Carrier CRECOMZR076A00, CRECOMZR078A00, CRECOMZR080A00 User Manual

CRECOMZR076A00 CRECOMZR078A00 CRECOMZR080A00
Installation Instructions
Read these instructions completely before attempting to install the Vertical EconoMi$er X Accessory.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . .1
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
EconoMi$er X Sensor Usage . . . . . . . . . . . . . 2
WIRING DIAGRAMS. . . . . . . . . . . . . . . . . . .5-7
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . .2-8
EconoMi$er X Standard Sensors . . . . . . . . . .8
EconoMi$er X Control Modes . . . . . . . . . .8-14
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . .16
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . .17
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or
use can cause explosion, re, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualied
installer, service agency, or your distributor or branch for information
or assistance. The qualied installer or agency must use factory­authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a re extinguisher available. Read these instructions thoroughly and follow all warnings
or cautions attached to the unit. Consult local building codes and
appropriate national electrical codes (in USE, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special
requirements.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions
or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identies the most serious hazards which will result in severe personal injury or death. WARNING signies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product
and property damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death. Before performing service or maintenance operations on the unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch. Ensure electrical service to rooftop unit agrees with voltage an amperage listed on the
unit rating plate.
!
WARNING
!
Small Rooftop Products
Select 3 to 12 1/2 Tons
Vertical EconoMi$er X Accessory
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing
roof top units.
GENERAL
IMPORTANT: These economizers meet the economizer requirements
as laid out in California’s Title 24 mandatory section 120.2 (fault detection and diagnostics).
The EconoMi$er X system utilizes the latest technology available
for integrating the use of free cooling with mechanical cooling for packaged rooftop units. The solid-state control system optimizes energy
consumption, zone comfort, and equipment cycling by operating the
compressors when the outdoor-air temperature is too warm, integrating the compressor with outdoor air when free cooling is available, and locking out the compressor when outdoor-air temperature is too cold. Demand control ventilation is supported.
This EconoMi$er X can be used with 1, 2, or 3 speed (48/50LC 07-12)
units.
The EconoMi$er X system utilizes gear-drive technology with a direct­mount spring return actuator that will close upon loss of power. The EconoMi$er X system comes standard with an outdoor air temperature sensor, mixed air temperature sensor. Outdoor enthalpy, indoor enthalpy, indoor temperature, and CO2 sensors are available for eld installation. See Table 3 for sensor usage.
Standard barometric relief dampers provide natural building pressurization control. An optional power exhaust system is available for applications requiring even greater exhaust capabilities. The power
exhaust set point is adjustable at the EconoMi$er X controller.
See Table 1 for package usage. See Table 2 for package contents. See Table 3 for sensor usage.
Table 1 - Package Usage
UNIT SIZE PART NUMBER
Small Cabinet, Footprint size: 46 3/4” x 74 3/8” CRECOMZR076A00
Large Cabinet, Footprint size: 58 1/2” x 88 1/8” CRECOMZR078A00
Extra-Large Cabinet, Footprint size: 63 3/8” x 115 7/8” CRECOMZR080A00
Table 2 - Package Contents
PACKAGE NO. QTY CONTENTS
1
Hood Top and Sides
1
Hood Divider
1
Aluminum Filter
CRECOMZR076A00,
CRECOMZR078A00
CRECOMZR080A00
18
Screws
1
EconoMi$er X Assembly
1
HH79ZZ007 Mixed (supply) Temperature Sensor
1
48TMHSRSE--A20 Harness
1
Hood Top and Sides
1
Hood Divider
1
Hood Filter Divider
2
Aluminum Filters
1
Hardware Bag
1
EconoMi$er X Assembly
1
HH79ZZ007 Mixed (supply) Temperature Sensor
1
48TMHSRSE--A20 Harness
1
Table 3 - EconoMi$er X Sensor Usage
ECONOMI$ER X WITH OUTDOOR AIR
APPLICATION
Outdoor Air
Dry Bulb
Mixed Air
Sensor
Single
Enthalpy
Differential
Enthalpy
CO2 for
DCV Control
Using a
Wall-Mounted
CO2 Sensor
CO2 for
DCV Control
Using a
Duct-Mounted
CO2 Sensor
†33ZCSENCO2 and CGCDXSEN004A00 are accessory CO2 sensors. **33ZCASPCO2 and CGCDXASP00100 are accessory aspirator boxes required for duct­mounted applications. ††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories.
HH79ZZ007 is factory installed on economizer
HH79ZZ007 provided with economizer and eld installed
33ZCSENCO2 or
CGCDXSEN004A00†
33ZCASPCO2 or
CGCDXASP00100**
DRY BULB SENSOR
Accessories Required
in blower compartment
33ZCSENCO2
CGCDXSEN004A00
and
HH57AC081
HH57AC081
or
OR
CRCBDIOX005A00††
ACCESSORIES LIST
The EconoMi$er X has several eld-installed accessories available to optimize performance. Refer to Table 4 for authorized parts and power
exhaust descriptions
Table 4 - EconoMi$er X Field-Installed
Accessories
DESCRIPTION PART NUMBER
Small Cabinet Power Exhaust 208-230 v 1 Ph CRPWREXH030A01
Small Cabinet Power Exhaust 460 v 3Ph CRPWREXH021A01
Large Cabinet Power Exhaust 208-230 v 1 Ph CRPWREXH022A01
Large Cabinet Power Exhaust 460 v 3 Ph CRPWREXH023A01
Extra Large Cabinet Power Exhaust 208-230 v 1 Ph CRPWREXH080A00
Extra Large Cabinet Power Exhaust 460 v 3 Ph CRPWREXH081A00
Outdoor Air Enthalpy Sensor HH57AC081
Indoor Air Enthalpy Sensor HH57AC081
Return Air CO2 Sensor (4 to 20 mA) CRCBDIOX005A00
CO2 Room Sensor (4 to 20 mA)
Aspirator Box for Duct Mount CO2 Sensor (4 to 20 mA)
Space Temperature and CO2 Room Sensor with Override (4 to 20 mA)
Space Temperature and CO2 Room Sensor with Override and Set Point (4 to 20 mA)
33ZCSENCO2 or
CGCDXSEN004A00
33ZCASPCO2 or
CGCDXASP001A00
33ZCT55CO2
33ZCT56CO2
INSTALLATION
1. Turn off unit power supply(s) and install lockout tag.
2. Remove the existing unit lter access panel. Raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. (See Fig. 2.)
3. Remove the indoor coil access panel and discard. (See Fig. 2.)
4. The EconoMi$er X hood components are shipped with the EconoMi$er X. Remove hood from packaging. The hood top and
sides are shipped factory assembled.
