Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or installation may damage Infinity Control System. Recognize safety
information. This is the safety-alert symbol
symbol on the equipment and in the instruction manual, be alert to
the potential for personal injury. Understand the signal words
DANGER, WARNING, and CAUTION.
COOL
OFF
A03149
. When you see this
SYSTXCCUID01
Infinity Control™
These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards, which will result in severe
personal injury or death. WARNING signifies a hazard, which
could result in personal injury or death. CAUTION is used to
identify unsafe practices, which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
INTRODUCTION
The Infinity System consists of intelligent communicating components (User Interface, variable speed furnace or fan coil, AC or
HP), which continually communicate with each other via a
four-wire connection called the ABCD bus. Conventional 24-volt
signals on dedicated wires are not needed. Commands, operating
conditions, and other data are passed continually between the
components over the ABCD bus. The result is a new level of
comfort, versatility, and simplicity.
An Infinity System consists of a Infinity Control™ (thermostat
plus much more) and an Infinity furnace or fan coil. All Infinity
furnaces or fan coils are variable-speed and multi stage for
maximum flexibility, efficiency, and comfort. They support controlled ventilation, humidification, dehumidification, and air quality control. Either an Infinity dual capacity (communicating), or a
standard 24 vac controlled outdoor unit may be used.
When using conventional outdoor units, the Infinity furnace or fan
coil provides the 24 volt signals needed to control them. Also, the
Infinity Network Interface Module (NIM) allows connection of a
conventional HRV or ERV without the need for a separate wall
control.
All system components are controlled through the wall mounted
Infinity Control™, which replaces the conventional thermostat and
provides the homeowner with a single wall control for all the
features of the system.
INSTALLATION AND START-UP OVERVIEW
This instruction covers installation of the Infinity Control™ only.
Physical installation instructions for the indoor, outdoor equipment
and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the
Infinity System is covered only in this installation instruction. It is
your guide to connecting the system components and commissioning the system once all the physical components are installed.
Special screen prompts and start-up capabilities are provided in the
Infinity System to simplify and lead you through the initial
commissioning of the system. So:
• Install the Infinity Control™ according to this instruction.
• Install the indoor unit, outdoor unit, and accessories according
to their instructions.
• Wire the complete system according to this instruction.
• Setup, commission, and operate the system according to this
instruction to assure yourself a smooth and trouble free
start-up.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab misc. misc.
PC 101Catalog No. 809-50020Printed in U.S.A.Form UID01-1SIPg 101-04Replaces: NEW
INSTALLATION
STEP 1 — CHECK EQUIPMENT AND JOB SITE
INSPECT EQUIPMENT — File claim with shipping company,
prior to installation, if shipment is damaged or incomplete.
STEP 2 — INFINITY CONTROL™ LOCATION AND WIRING
CONSIDERATIONS
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or possible equipment damage.
Disconnect Power before routing control wiring.
All wiring must comply with national, local, and state codes.
INFINITY CONTROL™ LOCATION— The Infinity Control™
is the command center for the Infinity System. It should be located
where it is easily accessible and visible to the adult homeowner or
end user.
For accurate temperature measurement, the following guidelines
should be followed:
The Infinity Control™ should be mounted:
• Approximately 5 feet (1.5 meters) from the floor.
• Close to or in a frequently used room, preferably on an inside
partitioning wall.
• On a section of wall without pipes or duct work.
The Infinity Control™ should NOT be mounted:
• Close to a window, on an outside wall, or next to a door leading
to the outside.
• Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature-radiating objects which could cause a false
reading.
• Close to or in direct airflow from supply registers.
• In areas with poor air circulation, such as behind a door or in
an alcove.
REMOTE SENSOR OPTION — A remote room sensor can be
used with the Infinity Control™ to take the place of the internal
temperature sensor. This allows the control to be mounted in areas
with less than optimal airflow (such as near an exterior door,
window or in a closet). The remote sensor is wired to the terminal
block connectors labeled S1 and S2. The Infinity Control™ will
automatically detect the remote sensor and ignore its internal
sensor. It is also important to note the humidity sensor cannot be
remotely located, so do not locate the Infinity Control™ in an area
where humidity sensing may not be accurate.
NOTE: S1 & S2 connection on UI back-plate is now used for the
Remote Room Sensor, NOT for OAT Sensor hookup (S1 & S2
was previously used for OAT).
WIRING CONSIDERATIONS — Ordinary thermostat wire is
recommended. Use 22 AWG or larger for normal wiring applications. Continuous wire lengths over 100 ft. should use 20 AWG or
larger.
NOTE: ABCD bus wiring only requires a four-wire connection;
however, it is good practice to run thermostat cable having more
than four wires in the event of a damaged or broken wire during
the installation.
Each device in the Infinity System has a four-pin connector labeled
ABCD. It is recommended that the following color code be used
when wiring each device:
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each
ABCD connector in the system MUST be wired consistently.
MOUNTING INFINITY CONTROL™—There are two options
for mounting the Infinity Control™ to the wall. First, familiarize
yourself with all plastic assembly pieces shown in Figs. 2 through
9. The User Interface will snap together with either the Recess
Mount or the Surface Mount backplate.
RECESS MOUNT — This provides the thinnest mounting configuration (See Fig. 3). The backplate containing the recessed
terminal block can be mounted directly to the wall by cutting a
hole 1 ½″ wide by 2 1/8″ high. Mark location and cut hole in wall.
NOTE: Always ensure the Infinity Control™ location is accept-
able before cutting any holes in wall.
