UV Lights
Once the indoor and outdoor equipment have been found or entered, the following screens will appear allowing the Installer to select the “AIR FILTER TYPE; HUMIDIFIER INSTALLED”; and “UV LIGHTS INSTALLED” (See Fig. 19). Use either Time or Temp +/-- buttons to make appropriate selections in the highlighted area on the display screen. Press right--side button to continue (or advance) to the next screen.
Air Filter Type
This accessory screen will appear first. The installer will need to enter the type of filter (MEDIA, EAC, or both). See Table 1 and make a selection using Time or Temp +/-- button, then press right--side button to continue.
Table 1 – Filter Selection
INSTALLED FILTER
1inchto4inchmedia MEDIA
High voltage EAC EAC
High voltage EAC + 1 to 4 inch media MEDIA + EAC
Infinity Air Purifier MEDIA
ACCESSORIES
U.V. LIGHTS INSTALLED?
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
YES
A03198
MENU
SELECTION
If the equipment is a fan coil, packaged heat pump, or packaged AC and the electric heater is not self--identifying, “ELECTRIC HEATER NOT IDENTIFIED” will appear (see Fig. 18). Press either Time or Temp +/-- buttons to select appropriate size of electric heater installed, then press right--side button to continue.
Humidifier Installed
This will appear after the Air Filter Type screen. Select whether a humidifier is installed on the system, YES or NO, then press right--side button to continue.
6
UV Lights Installed
This screen will appear to select whether UV lights are installed on the system, select YES or NO, then press right--side button to continue.
Equipment Summary
EQUIPMENT SUMMARY FURNACE 58MVB0100-12 AC FILTER EAC HUMIDIFIER YES UV LIGHTS YES
NO YES
24ANA136A003
NO YES
SETUP
COMPLETE!
SAVE
ALL SELECTIONS/
A07247
Fig. 20 -- Equipment Summary
The “EQUIPMENT SUMMARY” screen will appear after Accessories have been selected. This screen will give a summary of all equipment automatically found or manually selected. If a wrong selection was made, press left--side button (BACK selection) to go back to that particular screen and make changes. When everything is OK, press right--side button again to continue. (See Fig. 20.)
The “SETUP COMPLETE! SAVE ALL SELECTIONS?” screen will appear after Equipment Summary. To Save All Selections press (YES) right--side button. Pressing the left--side button (NO selection) will return to the Equipment Summary screen where changes can be performed to any of the equipment selection screens. After selecting YES, the initial power up sequence of the new Infinity Control is complete.
Static Pressure Check
STATI C
PRESSURE
CHECK
PLEASE WAIT
Fig. 21 -- Static Pressure Check
This screen will appear after Setup is exited. The system will perform a static pressure check. This process will take about 1 1/2 minutes to complete. When completed, a screen will appear displaying the static pressure (in inches) across the equipment at the expected highest delivered airflow. If the static pressure is over 1 inch, a warning will appear, but equipment operation and the TrueSenset dirty filter detection operation will not be affected.
NOTE: The static pressure check occurs only at initial installation, or when INSTALL is run in the INSTALL/SERVICE menu.
EXTERNAL STATIC PRESSURE MEASURED:
0.72 INCHES AT 1200 CFM
CONTINUE >
A05000
QUICK START
For first time installers, Quick Start will allow a quick start up of the Infinity System before learning all the details of system operation. However, for the best possible comfort and operation refer to the Infinity Control Owner’s Manual.
Set Day, Time & Desired Humidity
1. Flip down the door at the base of the Infinity Control and press the BASIC button.
2. Adjust the highlighted HOUR setting using the TIME (+/--) button.
3. Press SCROLL button (down) to highlight MINUTE.
4. Adjust the MINUTE setting using the TIME (+/--) button.
5. Press SCROLL button (down) to highlight DAY.
6. Adjust the current DAY setting using the TIME (+/--) but­ton.
7. Press SCROLL button (down) to highlight HUMIDITY.
8. Press the red HEAT button to select heating humidity.
9. Adjust desired heating humidity level using either (+/-- ) but­ton.
10. Press the blue COOL button to select cooling humidity.
11. Adjust the desired cooling humidity level using ei­ther(+/--)button.
12. To exit press BASIC button or close door.
13. If changes are made, you will be asked to “SAVE
CHANGES? YES/NO.”
Override Heating Schedule
1. Press the red HEAT button. Heating mode is confirmed when the red LED next to the red HEAT button is lit.
2. Use the TEMP (+/--) button to select your desired heating temperature.
3. The default time for temporarily overriding the temperature schedule is 2:00 HRS as indicated by the text on the lower left.
NOTE: Override time will not appear if programming has been turned off.
4. You can change the temporary override time in 15--minute increments by pressing the TIME (+/--) button until the de­sired override time is selected, or press the HOLD button anytime to override the schedule indefinitely.
Quick Program Schedule For All Days
This section will give you a quick program schedule for ALL DAYS of the week. For more information on how to create
customized schedules for every day, the entire week, or weekend, refer to the Owner’s Manual.
1. Flip down the door at the bottom o f the control.
2. Press the SCHEDULE button, which allows you to create one schedule for the entire home.
3. Press either the LEFT or RIGHT side button repeatedly (if necessary) until “ALLDAYS” is displayed. The WA KE time period will be highlighted.
