Carrier CONTAINER REFRIGERATION User Manual

Page 1
Container Refrigeration
OPERATION AND SERVICE
for
69NT40-561-001 to 199
Container Refrigeration Units
T--340 Rev A -- Change 08/10
Page 2
OPERATION AND SERVICE MANUAL
CONTAINER REFRIGERATION UNIT
69NT40--561--001 to 199
Page 3

TABLE OF CONTENTS

PARAGRAPH NUMBER Page
GENERAL SAFETY NOTICES Safety--1............................................................
FIRST AID Safety--1............................................................................
OPERATING PRECAUTIONS Safety--1...........................................................
MAINTENANCE PRECAUTIONS Safety--1..........................................................
SPECIFIC WARNING AND CAUTION STATEMENTS Safety--1.......................................
INTRODUCTION 1--1..............................................................................
1.1 INTRODUCTION 1--1.....................................................................
1.2 CONFIGURATION IDENTIFICATION 1-- 1...................................................
1.3 FEATURE DESCRIPTIONS 1--1............................................................
1.3.1 Control Box 1--1......................................................................
1.3.2 Temperature Readout 1--1..............................................................
1.3.3 Pressure Readout 1--1.................................................................
1.3.4 Compressor 1--1......................................................................
1.3.5 Condenser Coil 1--1...................................................................
1.3.6 Evaporator 1--1.......................................................................
1.3.7 Evaporator Fan Operation 1--1..........................................................
1.3.8 Plate Set 1--1.........................................................................
1.4 OPTION DESCRIPTIONS 1--1.............................................................
1.4.1 Battery 1--1...........................................................................
1.4.2 Dehumidification 1--1..................................................................
1.4.3 USDA 1--1...........................................................................
1.4.4 Interrogator 1-- 1.......................................................................
1.4.5 Remote Monitoring 1--1................................................................
1.4.6 Communications Interface Module 1--1...................................................
1.4.7 Autotransformer 1--2...................................................................
1.4.8 Temperature Recorder 1--2.............................................................
1.4.9 Handles 1--2..........................................................................
1.4.10 Thermometer Port 1--2.................................................................
1.4.11 Water Cooling 1--2....................................................................
1.4.12 Back Panels 1--2......................................................................
1.4.13 460 Volt Cable 1--2....................................................................
1.4.14 230 Volt Cable 1--2....................................................................
1.4.15 Cable Restraint 1--2...................................................................
1.4.16 Upper Air (Fresh Air Make Up) 1--2......................................................
1.4.17 Lower Air (Fresh Air Make Up) 1--2......................................................
1.4.18 Labels 1--2...........................................................................
1.4.19 Controller 1--2
1.4.20 Condenser Grille 1--2..................................................................
1.4.21 Emergency Bypass 1--2................................................................
1.4.22 eAutoFresh 1--2.......................................................................
DESCRIPTION 2--1...............................................................................
2.1 GENERAL DESCRIPTION 2--1.............................................................
2.1.1 Refrigeration Unit -- Front Section 2--1...................................................
2.1.2 Fresh Air Makeup Vent 2--1.............................................................
........................................................................
i T-340
Page 4
TABLE OF CONTENTS -- Continued
PARAGRAPH NUMBER Page
2.1.3 Evaporator Section 2-- 2................................................................
2.1.4 Compressor Section 2--3...............................................................
2.1.5 Air--Cooled Condenser Section 2--4......................................................
2.1.6 Water--Cooled Condenser Section 2--5...................................................
2.1.7 Control Box Section 2--6...............................................................
2.1.8 Communications Interface Module 2--6...................................................
2.2 REFRIGERATION SYSTEM DATA 2--7......................................................
2.3 ELECTRICAL DATA 2--8...................................................................
2.4 SAFETY AND PROTECTIVE DEVICES 2--9.................................................
2.5 REFRIGERATION CIRCUIT 2--10...........................................................
2.5.1 Standard Operation 2--10................................................................
2.5.2 Economized Operation 2--10.............................................................
2.5.3 Electronic Expansion Valve 2--10.........................................................
MICROPROCESSOR 3--1..........................................................................
3.1 TEMPERATURE CONTROL MICROPROCESSOR SYSTEM 3--1..............................
3.1.1 Keypad 3--2..........................................................................
3.1.2 Display Module 3--2...................................................................
3.1.3 Controller 3--3........................................................................
3.2 CONTROLLER SOFTWARE 3--3...........................................................
3.2.1 Configuration Software (V ariables) 3--3...................................................
3.2.2 Operational Software (Function Codes) 3--3..............................................
3.3 CONTROLLER SEQUENCE AND MODES OF OPERATION 3-- 4...............................
3.3.1 Start up -- Compressor Phase Sequence 3--4.............................................
3.3.2 Start up -- Compressor Bump Start 3--4..................................................
3.3.3 Perishable Set Point Temperature -- Perishable Pulldown 3--4...............................
3.3.4 Perishable Set Point Temperature -- Standard Temperature Control Mode 3--4.................
3.3.5 Perishable Set Point Temperature -- Economy Fan Operation Mode 3--4......................
3.3.6 Perishable Set Point Temperature Control 3--4............................................
3.3.7 Perishable Mode Cooling -- Sequence of Operation 3--5....................................
3.3.8 Perishable Mode Heating -- Sequence of Operation 3--6....................................
3.3.9 Sequence of Operation -- Perishable Mode (Capacity Trim Heat) 3--6........................
3.3.10 Perishable Mode -- Dehumidification 3--6.................................................
3.3.11 Perishable, Dehumidification -- Bulb Mode 3--7............................................
3.3.12 Frozen -- Pulldown 3--7................................................................
3.3.13 Frozen Mode T emperature Control 3--7..................................................
3.3.14 Frozen Mode -- Standard 3--7...........................................................
3.3.15 Frozen Mode -- Heat Lockout Temperature 3--7...........................................
3.3.16 Frozen Mode -- Economy 3--7...........................................................
3.3.17 Frozen Mode Cooling -- Sequence of Operation 3--8.......................................
3.3.18 Defrost Interval 3--9...................................................................
3.3.19 Defrost Mode -- Sequence of Operation 3--9..............................................
3.4 PROTECTION MODES OF OPERATION 3--10................................................
3.4.1 Evaporator Fan Operation 3--10..........................................................
3.4.2 Failure Action 3--10.....................................................................
T-340
ii
Page 5
TABLE OF CONTENTS -- Continued
PARAGRAPH NUMBER Page
3.4.3 Generator Protection 3--10..............................................................
3.4.4 Compressor High Temperature, Low Pressure Protection 3--10...............................
3.4.5 Perishable Mode -- System Pressure Regulation 3--10.......................................
3.4.6 Condenser Fan Override 3--10...........................................................
3.5 CONTROLLER ALARMS 3--10..............................................................
3.6 UNIT PRE--TRIP DIAGNOSTICS 3--11.......................................................
3.7 DataCORDER 3--11........................................................................
3.7.1 Description 3--11.......................................................................
3.7.2 DataCORDER Software 3--11............................................................
3.7.3 Sensor Configuration (dCF02) 3--12......................................................
3.7.4 Logging Interval (dCF03) 3--12...........................................................
3.7.5 Thermistor Format (dCF04) 3--12.........................................................
3.7.6 Sampling Type (dCF05 & dCF06) 3--14...................................................
3.7.7 Alarm Configuration (dCF07 -- dCF10) 3--14...............................................
3.7.8 DataCORDER Power Up 3--14...........................................................
3.7.9 Pre--trip Data Recording 3--14............................................................
3.7.10 DataCORDER Communications 3--14.....................................................
3.7.11 USDA Cold Treatment 3--15.............................................................
3.7.12 USDA Cold Treatment Procedure 3--15...................................................
3.7.13 DataCORDER Alarms 3--16.............................................................
3.7.14 ISO Trip Header 3--16..................................................................
OPERATION 4--1.................................................................................
4.1 INSPECTION (Before Starting) 4--1.........................................................
4.2 CONNECT POWER 4--1..................................................................
4.2.1 Connection To 380/460 VAC Power 4--1..................................................
4.2.2 Connection To 190/230 VAC Power 4--1..................................................
4.3 ADJUST FRESH AIR MAKEUP VENT 4--1...................................................
4.3.1 Upper Fresh Air Makeup Vent 4--2.......................................................
4.3.2 Lower Fresh Air Makeup Vent 4--2.......................................................
4.3.3 Vent Position Sensor 4--2..............................................................
4.4 EAUTOFRESH OPERATION 4--3...........................................................
4.4.1 eAutoFresh Pre--Trip Inspection 4--3.....................................................
4.4.2 eAutoFresh Start--Up Procedure 4--3....................................................
4.4.3 eAutoFresh Operation 4--3.............................................................
4.4.4 eAutoFresh Modes of Operation 4--3.....................................................
4.5 CONNECT WATER--COOLED CONDENSER 4--4............................................
4.5.1 Water--Cooled Condenser with Water Pressure Switch 4--4.................................
4.5.2 Water--Cooled Condenser with Condenser Fan Switch 4--4.................................
4.6 CONNECT REMOTE MONITORING RECEPTACLE 4--5......................................
4.7 STARTING AND STOPPING INSTRUCTIONS 4--5...........................................
4.7.1 Starting the Unit 4--5...................................................................
4.7.2 Stopping the Unit 4--5..................................................................
iii T-340
Page 6
TABLE OF CONTENTS -- Continued
PARAGRAPH NUMBER Page
4.8 START--UP INSPECTION 4--5.............................................................
4.8.1 Physical Inspection 4--5................................................................
4.8.2 Check Controller Function Codes 4--5....................................................
4.8.3 Start T emperature Recorder 4--5........................................................
4.8.4 Complete Inspection 4-- 5...............................................................
4.9 PRE--TRIP DIAGNOSIS 4-- 5...............................................................
4.10 OBSERVE UNIT OPERATION 4--6.........................................................
4.10.1 Probe Diagnostic Logic 4--6............................................................
4.11 EMERGENCY BYPASS OPERATION 4--7
TROUBLESHOOTING 5--1.........................................................................
5.1 UNIT WILL NOT START OR STARTS THEN STOPS 5--1......................................
5.2 UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING 5--1..............................
5.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING 5--2........................................
5.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING 5--2................................
5.5 UNIT WILL NOT TERMINATE HEATING 5--2................................................
5.6 UNIT WILL NOT DEFROST PROPERLY 5--2................................................
5.7 UNIT WILL NOT DEFROST PROPERLY (Continued) 5--3.....................................
5.8 ABNORMAL PRESSURES 5--3............................................................
5.9 ABNORMAL NOISE OR VIBRATIONS 5--3..................................................
5.10 MICROPROCESSOR MALFUNCTION 5--3..................................................
5.11 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW 5--4..............................
5.12 eAutoFresh NOT OPERATING 5--4.........................................................
5.13 ELECTRONIC EXPANSION VALVE MALFUNCTION 5--4......................................
5.14 AUTOTRANSFORMER MALFUNCTION 5--5................................................
5.15 WATER--COOLED CONDENSER OR WATER PRESSURE SWITCH 5--5.......................
5.16 COMPRESSOR OPERATING IN REVERSE 5--5.............................................
5.17 ABNORMAL TEMPERATURES 5--5........................................................
5.18 ABNORMAL CURRENTS 5--5..............................................................
SERVICE 6--1....................................................................................
6.1 SECTION LAYOUT 6--1...................................................................
6.2 MANIFOLD GAUGE SET 6--1..............................................................
6.3 REFRIGERATION SYSTEM SERVICE-UNITS WITH STANDARD PIPING (with Service Valves) 6--2
6.3.1 Service Connections 6--2...............................................................
6.3.2 Pumping Down the Unit 6--2............................................................
6.3.3 Refrigerant Leak Checking 6--3.........................................................
6.3.4 Evacuation and Dehydration 6--3........................................................
6.3.5 Refrigerant Charge 6--4................................................................
6.4 COMPRESSOR 6--4......................................................................
6.4.1 Removal and Replacement of Compressor 6--5...........................................
6.5 HIGH PRESSURE SWITCH 6--6...........................................................
6.5.1 Checking High Pressure Switch 6--6.....................................................
6.5.2 Replacing High Pressure Switch 6--6.....................................................
6.6 CONDENSER COIL 6--6..................................................................
6.7 CONDENSER FAN AND MOTOR ASSEMBLY 6-- 6...........................................
6.8 WATER--COOLED CONDENSER CLEANING 6--7............................................
...................................................
T-340 Change 11/09
iv
Page 7
TABLE OF CONTENTS -- Continued
PARAGRAPH NUMBER Page
6.9 FILTER DRIER 6--9.......................................................................
6.10 EVAPORATOR COIL AND HEATER ASSEMBLY 6--9.........................................
6.10.1 Evaporator Coil Replacement 6--9.......................................................
6.10.2 Evaporator Heater Removal and Replacement 6--9........................................
6.11 EVAPORATOR FAN AND MOTOR ASSEMBLY 6-- 10..........................................
6.11.1 Replacing The Evaporator Fan Assembly 6--10.............................................
6.11.2 Disassemble The Evaporator Fan Assembly 6--10..........................................
6.11.3 Assemble The Evaporator Fan Assembly 6--10.............................................
6.12 EAUTOFRESH SERVICE 6-- 11..............................................................
6.12.1 eAutoFresh Air Filter 6--11...............................................................
6.12.2 eAutoFresh Drive System 6--1 1..........................................................
6.12.3 Checking the Controller 6--12............................................................
6.12.4 eAutoFresh Drive System 6--12..........................................................
6.13 ELECTRONIC EXPANSION VALVE 6--14.....................................................
6.13.1 Replacing Electronic Expansion Valve and Screen 6--14.....................................
6.14 ECONOMIZER EXPANSION VALVE 6--14....................................................
6.14.1 Valve Replacement 6--14................................................................
6.15 ECONOMIZER SOLENOID VALVE 6-- 15.....................................................
6.16 DIGITAL UNLOADER VALVE 6--15..........................................................
6.17 VALVE OVERRIDE CONTROLS 6--16........................................................
6.18 AUTOTRANSFORMER 6--18...............................................................
6.19 CONTROLLER 6--18.......................................................................
6.19.1 Handling Modules 6--18.................................................................
6.19.2 Controller Troubleshooting 6--18..........................................................
6.19.3 Controller Programming Procedure 6--19..................................................
6.19.4 Removing and Installing a Module 6--21...................................................
6.19.5 Battery Replacement 6--21..............................................................
6.20 VENT POSITION SENSOR SERVICE 6--21...................................................
6.21 TEMPERATURE SENSOR SERVICE 6--22...................................................
6.21.1 Sensor Checkout Procedure 6--22........................................................
6.21.2 Sensor Replacement 6-- 22..............................................................
6.21.3 Sensor Re-Installation 6--23.............................................................
6.22 ELECTRONIC PAR TLOW TEMPERATURE RECORDER 6--25..................................
6.23 MAINTENANCE OF PAINTED SURFACES 6--27..............................................
6.24 COMMUNICATIONS INTERFACE MODULE INSTALLATION 6--27..............................
ELECTRICAL WIRING SCHEMATICS 7--1...........................................................
7.1 INTRODUCTION 7--1.....................................................................
v T-340
Page 8

LIST OF ILLUSTRATIONS

FIGURE NUMBER Page
Figure 2--1 Refrigeration Unit -- Front Section 2--1....................................................
Figure 2--2 Evaporator Section 2--2.................................................................
Figure 2--3 Compressor Section 2-- 3................................................................
Figure 2--4 Air--Cooled Condenser Section 2--4.......................................................
Figure 2--5 Water--Cooled Condenser Section 2--5....................................................
Figure 2--6 Control Box Section 2--6................................................................
Figure 2--7 Refrigeration Circuit Schematic -- Standard Operation 2--11...................................
Figure 2--8 Refrigeration Circuit Schematic -- Economized Operation 2--12................................
Figure 3--1 T emperature Control System 3--1.........................................................
Figure 3--2 Keypad 3--2...........................................................................
Figure 3--3 Display Module 3--3....................................................................
Figure 3--4 Control Module 3--3.....................................................................
Figure 3--5 Controller Operation -- Perishable Mode 3--5...............................................
Figure 3--6 Perishable Mode -- Cooling 3--5..........................................................
Figure 3--7 Perishable Mode Heating 3--6............................................................
Figure 3--8 Controller Operation -- Frozen Mode 3--8..................................................
Figure3--9FrozenMode 3--8......................................................................
Figure 3--10 Defrost 3--10..........................................................................
Figure 3--11 Standard Configuration Download Report 3--13.............................................
Figure 3--12 Data Reader 3--15......................................................................
Figure 4--1 Autotransformer 4--1....................................................................
Figure 4--2 Upper Fresh Air Make Up Flow Chart 4--2.................................................
Figure 4--3 Diagram of Emergency Bypass Connections 4--7
Figure 6--1 Manifold Gauge Set 6--1................................................................
Figure 6--2 R-134a Manifold Gauge/Hose Set 6--1....................................................
Figure 6--3 Service Valve 6-- 2......................................................................
Figure 6--4 Refrigeration System Service Connections 6--3.............................................
Figure 6--5 Compressor Kit 6--5....................................................................
Figure 6--6 High Pressure Switch Testing 6--6........................................................
Figure 6--7 Water-Cooled Condenser Cleaning - Forced Circulation 6--8.................................
Figure 6--8 Water-Cooled Condenser Cleaning - Gravity Circulation 6--9.................................
Figure 6--9 5+1 Heater Arrangement -- Omega Heater 6--10.............................................
Figure 6--10 Evaporator Fan Assembly 6--11..........................................................
Figure 6--11 Stepper Components 6--11..............................................................
Figure 6--12 Jumper Assembly 6-- 12.................................................................
Figure 6--13 Motor Cup Replacement 6--13...........................................................
Figure 6--14 Electronic Expansion Valve 6--14.........................................................
Figure 6--15 Economizer Expansion V alve 6--14.......................................................
Figure 6--16 Coil View of Economizer Solenoid Valve (ESV) 6--15.......................................
Figure 6--17 View of Digital Unloader Valve (DUV) Assembly 6--15.......................................
Figure 6--18 Controller Section of the Control Box 6--19.................................................
Figure 6--19 Sensor Types 6--23.....................................................................
Figure 6--20 Sensor and Cable Splice 6--23...........................................................
Figure 6--21 Supply Sensor Positioning 6--24..........................................................
Figure 6--22 Return Sensor Positioning 6--24..........................................................
Figure 6--23 Evaporator Temperature Sensor Positioning 6--24..........................................
...........................................
T-340 Change 11/09
vi
Page 9
LIST OF ILLUSTRATIONS (Continued)
FIGURE NUMBER Pag e
Figure 6--24 Electronic Partlow Temperature Recorder 6--26.............................................
Figure 6--25 Communications Interface Installation 6--27................................................
Figure 7--1 LEGEND -- Standard Unit Configuration 7--2...............................................
Figure 7--2 SCHEMATIC DIAGRAM -- Standard Unit Configuration 7--3..................................
Figure 7--3 LEGEND -- Configuration Includes Available Options (Except Vent Positioning System, eAutoFresh,
Emergency Bypass Options) 7--4.......................................................
Figure 7--4 SCHEMATIC DIAGRAM -- Configuration Includes Available Options (Except Vent Positioning System,
eAutoFresh, Emergency Bypass Options) 7--5............................................
Figure 7--5 LEGEND -- Configuration Includes eAutoFresh and Emergency Bypass Options 7--6............
Figure 7--6 SCHEMATIC DIAGRAM -- Configuration Includes eAutoFresh and Emergency Bypass Options 7--7
Figure 7--7 SCHEMATIC AND WIRING DIAGRAM -- Upper Vent Position Sensor (VPS) Option 7--8.........
Figure 7--8 SCHEMATIC AND WIRING DIAGRAM -- Lower Vent Position Sensor (VPS) Option 7--9.........
Figure 7--9 UNIT WIRING DIAGRAM -- Standard Unit Configuration with 3--Phase Condenser Fan Motors 7--10
Figure 7--10 UNIT WIRING DIAGRAM -- Configuration Includes 2 Phase Condenser Fan Motor and Optional Heater
Figure 7--11 UNIT WIRING DIAGRAM -- Configuration Includes eAutoFresh and Emergency Bypass Options7--14
Arrangement 7--12.....................................................................

LIST OF TABLES

TABLE NUMBER Page
Table 2--1 Safety and Protective Devices 2--9.........................................................
Table 3--1 Keypad Function 3--2.....................................................................
Table 3--2 DataCORDER Configuration Variables 3--12..................................................
Table 3--3 DataCORDER Standard Configurations 3--14.................................................
Table 3--4 Controller Configuration Variables 3--17......................................................
Table 3--5 Controller Function Codes 3--18.............................................................
Table 3--6 Controller Alarm Indications 3--22...........................................................
Table 3--7 Controller Pre--trip Test Codes 3--27.........................................................
Table 3--8 DataCORDER Function Code Assignments 3--31..............................................
Table 3--9 DataCORDER Pre--trip Result Records 3--32.................................................
Table 3--10 DataCORDER Alarm Indications 3--33......................................................
Table 6--1 Valve Override Control Displays 6--17........................................................
Table 6--2 Sensor Temperature/Resistance Chart (+/-.002%) 6--22........................................
Table 6--3 Recommended Bolt Torque Values 6--27.....................................................
Table 6--4 R-134a Temperature - Pressure Chart 6--28..................................................
vii T-340
Page 10

SAFETY SUMMARY

GENERAL SAFETY NOTICES
The following general safety notices supplement specif­ic warnings and cautions appearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and mainte­nance of the equipment covered herein. The general safety notices are presented in the following three sec­tions labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warn­ings and cautions appearing elsewhere in the manual follows the general safety notices.
FIRST AID
An injury, no matter how slight, should never go unat­tended. Always obtain first aid or medical attention im­mediately.
OPERATING PRECAUTIONS
Always wear safety glasses.
Keep hands, clothing and tools clear of the evaporator and condenser fans.
No work should be performed on the unit until all circuit breakers and start-stop switches are turned off, and power supply is disconnected.
In case of severe vibration or unusual noise, stop the unit and investigate.
CAUTION - means to warn against potential hazard or unsafe practice that could result in minor personal injury, product or property damage.
The statements listed below are applicable to the refrig­eration unit and appear elsewhere in this manual. These recommended precautions must be understood and ap­plied during operation and maintenance of the equip­ment covered herein.
DANGER
Never use air for leak testing. It has been de­termined that pressurized, mixtures of re­frigerant and air can undergo combustion when exposed to an ignition source.
WARNING
Beware of unannounced starting of the evaporator and condenser fans. The unit may cycle the fans and compressor unex­pectedly as control requirements dictate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator and condenser fans. Do not open the condenser fan grille or evaporator access panels before turning power off, dis­connecting and securing the power plug.
Be sure power is turned off before working on motors, controllers, solenoid valves and electrical control switches. Tag circuit breaker and power supply to pre­vent accidental energizing of circuit.
Do not bypass any electrical safety devices, e.g. bridg­ing an overload, or using any sort of jumper wires. Prob­lems with the system should be diagnosed, and any necessary repairs performed by qualified service per­sonnel.
When performing any arc welding on the unit or contain­er, disconnect all wire harness connectors from the modules in control boxes. Do not remove wire harness from the modules unless you are grounded to the unit frame with a static safe wrist strap.
In case of electrical fire, open circuit switch and extin­guish with CO
SPECIFIC WARNING AND CAUTION STATEMENTS
To help identify the label hazards on the unit and explain the level of awareness each one carries, an explanation is given with the appropriate consequences:
DANGER - means an immediate hazard that WILL re­sult in severe personal injury or death.
WARNING - means to warn against hazards or unsafe conditions that COULD result in severe personal injury or death.
(never use water).
2
WARNING
Do not attempt to remove power plug(s) be ­fore turning OFF start-stop switch (ST), unit circuit breaker(s) and external power source.
WARNING
Make sure the power plugs are clean and dry before connecting to power receptacle.
WARNING
Make sure that the unit circuit breaker(s) (CB-1 & CB-2) and the START-STOP switch (ST) are in the “O” (OFF) position before connecting to any electrical power source.
WARNING
Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply before working on moving parts.
Safety--1
T--340
Page 11
WARNING
CAUTION
Make sure power to the unit is OFF and power plug disconnected before replacing the compressor.
WARNING
Before disassembly of the compressor, be sure to relieve the internal pressure very carefully by slightly loosening the cou­plings to break the seal.
WARNING
Do not use a nitrogen cylinder without a pressure regulator. Do not use oxygen in or near a refrigeration system as an explosion may occur.
WARNING
Do not open the condenser fan grille before turning power OFF and disconnecting power plug.
Charge water--cooled condenser or receiv­er according to nameplate specifications to ensure optimal unit performance.
CAUTION
Do not remove wire harnesses from con­troller modules unless you are grounded to the unit frame with a static safe wrist strap.
CAUTION
Unplug all controller module wire harness connectors before performing arc welding on any part of the container.
CAUTION
Do not attempt to use an ML2i PC card in an ML3 equipped unit. The PC cards are physi­cally different and will result in damage to the controller.
WARNING
Oakite No. 32 is an acid. Be sure that the acid is slowly added to the water. DO NOT PUT WATER INTO THE ACID - thiswill cause spattering and excessive heat.
WARNING
Wear rubber gloves and wash the solution from the skin immediately if accidental con­tact occurs. Do not allow the solution to splash onto concrete.
WARNING
Always turn OFF the unit circuit breakers (CB-1 and CB-2) and disconnect main power supply before working on moving parts.
WARNING
Installation requires wiring to the main unit circuit breaker, CB1. Make sure the power to the unit is off and power plug disconnected before beginning installation.
CAUTION
Pre-tr ip inspection should not be per­formed with critical temperature cargoes in the containe r.
CAUTION
When Pre-Trip key is pressed, economy, de­humidification and bulb mode will be deac­tivated. At the completion of Pre-Trip activi­ty, econom y, dehumidification and bulb mode must be reactivated.
CAUTION
When condenser water flow is below 11 lpm (3 gpm) or when water-cooled operation is not in use, the CFS switch MUST be set to position “1” or the unit will not operate properly.
CAUTION
When a failure occurs during automatic testing, the unit will suspend operation awaiting operator intervention.
T--340
Safety--2
Page 12
CAUTION
CAUTION
When Pre-Trip test Auto 2 runs to comple­tion without being interrupted, the unit will terminate pre-trip and display “Auto 2” “end.” The unit will suspend operationuntil the user depresses the ENTER key!
CAUTION
Allowing the scroll compressor to operate in reverse for more than two minutes will re­sult in internal compressor damage. Turn the start-stop switch OFF immediately.
CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set besure set is brought to suction pressure before disconnecting.
CAUTION
Take necessary steps (place plywood over coil or use sling on motor) to prevent motor from falling into condenser coil.
CAUTION
Do not remove wire harnesses from module unless you are grounded to the unit frame with a static safe wrist strap.
CAUTION
Unplug all module connectors before per­forming arc welding on any part of the con­tainer.
CAUTION
The unit must be OFF whenever a program­ming card is inserted or removed from the controller programming port.
CAUTION
The scroll compressor achieves low suc­tion pressure very quickly. Do not use the compressor to evacuate the system below 0 psig. Never operate the compressor with the suction or discharge service valves closed (frontseated). Internal damage will result from operating the compressor in a deep vacuum.
Use care when cutting wire ties to avoid nicking or cutting wires.
CAUTION
Do not allow moisture to enter wire splice area as this may affect the sensor resis­tance.
Safety--3
T--340
Page 13
SECTION 1
INTRODUCTION

1.1 INTRODUCTION

The Carrier Transicold model 69NT40--561--001 to 199 series units are of lightweight aluminum frame construction, designed to fit in the front of a container and serve as the container’s front wall.
They are one piece, self--contained, all electric units, which include cooling and heating systems to provide precise temperature control.
The units are supplied with a complete charge of refrigerant R--134a and compressor lubricating oil, and are ready for operation upon installation. Forklift pockets are provided for unit installation and removal.
The base unit operates on nominal 380/460 volt, 3--phase, 50/60 hertz (Hz) power. An optional autotransformer may be fitted to allow operation on nominal 190/230, 3--phase, 50/60 Hz power. Power for the control system is provided by a transformer which steps the supply power down to 18 and 24 volts, single phase.
The controller is a Carrier Transicold Micro--Link 3 microprocessor. The controller will operate automatically to select cooling, holding or heating as required to maintain the desired set point temperature within very close limits. The unit may also be equipped with an electronic temperature recorder.
The controller has a keypad and display for viewing or changing operating parameters. The display is also equipped with lights to indicate various modes of operation.

