Facts you should know about your new Electronic Air Cleaner
1)Regular dusting & "white dust"4
2)Ozone4
3)Air flow sensor operation5
4)High altitude applications6
Replacing the ionizing wires7
CommonQ&A8-9
Maintenance of your Electronic Air Cleaner10
1)Removing the cells and prefilter10
2)Washing the cells and prefilter(s)11
3)Replacing the cells and prefilter(s)11
Common troubleshooting techniques12
Installation instructions ( for use by authorized HVAC
contractors)15-29
Technicaltroubleshootingflowchart29-30
Replacementpartlist 31-32
List of figuresPage
Figure 1Air flow sensor diagram5
Figure 2Reducing ozone in high altitude applications6
Figure 3Cleaning the ionizing-collector cells10
Table 1Symptoms of excessive arcing or zapping12
Unit dimensions13
Technical specifications15
Typical HVAC system configurations16
Figure 4Sheet metal transitions18
Figure 5Turning vanes from improving air flow18
Figure 6Proper installation of cell spacer19
Figure 7Proper mounting diagram21
Figure 8Wiring the unit to the input power source22
Figure 9Electrical schematic diagram26
Figure 10Testing the power supply output28
Troubleshooting flowchart29-30
Unitpartsdiagram 31-32
Page 3
NOTE:
Read the entire instruction manual before starting the installation.
Safety Considerations
Improper installation, adjustment, alteration, service, maintenance, or use
can cause explosion, fire, electrical shock, or other conditions which may
cause personal injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for information or assistance.
The qualified installer or agency must use factory authorized kits or
accessories when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Read these
instructions thoroughly and follow all warning or cautions attachedto the unit.
consult local building codes and National Electric Code (NEC) for special
requirements.
Recognize safety information. This is the safety-alert symbol. When you
see this symbol on unit or in instructions and manuals, be alert to potential for
personal injury.
Understand the signal wordsandThese
words are used with the safety alert symbol.identifies the most
DANGER, WARNING,CAUTION.
DANGER
serious hazards which will result in severe personal injury or death.
WARNINGcould
CAUTIONwould
personal injury or product and property damage.is used to highlight
signifies a hazard whichresult in personal injury or death.
is used to identify unsafe practices whichresult in minor
NOTE
suggestions that will result in enhanced installation, reliability, or operation.
This manual provides information for location, installation, operation and
service. Before installation and use of the air cleaner, carefully read these
instructions to insure maximum benefits from the unit and to avoid needless
service costs that can result from improper installation.
1
Page 4
INTRODUCTION
This electronic air cleaner is technically known as a two-stage electrostatic
precipitator.The air cleaner is designed to remove airborne particulates,
including dust, dirt, smoke, pollen, virus, spores, bacteria and mold, from indoor
air.
Air movement through the unit is provided by the heating, air conditioning or
ventilating system blower. As dirty air enters the air cleaner, the air passes
through a metal mesh prefilter.Theprefilter prevents lint, pet hair and other large
particulates from entering the air cleaner. It its important that these filters be in
place to prevent excessive dirt loading of the air cleaner collector cells. These
filters extend the time between maintenance of the air cleaner collector
cells.This allows the ionizing-collector cells to provide clean air for a longer
period between washings.
The prefiltered air then passes through a two-stage Electronic Air Cleaner. In the
first stage, all airborne particulate, even submicron size, are electronically
charged (positive) as they pass through the ionizer. The ionizer field is set up by
a corona discharge emanating from the fine, tightly strung wires suspended
between two adjacent flat plates. In the second stage, the charged particulate
passes through an intense electrical field established between alternately
charged and grounded parallel collector plates. Here, the positively charged
particulate is attracted to the negatively ground plates and removed from the air
stream.
For a unit diagram and a completelistingofallparts,pleasesee page 31-32.
2
Page 5
UNIT SPECIFICATIONS
This air cleaner is easy to install, operateand maintain. Its basic components
are the:
Cabinet
Mounts to existing ductwork; houses the ionizing-collecting cells and
prefilters.
Ionizing-Collector Cells
Collect the dust, dirt and other particulates in the air. They contain the
ionizing and collecting sections as described on page 2. The cells must be
installed with ionizing wires on the air intake side. A spring contact is located
on the top of each cell and must be in position to make contact with the
contact board assemblies on the bottom of the power tray assembly.
Prefilters
Trap large particulates before it enters the ionizing-collector cells.
Power Tray Assembly
Contains the indicating light, solid state power supply, contact boards and
electrical controls including ON/OFF switch and safety interlock switch. A
power cord at the rear of the tray allows the unit to be connected to a
standard 120V outlet. A wiring compartment isprovided at the rear ofthe tray
allowing the option to permanently wire the unit directly to a furnace control.
Air Flow Sensor (AFS)
Installed on certain models, this part controls the operation of the unit by
sensing the movement of air within the duct. This helps to reduce power
usage and prevents the possible buildup of ozone within the duct.
How to Identify Which Air Cleaner Model youown
The model number and serial number for your Electronic Air Cleaner can be
found on the data label located on the inside of the access door. This serial
number will be a ten (10) digit number.
3
Page 6
FACTS YOU SHOULD KNOW ABOUT YOUR NEW
ELECTRONIC AIR CLEANER
Dusting and "White Dust"
Your new Electronic Air Cleaner will efficiently clean and filter your household
air. Unfortunately, it will not eliminate the need for regular dusting of your
furniture and belongings. Due to the design of all duct-mounted air cleaners,
they can only clean the air that reaches the air cleaner. Therefore, if the
particulates are not being carried to the air cleaner in the air stream, the air
cleaner cannot remove them from your home.
Occasionally a "white dust" may be noticed in bedrooms or newly furnished
rooms. This is mainly composed of lint which, because it is heavier than other
particulates, settles before it reaches your unit.. This "white dust" is not mixed
with airborne dirt particles, therefore, it is clean and has no staining or soiling
properties. However, running the furnace blower continuously, day and night,
will help reduce this from occurring.
