Carrier CPLPCONV013A00 Installation Instructions Manual

40,000--130,000 Btu/hr Part Number:
ACCESSORY PROPANE GAS CONVERSION KIT
STANDARD ALTITUDE ONLY 0---2000 FT (0---610 m)
CPLPCONV013A00
Installation Instructions
577B, 577D, 677B, and 677D. (Two --Stage conversion starts on Page 2.)
Single--Stage (1--1/2 -- 5 Tons) Models: 48ES, (“1”) series or later (Examples: 48ES--060130311, 48ES--060130511, 48ES--060130611), 48ES--A, 48ESNA, 48EZ “1” series or later (Examples: 48EZ--060130311, 48EZ--060130511, 48EZ--060130611), 48EZ--A, 48EZNA, 48VL, 48VT, 574D “B” series or later (Examples: 574DNW060130NB, 574DPW060130NB, 574DEW060130NB), 574D*WA, 674D “B” series or later (Examples: 674DNW060130NB, 674DPW060130NB, 674DEW060130NB), 674D*WA, 577C, 677C, and all PY3G except “B” series (Example: PY3GNA060115AB). (Single--Stage conversion starts on Page
10.) NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the National Standards of Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane Installation codes, and Canadian Electrical Code CSA C22.1
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manu­als, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in per­sonal injury or death. CAUTION is used to identify unsafe practic­es which may result in minor personal injury or product and prop­erty damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
SMALL PACKAGED P RODUCTS
!
WARNING
FIRE, EXPLOSION, CARBON MONOXIDE POISONING, PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. The qualified service agency is responsible for the proper installatio n of this kit. The installation is not proper and complete until the operation of the converted furnace is checked as specified in the manufacturer ’s instructions supplied in the kit.
AVERTISSEMENT
!
FEU, EXPLOSION, EMPOISONNEMENT PAR CARBON DE MONOXYDE, RISQUE DE DOMMAGEÀLAPROPRIÉTÉ
La négligeance de suivre l’avis suivant, peut causer des blessures personnelles, la mort ou du dommage à la propriété.
Cette trousse de conversion doit être installée par un Entrepreneur qualifié, selon les instructions du fabricant et doit se conformer à toutes les exigences et tout les codes pertinents de l’autorité compétente. L’Entrepreneur qualifié est responsable, et doit s’assurer de bien suivre les instructions dans cet avis. L’installation sera considèrèè conforme et rencontrant les spécifications et instructions du fabriquant qui sont inclus dans la trousse, seulement aprés vérification de l’opération de la fournaise convertie.
!
.
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit components.
Before converting a unit to propane gas, remove the burner assembly and inspect the heat exchanger tubes. If there are V-- shaped NOx baffles installed in the firing tubes, (see Fig. 1). THEY MUST BE REMOVED PRIOR TO CONVERTING THIS UNIT TO PROPANE GAS.
CAUTION
1
Propane Gas Orifice #49* LH32RF073 3 Propane Gas Orifice #51* LH32RF067 3 Propane Gas Orifice #53* LH32RF060 3 Propane Gas Orifice #55* LH32RF052 3
Regulator Spring (92--- 0659) EF39ZW023 2
Nipple,1/8in.NPTx2in.(51mm) CA01CA010 1
ClosePipeNipple,1/8in.NPTx3/4in.(19mm) CA01CA001 2
Propane Conversion Label (Rating Plate) 48VL500206 1
Propane Conversion Label (Installer Responsibility) 48VL500207 1
Propane Conversion Warning Label (Gas Valve) 48DU500076 1
*Refer to Table 4 to determine the correct orifice to use.
Firing Tube
CPLPCONV
Table 1 – Two--Stage Kit Contents
ITEM PAR T NO. QUANTITY
Installation Instructions I I K --- C P L P C O N V --- 1 4 1
Pressure Switch HK02LB008 1
90oElbow, 1/8 in. NPT CA05RA001 2
Wire Harness 48DU400080 1
Burner Insert 48GS500465 3
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main
NOx Baffle
power to system. There may be more than one disconnect switch and install lockout tag.
A01051
Fig. 1 -- Low NOx Baffle Location
!
WARNING
EXPLOSION, PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury or death.
This unit is designed to operate at a minimum 10.0 IN. W.C. of manifold pressure on high stage with propane gas. Refer to Table 4 for proper manifold pressure settings for high stage and low stage.
TWO--STAGE KIT INTRODUCTION
These instructions cover the installation of a propane gas conversion kit on models 48DT, 48DU, 48XL, 48XT, 577B, 577D, 677B and 677D that are equipped with a White Rodgers 2--stage combination automatic gas valve regulator.