SURFACE MOUNT — This provides surface mounting configuration, which allows use of a small hole in the wall. A surface
mount backplate is supplied (See Fig. 4). Attach backplate as
shown in figure 7, and the assembly will mount directly to the wall
requiring only a small hole in the wall allowing a four wire
connection to pass through.
NOTE: Once Infinity Control™ is secured to wall with the
backplate assembly (snapped together), care must be taken not to
bend or break the interlocking tabs when removing. Gently remove
Infinity Control by rocking up/down until interlocking tabs release.
DECORATIVE BACKPLATE — Supplied, is a thin, decorative
backplate (see Fig. 5), to hide any marks/screw holes left from the
previous thermostat. This decorative backplate (or beauty ring) can
be used in either the recess or surface mount installation by
snapping it onto the back of the recessed mount backplate or
surface mount backplate before securing to the wall. See Fig. 8 and
9 for a larger decorative backplate (5.75″ wide X 6″ tall), which
can be ordered separately.
A03185
Fig. 2—Infinity Control™
STEP 3 — INSTALLING INFINITY CONTROL™
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing Infinity Control™, turn off all power to
equipment. There may be more than one power source to
disconnect.
1. Turn off all power to equipment.
2. If an existing thermostat is being replaced:
a. Remove existing thermostat from wall.
b. Disconnect wires from existing thermostat.
2
Recessed terminal
block in wall 11/2˝
wide by 2 1/8˝ high
Recessed Mount
Interlocking T abs (4)
Fig. 3—Recessed Mount Backplate
Fig. 4—Surface Mount Backplate
A03186
A03187
Fig. 6—Recessed Mount Assembly
Surface Mount
Backplate to wall
Interlocking T abs (4)
Fig. 7—Surface Mount Assembly
A03190
A03191
A04017
Fig. 5—Thin Decorative Backplate
c. Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and MUST be disposed of
properly.
3. Select Infinity Control™ mounting plastic (recess mount or
surface mount and decorative backplate if desired).
4. Route wires through large hole in mounting plastic. Level rear
plastic against wall (for aesthetic value only - Infinity Control™ need not be level to operate properly) and mark wall
through two mounting holes.
5. Drill two 3/16 inch mounting holes in wall where marked.
6. Secure mounting plastic to wall using two screws and anchors
provided.
7. Adjust length and routing of each wire to reach each wire
entry on the connector backplate. Strip ¼ inch of insulation
from each wire.
A03188
Fig. 8—Large Decorative Backplate
8. Match and connect thermostat wires to proper terminals on
User Interface backplate. See wiring diagram figures 12, 13
and 14.
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
NOTE: It is not mandatory that the above color code be used, but
each ABCD connection in the system MUST be wired consistently. A separate ABCD Connector comes inside packaging and
should be used when connecting to the furnace (or fan coil). (See
Fig. 10)
NOTE: Insert connector properly into circuit board.
3
Humidity/OAT
Button
Fan Button
Display Screen
(LCD)
A03192
Fig. 9—Decorative Backplate Assembly
ABCD
A03193
Fig. 10—4–Wire ABCD Connector
ELECTRICAL OPERATION HAZARD
Failure to follow this caution will result in equipment damage
or improper operation.
Improper wiring of the ABCD connector will cause the
Infinity Control™ to operate improperly. Check to make sure
all wiring is correct before proceeding with installation or
turning on power.
9. Push any excess wire into the wall. Seal hole in wall to prevent
any air leaks. Leaks can affect operation.
10. Attach Infinity Control™ to the mounting plastic by lining up
the plastic guides on the back of the control with the opening
on the mounting plastic and push on.
11. Perform installation of all other system equipment (i.e. humidifier, ventilator, UV lights, etc.)
12. Turn on power to equipment.
EQUIPMENT WIRING DIAGRAMS:
See wiring diagram Figs. 12, 13 and 14.
NOTE: For other applications not listed, refer to the Network
Interface Module (NIM) Installation Instructions.
See wiring diagram figure 12 for a Typical Four-Wire Connection
Diagram, which includes an Infinity indoor communicating furnace or FE fan coil with a 2-speed Puron® communicating outdoor
unit. No additional OAT (outdoor air temperature) sensor is
required because the Infinity Control will use the temperature
sensor inside the 2-speed unit.
See wiring diagram figure 13 for a Typical Connection Diagram,
which includes an Infinity indoor communicating furnace or FE
fan coil, with a 1-speed air conditioning unit (non-communicating
outdoor). An Outdoor Air Temperature sensor may be installed
(not required) at the indoor furnace or fan coil OAT terminals.
When OAT is applied, the Infinity System will provide full system
features and benefits.
See wiring diagram Fig. 14 for a Typical Connection Diagram for
FE fan coil with a 1-speed heat pump (using non-communicating
outdoor unit). When OAT is applied, the Infinity System will
provide full system features and benenfits.
Left-Side
Button
Time (+/-)
Button
Hold
Button
Schedule & Vacation
Program Buttons
Up/Down
Scroll Buttons
HOLD
SCHEDULE VACATION
PROGRAM
Schedule
to program
temperature
schedule
Vacation
to start/end
vacation
SCROLL
Scroll
up & down
Basic
to set time,
humidity
BASIC
SETUPS
ADVANCED
Advanced
for all other
settings
HEAT
COOL
Fig. 11—Functional Overview
Variable-Speed
Furnace/ Fan Coil
User Interface
A
B
C
D
S1
S2
Green
Yellow
White
Red
Optional Remote
Room Sensor
Connection
Humidifier
HUM
OAT
A
B
C
D
COM
24V
2-Spd. AC or HP
Green
Yellow
White
Red
ABCD
Connections
OA T
Sensor
(Optional)
Fig. 12—Universal Four-Wire Connection Diagram
HUMIDIFIER CONNECTION — A 24vac bypass or fan
powered humidifier may be installed.
