Carrier CRDMNDGW001A00, CRDMNDGW002A00 Installation Instructions Manual

Page 1
CRDMNDGW001A00 CRDMNDGW002A00 Energy Demand Gateway Rooftop Unit Accessory
Installation Instructions
C13331
NOTE: Read the entire instruction manual before starting the installation, and follow instructions carefully. Failure to do so may damage equipment, void warranties, or even cause serious injuries.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings and cautions included in literature and attached to the unit. Consult local building codes and the current edition of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING,andCAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies hazards, which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
on
INTRODUCTION
Carrierr’s Energy Demand System provides reliable and automated processes to manage the costs of energy consumption. Carrier’s Energy Demand System uses wireless devices incorporating patented Swarm Energy Management algorithms to create a network of coordinated rooftop units to reduce and optimize their energy usage. This system creates a wireless network of rooftop units with Energy Demand Load Controllers communicating through the Energy Demand Gateway.
Each individual Load Controller can independently decide whether it should allow its unit to run by a relay that can break the connection between the rooftop unit and the thermostat. By communicating energy information through the Gateway, units are prevented from running simultaneously when it is not necessary, thereby smoothing out peak demand over time. This method provides the ability to accomplish Demand Management, Demand Response, and energy trending over time.
Carrier offers two accessories that, when combined, make up the Energy Demand System. This technology utilizes Swarm Energy Managementt methodology as a basis for the operating sequence:
S Energy Management Gateway (Coordinator)
(Model Nos. CRDMNDGW001A00, CRDMNDGW002A00):
This model is packaged with a cellular modem and modem enclosure, and is the first controller to be attached to a packaged rooftop unit and powered up. This controller will both monitor/control the attached rooftop unit, as well as act as a communicationsgateway back to the Swarm Energy Management Web Portal, a service provided by REGEN Energy, Inc..
Table 1 – Kit Voltage Requirements
Kit No. Unit Voltage
CRDMNDGW001A00 208/230/460V CRDMNDGW002A00 575V
S Energy Demand Load Controller
(Model Nos. CRDMNDMD001A00, CRDMNDMD002A00):
This load controller is installed on the remaining packaged rooftop units that are to be monitored and controlled.
NOTE: Please ensure you have the correct Installation Instructions for the given type of controller before continuing.
INSTALLATION CONSIDERATIONS
RTU Checklist
Toward the end of this document, there is a RTU checklist that must be filled out for every Gateway (Coordinator) installed. The RTU checklist must be legible. The RTU checklists need to be
scanned and emailed to support@regenenergy.com within 48 hours of the completion of the installation. Providing this
checklist is vital to completing device set--up for operation.
Page 2
Wiring Diagram
A diagram noting all components and their proper wiring is provided. (See Fig. 11)
Installation Report
An Installation Report is provided at the end of this document, where you should record installation notes for each Gateway (Coordinator), and issues encountered.
Recommended Order of Operation To Install the Gateway (Coordinator):
1. Determine where to mount each component.
2. Mount the components.
3. Wire all components.
4. Power up and test the Gateway (Coordinator).
5. Fill out the required RTU Installation Checklist.
6. Fill out the Installation Report.
7. Scan and email “RTU Checklist” and “Installation Report” to fieldops@regenenergy.com within 48 hours of complet­ing device setup.
Preferred Location
(Please note the central location on the rooftop)
Equipment Location:
The first step is to decide which rooftop unit should have the Gateway (Coordinator). This device should be mounted preferably in the middle of the rooftop or on a rooftop unit where other controllers have line of sight access to this rooftop unit. (See Fig.
1.)
Overview Schematic
The components listed below must be installed. Refer to the diagram in Fig. 2. when deciding where to mount each component in relation to the rooftop unit.
Component Installation Location
Energy Demand Gateway
(Coordinator)
Transformer Inside cabinet
4--Pole Relay Inside cabinet
Modem Enclosure Exterior of cabinet
Antenna and Mounting Base Exterior of cabinet, on top
Inside cabinet
Supplied
Transformer
C13332
Fig. 1 -- Preferred Equipment Installation Locations
Supplied
4-Pole Relay
C13333
Fig. 2 -- Component Installation Schematic
2
Page 3
INSTALLATION
Basic list of tools and materials recommended to complete installation:
Material
S Small blue wire nuts S 9/16--in. Rubber grommet S #18 THHN standard wire S #18--22 fork connectors S #18--22 female connectors S #10 tek screws (3/4--in. long) S 5--1/2--in. And 7--1/2--in. zip ties S Tube of clear silicone
Tools
S Cordless drill S Control screw drivers S 1/4--in. Pilot bit S Nut drivers S Crimp tool S Wire strippers
Relay
Transformer
C13334
Fig. 3 -- Transformer and Relay Mounting Examples
Suggested Installation Sequence
1. Disable all power to the rooftop unit.
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect power before opening unit.
