SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardousdue to system pressure and electrical com­ponents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, ob­serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire ex­tinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
GENERAL
This installation instructioncovers accessory electric heater package numbers CRHEATER136A00,CRHEATER137A00, CRHEATER138A00, CRHEATER139A00, CRHEATER­140A00, CRHEATER141A00, CRHEATER142A00, and CRHEATER143A00. See Table 1 for kit contents. See Tables 2-4 for unit electrical data and kit usage.
NOTE: All units with electric heat require a field-supplied 90-degree elbow. The elbow must be installed in the supply ductwork below the unit discharge connection.
NOTE: Accessory heater package numbers CRHEATER142A00 and CRHEATER143A00 require an accessory electric heat box. Contact your distributor for more details.
Table 1 — Package Contents
QUANTITY ITEM
1 Heater Module 1 Heater Track 2
7
⁄8-in. Bushing 2 2-in. Bushing 7 No. 10 Screw 6 Plate Washer 6 Lock Nut 3
3
⁄8-in. Ring Terminal*
2 Spacer
*Ring terminals are included in package numbers CRHEATER137A00 and
CRHEATER138A00 only and are only used on heat pump units.
INSTALLATION
NOTE: A minimum ductwork clearance of 1 in. is re­quired for the first 24 in. of ductwork on 15 to 25 ton units with electric heat.
1. Turn off power to the unit.
2. Remove control box access panel and electric heater ac­cess panel. See Fig. 1.
3. Remove cover plates from both ends of electric heater compartment and save screws.
4. Install heater track from accessory package into heater compartment to facilitate installation of heater assem­bly.See Fig. 2. Locate track in compartment at side near­est indoor blower section. Secure track to basepans with field-supplied screws.
5. Install factory-supplied spacers at both sides of electric heater compartment. See Fig. 2 and 3.
6. Remove 2 knockouts (one
7
⁄8in. and one 2 in.) from the partition between electric heater compartment and con­trol box section. Insert bushings provided into the holes. See Fig. 2.
7. Install electric heater assembly (Fig. 4) into heater compartment.
8. Feed electric heater control wires through
7
⁄8-in. bush­ing and feed power wires through 2-in. bushing in par­tition and into the electric heat control box section.
9. Match the holes at the top of the heater assembly with the baffle at the end of the unit opposite the control sec­tion. See Fig. 5.
10. Reinstall cover plate over heater control section. To do so, line up cover plate, heater assembly, and baffle holes. Fasten heater assembly to unit with two no. 10 screws provided in accessory kit. Fasten bottom of cover plate to basepan with two no. 10 screws provided.
11. Fasten electric heat control box to baffle using remain­ing no. 10 screws provided in accessory kit. See Fig. 5.
Large Packaged Rooftop Units
121⁄2to 25 Tons
Accessory Electric Heater Packages
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1144 Tab 1b5a5a6b
PC 111 Catalog No. 565-058 Printed in U.S.A. Form 50H,T-1SI Pg 1 1-99 Replaces: 50-5SI
ELECTRIC HEATER ACCESS PANEL
UNIT CONTROL BOX ACCESS PANEL
NOTE: Typical unit shown with electric heater access panel removed.
Fig.1—Typical Unit Physical Details (13 to 18 Ton Unit Shown)
*Kit numbers CRHEATER142A00 and CRHEATER143A00 only.
Fig. 2 — Component Location — Electric Heat
2
Table 2 — Standard Efficiency Packaged Rooftop Units,
Electrical Data and Electric Heater Package Usage
UNIT 50TJ
and 559F
NOMINAL VOLTAGE
(3 Ph, 60 Hz)
ACCESSORY HEATER PART NO. CRHEATER
IFM
ACCESSORY
ELECTRIC HEAT
POWER SUPPLY
Hp FLA kW MCA MOCP
15 Tons
208/240
141A00
3.7
72/ 82 26/34 103/116 150/150 142A00 117/135 42/56 155/148 175/150 143A00 156/180 56/75 169/193 175/200
380
137A00
3
32 21.6 55 80
138A00 54 37.2 76 80
480
137A00
3.7
39 32 55 70 138A00 66 55 72 80 139A00 96 80 102 110
18 Tons
208/240
141A00
5
72/ 82 26/34 110/122 110/125 142A00 117/135 42/56 166/155 175/175 143A00 156/180 56/75 176/200 200/225
480
137A00 39 32 59 60 138A00 66 55 76 80 139A00 96 80 106 110
20 Tons
208/240
141A00
7.5
72/ 82 26/34 121/134 150/150 142A00 117/135 42/56 178/166 200/175 143A00 156/180 56/75 187/211 200/225
480
137A00 39 32 65 70 138A00 66 55 82 90 139A00 96 80 112 125
25 Tons
208/240
141A00
10
72/ 82 26/34 137/138 175/175 142A00 117/135 42/56 181/170 200/175 143A00 156/180 56/75 191/215 200/225
380
137A00 32 21.6 80 100 138A00 54 36 93 100
480
137A00 39 32 70 90 138A00 66 55 84 90 139A00 96 80 114 125
LEGEND
FLA Full Load Amps IFM Indoor-Fan Motor MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection
NOTE: Control circuit is 24 v.
