Carrier HRVCCSHB1100, HRVCCSVB1100, ERVCCSVB1100, ERVCCSHB1100 User Manual

ERVCCSVB1100, ERVCCSHB1100 HRVCCSVB1100, HRVCCSHB1100 Energy / Heat Recovery Ventilator
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PAGE
INTRODUCTION 2...................................
UNIT INSTALLATION 3...............................
WALL CONTROL 4...................................
OPERATING THE ERV/HRV WITH
THE INFINITY CONTROL 6...........................
ACCESSORIES 6.....................................
BAL AN CI NG ERV/H RV 7..............................
TROUBLESHOOTING 9...............................
1. Fresh air to building port
2. Exhaust air from building port
3. Fresh air from outside port
4. Exhaust air to outside port
A08103
Fig. 1 -- ERV/HRV Unit (Top Port)
A05330
Fig. 2 -- ERV/HRV Unit (Side Port)
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instruction manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,and
CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
.
INTRODUCTION
The Energy/Heat Recovery Ventilator (ERV/HRV) is used to exchange indoor stale air with outside fresh air. The unit is equipped with a special energy/heat recovery core which transfers both sensible and/or latent heat between the fresh incoming air and stale exhaust air. The cross--flow design core allows entering and leaving air streams to transfer heat and/or latent energy without mixing (See Fig. 3).
STALE AIR FROM BUILDING
FRESH AIR TO BUILDING
Fig. 3 -- ERV/HRV Airflow During Air Exchange
ERV / HRV
(Bottom view with access door removed)
The model operates at 2 airflows, 50 CFM in low speed and 100 CFM in high speed. This unit comes in two configurations, vertical or horizontal. Special attention should be given to duct application, balancing the ERV/HRV, and locating unit for easy access and routine maintenance.
INSTALLATION CONSIDERATIONS
Inspect Equipment
Move carton to final installation location. Remove ERV/HRV from carton taking care not to damage unit. Remove all packaging and inspect unit for damage. Remove parts bag from inside unit. File claim with shipping company if shipment is damaged or incomplete. Check to make sure ERV/HRV unit matches Fig. 1 or Fig. 2.
Select Location
The E RV/HRV should be located in a conditioned space and in close proximity to a fused power source. It should be easily accessible for routine maintenance.
If ERV/HRV is installed independent of a forced--air system, unit should be located near the center of the air distribution system. If
WALL CONTROL
FRESH AIR FROM OUTSIDE
STALE AIR TO OUTSIDE
A07460
ERV/HRV is installed in conjunction with a forced--air system, unit should be located next to (or close to) the indoor equipment.
COMPONENT DESCRIPTION
The following listed items are components of ERVCCSHA (See Fig. 4).
1. Exhaust--air connected to outdoor air exhaust hood.
2. Fresh--air intake connected to outdoor air inlet hood.
3. Fresh--air supply from ERV connected to return--air duct of forced--air system.
4. Mechanical filters trap dust contained in the air.
5. Energy recovery core is a cross--flow type. The core trans­fers heat between the 2 air streams.
6. Blowers bring in fresh--air from outside and exhaust stale-­air to outside.
7. Electronic control circuit ensures proper unit operation.
8. Stale air return from building connected to return--air duct system.
ERV ports on side (bottom view)
4 5
3
2
7
Fig. 4 -- Conventional Horizontal Unit
See Fig. 5 for terminal connector block for wiring wall and timer controls.
4
8
1
6
A05263
Ris k of electric s hoc k. Be fore per formin g
any maintenance or s ervici n g, al way s
disconnect the unit fr om itsp ow er sour ce .
Unscr ew both s cr ews to open the electrical
compar tment . To com plete ly remo ve , detac h
No light OFF or remote controled Amber light LOW speed Green ligh HIGH speed Blinking light See User Manual Sans lumière Arrêté ou contrôlé par contrôle mura l Lumière ambre Basse vitesse Lumière verte Haute vitesse Clignotant Voir guide d’utilisation
WARNING
CAUTIO N
from it s retention wire in s ide.
AVER TI SS EMENT
Danger d’électr ocution. Dé branchez toujour s l’a pp areil avant d’entre prendr e des tra vaux d’entretien ou de ré paration.
ATTENTION
Dévi ss er le s deux vi sp our ouvrir le com partiment
électrique . Pour retirer com plètement , le détacher de s on fil de rétention intérieur .
Terminal Connector
Fig. 5 -- Control Connector
2
BLACK
GREEN
RED
YELLOW
CONTROL
CONNECTOR
A
B
A07418
UNIT INSTALLATION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not install ERV/HRV in a corrosive or contaminated atmosphere.
CAUTION
alone unit. To ensure comfort, this type of application involves running both fresh--air and return--air registers (or stale--air pickup registers) throughout the home.
Fresh--air registers are normally located in bedrooms, dining room, living room, and basement. It is recommended that registers be placed 6 to 12--in. (152 to 305mm) from the ceiling on an interior wall and airflow directed toward ceiling. If registers are floor installed, airflow should be directed toward the wall.
!