NOTE: If the power exhaust accessory is to be installed on the unit, the hood shipped with the EconoMi$er X will not be used and may be discarded. Save the aluminum lter for use in the power exhaust hood
assembly.
5. Insert the hood divider between the hood sides. (See Fig. 3) Secure hood divider with 2 screws (provided) on each hood side. Screws
should go through the hood sides into the divider. The hood divider
is also used as the bottom lter rack for the aluminum lter. On hood for extra large cabinet install lter divider. (See Fig. 4A.)
6. Set the EconoMi$er X upright. (See Fig. 5.)
7. Slide the EconoMi$er X assembly into the rooftop unit. (See Fig. 5). On small and large cabinets be sure to engage the rear EconoMi$er X ange under the tabs in the return-air opening of the unit base. (See Fig. 6)
8. Secure the EconoMi$er X to unit along side and bottom anges using the screws provided.
9. Remove the tape securing the relief dampers in place.
10. Remove and save the 12-pin jumper plug from the unit wiring harness (located in the upper left corner of the unit). Insert the EconoMi$er X plug into the unit wiring harness. Refer to Fig. 7 and 8 for wiring details.
NOTE: The 12-pin jumper plug should be saved for future use, in the
event that the EconoMi$er X is removed from the unit. The jumper plug is not needed as long as the EconoMi$er X is installed.
11. If EconoMi$er X will be operating under enthalpy control, replace the factory installed HH79ZZ007 outdoor dry bulb temperature sensor with accessory enthalpy sensor HH57AC081. (See Fig. 1.)
12. Remove the indoor fan motor access panel. (See Fig. 9.)
13. The mixed (or supply) air temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located on the “crimp end” and is sealed from moisture. Locate the sensor in the economizer hardware bag. Mount the supply air temperature sensor (provided) to the lower left section of the indoor fan blower housing. (See Fig. 10.) Use the screw provided and use existing hole. Locate the orange and brown wires in wire bundle in the indoor fan section. Connect the orange and brown wires to the
corresponding connections on the supply air temperature sensor.
(See Fig. 8.)
Wiring Harness
Actuator (Hidden)
HH57AC081 Enthalpy Accessory Location (Field Installed)
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury and/
or death.
Disconnect power supply and install lockout tag before attempting
to install accessory.
HH79ZZ007 Outside Air Temperature Sensor
Fig. 1 - EconoMi$er X Component Locations
(Small Cabinet Economizer Shown)
2
Filter Access Panel
Fig. 2 - Typical Outdoor-Air Section
Outdoor-Air Opening and Indoor Coil Access Panel
Access Panel Locations
A
B
Compressor Access Panel
Wiring Harness
Hood Filter Divider
Fig. 4A - Hood for Extra Large Cabinet
HVAC Unit Filters
C
Hood Divider
D
Hood Top and Side Assembly
Fig. 3 - Hood Assembly
ECONOMIZER P/N A B C D SHIP WT.
CRECOMZR076A00 33.37” 17.43” 19.05” 29.5” 55 lb
CRECOMZR078A00 40.37” 22.28” 24.48” 36.27” 80lb
CRECOMZR080A00 52.92” 27.03” 33.41” 49.92” 98lb
NOTE: The CRECOMZR080A00 hood has 2 aluminum lters and a hood lter divider that installs between the lters. (See Fig. 5A.)
Hood Top
Filter Clip
Outside Air
EconoMi$er X
Fig. 5 - EconoMi$er X Installed in HVAC Unit
Unit Filter Rack
Unit Base
Insert Screw in EconoMi$er X Flanges
(Small Cabinet Economizer Shown)
EconoMi$er X Hold Down Tab
EconoMi$er X
Hood Divider
EconoMi$er IV Rear Flange
Fig. 6 - Rear EconoMi$er X Flange Installation
(Small and Large Cabinet)
Cleanable Aluminum Filter
Barometric
Airow
Fig. 4 - Filter Installation
3
14. While everything is open install and wire any other accessories
Plug 10-pin plug from
and/or sensors as applicable and convenient, per their installation instructions and/or the Conguration section of this instruction. Some accessories require that unit ducting already be installed.
NOTE: If also installing a power exhaust accessory, skip step 16 and follow the power exhaust instructions instead.
16. Install the EconoMi$er X hood over the EconoMi$er X. Use screws provided.
17. The W7220 EconoMi$er X controller is shipped mounted to a bracket. Install the controller / bracket in the top left corner of the unit control box as shown in wiring diagram, Fig. 8. Screw in place through pre-punched holes.
18. For 1 and 2 speed units connect the plugs coming from the
controller as shown in wiring diagram, Fig. 7 and 8A.
NOTE: Provided 48TMHSRSE--A20 harness will be connected as shown below.
19. For 3 speed (48/50LC 07-12) units, the harness attached to the
W7220 econoMi$er X controller must be removed, and can be discarded. Locate harness 48LCHSRADH--A00 shipped in
plastic bag in the control box of unit. Attach this harness to the
W7220 controller as shown in Fig 8B and 8C.
NOTE: Harness 48TMHSRSE--A20 provided with economizer is not
used with 3 speed (48/50LC 07-12) units.
20. Adjust controller settings (minimum position, outside air, etc.) per
instructions detailed later in this instruction.
21. Follow all local and other applicable codes.
Unplug the 10-pin plug from PL6 from the Central Terminal Board (in control box) and plug into 10-pin plug from W7220
Indoor Blower Section
SAT
PL6
Connect SAT sensor and Pink and Violet wires from PL6 to the 48TMHSRSE—A20 harness.