3
Table 3 — High Efficiency Packaged Rooftop Units
Electrical Data and Electric Heater Package Usage
UNIT 50HJ
and 551A
ELECTRIC HEATER RATING
VOLTAGE (3 Ph, 60 Hz)
ACCESSORY HEATER
PACKAGE NO. CRHEATER
IFM
ACCESSORY
ELECTRIC HEAT
POWER SUPPLY
Hp FLA kW MCA MOCP
13 Tons
208/240
140A00
3.7
39/ 45 14/19 88/ 88 100/100 141A00 72/ 82 26/34 103/116 110/125 142A00 117/135 42/56 159/148 175/175
380 137A00 3 32 21.6 52 60
480
136A00
3.7
18 15 39 45 137A00 39 32 55 60 138A00 66 55 72 80
15 Tons
208/240
141A00
5
72/ 82 26/34 111/122 125/125 142A00 117/135 42/56 167/154 175/175 143A00 156/180 56/75 177/199 200/200
480
137A00 39 32 58 60 138A00 66 55 76 80 139A00 96 80 106 110
20 Tons
208/240
141A00
10
72/ 82 26/34 129/138 150/150 142A00 117/135 42/56 185/170 200/175 143A00 156/180 56/75 195/215 225/225
380
137A00 32 21.6 71 90 138A00 54 36 89 90
480
137A00 39 32 66 70 138A00 66 55 83 90 139A00 96 80 113 125
LEGEND
FLA Full Load Amps IFM Indoor-Fan Motor MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection
NOTE: Control circuit is 24 v.
Table 4 — Packaged Heat Pump Units
Electrical Data and Electric Heater Package Usage
UNIT
50HJQ and
542J
ELECTRIC HEATER
RATING VOLTAGE (3 Ph, 60 Hz)
ACCESSORY HEATER
PACKAGE NO. CRHEATER
IFM
ACCESSORY
ELECTRIC HEAT
POWER
SUPPLY
Hp FLA kW MCA MOCP
12.5 Tons
208/240
140A00
3.7
39/ 45 14/19 114/123 125/150 141A00 72/ 82 26/34 155/168 175/175 142A00 117/135 42/56 211/200 225/225
480
136A00 18 15 54 60 137A00 39 32 81 90 138A00 66 55 98 110
15 Tons
208/240
141A00
5
72/ 82 26/34 174/187 175/200 142A00 117/135 42/56 231/219 250/225
480
137A00 39 32 91 100 138A00 66 55 108 110
LEGEND
FLA Full Load Amps IFM Indoor-Fan Motor MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection
NOTE: Control circuit is 24 v.
4
UnitsNot RequiringAccessoryElectric HeatBox (Accessory Kit Numbers CRHEATER136A00, 137A00, 138A00, 139A00, 140A00, 141A00)
1. Remove the 2-in. knockout from the bottom of the unit control box, and install a 2-in. bushing (provided) in the hole.
2. On heat pump units using number CRHEATER137A00 or CRHEATER138A00 accessory kits, remove the factory­supplied power wire terminals, and crimp the
3
⁄8-in. ring terminals (supplied in accessory kit) onto the ends of the power wires.
3. Route power wires fromthe electric heat control boxthrough the bushing, and into the unit control box.
4. Attach power wiring to the terminal block (TB) as shown in Fig. 6.
Units Requiring Accessory Electric Heat Box (Fig. 7) (Accessory KitsCRHEATER142A00and CRHEATER143A00)
1. Remove field power supply wiring from terminal block in base unit control box, and remove the wiring from the box.
2. Remove the 2-in. knockout from the bottom of the unit control box, and install a 2-in. bushing (provided) in the hole.
3. Install accessory electric heat box (Fig. 7) under the unit control box (Fig. 8). The holes in the accessory electric heat box align with the knockouts in the partition and the bottom of the unit control box.
