Failure to follow this warning could result in personal
injury or death.
Disconnect gas piping from unit when leak testing at
pressure greater than 0.5 psig (3450 Pa). Pressures
greater than 0.5 psig (3450 Pa) will cause gas valve
damage resulting in hazardous condition. If gas valve
is subjected to pressure greater than 0.5 psig (3450
Pa), it must be replaced before use. When pressure
testing field--supplied gas piping at pressures of 0.5
psig (3450 Pa) or less, a unit connected to such piping
must be isolated by closing the manual gas valve.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lock(s) and lockout tag(s). Unit may have more
than one power switch.
Improperinstallation,adjustment,alteration,service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal injury
or property damage. Consult a qualified installer, service
agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use
factory--authorized kits or accessories when modifying this
product. Refer to the individual instructions packaged with
the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
nationalelectricalcodes(inUSA,ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safety information. This is the
safety--alert symbol
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety--alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
. When you see this symbol on the
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at
higher pressures than standard R--22 systems. Do not
use R--22 service equipment or components on Puron
refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Ware safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning equipment.
2
Page 3
48HC
Fig. 1 -- Unit Dimensional Drawing – 17 Size Unit
C10896
3
Page 4
48HC
Fig. 1 -- Unit Dimensional Drawing – 17 Size Unit (cont.)
C10897
4
Page 5
48HC
Fig. 2 -- Unit Dimensional Drawing – 20 and 24 Size Units
C10892
5
Page 6
48HC
Fig. 2 -- Unit Dimensional Drawing – 20 and 24 Size Units (cont.)
C10893
6
Page 7
48HC
Fig. 3 -- Unit Dimensional Drawing – 28 Size Unit
C10900
7
Page 8
48HC
Fig. 3 -- Unit Dimensional Drawing – 28 Size Unit (cont.)
C10901
8
Page 9
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb
or other) that provides for the minimum clearances
required for safety. This includes the clearance to
combustible surfaces, unit performance and service access
below, around and above unit as specified in unit
drawings. See Fig. 4.
NOTE: Consider also the effect of adjacent units.
96” (2438)
36” (914)
42” (1067)
Be sure that the unit is installed such that snow will not
block the combustion air intake or flute outlet.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof--covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air. For proper unit operation, adequate combustion and
ventilation air must be provided in accordance with
Section 5.3 (Air for Combustion and Ventilation) of the
National Fuel Gas Code, ANSI Z223.1 (American
National Standards Institute) and NFPA (National Fire
Protection Association) 54 TIA----54----84----1. In Canada,
installation must be in accordance with the CAN1----B149
installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
Locate mechanical draft system flue assembly at least 4 ft
(1.2 m) from any opening through which combustion
products could enter the building, and at least 4 ft (1.2 m)
from any adjacent building (or per local code). Locate the
flue assembly at least 10 ft (3.05 m) from an adjacent
unit’s fresh air intake hood if within 3 ft (0.91 m) of same
elevation (or per local code). When unit is located
adjacent to public walkways, flue assembly must be at
least 7 ft (2.1 m) above grade.
48HC
42” (1067)
36” (914)
Fig. 4 -- Service Clearance Dimensional Drawing
Table 1 – Operating Weights
48HC**
Base Unit1892 (858)2102 (954)2247 (1019)2292 (1040)
Select a unit mounting system that provides adequate
height to allow installation of condensate trap per
requirements. Refer to Step 11 — Install External
Condensate Trap and Line – for required trap dimensions.
Roof Mount —
Checkbuildingcodesforweightdistribution
requirements. Unit operating weight is shown in Table 1.
UNIT LB (KG)
9
Page 10
Step 2 — Plan for Sequence of Unit Installation
A
The support method used for this unit will dictate different
sequences for the steps of unit installation. For example, on
curb--mounted units, some accessories must be installed on
the unit before the unit is placed on the curb. Review the
following for recommended sequences for installation steps.
Curb--mounted installation —
NOTE: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasket supplied with the roof
curb as shown in Figs. 6, 7 and 8. Improperly applied gasket
can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are show in
Fig. 9. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
curb and unit)
Rig and place unit
Remove top skid
Install outside air hood
Install smoke detector tube
Install combustion air hood
48HC
Install flue hood
Install gas piping
Install condensate line trap and piping
Make electrical connections
Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to curb and
not to the unit. Thru--the--base power connection must be
installed before the unit is set on the roof curb. If
field--installed thru--the--roof curb gas connections are
desired remove knockout in basepan located in the gas
section, see Fig. 5 for location. Gas connections and
power connections to the unit must be field installed after
the unit is installed on the roof curb.
If electric and control wiring is to be routed through the
basepan, remove knockouts in basepan located in control
box area of access panel; see Fig. 1, 2, or 3 for basepan
knockout locations for location. Attach the service
connections to the basepan.
Install other accessories
Hood Carton Location
Pad--mounted installation —
(rear access panel)
Prepare pad and unit supports
Rig and place unit
Remove duct covers and top skid
Control Box
ccess Panel
Install smoke detector return air sensor tube
Install field--fabricated ductwork at unit duct openings
Install outside air hood
Install combustion air hood
Install flue hood
Install gas piping
Install condensate line trap and piping
Make electrical connections
Install other accessories
Filter and
Indoor Coil
Access Panel
Indoor Blower
Access Panel
Gas Heat
Access Panel
Compressor
(each side)
C11154
Fig. 5 -- Typical Access Panel and Compressor Locations
Frame--mounted installation —
Frame--mountedapplicationsgenerally followthe
sequence for a curb installation. Adapt as required to
suit specific installation plan.
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim
with transportation agency.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of
6–in. (150 mm) beyond unit cabinet. Install a gravel apron
in front of condenser coil air inlet to prevent grass and
foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb
if required.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data
plate agree with power supply provided.
Locate the carton containing the outside air hood parts; see
Figs. 5 and 12. Do not remove carton until unit has been
rigged and located in final position.
Step 4 — Provide Unit Support
Roof Curb Mount —
Alternate Unit Support (In Lieu of Curb or Slab
Mount) —
A non--combustible sleeper rail can be used in the unit
curb support area. If sleeper rails cannot be used, support
the long sides of the unit with a minimum of 4 equally
spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each
side. Locate pads so that they support the rails. Make sure
to avoid the fork openings.
Accessory roof curb details and dimensions are shown in
Figs. 6, 7 and 8. Assemble and install accessory roof curb
in accordance with instructions shipped with the curb.
10
Page 11
48HC
C10954
Fig. 6 -- Roof Curb Details – 17 Size Unit
11
Page 12
48HC
Fig. 7 -- Roof Curb Details – 20 and 24 Size Units
C10955
12
Page 13
48HC
C10956
Fig. 8 -- Roof Curb Details – 28 Size Unit
13
Page 14
A minimum clearance is not required around ductwork.
C
A
B
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.25” (6)
B-C
0.5” (12)
Fig. 9 -- Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 0.5 in. wg (87 Pa) with economizer or
without economizer.
For vertical ducted applications, secure all ducts to roof curb
48HC
and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional
dimensions are equal to or greater than the unit supply
duct opening dimensions for the first 18 in. (458 mm) of
duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
A-C
0.5” (12)
C10628
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage
to roofing materials.
Membrane roofs can be cut by sharp sheet metal
edges. Be careful when placing any sheet metal parts
on such roof.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not
required if top crating is left on unit. Rollers may be used
to move unit across a roof. Level by using unit frame as a
reference. See Table 1 (on page 9) and Fig. 10 for
additional information.
Lifting holes are provided in base rails as shown in
Fig. 10. Refer to rigging instructions on unit.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck when packaging
is removed.
CAUTION
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with
applicable fire codes.
"914-1371"
(36"-54")
"B"
SEE DETAIL A
"C"
"A"
UNIT
48HC**1723391061127.8324958.7149152.31328
48HC**2025491156141.5359571.5181652.31328
48HC**2426991224141.5359571.5181660.31532
48HC**2827481246157.8400780.3204060.31532
NOTES:
1. Dimensions in ( ) are inches.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of
gravity. Use wooden top to prevent rigging straps from damaging unit.
MAX WEIGHT
LBKGINMMINMMINMM
Fig. 10 -- Rigging Details
Before setting the unit onto the curb, recheck gasketing on
curb.
PLACE ALL SEAL STRIP
IN PLACE BEFORE PLACING
UNIT ON ROOF CURB.
DUCT END
DIMENSIONS
ABC
DETAIL A
C09107
14
Page 15
PositioningonCurb—
r
Position unit on roof curb so that the following clearances
are maintained:
curb and the base rail inside the right and left,
1
/4in. (6 mm) clearance between the roof
1
/2in.
(12 mm) clearance between the roof curb and the base rail
inside the front and back. This will result in the distance
between the roof curb and the base rail inside on the
condenser end of the unit being approximately equal to
Details A and B in Figs. 6, 7 and 8.
Do not attempt to slide unit on curb after unit is set. Doing
so will result in damage to the roof curb seal.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal
clearance of 48 in. (1220 mm) from electric and gas meters,
gas regulators, and gas relief equipment. Minimum distance
between unit and other electrically live parts is 48 inches
(1220 mm).
Flue gas can deteriorate building materials. Orient unit such
that flue gas will not affect building materials. Locate
mechanical draft system flue assembly at least 48 in. (1220
mm) from an adjacent building or combustible material.
Field--supplied
(3
/4--inch) flanges should be attached to
horizontal duct openings (see Fig. 11) and all ductwork
should be secured to the flanges. Insulate and weatherproof
all external ductwork, joints, and roof or building openings
with counter flashing and mastic inaccordance with
applicable codes.
Step 8 — Install Outside Air Hood — Factory
Option
The outside air hood for factory--option economizer and
two--position damper is shipped in knock--down form and
requires field assembly. The panel for the hood top is
shipped on the end of the unit (see Fig. 12). The
remaining parts for the hood assembly (including side
panels, filters and tracks) are shipped in a carton that is
secured to the rear of the blower assembly. Access the
carton location through rear panel (see Fig. 13).
Hood Top
Shipping
Position
48HC
After unit is in position, remove rigging skids and
shipping materials.