BRN
ORN
Control box
W7220 into ECONO terminals on Central Terminal Board
W7720
48TMHSRSE--A20 harness with 4- pin plug
Central
Term Brd
See Picture
ECONO
Economizer X
Fig. 7 - Harness Detail
WIRING INSTRUCTIONS FOR 1 AND 2 SPEED UNITS:
A. Install W7220 (with harnesses attached) in unit control box. See
wiring diagram in instructions.
B. Unplug econo harness from PL6 with 10-pin plug shown above in
picture, from Central Terminal Board (CTB).
C. Attach 10-pin plug disconnected from (CTB) to 10- pin plug
harness from W7220 controller.
D. Connect other 10-pin plug from W7220 controller into ECONO
terminals on CTB. See picture above.
E. Connect 4-pin plug from the W7220 controller to the 4-pin
48TMHSRSE—A20 harness provided with economizer accessory.
F. Route 48TMHSRSE—A20 harness back to the indoor blower
section of the unit.
G. Mount Supply (or Mixed) Air Temperature sensor, and connect
Brown and Orange wires from harness to the SAT.
H. Connect Pink and Violet wires from 48TMHSRSE—A20 harness
to the Pink and Violet wires from PL6 economizer harness
4
48TMHSRSE--A20
If using HH57AC081 outside air enthalpy accessory, the OAT must be removed and disconnected. Set sensor dip-switches, see Table 11.
Fig. 8A - Typical EconoMi$er X Wiring Diagram For 1 and 2 Speed Units
(2 Speed Diagram Shown)
Harness
5
Fig. 8B - Typical EconoMi$er X Wiring Diagram For 3 Speed Units (48/50LC 07-12)
(See 3 Speed Unit Instructions for Complete Diagram)
NOTES:
1. Wires shown in bold are part of 48LCHSRADH--A00 harness which is provided with 48/50LC 07-12 3 speed units.
2. Harness 48TMHARSE--A20 which is provided with economizer accessory is not used on 3 speed units.
6
FIELD ATTACH TO W7220 CONTROLLER
CONNECT TO UNIT
(Provided with 3 Speed Units, Field Attached to W7220 Controller)
Fig. 8C - 48LCHSRADH--A00 Harness for 3 Speed Units (48/50LC 07-12)
BOARD
UNIT TERMINAL
CONNECT TO
TERMINAL BOARD
7
Thermostat Connection Access Panel
Center Post
Heating Access Panel
Indoor Fan Motor Access Panel
Fig. 9 - Typical Indoor Fan Motor
Access Panel Locations
Mixed Air Temperature Sensor Mounting Location
Mixed Air Temperature Sensor
To Unit Control Box
Fig. 10 - Mixed Air Sensor Placement
EconoMi$er X
The eld-installed accessory consist of the following:
Low leak economizer assembly
W7220 economizer controller
HH79ZZ007 Mixed (supply) air temperature sensor
HH79ZZ007 outside air temperature air sensor
48TMHSRSE--A20 harness (not used on 3 speed (48/50LC 07-
12) units.
W7220 Economizer
The economizer controller used on electro mechanical units is a
Honeywell W7220 which is to be located in the RTU base unit’s Control Box. See the Installation Instruction for your base unit for the location of the Control Box access panel.
The W7220 controller provide the following:
2-line LCD interface screen for setup, conguration and troubleshooting.
On-board fault detection and diagnostics
Sensor failure loss of communications identication
Automatic sensor detection
Capabilities for use with multiple-speed indoor fan systems
User Interface
The user interface consists of a LCD display and a 4-button keypad on
the front of the economizer controller.
Fig. 11 - W7220 Controller
Using the Keypad with Menus
To use the keypad when working with menus:
Press the ▲ (Up arrow) button to move to the previous menu.
Press the ▼ (Down arrow) button to move to the next menu.
Press the (Enter) button to display the rst item in the currently displayed menu.
Press the ↑ (Menu Up/Exit) button to exit a menu’s item and return to the list of menus.
Using the Keypad with Settings and Parameters
To use the keypad when working with Setpoints, System and Advanced Settings, Checkout tests and Alarms:
1. Navigate to the desire menu.
2. Press the (Enter) button to display the rst item in the currently
displayed menu.
3. Use the ▲ and ▼ buttons to scroll to the desired parameter.
4. Press the (Enter) button to display the value of the currently
displayed item.
5. Press the ▲ button to increase (change) the displayed parameter
value.
6. Press the ▼ button to decrease (change) the displayed parameter value.
NOTE: When values are displayed, pressing and holding the ▲ or ▼ button causes the display to automatically increment.
7. Press the (Enter) button to accept the displayed value and store
it in nonvolatile RAM.
8. “CHANGE STORED” displays.
9. Press the (Enter) button to return to the current menu parameter.
10. Press the ↑ (Menu Up/Exit) button to return to the previous
menu.
Menu Structure
Table 5 illustrates the complete hierarchy of menus and parameters for
the EconoMi$er X system.
The Menus in display order are:
STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
CHECKOUT
ALARMS
Keypad
The four navigation button (see Fig. 11) are used to scroll through the
menus and menu items, select menu items, and to change parameter and
conguration settings.
IMPORTANT NOTE: The default setting on the W7220 controller is for a “Fan Type” with 2 speed, which is correct for 2 or 3 speed units (48/50LC 07-12). If your unit is 1 (single) speed, the setting under SYSTEM SETUP > FAN TYPE must be changed to 1 speed.
8
IMPORTANT: Table 4 illustrates the complete hierarchy. Your menu parameters may be different depending on your conguration. For example if you do not have a DCV (CO2) sensor, then none of the DCV parameters appear.
a
Notes
Menu Parameter
Parameter
Default
Value
Table 5 Menu Structure
Parameter
Range and Increment
b
STATUS ECON AVAIL NO YES/NO YES = economizing available; the system can use
outside air for free cooling when required
ECONOMIZING NO YES/NO YES = outside air being used for 1st stage cooling
OCCUPIED NO YES/NO YES = OCC signal received from space thermostat
or unitary controller YES = 24 Vac on terminal OCC. NO = 0 Vac on terminal OCC.
HEAT PUMP n/a
c
COOL HEAT
Displays COOL or HEAT when system is set to heat pump (Non-conventional)
COOL Y1─IN OFF ON/OFF Y1─I signal from space thermostat or unitary controller for
cooling stage 1.