WARNING
Mount Unit
The ERV/HRV can be suspended from floor joists using chains and 4 springs. Attach metal hanging bracket to all 4 sides of cabinet. (See Fig. 6.) The unit may be installed on a shelf if an isolation pad is provided to dampen vibration. Unit should always be installed as level as possible.
A05331
Fig. 6 -- Chain Spring Installation
Independent System Application
In the absence of a forced--air system and a typical duct system layout, the ERV/HRV can be applied as an independent or stand
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do not install return--air registers (or stale--air pickup registers) in same room as gas furnace or water heater.
Return--air (or stale--air pickup registers) are normally located to draw from kitchen, bathroom, basement, or other rooms where stale--air can exist.
Proper size and type of registers must be used to minimize pressure drop. The velocity of airflow through register should not be above 400 ft (122m) per minute.
Maximum length of duct for the system should be designed according to the highest speed of the unit. Refer to specifications listed in unit Product Data Digest for ventilation capacities.
Forced--Air Application
Most ERV/HRV applications will be installed in conjunction with new or existing forced--air system. To operate properly, the fresh--air supply and stale--air return from ERV/HRV connect directly to return--air duct system. This is how the ERV/HRV distributes fresh air and removes stale air from inside of building (See Fig. 7). For these installations, furnace or fan coil blower must be interlocked and operate continuously whenever ERV/HRV is energized. See Fig. 17 for interlock wiring detail.
NOTE: The fresh air from ERV/HRV is introduced into return--air duct at a point no less than 6 ft (1.8m) upstream of furnace or fan coil. This connection should be direct (See Fig. 7). This is to allow incoming fresh--air to mix before entering indoor equipment.
ERV / HRV
FURNACE
NOTE: A + B = Not less than 10 ft / 3 m
A
B
ERV
INLET HOOD
REAR
6 ft / 1.8 m
Fig. 7 -- Exhaust Ventilation
3
EXHAUST HOOD
GROUND LEVEL
3 ft / .9 m MIN
INSULATED DUCT CONNECTING FRESH AIR & EXHAUST TO OUTSIDE NOTE: Supply & exhaust ducts have
internal balancing dampers that must be adjusted.
18" / 457 mm
A07282
Connect Ducts to ERV/HRV
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in minor property damage from sweating duct or loss of unit efficiency and capacity.
If ERV/HRV duct work is installed in an unconditioned space, insulated flexible duct is required.
Insulated flexible duct is required on both fresh--air inlet and exhaust--air outlet ducts connecting to exterior wall. When
using insulated flexible duct, the vapor barrier of the flexible ducts must be taped very tight to prevent condensation problems. To reducepressure drop, stretch the flex duct and support it in a proper manner to avoid reduced airflow.
When connecting the ERV/HRV to a return--air duct system, insulated flexible duct can be used. However, when metal or rigid ducts are applied use approximately 18--in. (457mm) of flexible duct at ERV/HRV ports for fresh--air supply, and stale--air return.
ERV / HRV
When using metal duct from fresh--air supply to system duct work, the metal duct should be insulated. (See Fig. 8.) This can act as a silencer when connecting ducts to return--air duct system. This should eliminate transmission of noise or vibration from unit to main duct system.
CAUTION
To connect condensate drain, proceed as follows:
1. Punch out holes in foam insulation and door, then insert sleeved grommets into bottom of unit using the gasket washer and nut. (See Fig. 9.)
2. Cut two sections of plastic tubing, about 12--in. / 305mm long and attach them to each drain.
3. Join the two short sections of plastic tubing to the “T” con­nector and the main tube as shown.
4. Make a loop in the tubing below the “T” connector to create a trap to prevent sewer gases from entering the ventilation system. (See Fig. 9.)
5. Connect unit drain to building’s main drain. Provide slight slope from unit for run--off.
STALE-AIR RETURN
FRESH-AIR SUPPLY
FLEXIBLE DUCTS CONNECTING TO
RETURN-AIR DUCT SYSTEM
A08102
Fig. 8 -- Flexible Duct Fit--Up
Locate and Install Exterior Hoods
IMPORTANT: To prevent condensation problems, insulated
flexible ducts are required on both fresh--air inlet and exhaust--air outlet ducts connecting between ERV/HRV and exterior wall.
Fresh--air intake and stale--air exhaust must be separated by at least 6 ft (1.8m). Fresh--air intake must be positioned at least 10 ft (3m) from nearest dryer vent, furnace exhaust, driveway, gas meter, or oil fill pipe. Fresh--air intake must be positioned as far as possible from garbage containers and potential chemical fumes. When possible, it is advised to locate the intake and exhaust hoods on same side of house or building. The intake and exhaust hoods should never be located on interior corners or in dead air pockets (See Fig. 7). Both intake and exhaust hoods must be 18--in. (457mm) from ground and at least 12--in. (305mm) above anticipated snow level.
After selecting proper hood locations, make appropriate size hole through exterior wall, pass flexible duct through hole and insert hood tube into duct. Tape duct vapor barrier tightly around hood tube and insert assembly back into wall and fasten securely.
Condensate Drain
(For ERV, skip this step and continue to the next step.)