Step 7 — Horizontal Duct Connection
Refer to Figs. 1, 2 and 3 for locations and sizes of the
horizontal duct connections. Note that there are two different
return air duct connection locations – one for unit without an
economizer (on back side of unit) and a different one for
unit equipped with an economizer (on left end, under the
economizer hood). The supply air duct connection is on the
back side.See Fig. 11 for top view depicting typical
horizontal duct arrangements.
C09134
Fig. 12 -- Hood Top – Shipping Position
To remove the hood parts package:
1. Remove the back blower access panel.
2. Locate and cut the strap, being careful to not damage
any wiring.
3. Carefully lift the hood package carton through the
back blower access opening.
See Fig. 14 for identification of the various parts of the
hood assembly.
Hood
Package
Horizontal
Supply Air
Supply
LocationBackBackLeft end
H e ig ht --- I n . ( mm )157/8(402)493/8(1253)183/8(467)
W i d t h --- i n. ( m m )293/4(756)233/8(593)615/8(1564)
Return Air Duct
Return without
Economizer
Fig. 11 -- Horizontal Duct Opening Dimensions
without
Economizer
Return Air Duct
with Economize
Return with
Economizer
C10626
C09133
Fig. 13 -- Hood Package – Shipping Location
15
Page 16
To assemble the outside air hood:
A
1. Remove hood top panel from shipping position on
unit end.
2. Install four angles to the upper end panel using the
screws provided.
The combustion air hood is attached to the back of the
burner access panel. Remove the two screws securing the
hood to the back of the burner access panel. Using the two
screws, re--attach the hood to the front of the burner
access panel as shown in Fig. 16.
3. Apply seal strip to mating flanges on the side plates
of the hood (see Fig. 14).
Apply Seal Strips
to the back of
Apply Seal Strip
to the front of
pply Seal Strips
to the back of
these flanges
2
Seal Strips
this flange
6
5
48HC
these surfaces
7
4
Item # Description Qty
1 Angles 4
2 Side Plates 2
3 Hood 1
4 Outdoor Air Screens 4
5 Side Filter Supports 2
6 Side Drip Angles 2
7 Top Diverters 2
4
1
Fig. 14 -- Hood Part Identification and Seal Strip
Application Areas
3
7
4
Apply Seal Strip
to the back of
this flange
Apply Seal Strip
to the front of
this flange
4
C09079
2
5
6
Combustion
Air Hood
Flue Hood
C10744
Fig. 16 -- Flue Hood and Combustion Air Hood Details
Step 10 — Install Gas Piping
Installation of the gas piping must be in accordance with
local building codes and with applicable national codes.
4. Secure side plates to panel using the screws provided.
5. Apply seal strip to mating flange of the hood (see
Fig. 14).
6. Secure top flange using screws provided in kit.
7. Install outdoor air screens by sliding them into the
channel formed by the four angles installed in step 2.
Make sure that the screens extend across the entire
length of the hood.
8. Install side filter supports using the screws provided.
9. Install side drip angles using the screws provided.
10. Run a continuous length of seal strip across the hood
covering the engagement holes in the lower hood.
11. Install top diverter using the screws provided.
12. On units with barometric relief, remove screws at bottom of relief damper. Do not discard damper door.
In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel
Gas Code (NFGC). In Canada, installation must be
accordance with the CAN/CSA B149.1 and CAN/CSA
B149.2 installation codes for gas burning appliances.
This unit is factory equipped for use with Natural Gas fuel
at elevations up to 2000 ft (610 m) above sea level. Unit
may be field converted for operation at elevations above
2000 ft (610 m) and/or for use with liquefied petroleum
fuel. See accessory kit installation instructions regarding
these accessories.
NOTE:Furnace gas input rate on rating plate is for
installation up to 2000 ft (610 m) above sea level. In
U.S.A. the input rating for altitudes above 2000 ft (610 m)
must be derated by 4% for each 1000 ft (305 m) above sea
level. In Canada the input rating must be derated by 10%
for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above
sea level.
For natural gas applications, gas pressure at unit gas
connection must not be less than 5 in. wg (1246 Pa) or
greater than 13 in. wg (3240 Pa) while the unit is
operating. For liquified petroleum applications, the gas
pressure must not be less than 11 in. wg (2740 Pa) or
greater than 13 in. wg (3240 Pa) at the unit connection.
C09090
Fig. 15 -- Hood Assembly – Completed
Step 9 — Install Flue Hood and Combustion Air
Hood
The flue hood is shipped screwed to the fan deck inside
the burner compartment. Remove the burner access panel
and then remove the flue hood from its shipping location.
Using the screws provided, install flue hood in the
Gas Supply Line —
The gas supply pipe enters the unit adjacent to the burner
access panel on the front side of the unit, through the
grommeted hole. The gas connection to the unit is made
3
to the
Table 2 lists typical
/4in. FPT gas inlet port on the unit gas valve.
3
/4inch NPT (National Pipe Thread)
field supplied pipe fittings required for Thru--Base gas
supply, starting from the unit gas valve (see Fig. 17).
location shown in Fig. 16.
16
Page 17
Table 2 – Typical3/4--in NPT Field Supplied Piping Parts
R
ItemQtyCPNDescription
11CA15RA20190 Deg Street Elbow
21CA01CA226 5 Inch Long Nipple
31CA85RA201Ground--- Joint Union
41CA01CA218 3 Inch Long Nipple
51CA05RA20190 Deg Elbow
61CA01CA250 12 Inch Long Nipple
71CA05RA20190 Deg Elbow
81CA01CA218 3 Inch Long Nipple
91CA20RA201TEE
101CA01CN222 4 Inch Long Nipple (Sediment Trap)
111CA38RA201 Cap
121CA01CA220 31/2Inch Long Nipple
131GB30NIBCORBall Valve
141CA01CA238 8 Inch Long Nipple
151CA05RA201 90 Deg Elbow
4
6
7
8
9
10
11
12
5
13
14
3
2
1
15
Fig. 17 -- Gas Supply Line Piping with Thru--Base
C10999
48HC
Pipe gas supply into 90 degree elbow item 15 (see Table 2)
through the hole in the unit basepan.
For typical
3
/4inch NPT field supplied fittings required
for NON Thru--Base gas supply starting from the unit gas
valve, omit items 14 and 15 from Table 2 and pipe gas
supply into TEE. See Fig. 18.
Table 3 – Natural Gas Supply Line Pressure Ranges
UNIT MODELUNIT SIZEMINMAX
48HC**17, 20, 24, 28
!
CAUTION
5.0 in. wg
(1246 Pa)
13.0 in. wg
(3240 Pa)
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage
to equipment.
When connecting the gas line to the unit gas valve,
the installer MUST use a backup wrench to prevent
damage to the valve.
Install a gas supply line that runs to the unit heating
section. Refer to the NFPA 54/NFGC or equivalent code
for gas pipe sizing data. Do not use a pipe smaller than the
size specified. Size the gas supply line to allow for a
maximum pressure drop of 0.5--in wg (124 Pa) between
gas regulator source and unit gas valve connection when
unit is operating at high--fire flow rate.
The gas supply line can approach the unit in two ways:
horizontally from outside the unit (across the roof), or
through unit basepan. Observe clearance to gas line
components per Fig. 19.
7
8
9
12
BASE UNIT
BASE RAIL
17
4
6
13
10
11
5
Fig. 18 -- Gas Supply Line Piping
9” MINIMUM CLEARANCE
FOR PANEL REMOVAL
MANUAL GAS
SHUTOFF VALVE
48” MINIMUM
ROOF
CURB
NFGC – National Fuel Gas Code
Field supplied.
*
NOTE: Follow all local codes.
STEEL PIPE
NOMINAL DIAMETER
1
1
(in.)
1
3
/
4
/
or larger
4
/
2
or 1
LEGEND
Fig. 19 -- Gas Piping Guide
3
2
1
X
GAS
REGULATOR
*
*
DRIP LEG
PER NFGC
SPACINGOFSUPPORTS
X DIMENSION
*
FIELD-
FABRICATED
SUPPORT
(ft)
6
8
10
C101006
FROM
GAS
METE
*
C11121
Page 18
Factory--Option Thru--Base Connections —
Electrical Connections: Knockouts are located in the
control box area. Remove the appropriate size knockout
for high voltage connection. Use the field supplied
connector depending on wiring or conduit being utilized.
7
Remove the
/8--in (22mm) knockout and appropriate
connector for low voltage wiring. If non--unit powered
convenience outlet is being utilized, remove the
(22mm) knockout and utilize appropriate connector for
115 volt line. See “Step 12 — Making Electrical
Connections” for details.
Gas Connections: Remove the knockout in the base pan
3
and route
/4--in. gas line up through the opening. Install
an elbow and route gas line through opening in panel after
first removing plastic bushing. Install a gas shut off
followed by a drip leg and ground--joint union. Route gas
line into gas section through the grommet (Part #:
KA56SL112) at the gas inlet and into the gas valve. See
48HC
Fig. 17 and Table 2. If a regulator is installed, it must be
located 4 feet (1.22 meters) from the flue outlet.
Some municipal codes require that the manual shutoff
valve be located upstream of the sediment trap. See
Fig. 18 for typical piping arrangements for gas piping that
has been routed through the sidewall of the base pan.
When installing the gas supply line, observe local codes
pertaining to gas pipe installations. Refer to the NFPA
54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA
B149.1). In the absence of local building codes, adhere to
the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
/4--in. in every 15 ft (7 mm in every 5 m) to prevent
traps. Grade all horizontal runs downward to risers.
Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical
and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one
hanger every 6 ft (1.8 m). For pipe sizes larger than
1
/2--in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections.
Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. If using PTFE (Teflon) tape, ensure the material is Double Density type and is labeled for use on gas
lines. Apply tape per manufacturer’s instructions.
4. Pressure--test all gas piping in accordance with local
and national plumbing and gas codes before connecting piping to unit.
7
/8-- i n
NOTE: Pressure test the gas supply system after the gas
supply piping is connected to the gas valve. The supply
piping must be disconnected from the gas valve during the
testing of the piping systems when test pressure is in
excess of 0.5 psig (3450 Pa). Pressure test the gas supply
piping system at pressures equal to or less than 0.5 psig
(3450 Pa). The unit heating section must be isolated from
the gas piping system by closing the external main manual
shutoff valve and slightly opening the ground--joint union.