4. Using the TIME (+/.) button, set the start time for this time period.
5. Press the red HEAT button. Heating temperature will begin flashing.
6. Set the heating temperature using the TEMP (+/.) button.
7. Press the blue COOL button. Cooling temperature will be­gin flashing.
8. Set the cooling temperature using the TEMP (+/.) button.
9. Set the remaining periods by using the SCROLL button to select “DAY”, “EVENING”, and “SLEEP”.
10. Exit the scheduling mode by either closing the door or pressing the SCHEDULE button.
11. If changes are made, you will be asked to “SAVE
CHANGES YES/NO.
INSTALL / SERVICE MENUS
The “INSTALL / SERVICE” menus contain a set of vital information. This information enables the Installer or Service person to view a summary of what has been installed, etc. This information is not covered in the Owner’s Manual.
To e n ter INSTALL / SERVICE menus, press and hold the ADVANCED button for at least ten seconds. The following menu will appear (See Fig. 22):
CCUID01 -- B
7
INSTALL/SERVICE
EQUIPMENT SUMMARY INSTALL SETUP CHECKOUT SERVICE
SOFTWARE VERSION 1
EXIT SELECT
Fig. 22 -- Install / Service Menus
NOTE: The INSTALL / SERVICE menu will automatically exit
after 60 minutes of no push button activity.
EQUIPMENT SUMMARY: Shows all equipment recognized by and attached to the system.
INSTALL: Used when adding, changing out, or un-- installing equipment.
SETUP: Used to view or modify equipment settings. CHECKOUT: Allows testing of equipment operation SERVICE: Used to view operation and fault history of equipment
and enter dealer name/phone number for display
CCUID01 -- B
EQUIPMENT SUMMARY MENU
This screen shows indoor unit type and model number, outdoor unit type (and model number if a 2--stage unit), filter type and any accessories that are installed are recognized. See Fig. 23.
EQUIPMENT SUMMARY FURNACE 58MVB0100-12 AC FILTER EAC HUMIDIFIER YES UV LIGHTS YES
NO YES
24ANA136A003
Fig. 23 -- Equipment Summary
INST ALL MENU
This menu item will perform start--up process in order to learn all equipment in system. Press right side button to initiate the process. See Fig. 24.
INSTALL
TO ADD, UNINSTALL OR RE-INSTALL EQUIPMENT, PRESS RIGHT SIDE BUTTON
BACK INSTALL
Fig. 24 -- Install Menu
A03200
A07025
A03202
SETUP MENU
This menu has several layers, allowing modification of equipment settings. No settings will need to be made at equipment (i.e. DIP switches on a furnace). All configuration settings made effective from this menu will override equipment configuration made by dip switches. Fig. 25 shows all the information that can be found in the SETUP menu.
SETUP
THERMOSTAT FURNACE HEAT PUMP ACCESSORIES SYSTEM MAINTENANCE
BACK SELECT
A03203
Fig. 25 -- Setup Menu
Setup -- Thermostat
Auto Mode Setup:
S Enable/Disable Auto Changeover mode (default=Enable).
S Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).
When Auto mode is enabled (factory default) a change from heat to cool (or vice versa) will not occur until the current cycle is satisfied and an opposite mode demand has existed for 30 minutes. If the setpoint is changed, the 30 minute timer is deleted.
Heat/Cool Deadband:
S 0to6_F/0to3_C, (default = 2_F)
The minimum difference enforced between heating and cooling desired temperatures. This can allow one setting to “push” the other to maintain this difference.
Offsets:
This option allows calibration (or deliberate miscalibration) of the temperature and humidity sensors. These offsets are added to the actual temperature/humidity values (defaults=0).
S Temperature Offset: --5_Fto+5_F(--3_Cto+3_C)
S Outside Temp Offset: --5_Fto+5_F(--3_Cto+3_C)
S Humidity Offset: --10 to +10%
Cycles Per Hour:
S Maximum cycles per hour = 4 (default) or 6.
S Anticipator = 1 to 9 (default=3). This adjusts sensitivity to
temperature changes. 1 = most sensitive, 9 = least sensitive.
S If space is over--conditioning, increase the anticipator setting.
S If space is under--conditioning, decrease the anticipator setting.
Programming:
S ON (default)-- allows program schedule to be set by user.
S OFF -- system becomes non --programmable
S Periods Per Day = 2 or 4 (default=4)
S Programmable Fan On/Off (default=Off). If ON is selected, fan
can be set to Auto, Low, Med, or High.
Smart Recovery:
S On or Off (default=On)
Applies to programmable operation only. Will start recovery 90 minutes prior to schedule change in both heating and cooling mode. Refer to operational information for more detail.
English/Metric Display:
S_For_C, (default = _F)
8
Reset Factory Defaults:
Program Schedule:
S Yes/No to reset back to Energy Star default Time and Temp
schedules.
User Settings:
S Yes/No to reset the user settings in the Advanced Setup to
factory default settings.
Install Settings:
S Yes/No to reset install settings in Install/Service menus to factory
default settings.
Last 10 System Events:
S Yes/No to reset last 10 events under Service Info menu.
Setup -- Furnace
Upon a first time start--up of the Infinity Control, the furnace DIP switch settings will be copied to the furnace setup menu. Any changes can then be made from the Infinity Control.
Airflow:
S COMFORT (default)
S EFFICIENCY
Selects the airflow of the furnace when heating. EFFICIENCY is the airflow used to meet specified ratings, COMFORT is a decreased airflow used to increase the output air temperature and provide increased comfort.