ON = 24 Vac on terminal Y1─I OFF = 0 Vac on terminal Y1─I
COOL Y1─OUT OFF ON/OFF Cool stage 1 Relay Output to stage 1 mechanical cooling
(Y1─OUT terminal)
COOL Y2─IN OFF ON/OFF Y2─I signal from space thermostat our unitary controller for
second stage cooling.
ON = 24 Vac on terminal Y2─I OFF = 0 Vac on terminal Y2─I
COOL Y2─OUT OFF ON/OFF Cool Stage 2 Relay Output to mechanical cooling
(Y2─OUT terminal)
MA TEMP _ _ . _oF 0 to 140oF Displays value of measured mixed air from MAT sensor.
Displays _ _ . _ oF if not connected, short or out-of-range.
DA TEMP _ _ . _oF 0 to 140oF Displays when Discharge Air sensor is connected and
displays measured discharge temperature. Displays _ _ . _oF if sensor sends invalid value, if not con­nected, short or out-of-range.
OA TEMP _ _ . _oF -40 to 140oF Displays measured value of outdoor air temperature.
Displays _ _ . _oF if sensor sends invalid value, short or out-of-range.
OA HUM _ _% 0 to 100% Displays measured value of outdoor humidity from OA
sensor. Displays _ _% if not connected short, or out-of-range.
RA TEMP _ _ . _oF 0 to 140oF Displays measured value of return air temperature from
RAT sensor. Displays _ _ . _oF if sensor sends invalid value, if not connected, short or out-of-range
RA HUM _ _% 0 to 100% Displays measured value of return air humidity from RA
sensor. Displays _ _% if sensor sends invalid value, if not con­nected, short or out-of-range
IN CO2 _ _ _ppm 0 to 2000 ppm Displays value of measured CO2 from CO2 sensor. Invalid if
not connected, short or out-of-range
DCV STATUS n/a ON/OFF Displays ON if above setpoint and OFF if below setpoint,
and ONLY if a CO2 sensor is connected.
DAMPER OUT 2.0V 2.0 to 10.0V Displays voltage output to the damper actuator.
EXH1 OUT OFF ON/OFF Output of EXH1 terminal:
ON = relay closed OFF = relay open
EXH2 OUT OFF ON/OFF Output of AUX terminal; displays only if AUX = EXH2
ERV OFF ON/OFF Output of AUX terminal; displays only if AUX = ERV
MECH COOL ON 0 0,1, or 2 Displays stage of mechanical cooling that is active.
9
Table 5 Menu Structurea (cont)
Menu Parameter
Default
Value
SETPOINTS MAT SET 53oF 38 to 65oF;
LOW T LOCK 32oF -45 to 80oF;
DRYBLB SET 63oF 48 to 80oF;
ENTH CURVE ES3 ES1,ES2,ES3,ES4, or
DCV SET 1100ppm 500 to 2000ppm;
MIN POS 4.4 V 2 to 10 Vdc Displays ONLY if a CO2 sensor is NOT connected
Parameter
VENTMAX With 2-speed
4.4 V 2 to 10 Vdc fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan) settings are required
VENTMAX L 6 V
VENTMAX H 4.4 V
VENTMIN With 2-speed
2.8 V 2 to 10 Vdc fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan) set
VENTMIN L 3.7 V
VENTMIN H 2.8 V
ERV OAT SP 32oF 0 to 50oF;
EXH1 SET With 2-speed
50% 0 to 100%; fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required
Exh1 L 65%
Exh1 H 50%
EXH2 SET With 2-speed
75% 0 to 100%; fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are required
Exh2 L 80%
Exh2 H 75%
SYSTEM
INSTALL 01/01/10 Display order = MM/DD/YY
SETUP
UNITS DEG
o
F
EQUIPMENT CONV Conventional or HP CONV = conventional; HP O/B = Enable Heat Pump mode. Use AUX2 I
AUX2 I W SD/W or HP(O)/HP(B) In CONV mode: SD + Enables conguration of shutdown (default); W
FAN TYPE 2 speed 1 speed/2 speed
FAN CFM 5000cfm 100 to 15000 cfm;
AUX OUT NONE NONE
OCC INPUT INPUT or ALWAYS When using a setback thermostat with occupancy out (24 Vac), the 24
Parameter
Range and Increment
increment by 1
increment by 1
increment by 1
ES5
increment by 100
or 100 to 9990 cfm increment by 10
or 100 to 9990 cfm increment by 10
increment by 1
increment by 1
increment by 1
o
F or oC Sets economizer controller in degrees Fahrenheit or Celsius
increment by 100
ERV EXH2 SYS
b
Notes
Setpoint determines where the economizer will modulate the OA damper to maintain the mixed air temperature.
Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout.
Setpoint determines where the economizer will assume outdoor air temperature is good for free cooling; e.g.; at 63oF unit will economize at 62oF and below and not economize at 64oF and above. There is a 2oF deadband.
Enthalpy boundary “curves” for economizing using single enthalpy
Displays only if CO2 sensor is connected. Setpoint for Demand Control Ventilation of space. Above the setpoint, the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint.
Displays only if a CO2 sensor is connected. Used for Vbz (ventilation max cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA,OA, and MA). In AUTO mode dampers controlled by CFM
Displays only if a CO2 sensor is connected. Used for Ba (ventilation min cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA, and MA). Va is only set if DCV is used. This is the ventilation for less than maximum occupancy of the space. In AUTO mode dampers controlled by CFM.
Only when AUX1 O = ERV
Setpoint for OA damper position when exhaust fan 1 is powered by the economizer.
Setpoint for OA damper position when exhaust fan 2 is powered by the economizer. Only used when AUX is set to EHX2.
Setting order = DD, MM, then YY.
for Heat Pump input from thermostat or controller.
= Informs controller that system is in heating mode. In HP O/B mode: HP(O) = energize heat pump on Cool (default); HP(B) = energize heat pump on heat.
Sets the economizer controller for operation of 1 speed or 2 speed supply fan. (Note: for 3 speed units (48/50LC 07-12), setpoint is a 2 speed.)
