Installation of this accessory can be hazardous due to system
pressures, electrical components and equipment, and equipment locations (such as a roof or elevated surface). Only
trained qualified installers and service technicians should install, start-up, and service this equipment.
When installing this accessory, observe precautions in the literature and on any labels attached to the equipment and all other safety precautions may apply.
•Follow all safety codes
•Wear safety glasses and work gloves
•Use care in handling and installing the accessory
It is important to recognize safety information. This is the safetyalert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert
symbol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury
or death. Before performing service or maintenance operations on the unit, always turn off main power switch to unit
and install lock(s) and lockout tag(s). Unit may have more
than one power switch. Ensure electrical service to rooftop
unit agrees with voltage and amperage listed on the unit rating plate.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing roof top units.
CAUTION
Failure to follow this caution may result in personal injury
and damage to the unit. Cover the duct opening as a precaution so objects cannot fall into the return duct opening. Be
sure to remove the cover when installation is complete.
GENERAL
IMPORTANT: These economizers meet all the economizer
requirements as laid out in California’s Title 24 mandatory
section 120.2 (fault detection and diagnostics).
Catalog No. 04-53480208-01Printed in U.S.A.Form IIK-CRECOMZR77-03Pg 1 11-18Replaces: NEW
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 2
IMPORTANT: Read these instructions completely before attempting to install accessory economizer.
®
The EconoMi$er
X system utilizes the latest technology available for integrating the use of free cooling with mechanical cooling for packaged rooftop units. The code compliant Jade W7220
control system optimizes energy consumption, zone comfort,
and equipment cycling by operating the compressors when the
outdoor-air temperature is too warm, integrating the compressor
with outdoor air when free cooling is available, and locking out
the compressor when outdoor-air temperature is too cold. Demand controlled ventilation is supported.
This EconoMi$er X can be used with 1 or 2 speed indoor fan
motor units. (All other speed settings listed are for future use.)
The EconoMi$er X system utilizes gear-drive technology with a
direct-mount spring return actuator that will close upon loss of
power. The EconoMi$er X system comes standard with fault detection and diagnostics (FDD), an outdoor air temperature sensor, and mixed air temperature sensor (also called supply air
temperature sensor). Outdoor enthalpy, indoor (return) dry bulb
or enthalpy, and CO
sensors are available for field installation.
2
Standard integrated barometric relief dampers provide natural
building pressurization control. An optional power exhaust
system is available for applications requiring even greater exhaust capabilities. The power exhaust set point is adjustable at
the EconoMi$er X controller.
See Table 1-3 for package usage. See Table 4 for package contents. See Table 5 for sensor usage.
Table 1 — Carrier Package Usage
MODEL NUMBER
48/50FC 04-07
48/50GC 04-06
48/50HC, LC 04-06
48/50TC 04-07
50TCQ 04-07
50HCQ 04-06
50KCQ04-06
48/50KC 04-06
48/050HC 07-12
48/50LC 07
48/50TC 08-14
50TCQ 08-12
50HCQ 07-09
48/50HC 14
48/50LC 08-12
48/50TC 16
50TCQ 14
50HCQ 12
Small Cabinet
Large Cabinet
Extra Large Cabinet
ECONOMI$ER X
PART NUMBER
CRECOMZR077A00
CRECOMZR079A00
CRECOMZR081A00
Table 2 — Bryant Package Usage
MODEL NUMBER
Small Cabinet
581K/551K 04-06
582K/559K 04-07
581J/551J 04-06
549J/547J/559J/582J 04-06
548J/580J/558J 04-07
Large Cabinet
581J/551J 07-12
580J/558J 08-14
548J 08-12
549J 07-09
Extra Large Cabinet
581J/551J 14
580J/558J 16
548J 14
549J 12
Table 3 — ICP Package Usage
MODEL NUMBER
Small Cabinet
RAV/RGV 036-072
RAW/RGW 036-060
RAH/RGH 036-060
RAS/RGS 036-072
RHS 036-072
RHX/RHH 036-060
RAX/RGX 036-060
Large Cabinet
RAH/RGH 072-120
RAS/RGS 090-150
RHH 072-102
RHS 090-120
Extra Large Cabinet
RAH/RGH 150
RAS/RGS 180
RHS 150
RHH 120
ECONOMI$ER X
PART NUMBER
CRECOMZR077A00
CRECOMZR079A00
CRECOMZR081A00
ECONOMI$ER X
PART NUMBER
CRECOMZR077A00
CRECOMZR079A00
CRECOMZR081A00
2
Page 3
Table 4 — Package Contents
PACKAGE NO.QTYCONTENTS
EconoMi$er Horizontal Damper
1
Assembly with Actuator and
HH79ZZ007 OA Sensor
Jade HW63AW002 (HW: W7220)
1
Controller with Attached Harness*
HH77ZZ007 Mixed Air Temp Sensor
1
CRECOMZR077A00
CRECOMZR079A00
CRECOMZR081A00
*Shipped in hardware kit for field installation.
HW – Honeywell
(ring terminal)*
148TMHSRSE--A20 4-Wire Harness*
1Hood Assembly
1Aluminum Filter
1Front Blank Off Panel
1Filter Access Door
1Hardware Bag*
EconoMi$er Horizontal Damper
1
Assembly with Actuator and
HH79ZZ007 OA Sensor
Jade HW63AW002 (HW: W7220)
1
Controller with Attached Harness*
HH77ZZ007 Mixed Air Temp Sensor
1
(ring terminal)*
148TMHSRSE--A20 4-Wire Harness*
1Hood Assembly
1Aluminum Filter
1Front Blank Off Panel
1Horizontal Blank Off Panel
1Filter Access Door
1Hardware Bag*
EconoMi$er Horizontal Damper
1
Assembly with Actuator and
HH79ZZ007 OA Sensor
Jade HW63AW002 (HW: W7220)
1
Controller with Attached Harness*
HH77ZZ007 Mixed Air Temp Sensor
1
(ring terminal)*
148TMHSRSE--A20 4-Wire Harness*
1Hood Assembly
1Aluminum Filter
1Front Blank Off Panel
1Horizontal Blank Off Panel
1Filter Access Door
1Hardware Bag*
Table 5 — EconoMi$er X Sensor Usage
APPLICATION
Outdoor Air
Dry Bulb
Mixed Air
Sensor
Single Enthalpy HH57AC081
Differential Dry
Bulb or Enthalpy
CO
for DCV
2
Control Using a
Wall-Mounted
CO
Sensor
2
for DCV
CO
2
Control Using a
Duct-Mounted
CO
Sensor
2
* Includes HH57AC081 sensor and wiring harness.
†Accessory CO2 sensors.
**Accessory aspirator boxes required for duct-mounted applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSEN-
CO2 and 33ZCASPCO2 accessories.
ECONOMI$ER X WITH OUTDOOR AIR DRY
The HH79ZZ007 outdoor air dry bulb sensor is
factory installed on economizer.
HH79ZZ007 provided with economizer and field
installed in blower compartment.
CRDIFRASN01A00* (When available,
or MicroMetl 9901-2022-DIFF JC2)
33ZCSENCO2 or CGCDXSEN004A00
33ZCSENCO2 or
CGCDXSEN004A00†
33ZCSENCO2 or
CGCDXASP00100**
BULB SENSOR
ACCESSORIES REQUIRED
and
or CRCBDIOX005A00††
ACCESSORIES LIST
The EconoMi$er X has several field-installed accessories
available to optimize performance. Refer to Table 6 for authorized parts and power exhaust descriptions.
Table 6 — EconoMi$er X Field-Installed Accessories
DESCRIPTIONPART NUMBER
Small & Large Cabinet Power Exhaust
208/230-v 1 Ph
Small & Large Cabinet Power Exhaust
460-v 3 Ph
Extra Large Cabinet Power Exhaust
208/230-v 1 Ph
Extra Large Cabinet Power Exhaust
460-v 3 Ph
Enthalpy Sensor (OA)HH57AC081
Differential (Return) SensorCRDIFRASN01A00*
CO
Sensor and Aspirator BoxCRCBDIOX005A00
2
Return Air CO
Room Sensor (4 to 20 mA)
CO
2
Aspirator Box for Duct Mount
CO
Sensor (4 to 20 mA)
2
Hinged Filter Door Kit for Small CabinetCRHNGPNL001A00
Hinged Filter Door Kit for Large CabinetCRHNGPNL002A00
Hinged Filter Door Kit for Extra Large
Cabinet
*When available, or MicroMetl 9901-2022-DIFF JC2
Sensor (4 to 20 mA)CRCBDIOX002A00
2
CRPWREXH028A01
CRPWREXH029A01
CRPWREXH082A01
CRPWREXH083A01
33ZCSENCO2 or
CGCDXSEN004A00
33ZCASPCO2 or
CGCDXASP001A00
CRHNGPNL003A00
INSTALLATION
1.Turn off unit power supply(s) and install lockout tag.