AC Airflow:
S COMFORT (default) -- cooling airflow is varied depending on
humidity and temperature demands settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When COMFORT is not selected, the unit will not run
reduced airflows for dehumidification.
S EFFICIENCY -- fixed airflow used to achieve specified ratings --
no dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2--stage outdoor unit is used.
S MAXIMUM -- 400 CFM/ton. No dehumidification airflow
reduction.
Dehum Airflow:
S NORMAL (factory default) -- When equipment is running to
dehumidify, the airflow is allowed to adjust to a minimum to
satisfy the dehumidification call.
S HIGH -- Minimum airflow during the dehumidify mode is
increased to reduce duct and register sweating.
Low Heat Rise
S ON
S OFF (default)
Set to ON if the system contains a bypass humidifier. The ON setting will increase the furnace low heat airflow.
Staging
S SYSTEM (default)
S LOW
S HIGH
S FURNACE
NOTE: Controls the staging of the furnace. More staging options will be available if furnace is capable of more stages. SYSTEM setting will allow the Infinity Control to determine furnace staging. LOW will only run the low stage of furnace heat. HIGH will only run the high stage of furnace heat. FURNACE will allow the furnace algorithm to control staging.
G Terminal
This setup option selects desired operation when the R--G circuit changes state on the furnace control board depending on setup.
S DISABLED (Default)
S FAN -- turns on fan to selected fan speed when G terminal is
energized. See Fig. 26.
S FAN SPEED -- select Low, Med, High for all zones when G
terminal is energized
S SHUTDOWN -- shuts off fan and equipment when initiated.
This function is not intended for emergency fire shutdown. It
may be activated by a dry contact from an external device such
as a float switch or a relay. User Interface displays SYSTEM
MALFUNCTION on screen and registers G terminal shutdown
event in Last 10 System Events. See Fig. 27.
R
CCUID01 -- B
FE Fan Coil or Variable Speed Furnace
G
A07114
Fig. 26 -- G Input Wiring for Blower Operation
R
FE Fan Coil or Variable Speed Furnace
G
A07115
Fig. 27 -- G Input Wiring for System Shutdown
with (-- B) Infinityt Control (Contact type selectable;
Normally Closed (default) or Normally Open)
High Stage Timer
Minimum amount of time low stage must operate before high stage is activated. T en to 60 minutes. 10 = default
A demand of 5_F/3_C or more will override the staging timer.
Off Delay
S 90 seconds
S 120 seconds (default)
S 150 seconds
S 180 seconds
Amount of time the blower will continue to run after heating has shut off.
9
Setup -- Fan Coil
HP/AC Airflow:
S COMFORT (default) Cooling airflow is varied depending on
humidity and temperature demand settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When COMFORT is not selected, the unit will not run
reduced airflows for dehumidification. Heat Pump airflow is
varied depending on outdoor temperature to maximize comfort.
S EFFICIENCY -- fixed airflow used to achieve specified ratings --
no dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2--stage outdoor unit is used.
S MAXIMUM -- 400 CFM/ton. No dehumidification airflow
reduction.
Dehum Airflow:
S NORMAL (factory default) -- When equipment is running to
dehumidify, the airflow is allowed to adjust to a minimum to
satisfy the dehumidification call.
S HIGH -- Minimum airflow during the dehumidify mode is
CCUID01 -- B
increased to reduce duct and register sweating. Also increases
minimum airflow during normal cooling operation to reduce
duct sweating.
Heater Size:
S (choices dependent upon fan coil model)
This will show the heater size entered during the start--up process. This value can be changed to another value (limited by the model number of the fan coil). If the electric heater is self--identifying, this value is not shown.
Elect Heat Lockout
S NONE (default)
S +5 to 55_F / --15 to 13_C
Outside temperature above which the electric heat will not operate except for defrost.
G Terminal
This setup option selects desired operation when the R--G circuit changes state on the fan coil control board depending on setup.
S DISABLED (Default)
S FAN -- turns on fan to selected fan speed when G terminal is
energized. See Fig. 26.
S FAN SPEED -- select Low, Med, High for all zones when G
terminal is energized
S SHUTDOWN -- shuts off fan and equipment when initiated.
This function is not intended for emergency fire shutdown. It
may be activated by a dry contact from an external device such
as a float switch or a relay. User selects whether the contact is
NC -- normally closed (default) or NO -- normally open. User
Interface displays SYSTEM MALFUNCTION on screen and
registers G terminal shutdown event in Last 10 System Events.
See Fig. 27.
Setup -- Heat Pump / AC
Cooling Lockout:
S NONE (default)
S 45_F/7_C
S 50_F/10_C
S 55_F/13_C
Outside temperature below which cooling will not be provided.
Low Ambient Cooling:
S NO (default)
S YES
Selecting YES will enable the low ambient cooling operation in the outdoor unit. This setting is only available with communicating outdoor units and with Cooling Lockout set to NONE.
For detailed sequence of operation, see outdoor unit installation instructions.
Entered Size:
S (dependent on indoor unit model)
Size of the outdoor unit entered during the start--up process. If the outdoor unit is a communicating model, this value will not be shown. This size can be changed here but is limited to sizes that the indoor unit can handle.
Defrost Interval:
S 30 minutes
S 60 minutes
S 90 minutes
S 120 minutes (default)
S Auto--Defrost interval optimized by outdoor control (default for
communicating HP)
Time interval at which defrost cycles can occur on a heat pump.