1.2 CONFIGURATION IDENTIFICATION

Unit identification information is provided on a plate located to the left of the receiver or water--cooled condenser, on the back wall of the condenser section. The plate provides the unit model number, the unit serial number and the unit parts identification number (PID). The model number identifies the overall unit configuration, while the PID number provides information on specific optional equipment, factory provisioned to allow for field installation of optional equipment and differences in detailed parts.

1.3 FEATURE DESCRIPTIONS

1.3.1 Control Box
Units are equipped with either an aluminum or composite material box, and may be fitted with a lockable door.
1.3.2 Temperature Readout
The unit is fitted with suction and discharge temperature sensors. The sensor readings may be viewed on the controller display.
1.3.3 Pressure Readout
The unit is fitted with evaporator and discharge transducers. The transducer readings may be viewed on the controller display.
1.3.4 Compressor
The unit is fitted with a scroll compressor equipped with suction and discharge service connections.
1.3.5 Condenser Coil
The unit is fitted with a four--row condenser coil using 7mm tubing.
1.3.6 Evaporator
Evaporator section is equipped with an electronic expansion valve (EEV).
1.3.7 Evaporator Fan Operation
Units are equipped with three--phase evaporator fan motors. Opening of an evaporator fan internal protector will shut down the unit.
1.3.8 Plate Set
Each unit is equipped with a tethered set of wiring schematics and wiring diagram plates. The plate sets are ordered using a seven--digit base part number and a two--digit dash number.

1.4 OPTION DESCRIPTIONS

Various options may be factory or field equipped to the base unit. These options are listed in the tables and described in the following subparagraphs.
1.4.1 Battery
The refrigeration controller may be fitted with standard replaceable batteries or a rechargeable battery pack. Rechargeable battery packs may be fitted in the standard or in a secure location.
1.4.2 Dehumidification
The unit may be fitted with a humidity sensor. This sensor allows setting of a humidity set point in the controller. In dehumidification mode, the controller will operate to reduce internal container moisture level.
1.4.3 USDA
The unit may be supplied with fittings for additional temperature probes, which allow recording of USDA Cold Treatment data by the integral DataCORDER function of the Micro--Link refrigeration controller.
1.4.4 Interrogator
Units that use the DataCORDER function are fitted with interrogator receptacles for connection of equipment to download the recorded data. Two receptacles may be fitted; one is accessible from the front of the container and the other is mounted inside the container (with the USDA receptacles).
1.4.5 Remote Monitoring
The unit may be fitted with a remote monitoring receptacle. This item allows connection of remote indicators for COOL, DEFROST and IN RANGE. Unless otherwise indicated, the receptacle is mounted at the control box location.
1.4.6 Communications Interface Module
The unit may be fitted with a communications interface module. The communications interface module is a slave module, which allows communication with a
1--1 T--340
Page 14
master central monitoring station. The module will respond to communication and return information over the main power line. Refer to the ship master system technical manual for further information.
1.4.7 Autotransformer
An autotransformer may be provided to allow operation on 190/230, 3--phase, 50/60 Hz power. The autotransformer raises the supply voltage to the nominal 380/460 volt power required by the base unit. The autotransformer may also be fitted with an individual circuit breaker for the 230 volt power.
If the unit is equipped with an autotransformer and communications module, the autotransformer will be fitted with a transformer bridge unit (TBU) to assist in communications.
1.4.8 Temperature Recorder
The units may be fitted with an electronic temperature recording device.
1.4.9 Handles
The unit may be equipped with handles to facilitate access to stacked containers. These fixed handles are located on either side of the unit.
1.4.10 Thermometer Port
The unit may be fitted with ports in the front of the frame for insertion of a thermometer to measure supply and/or return air temperature. If fitted, the port(s) will require a cap and chain.
1.4.11 Water Cooling
The refrigeration system may be fitted with a water--cooled condenser. The condenser is constructed using copper--nickel tube for sea water applications. The water--cooled condenser is in series with the air cooled condenser and replaces the standard unit receiver. When operating on the water--cooled condenser, the condenser fan is deactivated by a water pressure switch or condenser fan switch.
1.4.12 Back Panels
Aluminum back panels may have access doors and/or hinge mounting.
1.4.13 460 Volt Cable
Various power cable and plug designs are available for the main 460 volt supply. The plug options tailor the cables to each customer’s requirements.
1.4.14 230 Volt Cable
Units equipped with an autotransformer require an additional power cable for connection to the 230 volt source. Various power cable and plug designs are available. The plug options tailor the cables to each customer’s requirements.
1.4.15 Cable Restraint
Various designs are available for storage of the power cables. These options are variations of the compressor section cable guard.
1.4.16 Upper Air (Fresh Air Make Up)
The unit may be fitted with an upper fresh air makeup assembly. The fresh air makeup assembly is available with a vent positioning sensor (VPS) and may also be fitted with screens.
1.4.17 Lower Air (Fresh Air Make Up)
The unit may be fitted with a lower fresh air makeup assembly. The fresh air makeup assembly is available with a vent positioning sensor (VPS) and may also be fitted with screens.
1.4.18 Labels
Safety Instruction and Function Code listing labels differ, depending on the options installed. Labels available with additional languages are listed in the parts list.
1.4.19 Controller
Two replacement controllers are available:
1. Remanufactured -- Controller is the equivalent of a new OEM controller and is supplied with a 12--month warranty.
2. Repaired -- Controller has had previous faults repaired and upgraded with the latest software.
Note: Repaired controllers are NOT to be used for warranty repairs; only full OEM Remanufactured controllers are to be used.
Controllers will be factory--equipped with the latest version of operational software, but will NOT be configured for a specific model number and will need to be configured at the time of installation or sale.
1.4.20 Condenser Grille
Two styles of condenser grilles are available: direct bolted grilles and hinged grilles.
1.4.21 Emergency Bypass
The optional Emergency Bypass switch (EB) functions to bypass the controller in the event of controller failure.
1.4.22 eAutoFresh
The optional eAutoFresh venting system moderates the atmospheric level inside the container unit in response to cargo respiration.
T--340
1--2
Page 15
SECTION 2
DESCRIPTION

2.1 GENERAL DESCRIPTION

2.1.1 Refrigeration Unit -- Front Section
The unit is designed so that the majority of the compo­nents are accessible from the front (see Figure 2--1). The unit model number, serial number and parts identifi­cation number can be found on the serial plate to the left of the receiver or water--cooled condenser on the back wall of the condenser section.
18
2.1.2 Fresh Air Makeup Vent
The function of the upper or lower makeup air vent is to provide ventilation for commodities that require fresh air circulation. A manually operated venting system is loc­ated in the upper left access panel.
The optional eAutoFresh vent system is to moderate the atmospheric level in the container in response to cargo respiration. When transporting frozen cargo loads the vent will be closed. The upper left access panel contains the vent slide and motor assembly. It may be removed to allow entry into the evaporator section where the CO sensor and drive pack are located.
2
17
16
15
14
13
12
11
10
1. Access Panel (Evap. Fan #1)
2. Fork Lift Pockets
3. Control Box
4. Compressor
5. Economizer
6. Filter Drier
7. Receiver or Water Cooled Condenser
8. Unit Serial Number, Model Number and Parts Identification Number (PID) Plate
9. Power Cables and Plug (Location)
10. Condenser Fan
Figure 2--1 Refrigeration Unit -- Front Section
1
2
3
4
9
8
7
1 1. Autotransformer (Location)
12. TransFRESH Communications Connector
13. Interrogator Connector (Front left)
14. Temperature Recorder
15. Lower Fresh Air Makeup Vent Location
16. TIR (Transports Internationaux Routiers)
17. Upper Fresh Air Makeup Vent or eAutoFresh
18. Access Panel (Evap. Fan #2)
6
5
(Blank Cover Shown)
Sealing Provisions -- Typical All Panels
(Automatic Vent) panel
2--1
T-340
Page 16
2.1.3 Evaporator Section
The evaporator section (Figure 2--2) contains the return temperature sensor, humidity sensor, electronic expan­sion valve, dual speed evaporator fans (EM1 and EM2), evaporator coil and heaters, defrost temperature sen­sor, heat termination thermostat and evaporator tem­perature sensors (ETS1 and ETS2).
The evaporator fans circulate air through the container by pulling it in the top of the unit, directing it through the evaporator coil, where it is heated or cooled, and dis-
15
14
13
charging it at the bottom.
If unit is equipped with eAutoFresh, system compon­ents are mounted in addition to the standard refrigera­tion unit components. The stepper motor components is installed in the vent; the air filter, CO motor drive and CO
sensing lines are installed on the
2
sensor, stepper
2
rib of the upper grill.
Most evaporator components are accessible by remov­ing the upper rear panel (as shown in the illustration) or by removing the evaporator fan access panels (see Figure 2--1, Items 1 and 18.
12
10
11
4
3
2
1
9
16
21
20
19
6
18
17
7
8
1. Evaporator Fan Motor #1 (EM1)
2. Return Recorder Sensor/Temperature Sensor (RRS/RTS)
3. Humidity Sensor (HS)
4. Evaporator Fan Motor #2 (EM2)
5. Evaporator Coil
6. Evaporator Coil Heaters (Underside of Coil)
7. Heater Termination Thermostat (HTT)
8. Defrost Temperature Sensor (DTS)
9. Electronic Expansion Valve (EEV)
10. Evaporator Temperature Sensors (Location) (ETS1 and ETS2)
Figure 2--2 Evaporator Section
5
11. Air Filter
12. CO
13. CO
14. CO
Sensor Sensing Line
2
Sensor (COS)
2
Sensor Outlet Line
2
15. Stepper Motor Drive (SD)
16. Stepper Motor (AF)
17. Interrogator Connector (Rear) (ICR)
18. USDA Probe Receptacle PR2
19. USDA Probe Receptacle PR1
20. USDA Probe Receptacle PR3
21. Cargo Probe Receptacle PR4
2--2T-340
Page 17
2.1.4 Compressor Section
The compressor section includes the compressor, digital unloader valve (DUV), high pressure switch, discharge pressure transducer (DPT), evaporator
15
pressure transducer (EPT) and the suction pressure transducer (SPT).
The supply temperature sensor, supply recorder sensor and ambient sensor are located to the left of the com­pressor.
11
1
10
9
12
8
13
14
2
3
4
5
6
1. Compressor
2. Compressor Discharge Temperature Sensor (CPDS) (Location)
3. Discharge Connection
4. Suction Connection (Location)
5. Compressor Terminal Box
6. Oil Drain (Location)
7. Economizer Connection
8. Discharge Pressure Transducer (DPT)
Figure 2--3 Compressor Section
Change 11/09
7
9. Suction Pressure Transducer (SPT)
10. Digital Unloader Valve (DUV)
11. Evaporator Pressure Transducer (EPT)
12. Discharge Service Valve
13. High Pressure Switch (HPS)
14. Suction Service Valve
15. Supply Temperature/Supply Recorder Sensor Assembly (STS/SRS)
2--3
T-340
Page 18
2.1.5 Air--Cooled Condenser Section
The air--cooled condenser section (Figure 2--4) con­sists of the condenser fan, condenser coil, receiver, li­quid line service valve, filter drier, fusible plug, econo­mizer, economizer expansion valve, economizer
solenoid valve (ESV), and sight glass/moisture indicat­or.
The condenser fan pulls air through the bottom of the coil and discharges it horizontally through the con­denser fan grille.
2
1
3
4
5
6
89 10
7
1. Grille and Venturi Assembly
2. Condenser Fan
3. Key
4. Condenser Fan Motor
5. Condenser Coil
6. Condenser Coil Cover
7. Receiver
8. Sight Glass
15
14
13
9. Filter Drier
10. Economizer
11. Economizer Solenoid Valve (ESV)
12. Economizer Expansion Valve
13. Service Access Valve
14. Liquid Level/Moisture Indicator
15. Fusible Plug
Figure 2--4 Air--Cooled Condenser Section
2--4T-340
11
12
Page 19
2.1.6 Water--Cooled Condenser Section
The water--cooled condenser section (Figure 2--5) con­sists of a water--cooled condenser, sight glass, rupture disc, filter drier, water couplings, water pressure switch,
economizer, economizer expansion valve, economizer solenoid valve (ESV), and moisture/liquid indicator.
The water--cooled condenser replaces the standard unit receiver.
23 4
1
5
12
1. Water--Cooled Condenser
2. Rupture Disc
3. Moisture/Liquid Indicator
4. Filter Drier
5. Economizer
6. Economizer Solenoid Valve (ESV)
11
Figure 2--5 Water--Cooled Condenser Section
10 9
7. Economizer Expansion Valve
8. Coupling (Water In)
9. Liquid Line Service Valve/Connection
10. Self Draining Coupling (Water Out)
11. Water Pressure Switch (WP)
12. Sight Glass
8
6
7
2--5
T-340
Page 20
2.1.7 Control Box Section
2.1.8 Communications Interface Module
The control box (Figure 2--6) includes: the manual op­eration switches, circuit breaker (CB--1), compressor, fan and heater contactors, control power transformer, fuses, key pad, display module, current sensor module, controller module and the communications interface module.
1567
32
4
The optional communications interface module is a slave module that allows communication with a master central monitoring station. The module will respond to communication and return information over the main power line. Refer to the master central monitoring sta­tion technical manual for additional information.
8
15
1617 12
1. Compressor Contactor -- CH
2. Compressor Phase A Contactor -- PA
3. Compressor Phase B Contactor -- PB
4. Heater Contactor -- HR
5. Display Module
6. Communications Interface Module
7. Controller/DataCORDER Module (Controller)
8. Key Pad
9. Remote Monitoring Receptacle
14 13
Figure 2--6 Control Box Section
10
10. Controller Battery Pack (Standard Location) 1 1. Interrogator Connector (Box Location)
12. Control Transformer
13. High Speed Evaporator Fan Contactor -- EF
14. Low Speed Evaporator Fan Contactor -- ES
15. Condenser Fan Contactor -- CF
16. Circuit Breaker -- 460V
17. Current Sensor Module
2--6T-340
911
Page 21

2.2 REFRIGERATION SYSTEM DATA

Model Number ZMD26KVE--TFD--272
a. Compressor/Motor
Assembly
b. Electronic Expansion Valve
Superheat (Evaporator)
c. Economizer Expansion
Valve Superheat
d. Heater Termination Thermostat
e. High Pressure Switch
Weight (With Oil) 42.9 kg (95 lb) Approved Oil Uniqema Emkarate RL--32--3MAF Oil Charge 1774 ml (60 ounces) Verify at --18C
(0F) container box temperature
Verify at --18C (0F) container box temperature
Opens 54 (+/-- 3) C = 130 (+/-- 5) F Closes 38 (+/-- 4) C = 100 (+/-- 7) F Cutout 25 (+/-- 1.0) kg/cm2= 350 (+/-- 10) psig Cut--In 18 (+/-- 0.7) kg/cm2= 250 (+/-- 10) psig
4.4to6.7C(8to12F)
4.4 to 11.1C (8 to 20F)
CAUTION
Charge water--cooled condenser or receiver according to nameplate specifications to ensure optimal unit per formance.
Unit Configuration Charge Requirements
Water--Cooled
f. Refrigerant Charge -- R--134a
g. Fusible Plug
h. Rupture Disc
i. Unit Weight Refer to unit model number plate.
j. Water Pressure Switch
Condenser
Receiver
Melting point 99C = (210F) Torque 6.2to6.9mkg(45to50ft--lbs) Bursts at 35 +/-- 5% kg/cm2= (500 +/-- 5% psig) Torque 6.2to6.9mkg(45to50ft--lbs)
Cut--In 0.5 +/-- 0.2 kg/cm2(7 +/-- 3 psig) Cutout 1.6 +/-- 0.4 kg/cm2(22 +/-- 5 psig)
5.44 kg (12 lbs)
4.99 kg (11 lbs)
2--7
T-340
Page 22

2.3 ELECTRICAL DATA

a. Circuit Breaker
b. Compressor
Motor
c. Condenser Fan
Motor
d. Evaporator Coil
Heaters
e. Evaporator Fan
Motor(s)
f. Fuses
g. Vent Positioning
Sensor
h. Solenoid Va lve
Coils (ESV) 24 VDC
i. DUV Coils
12 VDC
j. EEV Nominal
Resistance
CB--1 Trips at 29 amps CB--2 (50 amp) Trips at 62.5 amps CB--2 (70 amp) Trips at 87.5 amps
Full Load Amps (FLA) 13 amps @ 460 VAC
380 VAC, Single Phase,
50 Hz
460 VAC, Single Phase,
60 Hz
Full Load Amps 1.3 amps 1.6 amps Horsepower 0.43 hp 0.75 hp Rotations Per Minute 1425 rpm 1725 rpm Voltage and Frequency 360 -- 460 VAC +/-- 2.5 Hz 400 -- 500 VAC +/-- 2.5 Hz Bearing Lubrication Factory lubricated, additional grease not required. Rotation Counter--clockwise when viewed from shaft end. Number of Heaters 6 Rating 750 watts +5/--10% each @ 230 VAC Resistance (cold) 66.8 to 77.2 ohms @ 20C (68F) Type Sheath
380 VAC/3 PH/50 Hz 460 VAC/3 PH/60 Hz
Full Load Amps
High Speed
Full Load Amps
Low Speed
Nominal Horsepower
High Speed
Nominal Horsepower
Low Speed
Rotations Per Minute
High Speed
Rotations Per Minute
Low Speed
1.0 1.2
0.6 0.6
0.49 0.84
0.06 0.11
2850 rpm 3450 rpm
1425 rpm 1725 rpm
Voltage and Frequency 360 -- 460 VAC +/-- 1.25 Hz 400 -- 500 VAC +/-- 1.5 Hz Bearing Lubrication Factory lubricated, additional grease not required Rotation CW when viewed from shaft end Control Circuit 7.5 amps (F3A,F3B) Controller/DataCORDER 5amps(F1&F2) Emergency Bypass 10 amps (FEB) Electrical Output 0.5 VDC to 4.5 VDC over 90 degree range Supply Voltage 5 VDC +/-- 10% Supply Current 5mA(typical) Nominal Resistance @
77F (25C)
7.7 ohms +/-- 5%
Maximum Current Draw 0.7 amps Nominal Resistance @
77F (20C)
14.8 ohms +/-- 5%
Maximum Current Draw 929 mA Coil Feed to Ground
(Gray Wire)
47 ohms
Coil Feed to Coil Feed 95 ohms
2--8T-340
Page 23
Section 2.3 -- ELECTRICAL DAT A--CONTINUED
Orange wire Power Red wire Output Brown wire Ground Input voltage 5VDC
k. Humidity Sensor
Output voltage 0to3.3VDC
Output voltage readings verses relative humidity (RH) percentage:
30% 0.99 V 50% 1.65 V 70% 2.31 V 90% 2.97 V

2.4 SAFETY AND PROTECTIVE DEVICES

Unit components are protected from damage by safety and protective devices listed in Table 2--1. These de­vices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition oc­curs.
Open safety switch contacts on either or both of devices IP--CP or HPS will shut down the compressor.
Table 2--1 Safety and Protective Devices
Open safety switch contacts on device IP--CM will shut down the condenser fan motor.
The entire refrigeration unit will shut down if one of the following safety devices open: (a) circuit breaker(s); (b) fuse (F3A/F3B, 7.5A); or (c) evaporator fan motor in­ternal protector(s) -- (IP).
UNSAFE CONDITION
DEVICE DEVICE SETTING
Circuit Breaker (CB--1) -- Manual Reset Tripsat29amps(460VAC)
Excessive current draw Circuit Breaker (CB--2, 50 a mp) -- Manual Reset Trips at 62.5 amps (230 VAC)
Circuit Breaker (CB--2, 70 a mp) -- Manual Reset Trips at 87.5 amps (230 VAC)
Excessive current draw in the control circuit
Excessive current draw by the controller
Excessive current draw by the Emergency Bypass module
Excessive condenser fan motor winding temperature
Excessive compressor motor winding temperature
Excessive evaporator fan motor(s) winding temperature
Abnormal pressures/tempera­tures in the high refrigerant side
Abnormally high discharge pressure
Fuse(F3A&F3B) 7.5 amp rating
Fuse (F1 & F2) 5 amp rating
Fuse (FEB) 10 amp rating
Internal Protector (IP--CM) -- Automatic Reset N/A
Internal Protector (IP--CP) -- Automatic Reset N/A
Internal Protector(s) (IP--EM) -- Automatic Reset N/A
FusiblePlug--UsedontheReceiver
Rupture Disc -- Used on the Water--Cooled Con-
99C = (210F)
35 kg/cm
2
= (500 psig)
denser
High Pressure Switch (HPS)
Opens at 25 kg/cm (350 psig)
2
2--9
T-340
Page 24

2.5 REFRIGERATION CIRCUIT

2.5.1 Standard Operation

Starting at the compressor, (see Figure 2--7, upper schematic) the suction gas is compressed to a higher pressure and temperature.
The refrigerant gas flows through the discharge line and continues into the air--cooled condenser. When operat­ing with the air--cooled condenser active, air flowing across the coil fins and tubes cools the gas to saturation temperature. By removing latent heat, the gas con­denses to a high pressure/high temperature liquid and flows to the receiver, which stores the additional charge necessary for low temperature operation.
When operating with the water--cooled condenser ac­tive (see Figure 2--7, lower schematic), the refrigerant gas passes through the air--cooled condenser and en­ters the water--cooled condenser shell. The water flow­ing inside the tubing cools the gas to saturation temper­ature in the same manner as the air passing over the air--cooled condenser. The refrigerant condenses on the outside of the tubes and exits as a high temperature liquid. The water--cooled condenser also acts as a re­ceiver, storing refrigerant for low temperature operation.
The liquid refrigerant continues through the liquid line, the filter drier (which keeps refrigerant clean and dry) and the economizer (not active during standard opera­tion) to the electronic expansion valve. As the liquid re­frigerant passes through the variable orifice of the ex­pansion valve, some of it vaporizes into a gas (flash gas). Heat is absorbed from the return air by the balance of the liquid, causing it to vaporize in the evaporator coil. The vapor then flows through the suction tube back to the compressor.
On systems fitted with a water pressure switch, the con­denser fan will be off when there is sufficient pressure to open the switch. If water pressure drops below the switch cut out setting, the condenser fan will automatic­ally start.
During the standard mode of operation, the normally closed digital unloader valve (DUV) controls the system
refrigerant flow and capacity by loading and unloading the compressor in frequent discrete time intervals. If the system capacity has been decreased to the lowest al­lowable capacity with the DUV, the unit will enter a trim heat mode of operation, during which the controller will pulse the evaporator heaters in sequence with the com­pressor digital signal in order to absorb the excess capa­city.
2.5.2 Economized Operation
In the economized mode, (see Figure 2--8) the frozen and pull down capacity of the unit is increased by sub­cooling the liquid refrigerant entering the electronic ex­pansion valve. Overall efficiency is increased because the gas leaving the economizer enters the compressor at a higher pressure, therefore requiring less energy to compress it to the required condensing conditions.
Liquid refrigerant for use in the economizer circuit is tak­en from the main liquid line as it leaves the filter drier. The flow is activated when the controller energizes the economizer solenoid valve (ESV).
The liquid refrigerant flows through the ESV to the ex­pansion valve internal passages, absorbing heat from the liquid refrigerant flowing to the electronic expansion valve. The resultant “medium” temperature/pressure gas enters the compressor at the economizer port fit­ting.
When the air temperature falls to 2.0 C (3.6 F) above set point, the DUV unloads the compressor’s scroll and be­gins to reduce the capacity of the unit. Percentage of the unit capacity is accessed through code select 01 (Cd01). For example, if Cd01 displays 70, it indicates that the compressor is operating unloaded with the DUV engaged 30% of the time.
2.5.3 Electronic Expansion Valve
The microprocessor controls the superheat leaving the evaporator via the electronic expansion valve (EEV), based on inputs from the evaporator pressure trans­ducer (EPT). The microprocessor transmits electronic pulses to the EEV stepper motor, which opens or closes the valve orifice to maintain the superheat set point.
2--10T-340
Page 25
ECONOMIZER SOLENOID VALV E
ECONOMIZER
TXV
FILTER DRIER
LIQUID LINE SERVICE VALV E
STANDARD OPERATION WITH RECEIVER
EVAPORATOR
CONDENSER
ECONOMIZER
ECON.
TXV
SENSING
BULB
SIGHT
GLASS
LIQUID LEVEL/
MOISTURE
INDICATOR
COMBO
ETS1 AND 2
RECEIVER
DISCHARGE PRESSURE TRANSDUCER
ELECTRONIC EXPANSION VALV E
DIGITAL UNLOADER VALV E
COMPRESSOR
DISCHARGE TEMPERATURE SENSOR
DISCHARGE SERVICE VALV E
EVAPORATOR PRESSURE TRANSDUCER
SUCTION PRESSURE TRANSDUCER
SUCTION SERVICE VALV E
STANDARD OPERATION WITH WATER--COOLED CONDENSER
ECONOMIZER SOLENOID VALV E
ECONOMIZER
TXV
FILTER DRIER
LIQUID LINE SERVICE VALV E
EVAPORATOR
CONDENSER
ECONOMIZER
MOISTURE INDICATOR
WATER-- COOLE D
ETS1 AND 2
CONDENSER
DISCHARGE PRESSURE TRANSDUCER
SIGHT GLASS
ELECTRONIC EXPANSION VALV E
DIGITAL UNLOADER VALV E
COMPRESSOR
DISCHARGE LIQUID
DISCHARGE TEMPERATURE SENSOR
DISCHARGE SERVICE VALV E
EVAPORATOR PRESSURE TRANSDUCER
SUCTION PRESSURE TRANSDUCER
SUCTION SERVICE VALV E
SUCTION
Figure 2--7 Refrigeration Circuit Schematic -- Standard Operation
2--11
T-340
Page 26
ECONOMIZER SOLENOID VALV E
ECONOMIZER
TXV
LIQUID LINE SERVICE VALV E
ECONOMIZER
ECON.
TXV
SENSING
BULB
RECEIVER
ELECTRONIC EXPANSION VALV E
COMPRESSOR
Figure 2--8 Refrigeration Circuit Schematic -- Economized Operation
LIQUID
ECONOMIZER PRESSURE
2--12T-340
Page 27
SECTION 3
MICROPROCESSOR