Ozone
Under normal operating conditions all Electronic Air Cleaners produce
minute quantities of ozone as an incidental by-product. In fact, all electronic
products, such as televisions, cordless phones and refrigerators, produce
some amount of ozone. The average homeowner can detect the smell of
ozone concentrations as low as 25 to 100 ppb (parts per billion). The design of
this unit has been tested and ozone production is approximately half of the
published permissible limits established by the Environmental Protection
Agency. These limits recommend that the concentration of indoor ozone not
exceed 50 ppb. Ozone is not harmful in these concentrations. In fact, the
ozone level in major cities can sometimes reach as high as 100 ppb on a
summer day. The addition of optional charcoal after-filters can help reduce
this.
Normally, a new unit will produce more ozone than one that has been in
operation for several weeks. This is due to sharp corners or manufacturing
burrs on the ionizing-collecting cell(s) and is normal. As the Electronic Air
Cleaner arcs and zaps, the voltage is vaporizing these areas and tends to
round them off. This is part of the breaking-in period of ownership and the
issue is self-correcting. Also, high-altitude locations can be more susceptible
to noticing the presence of ozone.
An ionizing-collecting cell that has been damaged or bent (the designed
spacing between electrically charged and ground components has been
decreased) may also produce an abnormal amount of ozone.
4
Page 7
How the Air Flow Sensor Works (available on specific models)
The electronic AFS was designed to provide an efficient and reliable method
of controlling the operation of the air cleaner when the dealer is unable to
wire the unit directly into the furnace blower. The electronic AFS utilizes a
thermistor that heats up to approximately 130°F. The AFS then stabilizes at
this temperature and when the furnace blowerturns on andair flows through
the ductwork, the same vacuum effect pulls cooler air over the hot surface.
This air movement cools down the thermistor and this cooling down effect
allows the electronic AFS to understandthat the furnace bloweris moving air
and the Electronic Air Cleaner must turn on to provide air cleaning.
If the air cleaner is installed in a location that is dusty and dirty, the sensor on
the AFS can become coated with dirt and lint. This coating can insulate the
AFS and keep it from operating properly. To clean the thermistor, take a
cotton swab dipped in rubbing alcohol and carefully insert it into the hole
located on the right hand side of the power pack assembly (when facing the
unit). The hole is 3/16 " in diameter and is located on the front of the power
tray assembly. Carefully twirl the cotton swab between your fingers, making
sure the tip is lightly in contact with the grey disc, cleaning this coating from
the thermistor.
AFS TROUBLESHOOTING
It is recommended that the following procedure only be performed
by an authorized HVAC contractor. Failure to do so may expose an
individual to personal injury
1. Make sure the furnace blower is not operating, the rocker switch
is OFF and the circuit breaker is turned OFF or cord is
disconnected.
2. Remove the access door.
3. Remove power tray assembly.
4. Locate the AFS. It is a circuit board with a small grey disc
connected to the circuit board by two(2) silver wires (similar to
Figure 1). Carefully bend the thermistor so that it is located in the
center of the opening and approximately 1/8" from the inside edge
of the power pack assembly.
5. Reinstall the power tray assembly and access door.
5
Page 8
High Altitude Operation
Because the air is less dense at higher altitudes, there is a possibility of
nuisance arcing. The homeowner can quickly and easily correct this
condition.
1. Turn the unit OFF. Disconnect cordor turn off circuit breaker.
2. Remove the two screws that secure the cover to the power tray and
remove it from the unit. (The entire power supply tray may be removed
from the cabinet by removing two screws from inside the cabinet.) Do
not lose these screws.
3. Locate the jumper terminal (see figure 2).
4. With a pair of needle nose pliers, carefully adjust the jumper settings
from HIGH to MED. Ensure that the jumper is firmly seated in the
terminal.
5. Replace the power tray cover and secure it withthe two screws.
6. Replace the access door and turn the unit ON.
This procedure will slightly reduce the output voltage, minimize arcing and
reduce ozone production. If the condition does not improve, repeat the
above procedure and move the jumper setting from MED to LOW. If this
does not correct the situation, contact your local HVAC dealer.
All Electronic Air Cleaners are produced atthe factory with the jumpersset in
the HIGH position. However, the output voltage may be lowered in any
situation where the unit is arcing excessively or there is excessive ozone
production.
6
Page 9
REPLACING THE IONIZING WIRES
Ionizing wire breakage is minimal because of the constant tension design
and fixed location of the ionizing wire supports. When an ionizing wire
breaks, the efficiency of the Electronic Air Cleaner will decrease slightly.
However, the unit will continue to operate with broken ionizing wires as long
as the broken wires have not caused a short circuit of the unit. Remove all
loose and broken wires as soon as they are identified.
Although the replacement of the ionizing wires can be attempted by a
homeowner, it is recommended that a qualified HVAC contractor be
contacted for replacement parts and/or servicing. Wires are supplied in a
coiled spring configuration, with a clinch nut on each end of the wire.
Replacement requires a pair of needle nose pliers. Exercise caution in
removing any broken wires in the collector cell. This will prevent accidental
shorting of the cell and reduce the need for further maintenance.
Use the following procedure when replacing an ionizing wire.
1. Ensure that all power to the Electronic Air Cleaner is OFF, remove the
access door and remove the ionizing-collector cells from the unit.
2. Carefully remove all remainsof the broken wire.
3. Grip the new wire at each end of the wire with your thumb and index
finger. While stretching the wire to approximately 6" allow one end of
the wire to uncoil between your thumb and index finger.
4. Place one end of the wire in the slot of the stainless steel support on
the collector cell from the front of the cell. This support is partially
covered by the cell brace in front of the support.
5. Grip the other end of the ionizing wire with needle nose pliers and
insert the terminated end of the wire into the slot on the support bar of
the opposite end of the collector cell.
6. The wire should be tight enough to be self supporting and remain
suspended between the two support slots in the support bar.