2.Remove the existing unit filter access panel. Raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed and discarded. See Fig. 2.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal inju-
ry and/or death.
Disconnect power supply and install lockout tag before at-
tempting to install accessory.
3.Remove the indoor coil access panel and discard. See
Fig. 2. Remove the horizontal cover panel (see Fig. 2).
Reinstall panel over return opening in bottom of unit.
4.The EconoMi$er X hood assembly is shipped assembled.
Aluminum filter must be installed on some models. See
Fig 3.
5.Set the EconoMi$er X assembly upright. See Fig. 4.
6.Insert the EconoMi$er X assembly into the rooftop unit,
positioning the EconoMi$er X to the far left side of the
opening. See Fig. 5.
3
Page 4
Damper
Compressor
Access Panel
Outdoor-Air Opening and
Indoor Coil Access Panel
Filter Access Panel
Horizontal
Cover Panel
B
A
HOOD
ALUMINUM
FILTER
FILTER
CLIP
CLEANABLE
ALUMINUM
FILTER
OUTSIDE AIR
RELIEF AIR
Wiring Harness PlugBarometric Relief
Outside Air
Temperature Sensor
Red Shipping Tape
Outside Air
Damper
Fig. 1 — EconoMi$er X Component Locations
Fig. 2 — Typical Outdoor Air Section Access Panel
Locations
Fig. 4 — EconoMi$er X Positioned for Installation in
7.Slide the EconoMi$er X assembly all the way back into
the unit until it locks into the horizontal opening of the
HVAC (heating, ventilation and air conditioning) unit.
8.Secure the EconoMi$er X mounting flanges to the HVAC
unit with the screws provided. See Fig. 6.
9.Install a screw through the pre-punched hole in the
EconoMi$er X assembly into the flange on the horizontal
duct opening. See Fig. 5 and 10.
10. Remove the red tape securing the relief dampers for shipping purposes.
11. On some units, the EconoMi$er X assembly and hood does
not reach to the top of the unit. In this case a front blank-off
panel must be installed. Install provided front blank-off
panel above hood. Screw in place. (See Fig. 8 and 9.)
Fig. 10 — Top View of EconoMi$er X Installed in Unit
NOTE: The front blank-off panel must be installed before the
hood because the top of the hood fits into a channel in the bottom
of the panel.
12. Install the EconoMi$er X hood over the EconoMi$er X.
Use screws provided. (See Fig. 7 and 9.) Insert screw
through right side flange of hood into EconoMi$er X
flange.
5
Page 6
13. On some units, the return damper does not reach to the top
0
500
1000
1500
2000
2500
00.050.10.150.20.250.3
Small Cabinet
Large a nd Extra
Large Cabinet
0
1000
2000
3000
4000
5000
6000
00.10.20.30.4
Small Cabinet
Large Cabinet
Extr a Large Cabinet
INDOOR FAN MOTOR
ACCESS PANEL
HEATING ACCESS
PANEL
THERMOSTAT
CONNECTION
ACCESS PANEL
CENTER POST
of the horizontal return opening in the unit. In this case, a
horizontal blank-off must be installed. Install the horizontal blank-off at the top of the horizontal return opening.
(See Fig. 8.) Screw in place through pre-punched holes.
14. Install access door next to hood. Screw bottom of door to
HVAC unit. (See Fig. 7 and 9.) For the economizer for the
extra large cabinet, install plastic inserts on right-hand vertical post and install long gasketed screws along the vertical edge. Use standard serrated screws along the bottom of
the panel for all units.
15. See economizer performance charts in Fig. 11 and 12. See
base unit installation manual to make adjustments to meet
building ventilation requirements.
ROOFTOP UNIT’S
12-PIN MALE PLUG
ECONOMI$ER X
12-PIN FEMALE PLUG
Fig. 13 — Connect EconoMi$er X Harness to Unit PL6
Economizer Harness
17. Remove and save the 12-pin jumper plug from the unit
economizer harness – located in the upper left corner of
RELIEF FLOW (CFM)
the unit. Insert the EconoMi$er X plug into the unit wiring
harness. See Fig. 13.
NOTE: The 12-pin jumper plug should be saved for future use, in
the event that the EconoMi$er X assembly is ever removed. The
RETURN DUCT STATIC PRESSURE (i n. wg)
jumper plug is not needed as long as the EconoMi$er X assembly
is installed.
Fig. 11 — Barometric Flow Capacity
18. Remove the indoor blower access panel and the panel(s)
covering the unit control box. See Fig. 14.
RETURN AIR F LOW (CFM)
RETURN DUCT STATIC PRESSURE DRO P (in. wg)
16. If the EconoMi$er X will be operating with an enthalpy
Fig. 12 — Return Air Pressure Drop
outside air sensor, remove the factory-installed
HH79ZZ007 dry bulb sensor from the front face of the
economizer (see Fig. 1), and install the accessory enthalpy
sensor HH57AC081 in the same location. Holes are prepunched. Connect the (2) wire gray harness with plug
from the EconoMi$er X to the enthalpy sensor. See wiring
diagram Fig. 25 and 30. Refer to the “Installing Optional
HH57AC081 Outside Air Enthalpy Sensor” section for
more details on enthalpy settings.
Fig. 14 — Typical Indoor Fan Motor Access Panel
Locations
19. In the hardware kit provided with the EconoMi$er X
assembly is the HH63AW002 Jade controller (Honeywell
W7220). The controller is attached to a mounting bracket
and the EconoMi$er X harness is attached to the controller. Mount the controller assembly on the left side of the
unit control box. Screw bracket to the control box through
pre-punched holes in control box. See Fig. 15.
6
Page 7
NOTE: Some control box configurations may differ.
CENTRAL
TE RM I NA L
BOARD
WHITE
WIRE
10-PIN
FEMALE
PLUG FROM
CONTROLLER
Fig. 15 — Mount Controller Assembly in Unit Control
Box
20. Unplug the 10-pin female ECON plug currently connected
to the Central Terminal Board (CTB). See Fig. 16.
Fig. 17 — Connect 10-pin Plugs Together
22. Connect the 10-pin female plug from the Jade controller
harness to ECON on the CTB. See Fig. 18 and 25.
Fig. 16 — Unplug ECON plug from Central
Terminal Board (CTB)
21. Connect the 10-pin female ECON plug removed from the
CTB to the 10-pin male plug from the Jade controller harness. See Fig. 17 and 25.
Fig. 18 — Connect 10-pin Jade Plug to Central
Terminal Board (CTB)
23. Connect the White wire from the Jade controller harness to
the W1 terminal on the CTB. See Fig. 18 and 25.
24. Connect the red and brown wires from the Jade controller
harness to the CTB. See Fig. 19 and 25. The red wire connects to “R” on the CTB, and the brown wire connects to
“C”.
7
Page 8
Fig. 19 — Connect Red and Brown Wires to Central
CENTRAL
TERMINAL
BOARD
Terminal Board (CTB)
25. Locate the green wire with yellow stripe from the Jade
controller harness and screw it to the control box (ground).
See Fig. 20.
4-PIN MALE PLUG
FROM CONTROLLER
48TMHSRSE--A20
HARNESS
Fig. 21 — Connect 48TMHSRSE--A20 Harness to
Harness from Controller
27. Route the 4-wire 48TMHSRSE--A20 harness through the
divider between the control box and the indoor blower section. See Fig. 22.
48TMHSRSE--A20
HARNESS
Fig. 20 — Connect Ground Wire From Controller
26. Locate the 48TMHSRSE--A20 harness (with 4-pin female
plug) provided in the hardware kit with the EconoMi$er X
assembly. Connect the 48TMHSRSE--A20 harness to the
4-wire harness with a male plug from the Jade controller
harness. See Fig. 21 and 25.