3.1 TEMPERATURE CONTROL MICROPROCESSOR SYSTEM

The temperature control Micro--Link 3 microprocessor system (see Figure 3--1) consists of a keypad, display module, the control module (controller) and intercon­necting wiring. The controller houses the temperature control software and the DataCORDER software. The temperature control software functions to operate the unit components as required to provide the desired car­go temperature and humidity. The DataCORDER soft­ware functions to record unit operating parameters and
CONTROL MODULE
TEMPERATURE CONTROL SOFTWARE
cargo temperature parameters for future retrieval. Cover­age of the temperature control software begins with para­graph 3.2. Coverage of the DataCORDER software is provided in paragraph 3.7.
The keypad and display module serve to provide user access and readouts for both of the controller functions, temperature control and DataCORDER. The functions are accessed by keypad selections and viewed on the display module. The components are designed to per­mit ease of installation and removal.
DISPLAY MODULE
KEYPAD
CONFIGURATION
SOFTWARE
CONFIGURATION
VARIABLE
(CnF##)
DataCORDER SOFTWARE
CONFIGURATION
SOFTWARE
CONFIGURATION
VARIABLE
(dCF## read only)
OPERATIONAL
SOFTWARE
FUNCTION CODE (Cd)
OPERATIONAL
SOFTWARE
FUNCTION CODE (dC)
ALARMS
(AL<70)
TO
DISPLAY
ALARMS
(AL>68)
TO
DISPLAY
PRE--TRIP
DATA
STORAGE
MEMORY
TO
DISPLAY
(Scrollback)
INTERROGATION CONNECTOR
DATAREADER
Computer Device
With DataLINE
Software
DATABANK CARD
Figure 3--1 Temperature Control System
3--1
T-340
Page 28
3.1.1 Keypad
Table 3--1 Keypad Function
The keypad (Figure 3--2) is mounted on the right--hand side of the control box. The keypad consists of eleven push button switches that act as the user’s interface with the controller. Descriptions of the switch functions are provided in Table 3--1.
1
3
2
4
5
6
8
10
1. Code Select
2. Pre--trip
3. Alarm List
4. Manual Defrost/ Interval
7
9
11
6. UP Arrow
7. DOWN Arrow
8. Return/Supply
9. Celsius/Fahrenheit
10. Battery Power
Figure 3--2 Keypad
3.1.2 Display Module
The display module (Figure 3--3) consists of two 5--digit displays and seven indicator lights. The indicator lights include:
1. Cool -- White or Blue LED: Energized when the re­frigerant compressor is energized.
2. Heat -- Orange LED: Energized to indicate heater op­eration in the heat or defrost mode.
3. Defrost -- Orange LED: Energized when the unit is in the defrost mode.
4. In--Range -- Green LED: Energized when the con­trol led tempe ratur eprobe is within specified tolerance of set point.
KEY
FUNCTION
Code Select Accesses function codes.
Pre--trip
Alarm List
Manual Defrost/
Interval
Displays the pre--trip selection menu. Discontinues pre--trip in progress.
Displays alarm list and clears the alarm queue.
Displays selected defrost mode. De­pressing and holding the Defrost in­terval key for five (5) seconds will ini­tiate defrost using the same logic as if the optional manual defrost switch was toggled on.
Enter
Arrow Up
Arrow Down
Return/
Supply
Confirms a selection or saves a selection to the controller.
Change or scroll a selection upward Pre--trip advance or test interruption.
Change or scroll a selection down­ward. Pre--trip repeat backward.
Displays non--controlling probe tem­perature (momentary display).
Displays alternate English/Metric scale (momentary display). When set to F, pressure is displayed in psig and
Celsius /
Fahrenheit
vacuum in “/hg.” “P” appears after the value to indicate psig and “i” appears for inches of mercury.
When set to C, pressure readings are in bars. “b” appears after the value to indicate bars.
Battery
Power
Initiate battery backup mode to allow set point and function code selection if AC power is not connected.
This key is pressed to switch the functions from the temperature soft­ware to the DataCORDER Software.
ALT. Mode
The remaining keys function the same as described above except the readings or changes are made to the DataCORDER programming.
NOTE
The controlling probe in the perishable range will be the SUPPLY air probe and the controlling probe in the frozen range will be the RETURN air probe.
5. Supply -- Yellow LED: Energized when the supply air probe is used for control. When this LED is illumi­nated, the temperature displayed in the AIR TEM­PERATURE display is the reading at the supply air probe. This LED will flash if dehumidification or hu­midification is enabled.
6. Return -- Yellow LED: Energized when the return air probe is used for control. When this LED is illumi­nated, the temperature displayed in the AIR TEM­PERATURE display is the reading at the return air probe. This LED will flash if dehumidification or hu­midification is enabled.
7. Alarm -- Red LED: Energized when there is an active or an inactive shutdown alarm in the alarm queue.
3--2T-340
Page 29
COOL HEAT DEFROST IN RANGE ALARM SUPPLY RETURN
SETPOINT/Code AIR TEMPERATURE/Data
Figure 3--3 Display Module
3.1.3 Controller
CAUTION
Do not remove wire harnesses from con­troller modules unless you are grounded to the unit frame with a static safe wrist strap.
CAUTION
Unplug all controller module wire harness connectors before performing arc welding on any part of the container.
CAUTION
Do not attempt to use an ML2i PC card in an ML3 equipped unit. The PC cards are physi­cally different and will result in damage to the controller.
NOTE
Do not attempt to service the controller mod­ules. Breaking the seal will void the warranty.
The Micro--Link 3 controller is a dual module micropro­cessor as shown in Figure 3--4. It is fitted with test points, harness connectors and a software card pro­gramming port.

3.2 CONTROLLER SOFTWARE

The controller software is a custom designed program that is subdivided into configuration software and opera­tional software. The controller software performs the fol­lowing functions:
a. Control supply or return air temperature to required
limits, provide modulated refrigeration operation, economized operation, unloaded operation, electric heat control and defrost. Defrost is performed to clear buildup of frost and ice and ensure proper air flow across the coil.
b. Provide default independent readouts of set point and
supply or return air temperatures.
c. Provide ability to read and (if applicable) modify the
configuration software variables, operating software Function Codes and Alarm Code indications.
d. Provide a Pre--trip step--by--step checkout of refrig-
eration unit performance including: proper compo­nent operation, electronic and refrigeration control operation, heater operation, probe calibration, pres­sure limiting and current limiting settings.
e. Provide battery--powered ability to access or change
selected codes and set point without AC power con­nected.
f. Provide the ability to reprogram the software through
the use of a memory card.
3.2.1 Configuration Software (Variables)
The configuration software is a variable listing of the components available for use by the operational soft­ware. This software is factory installed in accordance with the equipment fitted and options listed on the origi­nal purchase order. Changes to the configuration soft­ware are required only when a new controller has been installed or a physical change has been made to the unit such as the addition or removal of an option. A configu­ration variable list is provided in Table 3--4. Change to the factory--installed configuration software is achieved via a configuration card or by communications.
3.2.2 Operational Software (Function Codes)
The operational software is the actual operation pro­gramming of the controller which activates or deacti­vates components in accordance with current unit oper­ating conditions and operator selected modes of operation.
1. Mounting Screw
2. Micro--Link 3 Control/DataCORDER Module
3. Connectors
4. Test Points
Figure 3--4 Control Module
5. Fuses
6. Control Circuit Power Connection
7. Software Programming Port
8. Battery Pack (Standard Location)
3--3
812 33 3 3 345 67
T-340
Page 30
The programming is divided into function codes. Some of the codes are read only while the remaining codes may be user configured. The value of the user configur­able codes can be assigned in accordance with user de­sired mode of operation. A list of the function codes is provided in Table 3--5.
To access the function codes, perform the following:
a. Press the CODE SELECT key, then press an arrow
key until the left window displays the desired code number.
b. The right window will display the value of this item for
five seconds before returning to the normal display mode.
c. If a longer time is desired, press the ENTER key to ex-
tendthetimetofiveminutes.

3.3 CONTROLLER SEQUENCE AND MODES OF OPERATION

General operation sequences for cooling, heating and defrost are provided in the following subparagraphs. Schematic representation of controller action is provided in Figure 3--5.
The operational software responds to various inputs. These inputs come from the temperature and pressure sensors, the temperature set point, the settings of the configuration variables and the function code assign­ments. The action taken by the operational software will change if any one of the inputs change. Overall interac­tion of the inputs is described as a “mode” of operation. The modes of operation include perishable (chill) mode and frozen mode. Descriptions of the controller interac­tion and modes of operation are provided in the following sub paragraphs.
3.3.1 Start up -- Compressor Phase Sequence
The controller logic will check for proper phase sequen­cing and compressor rotation. If sequencing is allowing the compressor and three--phase evaporator fan motor to rotate in the wrong direction, the controller will ener­gize or de--energize relay TCP as required (see Figure 7--2). Relay TCP will switch its contacts, energizing or de--energizing relays PA and PB. Relay PA is wired to energize the circuits(s) on L1, L2 and L3. Relay PB is wired to energize the circuit(s) on L3, L2, and L1, thus providing reverse rotation.
3.3.2 Start up -- Compressor Bump Start
The controller logic will initiate a compressor bump start procedure to clear refrigerant from the compressor. If suction and discharge pressures have equalized, the compressor will perform three compressor bump starts. A compressor bump start may occur after a defrost has been completed.
During the procedure, the EEV will close. Relays TS, TQ, TN, TE, TV will be de--energized (opened). The res­ult of this action will close the ESV and shut all fans off. The compressor will start for 1 second, then pause for five seconds. This sequence will be repeated two addi­tional times. After the final bump start the unit will pre-­position the EEV to correct starting position pause and startup.
3.3.3 Perishable Set Point Temperature -- Perish-
able Pulldown
When cooling from a temperature that is more than 2.5C (4.5F) above set point, the system will be in the perish-
able pulldown mode in economized operation. Howev­er, pressure and current limit functions may restrict the valve if either exceeds the preset value.
3.3.4 Perishable Set Point Temperature -­Standard Temperature Control Mode
The unit is capable of maintaining supply air tempera­ture to within +/--0.2C (+/--0.36F) of set point. Supply air temperature is controlled by positioning of the electronic expansion valve (EEV), cycling of the digital unloader valve (DUV), cycling of the compressor and cycling of the heaters.
Once set point is reached, the unit will transition to the perishable steady state mode. This results in unloaded operation by cycling the DUV to limit capacity and main­tain steady temperature control.
If the controller has determined that cooling is not re­quired or the controller logic determines suction pres­sure is at the low pressure limit, the unit will transition to the perishable idle mode. The compressor is turned off and the evaporator fans continue to run to circulate air throughout the container. If temperature rises above set point +0.2C, the unit will transition back to the perishable steady state mode
If the temperature drops to 0.5C (0.9F) below set point, the unit will transition to the perishable heating mode and the heaters will be energized. The unit will transition back to the perishable idle mode when the temperature rises to 0.2C (0.4F) below the set point and the heaters will de--energize.
3.3.5 Perishable Set Point Temperature -­Economy Fa n Ope r a tion Mode
The economy mode is an extension of the standard mode. The mode is activated when the setting of func­tion code Cd34 is “ON.” Economy mode is provided for power saving purposes. Economy mode could be uti­lized in the transportation of temperature--tolerant cargo or non--respiration items which do not require high air­flow for removing respiration heat. There is no active display indicator that economy mode has been acti­vated. To check for economy mode, perform a manual display of code Cd34.
In order to achieve economy mode, a perishable set point must be selected prior to activation. When econ­omy mode is active, the evaporator fans will be con­trolled as follows:
At the start of each cooling or heating cycle, the evapo­rator fans will run in high speed for three minutes. They will then be switched to low speed any time the supply air temperature is within +/-- 0.2C (0.36F) of the set point and the return air temperature is less than or equal to the supply air temperature +3C (5.4F). The fans will contin­ue to run in low speed for one hour. At the end of the hour, the evaporator fans will switch back to high speed and the cycle will be repeated. If bulb mode is active, the economy fan activity will be overridden.
3.3.6 Perishable Set Point Temperature Control
With configuration variable CnF26 (Heat Lockout Tem­perature) set to -- 10C the perishable mode of operation is active with set points above --10C (+14F). With the variable set to -- 5C, the perishable mode is active above
--5C (+23F). Refer to Table 3--4.
When in the perishable mode, the controller maintains the supply air temperature at set point, the SUPPLY in­dicator light will be illuminated on the display module and the default reading on the display window will be the supply temperature sensor reading.
3--4T-340
Page 31
FALLING
TEMPERA TURE
RISING
TEMPERA TURE
+2.5C (4.5F)
MODULATED
UNLOADED
COOLING
MODULATED
UNLOADED
COOLING
+0.20C
SET POINT
AIR CIRCULATION
--0.20C
AIR CIRCULATION
--0.5C
(0.9F)
HEATING
NOTE 1: TEMPERATURE INDICATIONS ARE ABOVE OR BELOW SET POINT. NOTE 2: ECONOMIZED UNLOADED COOLING OCCURS IF RETURN TEMPERATURE
IS GREATER THAN SET POINT PLUS 1.9 C AND IS GREATER THAN 70%. IF BOTH CONDITIONS ARE NOT MET, STANDARD UNLOADED COOLING OCCURS.
HEATING
IF CAPACITY MODULATION
Figure 3--5 Controller Operation -- Perishable Mode
When the supply air temperature enters the in--range temperature tolerance (as selected at function code Cd30), the in--range light will energize.
3.3.7 Perishable Mode Cooling -- Sequence of Operation
NOTE
In the Standard Perishable Mode of Operation, the evaporator motors run in high speed. In the Economy Perishable Mode, the fan speed is varied.
a. With supply air temperature above set point and de-
creasing, the unit will cool with the condenser fan motor (CF), compressor motor (CH), evaporator fan motors (EF) energized and the COOL light illumin­ated. (See Figure 3--6). Also, if current or pressure limiting is not active, the controller will close contacts TS to open the economizer solenoid valve (ESV) and place the unit in economized operation.
b. When the air temperature decreases to a predeter-
mined tolerance above set point, the in--range light is illuminated.
ENERGIZED DE--ENERGIZED
ST
HPS
IP-- EM1
F
HTT
IP-- CM
TS
IP-- EM2
ESV
TC
TN
TH
24 VOLT POWER
CF
EF
TV
TE
HR
CH
ES
EF
NOTE: The EEV and DUV are independently oper­ated by the microprocessor. For full diagrams and leg­end, see Section 7.
Figure 3--6 Perishable Mode -- Cooling
3--5
T-340
Page 32
c. As the air temperature continues to fall, unloaded
cooling starts approximately 2.5C (4.5F) above set point. (See Figure 3--5). When unloaded cool starts, the EEV control will transition from a full cool super­heat set point to a lower modulated cool superheat set point. Once unloading starts, the EEV controls evaporator superheat based on the system duty cycle where instantaneous superheat will vary. When the return air has fallen to within 1.9C (3.4F) of set point temperature and the average capacity of the system has fallen below 70%, the unit will open con­tacts TS and close the ESV.
d. The controller monitors the supply air. Once the sup-
ply air falls below set point, the controller periodically records the supply air temperature, set point and time. A calculation is then performed to determine temperature drift from set point over time. If the calcu­lation determines cooling is no longer required, con­tacts TC and TN are opened to de--energize com­pressor motor and condenser fan motor. In addition the controller will close the EEV . Perishable heat mode is locked disabled for five minutes. The cool light is also de--energized.
e. The evaporator fan motors continue to run to circulate
air throughout the container. The in--range light re­mains illuminated as long as the supply air is within tolerance of set point.
f. If the return air temperature increases to 1.0C (1.8F)
above set point and three minutes have elapsed, con­tacts TC and TN close to restart the compressor and condenser fan motors in standard mode (non--eco­nomized) operation. The cool light is also illuminated.
g. If the average system capacity has risen to 100% dur-
ing unloaded cooling and three minutes has elapsed, relay TS will energize and open the ESV, placing the unit in economized mode.
h. If the supply air increases more than 2.5C (4.5F)
above set point temperature, the microprocessor will transition the evaporator superheat control from modulation back to full cool control.
3.3.8 Perishable Mode Heating -- Sequence of Operation
a. If the air temperature decreases 0.5C (0.9F) below
set point, the system enters the heating mode. (See Figure 3--5). The controller closes contacts TH (see Figure 3--7) to allow power flow through the heat ter­mination thermostat (HTT) to energize the heaters (HR). The HEAT light is also illuminated. The evapor­ator fans continue to run to circulate air throughout the container.
b. When the temperature rises to 0.2C (0.4F) below set
point, contacts TH open to de--energize the heaters. The HEAT light is also de--energized. The evaporator fans continue to run to circulate air throughout the container.
c. The safety heater termination thermostat (HTT) is at-
tached to an evaporator coil circuit and will open the heating circuit if overheating occurs.
ENERGIZED DE--ENERGIZED
ST
HPS
IP-- EM1
F
HTT
IP-- CM
TS
IP-- EM2
ESV
TC
TN
TH
24 VOLT POWER
TV
EF ES
TE
HR
CH
CF
EF
NOTE: The EEV and DUV are independently oper­ated by the microprocessor. For full diagrams and leg­end, see Section 7.
Figure 3--7 Perishable Mode Heating
3.3.9 Sequence of Operation -- Perishable Mode (Capacity Trim Heat)
a. If the system capacity has been decreased to the low-
est allowable capacity and conditions exist that warrant maximum temperature stability the controller will pulse the HR relay to energize the evaporator heaters in se­quence with the compressor digital signal. Trim heat is enabled only if (12.77C < set point < 15.55C [54.99F < set point < 59.99F]) and (--6.67C < ambient temperat­ure < 1.66 C [19.99F < ambient temperature < 34.99F]).
3.3.10 Perishable Mode -- Dehumidification
The dehumidification mode is provided to reduce the hu­midity levels inside the container. The mode is activated when a humidity value is set at function code Cd33. The display module SUPPLY LED will flash ON and OFF ev­ery second to indicate that the dehumidification mode is active. Once the Mode is active and the following condi­tions are satisfied, the controller will activate the heat relay to begin dehumidification.
1. The humidity sensor reading is above the set point.
2. The unit is in the perishable steady state mode and
supply air temperature is less than 0.2C (0.36F) above set point.
3. The heater debounce timer (three minutes) has
timed out.
4. Heater termination thermostat (HTT) is closed.
If the above conditions are true the evaporator fans will switch from high to low speed operation. The evaporator fan speed will switch every hour thereafter as long as all conditions are met (see Bulb Mode section for different evaporator fan speed options). If any condition except item (1) becomes false OR if the relative humidity sensed is 2% below the dehumidification set point, the high speed evaporator fans will be energized.
Power is applied to the defrost heaters in the dehumidifi­cation mode. This added heat load causes the controller to open the ESV to match the increased heat load while still holding the supply air temperature very close to the set point.
Opening the ESV reduces the temperature of the evap­orator coil surface, which increases the rate at which water is condensed from the passing air. Removing wa-
3--6T-340
Page 33
ter from the air reduces the relative humidity. When the relative humidity sensed is 2% below the set point, the controller de--energizes the heat relay . The controller will continue to cycle heating to maintain relative humid­ity below the selected set point. If the mode is termi­nated by a condition other than the humidity sensor, e.g., an out--of--range or compressor shutdown condi­tion, the heat relay is de--energized immediately.
Two timers are activated in the dehumidification mode to prevent rapid cycling and consequent contactor wear. They are:
1. Heater debounce timer (three minutes).
2. Out--of--range timer (five minutes).
The heater debounce timer is started whenever the heater contactor status is changed. The heat contactor remains energized (or de--energized) for at least three minutes even if the set point criteria are satisfied.
The out--of--range timer is started to maintain heater op­eration during a temporary out--of--range condition. If the supply air temperature remains outside of the user selected in--range setting for more than five minutes, the heaters will be de--energized to allow the system to re­cover. The out--of--range timer starts as soon as the temperature exceeds the in--range tolerance value set by function code Cd30.
3.3.11 Perishable, Dehumidification -- Bulb Mode
Bulb mode is an extension of the dehumidification mode, which allows changes to the evaporator fan speed and/or defrost termination set points.
Bulb mode is active when configuration code Cd35 is set to “Bulb.” Once the bulb mode is activated, the user may then change the dehumidification mode evaporator fan operation from the default (speed alternates from low to high each hour) to constant low or constant high speed. This is done by toggling function code Cd36 from its default of “alt” to “Lo” or “Hi” as desired. If low speed evaporator fan operation is selected, this gives the user the additional capability of selecting dehumidification set points from 60 to 95% (instead of the normal 65 to 95%).
In addition, if bulb mode is active, function code Cd37 may be set to override the previous defrost termination thermostat settings. (Refer to paragraph 3.3.19) The temperature at which the defrost termination thermostat will be considered “open” may be changed [in 0.1C (0.2F) increments] to any value between 25.6C (78F) and 4C (39.2F). The temperature at which the defrost termination thermostat is considered closed for interval timer start or demand defrost is 10C for “open” values from 25.6C (78F) down to a 10C setting. For “open” val­ues lower than 10C, the “closed” values will decrease to the same value as the “open” setting. Bulb mode is ter­minated when:
1. Bulb mode code Cd35 is set to “Nor.”
2. Dehumidification code Cd33 is set to “Off.”
3. The user changes the set point to one that is in the frozen range.
When bulb mode is disabled by any of the above, the evaporator fan operation for dehumidification reverts to “alt” and the DTS termination setting resets to the value determined by controller configuration variable CnF41.
3.3.12 Frozen -- Pulldown
Schematic representation of controller action is provided in Figure 3--8. When cooling from a tempera­ture that is more than 2.5C (4.5F) above set point, the system will be in the frozen pulldown mode. It will transi­tion to economized operation. However, pressure and current limit functions may restrict the valve, if either ex­ceeds the preset value.
3.3.13 Frozen Mode Temperature Control
When in the frozen mode, the controller maintains the return air temperature at set point, the RETURN indica­tor light will be illuminated on the display module andthe default reading on the display window will be the return air probe reading.
When the return air temperature enters the in--range temperature tolerance as selected at function code Cd30, the in--range light will energize.
3.3.14 Frozen Mode -- Standard
Frozen range cargos are not sensitive to minor temper­ature changes. The method of temperature control employed in this range takes advantage of this to greatly improve the energy efficiency of the unit. Temperature control in the frozen range is accomplished by cycling the compressor on and off as the load demand requires.
Once set point is reached, the unit will transition to the frozen steady state mode (economized operation).
When temperature drops to set point minus 0.2C and the compressor has run for at least five minutes, the unit will transition to the frozen idle mode. The compressor is turned off and the evaporator fans continue to run to cir­culate air throughout the container. If temperature rises above set point +0.2C, the unit will transition back to the frozen steady state mode.
3.3.15 Frozen Mode -- Heat Lockout Temperature
With configuration variable CnF26 (Heat Lockout Tem­perature) set to --10C the frozen mode of operation is active with set points at or below --10C (+14F). With the variable set to --5C, the frozen mode is active at or below
--5C (+23F).
If the temperature drops 10C below set point, the unit will transition to the frozen “heating” mode, in which the evaporator fans are brought to high speed. The unit will transition back to the frozen steady state mode when the temperature rises back to the transition point.
3.3.16 Frozen Mode -- Economy
In order to activate economy frozen mode operation, a frozen set point temperature must be selected. The economy mode is active when function code Cd34 isset to “ON.” When economy mode frozen is active, the sys­tem will perform normal frozen mode operations except that the entire refrigeration system, excluding the con­troller, will be turned off when the control temperature is less than or equal to the set point --2C. After anoff--cycle period of 60 minutes, the unit will turn on high speed evaporator fans for three minutes, and then check the control temperature. If the control temperature is greater than or equal to the set point +0.2C, the unit will restart the refrigeration system andcontinue to cooluntil the previously mentioned off--cycle temperature criteria are met. If the control temperature is less than the set point +0.2C, the unit will turn off the evaporator fans and restart another 60 minute off--cycle.
3--7
T-340
Page 34
FALLING
TEMPERATURE
RISING
TEMPERATURE
ECONOMIZED
COOLING
+0.2 C
SET POINT
SET POINT
-- 0 . 2 C
AIR CIRCULATION
NOTE: TEMPERATURES INDICATIONS ARE ABOVE OR BELOW SET POINT
Figure 3--8 Controller Operation -- Frozen Mode
3.3.17 Frozen Mode Cooling -- Sequence of Opera­tion
a. When the supply air temperature is above set point
and decreasing, the unit will transition to economized cooling with the condenser fan motor (CF), com­pressor motor (CH), economizer solenoid valve (ESV), low speed evaporator fan motors (ES) ener­gized and the COOL light illuminated. (See Figure 3--9).
b. When the air temperature decreases to a predeter-
mined tolerance above set point, the in--range light is illuminated.
c. When the return air temperature decreases to 0.2C
(0.4F) below set point, contacts TC, TS and TN are opened to de--energize the compressor, economizer solenoid valve and condenser fan motor. The cool light is also de--energized. The EEV will close.
d. The evaporator fan motors continue to run in low
speed to circulate air throughout the container. The in--range light remains illuminated as long as the re­turn air is within tolerance of set point.
e. If return air temperature drops to 10C (18F) or more
below set point, the evaporator fans increase to high speed.
f. When the return air temperature increases to 0.2C
(0.4F) above set point and three minutes have elapsed, the EEV opens and contacts TC, TS and TN close to restart the compressor, open the ESV and re­start the condenser fan motor. The cool light isillumin­ated.
ENERGIZED DE--ENERGIZED
ST
HPS
IP-- EM1
F
HTT
IP-- CM
TS
IP-- EM2
ESV
TC
TN
TH
24 VOLT POWER
TV
EF
TE
HR
CH
CF
ES
EF
NOTE: The EEV and DUV are independently oper-
ated by the microprocessor. For full diagrams and leg­end, see Section 7.
Figure 3--9 Frozen Mode
3--8T-340
Page 35
3.3.18 Defrost Interval
Controller function code Cd27 sets two modes for de­frost initiation, either user-- selected timed intervals or automatic control. The user--selected values are 3, 6, 9, 12, 24 hours orAUTO. Some units may be configured to allow defrost to be disabled altogether. In this case, a user--selected value of OFF will be available. The facto­ry default for defrost is AUTO. Refer to Table 3--5.
In perishable mode, perishable--pulldown mode, or frozen--pulldown mode, automatic defrost starts with an initial defrost set to three hours and then adjusts the in­terval to the next defrost based on the accumulation of ice on the evaporator coil. In this way, defrosts are scheduled to occur only when necessary.
Once set point has been reached in frozen operation, the automatic selection will set the time interval to 12 hours for the first two defrosts once the return probe is reading below the frozen set point and then adjust to 24 hours thereafter.
All defrost interval times reflect the number of compres­sor runtime hours since the last defrost de--ice cycle. The minimum defrost interval under the automatic set­ting is three hours while the maximum is 24. In frozen mode the amount of wall--clock time necessary to accu­mulate a given amount of defrost interval time will ex­ceed the defrost interval time by a factor of two to three depending on the compressor duty--cycle. Defrost inter­val time is not accumulated in any mode until the defrost termination sensor reads less than 10C (50F).
If defrost does not terminate correctly and temperature reaches set point of the heat termination thermostat (HTT), the thermostat will open to de--energize the heat­ers. If termination does not occur within two hours,the controller will terminate defrost. An alarm will be activ­ated to inform of a possible DTS failure.
If probe check (controller function code CnF31) is con­figured to SPECIAL, the unit will proceed to the next op­eration (snap freeze or terminate defrost). If the code is configured to STANDARD, the unit will perform a probe check. The purpose of the probe check is to detect mal­functions in the sensed temperature. If probe check fails, the system will run for eight minutes to validate. At the end of eight minutes, probe alarms will be set or cleared based on the conditions seen.
When the return air falls to 7C (45F), the controller en­sures that the defrost temperature sensor (DTS) read­ing has dropped to 10C or below. If it has not, a DTS fail­ure alarm is given and the defrost mode is operated by the return temperature sensor (RTS).
If controller function code CnF33 is configured to snap freeze, the controller will sequence to this operation. The snap freeze consists of running the compressor without the evaporator fans in operation for a period of 4 minutes at 100% capacity. When the snap freeze is completed, defrost is formally terminated.
3.3.19 Defrost Mode -- Sequence of Operation
a. The defrost cycle may consist of up to three distinct
operations. The first is de--icing of the coil, the second is a probe check cycle and the third is snap freeze. Defrost may be initiated by any one of the following methods:
1. The manual defrost function (also manual defrost switch function, if equipped) is initiated by the user through the use of the keypad or manual defrost
switch. The manual defrost function is ended by use of the DTS.
NOTE
The Manual Defrost / Interval key can be used to initiate a manual defrost.
Manual Defrost/Interval key operation: Depressing and holding the Defrost Interval key for five seconds will initiate defrost. If the defrost interval key is released in less than five seconds, defrost interval (code 27) shall be dis­played.
2. The user sends a defrost command by communica­tions.
3. The defrost interval timer (controller function code Cd27) reaches the defrost interval set by the user.
4. The controller probe diagnostic logic determines that a probe check is necessary based on the temperature values currently reported by the supply and return probes.
5. If the controller is programmed with the Demand De­frost option and the option is set to “IN” the unit will enter defrost if it has been in operation for more than
2.5 hours without reaching set point.
6. The system is actively in a compressor suction pres­sure or high pressure ratio protection mode and re­duced the average system capacity below apredeter­mined threshold value.
Defrost may be initiated any time the defrost temperat­ure sensor reading falls below the controller defrost ter­mination thermostat set point. Defrost will terminate when the defrost temperature sensor reading rises above the defrost termination thermostat set point. The defrost termination thermostat is not a physical com­ponent. It is a controller setting that acts as a thermo­stat, “closing” (allowing defrost) when the defrost tem­perature sensor reading is below the set point and “opening” (terminating or preventing defrost) when the sensor temperature reading is above set point. When the unit is operating in bulb mode (refer to paragraph
3.3.11), special settings may be applicable.
If the controller is programmed with the Lower DTT set­ting option, the defrost termination thermostat set point may be configured to the default of 25.6C (78F) or lowered to 18C (64F). When a request for defrost is made through the manual defrost switch, communica­tions or probe check the unit will enter defrost if the de­frost temperature thermostat reading is at or below the defrost termination thermostat setting. Defrost will ter­minate when the defrost temperature sensor reading rises above the defrost termination thermostat setting. When a request for defrost is made with the defrost in­terval timer or by demand defrost, the defrost temperat­ure setting must be below 10C (50F).
When the defrost mode is initiated, the controller closes the EEV, opens contacts TC, TN and TE (or TV) to de-­energize the compressor, condenser fan and evaporat­or fans. The COOL light is also de--energized. The con­troller then closes contacts TH to supply power to the heaters. The defrost light is illuminated. When the de­frost temperature sensor reading rises to the defrost ter­mination thermostat setting, the de--icing operation is terminated.
3--9
T-340
Page 36
ENERGIZED DE--ENERGIZED
ST
HPS
IP-- EM1
F
HTT
IP-- CM
TS
IP-- EM2
ESV
TC
TN
TH
24 VOLT POWER
CF
TV
EF ES
TE
HR
PB
EF
NOTE: The EEV and DUV are independently oper­ated by the microprocessor. For full diagrams and leg­end, see Section 7.
Figure 3--10 Defrost