High Cool Latch:
S NONE (default)
S On
S 80 to 110_F / 27 to 43_C
Outside temperature above which only the high stage (of a 2--stage outdoor unit) will run when cooling.
High Heat Latch
S OFF (default)
S On
S 20 to 50_F/--7to10_C 2 --stage heat pump runs only high
stage heating below a selectable outdoor temperature. Selections
from20to50_F/--7to10_C are available in 5_F/3_C
increments.
10
Setup -- Hybrid Heat
HYBRID HEAT SETUP
FURNACE LOCKOUT:
> 30 F
HEAT PUMP LOCKOUT:
< 15 F
DEFROST W/FURNACE: YES
< BACK
HP TO FURNACE STAGE TIME:
15 MIN
OUTSIDE LOCKOUT TEMPS
FURNACE LOCKOUT -- Temperature above which only the heat pump will operate, except for defrost.
S Default = NONE
S Available settings = NONE thru >55_F/13_C
HEAT PUMP LOCKOUT -- Temperature below wh ich only the furnace will operate.
S Default = NONE
S Available settings = NONE thru <55_F/13_C
DEFROST W/FURNACE -- Choose whether furnace operates during defrost cycle.
S Default = YES
S Available settings = YES / NO
HP TO FURNACE STAGING TIME -- Ad just the minimum amount of time the heat pump will run before furnace will be allowedtorun.
S Default = 15 MIN
S Available settings = 15--60 minutes. If a demand of 5_F/3_Cor
greater exists, the timer will be overridden.
Setup -- Hydronic Heat
HOT WATER LOCKOUT -- Outside temperature above which the hot water will not operate except for defrost (if needed).
S Available settings -- NO, 5 to 55_F / --15 to 13_Cin1_
increments
HEAT PUMP LOCKOUT -- Outside temperature below which only the hot water will run, 1_F/.6_C resolution.
S Appears only with a heat pump outdoor unit.
S Available settings -- NO, 5 to 55_F / --15 to 13_Cin1_
increments
DEFROST W/WATER:
S Available settings: YES / NO (Default =YES)
S Appears only if heat pump is available If no, hot water will not
run during a defrost.
AIRFLOW -- Selects desired airflow during Hydronic Heating
S Available range from OFF, 500 CFM(minimum) to 400
CFM/ton cooling maximum in 50 CFM increments.
Fig. 28 -- Hybrid Heat Setup
HYDRONIC HEAT SETUP HOT WATER LOCKOUT: HEAT PUMP LOCKOUT:
DEFROST W/WATER:
AIRFLOW:
BLOWER ON DELAY:
BLOWER OFF DELAY:
< BACK
> 30 F
< 45 F
YES
800 CFM
30 SEC
30 SEC
Fig. 29 -- Hydronic Heat Setup
A07030
A07031
S Default is the cooling airflow. (350 CFM/ton)
S OFF selection does not turn off airflow if heat pump is
defrosting.
BLOWER ON DELAY -- Time after hot water is requested that the blower will turn on.
S Available settings -- 0 to 240 seconds in 30 second increments
S Default is 30
BLOWER OFF DELA Y-- Time after hot water request terminates before the blower will turn off.
S Available settings -- 0 to 240 seconds in 30 second increments
S Default is 0.
Setup -- Accessories
Filter Type:
S MEDIA (i.e. TrueSenset)
S EAC
S MEDIA+EAC (i.e. TrueSenset)
CLEAN INTERVAL: 30 to 180 days (of actual blower operation). (Default = 90)
Interval at which the Clean Filter notification will turn on. Applies to EAC filter selection only.
Humidifier Installed:
S NO
S YES
If YES, indicates to the system whether a humidifier is installed and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months (default=12 months) Interval at which the Change Humidify Pad notification will be
displayed. HUMIDIFY WITH FAN: (Heating Mode Only)
S NO (default)
S YES
If YES, the humidifier will turn on if there is a humidify demand present. The fan will turn on to Low speed if the fan setting is Auto.
Ventilator:
NOTE: Only appears if ventilator is installed.
CLEAN INTERVAL:
S 60 to 180 days of actual operation (default=90)
Interval at which the Clean Ventilator Pre--filter notification will turn on.
UV Lights Installed
S NO
S YES
If YES, indicates to the system whether UV lights are installed. CHANGE INTERVAL:
S 6 to 48 months operation time (default=12 months)
Interval at which the Change UV Lights notification will be displayed.
Setup -- System Maintenance
Remind Owner of Routine Maintenance Every:
This setup is used to adjust the timer interval in which the normal System Maintenance notification is turned on for the homeowner. (See Fig. 30.)
Range =
S OFF
S 6 to 24 months, (default=12 months)
11
CCUID01 -- B
SYSTEM MAINTENANCE
REMIND OWNER OF MAINTENANCE EVERY:
12 MONTHS
% USED: 50%
< BACK
RESET >
Fig. 30 -- System Maintenance
Pressing the right side button will reset the timer. Pop --up confirmation will be shown.
Setup -- Utility Saver
Cooling/Heat Pump Heating: (Hybrid Heat & Hydronic Heat Only)
S Turn off, Low Stage
Utility Saver is used to force the equipment to a lower stage (low or off) when activated by the utility company, typically during peak load times.
CCUID01 -- B
This setup is available only if the equipment has a utility saver input (refer to equipment Installation Instructions.) This setup controls the response of the equipment when the utility saver input is active.