DESCRIPTION AND USAGE
This Two-- Stage kit is applicable to units with heating inputs from 40,000 to 130,000 Btu/hr installed at standard altitudes from 0 ft to 2000 ft (0 to 610 m). It cannot be used for high altitude installation. High altitude conversion (2001--6000 ft) (610--1829 m) must use kit CPLPCONV014A00.
TWO--STAGE KIT INSTALLATION
!
WARNING
FIRE, EXPLOSION, ELECTRICAL HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Gas supply MUST be shut off before disconnecting electrical power and proceeding with conversion.
1. Turn off gas supply first, then power to unit.
2. Remove the control access panel from unit.
3. Disconnect the gas pipe from the gas valve.
4. Remove the screw attaching the gas manifold to the basepan, and partially slide out the entire burner rack assembly from unit. Save screw. The fan partition mounting bracket may be removed for easier access to the burner assembly. The bracket may be removed by removing 2 screws (located on the left side of the control compartment on the fan partition panel) and sliding the bracket forward, bottom first. See Fig. 2.
5. Disconnect the gray, blue, brown and green/yellow wires from the gas valve and remove violet wires from the rollout switch.
NOTE: To locate rollout switch, see Fig. 3.
6. Disconnect orange sparker cable from the sparker.
7. Disconnect white flame sensor wire from the flame sensor.
8. Remove the ground screw securing the brown wire from the burner assembly. Ground screw is attached to the fan parti­tion. Save screw.
9. Completely slide out the entire burner rack assembly from unit.
10. Inspect the inlet of the heat exchanger tubes for presence of V-- shaped NOx baffles (see Fig. 1). If baffles are present, they must be removed prior to converting unit for propane gas. Using needle--nose pliers, remove NOx baffles, squeeze sides of the baffle, if necessary, to remove from the heat exchanger tubes.
IMPORTANT: If it is expected that this unit will be converted back to natural gas at a later time, these baffles should be retained for reuse. Otherwise the baffles may be discarded.
11. Using a 5/16 in. nut driver, remove the four screws securing the manifold/gas valve assembly to the burner assembly. Save these screws.
2
Fan Partition Panel
Fan Partition Mounting Bracket
Screw
See note below.
Screw
CPLPCONV
NOTE:
The fan partition bracket may be removed for easier access to the burner assembly. The bracket may be removed by removing 2 screws on the control side and sliding the bracket forward, bottom first.
If the fan partition bracket was removed, slide bracket back into place and fasten with 2 screws.
Fig. 2 -- Fan Partition Bracket Removal
A09320
3
CPLPCONV
ROLLOUT SWITCH
BURNER BRACKET
C00150
(2006 -- 2010 Models)
A07874
(2010 -- Current Models)
Fig. 3 -- Two--Stage Burner Bracket
12. For 2--stage 40,000 Btu/hr and 60,000 Btu/hr only! Remove the burners from the rack, save the screws. Remove the snap ring from the end of each burner. Install burner insert in the end of each burner with the flat sides of the square vertical and horizontal. Replace the snap ring to retain burner insert (see Fig 6 for correct orientation). Replace the burners in the rack using the saved screws, making sure closed crossovers of burners are at each end.
13. Remove the natural gas orifices from the manifold using a 9/16 in. wrench and install the correct propane gas orifices in the manifold (See Table 4 to select correct orifice size based on rated input. See Fig. 4 and 7 for orifice installation).
A07889
Fig. 4 -- Two--Stage Igniter, Flame Sensor, Orifice/Main
Burner Relationship
14. Replace the manifold/gas valve assembly into the burner assembly using the four screws saved from item 11.
15. Remove the plug on the inlet end of the gas valve using a 3/16 in. hex wrench.
16. Install the 1/8 in. NPT x 3/4 in. (19 mm) close pipe nipple where the plug was removed (see Fig. 11). Use pipe thread dope (field-- supplied, must be certified for use with propane gas) for all joints, making sure not to get any excess in the pipe or valve. Next, install a 1/8 in. elbow, a 1/8 in. NPT x 3/4 in. (19 mm) close pipe nipple, 1/8 in. elbow, 1/8 in. x NPT 2 in. (51 mm) nipple, and a low gas pressure switch as shown in Fig. 11.
17. Remove regulator cover screws for both high and low stage gas regulators (see Fig. 6). Save regulator cover screws.
18. Using a screwdriver, remove plastic adjust screws from both high and low stage gas regulators (see Fig. 6). Save plastic adjust screws.
19. Remove regulator springs (silver) from both high and low stage gas regulators (see Fig. 6). Discard regulator springs.