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, the main electrical disconnect switch must be in the OFF position. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label.
2. Open the main cabinet and control board cover
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when handling parts.
3. Determine where each component will be mounted: S Modem Enclosure: Mounted vertically, on a side of the
cabinet’s exterior
S Gateway (Coordinator): Mounted inside the cabinet,
such that allows access to the keypad and display. Mounting location examples include, mounting within the unit control box, on a side wall within the unit, or any available panel. Ensure the selected mounting loca­tion does not cause damage to coils or existing compo­nents.
S Antenna & Mounting Base: Mounted on top of the cabi-
net
S Relay: Located inside the cabinet such that it reaches
cooling and heating control lines
S Transformer: Located inside the cabinet such that it can
reach:
a. Transformer primary--side wires will be attached to the
rooftop unit’s load--side leads
b. Transformer secondary--side wires will be attached to
the Gateway (Coordinator) power wires (1 & 2) and modem power lines (24 & 25). See wiring diagram.
Mount Modem Enclosure:
S Modem enclosure should be mounted vertically on an exterior
fixed panel as close to the top of the cabinet as possible position that allows the cover to be opened.
S DO NOT MOUNT THE MODEM ENCLOSURE ON ANY
REMOVABLE DOORS
!
CAUTION
ACCESSORY RELIABILITY HAZARD
Failure to follow this caution may result in accessory component damage.
Installation of Modem Enclosure on moveable doors may make it difficult or impossible to remove doors. This may also result in dropping the door and damaging the attached component or severing wires.
S Choose a side of the cabinet with the least exposure to the sun if
possible.
S Ensure the enclosure’s cables can reach the Gateway
(Coordinator)’s cable inside the cabinet.
S Pass the cables to the cabinet inside the rooftop unit using
existing holes if available, or drill one so the cables can reach the control panel.
S Secure the cables using the black plastic gland (Hand--tighten).
,ina
Mount Gateway (Coordinator):
S Ensure the selected location for the Gateway (Coordinator)
allows access to see the display & use the keypad. (See Fig.4 )
S Ensure extension wire from the Antenna Mounting Base can
reach the top of the Gateway (Coordinator).
S Securely mount the Gateway (Coordinator) using four of the
Mounting Screws
3
Page 4
Coordinator
V
S Plug the Molex connector pair from a CT to one of the matching
connectors on the Gateway (Coordinator) cable.
Connect Data Cables
Attach the 3--wire Molex connector from the Modem Enclosure to the 3--wire Molex connector from the Gateway (Coordinator) (wires 3, 4, 11, 12).
C13335
Fig. 4 -- Gateway (Coordinator) Mounting Examples
Mount Transformer
Securely mount the transformer using 4 of the supplied mounting screws.(SeeFig.5)
Primary Side
Fig. 5 -- Transformer
Secondary Side, 24
C13336
Mount 4--Pole Relay
S Securely mount the 4--pole relay using the 2 supplied mounting
screws.
S The 4--pole relay has a set of pre--kitted wires to simplify
installation.
S When the coil is energized, this will allow the control signals to
pass on to the control board.
S The rooftop unit’s Y1 and Y2, W1 and W2 control lines should
be connected through the relays’ Normally Open control points (See Fig. 11) using the pre--kitted wires.
4-Pole Relay
Transformer
Coordinator
C13339
Fig. 7 -- Data Cable Connection
Install Antenna and Mounting Base
Antenna attached to magnetic mount
Magnetic mount with extension wire passed inside cabinet, attached to top of controller
C13340
Fig. 8 -- Antenna and Mounting Base
S Locate a smooth surface on the top of the cabinet to secure the
Antenna and Antenna Mounting Base. Ensure there is sufficient slack on the extension cable to reach the Gateway (Coordinator) (mounted inside the cabinet). (See Fig. 8)
S Locate a small hole through which the antenna wire can pass
into the cabinet (or drill a hole small enough for the wire). Ensure a 1/2--in. grommet is used to protect wiring from any sharp edges.