CONTROL
BOX
NOTE: Some control box configurations may differ.
INDOOR
BLOWER
SECTION
Fig. 22 — Route 48TMHSRSE--A20 Harness to Indoor
Blower Section
28. Screw the HH79ZZ007 mixed air (MAT) sensor to the left
side edge of indoor blower through pre-punched hole, see
Fig. 23. Confirm that the screw does not interfere with
blower rotation. Connect the (2) spade terminals on the
HH79ZZ007 sensor to the orange and brown wires from
the 4-wire 48TMHSRSE--A20 harness. See Fig. 23
and 25.
8
Page 9
Connect (2)
green wires from
HH79ZZ007 sensor
to the brown and
orange wires from
the 48TMHSRSE--A20
HH79ZZ007
MAT sensor
(Ring
terminal)
PINK AND
VIOLET WIRES
FROM
48TMHSRSE--A20
HARNESS
INDOOR
BLOWER
Indoor blower
Fig. 23 — Mount and Connect Mixed Air Sensor
29. Connect the pink and violet wires from the 4-wire
48TMHSRSE--A20 harness to the pink and violet terminals in the wire bundle in the indoor blower section. See
Fig. 24 and 25.
Fig. 24 — Connect Pink and Violet Wires in Indoor
Blower Section
30. If using differential return sensor or DCV sensor, install it
now. See installation details later in the instructions and
the wiring diagram for further information.
9
Page 10
Plug
4-Pin Male
UNIT CONTROL BOX COMPARTMENT
Harness with
48TMHSRSE--A20
4-Pin Female Plug
MAT
ORG
1
4
ORG
BRN
2
BRN
Controller.
W7220 JADE
Unit Control Box
Field Mounted in
C
BRN
9
R
RED
10
OAT
OAT
MAT
VIO
PNK
Plug
10-Pin Male
334
1
2
S-BUS
ACT 24V
BLU
10
1
S-BUS
ACT COM
“R” ON CTB
BLK
GRA
GRA
RED
645913827
8
2
6
7
5
10
ACT 2-10
ORG
3
EXH1
AUX1 OUT
“C” ON CTB
YEL
BRN
4
9
E-GRD
IAQ 2-10
IAQ COM
BLK
BLU
GRN / YEL
CO2
(Optional)
from CTB
10-Pin Female
Plug Disconnected
AUX2 IN
WHT
Ground
“W1” on CTB
BLU
1
Y1 IN
Y1 OUT
GRA
2
Y2 OUT
ORG
3
OCC
Y2 IN
BLK
YEL
5
4
ECON on
10-Pin Female
Plug Connects to
6
Board
Central Terminal
7
8
Harness
50HE403859
GRN
Indoor Blower
Field Mount on
Mixed Air Sensor
HH79AH001
GRN
HONEYWELL C7250
Harness
Economizer
VIO
VIO
In Unit
6
PNK
PNK
7
BLU
2
12-Pin Female
Plug from Economizer
VIO
PNK
BLU
GRN
GRN
Sensor
Dry Bulb
Outside Air
ECONOMIZER RETURN CHAMBERINDOOR BLOWER SECTION
HH79AH001
1
HONEYWELL C7250
1
RED
1
BLK
BLK
2
BLK
2
PNK
RED
GRA
GRA
GRA
3
10
GRA
3
WHT
3
11
GRA
4
GRN
4
1
5
RED
Actuator
Economizer
YEL
BRN
ORG
Plug in Unit
12-Pin Male
8
9
4
12
ORG
GRA
GRA
PL6
Plug
S-Bus
S-Bus
123
OA
RA
DA
Temp & Humidity
HH57AC081
HH57AC081
BRN
Air Sensor
Enthalpy Outside
YEL
To Optional
Power Exhaust
1
Either the OAT or the Enthalpy
Sensor can be used but not both.
Remove OAT if Enthalpy’s used.
1
LEGEND
CTB: Central Terminal Board
Refer to Figure 31 for wiring optional
Refer to Figures 33 and 34 for Remote
2
MAT: Mixed Air Temperature Sensor
Differential Return Air Sensor kit.
Fault Detection and Diagnostic Monitoring.
3
OAT: Outside Air Temperature Sensor
Fig. 25 — Typical EconoMi$er X Wiring Diagram for 1 or 2 Speed Units
(Not for 48/50LC 07-12 Units)
10
Page 11
INSTRUCTIONS FOR 48/50LC
07-12 UNITS ONLY
IMPORTANT: This section is for economizer installation instructions on 48/50LC 07-12 units only.
1.Follow steps 1 through 19 in the Installation section.
2.The 48/50LC 07-12 units require different wiring than is
factory-attached to the W7220 Jade controller. Disconnect
the complete wiring harness factory-attached to the
W7220 Jade controller, as shown below in Fig. 26. This
harness can be discarded.
NOTE: The 4-wire 48TMHSRSE--A20 harness provided with the
economizer will also NOT be used on the 48/50LC 07-12 units,
see Fig. 27.
Fig. 26 — Remove Complete Harness Factory-
Attached to W7220 Controller
Fig. 27 — 48TMHSRSE--A20 Not
12 Units
3.The 48/50LC 07-12 units that do not have a factory-installed
economizer will have a new Jade W7220 controller wiring
harness shipped in the control box section of the HVAC unit.
This harness, Carrier part number 48LCHSRADH-A00, is
shown below in Fig. 28 and 30.
Used on 48/50LC 07-
Fig. 28 — 48LCHSRADH-A00 W7220 Controller Harness Shipped With 48/50LC 07-12 Units
11
Page 12
Fig. 29 — Photo of 48LCHSRADH-A00 W7220
Controller Harness Shipped With
48/50LC 07-12 Units
4.The connectors on the right side of Fig. 28 on the 48LCHSRADH-A00 harness attach to the Jade W7220 controller
installed in the unit control box. See Fig. 28 and 30.
48LCHSRADH-A00 harness connectors are labeled to easily identify the plug-in location on the controller.
5.Locate the Compressor Staging Control (CSC) board in
the HVAC unit. When a field-installed economizer is used,
the J5 jumper on the CSC must be removed. Remove the
J5 jumper. See Fig. 30.
6.The connectors on the left side of Fig. 28 on the 48LCHSRADH-A00 harness attach to the unit’s CSC board. Connect J3 and J5 plugs to the CSC board. See Fig. 30.
7.Screw the green wire with yellow stripe in the 48LCHSRADH-A00 harness to the control box (ground). See
Fig. 20 and 30.
8.Mount the provided HH79ZZ007 mixed air temperature
(MAT) sensor to the indoor blower. Confirm that the
screws do not interfere with blower rotation (see Fig. 23).
Connect the (2) spade terminals on the HH79ZZ007 to
orange and brown wires in the indoor blower section wire
bundle.
9.If using a differential return sensor or DCV sensor, install
it now. See installation details later in this instructions and
the wiring diagram for further information.
12
Page 13
NOTE: Harness attached to the W7220 controller from the Carrier
factory is removed and not used with 48/50LC 07-12 units.
Fig. 30 — Typical EconoMi$er X Wiring Diagram For 48/50LC 07-12 Units
13
Page 14
Installing Optional HH57AC081 Single Outside
4/ (108)
2/ (70)
/ (21)
2/ (55)
Air Enthalpy Sensor
When using the HH57AC081 (Honeywell C7400S) enthalpy
sensor for outside air changeover (see Fig. 32), the existing
HH79ZZ007 dry bulb sensor must be removed. The enthalpy
sensor will be mounted in the same location as the dry bulb
sensor (see Fig. 1). When the enthalpy sensor’s OA temperature, enthalpy and dew point are below the respective set
points, the outside air can be used for free-cooling. When any
of these is above the set point, free-cooling will not be available. Figure 31 shows the enthalpy boundaries in the W7220
Jade controller. There are (5) enthalpy boundaries (set points
ES1 through ES5), which are defined by dry bulb temperature,
enthalpy, and dew point. ES3 is the default setting. Table 7
shows the High Limit Curves for each setting.
NOTE: To use the HH57AC081 sensor for outside air sensor, the
dipswitches on the sensor must be set to OFF-OFF-OFF. See
Tab le 8.
The (2) gray wires with a plug from the EconoMi$er X harness
in the return chamber plug directly into the HH57AC081 enthalpy sensor. See Fig. 25 and 30 for wiring.