7
Page 10
Common Questions and Answers
Q. Why isn't my air cleaner cleaning my air?
A. The air cleaner is most likely working just like it was designed.
However, manyfactors can affect the performance of the unit. Are cold air
registers located in the ceiling? If so, it will be difficult for the air flow to
carry heavier particulates to the air cleaner. Ifthe dirt doesn't get to the air
cleaner, it can't be removed from the air. Are both the Red and Green lights
illuminated? If not, then the unit may be in need of servicing. Contact your
local HVAC dealer for assistance.
Q. It still isn't cleaning my air the way I want it to. What can I do?
A. We recommend that you run the blower continuously so that the air
movement will carry the dirt to the air cleaner. Unfortunately, there will
always be some dirt that is left behind on the appliances, furniture, etc.
Regular dusting is recommended to stir up these pockets of dust so that
they can enter the airstream and be removed by the Electronic Air Cleaner.
Q. When I turn on my Electronic Air Cleaner, the lights come on for a couple
of seconds and then turn off. The air cleanerisn't working!
A. The air cleaner is fine as long as both the Red and Green lights are
coming on. Try turning the HVAC blower OFF and then turning the
Electronic Air Cleaner on. This should solve the problem.
Q. What is the zapping noise I'm hearing from my unit? Should I be
concerned?
A. The zapping or popping noise that you are hearing is the sound of larger
particles being "vaporized" by the ionizing-collector cell. This is normal
and is no cause for alarm. As your HVAC system blower moves the air
through the ductwork and allows the Electronic Air Cleaner to clean the
air, the noise will diminish. However, there will always be instances when
larger particles enter the ionizing-collector cell.
Q. Should I hear this zapping noise all the time?
A. All Electronic Air Cleaners will occasionally zap or pop as larger particles
pass through the ionizing-collector cells. However, if the sound is
constant or is repetitive in nature, then a large particle may have become
lodged in the ionizing-collector cells and they may require cleaning. If
cleaning the ionizing-collector cells does not stop the noise and there
are no large particles trapped in the ionizing-collector cells, then the
cause could be a broken/loose ionizing wire, bent collector plate or
other mechanical reason. Please contact your local HVAC dealer for
assistance.
8
Page 11
Q. What if I no longer hear any popping or zapping noises coming from
my unit? Is it still cleaning the air?
A. If the zapping noises stop and the air cleaner is not in need of
servicing, then one of two situations has occurred. First, the Electronic
Air Cleaner has successfully removed all larger particles from the air
and is cleaning microscopic particles which do not cause the zapping
noise. Second, the blower and/or HVAC system is not running and air
is not flowing through the ductwork. The Electronic Air Cleaner cannot
remove particles if the air stream is not moving.
Q. I lost power to my home during a storm. Should I worry about the
Electronic Air Cleaner?
A. The most common problem associated with power outages is the unit
will not turn on properly after power is restored. If the Red and Green
light come on for a couple of seconds and then go off, the unit is
OK. Just turn the HVAC blower off, turn the unit ON and then turn the
blower back on. If the Red and/or Green light does NOT come on
after a storm, the power supply in the Electronic Air Cleaner may be
short circuited. Contact a local HVAC contractor for further
information.
Q. My installer told me to keep my HVAC system blower running all the
time, but I don't want to increase my power bill. What should I do?
A. It is recommended that you keep your HVAC system blower running
all the time to achieve the maximum air cleaning efficiency. This will
allow the Electronic Air Cleaner to do what it is designed to do, which
is clean the air. Remember that if the air does not reach the air cleaner,
it cannot be cleaned. On average, your Electronic Air Cleaner will use
the same amount of electricity as a 55W light bulb. The energy usage
of the HVAC system blower will depend on the age of your system ,
energy costs in your regional location and other variables. The best
solution is to try running the HVAC system blower in continuous mode
for a month or two to estimate your annual energy costs and base
your final decision on what you feel most comfortable with.
9
Page 12
MAINTENANCE OF YOUR ELECTRONIC AIR CLEANER
WARNING :Handle ionizing-collector cells with care as plates
can be sharp and cause injury if nothandled properly.
WASHING CELLS ANDPREFILTERS
Regular washing is necessary to ensure proper performance. A thorough
washing once every two months will be adequate for most installations.
More frequent washing (once a month) may be necessary on some
installations (new homes for example) where there is new carpeting, plaster
dust, or excessive cigarette smoke (Figure 3).
To remove cells and prefilter
1. Push air cleaner switch to the OFF position. Wait 15 seconds. Open door
access panel.
2. Carefully remove cells and prefilter(s) and setaside in a safe place.
3. Do not drop the ionizing-collector cell. This could cause damage to the
cell plates or ionizing wires and cause excessive arcing and noise.
10
Page 13
To wash cells and prefilter(s)
We suggest that you follow the instructions below to properly and
thoroughly clean your collector cells.
1. Place enough hot water in a utility tub to cover the first cell. Dissolve 2
to 4 oz. of granulated automatic dishwasher detergent (not laundry
detergent) in the water.
2. Allow the cell to soak for 30 minutes. Agitate it up and down in the
solution until it appears clean and remove.
3. Repeat with second cell.
4. Agitate the prefilters up and down in the solution until they appear
clean.
5. With a hose, rinse the cells and prefilters. The hose should be held
about 10" from the cell plates and at a slight angle for better cleaning
results. Be careful not to spray the ionizing wires directly with the
hose. The water pressure can cause the wire to snap and break. The
cell frame should be thoroughly rinsed along the edges to dislodge
any trapped lint or dirt. Carefully wipe a damp cloth or sandpaper (not
emery cloth) along the ionizing wires.
6. Stand cells and prefilters up to drain. Let dry two hours. You may
experience a slight discoloration of the aluminum collector cells after
washing. This is a normal chemical reaction and will not harm your
unit or affect its performance.
To replace cells in air cleaner
1. Replace prefilter and cells in cabinet. Check that arrow on cells points
in same direction as air flows through the duct. (If you have to force it
past the positioning screw on bottom, it is probably in the wrong
position.)
2. Replace access door (engage tabs on lower edge of door into slots in
cabinet). Carefully close door.