Checkforgasleaksatthefield--installedand
factory--installed gas lines after all piping connections have
been completed. Use soap--and--water solution (or method
specified by local codes and/or regulations).
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
S Connect gas pipe to unit using a backup wrench to
avoid damaging gas controls.
S Never purge a gas line into a combustion chamber.
S Never test for gas leaks with an open flame. Use a
commercially available soap solution made
specifically for the detection of leaks to check all
connections.
S Use proper length of pipe to avoid stress on gas
control manifold.
NOTE: If orifice hole appears damaged or it is suspected to
have been redrilled, check orifice hole with a numbered drill
bit of correct size. Never redrill an orifice. A burr--free and
squarely aligned orifice hole is essential for proper flame
characteristics.
BURNER
ORIFICE
A93059
Fig. 20 -- Orifice Hole
18
Page 19
Step 11 — Install External Condensate Trap and
Line
The unit has one3/4-in. condensate drain connection on
the end of the condensate pan (see Fig. 21). See Figs. 1, 2
and 3,item“E”, inthe viewlabeled “BACK
(HORIZONTAL DISCHARGE)” for the location of the
condensate drain connection.
Step 12 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit
cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist
of electrical wire connected to unit ground lug in control
compartment, or conduit approved for electrical ground
when installed in accordance with NEC (National
Electrical Code); ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical
codes.
CONDENSATE
DRAIN
CONNECTION
C10729
Fig. 21 -- Condensate Drain Pan Connection
The piping for the condensate drain and external trap can
be completed after the unit is in place. Hand tighten
fittings to the drain pan fitting. Provide adequate support
for the drain line. Failure to do so can result in damage to
the drain pan. See Fig. 22.
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102) trap is recommended.
BASE RAIL
OPEN
VENT
2˝ (51) MIN
DRAIN PLUG
SEE NOTE
ROOF
CURB
C08022
Fig. 22 -- Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
3
/4-in.).
(
NOTE:Field--supplied wiring shall conform with the
limitations of minimum 63_F(33_C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet:
The power source leads to the convenience outlet’s
transformer primary are not factory connected. Installer
must connect these leads according to required operation
of the convenience outlet. If an always--energized
convenience outlet operation is desired, connect the
source leads to the line side of the unit--mounted
disconnect. (Check with local codes to ensure this method
is acceptable in your area.) On a unit without a
unit--mounted disconnect, connect the source leads to the
line side with unit field power leads. See Fig. 23.
BLK
YEL
BLU
LOAD
SIDE
LINE
SIDE
SEE
DETAIL
A
L1
L2
L3
A
DETAIL
CONTROL BOX
C11181
Fig. 23 -- Location of TB1
Field power wires are connected to the unit at line--side
pressure lugs on the terminal block (see wiring diagram
label for control box component arrangement) or at
factory--installed option non--fused disconnect switch. Use
copper conductors only.
NOTE:Make field power connections directly to line
connection pressure lugs only.
48HC
19
Page 20
!
WARNING
!
CAUTION
FIRE HAZARD
Failureto followthis warningcouldresult in
intermittent operation or unsatisfactory performance.
Do not connect aluminum wire between disconnect
switch and air conditioning unit. Use only copper
wire.(SeeFig.24.)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
48HC
ALUMINUM
WIRE
Fig. 24 -- Disconnect Switch and Unit
Units without Factory--Installed Disconnect —
When installing units, provide a disconnect switch per
NEC (National Electrical Code) of adequate size.
Disconnect sizing data is provided on the unit informative
plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative
plate if mounting the disconnect on the unit cabinet.
Units with Factory--Installed Disconnect —
A93033
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electrical components. Such operation would invalidate
any applicable Carrier warranty.
Units Without Disconnect Option
TB1
111213
Disconnect
per
NEC
L1
L2L3
208/230-3-60
460-3-60
575-3-60
Units With Disconnect Option
Factory
Wiring
The factory--installed option disconnect switch is located
in the main control box. The manual switch handle is
accessible on the corner post adjacent to the control box
access panel.
All Units --
All field wiring must comply with NEC and all local code
requirements.
Size wire based on MCA (Minimum Circuit Amps) on the
unit informative plate. See Fig. 25 for power wiring
connections to the unit power terminal block and equipment
ground. Maximum wire size is 2/0 AWG per pole.
Provide a ground--fault and short--circuit over--current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over--current Protection) device size.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Table 11. On 3--phase units, voltages between phases must
be balanced within 2% and the current within 10%. Use
the formula shown in the legend for Table 11 (see Note 2
on page 49) to determine the percent of voltage
imbalance.
T1T2T3
Optional
Disconnect
Switch
L1L2L3
L1L2L3
Fig. 25 -- Power Wiring Connections
Convenience Outlets —
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Lock--out and tag--out this switch, if necessary.
C101000
20
Page 21
Two types of convenience outlets are offered on 48HC
models: Non--unit powered and unit--powered. Both types
provide a 125--volt GFCI (ground--fault circuit--interrupter)
duplex receptacle rated at 15--A behind a hinged access
cover, located on the corner panel of the unit. See Fig. 26.
Control Box
Access Panel
Electric
Disconnect
Switch
Convenience
Outlet
C10641
Fig. 26 -- Convenience Outlet Location
InstallingWeatherproofCover:Aweatherproof
while-in-use cover for the factory-installed convenience
outlets is now required by UL standards. This cover cannot
be factory-mounted due to its depth; it must be installed at
unit installation. For shipment, the convenience outlet is
covered with a blank cover plate.
Non--unit powered type: This type requires the field
installation of a general--purpose 125--volt 15--A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125--v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Unit--powered type: A unit--mounted transformer is
factory--installed to stepdown the main power supply
voltage to the unit to 115--v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a control box and mounted on a bracket behind the
convenience outlet; access is through the unit’s control
box access panel. See Fig. 26.
The primary leads to the convenience outlet transformer
are not factory--connected. If local codes permit, the
transformer primary leads can be connected at the
line--side terminals on the unit--mounted non--fused
disconnect switch; this will provide service power to the
unit when the unit disconnect switch is open. See Fig. 28.
48HC
The weatherproof cover kit is shipped in the unit’s control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECTALLPOWERTOUNITAND
CONVENIENCE OUTLET. LOCK--OUT AND TAG--OUT
ALL POWER.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/2-in (13 mm) under screw heads are
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 27. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
COVER – WHILE-IN-USE
WEATHERPROOF
RECEPTACLE
NOT SHOWN
UNIT
VOLTAGE
208,
230
460480
575600
CONNECT
AS
240
PRIMARY
CONNECTIONS
L1: RED +YEL
L2: BLU + GRA
L1: RED
Splice BLU + YEL
L2: GRA
L1: RED
L2: GRA
C10730
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H1
H2 + H3
H4
H1
H2
Fig. 27 -- Weatherproof Cover Installation
BASE PLATE FOR
GFCI RECEPTACLE
Fig. 28 -- Powered Convenience Outlet Wiring
C09022
21
Page 22
Field Control Wiring —
NOTICE/AVIS
Convenience Outlet Utilization
Maximum Intermittent Use 15 - Amps
Maximum Continuous Use 8 - Amps
Observe a 50% limit on the circuit
Loading above 8 - Amps
Utilisation de la prise utilitaire
Usage intermittent maximum 15 - Amps
Usage continu maximum 8 - Amps
Observez une limite de 50% sur le circuit
Chargement au-dessus de 8 - Amps
Fig. 29 -- Convenience Outlet Utilization Notice
Test the GFCI receptacle by pressing the TEST button on
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires and power line phasing
if the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condition.
Using unit--mounted convenience outlets: Units with
48HC
unit--mounded convenience outlet circuits will often
require that two disconnects be opened to de--energize all
power to the unit. Treat all units as electrically energized
until the convenience outlet power is also checked and
de--energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
Factory--Option Thru--Base Connections —
All units are equipped with the ability to bring utilities
through the base.
Gas is brought up through an embossed area located in the
gas section behind the gas entrance post. Access is gained
through the gas access panel. A knock out must be
removed to accomplish this.
The electrical entrance is located in the control box area
and can be accessed through the control box access panel.
An embossed area is provided with three knock outs. High
voltage is brought through the multi knock out by
removing the appropriate size for the size of the fitting
7
required. A
An additional
/8--in. knock out is provided for low voltage.
7
/8--in. knock out is provided for a 115 volt
line which is used when the unit is equipped with the
non--unit powered convenience outlet option.
50HE501288
2.0
C10077
The 48HC unit requires an external temperature control
device. This device can be a thermostat (field--supplied)
or a PremierLink controller (available as factory--installed
option or as field--installed accessory, for use on a Carrier
Comfort Network or as a stand alone control) or the RTU
Open for Building Management Systems using non--CCN
protocols (RTU Open is available as a factory--installed
option only).
Thermostat —
Install a Carrier--approved accessory 2--stage thermostat
according to installation instructions included with the
accessory. Locate the thermostat accessory on a solid wall
in the conditioned space to sense average temperature in
accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24--v
power, use a thermostat cable or equivalent single leads of
different colors with minimum of seven leads. If the
thermostat does not require a 24--v source (no “C”
connection required), use a thermostat cable or equivalent
with minimum of six leads. Check the thermostat
installation instructions for additional features which
might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG
(American Wire Gage) insulated wire (35_C minimum).
For50to75ft.(15to23m),useno.16AWGinsulated
wire (35_C minimum). For over 75 ft. (23 m), use no. 14
AWG insulated wire (35_C minimum). All wire sizes
larger than no. 18 AWG cannot be directly connected to
the thermostat and will require a junction box and splice
at the thermostat.
Unit without Thru--Base Connection Kit —
Correctly rated low voltage wire can be routed through the
rubber grommet located on the corner post adjacent to the
control box access panel. Route wire through the grommet
and then route the wire behind the corner post utilizing the
factory provided wire ties secured to the control box. This
will insure separation of the field low voltage wire and the
high voltage circuit. Route the low voltage wire to the
central terminal board. See Fig. 30.