Fig. 31 — Enthalpy Curve Boundaries
Table 7 — Single Enthalpy and Dual Enthalpy High Limit Curves
DA — Discharge Air or Supply Sensor
RA — Return Air
OA — Outside Air
DIP SWITCH POSITIONS FOR SWITCHES 1,2, & 3
123
Fig. 32 — HH57AC081 Sensor, Dimensions and DIP
Switch Location
14
Page 15
Installing Differential Return Air Sensor
12-PIN FEMALE
PLUG FROM ECONOMIZER
BLU
BLK
GRAGRAGRA
GRAGRA
GRA
GRA
PNK
VIO
6
7
2
3
10
11
5
1
12
9
4
8
RED
ORG
PL6
PLUG
12-PIN MALE
PLUG IN UNIT
BRN
YEL
*HH57AC081
DIFFERENTIAL RETURN
SENSOR. FIELD MOUNTED
IN RETURN DUCT
WIRING
HARNESS*
*PROVIDED IN
CRDIFRASN01A00 Kit
The CRDIFRASN01A00 differential return air sensor kit must
be field mounted in the system’s return duct work. The kit includes a wiring harness that connects the EconoMi$er X harness in the return chamber of the unit to the provided
HH57AC081 sensor. Wire per Fig. 33.
In addition to using the HH57AC081 (Honeywell C7400S) sensor (see Fig. 32) for a single enthalpy sensor, it can also be used
as a differential return enthalpy or dry bulb sensor. Figure 31
shows the dual enthalpy boundaries in the W7220 Jade controller. With dual enthalpy, the HIGH LIMIT boundary is ES1 when
there are no stages of mechanical cooling energized and HL
(high limit) when a compressor stage is energized. Table 7
shows the High Limit Curves for each setting.
NOTE: To use the HH57AC081 sensor for differential return air,
the dipswitches on the sensor must be set to ON-OFF-OFF. See
Table 8.
When using the CRDIFRASN01A00 differential return enthalpy or dry bulb temperature option, see Table 9 for California
Title 24 setting requirements by region.
Fig. 33 — Wiring Differential Return Air Sensor
California’s Title 24 High Temperature Limit
Settings
California’s Title 24 code requires a high temperature limit setting for all dry bulb outside air economizer change over. The
temperatures vary by region within California. See Table 9 for
high limit settings.
Table 9 — California Title 24 Regional High Limit Dry
Bulb Temperature Settings
TABLE 140.4-B AIR ECONOMIZER HIGH LIMIT SHUT OFF
DEVICE TYPE*
Fixed Dry Bulb
Differential Dry Bulb
Fixed Enthalpy†
+ Fixed Dry Bulb
* Only the high limit control devices listed are allowed to be used and
at the set points listed. Others such as Dew Point, Fixed Enthalpy,
Electronic Enthalpy, and Differential Enthalpy Controls, may not be
used in any climate zone for compliance with Section 140.4(e)1
unless approval for use is provided by the Energy Commission
Executive Director.
†At altitudes substantially different than sea level, the Fixed
Enthalpy limit value shall be set to the enthalpy value at 75°F and
50% relative humidity. As an example, at approximately 6,000 foot
elevation, the fixed enthalpy limit is approximately 30.7 Btu/lb.
CONTROL REQUIREMENTS
REQUIRED HIGH LIMIT
CLIMATE
ZONES
1, 3, 5, 11-16OAT exceeds 75°F
2, 4, 10OAT exceeds 73°F
6, 8, 9OAT exceeds 71°F
7OAT exceeds 69°F
1, 3, 5, 11-16
2, 4, 10
6, 8, 9
7
OAT exceeds 28 Btu/lb of dry air
All
(ECONOMIZER
OFF WHEN):
DESCRIPTION
OAT exceeds
RA temperature
OAT exceeds return air
temperature minus 2°F
OAT exceeds return air
temperature minus 4°F
OAT exceeds return air
temperature minus 6°F
OAT exceeds 75°F
or
Demand Controlled Ventilation (DCV)
Refer to EconoMi$er X wiring diagram (Fig. 25 and 30) and
DCV instructions if demand controlled ventilation (CO
sor) is used. CO2 sensor will wire into the blue and black connections at the Jade controller as shown in Fig. 25, 30, and 34.
If a field-installed CO
sensor is connected to the
2
EconoMi$er X controller, a demand controlled ventilation
strategy will operate automatically. As the CO
level in the
2
space increases above the set point (on the EconoMi$er X controller), the minimum position of the dampers will be increased
proportionally, until the Maximum Ventilation setting is
reached. As the space CO
level decreases because of the in-
2
crease in fresh air, the outdoor damper will follow the higher
demand condition from the DCV mode or from the free cooling mode.
BLACK WIRE
IAQ 2-10 VDC
BLUE WIRE
IAQ COM
Fig. 34 — CO
Wiring Connections to Jade Controller
2
sen-
2
†
15
Page 16
Remote (Downstairs) Monitoring of Controller’s
CR
AUX2-1
OCC
E-GND
EXH1
AUX1-0
Y2-I
Y2-O
Y1-I
Y1-O
C
R
W7220 JADE
ECONOMIZER
U1
U1
R
Rc
C
A-L/A
FURNACE, AIR HANDLER,
OR RTU
TH8321R OR
TH8321WF
SUB-BASE
Fault Detection and Diagnostics
Many codes including IECC, Title 24, and ASHRAE 90.1 require that the economizer’s faults be accessible by operating or
service personal, or annunciated locally on zone thermostat. To
setup remote monitoring on the controller, under SYSTEM
SETUP, AUX1-OUT must be set to SYS.
The latest versions of Honeywell’s TH8321WF or TH8321R
thermostats are options for meeting this requirement. Figure 35
shows an example of the thermostat wiring to the Jade controller. Follow instructions provided with Honeywell thermostat.
Another option that is acceptable to some codes is an annunciator light visible by service personnel. See Fig. 36 for typical
wiring to the Jade controller. Refer to codes for proper labeling
of light.
W7220 Economizer Controller Module
Fig. 35 — Thermostat Wired for Remote FDD
MAT
MAT
OAT
OAT
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
JADE Setting: Under the “System Setup” menu, set AUX1-OUT to
“SYS” which will close JADE relay on fault detection
AUC2-1
OCC
E-GND
EXH1
AUX1-0
Y21
Y2O
Y1I
Y1O
=CR
TO “AUX1-0” TERMINAL
TO “C” TERMINAL
Annunciator Light*
Examples of annunciator lights
would include these Grainger lights:
- Item #20C841
- Item #20C846
Fig. 36 — Annunciator Light Wired for Remote FDD
16
Page 17
GENERAL JADE W7220 CONTROLLER AND
SENSOR INFORMATION
W7220 Economizer
The economizer controller used on electromechanical units is a
Honeywell W7220, which is located in the RTU base unit’s
Control Box. See the base unit’s Installation Instructions for
the location of the Control Box access panel.
The W7220 controller provides the following:
•2-line LCD interface screen for setup, configuration, and
troubleshooting.
•On-board fault detection and diagnostics
•Sensor failure loss of communications identification
•Automatic sensor detection
•Capabilities for use with multiple-speed indoor fan systems
User Interface
The user interface consists of a LCD display and a 4-button keypad on the front of the economizer controller.
Keypad
The four navigation buttons (see Fig. 37) are used to scroll
through the menus and menu items, to select menu items, and
to change parameter and configuration settings.
6.Press the ▼ button to decrease the displayed parameter
value.
NOTE: When values are displayed, pressing and holding the ▲or▼ button causes the display to automatically increment.
7.Press the (Enter) button to accept the displayed value
and store it in nonvolatile RAM.
8.The message “CHANGE STORED” displays.
9.Press the (Enter) button to return to the current menu
parameter.
10. Press the (Menu Up/Exit) button to return to the previous menu.
Menu Structure
Table 11 illustrates the complete hierarchy of menus and parameters for the EconoMi$er X system.
The Menus in display order are:
•STATUS
•SETPOINTS
•SYSTEM SETUP
•ADVANCED SETUP
•CHECKOUT
•ALARMS
IMPORTANT: The default setting on the W7220 controller
is for a “Fan Type” with 2 speed, which is correct for 2 or 3
speed units (48/50LC 07-12). For a 1 (single) speed unit, the
setting under SYSTEM SETUP > FAN TYPE must be
changed to 1 speed.
