Carrier SINGLE PACKAGE ROOFTOP 48HC, 48TC*D, 48HC17, 48HC20, 48HC24 Installation Instructions Manual

...
Page 1
48HC
Single Package Rooftop Gas Heating/Electric Cooling Unit with Puronr (R---410A) Refrigerant Sizes: 17, 20, 24, 28
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation
SAFETY CONSIDERATIONS 2....................
INSTALLATION 9...............................
Jobsite Survey 9................................
Step 1 -- Plan for Unit Location 9..................
Roof Mount 9...............................
Step 2 -- Plan for Sequence of Unit Installation 10.....
Curb--Mount Installation 10....................
Pad--Mount Installation 10.....................
Frame--Mount Installation 10...................
Step 3 -- Inspect Unit 10..........................
Step 4 -- Provide Unit Support 10..................
Roof Curb Mount 10.........................
Slab Mount (Horizontal Units Only) 10..........
Alternate Unit Support
(In Lieu of Curb or Slab Mount) 10.............
Step 5 -- Field Fabricate Ductwork 14...............
Step 6 -- Rig and Place Unit 14....................
Positioning on Curb 15.......................
Step 7 -- Horizontal Duct Connection 15............
Step 8 -- Install Outside Air Hood — Factory Option 15.. Step 9 -- Install Flue Hood and Combustion Air Hood 16..
Step 10 -- Install Gas Piping 16....................
Gas Supply Line 16..........................
Factory--Option Thru--Base Connections 18.......
Step 11 -- Install External Condensate Trap and Line 19..
Step 12 -- Make Electrical Connections 19...........
Field Power Supply 19........................
Units without Factory--Installed Disconnect 20....
Units with Factory--Installed Disconnect 20.......
All Units 20................................
Convenience Outlets 20.......................
Factory--Option Thru--Base Connections 22......
Units without Thru--Base Connections 22.........
Field Control Wiring 22.......................
Thermostat 22...............................
Unit without Thru--Base Conversion Kit 22.......
Heat Anticipator Settings 23...................
Transformer Connection
for 208--v Power Supply 23.....................
Humidi--MiZer
Humidi--MiZer -- Space RH Controller 24........
PremierLinkt (Factory Option) 26...............
Supply Air Temperature (SAT) Sensor 29.........
Outdoor Air Temperature (OAT) Sensor 29.......
EconoMi$er2 29.............................
Field Connections 29..........................
Space Sensors 31............................
Connect Thermostat 31.......................
Configure the Unit for Thermostat Mode 31......
Economizer Controls 32........................
Indoor Air Quality (CO
Outdoor Air Quality Sensor 32.................
Space Relative Humidity Sensor or
Humidistat Connections 33....................
Smoke Detector/Fire Shutdown (FSD) 34.........
Filter Status Switch 34........................
Supply Fan Status Switch 34...................
Remote Occupied Switch 34...................
Power Exhaust (output) 34.....................
CCN Communication Bus 35..................
RTU Open Control System 36...................
Supply Air Temperature (SAT) Sensor 39.........
Outdoor Air Temperature (OAT) Sensor 39.......
EconoMi$er2 39.............................
R
Control Connections 24..........
)Sensor 32.............
2
Page 2
Field Connections 39..........................
Space Temperature (SPT) Sensors 40............
Indoor Air Quality (CO
Outdoor Air Quality Sensor 41.................
Space Relative Humidity Sensor or Humidistat 41..
Smoke Detector/Fire Shutdown (FSD) 42.........
Connecting Discrete Inputs 42..................
Communication Wiring -- Protocols 43............
General 43.................................
Local Access 44.............................
RTU Open Troubleshooting 44.................
Outdoor Air Enthalpy Control 45.................
Differential Enthalpy Control 45................
Smoke Detectors 46...........................
48HC
Return Air Sensor Tube Installation 46...........
Smoke Detector Test Magnet 47................
Additional Application Data 47.................
Step 13 -- Adjust Factory--Installed Options 50........
Step 14 -- Install Accessories 50...................
)Sensor 40.............
2
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when leak testing at pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig (3450 Pa) will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig (3450 Pa), it must be replaced before use. When pressure testing field--supplied gas piping at pressures of 0.5 psig (3450 Pa) or less, a unit connected to such piping must be isolated by closing the manual gas valve.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Ware safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
2
Page 3
48HC
Fig. 1 -- Unit Dimensional Drawing – 17 Size Unit
C10896
3
Page 4
48HC
Fig. 1 -- Unit Dimensional Drawing – 17 Size Unit (cont.)
C10897
4
Page 5
48HC
Fig. 2 -- Unit Dimensional Drawing – 20 and 24 Size Units
C10892
5
Page 6
48HC
Fig. 2 -- Unit Dimensional Drawing – 20 and 24 Size Units (cont.)
C10893
6
Page 7
48HC
Fig. 3 -- Unit Dimensional Drawing – 28 Size Unit
C10900
7
Page 8
48HC
Fig. 3 -- Unit Dimensional Drawing – 28 Size Unit (cont.)
C10901
8
Page 9
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 4.
NOTE: Consider also the effect of adjacent units.
96” (2438)
36” (914)
42” (1067)
Be sure that the unit is installed such that snow will not block the combustion air intake or flute outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof--covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA----54----84----1. In Canada, installation must be in accordance with the CAN1----B149 installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adjacent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent to public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.
48HC
42” (1067)
36” (914)
Fig. 4 -- Service Clearance Dimensional Drawing
Table 1 – Operating Weights
48HC**
Base Unit 1892 (858) 2102 (954) 2247 (1019) 2292 (1040)
Economizer 245 (111) 245 (111) 245 (111) 245 (111)
Powered Outlet 32 (15) 32 (15) 32 (15) 32 (15)
H u m i d i --- M i Z e rRSystem
Curb
14--- in/356 mm 273 (124) 273 (124) 273 (124) 273 (124)
24--- in/610 mm 350 (159) 350 (159) 350 (159) 350 (159)
17 20 24 28
83 (38) 83 (38) 88 (40) 92 (42)
C10638
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 11 — Install External Condensate Trap and Line – for required trap dimensions.
Roof Mount —
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
UNIT LB (KG)
9
Page 10
Step 2 — Plan for Sequence of Unit Installation
A
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Curb--mounted installation —
NOTE: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasket supplied with the roof curb as shown in Figs. 6, 7 and 8. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 9. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Install curb Install field--fabricated ductwork inside curb Install thru--base service connection fittings (affects
curb and unit) Rig and place unit Remove top skid Install outside air hood Install smoke detector tube Install combustion air hood
48HC
Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and
not to the unit. Thru--the--base power connection must be installed before the unit is set on the roof curb. If
field--installed thru--the--roof curb gas connections are desired remove knockout in basepan located in the gas section, see Fig. 5 for location. Gas connections and power connections to the unit must be field installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the basepan, remove knockouts in basepan located in control box area of access panel; see Fig. 1, 2, or 3 for basepan knockout locations for location. Attach the service connections to the basepan.
Install other accessories
Hood Carton Location
Pad--mounted installation —
(rear access panel)
Prepare pad and unit supports Rig and place unit Remove duct covers and top skid
Control Box
ccess Panel
Install smoke detector return air sensor tube Install field--fabricated ductwork at unit duct openings Install outside air hood Install combustion air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Filter and
Indoor Coil
Access Panel
Indoor Blower Access Panel
Gas Heat
Access Panel
Compressor
(each side)
C11154
Fig. 5 -- Typical Access Panel and Compressor Locations
Frame--mounted installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim with transportation agency.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6–in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Locate the carton containing the outside air hood parts; see Figs. 5 and 12. Do not remove carton until unit has been rigged and located in final position.
Step 4 — Provide Unit Support
Roof Curb Mount —
Alternate Unit Support (In Lieu of Curb or Slab Mount) —
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 4 equally spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each side. Locate pads so that they support the rails. Make sure to avoid the fork openings.
Accessory roof curb details and dimensions are shown in Figs. 6, 7 and 8. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
10
Page 11
48HC
C10954
Fig. 6 -- Roof Curb Details – 17 Size Unit
11
Page 12
48HC
Fig. 7 -- Roof Curb Details – 20 and 24 Size Units
C10955
12
Page 13
48HC
C10956
Fig. 8 -- Roof Curb Details – 28 Size Unit
13
Page 14
A minimum clearance is not required around ductwork.
C
A
B
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.25” (6)
B-C
0.5” (12)
Fig. 9 -- Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition) shall not exceed 0.5 in. wg (87 Pa) with economizer or without economizer.
For vertical ducted applications, secure all ducts to roof curb
48HC
and building structure. Do not connect ductwork to unit. Fabricate supply ductwork so that the cross sectional
dimensions are equal to or greater than the unit supply duct opening dimensions for the first 18 in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
A-C
0.5” (12)
C10628
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roofing materials.
Membrane roofs can be cut by sharp sheet metal edges. Be careful when placing any sheet metal parts on such roof.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 (on page 9) and Fig. 10 for additional information.
Lifting holes are provided in base rails as shown in Fig. 10. Refer to rigging instructions on unit.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck when packaging is removed.
CAUTION
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
"914-1371"
(36"-54")
"B"
SEE DETAIL A
"C"
"A"
UNIT
48HC**17 2339 1061 127.8 3249 58.7 1491 52.3 1328
48HC**20 2549 1156 141.5 3595 71.5 1816 52.3 1328
48HC**24 2699 1224 141.5 3595 71.5 1816 60.3 1532
48HC**28 2748 1246 157.8 4007 80.3 2040 60.3 1532
NOTES:
1. Dimensions in ( ) are inches.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
MAX WEIGHT
LB KG IN MM IN MM IN MM
Fig. 10 -- Rigging Details
Before setting the unit onto the curb, recheck gasketing on curb.
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
DIMENSIONS
A B C
DETAIL A
C09107
14
Page 15
PositioningonCurb—
r
Position unit on roof curb so that the following clearances are maintained: curb and the base rail inside the right and left,
1
/4in. (6 mm) clearance between the roof
1
/2in. (12 mm) clearance between the roof curb and the base rail inside the front and back. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately equal to Details A and B in Figs. 6, 7 and 8.