3.4 PROTECTION MODES OF OPERATION

3.4.1 Evaporator Fan Operation
Opening of an evaporator fan internal protector will shut down the unit.
3.4.2 Failure Action
Function code Cd29 may be operator set to select ac­tion the controller will take upon system failure. The fac­tory default is full system shutdown. Refer to Table 3--5.
3.4.3 Generator Protection
Function codes Cd31(Stagger Start, Offset Time) and Cd32 (Current Limit) may be operator set to control start up sequence of multiple units and operating current draw. The factory default allows on demand starting (no delay) of units and normal current draw. Refer to Table 3--5.
3.4.4 Compressor High Temperature, Low Pres­sure Protection
The controller monitors compressor discharge pres­sure, and temperature and suction pressure. If dis­charge pressure or temperature rises above the allowed limit or suction pressure falls below the allowed limit, the compressor will be cycled off and on every 3 minutes. Condenser and evaporator fans continue to operate during the compressor off cycle.
If high compressor dome temperature occurs, the con­troller will allow additional refrigerant to be released into the system in order to provide cooling to the evaporator coil and compressor dome. The controller is alerted to high compressor dome temperatures via the CPDS when the ambient temperature is greater than 43.3C, the return air temperature is less than --17.5C and if the compressor discharge temperature is greater than 1 17.7C.
Dome temperature control logic will disengage when re­turn air temperature and ambient temperature return to allowed limits or when compressor turns off.
If the suction pressure low limit is triggered, the DUVwill energize to raise the suction pressure.
3.4.5 Perishable Mode -- System Pressure Regula­tion
In perishable mode, system pressures may need to be regulated at ambient temperatures of 20C (68F) and be­low. Once below this ambient temperature, the con­denser fan may cycle on and off based on limits imposed for discharge pressure. For extremely cold ambient temperatures, --18C (0F), heater cycling may occur within normal system operation based on discharge pressure limits.
3.4.6 Condenser Fan Override
When configuration variable CnF17 (Discharge Tem­perature Sensor) is set to “In” and CnF48 (Condenser Fan Switch Override) is set to “On”, the condenser fan switch override logic is activated. If condenser cooling water pressure is sufficient to open the water pressure switch (de--energizing the condenser fan) when water flow or pressure conditions are not maintaining dis­charge temperature, the logic will energize the condens­er fan as follows:
1. If the DUV is less than 80% open when the controller
calls for it to be100% open, the condenser fan is en­ergized. When the DUV is 100% open, the fan will de--energize.
2. If DPT reading is invalid or out of range (AL 65), the
condenser fan is energized and will remain ener­gized until system power is cycled.
3. If the system is running on condenser fan override
and the high pressure switch opens, the condenser fan is energized and will remain energized until the system power is cycled.

3.5 CONTROLLER ALARMS

Alarm display is an independent controller software function. If an operating parameter is outside of ex­pected range or a component does not return the cor­rect signals back to the controller, an alarm is gener­ated. A listing of the alarms is provided in Table 3--6, page 3--22.
The alarm philosophy balances the protection of the re­frigeration unit and that of the refrigerated cargo. The action taken when an error is detected always considers the survival of the cargo. Rechecks are made to confirm that an error actually exists.
Some alarms requiring compressor shutdown have time delays before and after to try to keep the compres­sor on line. An example is alarm code “LO,” (low main voltage), when a voltage drop of over 25% occurs, an in­dication is given on the display, but the unit will continue to run.
When an Alarm Occurs: a. The red alarm light will illuminate for alarm code num-
bers 15, 17, 20, 21, 22, 23, 24, 25, 26, and 27.
b. If a detectable problem exists, its alarm code will be
alternately displayed with the set point on the left dis­play.
c. The user should scroll through the alarm list to deter-
mine what alarms exist or have existed. Alarms must be diagnosed and corrected before Alarm List can be
cleared. To Display Alarm Codes: a. While in the Default Display mode, press the ALARM
LIST key. This accesses the Alarm List Display Mode,
which displays any alarms archived in the alarm
queue.
3--10T-340
Page 37
b. The alarm queue stores up to 16 alarms in the se-
quence in which they occurred. The user may scroll through the list by depressing an ARROW key.
c. The left display will show “AL##,” where ## is the
alarm number sequentially in the queue.
d. The right display will show the actual alarm code.
“AA##” will display for an active alarm, where “##” is the alarm code. Or “IA##” will display for an inactive alarm, See Table 3--6, page 3--22.
e. “END” is displayed to indicate the end of the alarm list
if any alarms are active.
f. “CLEAr” is displayed if all alarms are inactive. The
alarm queue may then be cleared by pressing the EN­TER key. The alarm list will clear and “ -- -- -- -- -- ” will be displayed.
Note:
AL26 is active when all of the sensors are not responding. Check the connector at the back of the controller; if it is loose or unplugged, recon­nect it, then run a pre- -trip test (P5) to clear AL26.
3.6 UNIT PRE--TRIP DIAGNOSTICS
Pre--trip Diagnostics is an independent controller func­tion that suspends normal refrigeration controller activi­ties and provide preprogrammed test routines. The test routines include Auto Mode testing, which automatically preforms a pre programmed sequenced of tests, or Manual Mode testing, which allows the operator to se­lect and run any of the individual tests.
CAUTION
Pre--trip inspection should not be per­formed with critical temperature cargoes in the containe r.
CAUTION
When Pre--trip key is pressed, economy, de­humidification and bulb mode will be deac­tivated. At the completion of Pre--trip activi­ty, econom y, dehumidification and bulb mode must be reactivated.
Testing may be initiated by use of the keypad or via com­munication, but when initiated by communication the controller will execute the entire battery of tests (auto mode).
At the end of a pre--trip test, the message “P,” “rSLts” (pretest results) will be displayed. Pressing the ENTER key will allow the user to see the results for all subtests. The results will be displayed as “PASS” or “FAIL” for all the tests run to completion.