Fig. 37 — W7220 Controller
Using the Keypad with Menus
To use the keypad when working with menus:
•Press the ▲ (Up arrow) button to move to the previous
menu.
•Press the ▼ (Down arrow) button to move to the next
menu.
•Press the (Enter) button to display the first item in the
currently displayed menu.
•Press the (Menu Up/Exit) button to exit a menu’s item
and return to the list of menus.
Using the Keypad with Settings and Parameters
To use the keypad when working with set points, system and
advanced settings, checkout tests, and alarms:
1.Navigate to the desired menu.
2.Press the (Enter) button to display the first item in the
currently displayed menu.
3.Use the ▲ and ▼ buttons to scroll to the desired parameter.
4.Press the (Enter) button to display the value of the
currently displayed item.
5.Press the ▲ button to increase the displayed parameter
value.
IMPORTANT: Table 11 illustrates the complete hierarchy.
Menu parameters may be different depending on configuration. For example, none of the DCV parameters appear for a
system that does not have a DCV (CO
) sensor.
2
Programming the Jade W2770 Controller
The next several pages detail the different status displays, set
points, setup, and alarms available on the controller. The list
below and Table 10 summarize the inputs required for a standard application with a single outside air sensor.
NOTE: Instead of setting the SETPOINTS, you can use the defaults already set in the Jade controller – see default settings below. See Table 10 for summarized standard settings or, for more
detail, see Table 11 – Menu Structure.
SETPOINTS
•MAT SET: this sets the mixed air temperature (MAT) setting. The controller has a default of 53°F, but the range is
anywhere from 38°F to 70°F.
•LOW T LOCK: This setting locks out the compressor (or
mechanical cooling) at a given temperature. The default is
32°F, but the controller’s range is from –45°F to 80°F.
•DRYBULB SET: if you have an economizer with a dry
bulb outside air sensor, you will see and set the DRYBULB SET. The default setting is 63°F but the controller’s
range is 48°F to 80°F.
•ENTH CURVE: if you have a single enthalpy outside air
sensor instead of a dry bulb, you will see and set the ENTH
CURVE setting. There are 5 setting options: ES1 thru ES5.
Check Table 7 for the limits for each of these settings. ES3
is the default setting.
•MIN POS: The minimum position allows for ventilation
even when not in the free-cooling mode. If you have a single speed unit there will be only one minimum position
17
Page 18
setting. The default is 4.4 volts, but the range is 2 to
10 vdc.
•MIN POS H and MIN POS L: If your unit is 2 speed, there
will be 2 minimum position settings that show up on the
menu. The first is MIN POS H (for high speed), which has
a default of 4.4-v. The second is MIN POS L (for low
speed), which has a default of 6.0-v. Note that MIN POS H
and MIN POS L are only displayed if under SYSTEM
SETUP, AUX2 IN is set to “W1”, and FAN TYPE is set to
2 speed.
Table 10 — Standard Jade W7220 Controller Configuration
SYSTEM SETUP
•INSTALL: Allows you to set the current date. Use the keypad buttons to scroll to the correct date.
•EQUIPMENT: Always set to CONV even if the unit is a
heat pump.
•AUX2 IN: Always set to W.
•FAN TYPE: Set for either single speed or 2 speed. The default setting is 2 speed.
•AUX OUT: If remote Fault Detection and Diagnostic
(FDD) monitoring is required, select SYS.
•OCC: occupancy, always set to INPUT
CONTROLLER
MENU ITEM
MAT SET53°F38°F to 70°F53°F38°F to 70°F
LOW T LOCK32°F–45°F to 80°F32°F–45°F to 80°F
DRYBLB SET63°F48°F to 80°F63°F48°F to 80°FOnly displayed if using single DB OA sensor
ENTH CURVEES3ES1 to ES5ES3ES1 to ES5Only displayed if using a single enthalpy OA sensor
MIN POS4.4 vdc2 to 10 vdcn/an/aOnly displayed if set up for single speed unit
SET POINTS
MIN POS Hn/an/a4.4 vdc2 to 10 vdcOnly displayed if set up for 2 speed unit
MIN POS Ln/an/a6.0 vdc2 to 10 vdcOnly displayed if set up for 2 speed unit
INSTALL1/1/2010Current date1/1/2010Current date
EQUIPMENTCONVCONVCONVCONVAlways set to CONV, even on HP units
AUX2 INWWWWAlways set to W
FAN TYPE2 speed1 speed2 speed2 speedSee Note 3
AUX1 OUTNONESYSNONESYSSet to SYS for remote FDD monitoring
OCCINPUTINPUTINPUTINPUTAlways set to INPUT
SYSTEM SETUP
n/a — Not applicable
NOTES:
1. For 2 speed unit, under SYSTEM SETUP: EQUIPMENT= CONV,
AUX2 I = W, and FAN TYPE = 2 SPEED
2. More sophisticated controller setups, including for DCV or power
exhaust, are available by referring to Table 11 options
3. Fan speed options are:
1) 1 Speed
2) 2 Speed
3) 2 Speed: 1 Heat, 1 Cool.
4) 3 Speed: 1 Heat, 2 Cool.
4. Do not use 3 speed setting for LC units.
FOR SINGLE SPEED UNITFOR 2 SPEED UNIT
DefaultSet to:DefaultSet To:
NOTE
18
Page 19
Table 11 — Menu Structure
1
MENUPARAMETER
ECON AVAILNOYES/NO
ECONOMIZINGNOYES/NO
OCCUPIEDNOYES/NO
HEAT PUMPn/a
COOL Y1-INOFFON/OFF
COOL Y1-OUTOFFON/OFF
COOL Y2-INOFFON/OFF
COOL Y2-OUTOFFON/OFF
MA TEMP_ _ . _°F (or °C)
DA TEMP_ _ . _°F (or °C)
STATUS
OA TEMP_ _ . _°F (or °C)
OA HUM_ _%0 to 100%
RA TEMP_ _ . _°F (or °C)
RA HUM_ _%0 to 100%
IN CO2_ _ _ppm0 to 2000 ppm
DCV STATUSn/aON/OFF
DAMPER OUT2.0V2.0 to 10.0-v
ACT POS_ _%0 to 100%
ACT COUNTn/a1 to 65535
ACTUATORn/a
EXH1 OUTOFFON/OFF
EXH2 OUTOFFON/OFF
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
COOL
HEAT
0°F to 140°F
(–18°C to 60 °C)
0°F to 140°F
(–18°C to 60 °C)
–40°F to 140°F
(–40°C to 60°C)
0°F to 140°F
(–18°C to 60°C)
OK/Alarm
(on Alarm menu)
2
ECONOMIZING AVAILABLE
YES = economizing available; the system can use outside air for free cooling
NOTES
when required
ECONOMIZING ACTIVE
YES = Outside air being used for 1st stage cooling
NO = Economizing not active
OCCUPIED
YES = OCC signal received from space thermostat or unitary controller
YES = 24 vac on terminal OCC.
NO = 0 vac on terminal OCC.
HEAT PUMP MODE
(Not available on 2-speed configuration)
FIRST STAGE COOLING DEMAND (Y1-IN)
Y1-I signal from space thermostat or unitary controller for cooling stage 1.
ON = 24 vac on terminal Y1-I
OFF = 0 vac on terminal Y1-I
FIRST STAGE COOLING RELAY OUTPUT
ON = 24 vac on terminal Y1-O; Stage 1 mechanical cooling called on
OFF = 0 vac on terminal Y1-O; no mechanical cooling
SECOND STAGE COOLING DEMAND (Y2-IN)
Y2-I signal from space thermostat our unitary controller for second stage
cooling.
ON = 24 vac on terminal Y2-I
OFF = 0 vac on terminal Y2-I
SECOND STAGE COOLING RELAY OUTPUT
ON = 24 vac on terminal Y2-O; stage 2 mechanical cooling called on
OFF = 0 vac on terminal Y2-O; no stage 2 mechanical cooling
MIXED AIR TEMPERATURE, Cooling Mode
Displays value of measured mixed air from MAT sensor. Displays _ _ . _ if
not connected, short or out-of-range.