S Hand--tightened the Antenna to the Mounting Base. S Hand--tighten the Mounting Base’s extension cable to the
antenna mount on the top of the Gateway (Coordinator). Do not attach the antenna directly to the top of a Gateway (Coordinator).
Fig. 6 -- 4--Pole Relay Mounting Example
Connect Current Sensors (CTS)
S The two current sensors should be carefully clamped around
different legs of the load--side leads, preferably L1 & L2 (L1 is often the leg powering single--phase fan motors; confirm via reading current with a clamp--on meter). (See Fig. 9)
S Ensure the locking tabs are fully secured.
!
CAUTION
ACCESSORY RELIABILITY HAZARD
Failure to follow this caution may result in accessory
C13337
component malfunction. The antenna must be installed outside of the rooftop unit
cabinet to ensure signal broadcast and reception.
S Glue the Antenna Mounting Base to the top of the rooftop unit
using silicone to ensure it remains fixed even under heavy winds.
S Use silicone to seal the hole where the antenna cable exits the
cabinet.
4
Page 5
2 Legs of Load-Side Leads
Locking Tab
CT Molex Connector mated to one of the
Controller Molex
Connectors
CTs
CT secured around
the load-side leads
Fig. 9 -- Connecting Current Sensors
Connect Power Lines
1. Connect the following wires in parallel to the 24V side of the transformer:
a. Modem Enclosure Power (wires 24, 25)
b. Gateway (Coordinator) Power – RED Pair, (wires 1 &
2) (See Fig. 11)
2. Connect the primary side of the transformer to the load--side leads. If a wire extension is required, use stranded 18 AWG wire.
3. When you power up the Gateway the green WAN light & green power light should be solid within one minute of power up. If these lights do not come on please contact RE­GEN Energy’s Operations Center at 949--258--4415, Option #2.
Fig. 10 -- Modem WAN and Power lights
Test Control Line Integration
1. Jumper the control lines to force the blower and compres­sors on.
2. Restore power to the rooftop unit.
3. Press the Gateway (Coordinator)’s ON button to power up the Gateway (Coordinator).
4. Wait until you see the indicators on the left of the display light up in a vertical row.
C13338
C13343
6. After the screen displays “rly”, it will then show “1 2”, where: “1” indicates that Relay 1 (blower control line) is closed (Applies only for Energy Demand Load Controller Accessory) and “2” indicates that Relay 2 (cooling and heat­ing control lines) is closed.
C13344
7. Press B to open Relay 2 and confirm that the compressor(s) turn off (after waiting for any minimum startup runtime de­lays). The display will show “1 –“, indicating that Relay 1 is still closed, yet Relay 2 is now open.
C13341
C13345
C13345
8. Wait 20 minutes and then press B to close Relay 2, and confirm that the compressor(s) resume operation. The dis­play will show“1 2”, indicating that Relay 1 and Relay 2 are both closed.
NOTE: Some control systems may have up startup delays
5. Press the unlock sequence: Y,B, ENTER. Confirm that the OVERRIDE indicator flashes and the screen displays “rly”, indicating that the Gateway (Coordinator) is in Relay Test Mode.
C13342
C13344
NOTE: The selected relay test settings will remain in place for up to 20 minutes, and up to 10 changes can be made to relay settings during each Relay Test, after which the Gateway (Coordinator)
5
Page 6
automatically exits the Relay Test Mode and commences regular
r
operation. After finished the relay test, leave the jumpers connected for at
least five more minutes in order to capture the readings for the maximum load of the unit.
Do not proceed to the next step until the Relay Test completes successfully. The Gateway (Coordinator) can be restarted in Test
mode as many times as desired.
Test Gateway (Coordinator) Signal Strength
1. Disconnect all power to the rooftop unit.
2. Remove jumper wires from control lines.
3. Restore all power to the rooftop unit.
4. Turn the Gateway (Coordinator) on, and wait approximate­ly 20 seconds until the TRAFFIC indicator turns on, indi­cating that the Gateway (Coordinator) is attempting to boot up in regular operation mode
C13359
5. Confirm that the READY indicator turns on, and at least two bars of signal strength are visible. Contact REGEN En­ergy’s Operation Center (949--258--4415, Option No. 2) for assistance if fewer than two signal strength bars are dis­played.
C13360
6. Close the rooftop unit’s control panel and all cabinet doors.
7. Contact REGEN Energy’s Operation Center (949--258--4415, Option No. 2) to notify that the Gateway (Coordinator) has been successfully commissioned (This step does not need to be repeated for each Energy Demand Load Controller).