3.7 DataCORDER

3.7.1 Description
The Carrier Transicold “DataCORDER” software is inte­grated into the controller and serves to eliminate the temperature recorder and paper chart. The DataCORD­ER functions may be accessed by keypad selections and viewed on the display module. The unit is also fitted with interrogation connections (see Figure 3--1) which may be used with the Carrier Transicold Data Reader to down load data. A personal computer with Carrier Transicold DataLINE software may also be used to download data and configure settings. The DataCORD­ER consists of:
Configuration Software Operational Software Data Storage Memory Real Time Clock (with internal battery backup) Six Thermistor Inputs Interrogation Connections Power Supply (battery pack)
The DataCORDER performs the following functions:
a. Logs data at 15, 30, 60 or 120 minute intervals and
stores two years of data (based on one hour interval).
b. Records and displays alarms on the display module.
c. Records results of pre--trip testing.
d. Records DataCORDER and temperature control
software generated data and events as follows:
Container ID Change Software Upgrades Alarm Activity Battery Low (battery pack) Data Retrieval Defrost Start and End Dehumidification Start and End Power Loss (with and without battery pack) Power Up (with and without battery pack) Remote Probe Temperatures in the Container (USDA Cold treatment and Cargo probe recording) Return Air Temperature Set Point Change Supply Air Temperature Real Time Clock Battery (internal battery) Replace­ment Real Time Clock Modification Trip Start ISO Trip Header (When entered via Interrogation program) Economy Mode Start and End “Auto 1/Auto 2/Auto 3” Pre--trip Start and End Bulb Mode Start Bulb Mode Changes Bulb Mode End USDA Trip Comment Humidification Start and End USDA Probe Calibration Fresh Air Vent Position
3.7.2 DataCORDER Software
A detailed description of the pre--trip tests and test codes is provided in Table 3--7, page 3--27. detailed op­erating instructions are provided in paragraph 4.9.
The DataCORDER Software is subdivided into the Op­erational Software, Configuration Software, and the Data Memory.
3--11
T-340
Page 38
a. Operational Software
The Operational Software reads and interprets inputs for use by the Configuration Software. The inputs are la­beled Function Codes. Controller functions (see Table 3--8, page 3--31) which the operator may access to examine the current input data or stored data. To ac­cess these codes, do the following:
1. Press the ALT. MODE and CODE SELECT keys.
2. Press an arrow key until the left window displays the desired code number. The right window will display the value of this item for five seconds before return­ing to the normal display mode.
3. If a longer display time is desired, press the ENTER
key to extend the display time to five minutes.
b. Configuration Software
The configuration software controls the recording and alarm functions of the DataCORDER. Reprogramming to the factory--installed configuration is achieved via a configuration card. Changes to the unit DataCORDER configuration may be made made using the DataLINE interrogation software. Alisting of the configuration vari­ables is provided in Table 3--2. Descriptions of Data­CORDER operation for each variable setting are pro­vided in the following paragraphs.
3.7.3 Sensor Configuration (dCF02)
Two modes of operation may be configured, the Stand­ard Mode and the Generic Mode.
a. Standard Mode
In the standard mode, the user may configure the Data­CORDER to record data using one of seven standard configurations. The seven standard configuration vari­ables, with their descriptions, are listed in Table 3--3.
The inputs of the six thermistors (supply, return, USDA #1, #2, #3 and cargo probe) and the humidity sensor in­put will be generated by the DataCORDER. See Figure 3--11.
NOTE
The DataCORDER software uses the supply and return recorder
sensors (SRS, RRS). The temperature control software uses the supply and return temperature
sensors (STS, RTS) .
b. Generic Mode
The generic recording mode allows user selection of the network data points to be recorded. The user may select up to a total of eight data points for recording. A list of the data points available for recording follows. Changingthe configuration to generic and selecting which data points to record may be doneusing the Carrier Transicold Data Retrieval Program.
1. Control mode
2. Control temperature
3. Frequency
4. Humidity
5. Phase A current
6. Phase B current
7. Phase C current
8. Main voltage
9. Evaporator expansion valve percentage
10. Discrete outputs (Bit mapped -- require special handling if used)
1 1. Discrete inputs (Bit mapped -- require special
handling if used)
12. Ambient sensor
13. Evaporator temperature sensor
14. Compressor discharge sensor
15. Return temperature sensor (RTS)
16. Supply temperature sensor (STS)
17. Defrost temperature sensor
18. Discharge pressure transducer
19. Suction pressure transducer
20. Condenser pressure transducer
21. Vent position sensor (VPS)
3.7.4 Logging Interval (dCF03)
The user may select four different time intervals be­tween data recordings. Data is logged at exact intervals in accordance with the real time clock. The clock is fac­tory set at Greenwich Mean Time (GMT).
3.7.5 Thermistor Format (dCF04)
The user may configure the format in which the thermis­tor readings are recorded. The short resolution is a 1 byte format and the long resolution is a 2 byte format. The short requires less memory and records tempera­ture with variable resolutions depending on temperature range. The long records temperature in 0.01C (0.02F) steps for the entire range.
CONFIGURATION NO.
dCF01 (Future Use) -- -- -- -­dCF02 Sensor Configuration 2 2,5,6,9,54,64,94 dCF03 Logging Interval (Minutes) 60 15,30,60,120 dCF04 Thermistor Format Short Long dCF05 Thermistor Sampling Type A A,b,C dCF06 Controlled Atmosphere/Humidity Sampling Type A A,b dCF07 Alarm Configuration USDA Sensor 1 A Auto, On, Off dCF08 Alarm Configuration USDA Sensor 2 A Auto, On, Off dCF09 Alarm Configuration USDA Sensor 3 A Auto, On, Off dCF10 Alarm Configuration Cargo Sensor A Auto, On, Off
Table 3--2 DataCORDER Configuration Variables
TITLE DEFAULT OPTION
3--12T-340
Page 39
Raw Data Report for ABC1234567
May 31, 2007 to Jun 04, 2007
System Configuration at the Time of Interrogation:
Interrogated On May 05, 2007 Extracted by DataLINE Rev 1.0.0
Controller Software: 5327 Controller Serial #: 04163552
Bill of Lading #: 1 Origin: Origin Date: Destination: Discharge Date: Comment: DataLINE Tool
Probe Calibration Readings: USDA1: 0.0 USDA2: 0.0 USDA3: 0.0 Cargo: 0.0 Temperature Units: Centigrade ________________________________________________________________________________________
May 31, 2007
Setpoint: 1.66, Container : Serial : 04189552
9 Sensors Logged at 15 Minute Interval
Sensor Format Resolution
Figure 3--11 Standard Configuration Download Report
3--13
T-340
Page 40
Table 3--3 DataCORDER Standard Configurations
Standard
Config.
2 sensors
(dCF02=2)
5 sensors
(dCF02=5)
6 sensors
(dCF02=6)
9 sensors
(dCF02=9)
6 sensors
(dCF02=54)
7 sensors
(dCF02=64)
10 sensors
(dCF02=94)
3.7.6 Sampling Type (dCF05 & dCF06)
Three types of data sampling are available: average snap­shot and USDA. When configured to average, the aver­age of readings taken every minute over the recording pe­riod is recorded. When configured to snapshot, the sensor reading at the log interval time is recorded. When USDA is configured, the supply and return temperature readings are averaged and the three USDA probe readings are snapshot.
3.7.7 Alarm Configuration (dCF07 -- dCF10)
The USDA and cargo probe alarms may be configured to OFF, ON or AUTO.
If a probe alarm is configured to OFF, the alarm for this probe is always disabled.
If a probe alarm is configured to ON, the associated alarm is always enabled.
If the probes are configured to AUTO, they act as a group. This function is designed to assist users who keep their DataCORDER configured for USDA record­ing, but do not install the probes for every trip. If all the probes are disconnected, no alarms are activated. As soon as one of the probes is installed, all of the alarms are enabled and the remaining probes that are not installed will give active alarm indications.
2 thermistor inputs (supply & return)
2 thermistor inputs (supply & return) 3 USDA thermistor inputs
2 thermistor inputs (supply & return) 3 USDA thermistor inputs 1 humidity input
Not Applicable
2 thermistor inputs (supply & return) 3 USDA thermistor inputs 1 cargo probe (thermistor input)
2 thermistor inputs (supply & return) 3 USDA thermistor inputs 1 humidity input 1 cargo probe (thermistor input)
2 thermistor inputs (supply & return) 3 USDA thermistor inputs 1 humidity input 1 cargo probe (thermistor input) 3 C.A. inputs (NOT APPLICABLE)
Description
nication when an interrogation cable is plugged into an interrogation receptacle.
3. External DC battery pack power: A 12 volt battery pack may also be plugged into the back of the interroga­tion cable, which is then plugged into an interrogation port. No controller battery pack is required with this method.
4. Real Time Clock demand: If the DataCORDER is equipped with a charged battery pack and AC power is not present, the DataCORDER will power up when the real time clock indicates that a data recording should take place. When the DataCORDER is finished record­ing, it will power down.
During DataCORDER power--up, while using battery-­pack power, the controller will perform a hardware volt­age check on the battery. If the hardware check passes, the controller will energize and perform a software bat­tery voltage check before DataCORDER logging. If ei­ther test fails, the real time clock battery power--up will be disabled until the next AC power cycle. Further Data­CORDER temperature logging will be prohibited until that time.
An alarm will be generated when the battery voltage transitions from good to bad indicating that the battery pack needs recharging. If the alarm condition persists for more than 24 hours on continuous AC power, the battery pack needs replacement.
3.7.9 Pre--trip Data Recording
The DataCORDER will record the initiation of a pre--trip test (refer to paragraph 3.6) and the results of each of the tests included in pre--trip. The data is time--stamped and may be extracted via the Data Retrieval program. Refer to Table 3--9 for a description of the data stored in the DataCORDER for each corresponding Pre--trip test.
3.7.10 DataCORDER Communications
Data retrieval from the DataCORDER can be accom­plished by using one of the following: DataReader, DataLINE or a communications interface module.
NOTE
A DataReader, DataLINE or a communications interface module display of Communication Failed is caused by faulty data transfer between the DataCORDER and the data retrieval de­vice. Common causes include:
1. Bad cable or connection between DataCORDER and data retrieval device.
2. PC communication port(s) unavailable or misassigned.
3. Chart Recorder Fuse (FCR) blown.
Configuration identification for the models covered herein may be obtained on the Container Products Group Information Center by authorized Carrier Trans­icold Service Centers.
3.7.8 DataCORDER Power Up
The DataCORDER may be powered up in any one of four ways:
1. Normal AC power: The DataCORDER is powered up when the unit is turned on via the stop--start switch.
2. Controller DC battery pack power: If a battery pack is installed, the DataCORDER will power up for commu-
a. DataReader
The Carrier Transicold Data Reader (see Figure 3--12) is a simple to operate handheld device designed to ex­tract data from the DataCORDER and upload it to a PC. The Data Reader has the ability to store multiple data files. Refer to Data Retrieval manual 62--02575 for a more detailed explanation of the DataReader.
3--14T-340
Page 41
DataReader
1
8
7
6
1. OFF
2. ON
3. UP Arrow
4. RIGHT Arrow
2
3
4
5
5. ENTER
6. Escape
7. DOWN Arrow
8. LEFT Arrow
Figure 3--12 Data Reader
b. DataBANKCard
The DataBANKcard is a PCMCIA card that interfaces with the controller through the programming slot and can download the data at a much faster rate, when compared to the PC or DataReader. Files downloaded to DataBANK card files are accessible through an Omni PC Card Drive. The files can then be viewed using the DataLINE software.
c. DataLINE
The DataLINE software for a personal computer is sup­plied on both floppy disks and CD. This software allows interrogation, configuration variable assignment, screen view of the data, hard copy report generation, cold treatment probe calibration and file management. Refer to Data Retrieval manual 62--10629 for a more detailed explanation of the DataLINE interrogation soft­ware. The DataLINE manual may be found on the inter­net at www.container.carrier.com.
d. Communications Interface Module
The communications interface module is a slave mod­ule, which allows communication with a master central monitoring station. The module will respond to commu­nication and return information over the main power line.
With a communications interface module installed, all functions and selectable features that are accessible at the unit may be performed at the master station. Re­trieval of all DataCORDER reports may also be per­formed. Refer to the master system technical manual for further information.
3.7.11 USDA Cold Treatment
Sustained cold temperature has been employed as an effective postharvest method for the control of Mediter­ranean and certain other tropical fruit flies. Exposing in­fested fruit to temperatures of 2.2C (36F) or below for specific periods results in the mortality of the various stages of this group of insects.
In response to the demand to replace fumigation with this environmentally sound process, Carrier has inte­grated Cold Treatment capability into its microprocessor system. These units have the ability to maintain supply air temperature within onePre--tripquarter degree Cel­sius of set point and record minute changes in product temperature within the DataCORDER memory, thus meeting USDA criteria. Information on USDA is pro­vided in the following subparagraphs
a. USDA Recording
A special type of recording is used for USDA cold treat­ment purposes. Cold treatment recording requires three remote temperature probes be placed at prescribed locations in the cargo. Provision is made to connect these probes to the DataCORDER via receptacles lo­cated at the rear left--hand side of the unit. Four or five receptacles are provided. The four 3--pin receptacles are for the probes. The 5--pin receptacle is the rear con­nection for the Interrogator. The probe receptacles are sized to accept plugs with tricam coupling locking de­vices. A label on the back panel of the unit shows which receptacle is used for each probe.
The standard DataCORDER report displays the supply and return air temperatures. The cold treatment report displays USDA #1, #2, #3 and the supply and return air temperatures. Cold treatment recording is backed up by a battery so recording can continue if AC power is lost.
b. USDA/ Message Trip Comment
A special feature in DataLINE allows the user to enter a USDA (or other) message in the header of a data report. The maximum message length is 78 characters. Only one message will be recorded per day.
3.7.12 USDA Cold Treatment Procedure
The following is a summary of the steps required to initi­ate a USDA Cold T reatment:
a. Calibrate the three USDA probes by ice bathing the
probes and performing the calibration function with the DataReader or DataLINE. This calibration proce­dure determines the probe offsets and stores them in the controller for use in generating the cold treatment report. Refer to the Data Retrieval manual 62--02575 for more details.
b. Pre--cool the container to the treatment temperature
or below.
c. Install the DataCORDER module battery pack (if not
already installed).
d. Place the three probes. The probes are placed into
the pulp of the product (at the locations defined in the following table) as the product is loaded.
3--15
T-340
Page 42
Sensor 1
Place in pulp of the product located next to the return air intake.
Place in pulp of the product five feet from the end of the load for 40 foot con-
Sensor 2
tainers, or three feet from the end of the load for 20 foot containers. This probe should be placed in a center carton at one--half the height of the load.
Place in pulp of product five feet from the end of the load for 40 foot containers
Sensor 3
or three feet from the end of the load for 20 foot containers. This probe should be placed in a carton at a side wall at one-­half the height of the load.
e. To initiate USDA recording, connect the personal
computer and perform the configuration as follows, using the DataLINE software:
1. Enter ISO header information.
2. Enter a trip comment if desired.
3. Configure the DataCORDER for five probes (s, r, P1, P2, P3) (dcf02=5).
4. Configure the logging interval for one hour.
5. Set the sensor configuration to “USDA.”
6. Configure for two byte memory storage format (dcf04=LONG).
7. Perform a “trip start.”
3.7.13 DataCORDER Alarms
The alarm display is an independent DataCORDER function. If an operating parameter is outside of the ex­pected range or a component does not return the cor­rect values to the DataCORDER, an alarm is generated. The DataCORDER contains a buffer of up to eight alarms. A listing of the DataCORDER alarms is pro­vided in Table 3--10, page 3--33. Refer to paragraph
3.7.7 for configuration information.
To display alarm codes:
a. While in the Default Display mode, press the ALT.
MODE & ALARM LIST keys. This accesses the Data­CORDER Alarm List Display Mode, which displays any alarms stored in the alarm queue.
b. To scroll to the end of the alarm list, press the UP AR-
ROW. Depressing the DOWN ARROW key will scroll the list backward.
c. The left display will show “AL#” where # is the alarms
number in the queue. The right display will show “AA##,” if the alarm is active, where ## is the alarm number. “IA##,” will show if the alarm is inactive
d. “END” is displayed to indicate the end of the alarm list
if any alarms are active. “CLEAr” is displayed if all the alarms in the list are inactive.
e. If no alarms are active, the alarm queue may be
cleared. The exception to this rule is the DataCORD­ER alarm queue Full alarm (AL91), which does not have to be inactive in order to clear the alarm list. To clear the alarm list:
1. Press the ALT. MODE & ALARM LIST keys.
2. Press the UP/DOWN ARROW key until “CLEAr” is displayed.
3. Press the ENTER key. The alarm list will clear and “-- -- -- -- -- ” will be displayed.
4. Press the ALARM LIST key. “AL” will show on the left display and “ -- -- -- -- --” on the right display when there are no alarms in the list.
5. Upon clearing of the alarm queue, the alarm light will be turned off.
3.7.14 ISO Trip Header
DataLINE provides the user with an interface to view/ modify current settings of the ISO trip header through the ISO Trip Header screen.
The ISO Trip Header screen is displayed when the user clicks on the “ISO Trip Header” button in the “Trip Func­tions” Group Box on the System T ools screen.
F9 function -- Provides the user with ashortcut for manu­ally triggering the refresh operation. Before sending modified parameter values, the user must ensure that a successful connection is established with the controller.
If the connection is established with the DataCORDER, the current contents of the ISO Trip Header from the Da­taCORDER will be displayed in each field. If the connec­tion is not established with the DataCORDER, all fields on the screen will be displayed as “Xs.” If at any time dur­ing the display of the ISO Trip Header screen the con­nection is not established or is lost, the user is alerted to the status of the connection.
After modifying the values and ensuring a successful connection has been made with the DataCORDER, click on the “Send” button to send the modified parame­ter values.
The maximum allowed length of the ISO Trip Header is 128 characters. If the user tries to refresh the screen or close the utility without sending the changes made on the screen to the DataCORDER, the user is alerted with a message.
3--16T-340
Page 43
Table 3--4 Controller Configuration Variables
CONFIGURATION
NUMBER
TITLE DEFAULT OPTION
CnF02 Evaporator Fan Speed dS (Dual) SS (Single)
CnF03 Control Sensors FOUr duAL
CnF04 Dehumidification Mode On OFF
CnF08 Single Phase/3--Phase Evaporator Fan Motor 1Ph 3Ph
CnF09 Refrigerant Selection r134a r744
CnF11 Defrost “Off” Selection noOFF OFF
CnF15 Discharge Temperature Sensor Out In
CnF16 DataCORDER Present On (Yes) (Not Allowed)
CnF17 Discharge Pressure Sensor Out (No) In (Yes)
CnF18 Heater Old (Low Watt) nEW (High Watt)
CnF20 Suction Pressure Sensor Out (No) In (Yes)
CnF22 Economy Mode Option OFF Std, Full
CnF23 Defrost Interval Timer Save Option noSAv SAv
CnF24 Advanced Pre--trip Enhanced T est Series Option Auto Auto2, Auto 3
CnF25 Pre--trip Test Points/Results Recording Option rSLtS dAtA
CnF26 Heat Lockout Change Option Set to --10C Set to --5C
CnF27 Suction Temperature Display Option Out In
CnF28 Bulb Mode Option NOr bULb
CnF31 Probe Check Option SPEC Std
CnF32 Single Evaporator Fan Option 2EF0 (Not Allowed)
CnF33 Snap Freeze Option OFF SnAP
CnF34 Degree Celsius Lockout Option bOth F
CnF37 Electronic T emperature Recorder rEtUR SUPPL, bOth
CnF41 Lower DTT Setting Out In
CnF44 eAutoFresh Enabled Out LO, UP
CnF45 Low Humidity Enabled Out In
CnF47 Fresh Air Vent Position Sensor OFF UP, LOW, CUStOM
CnF49 DataCORDER Configuration Restore OFF On
CnF50 Enhanced Bulb Mode Selection OFF Bulb, dEHUM
CnF51 Timed Defrost Disable 0 0--out, 1--in
CnF52 Oil Return Algorithm 1 0--out, 1--in
CnF53 Water Cool Oil Return Logic 0 0--out, 1--in
CnF55 TXV Boost Relay 0 0--out, 1--in
CnF56 TXV Boost Circuit 0 0--out, 1--in
CnF59 Electronic Expansion Valve 0 0--none, 1--EC,
2--KE, 3-- NA
CnF60 Compressor--Cycle Perishable Cooling 0 0--out, 1--in
CnF61 ACT ASC Control Enable 0 0--out, 1--in
CnF62 Extended Temperature Control Enable 0 0-- on, 1--in
CnF63 CCPC Pre--trip/Tripstart Default State 0 0--on, 1-- off
Note: Configuration numbers not listed are not used in this application. These items may appear when loading configura­tion software to the controller but changes will not be recognized by the controller programming.
3--17
T-340
Page 44
Table 3--5 Controller Function Codes
(Sheet 1 of 4)
Code
No.
TITLE DESCRIPTION
Note: If the function is not applicable, the display will read “ -- -- -- -- -- ”
Display Only Functions
Cd01
Cd03
Cd04
Cd05
Cd06
Cd07 Main Power Voltage The main supply voltage is displayed.
Cd08
Cd09
Cd10
Cd1 1
Cd12
Cd14
Cd15
Cd16
Cd18 Software Revision # The software revision number is displayed.
Cd19 Battery Check
Cd20 Config/Model #
Cd21 Capacity Mode The mode of operation is displayed (Unloaded -- Standard -- Economized). Cd22 Compressor State The status of the compressor is displayed (Off, On).
Digital Unloader Valve Closed (%)
Compressor Motor Current
Line Current, Phase A
Line Current, Phase B
Line Current, Phase C
Main Power Frequency
Ambient Temperature
Evaporator T emper­ature Sensor
Compressor Dis­charge Temperature
Compressor Suction Pressure
Compressor Dis­charge Pressure
Digital Unloader Val v e
Compressor Motor Hour Meter/Unit Run Time Hour Meter
Displays the DUV percent closed. The right display reads 100% when the valve is fully closed. The valve will usually be at 10% on start up of the unit except in very high ambient temperatures.
The current sensor measures current draw in lines L1 & L2 by all of the high volt­age components. It also measures current draw in compressor motor leg T3. The compressor leg T3 current is displayed.
The current sensor measures current on two legs. The third unmeasured leg is calculated based on a current algorithm. The current measured is used for control and diagnostic purposes. For control processing, the highest of the Phase A and B current values is used for current limiting purposes. For diagnostic processing, the current draws are used to monitor component energization. Whenever a heat­er or a motor is turned ON or OFF, the current draw increase/reduction for that activity is measured. The current draw is then tested to determine if it falls within the expected range of values for the component. Failure of this test will result in a pre--trip failure or a control alarm indication.
The value of the main power frequency is displayed in Hertz. The frequency dis­played will be halved if either fuse F1 or F2 is bad (alarm code AL21).
The ambient sensor reading is displayed.
Evaporator temperature sensor reading is shown on the right display.
Compressor discharge temperature sensor reading, using compressor dome tem­perature, is displayed.
Reading for evaporator pressure transducer (EPT) is shown on the left display; Press ENTER at Cd12 to show reading for compressor suction port pressure on right display.
Compressor discharges pressure transducer reading is displayed.
The status of the valve is displayed (Open -- Closed).
This code displays the compressor motor hours. User can view unit run time by pressing the ENTER key while in Cd16. Total hours are recorded in increments of 10 hours (i.e., 3000 hours is displayed as 300).
The Compressor Motor Hour Meter display can be reset to 0 by pressing and holding the ENTER key for 5 seconds. The Unit Run Time Hour Meter cannot be reset.
This code checks the Controller/DataCORDER battery pack. While the test is run­ning, “btest” will flash on the right display, followed by the result. “PASS” will be displayed for battery voltages greater than 7.0 volts. “FAIL” will be displayed for battery voltages between 4.5 and 7.0 volts, and “ -- -- -- -- -- ” will be displayed for battery voltages less than 4.5 volts. After the result is displayed for four seconds, “btest” will again be displayed, and the user may continue to scroll through the various codes.
This code indicates the dash number of the model for which the Controller is con­figured (i.e., if the unit is a 69NT40--551--100, the display will show “51100”). To display controller configuration database information, press ENTER. Values in “CFYYMMDD” format are displayed if the controller was configured with a config­uration card or with a valid OEM serial port configuration update; YYMMDD rep­resents the publication date of the model configuration database.
3--18T-340
Page 45
Table 3--5 Controller Function Codes (Sheet 2 of 4)
Cd23
Cd25
Cd26
Evaporator Fan Displays the current evaporator fan state (high, low or off).
Compressor Run Time Remaining Until Defrost
Defrost T emperature Sensor Reading
This code displays the time remaining until the unit goes into defrost (in tenths of an hour). This value is based on the actual accumulated compressor running time.
Defrost temperature sensor reading is displayed.
Configurable Functions
NOTE
Function codes Cd27 through Cd37 are user--selectable functions. The operator can change the value of these functions to meet the operational needs of the container.
There are two modes for defrost initiation: user--selected timed intervals or auto­matic control. The user--selected values are (OFF), 3, 6, 9, 12, 24 hours or AUTO. The factory default is AUTO. Automatic defrost starts with an initial defrost at three hours, then the interval to the next defrost is adjusted based on the accu­mulation of ice on the evaporator coil. Following a start--up or after termination of a defrost, the time will not begin counting down until the defrost temperature sen­sor (DTS) reading falls below set point. If the reading of DTS rises above set point any time during the timer count down, the interval is reset and the count­down begins over. If DTS fails, alarm code AL60 is activated and control switches over to the the return temperature sensor. The controller will act in the same man­ner as with the DTS except the return temperature sensor reading will be used. Defrost Interval Timer Value (Configuration variable CnF23): If the software is configured to “SAv” (save) for this option, the value of the defrost interval timer will be saved at power down and restored at power up. This option prevents short power interruptions from resetting an almost expired defrost interval, and possibly delaying a needed defrost cycle.
Cd27
Defrost Interval (Hours or Automatic)
Cd28
Cd29
Cd30 In--Range Tolerance
Cd31
Cd32
Temperature Units (C or F)
Failure Action (Mode)
Stagger Start Offset Time (Seconds)
Current Limit (Amperes)
NOTE
The defrost interval timer counts only during compressor run time.
This code determines the temperature units (C or F) that will be used for all tem­perature displays. The user selects C or F by selecting function code Cd28 and pushing the ENTER key. The factory default value is Celsius units.
NOTE
This function code will display “--- --- --- --- --- “ i f Configuration Variable CnF34 is set to F.
If all of the control sensors are out of range (alarm code AL26) or there is a probe circuit calibration failure (alarm code AL27), the unit will enter the shutdown state defined by this setting. The user selects one of four possible actions as follows:
A -- Full Cooling (Compressor is on, economized operation.) B -- Partial Cooling (Compressor is on, standard operation.) C -- Evaporator Fan Only (Evaporator fans on high speed, not applicable with frozen
set points.)
D -- Full System Shutdown -- Factory Default (Shut down every component in the
unit.)
The in--range tolerance will determine the band of temperatures around the set point which will be designated as in--range. If the control temperature is in--range, the in--range light will be illuminated. There are four possible values: 1 = +/-- 0.5C (+/-- 0.9F) 2 = +/-- 1.0C (+/-- 1.8F) 3 = +/-- 1.5C (+/-- 2.7F) 4 = +/-- 2.0C (+/-- 3.6F) -- Factory Default
The stagger start offset time is the amount of time that the unit will delay at start-­up, thus allowing multiple units to stagger their control initiation when all units are powered up together. The eight possible offset values are: 0 (Factory Default), 3, 6, 9, 12, 15, 18 or 21 seconds
The current limit is the maximum current draw allowed on any phase at any time. Limiting the unit’s current reduces the load on the main power supply. When de­sirable, the limit can be lowered. Note, however, that capacity is also reduced. The five values for 460 VAC operation are: 15, 17, 19, 21, or 23 amperes. The factory default setting is 21 amperes.
3--19
T-340
Page 46
Perishable Mode
Cd33
Dehumidification Control (% RH)
Cd34
Economy Mode (On--Off)
Cd35 Bulb Mode
Cd36
Evaporator Speed Select
Defrost T ermination
Cd37
Temperature Setting (Bulb Mode)
Cd38
Cd39
Cd40
Secondary Supply Temperature Sensor
Secondary Return Temperature Sensor
Container Identifica­tion Number
Cd41 Valve Override
Cd43 eAutoFresh Mode
Cd44 eAutoFresh Values
Cd45
Fresh Air Vent Position Sensor
Table 3--5 Controller Function Codes (Sheet 3 of 4)
Relative humidity set point is available only on units configured for dehumidifica­tion. When the mode is activated, the control probe LED flashes on and off every second to alert the user. If not configured, the mode is permanently deactivated and “-- -- -- -- -- ” will display. The value can be set to “OFF,” “TEST,” or a range of 65 to 95% relative humidity in increments of 1%. [If bulb mode is active (code Cd35) and “Lo” speed evaporator motors are selected (code Cd36), then set point ranges from 60 to 95%.] When “TEST” is selected or test set point is entered, the heat LED should illuminate, indicating that dehumidification mode is activated. After a period of five minutes in the “TEST” mode has elapsed, the previously selected mode is reinstated.
Economy mode is a user selectable mode of operation provided for power saving purposes.
Bulb mode is a user selectable mode of operation that is an extension of dehu­midification control (Cd33). If dehumidification is set to “Off,” code Cd35 will dis­play “Nor” and the user will be unable to change it. After a dehumidification set point has been selected and entered for code Cd33, the user may change code Cd35 to “bulb.” After bulb has been selected and entered, the user may utilize function codes Cd36 and Cd37 to make the desired changes.
This code is enabled only if in the dehumidification mode (code Cd33) and bulb mode (Cd35) has been set to “bulb.” If these conditions are not met, “alt” will be displayed (indicating that the evaporator fans will alternate their speed) and the display cannot be changed. If a dehumidification set point has been selected along with bulb mode, “alt” may be selected for alternating speed, “Lo” for low speed evaporator fan only, or “Hi” for high speed evaporator fan only. If a setting other than “alt” has been selected and bulb mode is deactivated in any manner, the selection reverts back to “alt.”
This code, as with function code Cd36, is used in conjunction with bulb mode and dehumidification. If bulb mode is active, this code allows the user to change the temperature above which defrost will terminate. It allows the user to change the setting within a range of 4C to 25.6C in 0.1C (0.2F) increments. This value is changed using the UP/DOWN ARROW keys, followed by the ENTER key when the desired value is displayed. If bulb mode is deactivated, the DTS setting re­turns to the default.
Display Only Functions -- Continued
Code Cd38 will display the current supply recorder sensor (SRS) reading for units configured for four probes. If the unit is configured with a DataCORDER, Cd38 will display “-- -- -- -- -- .” If the DataCORDER suffers a failure, (AL55) Cd38 will display the supply recorder sensor reading.
Code Cd39 will display the current return recorder sensor (RRS) reading for units configured for four probes. If the unit is configured with a DataCORDER, Cd39 will display “-- -- -- -- -- .” If the DataCORDER suffers a failure, (AL55) Cd39 will display the return recorder sensor reading.
Code Cd40 is configured at commissioning to read a valid container identification number. The reading will not display alpha characters; only the numeric portion of the number will display.
SERVICE FUNCTION: This code is used for troubleshooting, and allows manual positioning of the economizer solenoid valve, electronic expansion valve, and di­gital unloader valve. Provides readings such as: Percent Capacity, EEV, Capacity
Mode, LIV and DUV. Refer to paragraph 6.17 for operating instructions. Code Cd43 is used to select the mode of operation for the eAutoFresh slides. As-
sociated parameters can also be selected from submenus: OFF, USER, DELAY, TEST and gASLM (refer to section 4.4.4 for description of operational paramet­ers). If the unit is not configured for eAutoFresh, Cd43 will display “-- -- -- -- -- .”
Code Cd44 displays the eAutoFresh CO2and O2values (CO2 and O2) and CO and O2limits (CO2LIM and O2LIM), respectively. If the unit is not configured for eAutoFresh, Cd44 will display “-- -- -- -- -- .”
Unless AL50 is active or CnF47 is OFF, the fresh air flow (CMH/CFM) is displayed. This function code will automatically activate for 30 seconds and displayed when a vent position change occurs.
2
3--20T-340
Change 8/10
Page 47
Table 3--5 Controller Function Codes (Sheet 4 of 4)
Cd46
Cd47
Cd48
Cd49
Airflow Display Units
Variable Economy Temperature Setting
Dehumidification Pa­rameter Selection
Days Since Last Successful Pre--trip
Cd50 CCPC Disabled
Automatic Cold
Cd51
Treatment Parameter Selection
This code displays the airflow units to be displayed for Cd 45. Options are CF, CM or bOth (dependent on the setting of Cd28 or pressing of the C/F key).
Code Cd47 is used with optional economy mode. The values are 0.5C--4.0C. The default is 3.0C. If the unit is not configured for economy mode, “-- ------” will be dis­played.
Code Cd48 is used both when dehumidification set point is set above 65% RH and below 64% RH. When dehumidification set point is set above 65% RH, select goes to LO if it had been set to hi. When dehumidification set point is set below 64% RH, select goes to Alt if it had been set to LO.
Code Cd49 will display the time period (days) since the last successful pre--trip completion. Press ENTER repeatedly to display last pre--trip completion in Auto, Auto 1 and Auto 2 modes.
Code 50 allows selection of CCPC mode. The user can press ENTER, then arrow keys, then ENTER again to enable (On) or suspend (OFF) CCPC mode. If CCPC operation is On, it may be suspended due to one of the following conditions:
“SEtPt” =Set point is too low. “CAHUM”= CA or humidity control is active “ACT”=ACT is active. “FAIL”=Return temperature probe has failed. “PrtrP”=Pre--trip is active. “C LIM”= Cool limit logic is active. “PULL”=Unit is in pulldown mode.
Code Cd51 initially displays countdown timer increments of 1 day, 1 hour with the temperature default. Pressing ENTER allows selection of within the current menu and proceeds to the next menu. After five seconds of no activity, the display re­verts to normal system display, but retains the parameters previously selected.
“ACt” = “On,” “Off” or “---- ----”. The default is Off. “trEAt”=C /F in 0.1 degree increments. The default is 0.0C. “DAyS”= “0--99” increments of 1. The default is 0. “ProbE”=probe positions (example 12_4) . The default is -- ------. “SPnEW”= C /F in 0.1 degree increments. The default is 10.0C.
Automatic Set point
Cd53
Change Mode Parameter Selection
Cd54
Cd55
Electronic Expan­sion Valve Status
Discharge Super­heat
Water Pressure
Cd58
Switch/Condenser FanSwitchStateor Override Logic State
Cd59 Pump Down Logic
Code Cd53 initially displays countdown timer increments of 1 day, 1 hour with the temperature default. Pressing ENTER allows selection of within the current menu and proceeds to the next menu. After five seconds of no activity, the display re­verts to normal system display, but retains the parameters previously selected.
“ASC”=“On” or “Off” The default is Off. “NSC”=“1--2” “SP 0”=C /F in 0.1 degree increments. The default is 10.0C. “DAY 0”= “0--99” increments of 1. The default is 1. “SP 1”=C /F in 0.1 degree increments. The default is 10.0C. “DAY 1”= “0--99” increments of 1. The default is 1. “SP 2”=C /F in 0.1 degree increments. The default is 10.0C.
Reading for evaporator superheat is shown on the right display . Press ENTER at Cd54 to show reading for EEV position (in %) on left display.
Code Cd55 will display the discharge superheat values in C /F as calculated by the discharge temperature minus the discharge saturation temperature as calcu­lated from discharge pressure. “-- ------ --” will be displayed if the selection is not val­id.
Code Cd58 will display “CLOSE” if the WPS or CFS switch contacts are closed or that these options are not installed. “OPEn” is displayed when the WPS or CFS switch contacts are open. When the WPS/CFS Override Logic is “TRUE”, the right display will flash on all units.
Code Cd59 allows operation of the pump down logic control. The display will flash between “STArT PdN” and “PrESS EnTEr”. Once the operator confirms continu­ation of the sequence, pump down logic begins. If the pump down logic is com­pleted within 20 minutes, the unit will turn off and the display will flash “P dN DOnE” and “SHUT OFF”. The operator must shut off the unit. If the pump down logic is not completed within 20 minutes, the unit will return to its previous control condition.