A99268
Fig. 9 -- Condensate Drain With Loop Trap (HRV Only)
WALL CONTROL
Types
Four remote wall control options are available:
1. Basic Control (see Table 1).
2. OneTouch Control
3. Standard Control (includes dehumidistat)
4. Latent Control (includes humidistat for use with ERV’s only)
Table 1 – Basic Control
MODE OPERATION
Off Off Closed to outside Off
Low
Intermittent
High
Air exchange with
outside
Air exchange with
outside
Air exchange with
outside
DAMPER
POSITION
Open to outside Low
Open to outside Low
Open to outside High
Location
The Standard Control and the Latent Control sense humidity and not temperature. They must be located in an area where they will continually monitor fresh air circulating within the home. Install ERV/HRV wall controls as close as possible to main system thermostat and follow same guidelines as installing a thermostat (locate approximately 5 ft (1.5m) above floor, mount on an inside partitioning wall, etc.)
Wiring
Remove top cover assembly from wall control and pass thermostat wire through hole located on back of control before attaching to wall. Connect Y, R, G, and B (yellow, red, green, and black)
FAN
SPEED
4
between wall control and ERV/HRV connector following color code. (See Fig. 5 and 10.) Replace top cover assembly.
NOTE: ERV/HRV wall control and circuit board operate on 12VDC.
YELLOW
RED
GREEN
YR GB
BLACK
A98383
Fig. 10 -- Typical Wall Control
Operation
The Standard and Latent wall controls have 4 basic modes of operation, OFF, LOW, HIGH, and INTERMITTENT. Be sure that all modes of operation are fully functional. See Table 1 indicating standard control operation.
1. With switch off, ERV/HRV is inoperative and the LED is out.
2. With switch on LOW, ERV/HRV continuously exchanges air with outside. If control is satisfied, blower will run in low speed, otherwise, blower will run on high speed. The LED is illuminated all the time.
3. With switch on INTERMITTENT, the ERV/HRV ex­changes air with outside on high--speed blower, and unit shuts down when control is satisfied. The ON LED is illu­minated all the time, and AIR EXCHANGE LED is illumi­nated only when unit is running.
Humidity Selector
The humidity selector is a built--in control designed to properly control the level of humidity in the house during the winter and summer months. This control helps avoid condensation problems in upper northern regions where indoor humidity is a problem during the winter season.
NOTE: This control is not to be confused with a dehumidistat used during the summer months to control high relative indoor humidity.
Table 2 recommends humidity levels to avoid condensation.
Table 2 – Recommended Humidity Levels
OUTSIDE
TEMPERATURE
50°F/10°C 55% 65%
32°F/0°C 45% 55%
14°F / --- 1 0 °C 35% 45%
--- 4 °F / --- 2 0 °C 30% 45%
--- 2 2 °F / --- 3 0 °C 25% 35%
D O U B L E --- P A N E
WINDOWS
T R I P L E --- P A N E
WINDOWS
OneTouch Control
The OneTouch Control can be used as the primary wall control for the ERV/HRV. This control will step through the modes of operation with consecutive presses of the button. The LED indicates which mode is currently selected, Off, Intermittent, Low, or High.
NOTE: OneTouch Control does not have a humidity selector. NOTE: OneTouch Intermittent mode exchanges air on low speed
for 20 minutes per hour.
Latent Control
NOTE: For Latent Controls used with ERV;s, to ensure highest
degree of humidity control in cooling season, the INTERMITTENT mode should be used.
Integrated Control
All units are equipped with an integrated control, located under the unit, in front of the electrical compartment. Use the push button (1) to control the unit. The LED (2) will then shows on which mode the unit is in. Integrated Control overrides Wall Control function. When LED is off, ventilator responds to Wall Control command. See Fig. 11.
WARNING
Risk of electric shock. Before performing
any maintenance or servicing, always
disconnect the unit from its power source.
CAUTION
Unscrew both screws to open the electrical
compartment. To completely remove, detach
from its retention wire inside.
No li ght OFF or remote controled Amber light LOW speed Green ligh HIGH speed Blinking light See User Manual Sans lumière Arrêté ou contrôlé par contrôle mural Lumière ambre Basse vitesse Lumière verte Haute vitesse Clignotant Voir guide d’utilisation
1
2
Fig. 11 -- Integrated Control
Refer to table below to see how to operate the unit using its integrated control.
PRESS ON PUSH
BUTTON
Once Amber
Twic e Green
Three Times No Light Unit is OFF
LED COLOR RESULTS
If a problem occurs during the unit operation, its integrated control LED (2) will blink. The color of the blinking light depends on the type of error detected. Refer to Troubleshooting for further details.
NOTE: The ERV/HRV may be controlled using the Infinity system control. The ERV/HRV may be connected using either a NIM or a 4--Zone Damper Module. See the appropriate instructions if using the NIM or a 4--Zone Damper Module for connection instructions.
The Infinity system control will simultaneously control the ERV/HRV and the indoor blower.