Do not attempt to slide unit on curb after unit is set. Doing so will result in damage to the roof curb seal.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of 48 in. (1220 mm) from electric and gas meters, gas regulators, and gas relief equipment. Minimum distance between unit and other electrically live parts is 48 inches (1220 mm).
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate mechanical draft system flue assembly at least 48 in. (1220 mm) from an adjacent building or combustible material.
Field--supplied
(3
/4--inch) flanges should be attached to horizontal duct openings (see Fig. 11) and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Step 8 — Install Outside Air Hood — Factory Option
The outside air hood for factory--option economizer and two--position damper is shipped in knock--down form and requires field assembly. The panel for the hood top is shipped on the end of the unit (see Fig. 12). The remaining parts for the hood assembly (including side panels, filters and tracks) are shipped in a carton that is secured to the rear of the blower assembly. Access the carton location through rear panel (see Fig. 13).
Hood Top
Shipping Position
48HC
After unit is in position, remove rigging skids and shipping materials.
Step 7 — Horizontal Duct Connection
Refer to Figs. 1, 2 and 3 for locations and sizes of the horizontal duct connections. Note that there are two different return air duct connection locations – one for unit without an economizer (on back side of unit) and a different one for unit equipped with an economizer (on left end, under the economizer hood). The supply air duct connection is on the back side. See Fig. 11 for top view depicting typical horizontal duct arrangements.
C09134
Fig. 12 -- Hood Top – Shipping Position
To remove the hood parts package:
1. Remove the back blower access panel.
2. Locate and cut the strap, being careful to not damage any wiring.
3. Carefully lift the hood package carton through the back blower access opening.
See Fig. 14 for identification of the various parts of the hood assembly.
Hood
Package
Horizontal Supply Air
Supply
Location Back Back Left end
H e ig ht --- I n . ( mm ) 157/8(402) 493/8(1253) 183/8(467)
W i d t h --- i n. ( m m ) 293/4(756) 233/8(593) 615/8(1564)
Return Air Duct
Return without
Economizer
Fig. 11 -- Horizontal Duct Opening Dimensions
without
Economizer
Return Air Duct
with Economize
Return with
Economizer
C10626
C09133
Fig. 13 -- Hood Package – Shipping Location
15
Page 16
To assemble the outside air hood:
A
1. Remove hood top panel from shipping position on unit end.
2. Install four angles to the upper end panel using the screws provided.
The combustion air hood is attached to the back of the burner access panel. Remove the two screws securing the hood to the back of the burner access panel. Using the two screws, re--attach the hood to the front of the burner access panel as shown in Fig. 16.
3. Apply seal strip to mating flanges on the side plates of the hood (see Fig. 14).
Apply Seal Strips to the back of
Apply Seal Strip to the front of
pply Seal Strips to the back of these flanges
2
Seal Strips
this flange
6
5
48HC
these surfaces
7
4
Item # Description Qty 1 Angles 4 2 Side Plates 2 3 Hood 1 4 Outdoor Air Screens 4 5 Side Filter Supports 2 6 Side Drip Angles 2 7 Top Diverters 2
4
1
Fig. 14 -- Hood Part Identification and Seal Strip
Application Areas
3
7
4
Apply Seal Strip to the back of this flange
Apply Seal Strip to the front of this flange
4
C09079
2
5
6
Combustion
Air Hood
Flue Hood
C10744
Fig. 16 -- Flue Hood and Combustion Air Hood Details
Step 10 — Install Gas Piping
Installation of the gas piping must be in accordance with local building codes and with applicable national codes.
4. Secure side plates to panel using the screws provided.
5. Apply seal strip to mating flange of the hood (see Fig. 14).
6. Secure top flange using screws provided in kit.
7. Install outdoor air screens by sliding them into the channel formed by the four angles installed in step 2. Make sure that the screens extend across the entire length of the hood.
8. Install side filter supports using the screws provided.
9. Install side drip angles using the screws provided.
10. Run a continuous length of seal strip across the hood covering the engagement holes in the lower hood.
11. Install top diverter using the screws provided.
12. On units with barometric relief, remove screws at bot­tom of relief damper. Do not discard damper door.
In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances.
This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.
NOTE: Furnace gas input rate on rating plate is for installation up to 2000 ft (610 m) above sea level. In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas connection must not be less than 5 in. wg (1246 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection.
C09090
Fig. 15 -- Hood Assembly – Completed
Step 9 — Install Flue Hood and Combustion Air Hood
The flue hood is shipped screwed to the fan deck inside the burner compartment. Remove the burner access panel and then remove the flue hood from its shipping location. Using the screws provided, install flue hood in the
Gas Supply Line —
The gas supply pipe enters the unit adjacent to the burner access panel on the front side of the unit, through the grommeted hole. The gas connection to the unit is made
3
to the Table 2 lists typical
/4in. FPT gas inlet port on the unit gas valve.
3
/4inch NPT (National Pipe Thread) field supplied pipe fittings required for Thru--Base gas supply, starting from the unit gas valve (see Fig. 17).
location shown in Fig. 16.
16
Page 17
Table 2 – Typical3/4--in NPT Field Supplied Piping Parts
R
Item Qty CPN Description
1 1 CA15RA201 90 Deg Street Elbow
2 1 CA01CA226 5 Inch Long Nipple
3 1 CA85RA201 Ground--- Joint Union
4 1 CA01CA218 3 Inch Long Nipple
5 1 CA05RA201 90 Deg Elbow
6 1 CA01CA250 12 Inch Long Nipple
7 1 CA05RA201 90 Deg Elbow
8 1 CA01CA218 3 Inch Long Nipple
9 1 CA20RA201 TEE
10 1 CA01CN222 4 Inch Long Nipple (Sediment Trap)
11 1 CA38RA201 Cap
12 1 CA01CA220 31/2Inch Long Nipple
13 1 GB30 NIBCORBall Valve
14 1 CA01CA238 8 Inch Long Nipple
15 1 CA05RA201 90 Deg Elbow
4
6
7
8
9
10
11
12
5
13
14
3
2
1
15
Fig. 17 -- Gas Supply Line Piping with Thru--Base
C10999
48HC
Pipe gas supply into 90 degree elbow item 15 (see Table 2) through the hole in the unit basepan.
For typical
3
/4inch NPT field supplied fittings required for NON Thru--Base gas supply starting from the unit gas valve, omit items 14 and 15 from Table 2 and pipe gas supply into TEE. See Fig. 18.
Table 3 – Natural Gas Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE MIN MAX
48HC** 17, 20, 24, 28
!
CAUTION
5.0 in. wg (1246 Pa)
13.0 in. wg (3240 Pa)
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to equipment.
When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Do not use a pipe smaller than the size specified. Size the gas supply line to allow for a maximum pressure drop of 0.5--in wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high--fire flow rate.
The gas supply line can approach the unit in two ways: horizontally from outside the unit (across the roof), or through unit basepan. Observe clearance to gas line components per Fig. 19.
7
8
9
12
BASE UNIT
BASE RAIL
17
4
6
13
10
11
5
Fig. 18 -- Gas Supply Line Piping
9” MINIMUM CLEARANCE FOR PANEL REMOVAL
MANUAL GAS SHUTOFF VALVE
48” MINIMUM
ROOF CURB
NFGC – National Fuel Gas Code
Field supplied.
*
NOTE: Follow all local codes.
STEEL PIPE
NOMINAL DIAMETER
1
1
(in.)
1
3
/
4
/
or larger
4
/
2
or 1
LEGEND
Fig. 19 -- Gas Piping Guide
3
2
1
X
GAS REGULATOR
*
*
DRIP LEG
PER NFGC
SPACINGOFSUPPORTS
X DIMENSION
*
FIELD-
FABRICATED
SUPPORT
(ft)
6 8
10
C101006
FROM GAS METE
*
C11121
Page 18
Factory--Option Thru--Base Connections — Electrical Connections: Knockouts are located in the
control box area. Remove the appropriate size knockout for high voltage connection. Use the field supplied connector depending on wiring or conduit being utilized.
7
Remove the
/8--in (22mm) knockout and appropriate connector for low voltage wiring. If non--unit powered convenience outlet is being utilized, remove the (22mm) knockout and utilize appropriate connector for 115 volt line. See “Step 12 — Making Electrical Connections” for details.
Gas Connections: Remove the knockout in the base pan
3
and route
/4--in. gas line up through the opening. Install an elbow and route gas line through opening in panel after first removing plastic bushing. Install a gas shut off followed by a drip leg and ground--joint union. Route gas line into gas section through the grommet (Part #: KA56SL112) at the gas inlet and into the gas valve. See
48HC
Fig. 17 and Table 2. If a regulator is installed, it must be located 4 feet (1.22 meters) from the flue outlet.
Some municipal codes require that the manual shutoff valve be located upstream of the sediment trap. See Fig. 18 for typical piping arrangements for gas piping that has been routed through the sidewall of the base pan.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
/4--in. in every 15 ft (7 mm in every 5 m) to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appro­priate straps, hangers, etc. Use a minimum of one hanger every 6 ft (1.8 m). For pipe sizes larger than
1
/2--in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of lique­fied petroleum gases as specified by local and/or nation­al codes. If using PTFE (Teflon) tape, ensure the materi­al is Double Density type and is labeled for use on gas lines. Apply tape per manufacturer’s instructions.
4. Pressure--test all gas piping in accordance with local and national plumbing and gas codes before connect­ing piping to unit.
7
/8-- i n
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground--joint union.
Check for gas leaks at the field--installed and factory--installed gas lines after all piping connections have been completed. Use soap--and--water solution (or method specified by local codes and/or regulations).
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
S Connect gas pipe to unit using a backup wrench to
avoid damaging gas controls.
S Never purge a gas line into a combustion chamber. S Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections.
S Use proper length of pipe to avoid stress on gas
control manifold.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics.
BURNER
ORIFICE
A93059
Fig. 20 -- Orifice Hole
18
Page 19
Step 11 — Install External Condensate Trap and Line
The unit has one3/4-in. condensate drain connection on the end of the condensate pan (see Fig. 21). See Figs. 1, 2 and 3, item “E”, in the view labeled “BACK (HORIZONTAL DISCHARGE)” for the location of the condensate drain connection.