3. Turn air cleaner switch to ON.
11
Page 14
COMMON TROUBLESHOOTING TECHNIQUES
SYMPTOMPOSSIBLE CAUSESCORRECTIVE ACTION
Broken or loose ionizing wire(s)Remove broken or loose wire and
Dirty ionizing-collector cellClean as outlined on page 10-11
Rapid arcing or zapping
Damaged or bent collector platesStraighten plates with needlenose
Excessive ozone smell
Dirty insulator caps on ionizing-Clean with warm soapy water and
collector cellrinse well
Air cleaner is wired directly to aQualified HVAC contractor must
120V power sourceinstall AFS or rewire air cleaner
Excessive ozone smellLoose high voltage connectionsRepair or replace the component
Radio or television interferenceUncommon occurance --
Hissing or sizzling noisePoor electrical contactEnsure that there is a good
No power availableReset circuit breaker
Loose wiring at ON/OFF switchCheck for secure connection
Green LED light is not ON
Defective ON/OFF switchReplace ON/OFF switch
ON/OFF switch not in ON positionTurn the unit ON
Loose wiring within power packCheck for secure connections
assemblyContact HVAC contractor
Broken or shorted electricalContact HVAC contractor
component
Excessive dirt build up on ionizingClean wires with alcohol and
wiresallow to dry thoroughly before
Contact board assemblies areReplace contact board assembly
corroded or carbonized
Red LED light is not ONBroken ionizing wireRemove broken wire and replace
Dirty ionizing-collector cellClean as outlined on page 10-11
Foreign object located betweenRemove object from ionizingcollector platescollector cell
Damaged or bent collector platesStraighten with a pair of needle-
Insulators are corroded orReplace insulators or ionizingcarbonizedcollector cell
replace with new wire
pliers or replace entire ionizingcollector cell.
To the HVAC system blower
check for good common ground
for air cleaner
connection between the top of
the ionizing-collector cell and the
bottom of the contact board
assembly
Contact HVAC contractor
Dimensions are the same for both models with and without Air Flow Sensors installed
ABCD EFG
Inches MMInches MMInches MMInches MM Inches MMInchesMM Inches MM
13
Page 16
WARNING
Onlyatrained,experiencedserviceman
shouldinstallthiselectronicaircleaner.
A thorough checkout of the unit installation
shouldbecompletedbeforeunit
operation.Electricalshockcancause
serious injury or death.
14
Page 17
TECHNICAL SPECIFICATIONS
(Specifications subject to change without notice.)
MODEL NUMBER-EACA001400202020
DIMENSIONS (IN)20 1/4 x 7 1/8 x 24 7/8 24 1/4 x 7 1/8 x 24 7/824 1/4 x 7 1/8 x 21 3/8
UNIT COLORAmerican SterlingAmerican SterlingAmerican Sterling
Installationbeneathfurnace.Cleaner
mounts horizontally, where return air
mountshorizontally,wherereturnair
enters from below. Raise furnace by
entersfrombelow.Raisefurnaceby
installing a suitable wood structure and
installingasuitablewoodstructureand
install air cleaner.
installaircleaner.
HORIZONTAL FURNACE
Mounted vertically in return duct as close to
the furnace as possible
16
Page 19
PLANNING THE INSTALLATION
Application
The air cleaners are used in forced air heating cooling and ventilating systems. The
air cleaner should be installed in the system so that all the system air is circulated
through the air cleaner. The air cleaner will only remove the airborne contaminants
delivered to it. Maximum performance is obtainedwhen the system blower isset for
continuous operation.
Installation Requirements
The best location for the air cleaner is in the return air duct next to the blower
compartment. In thislocation, the blowermotor and coolingcoils will bekept clean.
DO NOT INSTALL THE AIR CLEANER
IN THE DISCHARGE AIR DUCT.
Before installing the air cleaner, consider the application and type of HVAC system
present. Refer tothe section entitled
Typical MountingPositions,
for the most common types. If a transition between the ductwork and air cleaner is
required, refer to section entitled. The unit must be readily accessible
Transitions
for periodic inspection and cleaning of the prefilters and electronic cells to maintain
maximum efficiency andtrouble-free operation.
Air Conditioning
The air cleaner should be installed upstream of the cooling coil. This will keep the
coil clean and reduce air conditioning coil maintenance. Improved cooling
efficiency is the result and directly affects energy costs. A clean coil, will reduce
utility costs. If the air cleaner is downstream of the cooling coil, condensation will
form on the cooled collector plates when the air conditioner cycles. This will allow
water droplets to form on the collector plates and cause nuisance arcing. Arcing will
reduce air cleanerefficiency and reducethe life ofthe high voltagepower supply.
Humidifiers
An evaporative humidifier can be mounted upstream of the air cleaner. It is best to
install an atomizing humidifier downstream of the air cleaner because hard water
salt deposits and water droplets may damage the air cleaner. If an atomizing
humidifier must bemounted upstream ofthe air cleaner:
1. Mount it as far upstream aspossible. (Recommended atleast 6 feet.)
2. Install a standard disposable furnace filter between the humidifier and
the air cleanerto trap waterdroplets and hardwater salts.
3. Clean the air cleaner more frequently to prevent a hard water salt
buildup.
Outdoor Air
When outdoor air is added to the return air duct, sufficient heat should be added to
maintain the returnair temperature at 40°F (4°C) minimum. Lower temperatures can
cause ionizer wirefailure.
17
Page 20
Atomizing Humidifiers
If an atomizing humidifier is installed, it must be mounted downstream of
the air cleaner.
1. Mount the humidifieras far downstream as possible. Itis recommended a
distance of at least 10 feet to reduce the possibility of excessive arcing
as water droplets pass through the Electronic Air Cleaner.
2. Install a standard disposable furnace filter between the humidifier and
the air cleaner to trap water droplets and hard water deposits.
3. Clean the air cleanermore frequently to prevent a hard water buildup.
Sheet Metal Installation
The Electronic Air Cleaner is adaptable to all new or existing residential
forced air furnace and cooling systems.