NOTE: Do Not Use a traditional humidistat to control humidifier
operation. If a humidifier is installed, let the Infinity System
control humidifier operation.
Bypass Humidifiers — A bypass humidifier should be wired
directly to the furnace or fan coil HUM and 24vac COM terminals.
The Infinity Control will automatically energize the HUM output
during a call for humidification.
Fan Powered Humidifiers — Most fan powered humidifiers
produce internal 24vac in order to energize upon a switch or
contact closure. For this application, a 24vac N.O. Isolation Relay
(DPST) MUST be used to prevent mixing the internal humidifier
power with the indoor equipment transformer. Applying 24vac
isolation relay coil to furnace or fan coil HUM and COM terminals
will allow the Infinity Control to automatically energize the HUM
output during a call for humidification. The N.O. relay contacts
will be used to energize the humidifier. See fan powered humidifier installation instructions for more details.
4
Right-Side
Button
Heat Button
Cool Button
Temperature
(+/-) Button
System
On/Off Button
Basic & Advanced
Setup Buttons
Flip Down
Door
A03194
A
B
C
D
A03146
User Interface
A
B
C
D
S1
S2
Green
Y ello w
White
Red
Optional Remote
Room Sensor
Humidifier
Connection
Variable-Speed
Furnace/Fan Coil
A
B
ABCD
C
Connection
D
HUM
COM
24V
Y/Y2
OAT
1-Spd. AC
C
Y
OAT
Sensor
typical example for a communicating Variable-Speed Furnace /
Fan Coil with a 2-spd. Air Conditioner / Heat Pump (including
Dual Fuel).
The User Interface display will light up and indicate that it is now
″ESTABLISHING COMMUNICATIONS WITH EQUIPMENT
PLEASE WAIT″. The User Interface will automatically continue
by ″SEARCHING FOR INDOOR EQUIPMENT″, followed by
″SEARCHING FOR OUTDOOR EQUIPMENT″ (See Figure 15).
Once the indoor and outdoor equipment has been found, the
Installer will be asked to select Accessories. Proceed to Section 4.
Selecting Accessories.
NOTE: If the variable-speed indoor equipment (furnace or fan
coil) cannot be found, the User Interface will display ″CANNOT
COMMUNICATE WITH INDOOR UNIT″. This MUST be
corrected before the initial power up sequence can continue. If
indoor unit is found, but the outdoor unit is not found, ″OUTDOOR UNIT NOT IDENTIFIED″ will appear. Proceed to the next
section for Outdoor Unit Identification.
Fig. 13—Connection Diagram for
Furnace or FE Fan Coil w/1-Spd. AC
User Interface
A
B
C
D
S1
S2
Green
Yellow
White
Red
Optional Remote
Room Sensor
Variable-Speed
Fan Coil
Humidifier
Connection
A
B
ABCD
Connection
C
D
HUM
C
R
O
W
Y
OAT
A03147
1-Spd. HP
C
R
O
W2
Y
OAT
Sensor
Fig. 14—Connection Diagram for
FE Fan Coil w/1-Spd. HP
FIRE OR EQUIPMENT HAZARD
Failure to follow this warning could result in equipment
damage or fire.
Do not apply 24vac fan powered humidifier (with internal
power supply) direct to indoor unit HUM and COM terminals.
INITIAL POWER-UP
NOTE: Refer to Functional Overview (Fig. 11) to become
familiar with key function buttons such as ″System On/Off″,
″Fan″, ″Left-Side″ and ″Right-Side″ buttons, etc. These function
buttons will be used frequently during setup.
SECTION 1 — POWER UP SEQUENCE
This section addresses initial power up (or commissioning) of a
new Infinity Control™. The User Interface will communicate and
identify all Infinity components in the system. The following is a
A03148
ESTABLISHING
COMMUNICATIONS
WITH EQUIPMENT
PLEASE WAIT
SOFTWARE
VERSION
INDOOR UNIT
SEARCHING FOR
INDOOR EQUIPMENT
WORKING
OUTDOOR UNIT
SEARCHING FOR
OUTDOOR EQUIPMENT
WORKING
A03195
Fig. 15 — Power Up Sequence
SECTION 2 — SELECTING OUTDOOR UNIT
If there is no communicating outdoor unit, the screen, shown in
Fig. 16, will appear. Press either Time or Temp +/- buttons to
select AC (air conditioner), HP (heat pump), or None (no unit
installed). Press the right-side button to continue to the next screen.
If you have selected either AC or HP as the outdoor unit type, the
following middle screen will appear (See figure 16). Press either
Time or Temp +/- buttons to select appropriate Btu size of outdoor
unit, then press right side button to continue. If a NIM (Network
Interface Module) is applied for non-communicating two-speed
outdoor equipment, select 1 or 2speed compressor operation , and
press right-side button to continue.
NOTE: Range of Btu selection is limited by the model number of
the indoor unit installed. The Infinity Control™ will not allow an
outdoor unit size that is not supported by the installed indoor unit.
OUTDOOR UNIT
NOT IDENTIFIED
SELECT TYPE: NONE
NONE, AC, HP
PRESS +/- TO MAKE
SELECTION
CONTINUE
OUTDOOR UNIT
ENTER HEAT PUMP
SIZE 36000 BTU
18000 TO 60000 BTU
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
OUTDOOR UNIT
HEAT PUMP
ENTER NUMBER OF
SPEEDS, 1 or 2: 1
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
A03196
Fig. 16—Selecting Outdoor Unit
NOTE: On new system installations, the model and serial number
will be recognized and displayed. On any indoor/outdoor board
replacements, the equipment will be recognized but the exact
model/serial number will not be displayed.