Push Button Timers may be used and are connected to the ERV/HRV. However, the Infinity system should be set to continuous fan to ensure that the fresh air is circulated in the home. In a Zoned System, at least one zone should be set to continuous fan.
AVERTISSEMENT
Danger d’électrocution. Débranchez toujours l’appareil avant d’entreprendre des travaux d’entretien ou de réparation.
ATTENTION
Dévisser les deux vis pour ouvrir le compartiment
électrique. Pour retirer complètement, le détacher de son fil de rétention intérieur.
A07260
Unit is on Low
Speed
Unit is on High
Speed
ERV / HRV
5
OPERATING THE ERV/HRV WITH
THE INFINITY CONTROL
The ventilator has four settings in heating mode and three settings in cooling mode.
Heating:
AUTO -- the ventilator selects the speed based on indoor humidity and outdoor temperature. It may cycle on/off every 30 minutes depending on humidity and outside temperature.
LOW -- low speed all of the time. HIGH -- high speed all of the time. DEHUM -- will only turn on if humidity is 3% over setpoint.
The speed is determined by indoor humidity and outdoor temperature.
Cooling:
AUTO -- the ventilator selects the speed based on indoor humidity and outdoor temperature. It may cycle on/off every 30 minutes depending on humidity and outside temperature.
LOW -- low speed all of the time.
ERV / HRV
HIGH -- high speed all of the time.
If the fan speed is set to Auto and the ventilator wants to run, the fan speed will run at High continuous speed. Otherwise, the fan will stay at the chosen continuous fan speed.
BOOT SEQUENCE
The unit boot sequence is similar to a personal computer boot sequence. Each time the unit is plugged after being unplugged, or after a power failure, the unit will perform a 30--second booting sequence before starting to operate. During the booting sequence, the integrated control LED will light GREEN or AMBER for 5 seconds, and then will shut off for 2 seconds. After that, the LED will light RED for the rest of the booting sequence. During this RED light phase, the unit is checking and resetting the motorized damper position.
Once the motorized damper position completely set, the RED light turns off and the booting sequence is done.
NOTE: No command will be taken until the unit is fully booted.
ACCESSORIES
20 Minute Timer
A push button timer can be used to override the wall control and put the ERV/HRV into high speed for 20 minutes. Connect switches in parallel and connect leads to ERV/HRV terminals I, OC, and OL (See Fig. 12). Push button locations are ideal in special activity areas, such as, bathroom, or kitchen, where high--speed exhaust operation is needed for a short period of time.
NOTE: The 20 minute timer will not function properly unless ERV/HRV wall control is applied and working correctly. Timing function is internal to electronic circuit board, it is activated by a momentary contact between OC and OL. The I connection is to illuminate the push button. The maximum number of push button timers that can be applied is 5.
60 Minute Adjustable Timer
A 60 minute adjustable timer can also be used to override wall control and put HRV into high--speed operation for a select amount of time. Connect timer in parallel with push button timers, or to ERV/HRV terminals OC and OL. (See Fig. 12.)
The 60 minute timer will provide a minimum of 10 minutes, and a maximum of 60 minutes of ventilation at high speed.
ELECTRONIC CONTROL
BOARD
J1
OL OC
J3
I
41 7
52 8
63 9
9 8 7 6 5 4 3
(OPTIONAL)
60 MINUTE TIMER
THE WIRES FROM THE SWITCH
YELLOW – INDICATOR, ( J3--3)
BLACK – COMMON, (J 3--4)
RED – SWITCH, (J3--5)
(OPTIONAL)
PUSH BUTTON SWITCHES
(5 SWITCHES MAXI MUM)
RED BLACK YELLOW
ELECTRICAL CONNECTIONS
115--VAC Wi ring
The ERV/HRV operates on 115VAC. It comes with a power cord attached to unit and ready to plug into a fused outlet. Unit must be grounded for proper operation.
All electrical connections must comply with National and Local Electrical Codes, or other ordinances that might apply.
!
ELECTRICAL SHOCK / FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not use an extension cord as a power source for operating the ERV/HRV.
12VDC Wiring
The ERV/HRV circuit board, wall control, and accessories operate on 12VDC. See Wall Control section, item Wiring and Fig. 5 and 10 for more information.
WARNING
(OC)
BLACK – (J3- 4)
COMMON
TERMINAL
STRIP
(I)
YELLOW – ( J3-3)
INDICATOR TERMINAL STRIP
RED – (J3- 5)
SWITCH TERMINAL STRIP
(OL)
BACK OF PUSH BUTTON SWITCH
Fig. 12 -- Push Button Timer Wiring Layout
A98386
6
BALANCING ERV/HRV
Balancing intake and exhaust airflow is very important for proper system operation and optimum performance when applying an ERV/HRV. Unit balancing prevents a positive and/or negative pressure within the home. Balancing the ERV/HRV is done by applying magnehelic gauge and using the balancing dampers at the fresh air intake and stale air exhaust ducts. (See Fig. 13.)