Transitions
If the air duct does not fit the aircleaner cabinet opening, gradual transitions
are recommended to reduce air turbulence through the air cleaner and
maximize efficiency. Not more than 20°
(about 4" per running foot) of expansion
should be used on each side of the
AIR FLOW
transition fitting (Figure 4).
Outdoor Air
When outdoor air is added tothe return air
duct, sufficient heat should be added to
maintain the return air temperature at40°F
(4°C) minimum. Lower temperatures can
cause ionizer wire failure.
Turning Vanes
If the air cleaner is installed adjacent to a
90° duct elbow, add turning vanes inside
the duct to improve air distribution across
the face of the air cleaner (Figure 5).
Failure to follow the recommendation can
reduce the efficiency of the Electronic Air
Cleaner.
18
AIR FLOW
AIR CLEANER
OPENING
AIR CLEANER
TRANSITION SECTION
OPENING
FURNACE
FURNACE
Page 21
SELECT LOCATION FOR AIR CLEANER
Remember to select a location that is readily accessible for periodic
inspection and cleaning of this air cleaner. Allow a minimum of 24"
clearance in front and 12" clearance above the air cleaner for component
removal and service space. For complete dimensions required refer to the
section entitled
UNIT DIMENSIONS.
DIRECTION OF AIR FLOW THROUGH THE AIR CLEANER
This air cleaner is set up for left to right air flow when you are facing the
access door.
For right to left airflow,follow these directions:
1. Remove the prefilter(s) and cells from the
cabinet. A plastic positioning spacer is
located inside the bottom of the cabinet.
This spacer is secured to the cabinet using
a #6-32 round head Phillips drive thread
cutting screw to assure installation of the
cells in the proper position with respect
to air flow (Figure 6).
2. Remove the screw and reposition the
spacer in the alternate hole at the bottom of
the cabinet.
3. Replace the screw to insure the plastic spacer is not accidentally
knocked out of place during normal maintenance. It must be installed in
the hole provided closest to the air leaving side of the cabinet. Seal the
unused hole with duct tape.
4. Remove the cell handle and reattach to the opposite end of the cell. Turn
cells around, replace in cabinet and replace prefilters on the air
entering side. The directional arrows on the cell end plates must point in
the direction of air flow.
19
Page 22
INSTALLATION
CAUTION: Only a trained, experienced serviceman should
install this electronic air cleaner. The power supply should be
removed before installation. To remove the power supply, remove
the two (2) screws (See Figure 7) in the top front of the cabinet.
Remember to keep this hardware for reinstallation of the power
supply when the air cleaner installation is complete. A thorough
checkout of the unit installation should be completed before unit
operation.
PHYSICAL INSTALLATIONOF THE AIR CLEANER
This Electronic Air Cleaner can be installed in any position, except with the
access door facing down. The section entitled
POSITIONS
show examples of proper air cleaner mounting with a variety of
TYPICAL MOUNTING
furnace installations.
Prior to installing this product...
1. Read rules and instructions carefully for safe operation. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given on the product to make sure it is suitable for your
application.
3. Select a locationfor the air cleaner.
4. Remove the oldfurnace filter and discard.
5. The air cleanercannot remove existing dirt from the blower and ducts.
Clean the area thoroughly before you begin.
6. Remove unit access panel, and slide theprefilters and ionizing-collecting
cells out of the cabinet. Place them safely aside with the warranty and
registration card.
NOTE:
The following is a typical installation of the air cleaner on a
highboy furnace. You may have to alter the installation to fit your
particular application.
20
Page 23
7. Locate the cabinet in the cold air return duct so that all of the return air
flows through the unit (Figure 6). If the furnace and air cleaner openings
are different, use a transition (Figure 4).
8. Mounting holes are provided for
ductwork attachment (Figure 7). The
.140" holes are sized for #8 sheet
metal screws, or 1/8" rivets. If the
adjoining ductwork is flanged, install
the screws so that the screw heads
are inside the cabinet. This will prevent
damage to the prefilters and
optional charcoal after-filter during
removal and installation after
cleaning.
9. After the unit has been secured, seal
seams air tight with duct tape or
caulking.
ATTENTION:
On Electronic Air Cleaners that have the air flow sensor
installed at the factory, be especially careful not to cover the air flow
sensor orifice when sealing the air cleaner and ductwork. This hole is
located on the right hand side of the enclosure that holds the power
pack assembly (when facing the unit). The hole is 3/16" in diameter and
is located on the front of the power tray assembly. In applications with
minimum air flow, it is helpful to seal any openings on the power tray
assembly or cabinet. This will increase the velocity of air flowing over the
air flow sensor, enabling the air flow sensor to turn the Electronic Air
Cleaner on and off. The only opening required for actuation of the
air flow sensor is the 3/16" diameter hole previously described.
10. Refer to the section entitled
DIRECTION OF AIR FLOW.
11. Install prefilters and ionizer-collector cells.
12. Reinstall power tray assembly into the cabinet.
13. Reinstall unit access panel.
21
Page 24
ELECTRICAL INSTALLATION
All wiring must comply with applicable local and national codes.
CAUTION:
Be sure all incoming power is OFF before beginning any procedures.
CAUTION:
The following instructionsare for use byqualified personnel only.
The following procedures will expose hazardous live parts. Disconnect power between checks and
WARNING:
proceed carefully.Electrical shock can causeinjury or death.
The Electronic Air Cleaner (without the AFS installed at the factory) is designed to take advantage of the integrated
accessory control panel available on most furnaces. The 120V Electronic Air Cleaner tap on the furnace will provide
power to the aircleaner only when the circulating air blower is inoperation.
Read the instructions in the furnace installation manual carefully before attempting installation or operation. Failure to
follow these instructions mayresult in improper installation and therefore void warranty.
An optional(on 120v model) electronic air flow sensor kit isavailable if the air cleaner is not equipped with an AFS. This
air flow sensor willsense the air movement within the duct and turnthe Electronic Air Cleaner on and off accordingly.