SECTION 3 — SELECTING ELECTRIC HEATER
If the indoor unit is a fan coil and the electric heater is not
self-identifying, ″ELECTRIC HEATER NOT IDENTIFIED″ will
appear (See figure 17). Press either Time or Temp +/- buttons to
select appropriate size of electric heater installed, then press the
right-side button to continue.
5
NOTE: Range of electric heaters available is limited by the model
of the fan coil installed. The Infinity Control™ will not allow an
electric heater size that is not supported by the installed fan coil.
ELECTRIC HEATER
NOT IDENTIFIED
ENTER SIZE: 5 KW
NONE, 5,10,15 KW
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
A03197
Fig. 17—Selecting Electric Heater
SECTION 4 — SELECTING ACCESSORIES
Once the indoor and outdoor equipment have been found or
entered, the following screens will appear allowing the Installer to
select the AIR FILTER TYPE; HUMIDIFIER INSTALLED; and
UV LIGHTS INSTALLED″ (See Fig. 18). Use either Time or
Temp +/- buttons to make the appropriate selections in the
highlighted area on the display screen. Press right-side button to
continue (or advance) to the next screen.
AIR FILTER TYPE— This accessory screen will appear first.
The installer will need to enter the type of filter (MEDIA, EAC, or
both). See Table 1 and make a selection using Time or Temp +/button, then press right-side button to continue.
Table 1 — Filter Selection
INSTALLED FILTERMENU SELECTION
1 Inch to 4 inch mediaMEDIA
High voltage EACEAC
High voltage EAC+1to4inch mediaMEDIA + EAC
HUMIDIFIER TYPE — This will appear after the Air Filter
Type screen. Select whether a humidifier is installed on the
system, YES or NO, then press the right-side button to continue.
UV LIGHTS INSTALLED— This screen will appear to select
whether UV lights are installed on the system, select YES or NO,
then press the right side button to continue.
ACCESSORIES
AIR FILTER TYPE:
EACEAC
MEDIA
MEDIA + EAC
PRESS +/- TO MAKE
SELECTION
CONTINUE
AIR FILTER MEDIA TYPEHUMIDIFIER INSTALLED?U.V. LIGHTS INSTALLED?
ACCESSORIES
HUMIDIFIER
INSTALLED? YES
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
ACCESSORIES
U.V. LIGHTS
INSTALLED? YES
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
A03198
Fig. 18—Accessories — UV Lights
SECTION 5 — EQUIPMENT SUMMARY
The ″EQUIPMENT SUMMARY″ screen will appear after Ac-
cessories have been selected. This screen will give a summary of
all equipment automatically found or manually selected. If a wrong
selection was made, press left-side button (BACK selection) to go
back to that particular screen and make changes. When everything
is OK, press right-side button again to continue. (See figure 19)
The ″SETUP COMPLETE! SAVE ALL SELECTIONS?″
screen will appear after Equipment Summary. To Save All
Selections press (YES) right-side button. Pressing the left-side
button (NO selection) will return to the Equipment Summary
screen where you can back up to any of the equipment selection
screens and perform changes. After selecting YES, the initial
power up sequence of the new Infinity Control™ is complete. The
User Interface screen will now display normal operating mode.
Also, after selecting YES, if the filter type is not an EAC, the
indoor unit will operate the blower for one minute to do a system
static pressure check.
For first time installers, Quick Start will allow you to start up the
Infinity System before you have the chance to learn all the details
of system operation. However, for the best possible comfort and
operation we recommend that you refer to the Infinity Control™
Homeowner’s Guide.
SET DAY, TIME & DESIRED HUMIDITY
1. Flip down the door at the base of the Infinity Control™ and
press the BASIC button.
2. Adjust the highlighted HOUR setting using the TIME (+/−)
button.
3. Press SCROLL button (down) to highlight MINUTE.
4. Adjust the MINUTE setting using the TIME (+/−) button.
5. Press SCROLL button (down) to highlight DAY.
6. Adjust the current DAY setting using the TIME (+/−) button.
7. Press SCROLL button (down) to highlight HUMIDITY.
8. Press the red HEAT button to select heating humidity.
9. Adjust desired heating humidity level using either (+/−)
button.
10. Press the blue COOL button to select cooling humidity.
11. Adjustthedesiredcoolinghumiditylevelusing
either(+/−)button.
12. To exit press BASIC button or close door.
OVERRIDE HEATING SCHEDULE
1. Press the red HEAT button. Heating mode is confirmed when
the red LED next to the red HEAT button is lit.
2. Use the TEMP (+/−) button to select your desired heating
temperature.
3. The default time for temporarily overriding the temperature
schedule is 2:00 HRS as indicated by the text on the lower left.
NOTE: Override time will not appear if programming has been
turned off.
4. You can change the temporarily override time in 15-minute
increments by pressing the TIME (+/−) button until the
desired override time is selected, or press the HOLD button
anytime to override the schedule indefinitely.
OVERRIDE COOLING SCHEDULE
1. Press the blue COOL button. Cooling mode is confirmed
when the blue LED next to the COOL button is lit.
2. Use the TEMP (+/−) button to select your desired cooling
temperature.
3. The default time for temporarily overriding the temperature
schedule is 2:00 HRS as indicated by the text on the lower left.
6
A03199
NOTE: Override time will not appear if programming has been
turned off.
4. You can change the temporary override time in 15-minute
increments by pressing the TIME (+/−) button until the
desired override time is selected, or press the HOLD button
anytime to override the schedule indefinitely.