Step 12 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
CONDENSATE DRAIN CONNECTION
C10729
Fig. 21 -- Condensate Drain Pan Connection
The piping for the condensate drain and external trap can be completed after the unit is in place. Hand tighten fittings to the drain pan fitting. Provide adequate support for the drain line. Failure to do so can result in damage to the drain pan. See Fig. 22.
MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE
TO ROOF DRAIN
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended.
BASE RAIL
OPEN VENT
2˝ (51) MIN
DRAIN PLUG
SEE NOTE
ROOF CURB
C08022
Fig. 22 -- Condensate Drain Piping Details
All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection
3
/4-in.).
(
NOTE: Field--supplied wiring shall conform with the limitations of minimum 63_F(33_C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always--energized convenience outlet operation is desired, connect the source leads to the line side of the unit--mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) On a unit without a unit--mounted disconnect, connect the source leads to the line side with unit field power leads. See Fig. 23.
BLK
YEL
BLU
LOAD
SIDE
LINE SIDE
SEE
DETAIL
A
L1
L2
L3
A
DETAIL
CONTROL BOX
C11181
Fig. 23 -- Location of TB1
Field power wires are connected to the unit at line--side pressure lugs on the terminal block (see wiring diagram label for control box component arrangement) or at factory--installed option non--fused disconnect switch. Use copper conductors only.
NOTE: Make field power connections directly to line connection pressure lugs only.
48HC
19
Page 20
!
WARNING
!
CAUTION
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or unsatisfactory performance.
Do not connect aluminum wire between disconnect switch and air conditioning unit. Use only copper wire.(SeeFig.24.)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
48HC
ALUMINUM
WIRE
Fig. 24 -- Disconnect Switch and Unit
Units without Factory--Installed Disconnect —
When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
Units with Factory--Installed Disconnect —
A93033
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
Units Without Disconnect Option
TB1
11 12 13
Disconnect
per
NEC
L1
L2 L3
208/230-3-60
460-3-60 575-3-60
Units With Disconnect Option
Factory
Wiring
The factory--installed option disconnect switch is located in the main control box. The manual switch handle is accessible on the corner post adjacent to the control box access panel.
All Units --
All field wiring must comply with NEC and all local code requirements.
Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 25 for power wiring connections to the unit power terminal block and equipment ground. Maximum wire size is 2/0 AWG per pole.
Provide a ground--fault and short--circuit over--current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over--current Protection) device size.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 11. On 3--phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 11 (see Note 2 on page 49) to determine the percent of voltage imbalance.
T1 T2 T3
Optional
Disconnect
Switch
L1 L2 L3
L1 L2 L3
Fig. 25 -- Power Wiring Connections
Convenience Outlets —
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Lock--out and tag--out this switch, if necessary.
C101000
20
Page 21
Two types of convenience outlets are offered on 48HC models: Non--unit powered and unit--powered. Both types provide a 125--volt GFCI (ground--fault circuit--interrupter) duplex receptacle rated at 15--A behind a hinged access cover, located on the corner panel of the unit. See Fig. 26.
Control Box
Access Panel
Electric
Disconnect
Switch
Convenience
Outlet
C10641
Fig. 26 -- Convenience Outlet Location
Installing Weatherproof Cover: A weatherproof
while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due to its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.
Non--unit powered type: This type requires the field installation of a general--purpose 125--volt 15--A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125--v power supply conductors into the bottom of the utility box containing the duplex receptacle.
Unit--powered type: A unit--mounted transformer is factory--installed to stepdown the main power supply voltage to the unit to 115--v at the duplex receptacle. This option also includes a manual switch with fuse, located in a control box and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 26.
The primary leads to the convenience outlet transformer are not factory--connected. If local codes permit, the transformer primary leads can be connected at the line--side terminals on the unit--mounted non--fused disconnect switch; this will provide service power to the unit when the unit disconnect switch is open. See Fig. 28.
48HC
The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.
DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET. LOCK--OUT AND TAG--OUT ALL POWER.
Remove the blank cover plate at the convenience outlet; discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as shown in Fig. 27. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.
COVER – WHILE-IN-USE WEATHERPROOF
RECEPTACLE NOT SHOWN
UNIT
VOLTAGE
208,
230
460 480
575 600
CONNECT
AS
240
PRIMARY
CONNECTIONS
L1: RED +YEL L2: BLU + GRA
L1: RED Splice BLU + YEL L2: GRA
L1: RED L2: GRA
C10730
TRANSFORMER
TERMINALS
H1 + H3 H2 + H4
H1
H2 + H3
H4
H1 H2
Fig. 27 -- Weatherproof Cover Installation
BASE PLATE FOR GFCI RECEPTACLE
Fig. 28 -- Powered Convenience Outlet Wiring
C09022
21
Page 22
Field Control Wiring —
NOTICE/AVIS
Convenience Outlet Utilization
Maximum Intermittent Use 15 - Amps
Maximum Continuous Use 8 - Amps
Observe a 50% limit on the circuit
Loading above 8 - Amps
Utilisation de la prise utilitaire
Usage intermittent maximum 15 - Amps
Usage continu maximum 8 - Amps
Observez une limite de 50% sur le circuit
Chargement au-dessus de 8 - Amps
Fig. 29 -- Convenience Outlet Utilization Notice
Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.
Using unit--mounted convenience outlets: Units with
48HC
unit--mounded convenience outlet circuits will often require that two disconnects be opened to de--energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de--energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
Factory--Option Thru--Base Connections —
All units are equipped with the ability to bring utilities through the base.
Gas is brought up through an embossed area located in the gas section behind the gas entrance post. Access is gained through the gas access panel. A knock out must be removed to accomplish this.
The electrical entrance is located in the control box area and can be accessed through the control box access panel. An embossed area is provided with three knock outs. High voltage is brought through the multi knock out by removing the appropriate size for the size of the fitting
7
required. A An additional
/8--in. knock out is provided for low voltage.
7
/8--in. knock out is provided for a 115 volt line which is used when the unit is equipped with the non--unit powered convenience outlet option.
50HE501288
2.0
C10077
The 48HC unit requires an external temperature control device. This device can be a thermostat (field--supplied) or a PremierLink controller (available as factory--installed option or as field--installed accessory, for use on a Carrier Comfort Network or as a stand alone control) or the RTU Open for Building Management Systems using non--CCN protocols (RTU Open is available as a factory--installed option only).
Thermostat —
Install a Carrier--approved accessory 2--stage thermostat according to installation instructions included with the accessory. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24--v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24--v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire (35_C minimum). For50to75ft.(15to23m),useno.16AWGinsulated wire (35_C minimum). For over 75 ft. (23 m), use no. 14 AWG insulated wire (35_C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Unit without Thru--Base Connection Kit —
Correctly rated low voltage wire can be routed through the rubber grommet located on the corner post adjacent to the control box access panel. Route wire through the grommet and then route the wire behind the corner post utilizing the factory provided wire ties secured to the control box. This will insure separation of the field low voltage wire and the high voltage circuit. Route the low voltage wire to the central terminal board. See Fig. 30.
All required fittings are field supplied. Install fittings when access to both top and bottom of the base pan is available. See electrical and gas connections for routing and connection information.
Units without Thru--Base Connections —
1. Install liquid tight conduit between disconnect and control box.
2. Pull correctly rated high voltage wires through the conduit.
3. Install power lines to terminal connections as shown in Fig. 25.
22
Page 23
Typical Thermostat Corrections
X
Central
Terminal
Board
Rubber
Grommet
X
C
G
W2
W1
O/B/Y2
(see Note)
Y1
R
Note: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2.
Field Wiring
!
See Caution
CAUTION
C
G
W2
W1
Y2
Y1
R
T–STAT
C
G
W2
W1
Y2
Y1
R
UNIT DAMAGE HAZARD
Failure to follow this caution may cause a short circuit.
Carefully check the connection of control coductor for indoor fan control at terminal G. Connecting the indoor fan lead to terminal C will cause a short circuit condition which can cause component damage inside the unit or at thermostat.
C10731
Fig. 30 -- Typical Low--Voltage Control Connections
NOTE: If utilizing the through the base connections,
route the low voltage wire through the wire ties to the central terminal board.
Corner
Post
Wire
Ties
Thru the Base
Connection
C10734
Fig. 31 -- Field Control Wiring Raceway
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second--stage heating.
Transformer Connection for 208--v Power Supply —
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire
1
with the connection and moving it to the 208-v
/4-in. female spade connector from the 230--v
1
/4-in. male
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information.
48HC
23
Page 24
Humidi--MiZerRControl Connections
Humidi--MiZer – Space RH Controller — NOTE: The Humidi--MiZer is a factory installed option.
The Humidi--MiZer dehumidification system requires a field--supplied and --installed space relative humidity control device. This device may be a separate humidistat control (contact closes on rise in space RH above control setpoint) or a combination thermostat--humidistat control device such as Carrier’s EDGE isolated contact set for dehumidification control. The humidistat is normally used in applications where a temperature control is already provided (units with PremierLinkt control).
To connect the Carrier humidistat (HL38MG029):
1. Route the humidistat 2--conductor cable (field--sup­plied) through the hole provided in the unit corner post.
48HC
2. Feed wires through the raceway built into the corner post (see Fig. 31) to the 24--v barrier located on the left side of the control box. The raceway provides the UL--required clearance between high--voltage and low--voltage wiring.
3. Use wire nuts to connect humidistat cable to two PINK leads in the low–voltage wiring as shown in Fig. 34.
To connect the Thermidistat device (33CS2PPRH--01):
1. Route the Thermidistat multi--conductor thermostat cable (field--supplied) through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post (see Fig. 31) to the 24--v barrier located on the left side of the control box. The raceway provides the UL--required clearance between high--voltage and low--voltage wiring.
3. The Thermidistat has dry contacts at terminals D1 and D2 for dehumidification operation (see Fig. 35). The dry contacts must be wired between CTB terminal R and the PINK lead to the LTLO switch with field--supplied wire nuts. Refer to the installation instructions included with the Carrier Edge Thermidistat device (Form 33CS--65SI or latest) for more information.