Balancing
Chart
1 12 12 11 1 12 12 11 3 13 33 23 1 12 12 11 1 12 12 11 3 13 33 23
See Detail A
DETAIL A
Port with integrated balancing damper Top View
Fig. 13 -- Balancing ERV/HRV
Airflow is determined by temporarily connecting a magnehelic gauge to the pressure taps on ERV/HRV. (See Fig. 14.) Balancing chart is located on unit door.
Fig. 14 -- Magnehelic Gauge
Fresh air flow
Exhaust air flow
A07261
A98400
Before proceeding with balancing, all windows, doors, and fireplace flues should be tightly closed. No exhaust systems such as range top exhausts, dryer exhaust, fume hoods, bath or roof fans should be in operation. The forced--air furnace (if used for circulation) should be operating in continuous fan mode for normal operating speed.
Balancing Procedure Step 1 — Set the unit to high speed.
Make sure that the furnace/air handler blower is ON if the installation is in any way connected to the ductwork of the cold air return. If not, leave furnace/air handler blower OFF. If the outside temperature is below 32_F(0_C), make sure the unit is not running in defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured that the unit is not in a defrost cycle.)
Step 2 — Magnehelic gauge placement.
Place the magnehelic gauge on a level surface and adjust it to zero.
Step 3 — Connect tubing from gauge to EX­HAUST air flow pressure taps.
Be sure to connect the tubes to their appropriate high/low fittings. (See Fig. 13.) If the gauge drops below zero, reverse the tubing connections.
NOTE: It is suggested to start with the exhaust air flow reading because the exhaust has typically more restriction than the fresh air, especially in cases of fully ducted installations or source point ventilation. Place the magnehelic gauge upright and level. Record equivalent AIR FLOW of the reading according to the balancing chart.
Step 4 — Move tubing to FRESH air flow pressure taps.
Adjust the fresh air balancing damper until the fresh air flow is approximately the same as the EXHAUST air flow. If fresh air flow is less than exhaust air flow, then go back and adjust the exhaust balancing damper to equal the fresh air flow. (See Fig. 13.)
Step 5 — Secure both dampers thumb screw in place with tape.
Step 6 — Record air flow information.
Write the required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows, your name, phone number and business address).
NOTE: The unit is considered balanced even if there is a difference of ±10 CFM (or ±5 l/s or 17 m3/h) between the two air flows.
Balancing Dampers
Balancing dampers (sometimes called butterfly dampers) are located in fresh--air intake and stale--air exhaust of the ERV/HRV. (See Fig. 13.) Insulating over these dampers is strongly recommended after balancing is complete to prevent condensation problems.
ERV / HRV
If supply--air from outside is greater than exhaust--air from the house, an imbalance can result over pressurizing the home. If exhaust--air is greater than supply--air, combustion appliances may backdraft, bringing exhaust fumes into the house. A balanced condition will ensure optimum performance, provide satisfied customers, and avoid expensive callbacks.
7
VENTILATION EVALUATION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced unit efficiency, capacity or unit life.
DO NOT use HRV during construction of a house or when sanding drywall. This type of dust may damage system.
Ventilator Sizing
Tables 3 and 4 should be used to determine the required airflow for a home. These guidelines are taken from ASHRAE 62.2--2004.
Table 3 – Ventilation Air Requirements, cfm
FLOOR
AREA (ft
ERV / HRV
1501--- 3000 45 60 75 90 105 3001--- 4500 60 75 90 105 120 4501--- 6000 75 90 105 120 135 6001--- 7500 90 105 120 135 150
AREA (m
139.1--- 279 21 28 35 42 50
279.1--- 418 28 35 42 50 57
418.1--- 557 35 42 50 57 64
557.1--- 697 42 50 57 64 71
2
)
<1500 30 45 60 75 90
>7500 105 120 135 150 165
Table 4 – Ventilation Air Requirements, L/s
FLOOR
2
)
<139 14 21 28 35 42
>697 50 57 64 71 78
CAUTION
BEDROOMS
0 --- 1 2 --- 3 4 --- 5 6 --- 7 >7
BEDROOMS
0 --- 1 2 --- 3 4 --- 5 6 --- 7 >7
CONTROL BOARD OPERATION
Defrost
The ERV/HRV continually monitors the outside air temperature. If the outside air is at or below 23°F(--5°C), the ERV/HRV will initiate a defrost cycle by closing the outside air damper and recirculating warm indoor air through the heat recovery core. This happens every 32 minutes with a 6 minute defrost cycle. During this process, core is defrosted without the use of electric strip heat. At 5°F(--15°C), unit will defrost for 6 minutes every 32 minutes. At --17°F(--27°C), the unit will sense a need to defrost every 20 minutes with a 6 minute cycle. See the Troubleshooting section for a control logic explanation.
Off and Intermittent/Off Mode
When ERV/HRV is Off, K1 relay is open, and K5 relay is energized which closes outside air damper.
High--Speed Air Exchange
When high--speed air exchange occurs, K1 and K2 relays are energized and K5 relay is de--energized. This opens low--speed contacts, and closes high--speed contact on K2 relay. This also opens contact on K5 relay which opens outside air damper. Then, 115VAC is applied between orange and gray wires on Molex plug (pins 1 and 6) and blower motor runs in high--speed operation.