QUICK PROGRAM SCHEDULE FOR ALL DAYS
This section will give you a quick program schedule for All Days
of the week. For more information on how to create customized
schedules for every day, the entire week, or weekend, refer to the
Homeowner’s Guide.
1. Flip down the door at the bottom of the control.
2. Press the SCHEDULE button, which allows you to create one
schedule for the entire home.
3. Press either the LEFT or RIGHT side button repeatedly (if
necessary) until ″ALLDAYS″ is displayed. The WAKE time
period will be highlighted.
4. Using the TIME (+/−) button, set the start time for this time
period.
5. Press the red HEAT button. Heating temperature will begin
flashing.
6. Set the heating temperature using the TEMP (+/−) button.
7. Press the blue COOL button. Cooling temperature will begin
flashing.
8. Set the cooling temperature using the TEMP (+/−) button.
9. Set the remaining periods by using the SCROLL button to
select ″DAY,″″EVENING,″ and ″SLEEP″.
10. Exit the scheduling mode by either closing the door or
pressing the SCHEDULE button.
11. If changes are made, you will be asked to ″SAVE CHANGES
YES/NO″
INSTALL / SERVICE MENUS
The ″INSTALL / SERVICE″ menus contain a set of vital
information. This information enables the Installer or Service
person to view a summary of what has been installed, etc.
To enter INSTALL / SERVICE menus, press and hold the
ADVANCED button for at least ten seconds. The following menu
will appear (See figure 20):
NOTE: The INSTALL / SERVICE menu will automatically exit
after 60 minutes of no push button activity.
EQUIPMENT SUMMARY: Shows all equipment recognized by
and attached to the system.
INSTALL: Used when adding, changing out, or uninstalling
equipment.
SETUP: Used to view or modify equipment settings.
CHECKOUT: Allows testing of equipment operation
SERVICE: Used to view operation and fault history of equipment
This screen shows indoor unit type and model number, outdoor
unit type (and model number if a 2-speed unit), filter type, any
accessories that are installed.
INSTALL MENU
This menu item will perform start-up process in order to learn all
equipment in system. Press right side button to initiate the process.
INSTALL
TO ADD, UNINSTALL OR
RE-INSTALL EQUIPMENT,
PRESS RIGHT SIDE
BUTTON
BACK INSTALL
Fig. 22 — INSTALL
7
A03201
A03202
SETUP MENU
This menu has several layers, allowing modification of equipment
settings. No settings will need to be made at equipment (i.e.dip
switches on a furnace). All configuration settings are made
effective from this menu. Fig. 23 shows all the information that
can be found in the SETUP menu.
SETUP
THERMOSTAT
FURNACE
HEAT PUMP
ACCESSORIES
SYSTEM MAINTENANCE
BACK SELECT
A03203
Fig. 23 — SETUP MENU
SETUP = THERMOSTAT:
AUTO MODE SETUP:
• Enable/Disable Auto Changeover mode (default=Enable).
• Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).
When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the set point is changed, the
30 minute timer is deleted.
HEAT/COOL DEADBAND:
• 0 to 6 degrees, (default = 2°).
A minimum difference of 2° is enforced between heating and
cooling desired temperatures. This will allow one setting to ″push″
the other to maintain this difference.
OFFSETS: This option allows calibration (or deliberate miscalibration) of the temperature and humidity sensors. These offsets are
added to the actual temperature/humidity values (defaults = 0).
• Room Temp Offset: -5 to +5 degrees.
• Outside Temp Offset: -5 to +5 degrees.
• Humidity Offset: -10 to +10 percent.
CYCLES PER HOUR:
• Maximum cycles per hour = 4 (default) or 6.
• Anticipator=1to9(default=3).
PROGRAMMING:
• On or Off (default=On)
• Periods Per Day=2or4(default=4)
• Programmable Fan On/Off (default=Off)
SMART RECOVERY:
• On or Off, (default=On)
Applies to programmable operation only. Will start recovery 90
minutes prior to schedule change in both heating and cooling.
ENGLISH/METRIC DISPLAY:
•°For°C, (default = °F)
RESET FACTORY DEFAULTS:
Program Schedule:
• Yes/No to reset back to Energy Star defaults.
User Settings:
• Yes/No to reset the user settings in the Advanced Setup.
Install Settings:
• Yes/No to reset install settings in Install/Service menus.
SETUP = FURNACE:
Upon a first time start-up of the Infinity Control™, the furnace dip
switch settings will be copied to the furnace setup menu. Any
changes can then be made from the Infinity Control™.
AIRFLOW:
• COMFORT (default)
• EFFICIENCY
Selects the airflow of the furnace when heating. EFFICIENCY is
the airflow used to meet specified ratings, COMFORT is a
decreased airflow used to increase the output air temperature and
provide increased comfort.
AC AIRFLOW:
• COMFORT (default)
• EFFICIENCY
• MAXIMUM
Selects the airflow of the furnace when cooling. COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY is the airflow used to meet specified ratings. MAXIMUM is a fixed airflow speed of 400 CFM/ton based on the
outdoor unit size.
DEHUM AIRFLOW:
• NORMAL (default)
• HIGH
NORMAL airflow adjustment is used during dehumidifying. If
duct sweating is an issue, selecting HIGH will increase the
dehumidifying airflow speed and reduce the sweating.
LOW HEAT RISE:
• ON
• OFF (default)
Set this to ON if the system contains a bypass humidifier. The ON
setting will increase the furnace low heat airflow.