R
Pro Thermidistat with
% RELATIVE HUMIDITY
C09295
Fig. 32 -- Accessory Field--Installed Humidistat
®
C09296
Fig. 33 -- EDGE Pro Thermidistat
24
Page 25
48HC
Fig. 34 -- Typical Humidi--MiZerRAdaptive Dehumidification System Humidistat Wiring
EDGE Pro THERMIDISTAT
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT RRS
SRTN
HUM
D1 D2 V+
Vg
Humidi-MiZer™ FIOP
Unit CTB
THERMOSTAT
X*
C
G
W2
W1
Y2
Y1
R
C11139
Fig. 35 -- Typical Rooftop Unit with Humidi--MiZer Adaptive Dehumidification System
*Connection not required.
C09298
with EDGE Pro Thermidistat Device
25
Page 26
PremierLinkt (Factory--Option)
48HC
Fig. 36 -- PremierLink Controller
The PremierLink controller (see Fig. 36) is compatible with Carrier Comfort Networkr (CCN) devices. This control is designed to allow users the access and ability to change factory--defined settings, thus expanding the function of the standard unit control board. CCN service access tools include System Pilott, Touch Pilott and Service Tool. (Standard tier display tools Navigatort and Scrolling Marquee are not suitable for use with latest PremierLink controller (Version 2.x).)
The PremierLink control is factory--mounted in the 48HC unit’s main control box to the right of the Central Terminal Board (CTB) (see Fig. 37). Factory wiring is completed through harnesses connected to the CTB thermostat. Field connections are made at a 16--pole terminal block (TB3) located at the top of the unit control box in front of the PremierLink controller. The factory--installed PremierLink control includes the supply--air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$ert2 package. (See page 45 for accessory enthalpy controls.)
The PremierLink controller requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied).
NOTE: PremierLink controller is shipped in Sensor mode. To be used with a thermostat, the PremierLink controller must be configured to Thermostat mode. Refer to PremierLink Configuration instructions for Operating Mode.
C08199
C10643
Fig. 37 -- 48HC Control Box Component Locations
26
Page 27
48HC
C11140
Fig. 38 -- PremierLink Wiring Schematic
27
Page 28
48HC
Fig. 39 -- PremierLink Wiring Schematic with Humidi--MiZer
28
R
C11141
Page 29
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 48HC unit, the unit is supplied with a supply--air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6--inches (12.7 mm) in length. It is a nominal 10--k ohm thermistor.
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor —
The SAT is factory--wired. The SAT probe is mounted in the fan deck (see Fig. 40). It can be removed or remounted per local codes.. Drill or punch a 1/2--in. hole in the flange or duct. Use two field--supplied, self--drilling screws to secure the sensor probe in a horizontal orientation. Insure that the sensor wires do not contact the hot surface of the heat exchanger.
SUPPLY AIR TEMPERATURE SENSOR
SUPPLY AIR
RETURN AIR
ROOF CURB
C10733
Fig. 40 -- Mounting Location for Supply Air
Temperature (SAT) Sensor on 48HC Units
NOTE: Refer to Form 33CS--67SI for complete
PremierLink configuration, operating sequences and troubleshooting information. Have a copy of this manual available at unit start--up.
The OAT is factory--mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.
EconoMi$er2 —
The PremierLink control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the PremierLink control; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors) Space CO Outdoor air CO
sensor
2
sensor
2
Refer to Table 4 for accessory part numbers.
Field Connections
Field connections for accessory sensor and input devices are made at the 16--pole terminal block (TB3, see Fig. 38 and Fig. 39) located on the control box top shelf in front of the PremierLink control. Some input devices also require a 24--vac signal source; connect at CTB terminal R at “THERMOSTAT” connection strip for this signal source. See connections figures on following pages for field connection locations (and for continued connections at the PremierLink board inputs).
Table 5 provides a summary of field connections for units equipped with Space Sensor. Table 6 provides a summary of field connections for units equipped with Space Thermostat.
48HC
OUTDOOR AIR
APPLICATION
Differential Dry Bulb
Tem p er at ur e w i th
PremierLink
(PremierLink requires
4 --- 2 0 m A A c t u a t o r)
Single Enthalpy with
PremierLink
(PremierLink requires
4 --- 2 0 m A A ct ua to r)
Differential Enthalpy
with PremierLink
(PremierLink requires
4 --- 2 0 m A A ct ua to r)
NOTES:
Sensors (Optional):
CO
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 --- Aspirator box used for duct--- mounted CO 33ZCT55CO2 --- Space temperature and CO 33ZCT56CO2 --- Space temperature and CO
TEMPERATURE
SENSOR
I nc lu de d ---
CRTEMPSN001A00
I nc lu de d ---
Not Used
I nc lu de d ---
Not Used
Table 4 – PremierLink Sensor Usage
RETURN AIR
TEMPERATURE
SENSOR
R eq ui re d ---
33ZCT55SPT
or equivalent
---
---
room sensor.
room sensor with override.
2
room sensor with override and setpoint.
2
2
29
ENTHALPY SENSOR
OUTDOOR AIR
--- ---
R eq ui re s ---
33CSENTHSW
R eq ui re s ---
33CSENTHSW
or equivalent
RETURN AIR
ENTHALPY SENSOR
---
R eq ui re s ---
33CSENTSEN
or equivalent
Page 30
TB3 TERMINAL FIELD CONNECTION INPUT SIGNAL
1 T5 5 --- S EN / T 5 6 --- S EN Analog (10k thermistor) 2 RMTOCC Discrete, 24VAC 3 T5 5 --- S EN / T 5 6 --- S EN Analog (10k thermistor) 4 CMPSAFE Discrete, 24VAC 5 T56--- SET Analog (10k thermistor) 6 FSD Discrete, 24VAC 7 LOOP --- PWR Analog, 24VDC 8 SPS Discrete, 24VAC
9 IAQ--- SEN A na lo g , 4 --- 2 0 m A 10 FILTER Discrete, 24VAC 11 I AQ --- C OM / O A Q --- C OM /R H --- C O M A n a l o g , 4 --- 2 0 m A 12 CCN + (RED) Digital,,5VDC 13 OAQ --- SEN /R H ---SEN A na lo g , 4 --- 2 0 m A 14 CCN Gnd (WHT) Digital, 5VDC 15 AUX OUT(Power Exhaust) (Output)Discrete 24VAC
48HC
LEGEND:
T55 --- Space Temperature Sensor T56 --- Space Temperature Sensor CCN --- Carrier Comfort Network (communication bus) CMPSAFE --- Compressor Safety
FILTER --- Dirty Filter Switch F S D --- F ir e S hu td ow n IAQ --- Indoor Air Quality (CO OAQ --- Outdoor Air Quality (CO RH --- Relative Humidity
SFS --- Supply Fan Status
16 CCN --- (BLK) Digital, 5VDC
)
2
)
2
Table 5 – Space Sensor Mode
Table 6 – Thermostat Mode
TB3 TERMINAL FIELD CONNECTION INPUT SIGNAL
1 RAT SEN Analog (10k thermistor) 2 G Discrete, 24VAC 3 RAT SEN Analog (10k thermistor) 4 Y1 Discrete, 24VAC 5 6 Y2 Discrete, 24VAC 7 LOOP---PWR Analog, 24VDC 8 W1 Discrete, 24VAC
9 I A Q --- S E N Analog, 4--- 20mA 10 W2 Discrete, 24VAC 11 I A Q --- C OM /O A Q --- C O M / R H --- C O M Analog, 4 ---20mA 12 CCN + (RED) Digital, 5VDC 13 O A Q --- S EN / R H --- S E N Analog, 4 ---20mA 14 CCN Gnd (WHT) Digital, 5VDC 15 AUX OUT (Power Exhaust) (Output) Discrete 24VAC 16 CCN --- (BLK) Digital, 5VDC
LEGEND:
CCN --- Carrier Comfort Network (communication bus) G --- T h e r m o st at Fa n IAQ --- Indoor Air Quality (CO OAQ --- Outdoor Air Quality (CO RAT --- Return Air Temperature RH --- Relative Humidity W1 --- Thermostat Heat Stage 1 W2 --- Thermostat Heat Stage 2 Y1 --- Thermostat Cool Stage 1 Y2 --- Thermostat Cool Stage 2
)
2
)
2
30
Page 31
Space Sensors —
The PremierLink controller is factory--shipped configured for Space Sensor Mode. A Carrier T--55 or T--56 space sensor must be used. T--55 space temperature sensor provides a signal of space temperature to the PremierLink control. T--56 provides same space temperature signal plus it allows for adjustment of space temperature setpoints from the face of the sensor by the occupants.
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
BRN (GND) BLU (SPT)
CCN COM
SENSOR WIRING
C08201
Fig. 41 -- T--55 Space Temperature Sensor Wiring
Connect T--55: See Fig. 41 for typical T--55 internal
connections. Connect the T--55 SEN terminals to TB3 terminals 1 and 3 (see Fig. 42).
TB3 PL
SEN J6-7
SEN
1
3
J6-6
C10023
Fig. 42 -- PremierLink T--55 Sensor
Connect T--56: See Fig. 43 for T--56 internal connections.
Install a jumper between SEN and SET terminals as illustrated. Connect T--56 terminals to TB3 terminals 1, 3 and 5 (see Fig. 44).
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
SET
BLK (T56)
BRN (GND) BLU (SPT)
CCN COM
SENSOR WIRING
JUMPER TERMINALS AS SHOWN
TB3 PL
SEN J6-7
SEN
Jumper
1
TB3
3
PL
J6-6
SET
SET
5
J6-5
C10022
Fig. 44 -- PremierLink T--56 Sensor
Connect Thermostat —
A 7--wire thermostat connection requires a 24--v power source and a common connection. Use the R and C terminals on the CTB’s THERMOSTAT connection strip for these. Connect the thermostat’s Y1, Y2, W1, W2 and G terminals to PremierLink TB3 as shown in Fig. 45.