Low--Speed Air Exchange
When low--speed air exchange occurs, K1 Relay is energized which closes the contacts. K2 and K5 relays are de--energized. This keeps low--speed contacts closed and high--speed contacts open on K2 relay, and opens outdoor air damper. 120VAC is applied
between Red and Gray wires on Molex plug (pins 1 and 4) and blower motor runs in low--speed operation.
CARE AND MAINTENANCE
Door
ERV/HRV door can be removed by unlatching brief case style latches, then slide door to the right and remove it from hinges. Door must be in place and secured shut for proper operation.
Filter
Filters in ERV/HRV are washable and should be cleaned every 3 months. Use a vacuum cleaner to remove heaviest portion of accumulated dust, then wash in lukewarm water. Allow filter to completely dry before reinstalling. A dirty air filter will cause excessive strain on blower motor. Never operate unit without a filter. Vacuum out debris.
In addition, regularly check and clean screens on exterior intake and exhaust hoods when necessary.
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
DO NOT clean filters in a dishwasher and DO NOT dry them with a heating appliance or permanent damage will result.
Blower Motor and Wheel
ERV/HRV blower motors are factory lubricated for life. Lubricating bearings is not recommended. However, inspect and clean any accumulated dirt and grease from blower motor and wheel annually.
Cleaning the Core
ERV is equipped with a special energy recovery core which utilizes a special membrane and allows transfer of sensible and latent energy. The core should always be vacuumed only every 3 months to remove dust and dirt that could prevent transfer of energy. (See Fig. 15 and 16.)
Fig. 15 -- ERV Ports on Side (Bottom View)
Fig. 16 -- HRV Ports on Side (Bottom View)
CAUTION
A05347
A05348
8
NOTE: The core should only be serviced when outdoor temperature is 60°Fto75°F(16°Cto24°C) and it is dry.
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
DO NOT use water to clean core or damage will result. In addition, before servicing or removing the core inspect the edges to see if they appear soft (or slightly expanded). This can be normal and due to moisture in the air. DO NOT handle or service core until it is dry or air passages can become damaged and/or closed.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than 1 disconnect switch.
!
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when handling parts.
CAUTION
WARNING
CAUTION
TROUBLESHOOTING
NOTE: Reference Table 5 Troubleshooting Chart
This can be a quick guide in resolving unit problems. It is also recommended to review and understand Wall Control Board Operation and Care and Maintenance sections before continuing.
NOTE: If there is a short circuit or an open circuit at thermistor, CPU will go into a 5 minute defrost cycle every 20 minutes. This feature is not there on older board versions with 3 pin jumpers.
Override Test
To use override test function, a thermistor must be connected to the control board. Unit must not be in defrost mode during an override test.
High Speed
1. Disconnect ERV/HRV from 115VAC.
1. Unplug wall control wires at control module terminal block in­side ERV/HRV.
2. Plug ERV/HRV back to 115VAC.
3. Attach a wire across J3--8 and J3--9 (B and G) on control mod­ule terminal block.
4. Close door, this will initiate a high--speed exchange.
Low Speed
1. Unplug ERV/HRV from 115VAC.
2. Disconnect wall control wires at control module terminal block inside ERV/HRV.
3. Plug ERV/HRV back to 115VAC.
4. Connect a 3.0 K ohm resistor between B and G on control module terminal block.
5. Close door, this will initiate a low--speed exchange.
Blower Speed Selection
Three--speed blowers are factory connected to electronic control board on HIGH-- and LOW--speed taps of blowers. Installer can easily change low--speed tap to medium--speed tap so electronic control will select between high and medium speed. Connections can be changed at transformer location. See Connection diagram, Fig. 17.
ERV / HRV
9
If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where on the unit the problem occurs.
Table 5 – Troubleshooting
LED flashes GREEN. Thermistor error. Reference Table 6 for proper temperature vs. resistance relationship. If thermistor
LED flashes RED.
LED flashes AMBER. Damper error. Go to Problem 6 below.
Problem: Possible causes: You should try this:
1. Unit does not work. S The circuit board may be defective. S Unplug the unit. Disconnect the main
2. The damper actuator does not work.
The door is open and the unit is not unplugged.
Exhaust motor error. Go to Problem 5 below.
S The damper actuator or the integrated
damper port mechanism may be defective.
ERV / HRV
S The circuit board may be defective. S If there is no 24VAC, replace the circuitboard.
3. The wall control does not work OR its indi­cator flashes.
4. The dehumidistat does not work OR the 20--minute. push -­button timer does not work OR its indicator light does not stay on.
5. The supply and/or exhaust motor do not work.
6. The defrost cycle does not work (the fresh air duct is fro­zen OR the fresh air distributed is very cold. (See Table 7 for Defrost Cycle Tim­ing.)
7. The integrated con­trol push button does not work.
S The wires may be in reverse position. S Ensure that the color coded wires have been connected to their work OR its
S The wires may be broken. S Inspect every wire and replace any that are damaged. S The wire in the wall OR the wall. S Remove the wall control and test it right beside the unit using another control
S The wires may be in reverse position. S Ensure that the color coded wires have been connected to their appropriate
S The dehumidified or push button may be
defective.