DISCHARGE AIR TEMPERATURE, after Heating section
(Accessory sensor required)
Displays when Discharge Air sensor is connected and displays measured
discharge temperature. Displays _ _ . _ if sensor sends invalid value, if not
connected, short or out-of-range.
OUTSIDE AIR TEMPERATURE
Displays measured value of outdoor-air temperature. Displays _ _ . _ if
sensor sends invalid value, short or out-of-range.
OUTSIDE AIR RELATIVE HUMIDITY
Displays measured value of outdoor humidity from OA sensor. Displays __%
if not connected, short, or out-of-range.
RETURN AIR TEMPERATURE
Displays measured value of return air temperature from RAT sensor.
Displays _ _ . _ if sensor sends invalid value, if not connected, short or outof-range
RETURN AIR RELATIVE HUMIDITY
Displays measured value of return air humidity from RA sensor. Displays
__% if sensor sends invalid value, if not connected, short or out-of-range
SPACE/RETURN AIR CO
(CO2 sensor required, accessory or factory option)
Displays value of measured CO
short or out-of-range
DEMAND CONTROLLED VENTILATION STATUS
(CO
sensor required, accessory or factory option)
2
Displays ON if above set point and OFF if below set point, and ONLY if a
CO
sensor is connected.
2
Displays voltage output to the damper actuator.
0% = OA Damper fully closed
2
from CO2 sensor. Invalid if not connected,
2
100%= OA Damper full open
Displays actual position of outdoor air damper actuator
2.0-v = OA Damper fully-closed
10.0-v = OA Damper full open
Displays number of times actuator has cycled.
1 cycle equals accrued 180° of actuator movement in any direction
Displays Error if voltage or torque is below actuator range
EXHAUST STAGE 1 RELAY OUTPUT
Output of EXH1 terminal:
ON = relay closed
OFF = relay open
EXHAUST STAGE 2 RELAY OUTPUT
Output of AUX terminal; displays only if AUX = EXH2
ON = relay closed
OFF = relay open
19
Page 20
Table 11 — Menu Structure1 (cont)
MENUPARAMETER
3
ERV
STATUS
(cont)
MECH COOL ON 00,1, or 2Displays stage of mechanical cooling that is active.
FAN SPEEDn/aLOW or HIGH
W (HEAT ON)n/aON/OFF
MAT SET53°F (12°C)
LOW T LOCK32°F (0°C)
DRYBLB SET63°F (17°C)
DRYBLB DIFF0°F
ENTH CURVEES3
DCV SET1100ppm
MIN POS 4.4 V2 to 10 vdc
MIN POS L6.0V2 to 10 vdc
SETPOINTS
MIN POS M5.4V2 to 10 vdc
MIN POS M4.4V2 to 10 vdc
VENTMAX L6.0 V2 to 10 vdc
VENTMAX M5.4 V2 to 10 vdc
VENTMAX H4.4 V2 to 10 vdc
VENTMIN L 3.7 V2 to 10 vdc
VENTMIN M 3.4 V2 to 10 vdc
VENTMIN H 2.8 V2 to 10 vdc
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
OFFON/OFF
38°F to 65°F
(3°C to 18°C);
increment by 1°
–45°F to 80°F
(–43°C to 27°C);
increment by 1°
48°F to 80°F
(9°C to 27°C);
increment by 1°
0°F to 6°F;
increment by 2°F
ES1,ES2,ES3,ES
4, or ES5
500 to 2000ppm;
increment by 100
2
ENERGY RECOVERY UNIT RELAY OUTPUT
Output of AUX terminal; displays only if AUX = ERV
ON = relay closed
NOTES
OFF = relay open
SUPPLY FAN SPEED
Displays speed setting of fan on a 2‒speed fan unit.
HEAT DEMAND STATUS
Displays status of heat demand on a 2‒speed fan unit.
MIXED AIR SET POINT
Set point determines where the economizer will modulate the OA damper to
maintain the mixed air temperature.
COMPRESSOR LOW TEMPERATURE LOCKOUT
Set point determines outdoor temperature when the mechanical cooling
cannot be turned on. Commonly referred to as the compressor lockout.
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Setpoint determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63°F (17°C), unit will economize
at 62°F (16.7°C) and below and not economize at 64°F (17.8°C) and above.
There is a 2°F (1.1°C) deadband.
DRYBULB SET is only displayed if the economizer has a single dry bulb
sensor
Dry bulb Differential will only show if using dual dry bulb - i.e. when an
outdoor air temperature sensor C7250 is attached to OAT terminals and
C7400S sensor is wired to S-Bus and configured for RAT (return air).
Free cooling will be assumed whenever OA temp is at or below RAT minus
this dry bulb setting.
ENTHALPY CHANGEOVER CURVE
(Requires enthalpy sensor option)
Enthalpy boundary “curves” for economizing using single enthalpy
DEMAND CONTROLLED VENTILATION SET POINT
Displays only if CO
Ventilation of space. Above the set point, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the set
point.
VENTILATION MINIMUM POSITION.
Only displayed if controller is set for single speed unit under FAN TYPE, and
if DCV is NOT used.
VENTILATION MINIMUM POSITION AT LOW SPEED.
Only displays if unit is set for 2 or 3 speed and CO
speed with 1 heat and 1 cool then set for HEATING ventilation. If using 3
speed with 1 heat and 2 cool then set for LOW SPEED COOLING
ventilation.
sensor is connected. Set point for Demand Control
2
is not used. IF using 2
2
VENTILATION MINIMUM POSITION AT MEDIUM SPEED.
Only displays if unit is set for 3 speed with 1 heat and 2 cool, and CO
used. Set for HEATING ventilation.
VENTILATION MINIMUM POSITION AT HIGH SPEED.
Only displays if unit is set for 2 or 3 speed and CO
speed with 1 heat and 1 cool then set for COOLING ventilation. If using 3
speed with 1 heat and 2 cool then set for HIGH SPEED COOLING ventilation
DCV MAXIMUM DAMPER POSITION AT LOW SPEED
Displays only if a CO
cfm) set point. Displays 2 to 10 V if <3 sensors (RA,OA, and MA). In AUTO
sensor is connected. Used for Vbz (ventilation max
2
is not used. IF using 2
2
mode dampers controlled by CFM
DCV MAXIMUM DAMPER POSITION AT MEDIUM SPEED.
Only displays if unit is set for 3 speed with 1 heat and 2 cool. Set for
HEATING ventilation.
DCV MAXIMUM DAMPER POSITION AT HIGH SPEED.
Only displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF
using 2 speed with 1 heat and 1 cool then set for COOLING ventilation. If
using 3 speed with 1 heat and 2 cool then set for HIGH SPEED COOLING
ventilation
DCV MINIMUM DAMPER POSITION AT LOW SPEED.
Only displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF
using 2 speed with 1 heat and 1 cool then set for HEATING ventilation. If
using 3 speed with 1 heat and 2 cool then set for LOW SPEED COOLING
DCV MINIMUM DAMPER POSITION AT MEDIUM SPEED.
Only displays if unit is set for 3 speed with 1 heat and 2 cool. Set for
HEATING ventilation.
DCV MINIMUM DAMPER POSITION AT HIGH SPEED.
Only displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF
using 2 speed with 1 heat and 1 cool then set for COOLING ventilation. If
using 3 speed with 1 heat and 2 cool then set for HIGH SPEED COOLING
ventilation
is not
2
20
Page 21
Table 11 — Menu Structure1 (cont)
MENUPARAMETER
ERV OAT SP 32°F (0°C)
EXH1 SET50%0 to 100%
EXH1 L SET65%0 to 100%
EXH1 M SET60%0 to 100%
SETPOINTS
(cont)
EXH2 H SET50%0 to 100%
EXH2 L SET80%0 to 100%
EXH2 M SET77%0 to 100%
EXH2 H SET75%0 to 100%
INSTALL01/01/10
UNITS DEG°F°F or °CSets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENTCONV
AUX2 IW
SYSTEM
SETUP
FAN TYPE2 speed1 speed/2 speed
* These Fan Type (speed) settings are for future use only. Do not use for 3 speed LC units.