If the 48HC unit is equipped with factory--installed smoke detector(s), disconnect the factory BLU lead at TB3--6 (Y2) before connecting the thermostat. Identify the BLU lead originating at CTB--DDC--1; disconnect at TB3--6 and tape off. Confirm that the second BLU lead at TB3--6 remains connected to PremierLink J4--8.
SPACE
THERMOSTAT
R
GJ4-12
Y1
Y2
W1
W2
C
CTB
THERMOSTAT
R
TB3
2
4
6
8
10
C
THERMOSTAT
PL
J4-10
J4-8
J4-6
J4-4
CTB
C10283
Fig. 45 -- Space Thermostat Connections
If the 48HC unit has an economizer system and free--cooling operation is required, a sensor representing Return Air Temperature must also be connected (field--supplied and installed). This sensor may be a T--55 Space Sensor (see Fig.
41) installed in the space or in the return duct, or it may be sensor PNO 33ZCSENSAT, installed in the return duct. Connect this sensor to TB3--1 and TB3--3 per Fig. 42.
Configure the Unit for Thermostat Mode —
Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value
1). Change the value to 0 to reconfigure the controller for Thermostat Mode.
48HC
Cool Warm
Fig. 43 -- T--56 Internal Connections
C08202
When the PremierLink is configured for Thermostat Mode, these functions are not available: Fire Shutdown (FSD), Remote Occupied (RMTOCC), Compressor Safety (CMPSAFE), Supply Fan Status (SFS), and Filter Pressure Switch (FILTER).
31
Page 32
Economizer Controls
Indoor Air Quality (CO2)Sensor—
The indoor air quality sensor accessory monitors space carbon dioxide (CO monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO
The CO
sensors are all factory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO requirements and terminal locations. See Fig. 46 for typical CO
sensor wiring schematic.
2
) levels. This information is used to
2
present in the space air.
2
sensor for electrical
2
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 46. Connect the 4--20 mA terminal to terminal TB3--9 and connect the SIG COM terminal to terminal TB3--11. See Fig. 47.
IAQ Sensor
24 VAC
J4
4-20mA
SIG COM
TB3
9
TB3
11
PL
J5-5
J5-3
C11156
Fig. 47 -- Indoor CO2Sensor (33ZCSENCO2)
Connections
Refer to Form 33CS--67SI, PremierLink Installation, Start--up, and Configuration Instructions, for detailed configuration information.
48HC
+
0-10VDC
-
SIG COM
+
4-20mA
NC
COM NO
24 VAC
HG
OR
+
-
24 VDC
2
1
J3 J4
5
1
4
32
7
6
8
Fig. 46 -- Indoor/Outdoor Air Quality (CO2)Sensor
(33ZCSENCO2) -- Typical Wiring Diagram
To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return--air grille (if present) so it senses the concentration of CO leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
ALARM RELAY
}
CONTACTS
C08635
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO dioxide (CO
) levels in the outside ventilation air and
2
sensor is designed to monitor carbon
2
interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 48. The outdoor air CO
sensor must be located in the
2
economizer outside air hood.
2
COVER REMOVED SIDE VIEW
Fig. 48 -- Outdoor Air Quality Sensor Cover
C07135
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor: For each sensor, use two 2--conductor 18 AWG (American Wire Gage) twisted--pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.
Wiring the Outdoor Air CO
Sensor: A dedicated
2
power supply is required for this sensor. A two--wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 46. Connect the 4 to 20 mA terminal to the TB3--13 terminal of the 48HC. Connect the SIG COM terminal to the TB3--11 terminal of the 48HC. See Fig. 49.
32
Page 33
OAQ Sensor
24 VAC
4-20mA
SIG COM
TB3
13
TB3
11
PL
J5-2
J5-3
C11157
Fig. 49 -- Outdoor CO2Sensor Connections
Space Relative Humidity Sensor or Humidistat Connections —
Space Relative Humidity Sensor connections: The
accessory space relative humidity sensor (33ZCSENSRH-01) is installed on an interior wall to measure the relative humidity of the air within the occupied space.
The use of a standard 2 X 4 inch electrical box to accommodate the wiring is recommended for installation. The sensor can be mounted directly on the wall, if acceptable by local codes.
The sensor must be mounted vertically on the wall. The Carrier logo should be orientated correctly when the sensor is properly mounted.
Avoid corner locations. Allow at least 4 ft between the sensor and any corner. Airflow near corners tends to be reduced, resulting in erratic sensor readings. The sensor should be vertically mounted approximately 5 ft up from the floor, beside the space temperature sensor.
For wiring distances up to 500 feet, use a 3--conductor, 18 or 20 AWG cable. ACCN communication cable can be used, although the shield is not required. The shield must be removed from the sensor end of the cable if this cable is used. See Fig. 51 for wiring details.
TB3-7
TB3-13
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in permanent damage to the sensor.
DO NOT clean or touch the sensing element with chemical solvents as they can permanently damage the sensor.
!
CAUTION
UNIT PERFORMANCE HAZARD
Failure to follow this caution will result in inaccurate sensor readings.
DO NOT mount the sensor in drafty areas such as near heating or air--conditioning ducts, open windows, fans, or over heat sources such as baseboard heaters, radiators, or wall--mounted dimmers. Sensors mounted in those areas will produce inaccurate readings.
If the sensor is installed directly on a wall service, install the humidity sensor using 2 screws and 2 hollow wall anchors (field supplied). Do not over tighten screws. See Fig. 50.
MOUNTING HOLES
Io
Gnd
Vin
Vo
WIRING OPENING
RED
BLACK
Io VoVin Gnd
C11085
Fig. 51 -- Space Relative Humidity Sensor Connection
The power for the sensor is provided by the PremierLink control on terminal J5--4 (+33 to +35vdc).
To wire the sensor:
1. At the sensor, remove 4 inches of the jacket from the cable. Strip or. Route the cable through the wire clearance open­ing in the center of the sensor. See Fig. 50.
2. Connect a field--supplied BLACK wire to the sensor screw terminal marked Vin.
3. Connect a field--supplied RED wire into the sensor screw terminal marked Io.
4. Connect the field--supplied RED wire from the sensor to TB3--13.
5. Connect the field--supplied BLACK wire from the sensor to TB3--7.
Humidistat connections: A humidistat can not be directly connected to the PremierLink controller. Follow the instructions on pages 24 & 25 to connect a humidistat or a thermostat as an electromechanical device.
1
/4inch of insulation from each conduct-
48HC
SW2
123456
ON
Fig. 50 -- Space Relative Humidity Sensor Installation
C11084
33
Page 34
Smoke Detector/Fire Shutdown (FSD) —
This function is available only when PremierLink is configured for (Space) Sensor Mode. The unit is factory--wired for PremierLink FSD operation when PremierLink is factory--installed.
On 48HC units equipped with factory--installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The PremierLink communicates the smoke detector’s tripped status to the CCN building control. See Figs. 38 and 39, the PremierLink wiring schematics.
Filter Status Switch —
Connect one side of the switch’s NO contact set to CTB’s THERMOSTAT--R terminal. Connect the other side of the NO contact set to TB3--8. Setpoint for Supply Fan Status is set at the switch. See Fig. 53.
Fan (Pressure) Switch (NO, close on rise in pressure)
CTB
Thermostat
R
TB3
8
PL
J4-6
C10287
Fig. 53 -- PremierLink Wiring Fan Pressure Switch
Connection
This function is available only when PremierLink is configured for (Space) Sensor Mode.
48HC
PremierLink control can monitor return filter status in two ways: By monitoring a field--supplied/installed filter pressure switch or via supply fan runtime hours.
Using switch input: Install the dirty filter pressure switch according to switch manufacturer’s instructions, to measure pressure drop across the unit’s return filters. Connect one side of the switch’s NO contact set to CTB’s THERMOSTAT--R terminal. Connect the other side of the NO contact set to TB3--10. Setpoint for Dirty Filter is set at the switch. See Fig. 52.
Filter Switch (NO, close on rising pressure (high drop))
CTB
Thermostat
R
TB3
10
Fig. 52 -- PremierLink Filter Switch Connection
When the filter switch’s NO contact set closes as filter pressure drop increases (indicating dirt--laden filters), the input signal to PremierLink causes the filter status point to read “DIRTY”.
Using Filter Timer Hours: Refer to Form 33CS--67SI for instructions on using the PremierLink Configuration screens and on unit alarm sequence.
Supply Fan Status Switch —
The PremierLink control can monitor supply fan operation through a field--supplied/installed differential pressure switch. This sequence will prevent (or interrupt) operation of unit cooling, heating and economizer functions until the pressure switch contacts are closed indicating proper supply fan operation.
Install the differential pressure switch in the supply fan section according to switch manufacturer’s instructions. Arrange the switch contact to be open on no flow and to close as pressure rises indicating fan operation.
PL
J4-4
C10286
Remote Occupied Switch —
The PremierLink control permits a remote timeclock to override the control’s on--board occupancy schedule and place the unit into Occupied mode. This function may also provide a “Door Switch” time delay function that will terminate cooling and heating functions after a 2--20 minute delay.
Connect one side of the NO contact set on the timeclock to CTB’s THERMOSTAT--R terminal. Connect the other side of the timeclock contact to the unit’s TB3--2 terminal.
Remote Occupied
Time Clock
LCTB
Thermostat
R
TB3
2
PL
J4-12
C10288
Fig. 54 -- PremierLink Wiring Remote Occupied
Refer to Form 33CS--67SI for additional information on configuring the PremierLink control for Door Switch timer function.
Power Exhaust (output) —
Connect the accessory Power Exhaust contactor coils(s) per Fig. 55.
Power Exhaust
PER
VIO
BRN
TB3
15
CTB
THERMOSTAT
C
PL
J8-3
C11158
Fig. 55 -- PremierLink Power Exhaust Output
Connection
NOTE: The Power Exhaust and Humidi--MiZer
R
options can not be used with PremierLink at the same time as both options require connection at TB3--15 (AUX OUT).
34
Page 35
CCN Communication Bus —
The PremierLink controller connects to the bus in a daisy chain arrangement. Negative pins on each component must be connected to respective negative pins, and likewise, positive pins on each component must be connected to respective positive pins. The controller signal pins must be wired to the signal ground pins. Wiring connections for CCN must be made at the 3--pin plug.