S The circuit board may be defective. S Press on the integrated control push button until the unit turn on low speed (the
S The motor(s) may be defective. S Using a multimeter, check the ohms value on each motor connectors. Black
S Ice deposits may be hindering the
damper operation.
S The damper rod or the port damperitself
may be broken.
S The damper actuator or circuit board
may be defective.
S The 30--second boot sequence is not
completed.
is defective, replace the entire port assembly (fresh air from outside port). Close the door and press once on the integrated control push button to reset the
unit.
control and the optional control(s) (if need be). Jump G and B terminals. Plug the unit back and wait about 10 seconds. If the motorsrunonhighspeedandthedamper opens, the circuit board is not defective.
S Unplug the unit.Disconnectthe main controland the optional controls(s)(if need
be).Wait 10 seconds and plug the unit back. Check if the damper opens. If not, use a multimeter and check for 24VAC on J12--1 and J12--2 (in electrical compartment). If there is 24VAC, replace the entire port assembly.
NOTE: It is normal to experience a small delay (7--8 seconds) before detecting the 24VAC signal at starting--up. This signal will stay during 17--18 seconds before disappearing.
indicator flashes. appropriate places.
may be defective. shorter wire. If the wall control works there, change the wire. If it does not, change the wall control.
places.
S Jump the OL and OC terminals. If the unit
switch to high speed, remove the dehumidistat or push button and test it right beside the unitusing anothershorter wire. If it works here, change the wire. If it doesn’t, change the dehumidistat or the push button.
LED will light AMBER). Using a multimeter, check the voltage on J4--1 and J4--2 (for supply motor), and on J5--1 and J5--2 (for exhaust motor). The reading must be ± 68VAC. Then set the unit on high speed by pressing on theintegrated control 1 more time (the LED will light GREEN).Using a multimeter, check the voltage on J4--1 and J4--2 (for supply motor), and on J5--1 and J5--2 (forexhaust motor). The reading must be ± 120VAC. If allthe readings correspond to theright voltage values, the circuit board is not defective. If one or both readings are different, change the circuit board.
motors values: For BLUE and BLACK motor wires, the right value is ± 55 ohms. For BLUE and BROWN motorwires, the right value is ± 35 ohms. ForBROWN and BLACK motor wires, the rightvalue is± 89 ohms.Aluminum motors values: For BLUE and BLACK motorwires,the right valueis ±51 ohms.For BLUE and BROWN motor wires, the right value is ± 47 ohms. For BROWN and BLACK motor wires, the right value is ± 98 ohms. If he ohms values are the same, the motor is not defective. Replace the motor capacitor.
S Remove the ice.
S Inspect these parts and replace if necessary.
S See Problem 2.
S See Boot Sequence.
NO C NC I OC OL Y R G B
NO C NC I OC OL Y R G B
10
Table 6 – Temperature / Ohm Relationship
TEMP. (°F/°C) RESISTANCE (OHMS)
--- 9 / --- 2 3 78330
--- 8 / --- 2 2 74610
--- 6 / --- 2 1 71100
--- 4 / --- 2 0 67770
--- 2 / --- 1 9 64570
--- . 4 / --- 1 8 61540 1 / --- 1 7 58680 3 / --- 1 6 55970 5 / --- 1 5 53410 7 / --- 1 4 50980 9 / --- 1 3 48680
10 / ---12 46500 12 / ---11 44430 14 / ---10 42470
1 6 / --- 9 40570 1 8 / --- 8 38770 1 9 / --- 7 37060 2 1 / --- 6 35440 2 3 / --- 5 33900 2 5 / --- 4 32440 2 7 / --- 3 31050 2 8 / --- 2 29730 3 0 / --- 1 28480
32 / 0 27280 34 / 1 26130 36 / 2 25030 37 / 3 23990 39 / 4 23000 41 / 5 22050 43 / 6 21150 45 / 7 20300 46 / 8 19480
48 / 9 18700 50 / 10 17960 52 / 11 17240 54 / 12 16560 55 / 13 15900 57 / 14 15280 59 / 15 14690 61 / 16 14120 63 / 17 13580 64 / 18 13060 66 / 19 12560 68 / 20 12090 70 / 21 11630 72 / 22 11200 73 / 23 10780 75 / 24 10380 77 / 25 10000 79 / 26 9632 81 / 27 9281 82 / 28 8944 84 / 29 8622 86 / 30 8313 88 / 31 8014 90 / 32 7728 91 / 33 7454 93 / 34 7192 95 / 35 6940 97 / 36 6699 99 / 37 6467
100 / 38 6245
Outside Temp
°F/°C
23 to ---17°F
--- 5 t o --- 2 7 °C
--- 1 7 °Fandless
--- 2 7 °Candless
Outside Temp
°F/°C
23 to ---17°F
--- 5 t o --- 2 7 °C
--- 1 7 °Fandless
--- 2 7 °Candless
Table 7 – Defrost Cycle
HRV DEFROST CYCLES
Defrosting
(minutes)
8 25
10 22
ERV DEFROST CYCLES
Defrosting
(minutes)
9 28
10 22
Operation time (min.)
between each
defrost cycle
Operation time (min.)
between each
defrost cycle
ERV / HRV
11
CONNECTION DIAGRAM
ERV / HRV
1. : USE SPECIFIED UL LISTED/CSA CERTIFIED LINE FUSE. Type 3AG, Littelfuse no
312003.