The choices include:
S Turn Off , (equipment turns off)
S Low Stage (available if the AC/heat pump is a 2--stage model,
runs low speed only)
CHECKOUT MENUS
The Checkout menu will show the equipment installed in the system. A sample checkout menu is shown in Fig. 31.
CHECKOUT
FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR
BACK SELECT
Fig. 31 -- Checkout Menu
Checkout -- Furnace or Gas PAC
Make sure the furnace is properly installed before continuing.
S LOW HEAT RUNTIME: 5 min.
S HIGH HEAT RUNTIME: 5 min.
This menu item allows the furnace to be exercised. First, a low heat runtime and high heat runtime are selected. Range = 5 -- 120 min.
If only the low heat is to be exercised: The furnace will execute its ignition start--up sequence. This
sequence will be displayed on the Infinity Control screen. After the gas valve and blower motor turn on, the screen will automatically change to “FURNACE CHECK” and show the current operating status of the furnace.
Checkout -- Electric Heat
S ELECTRIC HEAT RUNTIME: 5 min., Default time = 5 min.,
Range = 0 -- 120 min.
If you have a fan coil with electric heaters, this menu item will allow the heaters to be exercised.
A07033
A03204
With self--identifying electric heaters, three stages of electric heat are available to be exercised in any combination. Non--identifying heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be exercised then press START (right--side button). The display will change to show the fan coil’s operating status.
Checkout -- Heat Pump Heating
S HIGH HEAT RUNTIME: 5 min.
S LOW HEAT RUNTIME: 5 min.
S DEFROST: NO
The heat pump heating mode can be exercised with this menu option. With a 2 --stage heat pump, a low heat runtime and a high heat runtime are independently selectable to exercise. A defrost cycle is also selectable. Default time = Fixed 5 min. minimum, range = 5 -- 120 min.
NOTE: Airflows during Checkout modes are fixed to the Efficiency setting and are independent of other airflow settings. To view airflows for normal heat pump heating mode, exit the Checkout screen and apply a heating demand to the system.
Checkout -- H eat Pump Cooling or AC Cooling
S HIGH COOL RUNTIME: 5 min.
S LOW COOL RUNTIME: 5 min.
The heat pump cooling mode (or AC cooling mode) can be exercised with this menu option. With a 2--stage heat pump or AC unit, a low cool runtime and a high cool runtime are independently selectable to exercise. The display will change to show the heat pump or AC operating status.
Default time = Fixed 5 min. minimum, range = 5 -- 120 min.
NOTE: Airflows during Checkout modes are fixed to the Efficiency setting and are independent of other airflow settings. To view airflows for normal heat pump heating mode, exit the Checkout screen and apply a heating demand to the system.
Checkout -- Humidifier
S OFF
S ON
The humidifier can be exercised On and Off with this menu option.
Checkout -- Ventilator
Speed:
S OFF
S LOW
S HIGH
The ventilator can be exercised through all of its operating speeds with this menu option.
Checkout -- System Access Module (SAM)
See System Access Module Installation Instructions for full details.
SERVICE MENUS
The Service Info menu will only show the equipment installed in the system. Below is a sample using a furnace and a heat pump (Hybrid Heat). A sample service menu is shown in Fig. 32.
SERVICE INFO
FURNACE STATUS HEAT PUMP STATUS LAST 10 SYSTEM FAULTS RUN/FAULT HISTORY TODAY’S DATE MODEL/SERIAL NUMBER SERVICE PHONE NUMBER
BACK SELECT
A03205
Fig. 32 -- Service Info Menu
12
Service -- Furnace Status or Gas PAC Status
LAST 10 EVENTS
LOW PRESSURE
3/2/05
2:35 PM
< BACK MORE >
HP
3 EVENTS:
225 EVENTS _
ACTIVE
FN 2/28/05 6:10 PM 41-BLOWER MOTOR FAULT
F
SWITCH OPEN
F=FAULT
The Status screens will show all of the current operating parameters of each installed piece of equipment.
NOTE: To view a less detailed Equipment Status screen, press and hold the right side button for 3 seconds. This will display equipment stage, fan status, actual and target humidify settings.
Heat Stage:
S OFF, LOW, HIGH
Displays stage of heat that the furnace is currently delivering.
Airflow CFM:
S (furnace model dependent)
Cubic Feet per Minute of air the blower is currently delivering.
Inducer RPM (90% furnaces only):
S Inducer motor RPM value.
Blower RPM:
S Actual RPM feedback from indoor blower motor.
Static Press:
S Inches of water. Displays the calculated static pressure that the
fan coil is currently experiencing.
S If static pressure cannot be accurately calculated, the display will
read UNKNOWN. When this is seen, the system is adjusting to
high static pressure by cutting back blower RPM.
Lockout Timer:
S Seconds
If a lockout timer is active, this will show the current time value. See furnace manual for details on lockout timers.
Service -- Fan Coil Status
Electric Heat:
S OFF, LOW, MED, HIGH
Displays stages of electric heat that the fan coil is currently delivering.
Airflow CFM:
S (fan coil model number dependent)
Cubic Feet per Minute of air the User Interface is currently requesting.
Blower RPM:
S Actual blower motor RPM value
Static Press:
S Inches of water. Displays the calculated static pressure that the
fan coil is currently experiencing.
S If static pressure cannot be accurately calculated, the display will
read UNKNOWN. When this is seen, the system is adjusting to
high static pressure by cutting back blower RPM.