At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft (1219 m), with no more than 60 total devices on any 1000--ft section. Optically isolated RS--485 repeaters are required every 1000 ft (305 m).
NOTE: Carrier device default is 9600 baud. Communications Bus Wire Specifications: The CCN
Communication Bus wiring is field--supplied and field--installed. It consists of shielded 3--conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network.
See Table 7 for recommended cable.
Table 7 – Recommended Cables
MANUFACTURER CABLE PART NO.
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
NOTE: Conductors and drain wire must be at least 20 AWG, stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of
-- 2 0 _C(--4_F) to 60_C (140_F) is required. Do not run communication wire in the same conduit as or next to any AC voltage wiring.
The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communication bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).
Connecting CCN Bus: NOTE: When connecting the communication bus cable,
a color code system for the entire network is recommended to simplify installation and checkout. See Table 8 for the recommended color code.
Table 8 – Color Code Recommendations
SIGNAL TYPE
+ Red 1
Ground White 2
--- Black 3
CCN BUS WIRE
COLOR
CCN PLUG PIN
NUMBER
Connect the CCN (+) lead (typically RED) to the unit’s TB3--12 terminal. Connect the CCN (ground) lead (typically WHT) to the unit’s TB3--14 terminal. Connect the CCN (--) lead (typically BLK) to the unit’s TB3--16 terminal. See Fig. 56.
CCN Bus
PL
J2-1
J2-2GND (WHT)
J2-3– (BLK) 16
C10290
+ (RED)
TB3
12
TB3
14
TB3
Fig. 56 -- PremierLink CCN Bus Connections
48HC
35
Page 36
RTU Open Control System
The RTU Open control is factory--mounted in the 48HC unit’s main control box, to the right of the CTB. See Fig. 37. Factory wiring is completed through harnesses connected to the CTB. Field connections for RTU Open sensors will be made at the Phoenix connectors on the RTU Open board. The factory--installed RTU Open control includes the supply--air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er2 package.
48HC
The RTU Open controller is an integrated component of the Carrier rooftop unit. Its internal application programming provides optimum performance and energy efficiency. RTU Open enables the unit to run in 100% stand--alone control mode, Carrier’s I--Vu Open network, or a Third Party Building Automation System (BAS). On--board DIP switches allow you to select your protocol (and baud rate) of choice among the four most popular protocols in use today: BACnet, Modbus, Johnson N2 and LonWorks. (See Fig. 57.)
Refer to Table 9, RTU Open Controller Inputs and Outputs for locations of all connections to the RTU Open board.
Fig. 57 -- RTU Open Multi--Protocol Control Board
C10811
36
Page 37
48HC
Fig. 58 -- RTU Open System Control Wiring Diagram
C11142
37
Page 38
48HC
Fig. 59 -- RTU Open System Control Wiring Diagram with Humidi--MiZer
38
R
C11143
Page 39
Table 9 – RTU Open Controller Inputs and Outputs
POINT NAME
Space Temp / Zone Temp zone_temp AI (10K Thermistor) J2 0 --- 1 , 2 Supply Air Temperature sa_temp AI (10K Thermistor) J 2 --- 1 , 2 Outdoor Air Temperature oa_temp AI (10K Thermistor) J 2 --- 3 , 4 Space Temperature Offset Pot stpt_adj_offset AI (100K Potentiometer) J 20 --- 3 Safety Chain Feedback safety_status DI (24 VAC) J 1 --- 9 Compressor Safety Status comp_status DI (24 VAC) J 1 --- 2 Fire Shutdown Status firedown_status DI (24 VAC) J 1 --- 1 0 Enthalpy Status enthalpy_status DI (24 VAC) J 2 --- 6 Humidistat Input Status humstat_status DI (24 VAC) J 5 --- 7
Indoor Air CO2 iaq A I ( 4 --- 2 0 m a )
Space Relative Humidity space_rh A I ( 4 --- 2 0 m a) Supply Fan Status* sfan_status DI (24 VAC) Filter Status* filter_status DI (24 VAC) Door Contact Input* door_contact_status DI (24 VAC) Occupancy Contact* occ_contact_status DI (24 VAC)
Economizer Output econ_output AO ( 4 --- 2 0 ma ) J 2 --- 5 SupplyFanRelayState sfan DO Relay (24VAC , 1A) J 1 --- 4 Compressor 1 Relay State comp_1 DO Relay (24VAC , 1A) J 1 --- 8 Compressor 2 Relay State comp_2 DO Relay (24VAC , 1A) J 1 --- 7 Heat Stage 1 Relay State heat_1 DO Relay (24VAC , 1A) J 1 --- 6 Heat Stage 2 Relay State heat_2 DO Relay (24VAC , 1A) J 1 --- 5 Power Exhaust Relay State pexh DO Relay (24VAC , 1A) J 1 1 --- 3 Dehumidification Relay State dehum DO Relay (24VAC, 1A) J 11 --- 7 , 8
LEGEND AI --- A n al o g I np ut AO --- A na lo g O ut pu t DI --- D i sc re te In p ut DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Pa r al le l pi n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a re u s ed f or f i el d --- i n st al la t i on .
BACnet OBJECT
NAME
DEDICATED INPUTS
CONFIGURABLE INPUTS
TYPE OF I/O
OUTPUTS
CONNECTION PIN
NUMBER(S)
J 4 --- 2 o r J 4 --- 5Outdoor Air CO2 oaq A I ( 4 --- 2 0 m a)
J 5 --- 1 o r J 5 --- 3 o r
J55orJ5---7
48HC
The RTU Open controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 48HC unit, the unit is supplied with a supply--air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6--inches (12.7 mm) in length. It is a nominal 10--k ohm thermistor.
The SAT is factory--wired. The SAT probe is wire--tied to the supply--air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re--position the sensor in the flange of the supply--air opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/2--in. hole in the flange or duct. Use two field--supplied, self--drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 40.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.
EconoMi$er2 —
The RTU Open control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU Open control; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors) Space CO Outdoor air CO
sensor
2
sensor
2
Field Connections
Field connections for accessory sensors and input devices are made the RTU Open, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that connects to the RTU Open must be routed through the raceway built into the corner post as shown in Fig. 31. The raceway provides the UL required clearance between high-- and low--voltage wiring. Pass the control wires through the hole provided in the corner post, then feed the wires thorough the raceway
39
Page 40
to the RTU Open. Connect to the wires to the removable Phoenix connectors and then reconnect the connectors to the board.
Space Temperature (SPT) Sensors —
There are two types of SPT sensors available from Carrier, resistive input non-communicating (T55, T56, and T59) and Rnet communicating (SPS, SPPL, SPP, and SPPF) sensors. Each type has a variety of options consisting of: timed override button, set point adjustment, a LCD screen, and communication tie in. Space temperature can be also be written to from a building network or zoning system. However, it is still recommended that return air duct sensor be installed to allow stand-alone operation for back-up. Refer to the configuration section for details on controller configurations associated with space sensors.
S 33ZCT55SPT, space temperature sensor with override
button (T--55)
S 33ZCT56SPT, space temperature sensor with override
48HC
button and setpoint adjustment (T--56)
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and setpoint adjustment (T--59)
Use 20 gauge wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. (152 m). Use a three--conductor shielded cable for the sensor and setpoint adjustment connections. If the setpoint adjustment (slidebar) is not required, then an unshielded, 18 or 20 gauge, two--conductor, twisted pair cable may be used.
Connect T--55: See Fig. 41 for typical T--55 internal connections. Connect the T--55 SEN terminals to RTU Open J20--1 and J20--2. See Fig. 60.
SEN
SEN
J20-1
J20-2
Fig. 60 -- RTU Open T--55 Sensor Connections
C08460
Connect T--59: The T--59 space sensor requires a separate, isolated power supply of 24 VAC. See Fig. 62 for internal connections at the T--59. Connect the SEN terminal (BLU) to RTU Open J20--1. Connect the COM terminal (BRN) to J20--2. Connect the SET terminal (STO or BLK) to J20--3.
BLK (STO)
BRN (COM)
BLU (SPT)
OR SET SEN
OPB COM- PWR+
24 VAC
NOTE: Must use a separate isolated transformer.
J20-3
J20-2
J20-1
SENSOR WIRING
POWER WIRING
C10291
Fig. 62 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Indoor Air Quality (CO
)Sensor—
2
The indoor air quality sensor accessory monitors space carbon dioxide (CO
) levels. This information is used to
2
monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO
The CO
sensors are all factory set for a range of 0 to
2
present in the space air.
2
2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO
sensor for electrical
2
requirements and terminal locations. See Fig. 46 for typical CO
sensor wiring schematic.
2
Connect T--56: See Fig. 43 for T--56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T--56 terminals to RTU Open J20--1, J20--2 and J20--3 per Fig. 61.
SEN J20-1
SEN
Jumper
SET
SET
Fig. 61 -- RTU Open T--56 Sensor Connections
J20-2
J20-3
C08461
To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return--air grille (if present) so it senses the concentration of CO leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor: For each sensor, use two 2--conductor 18 AWG (American Wire Gage) twisted--pair cables (unshielded) to connect the separate
40
2
Page 41
isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 46. Connect the 4--20 mA terminal to RTU Open terminal J4--2 and connect the SIG COM terminal to RTU Open terminal J4--3. See Fig. 63.
IAQ Sensor
4-20mA
SIG COM
J4-2
J4-3
24 VAC
C10738
Fig. 63 -- RTU Open / Indoor CO2Sensor
(33ZCSENCO2) Connections
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO dioxide (CO
) levels in the outside ventilation air and
2
sensor is designed to monitor carbon
2
interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 48. The outdoor air CO
sensor must be located in the
2
economizer outside air hood. Wiring the Outdoor Air CO2Sensor: A dedicated
power supply is required for this sensor. A two--wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
Space Relative Humidity Sensor or Humidistat — Humidi--MiZer
R
Control Wiring: In units equipped
with the Humidi--MiZer option there are two pink (PNK) wires loose in the control box used to control the dehumidification function of the unit. These pink wires are meant to be tied to a space humidistat or thermidistat on an electromechanical unit. On RTU Open equipped units these pink wires must be connected to J11--7 & 8 to allow the Open board to operate the dehumidification function for the unit. Disconnect the J11 Phoenix style connector from the board and use the plug screws to secure the pink wires in pins 7 and 8, reconnect the plug to the board at J11.
