Carrier Ultra, Solara, Extra XT, Ultra XL Operator's Manual

OPERATOR’S MANUAL
for
Ultra/Ultra XL, Ultima and Solara
Beginning With
S/N HAR90573670
And Extra/Ultra XT
Trailer Refrigeration Units
Standard Microprocessors
62--10601 Rev G
Trailer Refrigeration
FAULT
START/STOP
FUNCTION CHANGE
UNIT
DATA
PRETRIP
CHECK
AUTOS/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
-20 34.5° F
STANDBY
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGIN E
R
MANUAL
for
OPERATOR’S
TRAILER
REFRIGERATION UNITS
WITH STANDARD
MICROPROCESSOR
CONTENTS
Page
Safety 1....................................
Unit Identification 2..........................
Unit Operation 4............................
Starting Unit 4..............................
Pretrip Check 8.............................
Changing Setpoint 10........................
Start--Stop Operation 12......................
Continuous Run Operation 14.................
Manual Defrost 16...........................
Function Change 18.........................
Unit Data 20................................
Alarm Display and Reset 22..................
Standby Operation 24........................
Stopping Unit 26............................
Pre--Trip Inspection 28.......................
Product Loading 30..........................
Recommended Transport Temperatures 32.....
Problems 33................................
Fuses 34...................................
Unit Maintenance 35.........................
Unit Maintenance Schedule 36................
Priming Fuel System 39......................
Emergency Road Service 40..................
1
62--10601
SAFETY
Your Carrier Transicold refrigeration unit has been designed with the safety of the operator in mind. During all pre-trip inspections, daily inspections, and problem troubleshooting, you may be exposedtomovingparts; pleasestayclear of allmoving partswhen the unit isin operation and when the Start/Run-Off Switch is in the START/RUN position.
AUTO-START
YourrefrigerationunitisequippedwithAuto-Startin both Start/Stop and Continuous Run modes. The unit may start at any time, a buzzer will sound for 5 seconds before the unit is started. When performing any check of the refrigeration unit (e.g., checking the belts, checking the oil), makecertain that the Start/Run-Off Switch is in the OFF position.
ENGINE COOLANT
The engine is equipped with a pressurized cooling system. Under normal operating conditions, the coolant in theengine andradiator isunder high pressureandis veryhot. Contact withhot coolantcan cause severe burns. Do not remove the cap from a hot radiator; if the cap must be removed, do sovery slowly in order to releasethe pressure without spray.
REFRIGERANTS
The refrigerant contained in the refrigeration system of your unit can cause frostbite, severe burns, or blindness when in direct contact with the skin or eyes. For this reason, and because of legislation regarding the handling of refrigerants during system service, we recommend that, whenever your unit requires service of the refrigeration system, you contact your nearest Carrier Transicold authorized repair facility for service.
BATTERY
This unit is equipped with a lead-acid type battery. The battery normally vents small amounts of flammable hydrogen gas. Do not smoke when checking the battery. A battery explosion can cause serious physical harm and/or blindness.
2
62--10601
UNIT IDENTIFICATION
Each unit is identified by a decal attached to the frame of the unit. This decal is on the roadside vertical frame post behind the roadside side door. This decal identifies the complete model number of the unit, the serial number, the refrigerant charge and quantity, and the date the unit was placed in service.
If a problem occurs, please refer to the information on this decal, and make a note of the model andserial number before calling for assistance. This information will be needed when you contact a technician orCarrier TransicoldService Engineer sothat they may properly assist you.
3
62--10601
Unit Identification Decal
4
62--10601
UNIT OPERATION STARTING UNIT - AUTO
FAUL T STAND-BY
START/STOP
FUNCTION
CHANGE
UNIT DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
88888
88
88
88
888888
88
88
88
88
88
88
88
88
88
8****
FAUL T STAND-BY
START/STOP
FUNCTION
CHANGE
UNIT DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
----22220000....00003
33
34444....5555°°°°F
FF
F
1. Place the START/RUN - OFF switch to START/RUN position.
DISPLAY
SELF TEST
5
62--10601
The microprocessor controller will run a self test. All of the mode lights will light, all of the segments on the display will be turned on.
The display willthen show the setpoint temperature onthe left and the box temperature of the trailer on the right. The last character (after the degree symbol) shows the temperature units as F (Fahrenheit) or C (Celsius).
If the unit is in Auto Start/Stop mode or Continuous Run/Auto Operation mode, the glow plugs will energize, the buzzer will sound, and the diesel engine will start.
If the unit is set for Continuous Run/Manual Operation mode, the unit must be started manually.
WARNING
Under no circumstances should ether or any other starting aids be used to start engine.