STAGING:
• SYSTEM (default)
• FURNACE
• LOW
• HIGH
Controls the staging of the furnace. SYSTEM setting will allow
the Infinity Control™ to determine furnace staging. FURNACE
will allow the Furnace algorithm to control staging. LOW will
only run the low stage of furnace heat. HIGH will only run the
high stage of furnace heat.
OFF DELAY:
• 90 seconds (default)
• 120 seconds
• 150 seconds
• 180 seconds
Amount of time the blower will continue to run after heating has
shut off.
LOCKOUT TEMP:
• NONE (default)
• +5 to 55 deg F
Appears on dual fuel systems only (furnace with heat pump).
Outside temperature above which the furnace will NOT run.
8
SETUP = FAN COIL:
HP/AC AIRFLOW:
• COMFORT (default)
• EFFICIENCY
• MAXIMUM
Selects the airflow of the fan coil when heating or cooling with a
heat pump (or cooling with an AC unit). COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY is the airflow used to meet specified ratings. MAXIMUM is a fixed airflow speed of 400 CFM/ton based on the
outdoor unit size.
DEHUM AIRFLOW:
• NORMAL (default)
• HIGH
Normal airflow adjustment used during dehumidifying. If duct
sweating is an issue, selecting HIGH will increase the dehumidifying airflow speed and reduce the sweating.
HEATER SIZE:
• (choices dependent upon fan coil model)
This will show the heater size entered during the start-up process.
This value can be changed to another value (limited by the model
of the fan coil). If the electric heater is self-identifying, this value
is not shown.
SETUP = HEAT PUMP / AC:
COOLING LOCKOUT:
• NONE (default)
• 45° F.
• 50° F.
• 55° F.
Outside temperature below which cooling will not be provided.
ENTERED SIZE:
• (dependent on indoor unit model)
Size of the outdoor unit entered during the start-up process. If the
outdoor unit is a communicating model, this value will not be
shown. This size can be changed here but is limited to sizes that the
indoor unit can handle.
DEFROST INTERVAL:
• 30 minutes
• 60 minutes
• 90 minutes (default)
• 120 minutes
Time interval at which defrost cycles can occur on a heat pump.
ELECT HEAT LOCKOUT:
• NONE (default)
• +5 to 55 deg. F
Outside temperature above which the electric heat will not operate.
HIGH COOL LATCH:
• NONE (default)
• 80 - 110 deg F
Outside temperature above which only the high speed (of a
2-speed outdoor unit) will run when cooling.
SETUP = ACCESSORIES
FILTER TYPE:
• MEDIA
• EAC
• MEDIA+EAC
CLEAN INTERVAL: 30 to 180 days (of blower operation).
(Default = 90)
Interval at which the Clean Filter notification will turn on. Applies
to EAC or MEDIA+EAC filter selection only.
SETUP = HUMIDIFIER
HUMIDIFIER INSTALLED:
• NO
• YES
If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months of humidifier
operation (default=6 months)
Interval at which the Change Humidify Pad notification will be
displayed.
HUMIDIFY WITH FAN:
• NO (default)
• YES
If YES, the humidifier will run with Continuous Fan if there is a
humidify demand.
SETUP = VENTILATOR
NOTE: Only appears if ventilator is installed.
CLEAN INTERVAL:
• 60 to 180 days of operation (default=90)
Interval at which the Clean Ventilator Pre-filter notification will
turn on.
SETUP = UV LIGHTS
UV LIGHTS INSTALLED:
• NO
• YES
If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:
• 6 to 48 months operation time (default=12 months)
Interval at which the Change UV Lights notification will be
displayed.
SETUP = SYSTEM MAINTENANCE
REMIND OWNER OF ROUTINE MAINTENANCE EVERY:
This setup is used to adjust the timer interval in which the normal
System Maintenance notification is turned on for the homeowner.
• Range= OFF, 6 to 24 months, (default=12)
9
CHECKOUT MENUS
The Checkout menu will show the equipment installed in the
system. A sample checkout menu is shown in Fig. 24.
Make sure the furnace is properly installed before continuing.
• LOW HEAT RUNTIME: 5 min.
• HIGH HEAT RUNTIME: 5 min.
This menu item allows the furnace to be exercised. First, a low
heat runtime and high heat runtime are selected.
If only the low heat is to be exercised:
The furnace will execute its ignition start-up sequence. This
sequence will be displayed on the Infinity Control screen. After the
gas valve and blower motor turn on, the screen will automatically
change to show the current operating status of the furnace.
Checkout = FAN COIL
ELECTRIC HEAT CHECK
• ELECTRIC HEAT RUNTIME: 5 min., Default time = 5 min.,
Range=0-120min.
If you have a fan coil with electric heaters, this menu item will
allow the heaters to be exercised.
With self-identifying electric heaters, three stages of electric heat
are available to be exercised in any combination. Non-identifying
heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be
exercised then press START (right-side button). The display will
change to show the fan coil’s operating status.
Checkout = HEAT PUMP HEATING
• HIGH HEAT RUNTIME: 5 min.
• LOW HEAT RUNTIME: 5 min.
• DEFROST: NO
The heat pump heating mode can be exercised with this menu
option. With a 2-speed heat pump, a low heat runtime and a high
heat runtime are independently selectable to exercise. A defrost
cycle is also selectable. Default time = Fixed 5 min. minimum,
range=5-120min.
Checkout = HEAT PUMP COOLING OR AC COOLING
• HIGH COOL RUNTIME: 5 min.
• LOW COOL RUNTIME: 5 min.
The heat pump cooling mode (or AC cooling mode) can be
exercised with this menu option. With a 2-speed heat pump or AC
unit, a low cool runtime and a high cool runtime are independently
selectable to exercise. The display will change to show the heat
pump or AC operating status. Default time = Fixed 5 min.
minimum, range=5-120min.