This is the capacity of the RTU. The value is found in the Project
Submittal documents for the specic RTU.
• NONE = not congured (output is not used)
• ERV = Energy Recovery Ventilatio
n
• EXH2 = second damper position relay closure for second exhaust fan
• SYS = use output as an alarm signal
Vac is input “INPUT” to the OCC terminal. If no occupancy output from the thermostat then change program to “ALWAYS” OR add a jumper from terminal R to OCC terminal
10
Table 5 Menu Structurea (cont)
Menu Parameter
Default
Value
Parameter
SYSTEM
FACTORY DEFAULT NO NO or YES Resets all set points to factory defaults when set to YES. LCD will
SETUP
ADVANCED
MA LO SET 45oF 35 to 55oF;
SETUP
FREEZE POS CLO CLO or MIN Damper position when freeze protection is active (closed or MIN POS).
CO2 ZERO 0ppm 0 to 500 ppm;
CO2 SPAN 2000ppm 1000 to 3000 ppm;
STG3 DLY 2.0h 0 min, 5 min, 15 min,
SD DMPR POS CLO CLO or OPN Indicates shutdown signal from space thermostat or unitary controller.
DCVCAL ENA MAN MAN (manual)
MAT T CAL 0.0oF +/-2.5oF Allows for the operator to adjust for an out of calibration temperature
OA T CAL 0.0oF +/-2.5oF Allows for the operator to adjust for an out of calibration temperature
OA H CAL 0% RH +/-10% RH Allows for operator to adjust for an out of calibration humidity sensor.
RA T CAL 0.0oF +/-2.5oF Allows for the operator to adjust for an out of calibration temperature
RA H CAL 0% RH +/-10% RH Allows for operator to adjust for an out of calibration humidity sensor.
DA T CA; 0.0oF +/-2.5oF Allows for the operator to adjust for an out of calibration temperature
CHECKOUT DAMPER VMIN─HS n/a n/a Positions damper to VMIN position
DAMPER VMAX─HS n/a n/a Positions damper to VMAX position
DAMPER OPEN n/a n/a Position damper to the full open position.
DAMPER CLOSE n/a n/a Positions damper to the fully closed position
CONNECT Y1─O n/a n/a Closes the Y1─O relay (Y1─O)
CONNECT Y2─O n/a n/a Closes the Y2─O relay (Y2─O)
CONNECT AUX n/a n/a Energizes the AUX output. If Aux setting is:
ALARMS(#) Alarms display only when they are active. The menu title
MA T SENS ERR n/a n/a Mixed air sensor has failed or become disconnected - check wiring then
CO2 SENS ERR n/a n/a CO2 sensor has failed, gone out of range or become disconnected -
OA SYLK T ERR n/a n/a Outdoor air enthalpy sensor has failed or become disconnected - check
OA SYLK H ERR n/a n/a
RA SYLK T ERR n/a n/a Return air enthalpy sensor has failed or become disconnected - check
RA SYLK H ERR n/a n/a
DA SYLK T ERR n/a n/a Discharge air sensor has failed or become disconnected - check wiring
OA SENS T ERR Outdoor air temperature sensor has failed or become disconnected -
Parameter
Range and Increment
Incremented by 1
o
Increment by 10
Increment by 10
then 15 min intervals. Up to 4 h or OFF
AUTO
b
Notes
briey ash YES and change to NO but all parameters will change to
the factory default values.
Temperature to achieve Freeze Protection (close damper and alarm if temperature falls below setup value).
CO2 ppm level to match CO2 sensor start level.
CO2 ppm span to match CO2 sensor.
Delay after stage 2 cool has been active. Turns on 2nd stage of cooling when economizer is 1st stage and mechanical cooling is 2nd stage. Allows three stages of cooling, 1 economizer and 2 mechanical. OFF = no Stage 3 cooling
When controller receives 24 Vac input on the SD terminal in conven­tional mode, the OA damper will open if programmed for OPN and OA damper will close if programmed for CLO. All other controls, e.g., fans, etc. will shut off.
Turns on the DCV automatic control of the dampers. Resets ventilation based on the RA, OA, and MA sensor conditions. Requires all 3 RA, OA, and MA sensors.
sensor.
sensor.
sensor.
sensor.
Exhaust fan contacts enable during the DAMPER OPEN test. Make sure you pause in the mode to allow exhaust contacts to energize due to the delay in the system.
• NONE ─ not action taken
• ERV ─ 24 Vac out. Turns on or signals an ERV that the conditions
are not good for economizing but are for ERV operation.
d
• SYS ─ 24 Vac out. Issues a system alarm
“ALARMS(#)” includes the number of active alarms in parenthe­sis ( ). When using SYLK bus sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will appear on the screen
replace sensor if the alarm continues.
check wiring then replace sensor if the alarm continues.
wiring then replace sensor if the alarm continues.
wiring then replace sensor if the alarm continues.
then replace sensor if the alarm continues
check wiring then replace if the alarm continues.
11
Table 5 Menu Structurea (cont)
Menu Parameter
Default
Value
Parameter
ALARMS(#)
ACT ERROR n/a n/a Actuator has failed or become disconnected - check for stall, over
CONTINUED
FREEZE ALARM n/a n/a Check if outsoor temperature is below the LOW Temp Lockout on
SHUTDOWN ACTIVE n/a n/a AUX2 IN is programmed for SHUTDOWN and 24 V has been applied
DMP CAL RUNNING n/a n/a If DCV Auto enalbe has been programmed, when the Jade is
DA SENS ALM n/a n/a Discharge air temperature is out of the range set in the ADVANCED
SYS ALARM n/a n/a When AUX1-0 is set to SYS and there is any alarm (e.g., failed
ACT UNDER V n/a n/a Voltage received by Actuator is above expected range.
ACT OVER V n/a n/a Voltage recieved by Actuator is below expected range.
ACT STALLED n/a n/a Actuator stopped before achieving commanded position.
a
Table 5 illustrates the complete hierarchy. Your menu parameters may be different depending on your conguration.
For example if you do not have a DCV (CO2) sensor, then none of the DCV parameters appear
b
When values are displayed, pressing and holding the ▲ or ▼ button causes the display to automatically increment.
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized.