Load-Side Powe
7
8
Molex
connector
CT Clamp
Sensor 1
CT
Clamp
Sensor 2
Controls
Terminal Board
W1
W2
Y1
18
19
20
21
Modem
Enclosure
9
10
GATEWAY
PWR RS232
GND
Molex
5
6
7
8
connector
Four pole Relay
Omron LY4
Transformer
24VAC-
12VDC
Fig. 11 -- Standard Wiring Schematic for Thermostat Controls (2--Stage Unit)
(COORDINATOR)
12 11
4 3
9
10
11
12
6
13
14
2
5
WIRE NUT CONNECTION
1
24 25
14
15
16
17
FIELD INSTALLED WIRE
Stepdown
Trasformer
FIELD INSTALLED WIRE
From
Thermostat
W1
W2
Y1
Y2
575V 480V
24V
C13361
6
Page 7
Parts List
The following equipment is shipped with each Gateway (Coordinator) Accessory.
1. Gateway (Coordinator) Controller
2. Magnetic antenna base
3. Antenna
4. Modem enclosure (with modem inside)
5. (2) Current Transformers
6. 4--Pole Relay (pre--wired with extension wires)
7. Mounting screws (supplied in a plastic bag, not displayed below
1. Gateway (Coordinator) Controller
4. Modem Enclosure
5. (2) Current Transformers
(with modem inside)
Fig. 12 -- Supplied Parts included with Each Gateway (Coordinator) Accessory
2. Magnetic antenna base
3. Antenna
6. 4-Pole Relay (pre-wired with extension wires)
C13362
7
Page 8
Site Installation Report
Section 1.- Site Summary
Customer Name
Site Address
Customer Phone Number
Customer Email
Installation Contractor
Section 2.- Installation Details
Qty. of Modems/Gateways (Coordinators) Shipped Installed
Qty. of Load Controllers Shipped Installed
Qty. of 4-Pole Relays Shipped Installed
Qty. of Transformers Shipped Installed
Qty. of Antennas Shipped Installed
Section 3.- Installation Issues
Facility Roof Access Delays: (Ex.: Security, Escort. Clearances, etc.)
List of any RTU #s not operational/disrepair:
(Ex.: RTUs shut down, locked out for service, obvious mechanical problems, etc.)
Customer Name (Print Name) Installer Name (Print Name)
Signature Signature
Date Date
8
Page 9
Gateway (Coordinator) RTU Checklist
Gateway (Coordinator) Installation Checklist
Site
RTU #, Zone Name
Controller ID
Tod a y ’ s D a t e
Installer Name
REGEN Energy Operations Center/Support- (949) 258-4415, Option #2
Step Notes
1 Power off RTU
2 Install Gateway (Coordinator) and components, incl.
wiring. Install Modem Enclosure, wire to Gateway (Coordi­nator) inside cabinet.
3 Connect test jumper wires: R to lines on relay that will be
connected to original G, Y1, Y2 lines.
4 Glue antenna base, caulk any drilled openings
5 Pause if need to return to previous RTU after
waiting for portal test, note time
6 Power up RTU
7 Confirm modem WAN light is on within one min. After
power up
8 Wait until blower and all stages of cooling are
energized, note any startup
9 Once all stages of cooling energized, measure
amperage on lines where CTs are clamped, measure incoming voltage
10 Perform relay test
UP, DOWN, ENTER
Factor in any blower/compressor min. run times and start delays, note any shutdown delays
111 Exit the relay test to start regular operation
12 Confirm READY indicator and at least two bars of signal
strength. Change Zigbee channel if directed by REGEN support.
UP, DOWN, UP, UP, ENTER
Note time
13 Move to next RTU, waiting at least 20 min. to
return
14 When you return, power off RTU
15 Remove jumper wires and dress wiring (e.g. tie wraps,
sticky backs)
16
Power up RTU & confirm controller connects to net­work (Confirm READY indicator and at least two
bars of signal strength)
delays
Time Paused: Time Resumed:
Blower Delay
st
stage Delay
1
nd
stage Delay
2
Incoming Voltage: 277/480/120/208 CT1 Amps: CT2 Amps:
Blower Delay:
Channel (default of 11 or new value): #ofbars:
9
Page 10
Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 05/13
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: CRDMNDGW001--- 01IIK
Replaces: NEW
10
Loading...