3--21
T-340
Page 48
Code
No.
AL03
AL05
AL06
Loss of Superheat Control
Manual Defrost Switch Failure
Keypad or Harness Failure
TITLE DESCRIPTION
Fresh Air Vent Open
AL07
withFrozenSet Point
AL08
High Compressor Pressure Ratio
AL10 CO2Sensor Failure
AL14
AL16
AL17
AL18
AL19
AL20
Phase Sequence Failure -- Electronic
Compressor Current High
Phase Sequence Failure -- Pressure
Discharge Pressure High
Discharge Tempera­ture High
Control Circuit Fuse Open (24 VAC)
Table 3--6 Controller Alarm Indications (Sheet 1 of 5)
Alarm 03 is triggered if superheat operates below 1.66C (3F) for five minutes continuously while the compressor is running and the EEV is at 0% open. The alarm will trigger off when superheat has remained above 1.66C (3F) for five minutes continuously while the compressor is running.
Alarm 05 is triggered if the controller detects continuous Manual Defrost Switch action for five minutes or more. The alarm will only trigger off when the unit is power cycled.
Alarm 06 is triggered if the controller detects continuous keypad button activity for five minutes or more. The alarm will only trigger off when the unit is power cycled.
Alarm 07 is triggered if the VPS is reading greater than 0 CMH based on the function code display value and a frozen set point is active. If AL 50 is active, AL 07 will not be generated. The alarm will go inactive if the VPS reading transitions to 0 CMH, the set point transitions to the perishable range, or an AL50 is active.
Alarm 08 is triggered when the controller detects that the discharge pressure to suction pressure ratio is too high. The alarm triggers shut down of the com­pressor, which will restart in normal staging logic, after three minutes.
Alarm 10 is triggered when the CO2sensor voltage is operating outside of the 0.9 v to 4.7 v range, or if the sensor is out of range. This is a display alarm and has no associated failure action.
Alarm 14 is triggered if the electronic phase detection system is unable to deter­mine the correct phase relationship. AL 14 is also triggered if electronic phase sequence detection was successful and conclusive, but unit is miswired. The miswiring causes increased suction pressure and decreased discharge pressure when the compressor is running; these conditions are present only when the compressor is energized in the direction opposite of that indicated by electronic phase sequence detection. If the system is unable to determine the proper rela­tionship, alarm 14 will remain active. Additional information on phase detection may be displayed at Function Code Cd41. If the right most digit of Code Cd41 is 3 or 4, this indicates incorrect motor or sensor wiring. If the right most digit is 5, this indicates a failed current sensor assembly.
Alarm 16 is triggered if compressor current draw is 15% over calculated maxi­mum for 10 minutes out of the last hour. The alarm is display only and will trigger off when the compressor operates for one hour without over current.
Alarm 17 is triggered if a compressor start in both directions fails to generate suf­ficient pressure differential. The controller will attempt restart every 20 minutes and deactivate the alarm if successful. This alarm triggers failure action C (evap­orator fan only) or D (all machinery off) of Function Code Cd29 if the unit has a perishable set point. Failure action D (all machinery off) is triggered if the unit has a frozen set point.
Alarm 18 is triggered if discharge pressure is 10% over calculated maximum for 10 minutes within the last hour. The alarm is display only and will trigger off when the compressor operates for one hour without overpressure.
Alarm 19 is triggered if discharge temperature exceeds 135C (275F) for 10 minutes within the last hour. The alarm is display only and will trigger off when the compressor operates for one hour without over temperature.
Alarm 20 is triggered by control power fuse (F3A, F3B) opening and will cause the software shutdown of all control units. This alarm will remain active until the fuse is replaced.
3--22T-340
Page 49
Table 3--6 Controller Alarm Indications (Sheet 2 of 5)
AL21
AL22
Micro Circuit Fuse Open (18 VAC)
Evaporator Fan Motor Safety
AL23 Loss of Phase B
AL24
AL25
Compressor Motor Safety
Condenser Fan Mo­tor Safety
All Supply and Re-
AL26
turn temperature Control Sensors Failure
AL27
AL28
A/D Accuracy Fail­ure
Low Suction Pres­sure
AL29 AutoFresh Failure
Alarm 21 is triggered by one of the fuses (F1/F2) being opened on 18 VAC power supply to the controller. Temperature control will be maintained by cycling the compressor.
Alarm 22 responds to the evaporator motor internal protectors. On units with Nor­mal Evaporator Fan Operation (CnF32 set to 2EFO), the alarm is triggered by opening of either internal protector. It will disable all control units until the motor protector resets. On units with Single Evaporator Fan Capability (CnF32 set to 1EFO), the alarm is triggered by opening of both internal protectors. It will disable all control units until a motor protector resets.
Alarm 23 is triggered if low current draw is detected on phase B and IPCP, HPS or IPEM is not tripped. If the compressor should be running, the controller will ini­tiate a start up every five minutes and trigger off if current reappears. If the evap­orator fan motors only should be running, the alarm will trigger off if current reap­pears. This alarm triggers failure action C (evaporator fan only) or D (all machin­ery off) of Function Code Cd29 if the unit has a perishable set point. Failure ac­tion D (all machinery off) is triggered if the unit has a frozen set point.
Alarm 24 is triggered when compressor is not drawing any current. It also triggers failure action “C” or “D” set by function Code 29 for perishable set point, or “D” for frozen set point. If the compressor should be running, the controller will initiate a start up every five minutes and trigger off, if current reappears. This alarm will re­main active until compressor draws current.
Alarm 25 is triggered by the opening of the condenser motor internal protector and will disable all control units except for the evaporator fans. This alarm will re­main active until the motor protector resets. This alarm triggers failure action C (evaporator fan only) or D (all machinery off) of Function Code Cd29 if the unit has a perishable set point. Failure action D (all machinery off) is triggered if the unit has a frozen set point.
Alarm 26 is triggered if the controller determines that all of the control sensors are out--of--range. This can occur for box temperatures outside the range of --50C to +70C (--58F to +158F). This alarm triggers the failure action code set by Func­tion Code Cd29.
The controller has a built--in Analog to Digital (A--D) converter, used to convert analog readings (i.e. temperature sensors, current sensors, etc.) to digital read­ings. The controller continuously performs calibration tests on the A--D converter. If the A--D converter fails to calibrate for 30 consecutive seconds, this alarm is activated.This alarm will be inactivated as soon as the A--D converter calibrates.
Alarm 28 is triggered if evaporator pressure is invalid. This alarm triggers shut down of the compressor off for three minutes. This alarm will be inactivated when suction pressure rises above 2 psia for three continuous minutes.
Alarm 29 is triggered if CO2 or O2 level is outside of the limit range and the vent position is at 100% for longer than 90 minutes. Alarm LED will be activated and user intervention is required. The alarm is triggered off when atmospheric condi­tions are within limit settings.
AL50
Fresh Air Position Sensor (VPS)
AL51 Alarm List Failure
AL52 Alarm List Full
Alarm 50 is activated whenever the sensor is outside the valid range. There is a four--minute adjustment period where the user can change the vent position with­out generating an alarm event. The sensor requires four minutes of no movement to confirm stability. If the vent position changes at any point beyond the four-­minute adjustment period, the sensor will generate an alarm event. The alarm is triggered off when the unit power cycles and the sensor is within valid range.
During start--up diagnostics, the EEPROM is examined to determine validity of its contents. This is done by testing the set point and the alarm list. If the contents are invalid, alarm 51 is activated. During control processing, any operation involv­ing alarm list activity that results in an error will cause alarm 51 to be activated. Alarm 51 is a “display only” alarm and is not written into the alarm list. Pressing the ENTER key when “CLEAr” is displayed will result in an attempt to clear the alarm list. If that action is successful (all alarms are inactive), alarm 51 will be re­set.
Alarm 52 is activated whenever the alarm list is determined to be full at start--up or after recording an alarm in the list. Alarm 52 is displayed, but is not recorded in the alarm list. This alarm can be reset by clearing the alarm list. This can be done only if all alarms written in the list are inactive.
3--23
T-340
Page 50
AL53
Battery Pack Failure
Supply Temperature
AL54
Sensor Failure (STS)
AL55 I/O Failure
Return Temperature
AL56
Sensor Failure (RTS)
Table 3--6 Controller Alarm Indications (Sheet 3 of 5)
Alarm 53 is caused by the battery pack charge being too low to provide sufficient power for battery--backed recording. If this alarm occurs on start up, allow a unit fitted with rechargeable batteries to operate for up to 24 hours to charge re­chargeable batteries sufficiently to deactivate the alarm.
Alarm 53 is also activated when there is no battery pack installed in the control­ler. To clear the alarm until another battery pack is installed, press ENTER and ALT simultaneously at the startup of Cd19.
Alarm 54 is activated by an invalid supply temperature sensor (STS) reading that is sensed outside the range of --50 to +70C (--58F to +158F) or if the probe check logic has determined there is a fault with this sensor. If alarm 54 is activated and the primary supply is the control sensor, the supply recorder sensor (SRS) will be used for control if the unit is so equipped. If the unit does not have a supply re­corder sensor, and AL54 is activated, the return temperature sensor (RTS) read­ing minus 2C will be used for control.
NOTE
The P5 Pre--trip test must be run to deactivate the alarm.
This alarm activates to indicate I/O functions have failed and require replace­ment.
Alarm 56 is activated by an invalid return temperature sensor (RTS) reading that is outside the range of --50 to +70C (--58F to +158F). If alarm 56 is activated and the primary return is the control sensor, the return recorder sensor (RRS) will be used for control if the unit is so equipped. If the unit is not equipped with a return recorder sensor or it fails, the supply temperature sensor (STS) will be used for control.
AL57
AL58
AL59
AL60
Ambient Tempera­ture Sensor Failure
Compressor High Pressure Safety
Heater Termination Thermostat (HTT)
Defrost T emperature Sensor Failure
AL61 Heaters Failure
AL63 Current Over Limit
AL64
Discharge Tempera­ture Over Limit
NOTE
The P5 Pre--trip test must be run to deactivate the alarm.
Alarm 57 is triggered by an ambient temperature reading outside the valid range from --50 to +70C (--58F to +158F).
Alarm 58 is triggered when the compressor high discharge pressure safety switch remains open for at least one minute. This alarm will remain active until the pres­sure switch resets, at which time the compressor will restart.
Alarm 59 is triggered when the heat termination thermostat switch is opened (ex­cept when defrost sensor alarm is active). This alarm will remain active until the heat termination thermostat closes.
Alarm 60 is an indication of a probable failure of the defrost temperature sensor (DTS). It is triggered by the opening of the heat termination thermostat (HTT) or the failure of the DTS to go above set point within two hours of defrost initiation. After one--half hour with a frozen range set point, or one--half hour of continuous compressor run time, if the return air falls below 7C (45F), the controller checks to ensure the DTS reading has dropped to 10C or below. If not, a DTS failure alarm is given and the defrost mode is operated using the return temperature sensor. The defrost mode will be terminated after one hour by the controller.
Alarm 61 is triggered by detection of improper amperage resulting from heater activation or deactivation. Each phase of the power source is checked for proper amperage. This alarm is a display alarm with no resulting failure action and will be reset by a proper amp draw of the heater.
Alarm 63 is triggered by the current limiting system. If the compressor is ON and current limiting procedures cannot maintain a current level below the user se­lected limit, the current limit alarm is activated. This alarm is a display alarm and is inactivated by power cycling the unit, changing the current limit via the code select Cd32, or if the current decreases below the activation level.
Alarm 64 is triggered if the discharge temperature sensed is outside the range of
--60C (--76F) to 175C (347F), or if the sensor is out of range. This is a display alarm and has no associated failure action.
3--24T-340
Page 51
AL65
AL66
AL67
AL68
AL69
Discharge Pressure Transducer Failure
Evaporator Pressure Transducer/Suction Pressure Transducer Out of Range
Humidity Sensor Failure
Condenser Pressure Sensor Fault
Primary Evaporator Temperature Sensor Out of Range
Table 3--6 Controller Alarm Indications (Sheet 4 of 5)
Alarm 65 is triggered if a compressor discharge transducer is out of range. This is a display alarm and has no associated failure action.
Alarm 66 is triggered if an evaporator pressure transducer (EPT) is less than 0.2 volts or greater than 4.95 volts.
Occasionally, readings for normally operating evaporator pressure transducers may drift. When this occurs, the SPT will be used to control both the EEV and DUV. If the unit operates “in range” within 30 minutes, the EEV and DUV will be controlled by the SPT. If not, the unit will return to normal operation and Alarm 66 will be activated. If the SPT assumes control of the EEV and DUV, Alarm 66 will be activated after the next Trip Start has begun. Pre--trip 5--9 is used to detect the failed transducer. A successful Pre--trip 5--9 will return the EEV and DUV to normal operation.
For the SPT to assume control of the unit, the unit must not be operating “in range” in addition to ALL 5 of the following conditions:
1. Unit is operating in frozen mode.
2. Unit has operated “in range” one time since the last Trip Start.
3. Both EPT and SPT are valid.
4. Both EPT readings are within +/-- 0.5 C (0.9 F) of each other.
5. Absolute difference between evaporator pressure and suction pressure readings is greater than 3.175.
Alarm is triggered off when evaporator pressure sensor is back in range. Alarm 67 is triggered by a humidity sensor reading outside the valid range of 0%
to 100% relative humidity. If alarm AL67 is triggered when the dehumidification mode is activated, then the dehumidification mode will be deactivated.
Alarm 68 is triggered when the Condenser Pressure Sensor is out of range. This is a display alarm and has no associated failure action.
Alarm 69 is triggered when the primary evaporator temperature sensor (ETS1) is out of range. The controller switches to use of the secondary evaporator temper­ature sensor (ETS2). This is a display alarm and triggered off when ETS1 is back within range.
3--25
T-340
Page 52
Table 3--6 Controller Alarm Indications (Sheet 5 of 5)
NOTE
If the controller is configured for four probes without a DataCORDER, the DataCORDER alarms AL70 and AL71 will be processed as Controller alarms AL70 and AL71. Refer to Table 3--10, page 3--33.
The controller performs self--check routines. If an internal failure occurs, an “ERR” alarm will appear on the display. This is an indication the controller needs to be replaced.
ERROR DESCRIPTION
ERR 0--RAM failure Indicates that the controller working memory has failed.
ERR
#
Entr
StPt
LO
Internal Microprocessor Failure
Enter Set point (Press Arrow & Enter)
Low Main V oltage (Function Codes Cd27--38 disabled and NO alarm stored.)
ERR 1--Program Memory
failure
ERR 2--Watchdog
time--out ERR 3--N/A N/A ERR 4--N/A N/A
ERR 5--A--D failure
ERR 6--IO Board failure Internal program/update failure. ERR 7--Controller failure Internal version/firmware incompatible. ERR 8--DataCORDER
failure ERR 9--Controller failure Internal controller memory failure. In the event that a failure occurs and the display cannot be updated, the status
LED will indicate the appropriate ERR code using Morse code as shown below.
ERR0to9
E R R 0 = . . -- . . -- . -- -- -- -- -­ERR1 = . .--. .--. . -------­ERR2 = . .--. .--. . . -- -- --
ERR3 = . .--. .--. . . . -- --
ERR4= . .--. .--. ....--
ERR5= . .--. .--. .....
ERR6= . .--. .--. --....
ERR7 = . .--. .--. -- -- . . . ERR8 = . .--. .--. -- ----. . E R R 9 = . . -- . . -- . -- -- -- -- .
The controller is prompting the operator to enter a set point.
This message will be alternately displayed with the set point whenever the supply voltage is less than 75% of its proper value.
Indicates a problem with the controller program.
The controller program has entered a mode whereby the controller program has stopped executing.
The controller’s Analog to Digital (A--D) converter has failed.
Internal DataCORDER memory failure.
3--26T-340
Page 53
Table 3--7 Controller Pre-- trip Test Codes (Sheet 1 of 4)
Code
No.
TITLE DESCRIPTION
“Auto” or “Auto1” menu includes the: P0, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu in­cludes P0, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts. “Auto3” menu includes P0, P1, P2, P3, P4, P5, P6, P7 and P8.
P0--0 Pre--trip Initiated
P1--0 Heaters Turned On
P1--1 Heaters Turned Off
P2--0 Condenser Fan On
P2--1 Condenser Fan Off
NOTE
All lights and display segments will be energized for five seconds at the start of the pre--trip. Since the unit cannot recognize lights and display failures, there are no test codes or results associated with this phase of pre--trip.
Setup: Heater must start in the OFF condition, and then be turned on. A current draw test is done after 15 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified. Setup: Heater must start in the ON condition, and then be turned off. A current
draw test is done after 10 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified. Requirements: Water pressure switch or condenser fan switch input must be
closed. Setup: Condenser fan is turned ON, a current draw test is done after 15 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified. Setup: Condenser fan is turned OFF, a current draw test is done after
10 seconds. Pass/Fail Criteria: Passes if current draw change is within the range specified.
Requirements: The unit must be equipped with a low speed evaporator fan, as determined by the Evaporator Fan speed select configuration variable.
P3
P3--0
P3--1
P4--0
P4--1
Low Speed Evaporator Fans
Low Speed Evaporator Fan Motors On
Low Speed Evaporator Fan Motors Off
High Speed Evaporator Fan Motors On
High Speed Evaporator Fan Motors Off
NOTE
If the unit is configured for single evaporator fan operation, Pre--trip tests P3--0, P3--1, P4--0 and P4--1 will fail immediately if Controller alarm codes AL11 or AL12 are active at the start of testing.
Setup: The High Speed Evaporator fans will be turned on for 10 seconds, then off for two seconds, then the low speed evaporator fans are turned on. A current draw test is done after 60 seconds. Pass/Fail Criteria: Passes if change in current draw is within the range speci­fied. Fails if AL11 or AL12 activates during test for units operating with single fan only.
Setup: The Low Speed Evaporator fan is turned off, a current draw test is done after 10 seconds. Pass/Fail Criteria: Passes if change in current draw is within the range speci­fied. Fails if AL11 or AL12 activates during test for units operating with single fan only.
Setup: The high speed evaporator fan is turned on, a current draw test is done after 60 seconds. Pass/Fail Criteria: Passes if change in current draw is within the range speci­fied. Fails if AL11 or AL12 activates during test for units operating with single fan only.
Setup: The high speed evaporator fan is turned off, a current draw test is done after 10 seconds. Pass/Fail Criteria: Passes if change in current draw is within the range speci­fied. Fails if AL11 or AL12 activates during test.
3--27
T-340
Page 54
P5--0
Supply/Return Probe Test
Table 3--7 Controller Pre-- trip Test Codes (Sheet 2 of 4)
Setup: The High Speed Evaporator Fan is turned on and run for eight minutes,
with all other outputs de--energized. Pass/Fail Criteria: A temperature comparison is made between the return and supply probes.
NOTE
If this test fails, “P5--0” and “FAIL” will be displayed. If both Probe tests (this test and the PRIMARY/ SECONDARY) pass, the display will read “P5” “PASS.”
Requirements: For units equipped with secondary supply probe only . Pass/Fail Criteria: The temperature difference between supply temperature sensor
(STS) and supply recorder sensor (SRS) probe is compared.
P5--1 Supply Probe Test
P5--2 Return Probe Test
P5--3
Evaporator Fan Direction Test
Primary .vs Sec-
P5--7
ondary Evaporator Temperature Sensor Test
NOTE
If this test fails, “P5--1” and “FAIL” will be displayed. If both Probe tests (this and the SUPPLY/RETURN TEST) pass, because of the multiple tests, the display will read “P 5” “PASS.”
Requirements: For units equipped with secondary return probe only. Pass/Fail Criteria: The temperature difference between return temperature sensor
(RTS) and return temperature sensor (RRS) probe is compared.
NOTES
1. If this test fails, “P5--2” and “FAIL” will be displayed. If both Probe tests (this test and the SUPPLY/RETURN) pass, because of the multiple tests, the display will read “P 5,” “PASS.”
2. The results of Pre--trip tests 5--0, 5--1 and 5--2 will be used to activate or clear control probe alarms.
Requirements: Test P5--0 must pass before this test is run. Setup: While the evaporator is running on high speed, the temperature differen-
tial between supply temperature sensor (STS) and return temperature sensor (RTS) probes is measured, with and without heaters energized. Pass/Fail Criteria: Passes if differential of STS is 0.25 degree C higher than RTS.
Pass/Fail Criteria: Passes if secondary evaporator temperature sensor (ETS2) is within +/-- 0.5 degree C of the primary evaporator temperature sensor (ETS1).
P5--8
P5--9
P5--10
P5--11
P5--12
Suction Pressure Transducer Test
Suction (Evaporat­or) Pressure Trans­ducer Test
Humidity Sensor Controller Configur­ation Verification Tes t
Humidity Sensor Installation Verifica­tion Test
Humidity Sensor Range Check Test
Requirements: Test P5--7 must pass before this test is run. Pass/Fail Criteria: Passes if suction pressure transducer (SPT) is within +/-- 0 psi
of saturation pressure at current evaporator temperature. Also passes if suction pressure transducer (SPT) is within +/-- 1 psi of discharge pressure 6 hours after a power interruption.
Pass/Fail Criteria: Passes if suction pressure transducer (SPT) is within +/-- 1.5 psi of the evaporator pressure transducer (EPT).
Requirements: Test P5--9 must pass before this test is run. Test is skipped if controller is not configured for the humidity sensor and the voltage is less than 0.20 volts. Pass/Fail Criteria: Passes if controller configuration has the humidity sensor in­stalled. Fails if controller is not configured for humidity sensor and the voltage is greater than 0.20 volts.
Requirements: Test P5--10 must pass before this test is run. Pass/Fail Criteria: Passes if voltage is greater than 0.20 volts for the humidity
sensor. Fails if voltage is less than 0.20 volts for the humidity sensor.
Requirements: Test P5--11 must pass before this test is run. Pass/Fail Criteria: Passes if the voltage for the humidity sensor is between 0.66
volts and 4 volts. Fails if voltage is outside of the 0.66 volt to 4 volt range.
3--28T-340
Page 55
Table 3--7 Controller Pre-- trip Test Codes (Sheet 3 of 4)
P6--0
P6--1
P6--2
P6--3
P6--4
Discharge Thermistor Test
Suction Thermistor Test
Discharge Pressure Sensor Test
Suction Pressure Sensor Test
Compressor Cur­rent Draw Test
If alarm 64 is activated any time during the first 45 second period of Step 1, the test fails.
Alarm is activated if suction temperature is outside of the valid range of --60C (--76F) to 150C (302F) any time during the first 45 second period of Step 1, the test fails.
If alarm 65 is activated any time during the first 45 second period of Step 1, the test fails.
If alarm 66 is activated, the test fails.
Compressor current is tested before and 10 seconds after start up. If current does not increase, the test fails. P6--7 is run at the end of P6--4. If this test fails, P6--6 is skipped.
NOTE
P6--6 through P6--10 tests are conducted by changing the status of each individual valve and comparing suction pressure change and/or compressor current change with predetermined values. The tests will cause the compressor and condenser fans to cycle on and of f as needed to generate the pressure required for the individual pre--trip sub tests. The compressor will start in order to build discharge pressure, followed by a compressor pump down sequence. At the conclusion of the compressor pump down sequence, the compressor will shut down and the valve test will start.
P6--6
P6--7
P6--10
Economizer Val v e Tes t
Digital Unloader Val v e Tes t
Electronic Expansion Valve Tes t
Passes if suction pressure increases a minimum of 4 psi when the valve opens for 15 seconds.
Passes if pressure and current changes are within 3 seconds of DUV switch sig­nal and either the pressure change or the current draw change is above 5 psi or above 1.5A, respectively.
Pass/Fail Criteria: The test records the suction pressure during the open valve position and passes if the suction pressure increase is above 3 psi when the valve opens for 10 seconds.
NOTE
P7--0 & P8 are included with “Auto2 & Auto 3” only. P9--0 through P10 are included with “Auto2” only.
NOTE
This test is skipped if the sensed ambient temperature is less than 7C (45F), the return air temperature is less than --17.8C (0F), the water pressure switch is open or the condenser fan switch is open.
P7--0
P7--1
High Pressure Switch Open
High Pressure Switch Closed
Setup: With the unit running, the condenser fan is turned off and a 900 second (15 minute) timer is started. The right display shows the value of the initial sensor configured and valid out of the discharge pressure, CPC pressure, dis­charge temperature.
Pass/Fail Criteria:The test fails immediately if:
--all three sensors are not configured or are invalid.
--the ambient temperature or return air temperature sensors are invalid at the start of the test.
The test fails if:
--the high pressure switch if open at the start of the test.
--the high pressure switch fails to open within 15 minutes.
--a valid discharge temperature exceeds 137.78 C (280 F).
--a valid discharge pressure or valid condensing pressure
exceeds 390 psig.
The test passes if the high pressure switch opens within the 15 minute time limit and before any of the valid and configured sensors exceed their limits.
Requirements: Test P7--0 must pass for this test to execute. Setup: The con­denser fan is started and a 60 second timer is started. Pass/Fail Criteria: Passes the test if the high pressure switch (HPS) closes within the 60 second time limit, otherwise, it fails.
3--29
T-340
Page 56
P8--0
P8--1
Perishable Mode Heat Test
Perishable Mode Pulldown Test
Perishable Mode
P8--2
Maintain Tempera­ture Test
P9--0 Defrost T est
P10--0
P10--1
Frozen Mode Heat Test
Frozen Mode Pulldown Test
Frozen Mode
P10--2
Maintain Temperature Test
Table 3--7 Controller Pre-- trip Test Codes (Sheet 4 of 4)
Setup: If the container temperature is below 15.6C (60F), the set point is
changed to 15.6C, and a 180--minute timer is started. The left display will read “P8--0.” The control will then heat the container until 15.6C is reached. If the con­tainer temperature is above 15.6C at the start of the test, then the test proceeds immediately to test P8--1 and the left display will change to “P8--1.” Pass/Fail Criteria: The test fails if the 180 minute timer expires before the con­trol temperature reaches set point. The display will read “P8--0,” “FAIL.”
Requirements: Control temperature must be at least 15.6C (60F). Setup: The set point is changed to 0C (32F), and a 180--minute timer is started.
The left display will read “P8--1,” the right display will show the supply air temper­ature. The unit will then start to pull down the temperature to the 0C set point. Pass/Fail Criteria: The test passes if the container temperature reaches set point before the 180 minute timer expires.
Requirements: Test P8--1 must pass for this test to execute. This test is skipped if the DataCORDER is not configured or not available. Setup: A 15--minute timer is started. The unit will be required to minimize control
temperature error (supply temperature minus set point) until the timer expires. The control temperature will be sampled at least once each minute starting at the beginning of P8--2. Pass/Fail Criteria: If the average recorded temperature is within +/-- 1.0C (1.8F) of set point, the test passes. If the average temperature is outside of the toler­ance range or if the DataCORDER supply temperature probe is invalid, the test fails and and the control probe temperature will be recorded as --50.0C. P8--2 will auto--repeat by starting P8--0 over.
Setup: The defrost temperature sensor (DTS) reading will be displayed on the left display. The right display will show the supply air temperature. The unit will run FULL COOL for 30 minutes maximum until the DTT is considered closed. Once the DTT is considered closed, the unit simulates defrost by running the heaters for up to two hours, or until the DTT is considered open. Pass/Fail Criteria: The test fails if: the DTT is not considered closed after the 30 minutes of full cooling, HTT opens when DTT is considered closed or if return air temperature rises above 49C (120F).
Setup: If the container temperature is below 7.2C (45F), the set point is changed to 7.2C and a 180--minute timer is started. The control will then be placed in the equivalent of normal heating. If the container temperature is above 7.2C at the start of the test, then the test proceeds immediately to test 10--1. During this test, the control temperature will be shown in the right display. Pass/Fail Criteria: The test fails if the 180--minute timer expires before the con­trol temperate reaches set point --0.3C (0.17F). If the test fails it will not auto--re­peat. There is no pass display for this test. Once the control temperature reach­es set point, the test proceeds to test 10--1
Requirements: Control temperature must be at least 7.2C (45F) Setup: The set point is changed to --17.8C (0F). The system will then attempt to
pull down the control temperature to set point using normal frozen mode cooling. During this test, the control temperate will be shown on the right display. Pass/Fail Criteria: If the control temperature does not reach set point --0.3C (0.17F) before the 180--minute timer expires the test fails and will auto--repeat by starting P10--0 over.
Requirements: Test P10--1 must pass for this test to execute. This test is skipped if the DataCORDER is not configured or not available. Setup: A 15--minute timer is started. The unit will be required to minimize return
probe temperature error (supply temperature minus set point) until the timer ex­pires. The return probe temperature will be sampled at least once each minute starting at the beginning of P10--2. Pass/Fail Criteria: If the average recorded temperature is within +/-- 1.6C (+/-- 2.9) of set point, the test passes. If the average temperature is outside of the tolerance range or if the DataCORDER return temperature probe is invalid, the test fails and the control probe temperature will be recorded as --50.0C. P10--2 will auto--repeat by starting P10--0 over.
3--30T-340
Page 57
Table 3--8 DataCORDER Function Code Assignments
NOTE
Inapplicable Functions Display “-- -- -- -- -- ”
To Access: Press ALT. MODE key
Code
No.
dC1
dC2
dC3--5
dC6--13
dC14
dC15--19 Future Expansion These codes are for future expansion, and are not in use at this time.
dC20--24
dC25 Future Expansion This code is for future expansion, and is not in use at this time.
dC26,27 S/N, Left 4, Right 4
dC28 Minimum Days Left
dC29 Days Stored Number of days of data that are currently stored in the DataCORDER.
dC30
dC31 Battery Test
dC32 Time: Hour, Minute Current time on the real time clock (RTC) in the DataCORDER. dC33 Date: Month, Day Current date (month and day) on the R TC in the DataCORDER. dC34 Date: Year Current year on the RTC in the DataCORDER.
dC35
Recorder Supply Temperature
Recorder Return Temperature
USDA 1,2,3 Temper­atures
Network Data Points 1--8
CargoProbe4Tem­perature
Temperature Sen­sors 1--5 Calibration
Date of Last Trip start
Cargo Probe 4 Calibration
TITLE DESCRIPTION
Current reading of the supply recorder sensor.
Current reading of the return recorder sensor.
Current readings of the three USDA probes.
Current values of the network data points (as configured). Data point 1 (Code 6) is generally the humidity sensor and its value is obtained from the controller once every minute.
Current reading of the cargo probe #4.
Current calibration offset values for each of the five probes: supply, return, USDA #1, #2, and #3. These values are entered via the interrogation pro­gram.
The DataCORDER serial number consists of eight characters. Function code dC26 contains the first four characters. Function code dC27 contains the last four characters. (This serial number is the same as the controller serial number.)
An approximation of the number of logging days remaining until the Data­CORDER starts to overwrite the existing data.
The date when a Trip Start was initiated by the user. In addition, if the system goes without power for seven continuous days or longer, a trip start will auto­matically be generated on the next AC power up. Press and hold “ENTER” key for five seconds to initiate a “Trip Start.”
Shows the current status of the optional battery pack.
PAS S: Battery pack is fully charged. FAIL: Battery pack voltage is low.
Current calibration value for the Cargo Probe. This value is an input via the interrogation program.
3--31
T-340
Page 58
Table 3--9 DataCORDER Pre--trip Result Records
Test
No.
TITLE DATA
1--0 Heater On Pass/Fail/Skip Result, Change in current for Phase A, B and C 1--1 Heater Off Pass/Fail/Skip Result, Change in currents for Phase A, B and C
2--0 Condenser Fan On
Pass/Fail/Skip Result, Water pressure switch (WPS) -- Open/Closed, Change in currents for Phase A, B and C
2--1 Condenser Fan Off Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3--0
3--1
4--0
4--1
Low Speed Evaporator Fan On
Low Speed Evaporator Fan Off
High Speed Evaporator Fan On
High Speed Evaporator Fan Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
5--0 Supply/Return Probe Test Pass/Fail/Skip Result, STS, RTS, SRS and RRS
5--1
5--2
Secondary Supply Probe (SRS)Test
Secondary Return Probe (RRS) Test
Pass/Fail/Skip
Pass/Fail/Skip
6--0 Discharge Thermistor Test Pass/Fail/Skip 6--1 Suction Thermistor Test Pass/Fail/Skip
6--2
Discharge Pressure Sensor Tes t
Pass/Fail/Skip
6--3 Suction Pressure Sensor Test Pass/Fail/Skip
6--4
Compressor Current Draw Tes t
Pass/Fail/Skip
6--6 Economizer Valve Test Pass/Fail/Skip 6--7 Digital Unloader Valve Test Pass/Fail/Skip
7--0 High Pressure Switch Closed
7--1 High Pressure Switch Open
Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped) Input values that component opens
Pass/Fail/Skip Result, STS, DPT or CPT (if equipped) Input values that component closes
8--0 Perishable Mode Heat Test Pass/Fail/Skip Result, STS, time it takes to heat to 16C (60F)
8--1
8--2
9--0 Defrost Test
Perishable Mode Pulldown Tes t
Perishable Mode Maintain Tes t
Pass/Fail/Skip Result, STS, time it takes to pull down to 0C (32F)
Pass/Fail/Skip Result, Averaged DataCORDER supply temperature (SRS) over last recording interval.
Pass/Fail/Skip Result, DTS reading at end of test, line voltage, line frequency, time in defrost.
10--0 Frozen Mode Heat Test Pass/Fail/Skip Result, STS, time unit is in heat. 10--1 Frozen Mode Pulldown Test Pass/Fail/Skip Result, STS, time to pull down unit to --17.8C (0F).
10--2 Frozen Mode Maintain Test
Pass/Fail/Skip Result, Averaged DataCORDER return temperature (RRS) over last recording interval.
3--32T-340
Page 59
Table 3--10 DataCORDER Alarm Indications
To Access: Press ALT. MODE key
Code No. TITLE DESCRIPTION
The supply recorder sensor reading is outside of the range of --50C to 70C
Recorder Supply
dAL70
dAL71
dAL72--74
dAL75
dAL76, 77 Future Expansion These alarms are for future expansion and are not in use at this time.
dAL78--85
dAL86 RTC Battery Low
dAL87 RTC Failure
dAL88
dAL89 Flash Memory Error
dAL90 Future Expansion This alarm is for future expansion, and is not in use at this time. dAL91 Alarm List Full The DataCORDER alarm queue is determined to be full (eight alarms).
Temperature Out of Range
Recorder Return Temperature Out of Range
USDA Temperatures 1, 2, 3 Out of Range
Cargo Probe 4 Out of Range
Network Data Point 1 -- 8 Out of Range
DataCORDER EEPROM Failure
(--58F to +158F), or the probe check logic has determined there is a fault with this sensor.
NOTE
The P5 Pre--trip test must be run to inactivate the alarm.
The return recorder sensor reading is outside of the range of --50C to 70C (--58F to +158F), or the probe check logic has determined there is a fault with this sensor.
NOTE
The P5 Pre--trip test must be run to inactivate the alarm.
The USDA probe temperature reading is outside of --50C to 70C (--58F to +158F) range.
The cargo probe temperature reading is outside of --50C to 70C (--58F to +158F) range.
The network data point is outside of its specified range. The DataCORD­ER is configured by default to record the supply and return recorder sen­sors. The DataCORDER may be configured to record up to eight addition­al network data points. An alarm number (AL78 to AL85) is assigned to each configured point. When an alarm occurs, the DataCORDER must be interrogated to identify the data point assigned. When a humidity sensor is installed, it is usually assigned to AL78.
The real time clock (RTC) backup battery is too low to adequately main­tain the RTC reading.
An invalid time has been detected. Either the DataCorder run time hour and minute have not changed at the start of the hour, or the real time clock (RTC) time has gained or lost more than 2 minutes in the hour. This situation may be corrected by cycling the power, setting the clock or meet­ing the above criteria for an hour.
A write of critical DataCORDER information to the EEPROM has failed.
An error has been detected in the process of writing daily data to the non-­volatile FLASH memory.
3--33
T-340
Page 60
SECTION 4
OPERATION