The microprocessor controller monitors box temperature, battery voltage, and engine coolant temperature. Once the setpoint is reached the controller will shut off the diesel engine to conserve fuel. The controller willnot shutoff theengine ifthebatteryvoltage is not sufficient to restart it.
The controller will restart the engine if any of the following criteria have been met:
SBox temperature has changed by ¦ 11°F(¦ 6.1°C)for setpoints in the perishable range and +1 1° F(+6.1°C) for setpoints in the frozen range DURING minimum off time.
SBox temperature has moved away from setpoint by ¦3.6°F (2.0°C) AFTER minimum off time for setpoints in the perishable range or +3.6°F(2.0°C) for setpoints in the frozen range.
SThe battery voltage drops below 11 Vdc (12.2 Vdc for units with EEPROM Rev 3.25 and higher -- Refer to Page 21 for unit data).
SThe engine coolant temperature drops below 34°F(1°C).
6
62--10601
STARTING UNIT - MANUAL (CONTINUOUS RUN ONLY)
FAUL T STAND-BY
FUNCTION CHANGE
UNIT
DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
M
MM
MAAAANNNNO
OO
OPPPP
Side of Control Box
4. Hold GLOW/CRANK switch in the GLOW position for
5 to 15 seconds (see chart on next page). Then hold the GLOW/CRANK switch in the CRANK position for up to 10 seconds to start the diesel engine.
1. Place START/RUN - OFF switch to the START/RUN position. If START/STOP is displayed, press AUTO S/S-CONTINUOUS toggle key to place unit in Continuous Run Mode .
2. Press FUNCTION CHANGE key until AUTO OP or MAN OP is displayed. If MAN OP appears, unit is in manual start mode.
3. If AUTO OP appears, first press ENTER key, then UP or DOWN arrow key until MAN OP is displayed. Press ENTER key to lock in manual mode.
5. With MAN OP selected, press AUTO S/S-CONTINUOUS key to toggle between Auto Start-Stop and Manual Start/Continuous Run modes.
7
62--10601
Glow Time
Engine Coolant Temperature Glow Time in Seconds Engine Coolant Temperature
TV/Short
(Default)
DI/
Long
Less than 32_F(0_C) 15 55 33_Fto50_F(1_Cto10_C) 10 40 51_Fto77_F(11_Cto25_C) 5 25 Greater than 78_F(26_C) 0 10
NOTE: When the unit is inContinuous Run mode and set for Manual Operation, the unit must be started manually
WARNING
Under no circumstances should ether or any other starting aids be used to start engine.
8
62--10601
PRETRIP CHECK 1.
FAUL T ST AND-BY
COOL
FUNCTION
CHANGE
UNIT DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
PPPPP
PP
PPPPPPPPP
2. Press PRETRIP CHECK key to start PRETRIP. “PPPP” will appear on the display.
1. Start and run unit until box temperature is 40_F(
4.4°C)or
lower.
9
62--10601
The PRETRIP mode is for checking unit operation and evaluating operation of all modes. The unit will cycle thru all modes of operation at30 secondintervals. WhenPretripis complete,Pretrip mode is terminated and the unit returns to normal operation.
The final PRETRIP mode is Defrost. When Defrost ends, PRETRIP will be complete.
This is not a self-diagnosing pretrip test. Nospecific pretrip alarms will be generated. Pretrip must be monitored by the user to verify that the unit operates through all cycles.
See Page 28 for more information on Pretrip.
10
62--10601
CHANGING SETPOINT
FAUL T STAND-BY
FUNCTION
CHANGE
UNIT DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
----22220000....00003
33
34444....5555°°°°F
FF
F
Press ENTER key when desired setpoint is
displayed to lock in new setpoint.
New setpoint will flash and then return to original
setpoint if ENTER key is not pressed.
Press UP arrow key to increase displayed
setpoint.
Press DOWN arrow key to decrease
displayed setpoint.
11
62--10601
Setpoints of -22°Fto+89°F (-30°Cto+32°C) may be entered via the keypad. The controller always retains thelast entered setpoint in memory. If no setpoint is in memory (i.e. on initial startup), the controller will lock out the run relay and flash “SP” on the left hand display until a valid setpoint is entered. The setpoint may be changed up or down in 1° increments by pressing and releasing either the UP ARROW or DOWN ARROW key.
Youcan notchangesetpoint when unit isin Pretripor whenviewing Unit Data or Functional Parameters.
Pressing the ENTER key will cause the new displayed setpoint value tobecome active. If thedisplay is flashing and the newvalue is not entered, after 5 seconds of no keyboard activity, the display will flash for 5 seconds and then revert back to the last setpoint. All other keys are active at this time and may be pushed while the display is flashing.