Service -- Heat Pump / AC Status
Stage: (Heat / Cool)
S OFF, LOW, HIGH
Displays stage of heating or cooling that the Heat Pump/AC is delivering.
Defrost:
S NO, YES
Displays status of defrost mode if heat pump.
Airflow CFM:
S Airflow User Interface is requesting from blower.
Outdoor Coil Temp:
S_For_C (default = _F)
Temperature of the outdoor unit coil (only available on 2--stage communicating outdoor units).
Blower RPM:
S Actual RPM feedback from indoor motor.
Static Press:
S Inches of water. Displays the calculated static pressure that the
fan coil is currently experiencing.
S If static pressure cannot be accurately calculated, the display will
read UNKNOWN. When this is seen, the system is adjusting to
high static pressure by cutting back blower RPM.
Service -- Last 10 System Events
A07032
Fig. 33 -- Last 10 System Events
CCUID01 -- B
This screen will show last 10 events that occurred throughout the system. Each entry has the time and date incident recorded. Service technician should enter current date in “TODAY’S DATE”menu section BEFORE checking and logging the last 10 system events.
Each entry has a two--letter acronym preceding the event name to identify which piece of equipment generated the event. This event history can be cleared under Thermostat Setup, Reset Factory Defaults.
HP = Heat Pump
AC = Air Conditioner FN = Furnace
FC = Fan Coil SPP = Packaged product SAM = System Access Module
Service -- Run / Fault History
The indoor unit and outdoor unit (if communicating) have the following histories:
NOTE: For Critical Fault Screens, see Troubleshooting section in this document.
Resettable Faults:
S Fault counters for each piece of equipment that can be reset.
Cycle Counters:
S Number of heat/cool/power cycles the unit has performed.
Run Times:
S Lifetime hours of operation in heating, cooling, and how long
the unit has been powered.
Service -- Today’s Date
This menu item allows the installer to enter the current date. It is used for time/date stamping of system faults. This should be entered every time prior to viewing “LAST 10 SYSTEM EVENTS” section.
Service -- Model / Serial Numbers
This menu item allows the installer to view the model number and serial number (if available) of all communicating pieces of equipment in the system. This is only available in original factory supplied circuit board. If a circuit board is replaced, the model and serial number information is no longer available.
Service -- Service Phone Number
This menu item allows the installer to enter a name and phone number that the homeowner can call for future service of the
13
system. This name and phone number will appear to the homeowner whenever a service reminder pop--up message is displayed (i.e. Change Filter, etc.)
To edit:
S Use Temp +/-- button to move cursor left and right.
S Use Time +/-- button to select numbers and letters.
S Use Scroll button to move up and down between NAME and
NUMBER.
OPERATIONAL INFORMATION
Continuous Fan Operation
Pressing FAN button will scroll through the following:
S AUTO = No fan operation except during equipment operation.
S LOW = Approximately 50% of High Speed operation.
S MED = Half way between High and Low speed operation.
S HIGH = Highest of either High Heating or High Cooling CFM.
Continuous fan operation is programmable. The programming option must be enabled in the Thermostat Setup. See the Homeowner’s Manual for detailed instructions on programming the fan.
CCUID01 -- B
Five--Minute Compressor Timeguard
This timer prevents compressor from starting unless it has been off for at least 5 minutes. It can be defeated by simultaneously pressing the Fan and Temp + buttons.
Emergency Heat (for heat pump applications)
To activate Emergency Heat, you must press and hold the HEAT button for 3 seconds to activate. Repeat to deactivate.
Heat Source Selection (Hybrid or Hydronic Heat)
If user wishes to override normal operation in Hybrid Heat or Hydronic Heat applications, press and hold the heat button for 3 seconds to select desired heat source.
Keypad Lockout
Keypad can be locked by pressing “Fan” and “Humidity/Oat” buttons at the same time for 3 seconds. When keys are locked, a lock symbol will appear in the upper left corner of screen. Follow same procedure to unlock keypad.
Heat and Cool LED
The Heat and Cool LEDs will pulsate during actual equipment operation. This can be defeated in the Advanced Setup Screens.
Equipment Cycle Timer (adjustable 4--6 cycles per hour)
This timer prevents the start of a heating or cooling cycle until 15 (or 10) minutes after the last start of the same cycle. Its function is to assure that the equipment is not cycled more than the selected times per hour. This timer is adjustable from 4 to 6 cycles per hour. This timer is defeated for one cycle when the desired temperature is manually changed. It can also be defeated for one cycle by simultaneously pressing the Fan and Temp + buttons.
Staging Timer
In multistage heating or cooling, this timer prevents any higher stage from turning on until the preceding stage has been on for 10 minutes.
For furnace heating, the high stage timer is adjustable to force longer minimum low stage run time. See Furnace Setup for details. A demand of 5_ or more will override the staging timer and allow higher stages to energize.
In Hybrid Heat, the staging timer is 15 minutes between heat pump and gas furnace operation. This timer is adjustable in the Hybrid Heat Setup menu to force longer minimum heat pump run time and
longer low stage furnace run time. A demand of 5_F or more will override the staging timer and allow higher stages to energize.
Three--Minute Minimum On Time
In normal operation, when a stage turns on, it will remain on for a minimum of three minutes. If the setpoint is changed, this timer is automatically cancelled, allowing the equipment to turn off immediately when the demand is removed.