2. If any of the original wire, as supplied, must be replaced, use the same equivalent wire.
3. Field wiring must comply with applicable codes, ordinances and regulations.
4. Remote controls available. See instruction manual. (class 2 circuit)
5. Furnace fan circuit must be class 2 circuit only.
GRN
Ref
1
BLK
Exhaust fan motor
Exhaust fan motor
capacitor
Supply fan motor
capacitor
Supply fan motor
M1
C1
C2
M2
GRN
BRN
BLK
BLK
BLK
BLK
BLK
BRN
BLU
BLU
COLOR CODE
BLK BLACK BLU BLUE BRN BROWN GRN GREEN GRY GRY ORG ORANGE RED RED WHT WHITE YEL YELLOW
Damper motor
BLK
BLU
PRP
ORG
GRY
RED
WHT
BLU
RED PRP ORG
GRY
120V
106V
81V
71V
64V
57V
(6)
neutral
1 2 3
2 1
2 1
1 2 3
J5
J7
J6
J4
T1
BLU RED
M3
nc nc nc
24V class 2
9.5V class 2
YEL
J8
See note 1
F1
YEL
J9
JU1
MED
J10
WHT
ORG
ORG
Line voltage factory wiring
Class 2 low voltage factory wiring
Class 2 low voltage field wiring
DAMPER ELECTRONIC
ASSEMBLY
J3
A2
123
J1
BLK
BLK
12
J2
4512
S1
ICP
J13
BLK
o
t
10
9 8 7 6 5 4 3 2 1
J14
A1
Defrost temperature
R1
sensor
Field wiring
remote control
(see notes 3, 4)
BLK
YEL
RED
GRN
Furnace blower interlock
J14-1 : NO
J14-2 : COM
J14-3 : NC
(optional; see notes 3, 5)
Door interlock
switch (magnetically actuated reed
switch)
WHT
WHT
12345
123
HI
12
34
12
BLK
J11
12
J12
12345
ELECTRONIC ASSEMBLY
120V, 60Hz
W1
GRN
K5 K2 K3 K1 MODE M1 "Supply" M2 - "Exhaust" DAMPER
0000 OFF OFF OFF Closed 1 0 1 1 Exchange low speed LO LO Opened 1 1 1 1 Exchange high speed HI HI Opened 1 1 1 0 Circulation high speed HI OFF Closed 1 1 1 0 Defrost HI OFF Closed
Fig. 17 -- ERV / HRV Wiring Diagram
12
A10001
Ref
1
BLK
BLU
RED
PRP
ORG
GRY
WHT
120V
106V
57V
81V
71V
64V
120V, 60Hz
MED
LO
nc
nc
nc
Line
J9-1
J9-2
J9-3
J9-4
F1
LOGIC DIAGRAM
MED
HI
1
3
2
JU1
K2
K1
K3
A1
J5-1
J5-3
J7-2
J7-1
J4-1
J4-3
J6-2
J6-1
Exhaust fan motor
Exhaust fan motor
capacitor
Supply fan motor
Supply fan motor
capacitor
120V, 60Hz
Neutral
J10-1J10-2
J5-2
J4-2
ERV / HRV
BLK
BLU
PRP
ORG
GRY
RED
WHT
120V
106V
81V
71V
64V
57V
neutral
K5
J2-5
J2-4
J2-3
J2-2
J2-1
A2
J3-2
J3-1
J14-3
J14-1
J14-2
J14-4
J14-5
J14-6
J14-7
J14-8
J14-9
J14-10
Damper motor
Door interlock switch
Furnace blower interlock (optional; see notes 3, 5)
Override switch (optional; see notes 3, 4)
Field wiring remote control (see notes 3, 4)
J12-5
K4
J12-4
J12-3
J12-2
J12-1
J11-2
J11-1
ORG
24V class 2
ORG
YEL
9.5V class 2
YEL
(6)
J8-1
J8-2
J8-4
J8-5
CPU
K2
K4
K5
K1
K3
Fig. 18 -- ERV / HRV Wiring Diagram
13
A10002
Energy Star (Canada)
S ERVCCSVB1100 S ERVCCSHB1100 S HRVCCSVB1100
These products earned the ENERGY STAR energy efficiency guidelines set by Natural Resources Canada and the US EPA. They meet ENERGY STAR requirements only when used in Canada.
®
by meeting strict
S HRVCCSHB1100
ERV / HRV
Copyright 2010 Carrier Corp. S 7310 W. Mo rris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 05/10
Manufacturer reserves the right to c hange, at any time, s pecifications and designs without notice and without obligations.
14
Catalog No: ERVHRV--- 3SI
Replaces: ERVHRV--- 2SI