All required fittings are field supplied. Install fittings
when access to both top and bottom of the base pan is
available. See electrical and gas connections for routing
and connection information.
Units without Thru--Base Connections —
1. Install liquid tight conduit between disconnect and
control box.
2. Pull correctly rated high voltage wires through the
conduit.
3. Install power lines to terminal connections as shown
in Fig. 25.
Failure to follow this caution may cause a short circuit.
Carefully check the connection of control coductor
for indoor fan control at terminal G. Connecting the
indoor fan lead to terminal C will cause a short circuit
condition which can cause component damage inside
the unit or at thermostat.
C10731
Fig. 30 -- Typical Low--Voltage Control Connections
NOTE:If utilizing the through the base connections,
route the low voltage wire through the wire ties to the
central terminal board.
Corner
Post
Wire
Ties
Thru the Base
Connection
C10734
Fig. 31 -- Field Control Wiring Raceway
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second--stage heating.
Transformer Connection for 208--v Power Supply —
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
1
with the
connection and moving it to the 208-v
/4-in. female spade connector from the 230--v
1
/4-in. male
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information.
48HC
23
Page 24
Humidi--MiZerRControl Connections
Humidi--MiZer – Space RH Controller —
NOTE: The Humidi--MiZer is a factory installed option.
The Humidi--MiZer dehumidification system requires a
field--supplied and --installed space relative humidity
control device. This device may be a separate humidistat
control (contact closes on rise in space RH above control
setpoint) or a combination thermostat--humidistat control
device such as Carrier’s EDGE
isolated contact set for dehumidification control. The
humidistat is normally used in applications where a
temperature control is already provided (units with
PremierLinkt control).
To connect the Carrier humidistat (HL38MG029):
1. Route the humidistat 2--conductor cable (field--supplied) through the hole provided in the unit corner
post.
48HC
2. Feed wires through the raceway built into the corner
post (see Fig. 31) to the 24--v barrier located on the
left side of the control box. The raceway provides the
UL--required clearance between high--voltage and
low--voltage wiring.
3. Use wire nuts to connect humidistat cable to two
PINK leads in the low–voltage wiring as shown in
Fig. 34.
To connect the Thermidistat device (33CS2PPRH--01):
1. Route the Thermidistat multi--conductor thermostat
cable (field--supplied) through the hole provided in
the unit corner post.
2. Feed wires through the raceway built into the corner
post (see Fig. 31) to the 24--v barrier located on the
left side of the control box. The raceway provides the
UL--required clearance between high--voltage and
low--voltage wiring.
3. The Thermidistat has dry contacts at terminals D1
and D2 for dehumidification operation (see Fig. 35).
The dry contacts must be wired between CTB
terminal R and the PINK lead to the LTLO switch
with field--supplied wire nuts. Refer to the installation
instructionsincludedwiththeCarrierEdge
Thermidistat device (Form 33CS--65SI or latest) for
more information.
R
Pro Thermidistat with
% RELATIVE HUMIDITY
C09295
Fig. 32 -- Accessory Field--Installed Humidistat
®
C09296
Fig. 33 -- EDGE Pro Thermidistat
24
Page 25
48HC
Fig. 34 -- Typical Humidi--MiZerRAdaptive Dehumidification System Humidistat Wiring
EDGE Pro THERMIDISTAT
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT
RRS
SRTN
HUM
D1
D2
V+
Vg
Humidi-MiZer™ FIOP
Unit CTB
THERMOSTAT
X*
C
G
W2
W1
Y2
Y1
R
C11139
Fig. 35 -- Typical Rooftop Unit with Humidi--MiZer Adaptive Dehumidification System
*Connection not required.
C09298
with EDGE Pro Thermidistat Device
25
Page 26
PremierLinkt (Factory--Option)
48HC
Fig. 36 -- PremierLink Controller
The PremierLink controller (see Fig. 36) is compatible
with Carrier Comfort Networkr (CCN) devices. This
control is designed to allow users the access and ability to
change factory--defined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilott, Touch Pilott and
Service Tool. (Standard tier display tools Navigatort and
Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The PremierLink control is factory--mounted in the 48HC
unit’s main control box to the right of the Central Terminal
Board (CTB) (see Fig. 37). Factory wiring is completed
through harnesses connected to the CTB thermostat. Field
connections are made at a 16--pole terminal block (TB3)
located at the top of the unit control box in front of the
PremierLink controller. The factory--installed PremierLink
control includes the supply--air temperature (SAT) sensor.
The outdoor air temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$ert2 package. (See page 45 for
accessory enthalpy controls.)
The PremierLink controller requires the use of a Carrier
electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is
necessary for broadcast of time of day functions
(occupied/unoccupied).
NOTE:PremierLink controller is shipped in Sensor
mode. To be used with a thermostat, the PremierLink
controller must be configured to Thermostat mode. Refer
to PremierLink Configuration instructions for Operating
Mode.
C08199
C10643
Fig. 37 -- 48HC Control Box Component Locations
26
Page 27
48HC
C11140
Fig. 38 -- PremierLink Wiring Schematic
27
Page 28
48HC
Fig. 39 -- PremierLink Wiring Schematic with Humidi--MiZer
28
R
C11141
Page 29
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 48HC unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches (12.7
mm) in length. It is a nominal 10--k ohm thermistor.
NOTE:The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor —
The SAT is factory--wired. The SAT probe is mounted in
the fan deck (see Fig. 40). It can be removed or
remounted per local codes.. Drill or punch a 1/2--in. hole
in the flange or duct. Use two field--supplied, self--drilling
screws to secure the sensor probe in a horizontal
orientation. Insure that the sensor wires do not contact the
hot surface of the heat exchanger.
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR
RETURN AIR
ROOF
CURB
C10733
Fig. 40 -- Mounting Location for Supply Air
Temperature (SAT) Sensor on 48HC Units
NOTE:Refer to Form 33CS--67SI for complete
PremierLink configuration, operatingsequences and
troubleshooting information. Have a copy of this manual
available at unit start--up.
The OAT is factory--mounted in the EconoMi$er2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
EconoMi$er2 —
The PremierLink control is used with EconoMi$er2
(option or accessory) for outdoor air management. The
damper position is controlled directly by the PremierLink
control; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
Outdoor air CO
sensor
2
sensor
2
Refer to Table 4 for accessory part numbers.
Field Connections
Field connections for accessory sensor and input devices
are made at the 16--pole terminal block (TB3, see Fig. 38
and Fig. 39) located on the control box top shelf in front
of the PremierLink control. Some input devices also
require a 24--vac signal source; connect at CTB terminal
R at “THERMOSTAT” connection strip for this signal
source. See connections figures on following pages for
field connection locations (and for continued connections
at the PremierLink board inputs).
Table 5 provides a summary of field connections for units
equipped with Space Sensor. Table 6 provides a summary of
field connections for units equipped with Space Thermostat.
48HC
OUTDOOR AIR
APPLICATION
Differential Dry Bulb
Tem p er at ur e w i th
PremierLink
(PremierLink requires
4 --- 2 0 m A A c t u a t o r)
Single Enthalpy with
PremierLink
(PremierLink requires
4 --- 2 0 m A A ct ua to r)
Differential Enthalpy
with PremierLink
(PremierLink requires
4 --- 2 0 m A A ct ua to r)
NOTES:
Sensors (Optional):
CO
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct--- mounted CO
33ZCT55CO2 --- Space temperature and CO
33ZCT56CO2 --- Space temperature and CO
TEMPERATURE
SENSOR
I nc lu de d ---
CRTEMPSN001A00
I nc lu de d ---
Not Used
I nc lu de d ---
Not Used
Table 4 – PremierLink Sensor Usage
RETURN AIR
TEMPERATURE
SENSOR
R eq ui re d ---
33ZCT55SPT
or equivalent
---
---
room sensor.
room sensor with override.
2
room sensor with override and setpoint.
2
2
29
ENTHALPY SENSOR
OUTDOOR AIR
------
R eq ui re s ---
33CSENTHSW
R eq ui re s ---
33CSENTHSW
or equivalent
RETURN AIR
ENTHALPY SENSOR
---
R eq ui re s ---
33CSENTSEN
or equivalent
Page 30
TB3 TERMINALFIELD CONNECTIONINPUT SIGNAL
1T5 5 --- S EN / T 5 6 --- S ENAnalog (10k thermistor)
2RMTOCCDiscrete, 24VAC
3T5 5 --- S EN / T 5 6 --- S ENAnalog (10k thermistor)
4CMPSAFEDiscrete, 24VAC
5T56--- SETAnalog (10k thermistor)
6FSDDiscrete, 24VAC
7LOOP --- PWRAnalog, 24VDC
8SPSDiscrete, 24VAC
9IAQ--- SENA na lo g , 4 --- 2 0 m A
10FILTERDiscrete, 24VAC
11I AQ --- C OM / O A Q --- C OM /R H --- C O MA n a l o g , 4 --- 2 0 m A
12CCN + (RED)Digital,,5VDC
13OAQ --- SEN /R H ---SENA na lo g , 4 --- 2 0 m A
14CCN Gnd (WHT)Digital, 5VDC
15AUX OUT(Power Exhaust)(Output)Discrete 24VAC
48HC
LEGEND:
T55--- Space Temperature Sensor
T56--- Space Temperature Sensor
CCN--- Carrier Comfort Network (communication bus)
CMPSAFE--- Compressor Safety
FILTER--- Dirty Filter Switch
F S D--- F ir e S hu td ow n
IAQ--- Indoor Air Quality (CO
OAQ--- Outdoor Air Quality (CO
RH--- Relative Humidity
9I A Q --- S E NAnalog, 4--- 20mA
10W2Discrete, 24VAC
11I A Q --- C OM /O A Q --- C O M / R H --- C O MAnalog, 4 ---20mA
12CCN + (RED)Digital, 5VDC
13O A Q --- S EN / R H --- S E NAnalog, 4 ---20mA
14CCN Gnd (WHT)Digital, 5VDC
15AUX OUT (Power Exhaust)(Output) Discrete 24VAC
16CCN --- (BLK)Digital, 5VDC
LEGEND:
CCN---Carrier Comfort Network (communication bus)
G---T h e r m o st at Fa n
IAQ---Indoor Air Quality (CO
OAQ---Outdoor Air Quality (CO
RAT---Return Air Temperature
RH---Relative Humidity
W1---Thermostat Heat Stage 1
W2---Thermostat Heat Stage 2
Y1---Thermostat Cool Stage 1
Y2---Thermostat Cool Stage 2
)
2
)
2
30
Page 31
Space Sensors —
The PremierLink controller is factory--shipped configured
for Space Sensor Mode. A Carrier T--55 or T--56 space
sensor must be used. T--55 space temperature sensor
provides a signal of space temperature to the PremierLink
control. T--56 provides same space temperature signal plus
it allows for adjustment of space temperature setpoints
from the face of the sensor by the occupants.
