Carrier SYSTXCCSMS01-A Installation Instructions Manual

SYSTXCCSMS01---A Infinity
r Smart Sensor for Zoning
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings and cautions included in literature and attached to the unit. Consult local building codes and the current edition of the National Electrical Code (NEC) NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING,andCAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies hazards, which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
on
INTRODUCTION
Carrier’s Infinityr Smart Sensors are optional replacements for Remote Room Sensors used with Infinityr Zoning systems. It provides a temperature display and buttons to adjust the desired temperature within the zone. It also displays outdoor temperature and indoor humidity. When used with an Infinityr Touch Control wall control-- FAN, HOLD and HOLD UNTIL features are available. When used with an Infinityr User Interface (UIZ) wall control-- FAN, HOLD, OVERRIDE, UNOCCUPIED features are available.
INSTALLATION CONSIDERATIONS
Any zone may use an Infinity Smart Sensor. The Infinity Smart Sensor can be “home run” wired directly to the Damper Control Module, or “daisy chained” from the wall control or another Smart Sensor via 4--wire ABCD communication bus. Ordinary thermostat wire is recommended; however, solid conductor, stranded, or shielded wire may be used. Use 22 AWG or larger for normal wiring applications. Continuous wire lengths over 100 ft. should use 20 AWG or larger. Plan the connection of each Smart Sensor to provide easiest wiring route.
NOTE: Whenever possible, it is suggested to always “home run” wires back to the Damper Control Module for convenience of
troubleshooting. Using a “pig--tailed” connection, or a field supplied terminal block may be helpful in achieving proper wire termination at the Damper Control Module.
An Infinity Smart Sensor may now be used to control Zone 1. In addition, a Remote Room Sensor may also be used in the same zone. If a Remote Room Sensor is applied in the same zone, the Remote Room Sensor has temperature priority over the Smart Sensor.
HOLD
A04147
Fig. 1 -- Infinity Smart Sensor
SYSTXCCSMS01--A
INSTALLATION
Step 1 — Select Smart Sensor Location
Sensor should be mounted:
S Approximately 5 ft. (1.5m) from floor. S Close to center of zone, preferably on inside partitioning wall. S On section of wall without pipes or ductwork. S Where wiring can be routed to it within wall. Avoid running
directly next to other AC power.
Sensor should NOT be mounted:
S Close to a window, on outside wall, or next to a door leading to
the outside.
S Exposed to direct light and heat from a lamp, sun, fireplace, or
other temperature radiating object which may cause a false reading.
S Close to or in direct airflow from supply registers and return--air
grilles.
S In areas with poor air circulation, such as behind a door or in an
alcove.
S Do not run wires next to AC power lines.
Outside Temp /
Indoor Humidity
Fan Status
Humidity/OAT
Hold/Unoccupied
HOLD
Time (+/-)
Fig. 2 -- Smart Sensor Functions
Step 2 — Install Infinity Smart Sensor
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing sensor, turn off all power to unit. There may be more than 1 power disconnect.
1. Turn OFF all power to unit.
2. If an existing thermostat or sensor is being replaced:
a. Remove existing device from wall.
b. Disconnect wires from existing device, 1 at a time. Be care-
ful not to allow wires to fall back into wall.
c. Discard or recycle old device.
d. If 4 wires exist in wall, they may be used. If not, plan and
route wiring to connect with either the Damper Control Module,orUser Interface. MultipleInfinity Smart Sensors may be daisy chained together, but somewhere chain must connect to either Damper Control Module or the Infinity Touch Control/Infinity User Interface wall control. (Smart Sensor daisy chain wire limit is 100 ft.) Recommended connection is: A -- Green = Data A B -- Yellow = Data B C -- White = 24vac (com) D -- Red = 24vac (hot)
NOTE: It is not mandatory that the above color code be used, but each ABCD connection in the system MUST be wired consistently.
3. To mount Smart Sensor, remove rear mounting base. Route wires through hole in mounting base and level base against wall.
4. Mark wall through 2 mounting holes and drill two 3/16--in. holes. Secure assembly to wall with 2 anchors and screws provided, making sure all wires properly extend through opening.
5. Adjust length and routing of thermostat wire to reach each terminal entry on the connector. Strip 1/4--in. of insulation from each wire and properly connect to A--B--C--D.
Fan Control
Room Tem perat ure
Set point
COOL / HEAT
Temp (+/-)
A04136
6. Push any excess wire into the wall. Seal hole in wall to pre­vent any air leaks. Leaks can affect Smart Sensor operation.
7. Attach Infinity Smart Sensor to the mounting base by lining up the plastic guides and gently snapping assembly togeth­er.
!
CAUTION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Improper wiring or installation may damage the Smart Sensor. Check to make sure wiring is correct before proceeding with installation or turning on unit.
Step 3 — Setup and Checkout
NEW INFINITY SMART SENSOR SETUP
Upon initial power up, the Infinity Smart Sensor will need to be properly addressed. “ZONE” will be displayed and default zone number “2” will be shown in the temperature display. The word “SETUP” will also appear in the lower left text area. Use the TEMP (+/--) button to select the correct zone address number 1 through 8. If only one Damper Control Module exists, the zone address selection will only be 1 through 4. Once the zone number is selected, press the FAN button to store the zone address and exit the setup menu. The Infinity Smart Sensor is ready to operate.
CHANGING ZONE ADDRESS
To change an existing zone address, enter the setup menu by pressing the FAN button for 10 seconds until “ZONE” is displayed. Use the TEMP (+/--) button to select the correct zone address and then press the FAN button once to automatically save and exit the setup menu. If no buttons are pressed for approximately 3 minutes, the screen will automatically save and exit back to a normal display.
To ensure that all changes are recognized by the main control, perform the “Full Installation” function in the Installation & Service Menu of the Infinity Touch Control after zone addresses are changed.
BACKLIGHTING
The LCD backlighting will energize whenever a button is pressed. The backlighting will de--energize after 10 seconds of no push button or activity. To enable constant backlighting, press the FAN
2