4. Install field power supply wiring in accessory electric heat box and connect it to TB (see Fig. 8 and label diagram on the unit).
5. Route 1/0 wire with pigtails from the accessory electric heat box into base unit control box.
6. Fasten the pigtails to TB1 in the unit control box as shown in Fig. 8.
7. Install electric heater power wiring from the electric heat control box to TB in accessory electric heat box as shown in Fig. 8. Fasten wires with plate washers and lock nuts provided. When running power wiring through unit cor­ner post, install a field-supplied watertight connector.
All Units
1. Remove knockout in base unit control box below the low­voltage barrier.
2. Install a
7
⁄8-in. bushing (provided).
3. Feed control wiringfrom electric heater controlbox through hole and secure to TB2 or TB3 as shown in Fig. 6 and 8.
4. Mark the space on the unit nameplate labelled ‘‘Check Here’’ with appropriate unit minimum circuit amps and overcurrent protection device.
5. Set heat anticipator settings according to Table 5.
6. Replace all panels.
7. Turn on power to the unit.
ELECTRIC HEATER COMPARTMENT
SPACER
ELECTRIC HEATER CONTROL BOX
CONTROL BOX COMPARTMENT
ELECTRIC HEATER POWER WIRING
ELECTRIC HEATER CONTROL WIRING
ELECTRIC HEATER ELEMENTS
Fig. 3 — Accessory Electric Heater Installation
HEATER ELEMENTS
ELECTRIC HEATER CONTROL BOX
HEATER POWER WIRING
HEATER CONTROL WIRING
Fig. 4 — Accessory Electric Heater Assembly
5
ELECTRIC HEATER ASSEMBLY (UNIT END OPPOSITE CONTROL SECTION)
BASEPAN
BAFFLE
ELECTRIC HEATER CONTROL BOX
SPACER
BAFFLE
Fig. 5 — Electric Heater Installation Details
LEGEND
ASY — Assembly TB Terminal Block
Fig. 6 — Accessory Electric Heat — Wiring Connection Diagram,
Package Numbers CRHEATER136A00, 137A00, 138A00, 139A00, 140A00, 141A00
6
DOOR
FIELD POWER SUPPLY WIRING
ELECTRIC HEATER POWER WIRING
TO TB1 (BASE UNIT CONTROL BOX)
LEGEND
TB — Terminal Block NOTE: This accessory is only required for accessory electric heater
kit part numbers CRHEATER142A00 and CRHEATER143A00.
Fig. 7 — Accessory Electric Heat Box
NOTE: Route heater control wiring outside of accessory electricheat box. Secure withfield-suppliedwiretiestobaseunitcontrolbox.Con­trol wiring must clear hinged door on electric heat box.
LEGEND
ACY Accessory ASMLY — Assembly EQUIP — Equipment
FU Fuse GND — Ground TB Terminal Block
Fig. 8 — Electric Heater Wiring Connections Using Accessory Electric Heat Box
(Accessory Electric Heat Kit Numbers CRHEATER142A00 and CRHEATER143A00)
7
Table 5 — Heat Anticipator Settings
UNIT VOLTAGE HEATER kW* STAGE 1 STAGE 2
50TJ/559F
15 to 25 Tons
208/230
26/34 0.40 0.66 42/56
0.66
0.40
56/75 0.66
380
21.6†
0.40
0.40
36** 0.66
37.2†† 0.66
460
32
0.40
0.40
55
0.66
80 0.66
50HJ/551A
13 Tons
208/230
14/19
0.40
26/34
0.40
42/56 0.66
380 21.6 0.40 0.40
460
15
0.40
— 32 0.40 55 0.66
50HJ/551A
15 and 20 Tons
208/230
26/34 0.40 0.66 42/56
0.66
0.40
56/75 0.66
380\
21.6
0.40
0.40
36 0.66
460
32
0.40
0.40
55
0.66
80 0.66
50HJQ/542J
12.5 and 15 Tons
208/230
14/19¶
1.0
0.26 26/34 0.52 42/56 0.78
460
15¶
1.0
0.26
32 0.52 55 0.78
*Heater capacity (kW) is based on heater voltage of 208 V, 240 v,
380 v, or 480 v. Heaters are rated at 240 v and 480 v. If distribution voltage to unit power varies from rated heater voltage, heater kW will vary accordingly.
†Only available on 50TJ/559F, 15 and 25 ton units.
**Only available on 50TJ/559F, 25 ton units.
††Only available on 50TJ/559F, 15 ton units.
\ Only available on 50HJ/551A, 20 ton units.