Heat/Cool setpoints (Desired Temperatures)
A minimum difference of 2_ (default) is enforced between heating and cooling desired temperatures. This is done by allowing one setting to “push” the other to maintain this difference. This difference is adjustable via the Install/Service menu under Thermostat Setup.
Temperature Display
The actual temperature displayed is always rounded toward the setpoint. This is because the system is operating and measuring the temperature in sixteenths of a degree, but displaying in whole numbers. The system may be turned off and on within .5_ of setpoint, but the display may not change. This is by design and does not indicate a problem with the control.
Auto Changeover
When Auto mode is enabled (factory default) a change from heat to cool (or vice versa) will not occur until an opposite mode demand has existed for 30 minutes. If the setpoint is changed, the 30-- minute requirement is defeated. This Auto Changeover time is adjustable via the Install/Service menu under Thermostat Setup. Range = 5 -- 120 min.
Smart Recovery
With Smart Recovery selected (factory default), transition out of setback begins 1.5 hours before selected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time. It operates in both heating and cooling. This only applies to programmable operation.
For example: Set back temperature in heating is 64_F. Sma rt Recovery setpoint is 70_F at 7:00 a.m. At 5:30 a.m., the control calculates the required temperature recovery rate (recovery temp -­set back temp or current temp if greater) / 90 minutes. If the current temp at 5:30 = 66_F, the recovery rate = (70 -- 66)_F/90 minutes =
0.04_ per minute. In order to achieve setpoint, the control ramps up the setpoint 0.04_F / minute from 5:30 a.m. until 7:00 a.m.
NOTE: Temperatures should not be set back so far that the equipment cannot recover in 90 minutes.
Media Filter
If MEDIA or MEDIA+EAC is installed in the indoor unit, the system will perform a static pressure check of the system every 24 hours at 1:00 p.m. to monitor filter accumulation (TrueSenset Dirty Filter Detection) or whenever power is applied to the system or the system is transitioned from Off to Cool or Heat modes. The blower will run at a medium airflow for one minute.
This system operates by setting a base line static pressure based on the highest airflow the system could run (this could be heat or cool airflow.) The measurement is taken at a low airflow and then calculated up to the highest airflow the system could see.
Selecting MEDIA will use TrueSense filter detection. Selecting MEDIA+EAC will use either TrueSense or the clean interval selection, whichever happens first.
Frozen Coil Detection
During cooling operation, the User Interface will monitor the static pressure of the system. If the static pressure is increasing dramatically, the User Interface will turn off cooling for up to one hour, record fault in the “Last 10 Events” screen, and run the fan at a reduced airflow. The User Interface will continue to monitor the
14
static pressure. If it is reduced before one hour has elapsed, it will resume cooling operation. After one hour, cooling will be resumed.
Dehumidify Operation
Once a target cooling humidity setpoint is selected in the Advanced Setup COOLING HUMIDITY screen, two other setup options affect Dehumidify operation: AC AIRFLOW and DEHUMIDIFY.
AC AIRFLOW: This setting is located in the Furnace or Fan Coil Setup screens and must be set to COMFORT to enable normal dehumidify operation. If set to EFFICIENCY or MAXIMUM, no special dehumidify operation will take place during a normal cooling call. Cooling will only operate to satisfy the space temperature setpoint.
DEHUMIDIFY: Located in the Cooling Humidity screen of the Advanced Setup, this option has 2 settings: ON and OFF.
If DEHUMIDIFY is set to ON (factory default), then the cooling unit will be allowed to overcool the space up to 3_F/2_Cifthe humidity level is above the cooling humidity target setpoint.
The amount of over--cooling allowed varies with the dehumidification demand, the cooling demand, and the actual space temperature. More over--cooling is allowed with greater dehumidification demand.
When the space temperature is at or above 75_F/24_Candthe dehumidify demand is high, over--cooling up to 3_F/2_Cis allowed. As the space temperature approaches 70_F/21_C, less over--cooling is allowed. At 70_F/21_C space temperature, no more over--cooling is allowed no matter how great the dehumidify demand. This is done to protect the equipment.
If DEHUMIDIFY is set to OFF and AC Airflow is set to COMFORT, normal dehumidification mode is enabled. For
normal dehumidification, no over-- cooling is allowed when the cooling humidity is above the target setpoint, but airflow will be reduced during a normal cooling mode to reduce humidity. The airflow depends on the amount of dehumidify demand. If AC Airflow is set to EFFICIENCY or MAXIMUM, only Dehumidify (over--cooling to dehumidify) will be performed.
Hybrid Heat Setup / Operation
Furnace Lockout — (in HYBRID HEAT SETUP menu) is the
outside temperature above which the furnace will not run except for defrost (otherwise known as the aux heat lockout).
Heat Pump Lockout — (in HYBRID HEAT SETUP) is the outside temperature below which the heat pump will not run (otherwise known as the balance point).
These values can be set identical to each other. If they are not identical, the system will stage up and down normally from heat pump to furnace when the outside temperature is between these settings. The User Interface will not allow the heat pump lockout setting to be above the furnace lockout setting.
The factory default settings for both of these is NONE (no lockouts). Even though a heat pump lockout temperature may be set, the system will still use the furnace in defrost operation, and may stage back down to heat pump when defrost is completed after a2minutedelay.
Hybrid Heat Defrost — (in HYBRID HEAT SETUP) When the outdoor unit needs a defrost cycle, the furnace will run during defrost regardless of lockout temperature, unless told not to in the Hybrid Heat Setup screen. After defrost, the system may stage down to heat pump after a 2 minute delay.