In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
Parameter
Range and Increment
b
Notes
voltage, undervoltage and actuator count. Replace actuator if damper is moveable and supply voltage is between 21.6 V and 26.4 V. Check actuato count on STATUS menu
setpoint menu. Check if Mixed air temperature on STATUS menu is below the Lo Setpoint on Advanced menu. When conditions are back in normal range then the alarm will go away.
to AUX 2IN terminal.
completing a calibration on the dampers, this alarm will display. Wait until the calibration is completed and the alarm will go away. Must have OA, MA and RA sensors for DCV calibration; set up in the Advanced setup menu.
SETUP Menu. Check the termperature of the discharge air.
sensors, etc.), the AUX1-0 terminal has 24 Vac out.
12
Checkout Tests
Use the Checkout menu (see Table 5) to test the damper operation and any congured outputs. Only items that are congured are shown in the Checkout menu.
NOTE: See User Interface on page 3 for information about menu navi­gation and use of the keypad.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the ▲ and ▼ buttons.
2. Press the button to select the item.
3. RUN? appears.
4. Press the button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all desired parameters have been tested, press the ↑ (Menu up) button to end the test.
Checkout test can be performed at any time during the operation of the
system as a test that the system is operable.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to equipment
Be sure to allow enough time for compressor startup and shutdown between checkout tests so that you do not short-cycle the compressors.
Table 6 - Economizer Module -
Left Hand Terminal Blocks
Label Type Description
Top Left Terminal Block
MAT MAT
OAT OAT
S─BUS S─BUS
20k NTC and COM
20k NTC and COM
S─BUS
(Sylk Bus)
Mixed Air Temperature Sensor (Polarity insensitive connections)
Outdoor Air Temperature Sensor (Polarity insensitive connection)
Enthalpy Control Sensor (Polarity insensitive connection)
Bottom Left Terminal Block
IAQ 2─10 2─10 Vdc Air Quality Sensor Input
(e.g. CO2 sensor)
IAQ COM COM Air Quality Sensor Common
IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source
ACT 2─10 2─10 Vdc Damper Actuator Output (2─10 Vdc)
ACT COM COM Damper Actuator Output Common
ACT 24V 24 Vac Damper Actuator 24 Vac Source
Table 7 - Economizer Module -
Right Hand Terminal Blocks
SETUP AND CONFIGURATION
W7220 Economizer Module Wiring
Use Fig. 12 and Tables 6 and 7 to locate the wiring terminals for the
economizer module.
NOTE: The four terminal blocks are removable. You can slide out each terminal block, wire it, and then slide it back into place.
HJW10
50048848-002
NA
AUX2-
OCC
E-GND
EXH1
AUX1-O
Y2-
Y2-O
Y1-
Y1-O
C
R
Rev. A
MAT
MAT
OAT
OAT
S-BUS
S-BUS
IAQ 2-10
IAQ COM
IAQ 24V
ACT 2-10
ACT COM
ACT 24V
50040839-001
Rev. G
MA MA
OA OA
SB SB
SB SB
SB SB
V C R
V C R
NA
NA
A2
OCC
EX
A1
Certied FDD Product
California Title 24, Part 6
www.energy.ca.gov
Y2I
Y2O
Y1I
Y1O
C
R
Fig. 12 - W7220 Economizer Module Terminal
Connection Labels
Label Type Description
Top Right Terminal Block
n/a The rst terminal is not used
AUX2 I 24 Vac IN Shut Down (SD) or Heat (W)
Conventional only and Heat Pump Changeover (O?B) in Heat Pump mode.
OCC 24 Vac IN Occupied / Unoccupied Input
E - GND E─GND Earth Ground - System Required
EXH1 24 Vac OUT Exhaust Fan 1 Output
AUX1 O 24 Vac OUT Programmable:
Exhaust fan 2 output or ERV or System alarm output
Bottom Right Terminal Block
Y2─1 24 Vac IN Y2 in - Cooling Stage 2 Input from
space thermostat
Y2─O 24 Vac OUT Y2 out - Cooling Stage 2 Output to
stage 2 mechanical cooling
Y1─I 24 Vac IN Y1 in - Cooling Stage 2 Input from
space thermostat
Y1─O 24 Vac OUT Y1 out - Cooling Stage 2 Output to
stage 2 mechanical cooling
C COM 24 Vac Common
R 24 Vac 24 Vac Power (Hot)
Time-out and Screen Saver
When no buttons have been pressed for 10 minutes, the LCD displays a screen saver, which cycles through the Status items. Each Status item displays in turn and cycles to the next item after 5 seconds.
13
HH79ZZ007 Dry Bulb Sensor
Economizers are shipped standard with an HH79ZZ007 outside air dry bulb sensor, which looks like an eyelet terminal with 2 green wires. This sensor is factory installed on the front of the economizer in the out-
20k Sensor
GREEN
1/4 Terminal (2)
side air stream. System default setting (high temp limit) is 63 degrees F, and has a range of 48 to 80 degrees F. Note: a 2nd HH79ZZ007 sensor is provided for mixed (supply) air temperature.
NOTE: California high temperature setting requirements by region are
shown below.
Device Type
a
Climate Zones
Fig. 12A - HH79ZZ007 Sensor
Required High Limit (Economizer Off When):
Description
GREEN
1, 3, 5, 11-16 Outdoor air temperature exceeds 75°F
Fixed Dry Bulb
2, 4, 10 Outside air temperature exceeds 73°F
6, 8, 9 Outdoor air temperature exceeds 71°F
7 Outdoor air temperature exceeds 69°F
1, 3, 5, 11-16 Outdoor air temperature exceeds return air temperature
Differential Dry Bulb
2, 4, 10 Outdoor air temperature exceeds return air temperature minus 2°F
6, 8, 9 Outdoor air temperature exceeds return air temperature minus 4°F
7 Outdoor air temperature exceeds return air temperature minus 6°F
Fixed Enthalpyb + Fixed
Dry Bulb
a
Only the high limit control devices listed are allowed to be used and at the setpoints listed. Others such as Dew Point, Fixed
All
Outdoor air enthalpy exceeds 28 Btu/lb of dry airb or
Outdoor air temperature exceeds 75°F
Enthalpy, Electronic Enthalpy, and Differential Enthalpy Controls, may not be used in any climate zone for compliance with Sec­tion 140.4(e)1 unless approval for use is provided by the Energy Commission Executive Director.
b
At altitudes substantially different than sea level, the Fixed Enthalpy limit value shall be set to the enthalpy value at 75°F and
50% relative humidity. As an example, at approximately 6,000 foot elevation, the xed enthalpy limit is approximately 30.7 Btu/lb.