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
C08201
Fig. 41 -- T--55 Space Temperature Sensor Wiring
Connect T--55: See Fig. 41 for typical T--55 internal
connections. Connect the T--55 SEN terminals to TB3
terminals 1 and 3 (see Fig. 42).
TB3PL
SENJ6-7
SEN
1
3
J6-6
C10023
Fig. 42 -- PremierLink T--55 Sensor
Connect T--56: See Fig. 43 for T--56 internal connections.
Install a jumper between SEN and SET terminals as
illustrated. Connect T--56 terminals to TB3 terminals 1, 3
and 5 (see Fig. 44).
2
SW1
3
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
SET
BLK
(T56)
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
TB3PL
SENJ6-7
SEN
Jumper
1
TB3
3
PL
J6-6
SET
SET
5
J6-5
C10022
Fig. 44 -- PremierLink T--56 Sensor
Connect Thermostat —
A 7--wire thermostat connection requires a 24--v power
source and a common connection. Use the R and C
terminals on the CTB’s THERMOSTAT connection strip
for these. Connect the thermostat’s Y1, Y2, W1, W2 and
G terminals to PremierLink TB3 as shown in Fig. 45.
If the 48HC unit is equipped with factory--installed smoke
detector(s), disconnect the factory BLU lead at TB3--6
(Y2) before connecting the thermostat. Identify the BLU
lead originating at CTB--DDC--1; disconnect at TB3--6
and tape off. Confirm that the second BLU lead at TB3--6
remains connected to PremierLink J4--8.
SPACE
THERMOSTAT
R
GJ4-12
Y1
Y2
W1
W2
C
CTB
THERMOSTAT
R
TB3
2
4
6
8
10
C
THERMOSTAT
PL
J4-10
J4-8
J4-6
J4-4
CTB
C10283
Fig. 45 -- Space Thermostat Connections
If the 48HC unit has an economizer system and free--cooling
operation is required, a sensor representing Return Air
Temperature must also be connected (field--supplied and
installed). This sensor may be a T--55 Space Sensor (see Fig.
41) installed in the space or in the return duct, or it may be
sensor PNO 33ZCSENSAT, installed in the return duct.
Connect this sensor to TB3--1 and TB3--3 per Fig. 42.
Configure the Unit for Thermostat Mode —
Connect to the CCN bus using a CCN service tool and
navigatetoPremierLink Configurationscreen for
Operating Mode. Default setting is Sensor Mode (value
1). Change the value to 0 to reconfigure the controller for
Thermostat Mode.
48HC
CoolWarm
Fig. 43 -- T--56 Internal Connections
C08202
When the PremierLink is configured for Thermostat
Mode, these functions are not available: Fire Shutdown
(FSD), Remote Occupied (RMTOCC), Compressor Safety
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure
Switch (FILTER).
31
Page 32
Economizer Controls
Indoor Air Quality (CO2)Sensor—
The indoor air quality sensor accessory monitors space
carbon dioxide (CO
monitor IAQ levels. Several types of sensors are available,
for wall mounting in the space or in return duct, with and
without LCD display, and in combination with space
temperature sensors. Sensors use infrared technology to
measure the levels of CO
The CO
sensors are all factory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
requirements and terminal locations. See Fig. 46 for
typical CO
sensor wiring schematic.
2
) levels. This information is used to
2
present in the space air.
2
sensor for electrical
2
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 46. Connect the 4--20 mA terminal to
terminal TB3--9 and connect the SIG COM terminal to
terminal TB3--11. See Fig. 47.
IAQ Sensor
24 VAC
J4
4-20mA
SIG COM
TB3
9
TB3
11
PL
J5-5
J5-3
C11156
Fig. 47 -- Indoor CO2Sensor (33ZCSENCO2)
Connections
Refer to Form 33CS--67SI, PremierLink Installation,
Start--up, and Configuration Instructions, for detailed
configuration information.
48HC
+
0-10VDC
-
SIG COM
+
4-20mA
NC
COM
NO
24 VAC
HG
OR
+
-
24 VDC
2
1
J3J4
5
1
4
32
7
6
8
Fig. 46 -- Indoor/Outdoor Air Quality (CO2)Sensor
(33ZCSENCO2) -- Typical Wiring Diagram
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return--air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
ALARM
RELAY
}
CONTACTS
C08635
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) —
The outdoor air CO
dioxide (CO
) levels in the outside ventilation air and
2
sensor is designed to monitor carbon
2
interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 48. The outdoor air CO
sensor must be located in the
2
economizer outside air hood.
2
COVER REMOVEDSIDE VIEW
Fig. 48 -- Outdoor Air Quality Sensor Cover
C07135
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor: For each sensor,
use two 2--conductor 18 AWG (American Wire Gage)
twisted--pair cables (unshielded) to connect the separate
isolated 24 vac power source to the sensor and to connect
the sensor to the control board terminals.
Wiring the Outdoor Air CO
Sensor: A dedicated
2
power supply is required for this sensor. A two--wire cable
is required to wire the dedicated power supply for the
sensor. The two wires should be connected to the power
supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 46. Connect the 4 to 20 mA
terminal to the TB3--13 terminal of the 48HC. Connect the
SIG COM terminal to the TB3--11 terminal of the 48HC.
See Fig. 49.
32
Page 33
OAQ Sensor
24 VAC
4-20mA
SIG COM
TB3
13
TB3
11
PL
J5-2
J5-3
C11157
Fig. 49 -- Outdoor CO2Sensor Connections
Space Relative Humidity Sensor or Humidistat
Connections —
SpaceRelativeHumiditySensorconnections: The
accessory space relative humidity sensor (33ZCSENSRH-01)
is installed on an interior wall to measure the relative
humidity of the air within the occupied space.
The use of a standard 2 X 4 inch electrical box to
accommodate the wiring is recommended for installation.
The sensor can be mounted directly on the wall, if
acceptable by local codes.
The sensor must be mounted vertically on the wall. The
Carrier logo should be orientated correctly when the
sensor is properly mounted.
Avoid corner locations. Allow at least 4 ft between the
sensor and any corner. Airflow near corners tends to be
reduced, resulting in erratic sensor readings. The sensor
should be vertically mounted approximately 5 ft up from
the floor, beside the space temperature sensor.
For wiring distances up to 500 feet, use a 3--conductor, 18
or 20 AWG cable. ACCN communication cable can be
used, although the shield is not required. The shield must
be removed from the sensor end of the cable if this cable
is used. See Fig. 51 for wiring details.
TB3-7
TB3-13
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
permanent damage to the sensor.
DO NOT clean or touch the sensing element with
chemical solvents as they can permanently damage the
sensor.
!
CAUTION
UNIT PERFORMANCE HAZARD
Failure to follow this caution will result in inaccurate
sensor readings.
DO NOT mount the sensor in drafty areas such as near
heating or air--conditioning ducts, open windows, fans,
or over heat sources such as baseboard heaters,
radiators, or wall--mounted dimmers. Sensors mounted
in those areas will produce inaccurate readings.
If the sensor is installed directly on a wall service, install the
humidity sensor using 2 screws and 2 hollow wall anchors
(field supplied). Do not over tighten screws. See Fig. 50.
MOUNTING
HOLES
Io
Gnd
Vin
Vo
WIRING
OPENING
RED
BLACK
IoVoVin Gnd
C11085
Fig. 51 -- Space Relative Humidity Sensor Connection
The power for the sensor is provided by the PremierLink
control on terminal J5--4 (+33 to +35vdc).
To wire the sensor:
1. At the sensor, remove 4 inches of the jacket from the
cable. Strip
or. Route the cable through the wire clearance opening in the center of the sensor. See Fig. 50.
2. Connect a field--supplied BLACK wire to the sensor
screw terminal marked Vin.
3. Connect a field--supplied RED wire into the sensor
screw terminal marked Io.
4. Connect the field--supplied RED wire from the sensor
to TB3--13.
5. Connect the field--supplied BLACK wire from the
sensor to TB3--7.
Humidistat connections: A humidistat can not be directly
connected to the PremierLink controller. Follow the
instructions on pages 24 & 25 to connect a humidistat or a
thermostat as an electromechanical device.
1
/4inch of insulation from each conduct-
48HC
SW2
123456
ON
Fig. 50 -- Space Relative Humidity Sensor Installation
C11084
33
Page 34
Smoke Detector/Fire Shutdown (FSD) —
This function is available only when PremierLink is
configured for (Space) Sensor Mode. The unit is
factory--wired for PremierLink FSD operation when
PremierLink is factory--installed.
On 48HC units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The PremierLink
communicates the smoke detector’s tripped status to the
CCN building control. See Figs. 38 and 39, the PremierLink
wiring schematics.
Filter Status Switch —
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT--R terminal. Connect the other side of the
NO contact set to TB3--8. Setpoint for Supply Fan Status
is set at the switch. See Fig. 53.
Fan (Pressure) Switch (NO, close on rise in pressure)
CTB
Thermostat
R
TB3
8
PL
J4-6
C10287
Fig. 53 -- PremierLink Wiring Fan Pressure Switch
Connection
This function is available only when PremierLink is
configured for (Space) Sensor Mode.
48HC
PremierLink control can monitor return filter status in two
ways: By monitoring a field--supplied/installed filter
pressure switch or via supply fan runtime hours.
Using switch input: Install the dirty filter pressure switch
according to switch manufacturer’s instructions, to
measure pressure drop across the unit’s return filters.