Checkout = HUMIDIFIER
• ON
• OFF
The humidifier can be exercised On and Off with this menu option.
Checkout = VENTILATOR
The ventilator can be exercised through all of its operating speeds
with this menu option.
SERVICE MENUS
The Service Info menu will only show the equipment installed in
the system. Below is a sample using a furnace and a dual fuel heat
pump. A sample service menu is shown in Fig. 25.
SERVICE INFO
FURNACE STATUS
HEAT PUMP STATUS
LAST 10 SYSTEM FAULTS
RUN/FAULT HISTORY
TODAY’S DATE
MODEL/SERIAL NUMBER
SERVICE PHONE NUMBER
BACK SELECT
A03205
Fig. 25 — SERVICE INFO MENUS
Service = FURNACE STATUS
The Status screens will show all of the current operating parameters of each installed piece of equipment.
HEAT STAGE:
• OFF, LOW, HIGH
Displays stage of heat that the furnace is currently delivering.
AIRFLOW CFM:
• (furnace model dependent)
Cubic Feet per Minute of air the blower is currently delivering.
INDUCER RPM (90% furnaces only):
• Inducer motor RPM value.
BLOWER RPM:
• Blower motor RPM value.
STATIC PRESS:
• Inches of water. Displays static pressure that the furnace is
currently experiencing.
LOCKOUT TIMER:
• Seconds
If a lockout timer is active, this will show the current time value.
See furnace manual for details on lockout timers.
Service = FAN COIL
ELECTRIC HEAT STATUS:
• OFF, LOW, MED, HIGH
Displays stages of electric heat that the fan coil is currently
delivering.
AIRFLOW CFM:
• (fan coil model dependent)
Cubic Feet per Minute of air the blower is currently delivering.
BLOWER RPM:
• Blower motor RPM value
STATIC PRESS:
• Inches of water
Displays static pressure that the fan coil is currently experiencing.
10
Service = HEAT PUMP / AC STATUS
STAGE: (HEAT / COOL):
• OFF, LOW, HIGH
Displays stage of heating or cooling that the heat pump/AC is
delivering.
DEFROST:
• NO, YES
Displays status of defrost mode if heat pump.
AIRFLOW CFM:
• Indoor unit cfm measurement.
BLOWER RPM:
• RPM feedback from indoor motor.
COIL TEMP:
• Degrees F.
Temperature of the outdoor unit coil (only available on 2-speed
communicating outdoor units).
STATIC PRESS:
• Static pressure of indoor unit.
Service = LAST 10 SYSTEM FAULTS
This screen will show last 10 faults that occurred throughout the
system. Each fault has the time and date of incident recorded.
Service technician should enter current date in ″TODAY’S
DATE″ menu section before checking and logging the last 10
system faults. Each fault has a two-letter acronym preceding the
fault name to identify which piece of equipment generated the
fault.
• HP = heat pump
• AC = air conditioner
• FN = furnace
• FC = fan coil.
Service = RUN / FAULT HISTORY
The indoor unit and outdoor unit (if communicating) has the
following histories:
NOTE: For Critical Fault Screens, see Trouble Shooting section
in this document.
Resettable Faults:
• Fault counters for each piece of equipment that can be reset.
Cycle Counters:
• Number of heat/cool/power cycles the unit has performed.
Run Times:
• Lifetime hours of operation in heating, cooling, and how long
the unit has been powered.
Service = TODAY’S DATE
• This menu item allows the installer to enter the current date. It
is used for time/date stamping of system faults. This should be
entered every time prior to viewing ″LAST 10 SYSTEM
FAULTS″ section.
Service = MODEL / SERIAL NUMBERS
• If available, this menu item allows the installer to view the
model number and serial number of all communicating pieces
of equipment in the system.
Service = SERVICE PHONE NUMBER
This menu item allows the installer to enter a name and phone
number that the homeowner can call for future service of the
system. This name and phone number will appear to the homeowner whenever a service reminder pop-up message is displayed
(i.e. Change Filter, etc.)
To edit:
• Use Temp +/- button to move cursor left and right.
• Use Time +/- button to select numbers and letters.
• Use Scroll button to move up and down between NAME and
NUMBER.
OPERATIONAL INFORMATION
Continuous Fan Operation
Pressing FAN button will scroll through the following:
• AUTO = No fan operation except during equipment operation.
• LOW = Approximately 50% of High Speed operation.
• MED = The difference between High and Low speed operation.
• HIGH = Highest of either High Heating or High Cooling CFM.
Five-Minute Compressor Timeguard
This timer prevents compressor from starting unless it has been off
for at least 5 minutes. It can be defeated by simultaneously
pressing the Fan and Temp + buttons.
Emergency Heat (for heat pump applications)
To activate Emergency Heat, you must press and hold the HEAT
button for 3 seconds to activate.
Keypad Lockout
Keypad can be locked by pressing Fan and Humidity/OAT buttons
at the same time for 3 seconds. When keys are locked, a lock
symbol will appear in the upper left corner of screen. Follow same
procedure to unlock keypad.
Heat and Cool LED
The Heat and Cool LEDs will pulsate during actual equipment
operation.
Equipment Cycle Timer (adjustable 4-6 cycles per hour)
This timer prevents the start of a heating or cooling cycle until 15
(or 10) minutes after the last start of the same cycle. Its function is
to assure that the equipment is not cycled more than the selected
times per hour. This timer is adjustable from 4 to 6 cycles per hour.
This timer is defeated for one cycle when the desired temperature
is manually changed. It can also be defeated for one cycle by
simultaneously pressing the Fan and Temp + buttons.