Table 8 - California Title 24 Regional High Limit Dry Bulb Temperature Settings
TABLE 140.4-B AIR ECONOMIZER HIGH LIMIT SHUT OFF CONTROL REQUIREMENTS
Fig. 13 - Single Enthalpy Curve boundaries
14
Table 9 - Single Enthalpy and Dual Enthalpy High Limit Curves
Enthalpy
Curve
ES1 80.0 60.0 28.0 80.0 36.8 66.3 80.1
ES2 75.0 57.0 26.0 75.0 39.6 63.3 80.0
ES3 70.0 54.0 24.0 70.0 42.3 59.7 81.4
ES4 65.0 51.0 22.0 65.0 44.8 55.7 84.2
ES5 60.0 48.0 20.0 60.0 46.9 51.3 88.5
HL 86.0 66.0 32.4 86.0 38.9 72.4 80.3
Temp.
Dry Bulb (oF)
Temp.
Dewpoint (oF)
Enthalpy
(btu/lb/da)
Temp (oF) Humidity %RH Temp (oF)
Point P1 Point P2
Enthalpy Settings (Optional Accessory)
If installing the optional HH57AC081 enthalpy sensor. The HH79AH001 dry bulb outside air sensor must rst be removed. Wire enthalpy to S-BUS connections on W7220 controller thru (2) gray wires.
When the OA temperature, enthalpy and dew point are below the respective setpoints, the Outdoor Air can be used for economizing. Fig. 13 shows the new single enthalpy boundaries in the W7220. There are 5 boundaries (setpoints ES1 thru ES5), which are dened by dry bulb temperature, enthalpy and dew point.
Refer to Table 9 for ENTH CURVE setpoint values.
To use enthalpy the W7220 must have a HH57AC081 enthalpy control sensor for OA. The W7220 calculates the enthalpy and dewpoint using the OA temperature and humidity input from the OA sensor. When the OA temperature, OA humidity and OA dew point are all below the selected boundary, the economizer sets the economizing mode to YES,
economizing is available.
When all of the OA conditions are above the selected boundary, the conditions are not good to economize and the mode is set to NO.
Fig. 13 shows the 5 current boundaries. There is also a high limit boundary for differential enthalpy. The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL (high limit) when a compressor stage is energized.
Table 8 provided the values for each boundary limit.
If using OA enthalpy sensor HH57AC081 accessory, remove and
discard the dry bulb sensor shipped with the economizer. System enthalpy default is ES3 curve.
See Table 8 for California Title 24 high limit settings.
Enthalpy control Sensor Conguration
The optional Enthalpy Control sensor (Part Number: HH57AC081) communicates with the W7220 Economizer controller on the two-wire communications bus and can either be wired using a two pin header or
using a side connector. This sensor can be used for outdoor enthalpy,
or indoor dry bulb or enthalpy depending on the dip-swtich setting. System enthalpy default is ES3 curve. See Table 8 for California Title 24 high limit settings.
Use Fig. 14 and Table 10 to locate the wiring terminals for each
Enthalpy Control sensor.
Use Fig. 14 and Table 11 to set the DIP switches for the desired use of
the sensor.
If using differential (return) enthalpy or temperature, see Table 8 for California Title 24 setting requirements by region.
(Used for Outdoor Enthalpy, or Indoor Return
Nbr Label
1 S─BUS S─BUS
2 S─BUS S─BUS
a DA = Discharge Air or Supply Sensor b RA = Return Air c OA = Outside Air
Fig. 14 - HH57AC081 Accessory
Temperature or Enthalpy)
Table 10 - HH57AC081 Sensor
Wiring Terminations
Terminal
Type Description
S─Bus Communications
(Enthalpy Control Sensor Bus)
S─Bus Communications
(Enthalpy Control Sensor Bus)
Table 11 - HH57AC081 Sensor DIP Switch
Use
DA
RA
OA
DIP Switch Positions for Switches 1,2, & 3
1 2 3
a
b
c
OFF ON OFF
ON OFF OFF
OFF OFF OFF
Humidity
%RH
a
15
OPERATION
Cooling, Unit with EconoMi$er X
For Occupied mode operation of EconoMi$er X, here must be a 24-v signal at terminals R and OCC (provided through PL6-3 from the unit’s IFC coil). Removing the signal at OCC places the EconoMi$er X control in Unoccupied mode.
During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a Cooling (by free cooling) or DCV demand is received.
When free cooling using outside air is not available, the unit cooling sequence will be controlled directly by the space thermostat. Outside air damper position will be closed or Minimum Position as determined by Occupancy mode and fan signal.
When free cooling is available as determined by the appropriate
changeover command (dry bulb, outdoor enthalpy, differential dry bulb or differential enthalpy), a call for cooling (Y1 closes at the thermostat)
will cause the economizer control to modulate the dampers open and closed to maintain the unit supply air temperature. Default supply air temperature is 53°F, with a range of 38° to 70°F. Compressor will not
run.
Should 100% outside air not be capable of satisfying the space temperature, space temperature will rise until Y2 is closed. The economizer control will call for compressor operation. Dampers will modulate to maintain SAT at setpoint concurrent with Compressor 1 operation. The “Low T Temp” setting (default 32°F) will lock out
compressor operation.
When space temperature demand is satised (thermostat Y1 opens), the dampers will return to Minimum Damper position if indoor fan is
running or fully closed if fan is off.
If accessory power exhaust is installed, the power exhaust fan motors will be energized by the economizer control as the dampers open above the EXH1 SET setpoint and will be-energized as the dampers close below the EXH1 SET setpoint.
Damper movement from full closed to full open (or vice versa) will take between 1-1/2 and 2-1/2 minutes.
Heating with EconoMi$er X
During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a DCV
demand is received.