4.1 INSPECTION (Before Starting)

WARNING
Beware of unannounced starting of the evaporator and condenser fans. The unit may cycle the fans and compressor unex­pectedly as control requirements dictate.
a. If container is empty , check inside for the following:
1. Check channels or “T” bar floor for cleanliness. Channels must be free of debris for proper air cir­culation.
2. Check container panels, insulation and door seals for damage. Effect permanent or temporary repairs.
3. Visually check evaporator fan motor mounting bolts for proper securement (refer to paragraph 6.1 1).
4. Check for dirt or grease on evaporator fans or fan deck and clean if necessary.
5. Check evaporator coil for cleanliness or obstruc­tions. Wash with fresh water.
6. Check defrost drain pans and drain lines for obstruc­tions and clear if necessary. Wash with fresh water .
7. Check panels on refrigeration unit for loose bolts and condition of panels. Make sure TIR devices are in place on access panels.
b. Check condenser coil for cleanliness. Wash with
fresh water.
c. Open control box door. Check for loose electrical con-
nections or hardware.
d. Check color of moisture--liquid indicator.
2. Plug the 460 VAC (yellow) cable into a de--energized 380/460 VAC, 3--phase power source. Energize the power source. Place circuit breaker (CB--1) in posi­tion “I” (ON). Close and secure control box door.
4.2.2 Connection To 190/230 VAC Power
An autotransformer (Figure 4--1) is required to allow op­eration on nominal 230 volt power. It is fitted with a 230 VAC cable and a receptacle to accept the standard 460 VAC power plug. The 230 volt cable is black in color while the 460 volt cable is yellow. The transformer may also be equipped with a circuit breaker (CB--2). The transformer is a step up transformer that will provide 380/460 VAC, 3--phase, 50/60 Hz power to the unit when the 230 VAC power cable is connected to a 190/230 V AC, 3--phase power source.
1. Make sure that the start--stop switch (ST, on control panel) and circuit breakers CB--1 (in the control box and CB--2 (on the transformer) are in position “0” (OFF). Plug in and lock the 460 VAC power plug at the receptacle on the transformer.
2. Plug the 230 VAC (black) cable into a de--energized 190/230 VAC, 3--phase power source. Energize the power source. Set circuit breakers CB--1 and CB--2 to position “I” (ON). Close and secure control box door.
2
1
3

4.2 CONNECT POWER

WARNING
Do not attempt to remove power plug(s) be ­fore turning OFF start--stop switch (ST), unit circuit breaker(s) and external power source.
WARNING
Make sure the power plugs are clean and dry before connecting to power receptacle.
4.2.1 Connection To 380/460 VAC Power
1. Make sure start--stop switch (ST, on control panel) and circuit breaker (CB--1, in the control box) are in position “0” (OFF).
1. Dual Voltage Modular Autotransformer
2. Circuit Breaker (CB--2) 230--Volt
3. 460 VAC Power Receptacle
Figure 4--1 Autotransformer

4.3 ADJUST FRESH AIR MAKEUP VENT

The purpose of the fresh air makeup vent is to provide ventilation for commodities that require fresh air circula­tion. The vent must be closed when transporting frozen foods.
Air exchange depends on static pressure differential, which will vary depending on the container and how the container is loaded.
Units may be equipped with a vent position sensor (VPS). The VPS determines the position of the f resh air vent and sends data to the controller display.
4--1
T-340
Page 61
4.3.1 Upper Fresh Air Makeup Vent
Two slots and a stop are designed into the Upper Fresh Air disc for air flow adjustments. The first slot allows for a 0 to 30% air flow; the second slot allows for a 30 to 100% air flow. To adjust the percentage of air flow, loosen the wing nut and rotate the disc until the desired percentage of air flow matches with the arrow. Tighten the wing nut. To clear the gap between the slots, loosen the wing nut until the disc clears the stop.
Figure 4--2 gives air exchange values for an empty con­tainer. Higher values can be expected for a fully loaded container.
AIR FLOW (CMH)
250
200
150
100
50
0
0 102030405060708090
AIR FLOW (CMH)
300
250
200
150
100
50
0
0 102030405060708090
50HZ
PERCENT OPEN
60HZ
PERCENT OPEN
TBAR
TBAR 25/8”
TBAR 3”
100
100
11/2”
TBAR
11/2”
TBAR 25/8”
TBAR 3”
Figure 4--2 Upper Fresh Air Make Up Flow Chart
4.3.2 Lower Fresh Air Makeup Vent
a. Full Open or Closed Positions
Maximum air flow is achieved by loosening the wing nuts and moving the cover to the maximum open position (100% position). The closed position is 0% air flow position. The operator may also adjust the opening to increase or decrease the air flow volume to meet the required air flow.
b. Reduced Flow for Lower Fresh Air Makeup
NOTE
In order to prevent inaccurate display readings on units equipped with a Vent Position Sensor (VPS), ensure that the rack and pinion drive of the VPS is not disrupted when adjusting the air makeup vent.
NOTE
Do not loosen the hex nut beyond its stop. Do­ing so may cause inaccurate display readings and errors in DataCORDER reports.
Similar to the Upper Fresh Air Makeup vent, two slots and a stop are designed into the Lower Fresh Air slide for air flow adjustments. The first slot allows for a 0 to 25% air flow; the second slot allows for a 25 to 100% air flow. To adjust the percentage of air flow, loosen the hex nut and rotate the disc until the desired percentage of air flow matches with the arrow. Tighten the hex nut. To clear the gap between the slots, loosen the hex nut until the disc clears the stop.
On some models the air slide is supplied with two adjustableair control discs. The fresh air makeup canbe adjusted for 15, 35, 50 or 75 cubic meters per hour (CMH). The air flow has been established at 60 Hz power and 2--1/2 inch T bar and with 15 mm (0.6 inch) H
O external static above free blow.
2
Loosen the hex nut, adjust each disc to the required air flow, then tighten hex nut.
NOTE
The main air slide is in the fully closed position during reduced air flow operation when equipped with air control discs.
c. Air Sampling for Carbon Dioxide (CO
) Level
2
Loosen hex nuts and move the cover until the arrow on the cover is aligned with the “atmosphere sampling port” label. Tighten the hex nuts and attach a 3/8 in. hose to the sampling port.
If the internal atmosphere content has reached an unacceptable level, the operator may adjust the disc opening to meet the required air flow volume to ventilate the container.
4.3.3 Vent Position Sensor
The VPS allows the user to determine the position of the fresh air vent via Function Code 45. This function code is accessible via the Code Select key.
The vent position will display for 30 seconds whenever motion corresponding to 5 CMH (3 CFM) or greater is detected. It will scroll in intervals of 5 CMH (3 CFM). Scrolling to Function Code 45 will display the Fresh Air Vent Position.
The position of the vent will be recorded in the DataCORDER whenever the unit is running under AC power and any of the following:
Trip start On every power cycle Midnight Manual changes greater than 5 CMH (3 CFM) remaining in the new position for at least 4 minutes
T-340 4--2
Page 62
NOTE
The user has four minutes to make necessary adjustments to the vent setting. This time calculation begins on the initial movement of the sensor. The vent can be moved to any position within the four minutes. On completion of the first four minutes, the vent is required to remain stable for the next four minutes. If vent position changes are detected during the four--minute stability period, an alarm will be generated. This provides the user with the ability to change the vent setting without generating multiple events in the DataCORDER.

4.4 EAUTOFRESH OPERATION

The eAutoFresh system allows the opening and closing of the mechanical air vent slide. The opening and closing of the slide is determined by the mode selected through function code Cd43.
Upon power up, the controller will fully close the eAutoFresh air vent. Nine seconds after power up, the controller will check if there is a carbon dioxide (CO sensor connected. When a CO2sensor is detected, the controller will enable access to the Gas Limit mode of operation. If no sensor is detected, the only modes of operation available will be Test, User, and Delay . The controller will then resume operation in the last mode of operation before power interruption.
4.4.1 eAutoFresh Pre--Trip Inspection
Pre--trip testing of the eAutoFresh system is performed during Pre--Trip test P0. Operation of the system may be observed during this test.
Upon initiation of Pre- -Trip P0, the current state will be saved and the vent will fully close. This will be followed by two sequences of opening to 100% and returning to the closed position. No other eAutoFresh mode of operation will be available until the two cycles of opening and closing have completed. Upon termination of the test, the vent will open to the previous state and operation will return to the previous mode.
If the last mode was gASLM, the vent will open to the preset FLO setting, the controller will start taking new readings and control based on those readings.
4.4.2 eAutoFresh Start--Up Procedure
To start the system, do the following: a. Press the “CODE SELECT” key (see Figure 3--2). b. Press the “UP or DOWN“ arrow key until “CD43“ is
displayed, then press “ENTER”.
c. Press the “UP or DOWN“ arrow key to access the de-
sired mode of operation. When the mode operation is displayed press t he enter key to access the submenu parameters.
4.4.3 eAutoFresh Operation
The modes of operation are: OFF, USER, TEST, DELAY, and GASLIMIT. Each mode of operation has submenus with selectable parameters. Not all parameters are available in each submenu.
Operational Parameters
FLO indicates the opening to which the slide will move based on the stored value in CMH(in increments of 5) or CFM depending on the selection of Cd46 (Airflow dis­play units), Cd28 (Metric/Imperial) or the pressing of the
deg C/F key. CFM is displayed as CF, CMH is displayed as CM.
tIM is the time delay prior to the door opening. The time range is from 1 to 72 hrs in 1 hr increments.
CO2LM is the maximum level of carbon dioxide that is allowed for the cargo. The range is from 0% to 19% in 1% increments, the default setting is 10.
O2LM is the minimum level of O
that is allowed for the
2
cargo. The range is from 2% to 20% in 1% increments, the default setting is 10.
Rtn is an offset value used to expand the return air tem­perature value to compensate for the fresh air entering the container. The allowable range is from 0.6C to 2.8C or 1.0F to 5.0F in 0.1 degree increments the default set­ting is 2.8C (5F).
2)
4.4.4 eAutoFresh Modes of Operation
NOTE
When setting any mode of operation, complete the entire process to ensure all parameters are set.
a. OFF
A setting of OFF will disable all automatic venting operations. The eAutoFresh vent will be driven fully closed and the eAutoFresh opening set to 0 CMH in function code Cd44. This is the default mode whenever a frozen mode of operation has been selected. When the frozen set point is selected, the current eAutoFresh setting is saved. The vent position will restore when a perishable set point is selected.
b. USER
The USER mode provide ventilation for commodities that require fresh air circulation. The flow rate can be accessed through the submenu if a perishable set point has been selected. To set the flow rate, press the ENTER key to activate the selection mode. When FLO appears in the left hand window, use the UP or DOWN arrow key to scroll to the desired opening. The range is from 0 to 220CM (0 to 129CF) in increments of 5. Press the ENTER key to set the value and begin operation.
c. TEST
TEST mode allows the operator to test the movement of the mechanical slide air vent and calibrate the carbon dioxide sensor.
4--3
T-340
Page 63
tESt -- When “tESt” appears in the left window, press the ENTER key to begin the test. The eAutoFresh slide will open fully and then return to the closed position. The test may be observed by the operator to ensure proper operation of the vent. After completion of the TEST, the unit will return to the previous mode of operation.
NOTE
It is recommended that the calibration proced­ure only be performed during pre--trip or when the container has been fully vented.
CAL will attempt to calibrate the carbon dioxide sensor. When “CAL“ mode is selected the display will flash “CAL“. The operator is to hold the “ENTER“ key for 5 seconds. The display will stop flashing and read “CAL“ for 5 seconds. The microprocessor will read the CO value, and then compare that value to a known zero value. If the sensor is within the calibration parameter range, the microprocessor will determine the appropriate offset for the sensor. If the sensor is outside of this range, for example if the container is loaded or has a high level of CO
the controller will flash “NOCAL“
2,
for 5 seconds then revert to the previous mode of operation.
d. DELAY
In DELAY mode, the operation of the eAutoFresh system will be delayed for a set amount of time. This allows time for the cargo to reach set point. In DELAY mode, the eAutoFresh vent will open to the stored (FLO) value when the return air temperature sensor is at or below set point plus the return offset value (rtn) or the delay time (tIM), whichever comes first. The eAutoFresh vent will be fully closed when return air temperature sensor is greater than the set point plus the offset temperature (rtn).
To set the unit in Delay mode, scroll until “DELAY“ appears in the left window, press the ENTER key to activate the submenu. The first selection is the amount of time (tIM) for the delay . Select the amount of time for the delay by using the UP and DOWN arrow keys. The range is from 1 to 72 hours in 1 hour increments. Press the ENTER key to set the value and move to the FLO rate. Use the UP or DOWN arrow key to scroll to the desired FLO rate. The range is from 0 to 220CM (0 to 129CF) in increments of 5 and 3 respectively. Press the ENTER key to set the value and move to the return temperature offset. Use the UP or DOWN arrow key to scroll to the desired rtn rate. The range of offset is from
0.6C to 2.8C (1.0F to 2.8F) in 0.1 degree increments. Press the ENTER key to set the value and begin operation.
e. GAS LIMIT (gASLM)
In GAS LIMIT mode, access to the submenu is available provided a perishable set point has been selected, and a valid reading is detected from the carbon dioxide sensor. In “Gas limit” mode the microprocessor will monitor and limit the amount of carbon dioxide within the container by opening and closing the eAutoFresh vent. The vent will open to the (FLO) setting once the unit has completed initial temperature pull down or if the cargo temperature is within 5C of set point and the carbon dioxide level has reached the max limit or if the Oxygen level has reached the lower limit. After the first 15 minutes of the vent opening the controller will again evaluate the level of CO first 15 minutes the gas limit values are satisfied, the
, and/or O2levels. If after the
2
vent will close, if either gas limit has not been satisfied within 15 minutes the air exchange vent will open in 10 CMH increments every 15 minutes until both gas concentrations are satisfied. Once all limits are satisfied the vent will return to the closed position. If conditions are not met with slide open 100% for 90 minutes Alarm 29 will be activated.
To operate in Gas Limit mode, scroll until gASLM appears in the left window, press the ENTER key to activate the submenu. The first selection is the maximum carbon dioxide (CO2LM). Select the max level by using the UP and DOWN arrow keys. The range is from 0 to 19% in 1% increments. Press the ENTER key to set the value and move to the minimum Oxygen level (O2LM). The range is from 2 to 20% in 1% increments. Press the ENTER key to set the value and move to the FLO rate. Use the UP or DOWN arrow key
2
to scroll to the desired FLO rate. The range is from 0 to 220CM (0 to 129CF) in increments of 5 and 3 respectively. Press the ENTER key to set the value and begin operation.
4.5 CONNECT WATER--COOLED CONDENSER
The water--cooled condenser is used when cooling wa­ter is available and heating the surrounding air is objec­tionable, such as in a ship’s hold. If water--cooled opera­tion is desired, connect in accordance with the following subparagraphs.
4.5.1 Water--Cooled Condenser with Water Pres­sure Switch
a. Connect the water supply line to the inlet side of con-
denser and the discharge line to the outlet side of the condenser. (See Figure 2--5.)
b. Maintain a flow rate of 11 to 26 liters per minute (3 to 7
gallons per minute). The water pressure switch will open to de--energize the condenser fan relay. The condenser fan motor will stop and will remain stopped until the water pressure switch closes.
c. To shift to air--cooled condenser operation, discon-
nect the water supply and the discharge line to the water--cooled condenser. The refrigeration unit will shift to air--cooled condenser operation when the wa­ter pressure switch closes.
4.5.2 Water--Cooled Condenser with Condenser Fan Switch
a. Connect the water supply line to the inlet side of con-
denser and the discharge line to the outlet side of the
condenser. (See Figure 2--5.) b.Maintainaflowrateof11to26lpm(3to7gpm). c. Set the condenser fan switch to position “O.” This will
de--energize the condenser fan relay. The condenser
fan motor will stop and remain stopped until the CFS
switch is set to position “I.”
CAUTION
When condenser water flow is below 11 lpm (3 gpm) or when water--cooled operation is not in use, the CFS switch MUST be set to position “1” or the unit will not operate properly.
d. To shift to air--cooled condenser operation, stop the
unit, set the CFS switch to position ”I” and restart the
unit. Disconnect the water lines to the water--cooled
condenser.
T-340 4--4
Page 64
4.6 CONNECT REMOTE MONITORING RECEPTACLE
If remote monitoring is required, connect remote moni­tor plug at unit receptacle. When the remote monitor plug is connected to the remote monitoring receptacle, the following remote circuits are energized:
CIRCUIT
Sockets B to A Energizes remote cool light Sockets C to A Energizes remote defrost light Sockets D to A Energizes remote in--range light