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT--R terminal. Connect the other side of the
NO contact set to TB3--10. Setpoint for Dirty Filter is set
at the switch. See Fig. 52.
Filter Switch (NO, close on rising pressure (high drop))
CTB
Thermostat
R
TB3
10
Fig. 52 -- PremierLink Filter Switch Connection
When the filter switch’s NO contact set closes as filter
pressure drop increases (indicating dirt--laden filters), the
input signal to PremierLink causes the filter status point to
read “DIRTY”.
Using Filter Timer Hours: Refer to Form 33CS--67SI for
instructions on using the PremierLink Configuration
screens and on unit alarm sequence.
Supply Fan Status Switch —
The PremierLink control can monitor supply fan operation
through a field--supplied/installed differential pressure
switch. This sequence will prevent (or interrupt) operation
of unit cooling, heating and economizer functions until
the pressure switch contacts are closed indicating proper
supply fan operation.
Install the differential pressure switch in the supply fan
section according to switch manufacturer’s instructions.
Arrange the switch contact to be open on no flow and to
close as pressure rises indicating fan operation.
PL
J4-4
C10286
Remote Occupied Switch —
The PremierLink control permits a remote timeclock to
override the control’s on--board occupancy schedule and
place the unit into Occupied mode. This function may also
provide a “Door Switch” time delay function that will
terminate cooling and heating functions after a 2--20
minute delay.
Connect one side of the NO contact set on the timeclock
to CTB’s THERMOSTAT--R terminal. Connect the other
side of the timeclock contact to the unit’s TB3--2 terminal.
Remote Occupied
Time Clock
LCTB
Thermostat
R
TB3
2
PL
J4-12
C10288
Fig. 54 -- PremierLink Wiring Remote Occupied
Refer to Form 33CS--67SI for additional information on
configuring the PremierLink control for Door Switch
timer function.
Power Exhaust (output) —
Connect the accessory Power Exhaust contactor coils(s)
per Fig. 55.
Power Exhaust
PER
VIO
BRN
TB3
15
CTB
THERMOSTAT
C
PL
J8-3
C11158
Fig. 55 -- PremierLink Power Exhaust Output
Connection
NOTE: The Power Exhaust and Humidi--MiZer
R
options
can not be used with PremierLink at the same time as both
options require connection at TB3--15 (AUX OUT).
34
Page 35
CCN Communication Bus —
The PremierLink controller connects to the bus in a daisy
chain arrangement. Negative pins on each component
must be connected to respective negative pins, and
likewise, positive pins on each component must be
connected to respective positive pins. The controller
signal pins must be wired to the signal ground pins.
Wiring connections for CCN must be made at the 3--pin
plug.
At any baud (9600, 19200, 38400 baud), the number of
controllers is limited to 239 devices maximum. Bus length
may not exceed 4000 ft (1219 m), with no more than 60
total devices on any 1000--ft section. Optically isolated
RS--485 repeaters are required every 1000 ft (305 m).
NOTE: Carrier device default is 9600 baud.
Communications Bus Wire Specifications: The CCN
CommunicationBuswiringisfield--suppliedand
field--installed. It consists of shielded 3--conductor cable
with drain (ground) wire. The cable selected must be
identical to the CCN Communication Bus wire used for
the entire network.
See Table 7 for recommended cable.
Table 7 – Recommended Cables
MANUFACTURERCABLE PART NO.
Alpha2413 or 5463
AmericanA22503
Belden8772
Columbia02525
NOTE: Conductors and drain wire must be at least 20
AWG, stranded, and tinned copper. Individual conductors
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or
polyethylene. An aluminum/polyester 100% foil shield
and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of
-- 2 0 _C(--4_F) to 60_C (140_F) is required. Do not run
communication wire in the same conduit as or next to any
AC voltage wiring.
The communication bus shields must be tied together at
each system element. If the communication bus is entirely
within one building, the resulting continuous shield must
be connected to ground at only one single point. If the
communication bus cable exits from one building and
enters another building, the shields must be connected to
the grounds at a lightning suppressor in each building (one
point only).
Connecting CCN Bus:
NOTE: When connecting the communication bus cable,
acolor codesystemfortheentirenetworkis
recommended to simplify installation and checkout. See
Table 8 for the recommended color code.
Table 8 – Color Code Recommendations
SIGNAL TYPE
+Red1
GroundWhite2
---Black3
CCN BUS WIRE
COLOR
CCN PLUG PIN
NUMBER
Connect the CCN (+) lead (typically RED) to the unit’s
TB3--12 terminal. Connect the CCN (ground) lead
(typically WHT) to the unit’s TB3--14 terminal. Connect
the CCN (--) lead (typically BLK) to the unit’s TB3--16
terminal. See Fig. 56.
CCN Bus
PL
J2-1
J2-2GND (WHT)
J2-3– (BLK)16
C10290
+ (RED)
TB3
12
TB3
14
TB3
Fig. 56 -- PremierLink CCN Bus Connections
48HC
35
Page 36
RTU Open Control System
The RTU Open control is factory--mounted in the 48HC
unit’s main control box, to the right of the CTB. See
Fig. 37. Factory wiring is completed through harnesses
connected to the CTB. Field connections for RTU Open
sensors will be made at the Phoenix connectors on the
RTU Open board. The factory--installed RTU Open
control includes the supply--air temperature (SAT) sensor.
The outdoor air temperature (OAT) sensor is included in
the FIOP/accessory EconoMi$er2 package.
48HC
The RTU Open controller is an integrated component of the
Carrier rooftop unit. Its internal application programming
provides optimum performance and energy efficiency. RTU
Open enables the unit to run in 100% stand--alone control
mode, Carrier’s I--Vu Open network, or a Third Party
Building AutomationSystem (BAS).On--boardDIP
switches allow you to select your protocol (and baud rate) of
choice among the four most popular protocols in use today:
BACnet, Modbus, Johnson N2 and LonWorks. (See Fig. 57.)
Refer to Table 9, RTU Open Controller Inputs and Outputs
for locations of all connections to the RTU Open board.
Fig. 57 -- RTU Open Multi--Protocol Control Board
C10811
36
Page 37
48HC
Fig. 58 -- RTU Open System Control Wiring Diagram
C11142
37
Page 38
48HC
Fig. 59 -- RTU Open System Control Wiring Diagram with Humidi--MiZer
Space Relative Humidityspace_rhA I ( 4 --- 2 0 m a)
Supply Fan Status*sfan_statusDI (24 VAC)
Filter Status*filter_statusDI (24 VAC)
Door Contact Input*door_contact_statusDI (24 VAC)
Occupancy Contact*occ_contact_statusDI (24 VAC)
LEGEND
AI --- A n al o g I np ut
AO --- A na lo g O ut pu t
DI --- D i sc re te In p ut
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Pa r al le l pi n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a re u s ed f or f i el d --- i n st al la t i on .
BACnet OBJECT
NAME
DEDICATED INPUTS
CONFIGURABLE INPUTS
TYPE OF I/O
OUTPUTS
CONNECTION PIN
NUMBER(S)
J 4 --- 2 o r J 4 --- 5Outdoor Air CO2oaqA I ( 4 --- 2 0 m a)
J 5 --- 1 o r J 5 --- 3 o r
J55orJ5---7
48HC
The RTU Open controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with
the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 48HC unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT). This
sensor is a tubular probe type, approx 6--inches (12.7 mm) in
length. It is a nominal 10--k ohm thermistor.
The SAT is factory--wired. The SAT probe is wire--tied to the
supply--air opening (on the horizontal opening end) in its
shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/2--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 40.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
EconoMi$er2 —
The RTU Open control is used with EconoMi$er2 (option
or accessory) for outdoor air management. The damper
position is controlled directly by the RTU Open control;
EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
Outdoor air CO
sensor
2
sensor
2
Field Connections
Field connections for accessory sensors and input devices
are made the RTU Open, at plugs J1, J2, J4, J5, J11 and
J20. All field control wiring that connects to the RTU
Open must be routed through the raceway built into the
corner post as shown in Fig. 31. The raceway provides the
UL required clearance between high-- and low--voltage
wiring. Pass the control wires through the hole provided in
the corner post, then feed the wires thorough the raceway
39
Page 40
to the RTU Open. Connect to the wires to the removable
Phoenix connectors and then reconnect the connectors to
the board.
Space Temperature (SPT) Sensors —
There are two types of SPT sensors available from Carrier,
resistive input non-communicating (T55, T56, and T59)
and Rnet communicating (SPS, SPPL, SPP, and SPPF)
sensors. Each type has a variety of options consisting of:
timed override button, set point adjustment, a LCD
screen, and communication tie in. Space temperature can
be also be written to from a building network or zoning
system. However, it is still recommended that return air
duct sensor be installed to allow stand-alone operation for
back-up. Refer to the configuration section for details on
controller configurations associated with space sensors.
S 33ZCT55SPT, space temperature sensor with override
button (T--55)
S 33ZCT56SPT, space temperature sensor with override
48HC
button and setpoint adjustment (T--56)
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment (T--59)
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. (152 m).
Use a three--conductor shielded cable for the sensor and
setpointadjustmentconnections.Ifthesetpoint
adjustment (slidebar) is not required, then an unshielded,
18 or 20 gauge, two--conductor, twisted pair cable may be
used.
Connect T--55: See Fig. 41 for typical T--55 internal
connections. Connect the T--55 SEN terminals to RTU
Open J20--1 and J20--2. See Fig. 60.
SEN
SEN
J20-1
J20-2
Fig. 60 -- RTU Open T--55 Sensor Connections
C08460
Connect T--59: The T--59 space sensor requires a
separate, isolated power supply of 24 VAC. See Fig. 62
for internal connections at the T--59. Connect the SEN
terminal (BLU) to RTU Open J20--1. Connect the COM
terminal (BRN) to J20--2. Connect the SET terminal (STO
or BLK) to J20--3.
BLK (STO)
BRN (COM)
BLU (SPT)
ORSETSEN
OPB COM- PWR+
24 VAC
NOTE: Must use a separate isolated transformer.