FAN CFM5000cfm
AUX OUTNONE
OCCINPUT
MA LO SET45°F (7°C)
FREEZE POSCLOCLO or MIN
CO2 ZERO0ppm
CO2 SPAN2000ppm
ADVANCED
SETUP
STG3 DLY2.0h
SD DMPR POSCLOCLO or OPN
DCVCAL ENAMAN
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
0°F to 50°F
(–18°C to 10°C);
increment by 1°
2
Conventional or
HP
W required for
2-speed mode
100 to 15000 cfm;
increment by 100
NONE
ERV
EXH2
SYS
INPUT or
ALWAYS
35°F to 55°F
(2°C to 12°C);
incremented by 1°
0 to 500 ppm;
Increment by 10
1000 to 3000 ppm;
Increment by 10
0 min, 5 min, 15
min, then 15 min
intervals. Up to 4 h
or OFF
MAN (manual)
AUTO
NOTES
ENERGY RECOVERY VENTILATION UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Only displayed when AUX1 O = ERV
Exhaust fan set point for single speed units. Based on OA Damper position
to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT LOW SPEED
On 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
EXHAUST POINT 1 SETPOINT AT MEDIUM SPEED
Only displays if unit is set for 3 speed with 1 heat and 2 cool. Based on
economizer OA damper position to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT HIGH SPEED
On 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT LOW SPEED
On 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT MEDIUM SPEED
Only displays if unit is set for 3 speed with 1 heat and 2 cool. Based on
economizer OA damper position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT HIGH SPEED
On 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
Always set to CONV even for heat pump
Always set to W
Sets the economizer controller to the number of unit fan speeds.
Fan Type options:
1 Speed units
2 speed units
*2 speed units: 1 for heat and 1 for cool
*3 speed units: 1 for heat and 2 for cool
UNIT DESIGN AIRFLOW (CFM)
Enter ONLY if using DCVCAL ENA = AUTO
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilation
• EXH2 = second damper position relay closure for second exhaust fan
• SYS = use output as an alarm signal
Always set to INPUT
MIXED AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if
temperature falls below setup value).
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active
CLO = closed
MIN = MIN POS or VENTMIN
CO
ppm level to match CO2 sensor start level.
2
ppm span to match CO2 sensor.
CO
2
COOLING STAGE 3 DELAY
Delay after stage 2 for cool has been active. Turns on 2nd stage of cooling
when economizer is 1st stage and mechanical cooling is 2nd. Allows three
stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling
Function NOT AVAILABLE with 2-speed mode
Indicates shutdown signal from space thermostat or unitary controller. When
controller receives 24 vac input on the SD terminal in conventional mode, the
OA damper will open if programmed for OPN and OA damper will close if
programmed for CLO. All other controls, e.g., fans, etc. will shut off.
Turns on the DCV automatic control of the dampers. Resets ventilation
based on the RA, OA, and MA sensor conditions. Requires all 3 RA, OA, and
MA sensors.
For single speed units only.
21
Page 22
Table 11 — Menu Structure1 (cont)
MENUPARAMETER
PARAMETER
DEFAULT
VALUE
MAT T CAL0.0°F (or °C)±2.5°F (±1.4°C)
OA T CAL0.0°F (or °C)±2.5°F (±1.4°C)
OA H CAL0% RH±10% RH
ADVANCED
SETUP (cont)
RA T CAL2.0°F (or °C)±2.5°F (±1.4°C)
RA H CAL0% RH±10% RH
DA T CAL0.0°F (or °C)±2.5°F (±1.4°C)
2SP FAN DELAY 5 minutes
DAMPER VMINHS
DAMPER VMAXHS
n/an/aPositions OA damper to VMIN High Speed position
n/an/aPositions OA damper to VMAX High Speed position
DAMPER OPENn/an/a
CHECKOUT
DAMPER CLOSE n/an/aPositions damper to the fully closed position
CONNECT
Y1-O
CONNECT
Y2-O
CONNECT
AUX1O
n/an/aCloses the Y1-O relay (Y1-O)
n/an/aCloses the Y2-O relay (Y2-O)
n/an/a
Alarms display only when they are active. The menu title “ALARMS(_)” includes the number of active alarms in parenthesis
( ). When using SYLK bus sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS
T” will appear on the screen
MA T SENS ERR n/an/a
CO2 SENS ERR n/an/a
OA SENS T ERR n/an/a
ALARMS(_)
OA SYLK SENS
ERR
n/an/a
DA T SENS ERR n/an/aDISCHARGE AIR TEMPERATURE SENSOR ERROR
SYS ALARMn/an/a
ACT UNDER Vn/an/a
ACT OVER Vn/an/a
ACT STALLEDn/an/a
See Legend and Notes for Table 11 on page 23.
PARAMETER
RANGE AND
INCREMENT
2
0 to 20 minutes in
1 minute
increments
NOTES
MIXED AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration mixed air
temperature (MAT) sensor
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration outside air
temperature (OAT) sensor
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of calibration outside air enthalpy
sensor
RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration return air
temperature (RA) sensor
RETURN AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of calibration return air enthalpy
sensor
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration discharge air
temperature (DAT) sensor
TIME DELAY ON SECOND STAGE ECONOMIZING
While in the Economizing mode, this is the delay between thermostat Y2
call and Y1-O output to mechanical cooling stage, to allow high speed fan
operation to attempt to cool space first.
Position OA damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make sure to
pause in the mode to allow exhaust contacts to energize due to the delay in
the system.
Energizes the AUX1O output. If Aux setting is:
• NONE—no action taken
• ERV—24 vac out. Turns on or signals an ERV that the conditions
are not good for economizing but are for ERV operation.
• SYS—24 vac out. Issues a system alarm
d
MIXED AIR TEMPERATURE SENSOR ERROR
Mixed air sensor has failed or become disconnected - check wiring then
replace sensor if the alarm continues.
SENSOR ERROR
CO
2
CO
sensor has failed, gone out of range or become disconnected - check
2
wiring, then replace sensor if the alarm continues.
OUTSIDE AIR TEMPERATURE SENSOR ERROR
Outdoor-air temperature sensor has failed or become disconnected - check
wiring (OAT sensor connected at input terminals OAT), then replace if the
alarm continues.
OUTSIDE AIR ENTHALPY SENSOR ERROR
OAT sensor connected on S-bus.
When AUX1-0 is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX1-0 terminal has 24 vac out.
ACTUATOR VOLTAGE LOW
Voltage received by Actuator is below expected range.
ACTUATOR VOLTAGE HIGH
Voltage received by Actuator is over expected range.
ACTUATOR STALLED
Actuator stopped before achieving commanded position.
22
Page 23
Legend and Notes for Table 11.
NA
AUX2-
OCC
E-GND
EXH1
AUX1- O
Y2-
Y1-
Y2-O
Y1-O
C
R
50048848-002
Rev. A
NA
A2
OCC
EX
A1
Y2I
Y2O
Y1I
Y1O
C
R
CertProduct
California Title 24, Part 6
HJW10
www.energy.ca.gov
MAT
MAT
OAT
OAT
S-BUS
S-BUS
IAQ 2-10
IAQ COM
IAQ 24V
ACT 2-10
ACT COM
ACT 24V
MA
MA
OA
OA
SB
SB
SB
SB
SB
SB
V
C
R
V
C
R
NA
50040839-001
Rev. G
LEGEND
n/a— Not applicable
LCD— Liquid Crystal Display
MAT— Mixed Air Temperature
OAT— Outdoor Air Temperature
OCC— Occupied
RAT— Return Air Temperature
RTU— Rooftop Unit
NOTES:
1. Table 11 illustrates the complete hierarchy. Menu parameters may
be different depending on configuration. For example, none of the
DCV parameters appear for a system that does not have a DCV
) sensor.
(CO
2
2. When values are displayed, pressing and holding the
ton causes the display to automatically increment.
3. ERV Operation: When in Cooling mode AND the conditions are
NOT OK for economizing - the ERV terminal will be energized. In
the Heating mode the ERV terminal will be energized when the OA
is below the ERV OAT set point in the set point menu.
▲ or ▼ but-
Checkout Tests
Use the Checkout menu (see Table 11) to test the damper operation and any configured outputs. Only items that are configured are shown in the Checkout menu.
NOTE: See User Interface for information about menu navigation
and use of the keypad.
To perform a Checkout test:
1.Scroll to the desired test in the Checkout menu using the
▲ and ▼ buttons.
2.Press the button to select the item.
3.RUN? appears.
4.Press the button to start the test.