Ten-Minute Staging Timer
In multistage heating or cooling, this timer prevents any higher
stage from turning on until the preceding stage has been on for 10
minutes. This timer is defeated if temperature error is greater than
5°F (usually due to a large change in desired temperature).
Three-Minute Minimum On Time
In normal operation, when a stage turns on, it will remain on for a
minimum of three minutes. If the set point is changed, this timer is
automatically cancelled, allowing the equipment to turn off immediately when the demand is removed.
Heat/Cool Set points (Desired Temperatures)
A minimum difference of 2° (default) is enforced between heating
and cooling desired temperatures. This is done by allowing one
setting to ″push″ the other to maintain this difference. This
difference is adjustable via the Install/Service menu under Thermostat Setup.
Auto Changeover
When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the set point is changed, the
30-minute requirement is defeated. This Auto Changeover time is
adjustable via the Install/Service menu under Thermostat Setup.
Range=5-120min.
Smart Recovery
11
With Smart Recovery selected (factory default), transition out of
setback begins a fixed time period before selected recovery time
and gradually adjusts room temperature so desired temperature
will be achieved at selected recovery time. The fixed time period
is 1.5 hours. It operates in both heating and cooling. This only
applies to programmable operation.
Media Filter
If a media filter is installed in the indoor unit, the system will
perform a static pressure check of the system whenever power is
applied to the system, or the system is transitioned from Off to
Cool or Heat modes. The blower will run at a medium airflow for
one minute.
TrueSense™ Dirty Filter Detection
When MEDIA or MEDIA+EAC is installed, a static pressure
check will automatically be performed every 24 hours at 1:00PM
to monitor filter accumulation.
TROUBLESHOOTING
The following errors will cause a Critical Malfunction screen to
pop up. Heat and Cool LEDs will alternately flash at a 1 second
rate.
FAN COIL
Code 44 - Motor Communication Fault
Code 41 - Blower Motor Fault
FURNACE
Code 15 - Blower Motor Lockout
Code 22 - Abnormal Flame Proving Signal (not dual fuel)
Code 41 - Blower Motor Fault
USER INTERFACE
No communication with indoor unit
SYSTEM MALFUNCTION SCREEN
The following errors will cause a System Malfunction Screen to
pop up:
o
OUTSIDE: 94
FAN: AUTO
Infinity Control™ does not power up.
1. Recheck wiring to ABCD on all devices.
2. Make sure all colors match for every terminal.
3. Make sure power is applied to the indoor unit, and the amber
LED is lit on indoor control circuit board.
4. Check for 24VAC between the C and D terminals at Infinity
Control™ terminal connector.
5. Check fuse on indoor unit’s circuit board.
Display says ″Indoor Unit Not Found″
1. Recheck wiring to ABCD on all devices.
2. Make sure all colors match for every terminal.
3. Press left-side button to try again.
4. If display still reads ″Indoor Unit Not Found″, disconnect all
devices from ABCD and connect User Interface directly to
indoor unit.
Display says ″Outdoor Unit Not Found″, and I have a twospeed communicating outdoor unit:
1. Recheck wiring to ABCD connector on outdoor unit.
2. Make sure all colors match for every terminal.
3. Check for 24VAC between the C and D terminal connector.
I made a mistake on the start-up screens, and hit the right-side
button to get to the run mode. How do I get back to start-up?
1. Press the ADVANCED button for at least 10 seconds.
2. Install/Service menu will appear.
3. Scroll down to the INSTALL selection.
4. Press the right-side button; the screen will prompt you to press
the right side again to re-install the system.
CRITICAL ALERT SCREEN
o
OUTSIDE: 94
CRITICAL MALFUNCTION
Fig. 26 — Critical Alert Screen
FAN: AUTO
ALERT !
71
HVAC SERVICE
1 800 555-1212
CALL TECHNICIAN
˚
A04027
71
HVAC SERVICE
1 800 555-1212
SYSTEM MALFUNCTION
CALL TECHNICIAN
Fig. 27 — System Malfunction Screen
FAN COIL
Code 37 - Heater output sensed ON when not energized
FURNACE
Code 13 - Limit Circuit Lockout
Code 14 - Ignition Lockout
Code 21 - Gas Heating Lockout
Code 22 - Abnormal Flame Proving Signal (dual fuel only)
Code 23 - Pressure Switch Did Not Open
Code 24 - Secondary Voltage Fuse Open
Code 33 - Limit Circuit Fault AND High Heat Only is active
Code 45 - Control Circuitry Lockout
NOTE: For all the above furnace error codes, the system will use
heat pump heating exclusively if available. When the error code is
cleared or disappears, furnace heating will resume.
TWO-SPEED OUTDOOR UNIT
Code 85 - VC voltage at standby
Code 86 - High capacity compressor lockout
USER INTERFACE
Temp Sensor Failed, ″NO SENSOR DATA″ shown in place of
actual temp.
Outdoor Unit communication fault.
Network Interface Module (NIM) communication fault
Defrost Error (defrost signal on for more than 15 minutes)
The user can press the right side button to dismiss the notice. The
regular run mode screen will then appear except ″SYSTEM
MALFUNCTION″ will appear in place of the day/time. If the error
has not disappeared within 24 hours, the above display will return.
If the error code disappears, ″SYSTEM MALFUNCTION″ will
disappear and the day/time will reappear.
˚
DISMISS
NOTICE >
A04028
Copyright 2004 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231uid01-1si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab misc. misc.
PC 101Catalog No. 809-50020Printed in U.S.A.Form UID01-1SIPg 1201-04Replaces: NEW
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.