20. Install propane gas regulator springs (white) shipped with this kit. One into the low stage gas regulator and one into the high stage gas regulator (see Fig. 6).
21. Install plastic adjust screw into the high stage gas regulator. turn clockwise 13.5 turns (see Fig. 6).
4
MANIFOLD PIPE PLUG
C99019
Fig. 5 -- Two--Stage Burner Assembly
REGULATOR COVER SCREW
ON/OFF SWITCH
INLET PRESSURE TAP
PLASTIC ADJUST SCREW
REGULATOR SPRING
(Propane - White, Natural - Silver)
HIGH STAGE GAS PRESSURE REGULATOR ADJUSTMENT
LOW STAGE GAS PRESSURE REGULATOR ADJUSTMENT
MANIFOLD PRESSURE TAP
A07804
Fig. 6 -- Two--Stage Gas Valve
22. Install plastic adjust screw into the low stage gas regulator. turn clockwise 9.5 turns (see Fig. 6).
23. Verify igniter, flame sensor, orifice/main burner relationship p rior to completing conversion. (See Fig. 4.) Partially slide burner rack assembly into unit.
24. Disconnect the orange wire from the combustion air pressure switch and connect it to the orange wire on the low gas pressure switch (LGPS) equipped with a 1/4 in. male quick--connect terminal. The low gas pressure switch should have one unconnected orange wire remaining. Connect this wire to the vacant terminal on the combustion air pressure switch (see Fig. 8).
25. Reconnect the violet wires removed in item 5 to the rollout switch and reinstall the rollout switch.
26. Reconnect orange sparker cable to sparker and reconnect thewhiteflamesensorwiretotheflamesensor.
27. Reconnect the remaining wires removed in item 5 to the gas valve. Connect the gray wires to (HI). Connect the blue wires to (M). Connect the brown and green/yellow wires to (C).
28. Slide burner rack assembly into base pan. Align burner rack with screws on sheet metal partition and slide assembly back tight to the partition. Replace the screw attaching the burner rack to the base pan removed in step 4. If the Fan partition mounting bracket was removed, slide bracket back into placed and fasten with 2 screws. (See Fig. 2.)
29. Reconnect the brown wire from the burner assembly to the fan partition panel, using the ground screw saved from Step
8.
30. Remove the 1/8 in. pipe plug on the gas manifold and connect a pressure manometer (see Fig. 5).
31. Reconnect electrical power and gas supply to the unit. For propane applications, the gas pressure must not be less than
11.0IN.W.C.orgreaterthan13IN.W.C.attheunit connection. A 1/8--in. NPT plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the gas valve and downstream of manual equipment shutoff valve.
The newly installed low gas pressure switch is a safety device used to guard against adverse burner operating characteristics that can result from low gas supply pressure. Switch opens at not less than
6.5 IN. W.C. and closes at not greater than 10.2 IN. W.C. This switch also prevents operation when the propane tank level is
low which can result in gas with a high concentration of impurities, additives, and residues that have settled to the bottom of the tank. Operation under these conditions can cause harm to the heat exchanger system.
This normally open switch closes when gas is supplied to gas valve under normal operating pressure. The closed switch completes control circuit. Should an interruption or reduction in gas supply occur, the gas pressure at switch drops below low gas pressure switch setting, and switch opens. Any interruption in control circuit (in which low gas pressure switch is wired) quickly closes gas valve and stops gas flow to burners.
!
WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury and/or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
IMPORTANT: Restart unit and leak check all gas connections including the main service connection, gas valve, gas spuds, and manifold pipe plug. All leaks must be repaired before firing unit.
32. Fire unit and verify proper ignition and proper sequence of operation (Table 2). See Table 4 for proper low stage and high stage manifold pressure settings for your unit. Adjust the gas valve setting for high and low stages by turning the plastic adjustment screws clockwise to increase pressure and counter--clockwise to decrease pressure for the respective stages. Refer to Table 3 for required rated heating input rates. Replace regulator cover screws when finished (see Fig. 6).
33. With control access panel removed, observe unit heating operation in both low stage operation and high stage opera­tion. Watch burner flames to see if they are blue in appear­ance, and that the flames are approximately the same for each burner (see Fig. 9).
34. Turn off unit, remove pressure manometer and replace the 1/8 in. pipe fitting on the gas manifold (see Fig. 5).
35. Attach warning label (P/N 48DU500076) to visible side of gas valve.
36. Attach conversion label (P/N 48VL500206) above unit rating plate on exterior of unit.
37. Attach completed conversion responsibility label (see Fig. 10, P/N 48VL500207) inside control access panel.
CPLPCONV
5
Loading...
+ 11 hidden pages