J20-3
J20-2
J20-1
SENSOR
WIRING
POWER
WIRING
C10291
Fig. 62 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Indoor Air Quality (CO
)Sensor—
2
The indoor air quality sensor accessory monitors space
carbon dioxide (CO
) levels. This information is used to
2
monitor IAQ levels. Several types of sensors are available,
for wall mounting in the space or in return duct, with and
without LCD display, and in combination with space
temperature sensors. Sensors use infrared technology to
measure the levels of CO
The CO
sensors are all factory set for a range of 0 to
2
present in the space air.
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
sensor for electrical
2
requirements and terminal locations. See Fig. 46 for
typical CO
sensor wiring schematic.
2
Connect T--56: See Fig. 43 for T--56 internal connections.
Install a jumper between SEN and SET terminals as
illustrated. Connect T--56 terminals to RTU Open J20--1,
J20--2 and J20--3 per Fig. 61.
SENJ20-1
SEN
Jumper
SET
SET
Fig. 61 -- RTU Open T--56 Sensor Connections
J20-2
J20-3
C08461
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return--air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor: For each sensor,
use two 2--conductor 18 AWG (American Wire Gage)
twisted--pair cables (unshielded) to connect the separate
40
2
Page 41
isolated 24 vac power source to the sensor and to connect
the sensor to the control board terminals.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 46. Connect the 4--20 mA terminal to
RTU Open terminal J4--2 and connect the SIG COM
terminal to RTU Open terminal J4--3. See Fig. 63.
IAQ Sensor
4-20mA
SIG COM
J4-2
J4-3
24 VAC
C10738
Fig. 63 -- RTU Open / Indoor CO2Sensor
(33ZCSENCO2) Connections
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) —
The outdoor air CO
dioxide (CO
) levels in the outside ventilation air and
2
sensor is designed to monitor carbon
2
interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 48. The outdoor air CO
sensor must be located in the
2
economizer outside air hood.
Wiring the Outdoor Air CO2Sensor: A dedicated
power supply is required for this sensor. A two--wire cable
is required to wire the dedicated power supply for the
sensor. The two wires should be connected to the power
supply and terminals 1 and 2.
Space Relative Humidity Sensor or Humidistat —
Humidi--MiZer
R
Control Wiring: In units equipped
with the Humidi--MiZer option there are two pink (PNK)
wires loose in the control box used to control the
dehumidification function of the unit. These pink wires
are meant to be tied to a space humidistat or thermidistat
on an electromechanical unit. On RTU Open equipped
units these pink wires must be connected to J11--7 & 8 to
allow the Open board to operate the dehumidification
function for the unit. Disconnect the J11 Phoenix style
connector from the board and use the plug screws to
secure the pink wires in pins 7 and 8, reconnect the plug
to the board at J11.
Relative Humidity Sensors (Space or Duct Mounted):
The accessory space humidity sensor (33ZCSENSRH-01)
or duct humidity sensor (33ZCSENDRH-01) is used to
measure the relative humidity of air within the space or
return air duct. The RH reading is used to control the
Humidi--MiZer option of the rooftop unit. For wiring
distances up to 500 ft (152 m), use a 3--conductor, 18 or
20 AWG shielded cable. The shield must be removed
from the sensor end of the cable and grounded at the unit
end. The current loop power for sensor is provided by the
RTU Open controller as 24vdc. Refer to the instructions
suppliedwiththeRHsensor fortheelectrical
requirementsandterminallocations.RTUOpen
configurations must be changed after adding an RH
sensor. See Fig. 65 and 66 for typical RH sensor wiring.
S J4--1 or J4--4 = 24vdc loop power
S J4--2 or J4--5 = 4--20mA signal input
NOTE: The factory default for dehumidification control
is normally open humidistat.
48HC
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 46. Connect the 4 to 20 mA
terminal to RTU Open terminal J4--5. Connect the SIG
COM terminal to RTU Open terminal J4--6. See Fig. 64.
OAQ Sensor/RH Sensor
4-20mA
SIG COM
J4-5
J4-6
24 VAC
Fig. 64 -- RTU Open / Outdoor CO2Sensor
C10739
(33ZCSENCO2) Connections
MOUNTING
HOLES
Io
Gnd
Vin
Vo
SW2
123456
ON
Vin - J4-1 or J4-4 24Vdc
Io - J4-2 or J4-5 -20mA output
WIRING
OPENING
C11087
Fig. 65 -- Space Relative Humidity Sensor Typical Wiring
41
Page 42
J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output
to RTU-OPEN
Relative Humidity Sensor
(Polarized Male Connector)
Humidistat: The accessory humidistat provides the RTU
Open insight to the relative humidity in the space. The
humidistat reads the RH level in the space and compares it
to its setpoint to operate a dry contact. The humidistat is a
dedicated input on the configurable input 9 and tells the
RTU Open when the RH level is HIGH or LOW. The
normal condition for humidity is LOW. A normally open
humidistatis thefactory defaultcontrolfor the
Humidi--MiZer
R
option.
To wire in the field:
S J5--8 = 24 VAC source for dry contact
S J5--7 = Signal input
Smoke Detector/Fire Shutdown (FSD) —
On 48HC units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The RTU Open
controller communicates the smoke detector’s tripped status
to the BAS building control. See Figs. 58 and 59, the RTU
Open wiring schematics.
TheFireShutdownSwitchconfiguration,
→
MENU
Config→Inputs→input5,identifiesthe
normally open status of this input when there is no fire
alarm.
Connecting Discrete Inputs —
FilterStatus:Thefilterstatusaccessoryisa
field--installed accessory. This accessory detects plugged
filters. When installing this accessory, the unit must be
configuredforfilterstatusbysetting
→
MENU
Config→Inputs→input3,5,8,or9to Filter
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 57 and Fig. 58 or 59 for wire terminations at J5.
Fan Status: The fan status accessory is a field--installed
accessory. This accessory detects when the indoor fan is
blowing air. When installing this accessory, the unit must
beconfiguredforfanstatusbysetting
→
MENU
Config→Inputs→input3,5,8,or9to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 57 and Fig. 58 or 59 for wire terminations at J5.
Remote Occupancy: The remote occupancy accessory is
a field--installed accessory. This accessory overrides the
unoccupied mode and puts the unit in occupied mode.
When installing this accessory, the unit must be
configuredforremoteoccupancybysetting
→
MENU
Config→Inputs→input3,5,8,or9to Remote
Occupancy and normally open (N/O) or normally closed
(N/C).
→
Also set MENU
Schedules→occupancy source to DI
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 57 and Table 9 for wire
terminations at J5.
Power Exhaust (output): The relay used by the RTU
Open board to control power exhaust is a dry contact
which means it does not have 24vac. This 24vac must be
connected to the relay to allow it to operate the power
exhaust relay in the PE accessory. A 24vac source must be
provided to J11--2 on the RTU Open control board. This
can be provided by the unit’s transformer from various
sources. The “R” terminal on the unit’s low voltage
terminal board (LVTB) is a logical source. Refer to Fig.
57 and Fig. 58 or 59 for wire terminations at J11.
42
Page 43
Communication Wiring -- Protocols
The RTU Open can be set to communicate on four
different protocols: BACnet, Modbus, N2, and LonWorks.
General —
Protocols are the communication languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
Switch 3 (SW3) on the board is used to set protocol and
baud rate. Switches 1 and 2 (SW1 and SW2) are used to
set the board’s network address. See Fig. 67 and 68 for
protocol switch settings and address switches. The 3rd
party connection to the RTU Open is through plug J19.
See Fig. 69 for wiring.
NOTE: Power must be cycled after changing the SW1--3
switch settings.
Refer to the RTU Open Controller Integration Guide
(Catalog No. 11--808--428--01) for more detailed information
on protocols, 3rd party wiring, and networking.
SW3 Protocol Selection
PROTOCOLDS8DS7DS6DS5DS4DS3DS2DS1
BACnet MS/TP
(Master)
Modbus
(Slave)
N2
(Slave)
LonWorksUnusedONONOFFONOFFOFFOFF
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
UnusedOFFOFFOFFONOFFSelect Baud Select Baud
UnusedOFFOFFONONOFFSelect Baud Select Baud
UnusedOFFOFFOFFONONOFFOFF
48HC
Baud Rate Selections
BAUD RATEDS2DS1
9600OFFOFF
19,200ONOFF
38,400OFFON
76,800ONON
Fig. 67 -- RTU Open SW3 Dip Switch Settings
Fig. 68 -- RTU Open Address Switches
C07166
C10815
C10816
Fig. 69 -- Network Wiring
43
Page 44
Local Access —
BACview
6
Handheld: The BACview6is a keypad/display
interface used to connect to the RTU Open to access the
control information, read sensor values, and test the RTU,
see Fig. 70. This is an accessory interface that does not
come with the RTU Open controller and can only be used
6
at the unit. Connect the BACview
to the RTU Open J12
local access port. There are 2 password protected levels in
the display (User and Admin). The user password is
defaulted to 0000 but can be changed. The Admin
password is 1111 and cannot be changed. There is a 10
minute auto logout if a screen is idle. See Form
48--50HCTQ--01T, Appendix A for navigation and screen
content.
48HC
Virtual BACview: Virtual BACview is a freeware computer
program that functions as the BACview
6
Handheld. The
USB Link interface (USB--L) is required to connect a
computer to the RTU Open board. The link cable connects
a USB port to the J12 local access port. This program
functions and operates identical to the handheld.
RTU Open Troubleshooting —
Communication LEDs: The LEDs indicate if the
controller is speaking to the devices on the network. The
LEDs should reflect communication traffic based on the
baud rate set. The higher the baud rate the more solid the
LEDs will appear. See Table 10.
Cable
Access Port
P1P1
J12
P5P5
BACview
Fig. 70 -- BACview6Handheld Connections
Protocol Selector
RTU Open
6
Local Access Cable
C10812
44
Page 45
Table 10 – LEDs
The LEDs on the RTU Open Control Board (see Fig. 57) show the status of certain functions:
If this LED is on...Status is...