CAUTION
CAUTION
Figure 8
WIRING PROCEDURE
This air cleaner is powered by providing power to pigtail
leads at field wiring compartment (see knock-out holes)
located at the rear of the power pack assembly (See Fig.
8).
1. Turn air cleaner OFF using ON/OFF switch located on
front panel.
2. Remove power pack cover plate by removing front
door and two screws holding assembly to the top of
the air cleaner.
3. Make wiring connections inside junction box area
(See Fig. 8). Remove knock-out and use conduit or
other approved methods to supply input power.
Connect ground wire toclip.
4. Replace thepower supply cover plate andsecure with
screws removed from step2.
5. Replace the unit doorto thefront of the air cleaner.
6. Air cleaner will now operate when door is in place,
ON/OFF rocker switch is in the ON position and input
voltage is present in the junction box. The following
should be completed to supply input power to the air
cleaner.
FURNACE APPLICATION
It is recommended to use EAC 1 and EAC 2 terminals
when provided by the furnace circuit board. These
outputs will provide 120 vac whenever the blower motor
is energized.
Furnace circuit boards without EAC 1 and EAC 2
terminals MUST use alternate methods to supply to
supply power to the air cleaner. Options include Sail
Switch ,Isolation relay or OptionalAFS (Air FlowSensor).
Air cleaner should only operate when blower motor is
running.
This unit cannot be powered directly from blower motor
leads. Voltages can exceed 190vac for 120-v. motors or
possibly double with 240-v. fancoil motors.
FAN COIL APPLICATIONof 0014 or 0020 Models (120-v.)
If EAC 1 and EAC 2 terminals are provided by fan coil
board, refer to fan coil data to determine voltage
circuit
output. Most fan coils do not provide 120-v. at these
terminals. Alternate methods may be needed to convert
fan coil supply voltage to 120-v. for the cleaner. A 240-v. to
120-v step downtransformer(60 v.)will be needed inmost
applications. Sail Switch, Isolation relay or Optional AFS
(Air Flow Sensor) mayalso be needed.
FAN COIL APPLICATION of 2020 Model (240-v.)
The Model 2020 isa 240-v. power supplymodel designed
to matchyou fan coil.To install this model with a 240-v. fan
coil:
This unit cannot bepowered directly from blower motor
leads. Back EMF (electro magnetic field) voltages can
reach 400 vac for240-v. fan coil motors.
1. Turn air cleaner OFF using ON/OFF rocker switch
located on front panel.
2. Remove power pack cover plate by removing front
door andtwo screws holding assembly to the topof the
air cleaner.
3. Make wiring connections inside junction box area (See
Fig. 8). Remove knock-out and use conduit or other
approved methods to supply input power. Connect
ground wire to clip.
4. Replace the power supply cover plate and secure with
screws removed from step2.
5. Replace the unitdoor to the front of the air cleaner.
6. Air cleaner will now operate when door in place,
ON/OFF rocker switch is in the ON position and input
voltage is present inthe junction box.
22
Page 25
SYSTEM CHECKOUT
WARNING: The following procedures should be conducted by a
qualified HVAC contractor or repair person ONLY. These procedures
will expose hazardous electrically energized charged components.
Disconnect power between checks and proceed carefully.
1. The HVAC system blower should be turned OFF.
2. Switch the ON/OFF rocker switch to the ON position. The bright red
segment of the rocker switch should be visible.
3. Inspect both the Green INPUT POWER light and the Red CELL
ENERGIZED light:
• If the unit has an AFS installed, the lights should go out in
approximately 20 to 60 seconds. This is the normal time for the
electronic air flow sensor to complete its stabilization period. Both
lights will come back on when the HVAC system blower begins to
operate. See the section entitled
WORKS
for more information
HOW THE AIR FLOW SENSOR
• If the unit iswired directly to the HVAC system blower, the lights will not
come on until the blower begins to operate. In this case, the electronic
air cleaner will stay on as long as the ON/OFF switch is in the ON
position and the blower is operating.
• If the unitis wired directly to a dedicated 120V power source, the lights
will come on immediately and stay on for as long as the ON/OFF
switch is in the ON position, regardless of the HVAC system blower
operation. This type of installation is NOT recommended due to the
excessive production of ozone. See the section entitled
FACTS YOU
SHOULD KNOW ABOUT YOUR ELECTRONIC AIR CLEANER OZONE
for more information.
4. Wait approximately one (1) minute and turn the HVAC system blower
ON. Most thermostats have a setting that will allow you to run the fan
manually. If not, then set the thermostat so that either hot or cold air
begins to flow through the ductwork.
5. The Green INPUT POWER light and Red CELL ENERGIZED light should
come on, if the unit is wired directly to a dedicated 120V power source,
the lights will already be on and will not be affected by the HVAC system
blower operation (see Step 3).
6. Check to make sure that the Red CELL ENERGIZED light goes out when
the following conditions occur:
• Cell access panel is removed
• Rocker switch is switched to the OFF position
• HVAC system blower is not running.
23
Page 26
TROUBLESHOOTING
CAUTION:
• These procedures should only be attempted by a qualifiedHVAC
technician or electrician.
• Risk of personal injury could occur by attempting to troubleshoot or
repair this unit by untrained persons.
• Exercise the usual precautions when working with high voltage.
• When the circuit has been de-energized, always discharge any
residual current in the secondary with an insulated handle
screwdriver.
• Always ground power supply and ionizing-collecting cell when
bench testing.
Recommended Service Tools
• Screwdriver, 8" common with insulated handle (plastic)
• ScrewdriversPhillips #1 and #2 with plastic insulated handles
• Needlenose pliers
• Multimeter
• Highvoltage probe
Indication of Electrical Trouble
The air cleaner is equipped with a Red CELL ENERGIZED light for indicating
proper unit operation. When the unit is in normal operation (with the HVAC
system fan running, access door in place and rocker switch in the ON
position) and the Red CELL ENERGIZED light is not lit, the problem is a
shorted secondary. Although failure of the indicating light itself should not
be overlooked, this condition is unusual and rather remote.