When the room temperature calls for heat (W1 closes), the heating
controls are energized.
Demand Controlled Ventilation
If a eld-installed CO2 sensor is connected to the EconoMi$er X control, a Demand controlled Ventilation strategy will operate automatically. As the CO2 level in the space increases above the setpoint (on the EconoMi$er X controller), the minimum position of the dampers will
be increased proportionally, until the Maximum Ventilation setting is
reached. As the space CO2 level decreases because of the increase in fresh air, the outdoor damper will follow the higher demand condition from the DCV mode or from the free cooling mode.
DCV operation is available in Occupied and Unoccupied periods with EconoMi$er X. However, a control modication will be required on the units to implement the Unoccupied period function.
Table 12 - Damper Position Control, 2-Speed Fan Motor, Economizer Cooling Not Available
INPUT
OCC 0 - V 24 - V 24 - V 24 - V 24 - V
Y1 0 - V 0 - V 24 - V 24 - V 0 - V
Y2 0 - V 0 - V 0 - V 24 - V 0 - V
W1 0 - V 0 - V 0 - V 0 - V 24 - V
SUPPLY FAN
MOTOR SPEED
DAMPER POSITION
NO CI2 SENSOR CLOSED MIN POS MIN POS MIN POS MIN POS
W/ CO2 SENSOR CLOSED
OFF LOW LOW HIGH HIGH
FROM
VENTMIN L
TO
VENTMAX L
FROM
VENTMIN L
TO
VENTMAX L
FROM
VENTMIN H
TO
VENTMAX H
FROM
VENTMIN H
TO
VENTMAX H
16
TROUBLESHOOTING
Power Loss (Outage or Brownout)
All setpoints and advanced settings are restored after any power loss
or interruption, as all settings are stored in the Economizer controller’s
non-volatile ash memory. NOTE If the power goes below 18 Vac, the W7220 controller module assumes a power loss and the 5 minute power up delay will become functional when power returns above 18 Vac.
Clearing Alarms
Once the alarm has been identied and the cause has been removed (e.g. replaced faulty sensor). The can be cleared from the display. To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the button.
3. ERASE? displays.
4. Press the button.
5. ALARM ERASED displays.
Alarms
The Economizer module provides alarm messages that display on the
2-line LCD NOTE: Upon power up, the module waits several seconds before
6. Press the ↑ (Menu up/Exit) button to complete the action and
return to the previous menu. NOTE: If the alarm still exists after you clear it, it is redisplayed
within 5 seconds.
checking for alarms. This allows time for all the congured devices (e.g. sensors, actuator) to become operational. If one or more alarms are present and there has been no keypad activity for at least 5 minutes, the Alarms menu displays and cycles through the
active alarms.
You can also navigate to the Alarms menus at any time. See Table 5 for the Alarms menu.
Table 13 - Operating Issues and Concerns
Issue or Concern Possible Cause and Remedy
My outdoor temperature reading on the STATUS menu is not accurate
If my enthalpy sensor drifts in accuracy over time, can I re-calibrate it?
Can I go back to factory defaults and start over?
Will I be able to see the LCD screen when it is in the unit?
What is a good setpoint for the Mixed Air Temperature (MAT)?
I am using enthalpy sensors. Why did the control ask me to input a dry bulb changeover temperature?
In checkout, the outdoor damper closes when I command it to open.
How do I set my minimum position? The minimum position is set using the VENTMIN and VENTMAX setup in the
What if my damper does not go completely closed in the checkout operation?
How do I set the OCC? There are two setting for the OCC setting, INPUT and ALWAYS, INPUT is from the
Does the economizer save my program val­ues if the unit loses power?
If the unit is left in checkout, how long will the unit stay in checkout mode without input?
Check the sensor wiring:
• Enthalpy sensors are to be wired to the S-Bus terminals.
• Temperature sensors are to be wired to the OAT and MAT terminals.
The sensor is not able to be re-calibrated in the eld. However there is a menu
item under the ADVANCED menu where you are able to input a limited off set in temperature and humidity for each sensor you have connected to the economizer.
Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults.
The LCD screen has a backlight that is always illuminated.
The mixed are temperature is the temperature of air that you want to supply to the space. In a commercial building, this is between 50 to 55oF (10 to 13oC). The mixed are is the mixing of the return air and the outdoor air.
In the even the humidity sensor in the enthalpy sensors fails, the backup algorithm in the control is to default to the temperature sensor in the enthalpy sensor.
Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper should drive open or closed with the return air damper having the opposite effect.
SETPOINTS menu. VENTMIN is the minimum ventilation required when using an occupancy sensor and VENTMAX is the minimum ventilation when not using an occupancy sensor for Demand Control Ventilation. The VENTMAX position is set the dame as with the potentiometer on the analog economizers and is the output voltage to the damper actuator. The range is 2 Vdc closed OA damper and 10 Vdc open OA damper.
Check the damper linkage or hub to make sure the damper is able to close completely.
space thermostat, if it has an occupancy output. ALWAYS is the unit in the occupied mode, if the economizer is powered (fan on).
Yes, once the changes are stored in the controller they will be stored until they are changed by the operator.
The unit will remain in checkout for 10 minutes, then return to normal operation.
17
Fig. 15 - Barometric Relief Flow Capacity
0
500
1000
1500
2000
2500
0 0.05 0.1 0.15 0.2 0.25 0.3
RELIEF FLOW (CFM)
RETURN DUCT STATIC PRESSURE (in. wg)
Small
Cabinet
Large and
Extra
Large
Cabinet
0
1000
2000
3000
4000
5000
6000
0 0.1 0.2 0.3 0.4
RETURN AIR FL OW (CFM)
RETURN DUCT STATIC PRESSURE DROP (i n. wg)
Small Cabinet
Large Cabinet
Extra Large C abinet
Fig. 16 - Return Air Pressure Drop
Copyright 2014 Carrier Corporation ● 7310 W. Morris St. ● Indianapolis, IN
Manufacturer reserves the right to discontinue, or change at any time, specication or designs without notice and without incurring obligations
Catalog No. IIK-CRECOMZR76-02Edition Date: 04/14
Replaces: IIK-CRECOMZR076-01
18
Loading...