PowerRTU Open has power
RxRTU Open is receiving data from the network segment
TxRTU Open is transmitting data over the network segment
DO#The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
2 flashes per secondOffNormal
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per secondOn
5 flashes per secondOnExec start ---up aborted, Boot is running
5 flashes per secondOffFirmware transfer in progress, Boot is running
7 flashes per second
14 flashes per second
OnOn
NOTE:Refer to Catalog No. 48--50HCTQ--01T for
complete configuration of RTU Open, operating sequences
and troubleshooting information. Refer to RTU OpenController Integration Guide (Catalog No. 11--808--428--01)
And Error LED shows...Status is...
2flashes,
alternating with Run LED
3flashes,
then off
4flashes,
then pause
7 flashes per second, alternating with
Run LED
14 flashes per second,
alternating with Run LED
Enthalpy
Switch
Five minute auto --- restart delay after system error
Control module has just been formatted
Two or more devices on this network have the
same ARC156 network address
Exec halted after frequent system errors or
control programs halted
The enthalpy control (33CSENTHSW) is available as a
field--installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
theenthalpycontrol.(Theseparatefield--installed
accessory return air enthalpy sensor (33CSENTSEN) is
required for differential enthalpy control. See Fig. 71.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 71. Connect the
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and
comparing the outside air and return air enthalpy
conditions. Install the outdoor air enthalpy control as
described above. Add and install a return air enthalpy
sensor (see Fig. 72).
enthalpy control power input terminals to economizer
actuator power leads RED (connect to 24V) and BLK
(connect to GND).
48HC
C11160
45
Page 46
– 4-20
Main
+ VDC
Out
Outside Air
Enthalpy Switch
+ 24-36
VDC In
– 4-20 Main
Out
24V
GND
LOW
RED
BLK
GRA
Return Air
Enthalpy
Sensor
PL6-1 (24-V)
PL6-4 (COM)
CTB ECON
7
(P’LINK: to J4-2) or
(RTU Open: to J2-6)
ROTATION
Return Air Sampling Tube
(Shipping Location)
Fig. 72 -- Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the
following:
48HC
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the enthalpy controller.
2. Connect the field--supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(+) terminal on the enthalpy controller. Connect the
BLK wire to (--) spade connector on the return air enthalpy sensor and the (--) terminal on the enthalpy
controller.
Smoke Detectors
Smoke detectors are available as factory--installed options
on 48HC models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Return
Air. Return Air smoke detectors are arranged for vertical
return configurations only. The unit is factory--configured
for immediate smoke detector shutdown operation;
additional wiring or modifications to unit terminal board
may be necessary to complete the unit and smoke detector
configuration to meet project requirements.
C11161
C09102
Fig. 73 -- Typical Supply Air Smoke Detector Sensor
Location
Return Air Detector
Sampling Tube
C09135
Fig. 74 -- Return Air Sampling Tube Location
in Unit without Economizer
Return Air Sensor Tube Installation –
The return air sampling tube is shipped in the units
supply fan section, attached to the blower housing (see
Fig. 73. Its operating location is in the return air section
of the unit (see Fig. 74, unit without economizer, or
Fig. 75, unit with economizer), inserted into the return air
sensor module housing which protrudes through the back
of the control box.
Return Air Detector
Sampling Tube
Fig. 75 -- Return Air Sampling Tube Location
in Unit with Economizer
46
C09136
Page 47
To install the return air sensor sampling tube:
1. Remove the tube from its shipping location.
2. Open the unit end to access the return air sensor (located on right--hand partition)
3. Orient the tube’s sampling holes into the return air
flow direction. For vertical application, position the
sampling holes on the bottom of the tube, facing into
the bottom return duct opening. For horizontal application, position the sampling holes on the side of the
tube, facing the unit’s end panel.
4. Insert the sampling tube into the return air sensor
module until the tube snaps into position.
5. Replace end panel or outside air hood.
Table 11 – Unit Wire/Fuse or HACR Breaker Sizing Data
Smoke Detector Test Magnet —
Locate the magnet; it is shipped in the control box area.
Additional Application Data —
Refer to Catalog No. HKRNKA--1XA for discussions on
additional control features of these smoke detectors
including multiple unit coordination.
NOM.
V --- P h --- H z
UNIT
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D17
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D20
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D24
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D28
5 7 5 --- 3 --- 6 0
COMBUS T IO N
FAN MOTOR
IFM
TYPE
STD
MED71.090.07441082.8100.088430
HIGH75.8100.08041987.6100.093439
STD
MED36.345.03824342.550.045255
HIGH38.950.04124745.150.048259
STD
MED26.230.02718431.040.033192
HIGH29353119833.84036206
STD
MED80.51008544992.310098469
HIGH85.91009145997.7125104479
STD
MED39.2504124945.45049261
HIGH42504525448.26052266
STD
MED29353120033.84036208
HIGH32.4403519837.24540206
STD
MED94.1110100554105.9125113574
HIGH107.6125114628119.4150128648
STD
MED51.4605428257.67061294
HIGH57.4706131963.68068331
STD
MED38.9504120243.75047210
HIGH39.4504222944.25047237
STD
MED122.8150127594134.6175141614
HIGH135.5175142668147.3175156688
STD
MED56.87060308638067320
HIGH62.88067345698074357
STD
MED43.8504622648.66052234
HIGH44.3504725349.16052261
FLAFLA
0.525.9
0.33.1
0.242.4
0.525.9
0.33.1
0.242.4
0.525.9
0.33.1
0.242.4
0.525.9
0.33.1
0.242.4
POWER
EXHAUST
NO C.O. or UNPWR C.O.
NO P.E.w/ P.E. (pwrd fr/ unit)
MCA
68.390.07139380.1100.085413
34.945.03623441.150.044246
26.230.02718431.040.033192
75.71007944087.510093460
36.6453824542.85046257
26.23027186314033194
88.7100.093544100.5125.0107564
48.660.05127754.860.058289
35.545.03720440.350.043212
117.4150.0121584129.2175.0135604
54.060.05730360.270.064315
40.450.04222845.250.048236
FUSE or
HACR
BRKR
DISC. SIZE
FLALRAFLALRA
MCA
FUSE or
HACR
BRKR
DISC. SIZE
48HC
NOTE: See page 49 for table legend and notes.
47
Page 48
Table 11 -- Unit Wire/Fuse or HACR Breaker Sizing Data (cont)
COMBUS T IO N
NOM.
V --- P h --- H z
UNIT
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D17
5 7 5 --- 3 --- 6 0
208/230---3---60
48HC
4 6 0 --- 3 --- 6 0
48HC*D20
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D24
5 7 5 --- 3 --- 6 0
208/230---3---60
4 6 0 --- 3 --- 6 0
48HC*D28
5 7 5 --- 3 --- 6 0
IFM
TYPE
STD
MED75.8100.08041587.6100.093435
HIGH80.6100.08542492.4100.099444
STD
MED38.550.04124544.750.048257
HIGH41.150.04424947.360.051261
STD
MED27.935.02918632.740.035194
HIGH30.740.03320035.545.038208
STD
MED85.31009045497.1110104474
HIGH90.710096464102.5125110484
STD
MED41.4504425147.66051263
HIGH44.2504725650.46054268
STD
MED30.7403320235.54538210
HIGH34.1403620038.94542208
STD
MED98.9125105559110.7125119579
HIGH112.4125120633124.2150133653
STD
MED53.6605728459.87064296
HIGH59.6706432165.88071333
STD
MED40.6504320445.45049212
HIGH41.1504423145.95049239
STD
MED127.6175133599139.4175147619
HIGH140.3175148673152.1200161693
STD
MED59706231065.28070322
HIGH65806934771.28076359
STD
MED45.5604822850.36054236
HIGH46604925550.86054263
FAN MOTOR
FLAFLAMCA
0.525.9
0.33.1
0.242.4
0.525.9
0.33.1
0.242.4
0.525.9
0.33.1
0.242.4
0.525.9
0.33.1
0.242.4
POWER
EXHAUST
NO P.E.w/ P.E. (pwrd fr/ unit)
FUSE or
HACR
BRKR
73.190.07739884.9100.090418
37.145.03923643.350.046248
27.935.02918632.740.035194
80.51008544592.310098465
38.85041247455048259
27.9352918832.74035196
93.5110.099549105.3125.0112569
50.860.05427957.070.061291
37.245.03920642.050.045214
122.2150.0127589134.0175.0140609
56.270.05930562.480.066317
42.150.04423046.960.050238
DISC. SIZE
FLALRAFLALRA
w/ PWRD C.O.
MCA
FUSE or
HACR
BRKR
DISC. SIZE
NOTE: See page 49 for table legend and notes.
48
Page 49
Legend and Notes for Table 11
LEGEND:
BRKR--- Circuit breaker
CO--- Convenience outlet
DISC--- Disconnect
FLA--- Full load amps
LRA--- Locked rotor amps
MCA--- Minimum circuit amps
P E--- P ow er e xh au st
PWRD CO--- Powered convenient outlet
UNPWR CO--- Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 + 231 + 226)
=227
3
=
681
3
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
= 1.76%
4
227
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
48HC
49
Page 50
48HC
Economizer2 Position Damper
Fig. 76 -- EconoMi$ert IV Wiring
Step 13 — Adjust Factory--Installed Options
EconoMi$er IV Occupancy Switch —
Refer to Fig. 76 for general EconoMi$er IV wiring.
External occupancy control is managed through a
connection on the Central Terminal Board.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked
OCCUPANCY on CTB. Remove or cut jumper JMP 2 to
complete the installation.
Step 14 — Install Accessories
Available accessories include:
Roof Curb
Thru--base connection kit (must be installed before unit
is set on curb)
LP conversion kit
Manual outside air damper
High Altitude Gas kits
Low Ambient Controls
Thermostat / Sensors
Unit Without Economizer or
2 Position Damper
C10645
Two--Position motorized outside air damper
EconoMi$er2 (without control/for external signal and
integrated barometric relief)
EconoMi$er IV (with control and integrated barometric
Refer to separate installation instructions for information
on installing these accessories.
Pre--Start and Start--Up
This completes the mechanical installation of the unit.
Refer to the unit’s Service and Maintenance manual for
detailed Pre--Start and Start--up instructions.
50
Page 51
48HC
51
Page 52
48HC
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 04/11
Manufacturer reserves the r ight to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 48HC ---11SI
Replaces: 48HC ---08SI
52
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.