5.The unit pauses and then displays IN PROGRESS.
6.When the test is complete, DONE appears.
7.When all desired parameters have been tested, press the
(Menu up) button to end the test.
Checkout test can be performed at any time during the operation of the system as a test that the system is operable.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to
equipment.
Be sure to allow enough time for compressor startup and
shutdown between checkout tests. Do not short-cycle the
compressors.
SETUP AND CONFIGURATION
W7220 Economizer Module Wiring
Use Fig. 38 and Tables 12 and 13 to locate the wiring terminals
for the economizer module.
NOTE: The four terminal blocks are removable. Slide out each
terminal block, wire it, and then slide it back into place.
Mixed Air Temperature Sensor
(Polarity insensitive connections)
Outdoor Air Temperature Sensor
(Polarity insensitive connection)
Enthalpy Control Sensor
(Polarity insensitive connection)
Air Quality Sensor Input
(e.g. CO
sensor)
2
23
Page 24
Table 13 — Economizer Module — Right Hand
Terminal Blocks
LABELTYPEDESCRIPTION
Top Right Terminal Block
n/aThe first terminal is not used
Shut Down (SD) or Heat (W)
AUX2 I24 vac IN
OCC24 vac INOccupied / Unoccupied Input
E - GNDE-GNDEarth Ground - System Required
EXH124 vac OUT Exhaust Fan 1 Output
AUX1 O24 vac OUT
Y2-124 vac IN
Y2-O24 vac OUT
Y1-I24 vac IN
Y1-O24 vac OUT
CCOM24 vac Common
R24 vac24 vac Power (Hot)
Conventional only
and
Heat Pump Changeover (O?B) in Heat
Pump mode.
Programmable:
Exhaust fan 2 output
or
ERV
or
System alarm output
Bottom Right Terminal Block
Y2 in - Cooling Stage 2 Input from space
thermostat
Y2 out - Cooling Stage 2 Output to stage 2
mechanical cooling
Y1 in - Cooling Stage 2 Input from space
thermostat
Y1 out - Cooling Stage 2 Output to stage 2
mechanical cooling
Time-out and Screen Saver
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each Status item displays in turn and cycles to the next item after 5 seconds.
START-UP AND OPERATION
Cooling with EconoMi$er X
For Occupied mode operation of EconoMi$er X, there must be
a 24-v signal at terminals R and OCC (provided through PL6-3
from the unit’s IFC coil). Removing the signal at OCC places
the EconoMi$er X control in Unoccupied mode. See Table 14
for Damper Position Control.
Table 14 — Damper Position Control, 2-Speed Fan Motor, Economizer Cooling Not Available
During Occupied mode operation, indoor fan operation will be
accompanied by economizer dampers moving to Minimum Position set point for ventilation. If indoor fan is off, dampers will
close. During Unoccupied mode operation, dampers will remain closed unless a Cooling (by free cooling) or DCV demand is received.
When free cooling using outside air is not available, the unit
cooling sequence will be controlled directly by the space thermostat. Outside air damper position will be closed or Minimum
Position as determined by Occupancy mode and fan signal.
When free cooling is available as determined by the appropriate changeover command (dry bulb, outdoor enthalpy, differential dry bulb, or differential enthalpy), a call for cooling (Y1
closes at the thermostat) will cause the economizer control to
modulate the dampers open and closed to maintain the unit
supply air temperature. Default supply air temperature is 53°F,
with a range of 38°F to 70°F. Compressor will not run.
Should 100% outside air not be capable of satisfying the space
temperature, space temperature will rise until Y2 is closed. The
economizer control will call for compressor operation. Dampers will modulate to maintain SAT set point concurrent with
Compressor 1 operation. The “Low T Lock” setting (default
32°F) will lock out compressor operation when outside air temperature is below set point.
When space temperature demand is satisfied (thermostat Y1
opens), the dampers will return to Minimum Damper position
if indoor fan is running or fully closed if fan is off.
If accessory power exhaust is installed, the power exhaust fan
motors will be energized by the economizer control as the
dampers open above the EXH1 SET set point and will be energized as the dampers close below the EXH1 SET set point.
Damper movement from full closed to full open (or vice versa)
will take between 1
1
/2 and 21/2 minutes.
Heating with EconoMi$er X
During Occupied mode operation, indoor fan operation will be
accompanied by economizer dampers moving to Minimum Position set point for ventilation. If indoor fan is off, dampers will
close. During Unoccupied mode operation, dampers will remain
closed unless a DCV demand is received.
When the room temperature calls for heat (W1 closes), the
heating controls are energized.
For a list of common operating issues and concerns, see
Table 15.
Power Loss (Outage or Brownout)
All set points and advanced settings are restored after any power loss or interruption, as all settings are stored in the Economizer controller’s non-volatile flash memory.
NOTE: If the power goes below 18 vac, the W7220 controller
module assumes a power loss and the 5 minute power up delay
will become functional when power returns above 18 vac.
Alarms
The economizer module provides alarm messages that display
on the 2-line LCD.
NOTE: Upon power up, the module waits several seconds before
checking for alarms. This allows time for all the configured devices (e.g., sensors, actuator) to become operational.
If one or more alarms are present and there has been no keypad
activity for at least 5 minutes, the Alarms menu displays and
cycles through the active alarms.
The Alarms menus can be navigated at any time. See Table 11
for the Alarms menu.
CLEARING ALARMS
Once the alarm has been identified and the cause has been re-
moved (e.g., replaced faulty sensor), the alarm can be cleared
from the display.
To clear an alarm, perform the following:
1.Navigate to the desired alarm.
2.Press the button.
3.ERASE? displays.
4.Press the button.
5.ALARM ERASED displays.
6.Press the (Menu up/Exit) button to complete the
action and return to the previous menu.
NOTE: If an alarm still exists after it has been cleared, it will redisplay within 5 seconds.
Table 15 — Operating Issues and Concerns
ISSUE OR CONCERNPOSSIBLE CAUSE AND REMEDY
My outdoor temperature reading on the STATUS menu is
not accurate
If my enthalpy sensor drifts in accuracy over time, can I
recalibrate it?
Can I go back to factory defaults and start over?
Will I be able to see the LCD screen when it is in the unit?The LCD screen has a backlight that is always illuminated.
What is a good set point for the Mixed Air Temperature
(MAT)?
I am using enthalpy sensors. Why did the control ask me to
input a dry bulb changeover temperature?
In checkout, the outdoor damper closes when I command it
to open.
How do I set my minimum position when using a CO
sensor?
What if my damper does not go completely closed in the
checkout operation?
How do I set the OCC?
Does the economizer save my program values if the unit
loses power?
If the unit is left in checkout, how long will the unit stay in
checkout mode without input?
2
Check the sensor wiring:
• Enthalpy sensors are to be wired to the S-Bus terminals.
• Temperature sensors are to be wired to the OAT and MAT terminals.
The sensor is not able to be re-calibrated in the field. However, there is a menu item
under the ADVANCED menu to input a limited offset in temperature and humidity for
each sensor that is connected to the economizer.
Under the SYSTEM SETUP menu, you can change the set points to the factory
defaults.
The Mixed Air Temperature is the temperature of air to supply to the space. In a
commercial building, this is between 50°F and 55°F (10°C and 13°C). Mixed air is the
combination of return air and outdoor air.
If the humidity sensor in the enthalpy sensors fails, the backup algorithm in the control is
to default to the temperature sensor in the enthalpy sensor.
Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper
should drive open or closed with the return air damper having the opposite effect.
The minimum position is set using the VENTMIN and VENTMAX setup in the
SETPOINTS menu. VENTMIN is the minimum ventilation required when using an
occupancy sensor and VENTMAX is the minimum ventilation when not using an
occupancy sensor for Demand Control Ventilation. The VENTMAX position is set the
same as with the potentiometer on the analog economizers and is the output voltage to
the damper actuator. The range is 2 vdc closed OA damper and 10 vdc open OA
damper.
Check the damper linkage or hub to make sure the damper is able to close completely.
There are two settings for the OCC setting: INPUT and ALWAYS. INPUT is from the
space thermostat, if it has an occupancy output. ALWAYS is the unit in the occupied
mode, if the economizer is powered (fan on).
Yes, once the changes are stored in the controller they will be stored until they are
changed by the operator.
The unit will remain in checkout for 10 minutes, then return to normal operation.