24
Page 27
PRIMARY CIRCUIT WITH FURNACE BLOWER OPERATING
If there is supply line voltage at the connections and no input voltage to the
power supply, the outage can be located by checking operation of the
safety switch and the interconnecting wiring with a multimeter. Refer to
Circuit Diagram, (Figure 9) to check operation of the switches.
Following these steps to test for proper operation of the circuit board and
power supply assembly:
1. Ensure that the circuit breaker controlling the furnace blower is in the ON
position and the main fuse is not open.
2. The power supply board has a built-in internal fuse to protect the 24V
transformer. It can be checked visually by inspecting the fuse. If the fine
wire inside the fuse is broken, this indicates a problemin the 24V circuit of
the power supply board. Do NOT replace this fuse. The entire power
supply board must be replaced. The purpose of the fuse is not to protect
the power supply board, but to function as a troubleshooting feature of
the product and to protect the transformer from damage.
3. If the fuse is NOT blown, check the ON/OFF switches and safety interlock
switch for proper engagement and operation. This can be completed
using a volt ohm millimeter on a scale that will measure ohms as low as
1.0. If you are using the recommended meter previously mentioned in
this manual, set the meter to read 200 ohm and proceed with Steps 4
through 6.
4. Remove the fuse. Connect one lead to the test pin located directly beside
the wire that connects the ON/OFF switch to the power supply board.
Connect the other lead to the fuse connection closest to the front panel.
5. Turn the ON/OFF switch to the ON position and depress the safety
interlock switch. The meter should have the capability of reading levels
as low as 1.0 ohm.
6. If there is no reading on the meter, begin the process of elimination by
disconnecting the wire from the test point and connecting it to the
terminal with the blue wire located on the safetyinterlock switch. Depress
the safety interlock switch. If the reading on the meter is greater than 1.0
ohm, the safety interlock switch is defective and must be replaced. If the
reading on the meter is less than 1.0ohm, the ON/OFF switch is defective
and must be replaced.
25
27
Page 28
SECONDARY CIRCUIT
IONIZING-COLLECTING CELL
The cell is electrically energized througha contact terminal locatedat the top center
of the cell. The ionizing wires and alternating collector plates are electrically
charged while theinterleaving plates aregrounded.
If the space between the charged and grounded plates is bridged with conductive
or semi-conductive material, a short circuit develops. The bridging or short may be
caused by damaged plates, or foreign material lodged between/on the
components. Since the cell should be periodically removed from the unit to wash
away collected dirt, it is susceptible to physical damage. The cell also contains the
ionizing wires which, due to their function, have been designed with minimal
structural support and are susceptible to breakage. However, trouble related to a
shorted collector cell is readily shown by the Red CELL ENERGIZED light and can
be quickly isolatedby a simpleprocedure.
To determine if a short exists in one or both of the collector cells, turn the Electronic
Air Cleaner OFF and remove both electronic cells from the cabinet. Shut the door
and repower the unit. If the Red CELL ENERGIZED light comes on, an electrical
short exists in one or both of the electronic cells. Replace the cells in the unit, one at
a time, todetermine which cellis shorted.
The ionizer collector cells are not designed for field repair. Ionizing wires and
insulators can be field replaced. It is not recommended that you attempt to replace
other cell components(i.e. Collector plates,end plates, ionizersupports).
EACA-0014 & 0020
120V
Figure 9A
EACA-2020
240V
Figure 9B
26
Page 29
CHECKING THE POWER SUPPLY
If the output light remains out with the collector cells removed from the
cabinet, the power supply is defective. Specific problems on the power tray
assembly can be isolated by using a multimeter and high voltage probe to
check the output voltages.
To check the secondary circuit, a high voltage meter is required. See the
section entitled RECOMMENDED SERVICE TOOLS. To check for proper
operation, it is imperative that the procedure be followed as outlined below:
1. Make sure the furnace blower is operating, the control switch is on and
input voltage is 120 volts, 60 Hz.
2. Remove front door assembly panel.
3. Remove power pack access cover.
4. Check the highvoltage contact board assembly(s)for damage or carbon
tracking.
NOTE:
The cell contacts should be visually checked for corrosion,
excessive dirt build up, and electrical arc tracking (Carbon path from
stainless steel spring to grounded metal). Clean or replace as required.
5. Make connections from the high voltage probe to the multimeter in
accordance with the operator's manual. The meter should be set for
reading DC voltage on the 20 volt full scale.
6. Attach the high voltage probe ground lead to the cabinet. While
depressing the safety switch lever, touch the ionizer wire support bar
with end of the high voltage probe (Figure 10). The meter reading should
be 6.2 kVDC ± .2 kVDC.
7. If no voltage is measured, remove the first cell andcheck the second cell.
The meter should read 6.2 kVDC ± .2 kVDC.
8. If proper voltage is measured, the first cell is shorted. Refer to Table 1, on
page 12.
27
Page 30
9. If no voltage is present, remove the second cell. Install cell number one
and measure voltage as described above. If voltage is present, the
second cell, which is now out of the cabinet, is shorted. Refer to Table 1
on page 12.
10. If no voltage is present, remove both cells and measure the power
supply output. While depressing the safety switch, touch the end of the
high voltage probe to either the front or rear contact board assembly
(Figure 10). The meter should read 6.2 kVDC or higher.
11. If no voltage is present, check the power supply. Set the multimeter for
reading AC voltage at 200 volt full scale and attach meter test leads.
12. While depressing the safety lever, touch the two transformer output lead
junctions to the power supply board with the meter leads and read the
meter.
13. If there is no output voltage from 24 volt transformer, replace the 24 volt
transformer and power supply board.
28
Page 31
TROUBLE SHOOTING THE DUCT MOUNT ELECTRONIC AIR CLEANER
No
Is the unit operating?Is the furnace blower on?
Is input AC power available?
Is the safety interlock system OK?
Yes
Is ON/OFF switch working?
No
Is red light on?Is cell dirty or defective?