Relative Humidity Sensors (Space or Duct Mounted):
The accessory space humidity sensor (33ZCSENSRH-01) or duct humidity sensor (33ZCSENDRH-01) is used to measure the relative humidity of air within the space or return air duct. The RH reading is used to control the Humidi--MiZer option of the rooftop unit. For wiring distances up to 500 ft (152 m), use a 3--conductor, 18 or 20 AWG shielded cable. The shield must be removed from the sensor end of the cable and grounded at the unit end. The current loop power for sensor is provided by the RTU Open controller as 24vdc. Refer to the instructions supplied with the RH sensor for the electrical requirements and terminal locations. RTU Open configurations must be changed after adding an RH sensor. See Fig. 65 and 66 for typical RH sensor wiring.
S J4--1 or J4--4 = 24vdc loop power S J4--2 or J4--5 = 4--20mA signal input
NOTE: The factory default for dehumidification control is normally open humidistat.
48HC
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 46. Connect the 4 to 20 mA terminal to RTU Open terminal J4--5. Connect the SIG COM terminal to RTU Open terminal J4--6. See Fig. 64.
OAQ Sensor/RH Sensor
4-20mA
SIG COM
J4-5
J4-6
24 VAC
Fig. 64 -- RTU Open / Outdoor CO2Sensor
C10739
(33ZCSENCO2) Connections
MOUNTING HOLES
Io
Gnd
Vin
Vo
SW2
123456
ON
Vin - J4-1 or J4-4 24Vdc Io - J4-2 or J4-5 -20mA output
WIRING OPENING
C11087
Fig. 65 -- Space Relative Humidity Sensor Typical Wiring
41
Page 42
J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output
to RTU-OPEN
Relative Humidity Sensor (Polarized Male Connector)
4-20 VAC GND 0-5V mA or or VDC 0-10V
SPAN
ZERO
48HC
C10839
Fig. 66 -- Duct Relative Humidity Sensor Typical Wiring
Humidistat: The accessory humidistat provides the RTU
Open insight to the relative humidity in the space. The humidistat reads the RH level in the space and compares it to its setpoint to operate a dry contact. The humidistat is a dedicated input on the configurable input 9 and tells the RTU Open when the RH level is HIGH or LOW. The normal condition for humidity is LOW. A normally open humidistat is the factory default control for the Humidi--MiZer
R
option.
To wire in the field:
S J5--8 = 24 VAC source for dry contact S J5--7 = Signal input
Smoke Detector/Fire Shutdown (FSD) —
On 48HC units equipped with factory--installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The RTU Open controller communicates the smoke detector’s tripped status to the BAS building control. See Figs. 58 and 59, the RTU Open wiring schematics.
The Fire Shutdown Switch configuration,
MENU
Config→Inputs→input 5, identifies the
normally open status of this input when there is no fire alarm.
Connecting Discrete Inputs —
Filter Status: The filter status accessory is a
field--installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting
MENU
Config→Inputs→input3,5,8,or9to Filter
Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 57 and Fig. 58 or 59 for wire terminations at J5.
Fan Status: The fan status accessory is a field--installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting
MENU
Config→Inputs→input3,5,8,or9to Fan
Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 57 and Fig. 58 or 59 for wire terminations at J5.
Remote Occupancy: The remote occupancy accessory is a field--installed accessory. This accessory overrides the unoccupied mode and puts the unit in occupied mode. When installing this accessory, the unit must be configured for remote occupancy by setting
MENU
Config→Inputs→input3,5,8,or9to Remote
Occupancy and normally open (N/O) or normally closed (N/C).
Also set MENU
Schedules→occupancy source to DI
on/off. Input 8 or 9 is recommended for easy of installation. Refer to Fig. 57 and Table 9 for wire terminations at J5.
Power Exhaust (output): The relay used by the RTU Open board to control power exhaust is a dry contact which means it does not have 24vac. This 24vac must be connected to the relay to allow it to operate the power exhaust relay in the PE accessory. A 24vac source must be provided to J11--2 on the RTU Open control board. This can be provided by the unit’s transformer from various sources. The “R” terminal on the unit’s low voltage terminal board (LVTB) is a logical source. Refer to Fig. 57 and Fig. 58 or 59 for wire terminations at J11.
42
Page 43
Communication Wiring -- Protocols
The RTU Open can be set to communicate on four different protocols: BACnet, Modbus, N2, and LonWorks.
General —
Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possible. Different protocols exist to provide different kinds of information for different applications. In the BAS application, many different protocols are used, depending on manufacturer. Protocols do not change the function of a controller; just make the front end user different.
Switch 3 (SW3) on the board is used to set protocol and baud rate. Switches 1 and 2 (SW1 and SW2) are used to set the board’s network address. See Fig. 67 and 68 for protocol switch settings and address switches. The 3rd party connection to the RTU Open is through plug J19. See Fig. 69 for wiring.
NOTE: Power must be cycled after changing the SW1--3 switch settings.
Refer to the RTU Open Controller Integration Guide (Catalog No. 11--808--428--01) for more detailed information on protocols, 3rd party wiring, and networking.
SW3 Protocol Selection
PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1
BACnet MS/TP (Master)
Modbus (Slave)
N2 (Slave)
LonWorks Unused ON ON OFF ON OFF OFF OFF
NOTE: DS = Dip Switch BACnet MS/TP SW3 example shown
Unused OFF OFF OFF ON OFF Select Baud Select Baud
Unused OFF OFF ON ON OFF Select Baud Select Baud
Unused OFF OFF OFF ON ON OFF OFF
48HC
Baud Rate Selections
BAUD RATE DS2 DS1
9600 OFF OFF
19,200 ON OFF
38,400 OFF ON
76,800 ON ON
Fig. 67 -- RTU Open SW3 Dip Switch Settings
Fig. 68 -- RTU Open Address Switches
C07166
C10815
C10816
Fig. 69 -- Network Wiring
43
Page 44
Local Access — BACview
6
Handheld: The BACview6is a keypad/display
interface used to connect to the RTU Open to access the control information, read sensor values, and test the RTU, see Fig. 70. This is an accessory interface that does not come with the RTU Open controller and can only be used
6
at the unit. Connect the BACview
to the RTU Open J12 local access port. There are 2 password protected levels in the display (User and Admin). The user password is defaulted to 0000 but can be changed. The Admin password is 1111 and cannot be changed. There is a 10 minute auto logout if a screen is idle. See Form 48--50HCTQ--01T, Appendix A for navigation and screen content.
48HC
Virtual BACview: Virtual BACview is a freeware computer
program that functions as the BACview
6
Handheld. The USB Link interface (USB--L) is required to connect a computer to the RTU Open board. The link cable connects a USB port to the J12 local access port. This program functions and operates identical to the handheld.
RTU Open Troubleshooting — Communication LEDs: The LEDs indicate if the
controller is speaking to the devices on the network. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs will appear. See Table 10.
Cable
Access Port
P1 P1
J12
P5 P5
BACview
Fig. 70 -- BACview6Handheld Connections
Protocol Selector
RTU Open
6
Local Access Cable
C10812
44
Page 45
Table 10 – LEDs
The LEDs on the RTU Open Control Board (see Fig. 57) show the status of certain functions:
If this LED is on... Status is...
Power RTU Open has power
Rx RTU Open is receiving data from the network segment
Tx RTU Open is transmitting data over the network segment
DO# The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
2 flashes per second Off Normal
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second On
5 flashes per second On Exec start ---up aborted, Boot is running
5 flashes per second Off Firmware transfer in progress, Boot is running
7 flashes per second
14 flashes per second
On On
NOTE: Refer to Catalog No. 48--50HCTQ--01T for complete configuration of RTU Open, operating sequences and troubleshooting information. Refer to RTU Open Controller Integration Guide (Catalog No. 11--808--428--01)
And Error LED shows... Status is...
2flashes, alternating with Run LED
3flashes, then off
4flashes, then pause
7 flashes per second, alternating with Run LED
14 flashes per second, alternating with Run LED
Enthalpy Switch
Five minute auto --- restart delay after system error
Control module has just been formatted
Two or more devices on this network have the same ARC156 network address
Exec halted after frequent system errors or control programs halted
Ten second recovery period after brownout
Brownout
Failure. Try the following solutions:
S TurnRTUOpenoff,thenon. S Format RTU Open. S Download memory to RTU Open. S Replace RTU Open.
24V
GND
RED
BLK
PL6-1 (24-V)
PL6-4 (COM)
for details on configuration and troubleshooting of connected networks. Have a copy of these manuals available at unit start--up.
Outdoor Air Enthalpy Control (PNO
33CSENTHSW)
LOW
GRA
Factory Wiring Harness
CTB ECON
7
(P’LINK: to J4-2) or (RTU Open: to J2-6)
Fig. 71 -- Enthalpy Switch (33CSENTHSW) Connections
The enthalpy control (33CSENTHSW) is available as a field--installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of
The outdoor enthalpy changeover setpoint is set at the enthalpy controller.
the enthalpy control. (The separate field--installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 71.)
Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled “ESL” to the terminal labeled “LOW”. See Fig. 71. Connect the
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor (see Fig. 72).
enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND).
48HC
C11160
45
Page 46
– 4-20 Main
+ VDC Out
Outside Air Enthalpy Switch
+ 24-36 VDC In
– 4-20 Main Out
24V
GND
LOW
RED
BLK
GRA
Return Air Enthalpy Sensor
PL6-1 (24-V)
PL6-4 (COM)
CTB ECON
7
(P’LINK: to J4-2) or (RTU Open: to J2-6)
ROTATION
Return Air Sampling Tube (Shipping Location)
Fig. 72 -- Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the following:
48HC
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthal­py controller.