CCUID01 -- B
TROUBLESHOOTING
Please refer to the Troubleshooting Guide available on HVAC Partners for more detail.
Infinity Control does not power up.
1. Recheck wiring to ABCD on all devices.
2. Make sure all colors match for every terminal.
3. Make sure power is applied to the indoor unit, and the amber LED is lit on indoor control circuit board.
4. Check for 24VAC between the C and D terminals at Infinity Control terminal connector and Damper Control Module.
5. Check fuse on indoor unit’s circuit board.
Display says “Indoor Unit Not Found”
1. Recheck wiring to ABCD on all devices.
2. Make sure all colors match for every terminal.
3. Press left--side button to try again.
4. If display still reads “Indoor Unit Not Found”, disconnect accessories and all devices from ABCD and connect User Interface directly to indoor unit with a short piece of thermostat wire. Add other devices one at a time to determine where the communication issue exists.
Display says “Outdoor Unit Not Found” and I have a two--stage communicating outdoor unit:
1. Recheck wiring to ABCD connector on outdoor unit.
2. Make sure all colors match for every terminal.
3. Check for 24VAC between the C and D terminal connector of outdoor unit.
I made a mistake on the start--up screens and pressed the right--side button to get to the run mode. How do I get back to start--up?
1. Press the ADVANCED button for at least 10 seconds.
2. Install/Service menu will appear.
3. Scroll down to the INSTALL selection.
4. Press the right--side button; the screen will prompt you to press the right side again to re--install the system.
To check current system status.
1. Press and hold the right side button for 3 seconds. This will display the current active system faults.
2. If no faults are active, the Status screen will show status of each component in the system.
15
SYSTEM MALFUNCTION SCREEN
OUTSIDE: 84_ |FAN:AUTO
71_
HVAC SERVICE
1---800---555--- 1212
SYSTEM MALFUNCTION
CALL TECHNICIAON
Fig. 34 -- System Malfunction Screen
Fan Coil
The code number represents flash code on circuit board of fan coil.
Certain faults will generate a system malfunction message on the main screen. When this occurs, a technician should proceed to the Last 10 System Events screen in the Service Menu to determine which fault has caused the message.
A new feature in the --B model is that the Status screen (right side
CCUID01 -- B
button press for 3 seconds) will reveal the active fault to the homeowner.
Below is a list of which faults will result in a System Malfunction event:
Code 37 -- Heater output sensed On when not energized
Code 41 -- Blower Motor Fault (ventilator, humidifier, dehumidifier, outdoor unit will be turned off)
Code 44 -- Motor Communication Fault (ventilator, humidifier, dehumidifier, outdoor unit will be turned off)
Code 45 -- Control failure
Furnace
The code number represents flash code on circuit board of furnace. Code 13 -- Limit Circuit Lockout Code 14 -- Ignition Lockout
Code 15 -- Blower Motor Lockout (ventilator, humidifier, dehumidifier, outdoor unit will be turned off)
Code 21 -- Gas Heating Lockout Code 22 -- Abnormal Flame Proving Signal
Code 23 -- Pressure Switch Did Not Open Code 24 -- Secondary Voltage Fuse Open Code 33 -- Limit Circuit Fault AND high heat only is active
Code 41 -- Blower Motor Fault (cooling mode only) (ventilator, humidifier, dehumidifier, outdoor unit will be turned off)
Code 45 -- Control Circuitry Lockout NOTE: For codes 13, 14 and 21, the system will use heat pump
heating exclusively if available. When the error code is cleared or disappears, furnace heating will resume if still requested.
A07036
Outdoor Unit
The code number represents flash code on circuit board of outdoor unit.
Code 25 -- Invalid model plug Code 45 -- Control Failure
Code 47 -- No 230V at unit Code 73 -- Contactor shorted
Code 74 -- No high voltage at compressor Code 76 -- Low stage didn’t start three times
Code 78 -- High stage didn’t start three times Code 81 -- Thermal lockout in low stage -- 4 hrs. Code 82 -- Thermal lockout in high stage -- 4 hrs.
Code 83 -- Low Pressure Lockout -- 4 hrs. Code 84 -- High Pressure Lockout -- 4 hrs.
Code 85 -- Low contactor open Code 86 -- Low contactor shorted Code 87 -- High contactor open
User Interface
S Temp sensor failed, loss of communication with smart sensor,
smart sensor fault. “NO SENSOR DATA” shown
S Indoor unit communication fault
S Outdoor unit communication fault
S Packaged product communication fault
S NIM communication fault
S SAM communication fault
S Possible Frozen Coil
S High Room Temp Alert, when 100_F exists for at least 10
minutes, and removed when less than or equal to 98_Fexists
S Low Room Temp Alert, when 38_F exists for at least 10
minutes, and removed when greater than or equal to 40_Fexists
S High Humidity Alert, when 80% Rh exists for 30 minutes, and
removed when less than or equal to 78% Rh exists
The user can press the right side button to dismiss the notice. The regular run mode screen will then appear except “SYSTEM MALFUNCTION” will appear in place of the day/time. If the error has not disappeared within 24 hours, the above display will return. If the error code disappears, “SYSTEM MALFUNCTION” will disappear and the day/time will reappear.
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in China Edition Date: 03/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
C a t a l o g N o : U I D 0 1 --- 4 S I
Replaces: UID01---3SI
Loading...