Are contact boards OK?
YesIs the power supply wiring OK?
Yes
No
Yes
No
Yes
No
Yes
Yes
No
No
Yes
No
Is cell crackling and snapping?
NO
Is cell sizzling?Yes
Yes
Yes
Is power supply defective?
No
Yes
Is transformer defective?
Yes
29
Page 32
WARNING:
The following steps will expose hazardous live parts. Disconnect power between checks
and proceed carefully.
1. Replace any blown fuses and resetany tripped breakers.
2. Repair or replace any loose wiresor bad connections.
3. Inspect AFS for proper location andoperation.
1. Check that the access door isnot open or ajar.
2. Repair or replace any loose wiresor bad connections.
3. Replace defective momentary contact switch.
4. Inspect AFS for proper location andoperation.
1. Ensure that ON/OFF switch is turnedON.
2. Repair or replace any loose wiresor bad connections.
3. Replace defective ON/OFF switch.
4. Inspect AFS for proper location andoperation.
1. Remove any objects between adjacent collectorplates.
2. Replace corroded or carbonized insulators.
3. Replace any broken ionizing wires.
4. Wash dirtycells..
1. Replace contact board if contacts arecorroded and carbonized.
2. Replace any defective wires.
3. Withalcohol, clean dirt build-uponcontacts and let drythoroughly.
1. Repair or replace any loose wiresor bad connections.
1. Replace defective high frequency power supply.
1. Replace power supply.
2. Replace transformer.
1. Wash dirtycell, including any powder build-upon ionizing wires.
2. Straighten any bent plates.
3. Replace any broken or loose ionizingwires.
1. Ensure good contact between cell andcontact boards.
Replace defective contactboards..
30
Repeat these
steps until all
problems are
eliminated
Page 33
EACA
31
Page 34
EACA PARTS LIST
REF. DESCRIPTION NO..
1. Power Tray Assembly (W/ AFS) 120V
1A. Power Tray Assembly (W/ AFS) 240V
1B. Power Tray Assembly (W/O AFS)120V
2. High Frequency Power Supply
3. Electronic Air Flow Sensor (Optional)
4. ON/OFF Switch
5. Interlock Switch
6. Cabinet Assembly
7. Pre-Filter (2/ package)
8. Cell, Ionizing-Collecting
9. Ionizing Wire Assembly
10 Front Panel Assembly
11. Contact Board Assembly
12. Charcoal Filter
13. Stepdown Transformer 120V to 24V (0014 & 0020)
13A. Stepdown Transformer 240V to 24V(2020)
(optional, not shown)(2/ package)
14. Insulator (6/ package)
15. Cell Key (not shown)
16. Power Tray Cover
(Full Set / package)
(2/ package)
OWNER RESPONSIBILITIES
The completion and return of the Warranty Registration Card is a condition precedent
to warranty coverage and performance. This warranty is not valid unless the warranty
card is completed and mailed to the factory within fifteen (15) days of equipment
installation.
32
Page 35
Warranty
Two-Year Limited Warranty
workmanship. If Defect appears within Two yearsfrom the dateof original installation, whether or not actual
use begins on that date, product is warranted. If product installation criteria meets this standard, a new or
remanufactured part, at the manufacturer’s sole option, to replace any defective part will be provided
without charge for the part itself; PROVIDED the defective part is returned to the distributor through a
qualified servicing dealer.
Five-Year Limited Warranty on Power Supply
material and workmanship. If Defect appears within Five years from the date oforiginal installation, whether
or not actual use begins on that date, product is warranted. If product installation criteria meets this
standard, anew or remanufactured part, at the manufacturer’s sole option, to replace anydefective part will
be provided without charge for the part itself; PROVIDED the defective part is returned to the distributor
through a qualifiedservicing dealer.
Limited Labor Allowance - If service call on this unit must be made in the first 120 days from original date of
installation a $25.00 (USD) labor allowance will be given. If Power Supply must be replaces in the first five
years after originalinstallation date a $50.00 (USD) laborallowancewill be given.
THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS-OTHER THAN THAT SPECIFIED
ABOVE incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling of either
defective parts or replacement parts. Such costs may be covered by a separate warranty provided by the
installer.
THIS WARRANTY APPLIES ONLY TO PRODUCTS IN THEIR ORIGINAL INSTALLATION LOCATION AND
BECOMES VOID UPONREINSTALLATION.
LIMITATIONS OF WARRANTIES – ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE ANDMERCHANTABILITY) ARE HEREBY LIMITED IN DURATION
TO THE PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW
LIMITATIONSON HOW LONG AN IMPLIEDWARRANTY LASTS, SO THEABOVE MAY NOT APPLYTO YOU.
THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE
ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON
WHATSOEVER.
- This Product is warranted to be free from defects in material and
- This Power Supply is warranted to be free from defects in
ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL
WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR REMANUFACTURED, ASSUME AS
THEIR WARRANTY PERIOD ONLY THEREMAINING TIME PERIOD OF THIS WARRANTY.
1. Normal maintenance as outlinedin the installation andservicing instructions or ownersmanualincluding
filter cleaning and/orreplacement and lubrication.
2. Damage or repairs required as a consequence of faulty installation, misapplication, abuse, improper
servicing, unauthorized alterationor improper operation.
3. Failure to startdue to voltage conditions, blownfuses, open circuit breakers or other damages dueto the
inadequacy or interruptionof electrical service.
4. Damage as a result of floods, winds, fires, lightning, accidents, corrosive environments or other
conditions beyond thecontrol of the Manufacturer.
5. Partsnot supplied or designatedby the Manufacturer, or damagesresultingfrom their use.
7. Electricity or fuel costs or increases in electricity or fuel costs from any reason whatsoever including
additional or unusualuse of supplemental electric heat.
8. ANY SPECIAL INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE OF ANY
NATURE WHATSOEVER. Some states do not allow the exclusion of incidental or consequential
damages, so theabove may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights which may vary from state
to state.
Part Number 155587-005 • 7/02
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR:
Page 36
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.