2. Connect the field--supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (+) terminal on the enthalpy controller. Connect the BLK wire to (--) spade connector on the return air en­thalpy sensor and the (--) terminal on the enthalpy controller.
Smoke Detectors
Smoke detectors are available as factory--installed options on 48HC models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. The unit is factory--configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements.
C11161
C09102
Fig. 73 -- Typical Supply Air Smoke Detector Sensor
Location
Return Air Detector Sampling Tube
C09135
Fig. 74 -- Return Air Sampling Tube Location
in Unit without Economizer
Return Air Sensor Tube Installation –
The return air sampling tube is shipped in the units supply fan section, attached to the blower housing (see Fig. 73. Its operating location is in the return air section of the unit (see Fig. 74, unit without economizer, or Fig. 75, unit with economizer), inserted into the return air sensor module housing which protrudes through the back of the control box.
Return Air Detector Sampling Tube
Fig. 75 -- Return Air Sampling Tube Location
in Unit with Economizer
46
C09136
Page 47
To install the return air sensor sampling tube:
1. Remove the tube from its shipping location.
2. Open the unit end to access the return air sensor (loc­ated on right--hand partition)
3. Orient the tube’s sampling holes into the return air flow direction. For vertical application, position the sampling holes on the bottom of the tube, facing into the bottom return duct opening. For horizontal applic­ation, position the sampling holes on the side of the tube, facing the unit’s end panel.
4. Insert the sampling tube into the return air sensor module until the tube snaps into position.
5. Replace end panel or outside air hood.
Table 11 – Unit Wire/Fuse or HACR Breaker Sizing Data
Smoke Detector Test Magnet —
Locate the magnet; it is shipped in the control box area.
Additional Application Data —
Refer to Catalog No. HKRNKA--1XA for discussions on additional control features of these smoke detectors including multiple unit coordination.
NOM.
V --- P h --- H z
UNIT
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D17
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D20
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D24
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D28
5 7 5 --- 3 --- 6 0
COMBUS T IO N
FAN MOTOR
IFM
TYPE
STD
MED 71.0 90.0 74 410 82.8 100.0 88 430
HIGH 75.8 100.0 80 419 87.6 100.0 93 439
STD
MED 36.3 45.0 38 243 42.5 50.0 45 255
HIGH 38.9 50.0 41 247 45.1 50.0 48 259
STD
MED 26.2 30.0 27 184 31.0 40.0 33 192
HIGH 29 35 31 198 33.8 40 36 206
STD
MED 80.5 100 85 449 92.3 100 98 469
HIGH 85.9 100 91 459 97.7 125 104 479
STD
MED 39.2 50 41 249 45.4 50 49 261
HIGH 42 50 45 254 48.2 60 52 266
STD
MED 29 35 31 200 33.8 40 36 208
HIGH 32.4 40 35 198 37.2 45 40 206
STD
MED 94.1 110 100 554 105.9 125 113 574
HIGH 107.6 125 114 628 119.4 150 128 648
STD
MED 51.4 60 54 282 57.6 70 61 294
HIGH 57.4 70 61 319 63.6 80 68 331
STD
MED 38.9 50 41 202 43.7 50 47 210
HIGH 39.4 50 42 229 44.2 50 47 237
STD
MED 122.8 150 127 594 134.6 175 141 614
HIGH 135.5 175 142 668 147.3 175 156 688
STD
MED 56.8 70 60 308 63 80 67 320
HIGH 62.8 80 67 345 69 80 74 357
STD
MED 43.8 50 46 226 48.6 60 52 234
HIGH 44.3 50 47 253 49.1 60 52 261
FLA FLA
0.52 5.9
0.3 3.1
0.24 2.4
0.52 5.9
0.3 3.1
0.24 2.4
0.52 5.9
0.3 3.1
0.24 2.4
0.52 5.9
0.3 3.1
0.24 2.4
POWER
EXHAUST
NO C.O. or UNPWR C.O.
NO P.E. w/ P.E. (pwrd fr/ unit)
MCA
68.3 90.0 71 393 80.1 100.0 85 413
34.9 45.0 36 234 41.1 50.0 44 246
26.2 30.0 27 184 31.0 40.0 33 192
75.7 100 79 440 87.5 100 93 460
36.6 45 38 245 42.8 50 46 257
26.2 30 27 186 31 40 33 194
88.7 100.0 93 544 100.5 125.0 107 564
48.6 60.0 51 277 54.8 60.0 58 289
35.5 45.0 37 204 40.3 50.0 43 212
117.4 150.0 121 584 129.2 175.0 135 604
54.0 60.0 57 303 60.2 70.0 64 315
40.4 50.0 42 228 45.2 50.0 48 236
FUSE or
HACR BRKR
DISC. SIZE
FLA LRA FLA LRA
MCA
FUSE or
HACR BRKR
DISC. SIZE
48HC
NOTE: See page 49 for table legend and notes.
47
Page 48
Table 11 -- Unit Wire/Fuse or HACR Breaker Sizing Data (cont)
COMBUS T IO N
NOM.
V --- P h --- H z
UNIT
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D17
5 7 5 --- 3 --- 6 0
208/230---3---60
48HC
4 6 0 --- 3 --- 6 0
48HC*D20
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D24
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D28
5 7 5 --- 3 --- 6 0
IFM
TYPE
STD
MED 75.8 100.0 80 415 87.6 100.0 93 435
HIGH 80.6 100.0 85 424 92.4 100.0 99 444
STD
MED 38.5 50.0 41 245 44.7 50.0 48 257
HIGH 41.1 50.0 44 249 47.3 60.0 51 261
STD
MED 27.9 35.0 29 186 32.7 40.0 35 194
HIGH 30.7 40.0 33 200 35.5 45.0 38 208
STD
MED 85.3 100 90 454 97.1 110 104 474
HIGH 90.7 100 96 464 102.5 125 110 484
STD
MED 41.4 50 44 251 47.6 60 51 263
HIGH 44.2 50 47 256 50.4 60 54 268
STD
MED 30.7 40 33 202 35.5 45 38 210
HIGH 34.1 40 36 200 38.9 45 42 208
STD
MED 98.9 125 105 559 110.7 125 119 579
HIGH 112.4 125 120 633 124.2 150 133 653
STD
MED 53.6 60 57 284 59.8 70 64 296
HIGH 59.6 70 64 321 65.8 80 71 333
STD
MED 40.6 50 43 204 45.4 50 49 212
HIGH 41.1 50 44 231 45.9 50 49 239
STD
MED 127.6 175 133 599 139.4 175 147 619
HIGH 140.3 175 148 673 152.1 200 161 693
STD
MED 59 70 62 310 65.2 80 70 322
HIGH 65 80 69 347 71.2 80 76 359
STD
MED 45.5 60 48 228 50.3 60 54 236
HIGH 46 60 49 255 50.8 60 54 263
FAN MOTOR
FLA FLA MCA
0.52 5.9
0.3 3.1
0.24 2.4
0.52 5.9
0.3 3.1
0.24 2.4
0.52 5.9
0.3 3.1
0.24 2.4
0.52 5.9
0.3 3.1
0.24 2.4
POWER
EXHAUST
NO P.E. w/ P.E. (pwrd fr/ unit)
FUSE or
HACR BRKR
73.1 90.0 77 398 84.9 100.0 90 418
37.1 45.0 39 236 43.3 50.0 46 248
27.9 35.0 29 186 32.7 40.0 35 194
80.5 100 85 445 92.3 100 98 465
38.8 50 41 247 45 50 48 259
27.9 35 29 188 32.7 40 35 196
93.5 110.0 99 549 105.3 125.0 112 569
50.8 60.0 54 279 57.0 70.0 61 291
37.2 45.0 39 206 42.0 50.0 45 214
122.2 150.0 127 589 134.0 175.0 140 609
56.2 70.0 59 305 62.4 80.0 66 317
42.1 50.0 44 230 46.9 60.0 50 238
DISC. SIZE
FLA LRA FLA LRA
w/ PWRD C.O.
MCA
FUSE or
HACR BRKR
DISC. SIZE
NOTE: See page 49 for table legend and notes.
48
Page 49
Legend and Notes for Table 11
LEGEND:
BRKR --- Circuit breaker CO --- Convenience outlet DISC --- Disconnect FLA --- Full load amps LRA --- Locked rotor amps MCA --- Minimum circuit amps P E --- P ow er e xh au st PWRD CO --- Powered convenient outlet UNPWR CO --- Unpowered convenient outlet NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to de­termine the percentage of voltage imbalance.
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60
AB = 224 v BC = 231 v AC = 226 v
Average Voltage =
(224 + 231 + 226)
= 227
3
=
681
3
Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.76%
4
227
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
48HC
49
Page 50
48HC
Economizer 2 Position Damper
Fig. 76 -- EconoMi$ert IV Wiring
Step 13 — Adjust Factory--Installed Options
EconoMi$er IV Occupancy Switch —
Refer to Fig. 76 for general EconoMi$er IV wiring. External occupancy control is managed through a connection on the Central Terminal Board.
If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked OCCUPANCY on CTB. Remove or cut jumper JMP 2 to complete the installation.
Step 14 — Install Accessories
Available accessories include:
Roof Curb Thru--base connection kit (must be installed before unit
is set on curb) LP conversion kit Manual outside air damper High Altitude Gas kits Low Ambient Controls Thermostat / Sensors
Unit Without Economizer or 2 Position Damper
C10645
Two--Position motorized outside air damper EconoMi$er2 (without control/for external signal and
integrated barometric relief) EconoMi$er IV (with control and integrated barometric
relief) Power Exhaust Differential dry--bulb sensor (EconoMi$er IV) Outdoor enthalpy sensor Differential enthalpy sensor
sensor
CO
2
DDC interface (PremierLink) Louvered hail guard Phase monitor control Winter Start kit
Refer to separate installation instructions for information on installing these accessories.
Pre--Start and Start--Up
This completes the mechanical installation of the unit. Refer to the unit’s Service and Maintenance manual for detailed Pre--Start and Start--up instructions.
50
Page 51
48HC
51
Page 52
48HC
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 04/11
Manufacturer reserves the r ight to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 48HC ---11SI
Replaces: 48HC ---08SI
52
Loading...