4.7 STARTING AND STOPPING INSTRUCTIONS

FUNCTION
WARNING
Make sure that the unit circuit breaker(s) (CB--1 & CB--2) and the START-- STOP switch (ST) are in the “O” (OFF) position be­fore connecting to any electrical power source.
4.7.1 Starting the Unit
a. With power properly applied, the fresh air vent posi-
tion set and (if required) the water--cooled condenser connected (refer to paragraphs 4.2, 4.3 & 4.5), place the START--STOP switch to “I” (ON).
NOTE
The electronic phase detection system will check for proper compressor rotation within the first 30 seconds. If rotation is not correct, the compressor will be stopped and restarted in the opposite direction. If the compressor is produc­ing unusually loud and continuous noise after the first 30 seconds of operation, stop the unit and investigate.
b. The Controller Function Codes for the container ID
(Cd40), software version (Cd18) and unit model num­ber (Cd20) will be displayed in sequence.
c. Continue with Start Up Inspection, paragraph 4.8.
4.7.2 Stopping the Unit
To stop the unit, place the START--STOP switch in posi­tion “0” (OFF).
4.8 START--UP INSPECTION
4.8.1 Physical Inspection
a. Check rotation of condenser and evaporator fans.
4.8.2 Check Controller Function Codes
Check, and if required, reset controller Function Codes (Cd27 through Cd39) in accordance with desired oper­ating parameters. Refer to Table 3--5.
4.8.3 Start T emperature Recorder
Partlow Recorders
a. Open recorder door and check battery of electronic
recorder. Be sure key is returned to storage clip of mechanical recorder.
b. Lift stylus (pen) by pulling the marking tip outward un-
til the stylus arm snaps into it’s retracted position.
c. Install new chart, making sure chart is under the four
corner tabs. Lower the stylus until it has made contact with the chart. Close and secure door.
DataCORDER
a. Check and, if required, set the DataCORDER Config-
uration in accordance with desired recording parame­ter. Refer to paragraph 3.7.3.
b. Enter a “Trip Start.” To enter a “Trip Start,” do the fol-
lowing:
1. Depress the ALT MODE key. When the left display shows, dC, depress the ENTER key.
2. Scroll to Code dC30.
3. Depress and hold the ENTER key for five seconds.
4. The “Trip Start” event will be entered in the Data­CORDER.
4.8.4 Complete Inspection
Allow unit to run for five minutes to stabilize conditions and perform a pre--trip diagnosis in accordance with the following paragraph.
4.9 PRE--TRIP DIAGNOSIS
CAUTION
Pre--trip inspection should not be per­formed with critical temperature cargoes in the container.
CAUTION
When Pre--Trip key is pressed, economy, dehumidification and bulb mode will be deactivated. At the completion of Pre--Trip activity, economy, dehumidification and bulb mode must be reactivated.
Pre--Trip diagnosis provides automatic testing of the unit components using internal measurements and comparison logic. The program will provide a “PASS” or “FAIL” display to indicate test results.
The testing begins with access to a pre--trip selection menu. The user may have the option of selecting one of two automatic tests. These tests will automatically perform a series of individual pre--trip tests. The user may also scroll down to select any of the individual tests. When only the short sequence is configured, it will appear as “AUtO” in the display. Otherwise “AUtO1” will indicate the short sequence and “AUtO2” will indicate the long sequence. The test short sequence will run tests P0 through P6. The long test sequence will run tests P0 through P10.
A detailed description of the pre--trip test codes is listed in Table 3--7, page 3--23. If no selection is made, the pre--trip menu selection process will terminate automatically. However, dehumidification and bulb mode must be reactivated manually if required.
Scrolling down to the “rSLts” code and pressing ENTER will allow the user to scroll through the results of the last pre--trip testing run. If no pre--testing has been run (or an individual test has not been run) since the unit was powered up, “-- ---- --” will be displayed.
4--5
T-340
Page 65
To start a pre--trip test, do the following:
NOTE
1. Prior to starting tests, verify that unit voltage (Function Code Cd07) is within tolerance and unit amperage draw (Function Codes Cd04, Cd05, Cd06) are within expected limits. Otherwise, tests may fail incorrectly.
2. All alarms must be rectified and cleared before starting tests.
3. Pre--trip may also be initiated via communications. The operation is the same as for the keypad initiation described below except that should a test fail, the pre--trip mode will automatically terminate. When initiated via communications, a test may not be interrupted with an arrow key, but the pre--trip mode can be terminated with the PRE--TRIP key.
a. Press the PRE--TRIP key. This accesses a test
selection menu.
b. TO RUN AN AUTOMATIC TEST: Scroll through the
selections by pressing the UP ARROW or DOWN ARROW keys to display AUTO, AUTO 1, AUTO 2 or AUTO 3 as desired, then press the ENTER key.
1. The unit will execute the series of tests without any need for direct user interface. These tests vary in length, depending on the component under test.
2. While tests are running, “P#--#” will appear on the left
display; the #’s indicate the test number and sub--test. The right display will show a countdown time in minutes and seconds, indicating the amount of time remaining in the test.
CAUTION
When a failure occurs during automatic testing, the unit will suspend operation awaiting operator intervention.
When an automatic test fails, it will be repeated once. A repeated test failure will cause “FAIL” to be shown on the right display, with the corresponding test num­ber to the left. The user may then press the DOWN ARROW to repeat the test, the UP ARROW to skip to the next test or the PRE--TRIP key to terminate test­ing. The unit will wait indefinitely or until the user manually enters a command.
CAUTION
When Pre--Trip test Auto 2 runs to comple­tion without being interrupted, the unit will terminate pre-- trip and display “Auto 2” “end.” The unit will suspend operation until the user depresses the ENTER key!
When an Auto 1 runs to completion without a failure, the unit will exit the pre--trip mode and return to nor­mal control operation. However, dehumidification and bulb mode must be reactivated manually if required.
c. TO RUN AN INDIVIDUAL TEST: Scroll through the
selections by pressing the UP ARROW or DOWN
ARROW keys to display an individual test code. Pressing ENTER when the desired test code is displayed.
1. Individually selected tests, other than the LED/Display test, will perform the operations necessary to verify the operation of the component. At the conclusion, PASS or FAIL will be displayed. This message will remain displayed for up to three minutes, during which time a user may select another test. If the three minute time period expires, the unit will terminate pre--trip and return to control mode operation.
2. While the tests are being executed, the user may terminate the pre--trip diagnostics by pressing and holding the PRE--TRIP key. The unit will then resume normal operation. If the user decides to terminate a test but remain at the test selection menu, the user may press the UP ARROW key. When this is done, all test outputs will be de--energized and the test selection menu will be displayed.
3. Throughout the duration of any pre--trip test (except the P--7 high pressure switch tests), the current and pressure limiting processes are active. The current limiting process only is active for P--7.
d. Pre--Trip Test Results
At the end of the pre--trip test selection menu, the mes­sage “P,” “rSLts” (pre--trip results) will be displayed. Pressing the ENTER key will allow the user to see the results for all subtests (i.e., 1--0, 1--1, etc). The results will be displayed as “PASS” or “FAIL” for all the tests run to completion since power up. If a test has not been run since power up, “-- -- -- -- -- ” will be displayed. Once all pre--test activity is completed, dehumidification and bulb mode must be reactivated manually if required.

4.10 OBSERVE UNIT OPERATION

4.10.1 Probe Diagnostic Logic
Units configured with four temperature control four-­probe configuration, which includes the DataCORDER supply and return air probes as the secondary controller probes. The controller continuously performs probe diagnosis testing that compares the four probes. If the diagnosis result indicates a problem exists, the control­ler will perform a probe check to identify which probe or probes are in error.
a. Probe Diagnostic Logic
In the perishable mode of operation, both pairs of supply and return probes are monitored for probe disagreement. Probe disagreement is considered a difference of 0.5 C (0.9 F) or greater between the supply air sensors and/or a difference of 2.0 C (3.6 F) between the return air sensors. Probe disagreement found in either pair can trigger a defrost probe check.
In the frozen mode of operation, only the controlling probes are considered. Disagreement of the controlling probes can trigger a defrost probe check, which will occur when the difference between the sensors are greater than 2.0 C (3.6 F). Normally, the controlling probes are the return probes but if both return probes are invalidated, the supply probes are used for control purposes. Probe disagreement of the non--controlling probe pair will not trigger a defrost probe check.
If the supply probes agree and return probes agree, all supply and return sensors are valid and the unit returns to normal control.
T-340 4--6
Page 66
If supply probes disagree and the return probes agree, then invalidate the worst supply probe. If the probe check is run as part of Pre--trip P--5, an alarm will be triggered for the invalidated probe. If it is a run time de­frost probe check, the invalidated probe will be passed over and no alarm will be triggered. However , if the best supply probe is greater than 1.2 C (2.2 F) difference with respect to its return probes, the best supply probe is also invalidated. If unit is in perishable operation, a probe alarm will be triggered for both supply probes.
If the supply probes agree and return probes disagree, invalidate the worst return probe. If the probe check is being run as part of Pre--trip P--5, an alarm will be triggered for the invalidated probe. If it is a run time de­frost probe check, the invalidated probe will be passed over and no alarm will be necessary. If the best return probe is greater than 1.2 C (2.2 F) difference with re­spect to its supply probes, then the best return probe is also invalidated. If unit is in perishable operation, a probe alarm will be triggered for both return probes.
b. Probe Check Procedure
A probe check diagnostic procedure is executed during Pre--trip P--5. A defrost cycle probe check may be accomplished at the end of defrost by energizing the evaporator motors for eight minutes at the end of the normal defrost. The defrost light will remain on during this period. If supply probes are within limits and return probes are within limits, the unit will return to normal control.

4.11 Emergency Bypass Operation

To place the unit in the emergency bypass mode:
1. Locate the connection diagram and connectors for the emergency bypass (EB) sensors behind the top left side of the compressor.
2. Disconnect the emergency bypass connector from
the controller connector and attach it to the emergency bypass module connector. See Figure 4--3.
3. Locate the wire tire located at the EB switch in the
control box.
4. Cut the wire tie, then place the EB switch in the On
position.
5. Place the Mode Switch (MS) in the Full Cool position
to enable the system for cooling.
6. Manually control container air temperature by cycling
the Mode switch between Full Cool and evaporator Fans Only.
To operate the fans only, the MODE switch must be in the FANS ONLY position and the EMERGENCY BYPASS switch must be in the ON position.
The EBS module uses the system’ssafety devices (high pressure switch, motor internal protectors, and heat termination thermostat) to protect the system while in Emergency Bypass Mode.
CAUTION
The unit will remain in the full coolingmode as long as the EB switch is in the On posi­tion and the Mode Switch is in the Full Cool position. If the cargo can be damaged by low temperatures, the operator must monit­or container temperature and manually cycle operation as required to maintain temperature within required limits.
When the Emergency Bypass switch is in the On position, the EBS will be enabled. With the Mode switch in Full Cool mode, the following will occur simultaneously:
a. The EBS switch will enable EBS input. b. The phase detection circuit will detect the phase
rotation and close to provide power to the compressor contactor.
c. The condenser fan contact will close to energize the
condenser contactor and provide power to the con­denser fan motor.
d. The evaporator fan contact will close to energize the
high speed evaporator contactor and provide power to the evaporator fan motor.
e. The EBS electronic module will operate the EEV to
control superheat.
To return the unit to normal operation:
1. Locate the connectors behind the compressor.
2. Disconnect the Emergency Bypass connector from the EBS module connector and reconnect it to the controller connector. See Figure 4--3.
3. Inside the control box, place the EB switch in the Off
position.
4. Re-install the wire tie at the switch mounting.
EMERGENCY BYPASS
CONNECTOR
Figure 4--3 Diagram of Emergency Bypass
Connections
Change 11/09
4--7
T-340
Page 67
SECTION 5
TROUBLESHOOTING
CONDITION POSSIBLE CAUSE

5.1 UNIT WILL NOT START OR ST ARTS THEN STOPS

External power source OFF Turn on
No power to unit
Loss of control power
Component(s) not operating
Compressor hums, but does not start
Start--Stop switch OFF or defective Check Circuit breaker tripped or OFF Check Autotransformer not connected 4.2.2 Circuit breaker OFF or defective Check Control transformer defective Replace Fuse (F3A/F3B) blown Check Start--Stop switch OFF or defective Check Evaporator fan motor internal protector open 6.11 Condenser fan motor internal protector open 6.7 Compressor internal protector open 6.4 High pressure switch open 5.8 Heat termination thermostat open Replace Malfunction of current sensor Replace Low line voltage Check Single phasing Check Shorted or grounded motor windings 6.4 Compressor seized 6.4
REMEDY/
REFERENCE
SECTION

5.2 UNIT OPERA TES LONG OR CONTINUOUSLY IN COOLING

Container
Refrigeration system
Hot load Normal Defective box insulation or air leak Repair Shortage of refrigerant 6.3 Evaporator coil covered with ice 5.6 Evaporator coil plugged with debris 6.10 Evaporator fan(s) rotating backwards 6.10/6.1 1 Air bypass around evaporator coil Check Controller set too low Reset Compressor service valves or liquid line shutoff valve
partially closed
Dirty condenser 6.6 Compressor worn 6.4 Current limit (function code Cd32) set to wrong value 3.4.3 Economizer solenoid valve malfunction 6.17 Digital unloader valve stuck open Replace Electronic expansion valve Replace
Open valves completely
5--1
T-340
Page 68
CONDITION POSSIBLE CAUSE

5.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING

Abnormal pressures 5.8 Abnormal temperatures 5.17 Abnormal currents 5.18 Controller malfunction 5.10
Refrigeration system

5.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING

No operation of any kind
No control power
Unit will not heat or has insuffi­cient heat
Evaporator fan or motor defective 6.11 Compressor service valves or liquid line shutoff valve
partially closed
Frost on coil 5.11 Digital unloader valve stuck open Replace Electronic expansion valve Replace
Start--Stop switch OFF or defective Check Circuit breaker OFF or defective Check External power source OFF Turn ON Circuit breaker or fuse defective Replace Control Transformer defective Replace Evaporator fan internal motor protector open 6.11 Heat relay defective Check Heater termination thermostat open 6.10 Heater(s) defective 6.10 Heater contactor or coil defective Replace Evaporator fan motor(s) defective or rotating backwards 6.10/6.11 Evaporator fan motor contactor defective Replace Controller malfunction 5.10 Defective wiring Replace Loose terminal connections Tighten Low line voltage 2.3
REMEDY/
REFERENCE
SECTION
Open valves completely

5.5 UNIT WILL NOT TERMINATE HEATING

Controller improperly set Reset
Unit fails to stop heating

5.6 UNIT WILL NOT DEFROST PROPERLY

Will not initiate defrost automatically
Will not initiate defrost manually
Initiates but relay (DR) drops out Low line voltage 2.3
Controller malfunction 5.10 Heater termination thermostat remains closed along with
the heat relay
Defrost timer malfunction (Cd27) Table 3--5 Loose terminal connections Tighten Defective wiring Replace Defrost temperature sensor defective or heat termination
thermostat open
Heater contactor or coil defective Replace Manual defrost switch defective Replace Keypad is defective Replace Defrost temperature sensor open Replace
5--2T-340
6.10
Replace
Page 69
CONDITION POSSIBLE CAUSE

5.7 UNIT WILL NOT DEFROST PROPERLY (Continued)

REMEDY/
REFERENCE
SECTION
Initiates but does not defrost
Frequent defrost Wet load Normal

5.8 ABNORMAL PRESSURES

High discharge pressure
Low suction pressure
Suction and discharge pres­sures tend to equalize when unit is operating
Heater contactor or coil defective Replace Heater(s) burned out 6.10
Condenser coil dirty 6.6 Condenser fan rotating backwards 6.7 Condenser fan inoperative 6.7 Refrigerant overcharge or noncondensibles 6.3 Discharge service valve partially closed Open Electronic expansion valve (EEV) control malfunction Replace Incorrect software and/or controller configuration Check Failed suction pressure transducer (SPT) or evaporator
pressure transducer (EPT)
Suction service valve partially closed Open Filter drier partially plugged 6.9 Low refrigerant charge 6.3 No evaporator air flow or restricted air flow 6.10 Excessive frost on evaporator coil 5.6 Evaporator fan(s) rotating backwards 6.11.3 EEV control malfunction Replace Failed digital unloader valve (DUV) Replace Compressor operating in reverse 5.16 Compressor cycling/stopped Check Failed digital unloader valve (DUV) Replace
Replace

5.9 ABNORMAL NOISE OR VIBRATIONS

Compressor start up after an extended shutdown Brief chattering when manually shut down
Compressor
Condenser or Evaporator Fan

5.10 MICROPROCESSOR MALFUNCTION

Will not control
Compressor operating in reverse 5.16 Loose mounting bolts or worn resilient mounts Tighten/Replace Loose upper mounting 6.4.1 Liquid slugging 6.13 Bent, loose or striking venturi Check Worn motor bearings 6.7/6.11 Bent motor shaft 6.7/6.11
Incorrect software and/or controller configuration Check Defective sensor 6.21 Defective wiring Check Low refrigerant charge 6.3
Normal
5--3
T-340
Page 70
CONDITION POSSIBLE CAUSE

5.11 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW

REMEDY/
REFERENCE
SECTION
Evaporator coil blocked
No or partial evaporator air flow

5.12 eAutoFresh NOT OPERATING

Vent not opening
Gas Limit mode unavailable
Unable to calibrate CO2sensor
Code 44 displays “----------”
Frost on coil 5.6 Dirty coil 6.10 Evaporator fan motor internal protector open 6.11 Evaporator fan motor(s) defective 6.11 Evaporator fan(s) loose or defective 6.11 Evaporator fan contactor defective Replace
Unit not Configured for eAutoFresh Operation No action Code 43 in Off mode 4.4.2 Wiring disconnected Check wiring Stepper drive defective 6.12.2 Stepper motor defective 6.12.3 Unit operating in frozen mode 4.4.4 Check CO2sensor 4.4.4 Wiring disconnected Check wiring Unit operating in frozen mode 4.4.4 “Enter“ Key not held for sufficient length of time 4.4.4 CO2outside of acceptable levels Check Check CO2sensor 4.4.4 Unit not Configured for eAutoFresh Operation No action Check CO2sensor 4.4.4

5.13 ELECTRONIC EXPANSION VALVE MALFUNCTION

Incorrect software and/or controller configuration Check Failed suction pressure transducer (SPT) or evaporator
pressure transducer (EPT)
Suction service valve partially closed Open Filter drier partially plugged 6.9
Low suction pressure
High suction pressure with low superheat
Liquid slugging in compressor
Low refrigerant charge 6.3 No evaporator air flow or restricted air flow 6.10 Excessive frost on evaporator coil 5.6 Evaporator fan(s) rotating backwards 6.11.3 EEV control malfunction 6.13 Failed digital unloader valve (DUV) Replace Loose or insufficiently clamped sensor Replace Foreign material in valve 6.13 Failed suction pressure transducer (SPT) or evaporator
pressure transducer (EPT)
EEV control malfunction Replace
Improperly seated powerhead
Failed suction pressure transducer (SPT) or evaporator pressure transducer (EPT)
Failed EEV Replace
Replace
Replace
Ensure power­head is locked and in place
Replace
5--4T-340
Page 71
CONDITION POSSIBLE CAUSE

5.14 AUTOTRANSFORMER MALFUNCTION

Circuit breaker (CB--1 or CB--2) tripped Check
Unit will not start
5.15 WATER--COOLED CONDENSER OR WATER PRESSURE SWITCH
Autotransformer defective 6.18 Power source not turned ON Check 460 VAC power plug is not inserted into the receptacle 4.2.2
REMEDY/
REFERENCE
SECTION
High discharge pressure
Condenser fan starts and stops
5.16 COMPRESSOR OPERATING IN REVERSE
The compressor may start in reverse for up to 10 seconds to determine correct phase rotation if required for phase detection.
Allowing the scroll compressor to operate in reverse for more than two minutes will result in internal compressor damage. Turn the start--stop switch OFF immediately.
Electrical
5.17 ABNORMAL TEMPERATURES
High discharge temperature
Dirty coil Noncondensibles Water pressure switch malfunction Check Water supply interruption Check
NOTE
CAUTION
Incorrect wiring of compressor Incorrect wiring of compressor contactor(s) Incorrect wiring of current sensor
Condenser coil dirty 6.6 Condenser fan rotating backwards 6.7 Condenser fan inoperative 6.7 Refrigerant overcharge or noncondensibles 6.3 Discharge service valve partially closed Open Electronic expansion valve (EEV) control malfunction Replace Failed suction pressure transducer (SPT) or evaporator
pressure transducer (EPT)
Discharge temperature sensor drifting high Replace Failed economizer expansion valve, economizer coil, or
economizer solenoid valve
Plugged economizer expansion valve, economizer coil, or economizer solenoid valve
Loose or insufficiently clamped sensor Replace
6.8
Check
Replace
Replace
Replace
5.18 ABNORMAL CURRENTS
Unit reads abnormal currents Current sensor wiring Check
5--5
T-340
Page 72
SECTION 6
SERVICE
NOTE
Use a refrigerant recovery system whenever removing refrigerant. When working with refrigerants you must comply with all local government environmental laws. In the U.S.A., refer to EPA section 608.
A R-134a manifold gauge/hose set with self-sealing ho-
DANGER
Never use air for leak testing. It has been de­termined that pressurized, mixtures of re­frigerant and air can undergo combustion when exposed to an ignition source.

6.1 SECTION LAYOUT

Service procedures are provided herein beginning with refrigeration system service, then refrigeration system component service, electrical system service, tempera­ture recorder service and general service. Refer to the Table of Contents to locate specific topics.

6.2 MANIFOLD GAUGE SET

The manifold gauge set (see Figure 6--1) is used to determine system operating pressure, add refrigerant charge, and to equalize or evacuate the system.
ses (see Figure 6--2) is required for service of the mod­els covered within this manual. The manifold gauge/ hose set is available from Carrier Transicold. (Carrier Transicold part number 07-00294-00, which includes items 1 through 6, Figure 6--2.) To perform service using the manifold gage/hose set, do the following:
a. Preparing Manifold Gauge/Hose Set For Use
If the manifold gauge/hose set is new or was exposed to the atmosphere, it will need to be eva­cuated to remove contaminants and air as follows:
1. Back seat (turn counterclockwise) both field service couplings (see Figure 6--2) and midseat both hand valves.
2. Connect the yellow hose to a vacuum pump and re­frigerant 134a cylinder.
1
2
1
67
5
3
4
1. Opened (Backseated) Hand Valve
2. Suction Pressure Gauge
3. Discharge Pressure Gauge
4. Closed (Frontseated) Hand Valve
5. Connection to high side of system
6. Connection to either: a. Refrigerant cylinder OR b. Oil Container
7. Connection to low side of system
Figure 6--1 Manifold Gauge Set
When the suction pressure hand valve is frontseated (turned all the way in), the suction (low) pressure can be checked. When the discharge pressure hand valve is frontseated, the discharge (high) pressure can be checked. When both valves are open (all the way out), high pressure vapor will flow into the low side. When the suction pressure valve is open and the discharge pres­sure valve shut, the system can be charged. Oil can also be added to the system.
To Low Side Access Valve
7
3
To High Side Access Valve
2
4
8
5
3
5
6
1. Manifold Gauge Set
2. RED Refrigeration and/or Evacuation Hose (SAE J2196/R-134a)
3. Hose Fitting (0.5-16 Acme)
4. YELLOW Refrigeration and/or Evacuation Hose (SAE J2196/R-134a)
5. Hose Fitting with O-ring (M14 x 1.5)
6. High Side Field Service Coupling (Red Knob)
7. BLUE Refrigeration and/or Evacuation Hose (SAE J2196/R-134a)
8. Low Side Field Service Coupling (Blue Knob)
Figure 6--2 R-134a Manifold Gauge/Hose Set
3. Evacuate to 10 inches of vacuum and then charge with R-134a to a slightly positive pressure of 0.1 kg/
2
cm
(1.0 psig).
4. Front seat both manifold gauge set valves and dis­connect from cylinder. The gauge set is now ready for use.
6--1
T-340
Page 73
6.3 REFRIGERATION SYSTEM SERVICE-UNITS WITH STANDARD PIPING (with Service Valves)
6.3.1 Service Connections
The compressor suction, compressor discharge, and the liquid line service valves (see Figure 6--3) are pro­vided with a double seat and an access valve which enable servicing of the compressor and refrigerant lines. T urning the valve stem clockwise (all the way for­ward) will frontseat the valve to close off the lineconnec­tion and open a path to the access valve. Turning the stem counterclockwise (all the way out) will backseat the valve to open the line connection and close off the path to the access valve.
With the valve stem midway between frontseat and backseat, both of the service valve connections are open to the access valve path.
For example, the valve stem is first fully backseated when connecting a manifold gauge to measure pres­sure. Then, the valve is opened 1/4 to 1/2 turn to mea­sure the pressure.
2
1
6
5
4
3
7
2. Midseat both hand valves on the manifold gauge set and allow the pressure in the manifold gauge set to be drawn down to low side pressure. This returns any liquid that may be in the high side hose to the system.
3. Backseat the low side service valve. Backseat both field service couplings and frontseat both manifold hand valves. Remove the couplings from the access valves.
4. Install both service valve stem caps and service port caps (finger-tight only).
6.3.2 Pumping Down the Unit
To service the filter drier, economizer, expansion valves, economizer solenoid valve, digital unloader valve or evaporator coil, pump the refrigerant into the high side as follows:
CAUTION
The scroll compressor achieves low suc­tion pressure very quickly. Do not use the compressor to evacuate the system below 0 psig. Never operate the compressor with the suction or discharge service valves closed (frontseated). Internal damage will result from operating the compressor in a deep vacuum.
1. Line Connection
2. Access Valve
3. Stem Cap
4. Valve stem
Figure 6--3 Service Valve
To connect the manifold gauge/hose set for reading pressures, do the following:
1. Remove service valve stem cap and check to make sure it is backseated. Remove access valve cap. (See Figure 6--3).
2. Connect the field service coupling (see Figure 6--2) to the access valve.
3. Turn the field service coupling knob clockwise, which will open the system to the gauge set.
4. To read system pressures, slightly midseat the ser­vice valve.
5. Repeat the procedure to connect the other side of the gauge set.
5. Compressor Or Filter Drier Inlet Connection
6. Valve (Frontseated)
7. Valve (Backseated)
CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set besure set is brought to suction pressure before disconnecting.
a. Removing the Manifold Gauge Set
1. While the compressor is still ON, backseat the high side service valve.
a. Attach manifold gauge set to the compressor suction
and discharge service valves. Refer to paragraph 6.2.
b. Start the unit and run in the frozen mode (controller
set below -10C (14F) for 10 to 15 minutes.
c. Check function code Cd21 (refer to paragraph 3.2.2).
The economizer solenoid valve should be open. If not, continue to run until the valve opens.
d. Frontseat the liquid line service valve. Place start-
stop switch in the OFF position when the suction reaches a positive pressure of 0.1 bar (1.4 psig).
e. Frontseat the suction and discharge service valves.
The refrigerant will be trapped between the compres­sor discharge service valves and the liquid line valve.
f. Before opening up any part of the system, a slight
positive pressure shouldbe indicated on the pressure gauge. Remove power from the unit before opening any part of the system. If a vacuum is indicated, emit refrigerant by cracking the liquid line valve momen­tarily to build up a slight positive pressure.
g. When opening up the refrigerant system, certain
parts may frost. Allow the part to warm to ambient temperature before dismantling. This avoids internal condensation which puts moisture in the system.
h. After repairs have been made, be sure to perform a
refrigerant leak check (refer to paragraph 6.3.3), and evacuate and dehydrate the low side (refer to paragraph 6.3.4).
i. Check refrigerant charge (refer to paragraph 6.3.5).
6--2T-340
Page 74
6.3.3 Refrigerant Leak Checking
DANGER
Never use air for leak testing. It has been de­termined that pressurized, mixtures of re­frigerant and air can undergo combustion when exposed to an ignition source.
1
2
3
4
5
a. The recommended procedure for finding leaks in a
system is with a R-134a electronic leak detector. Testing joints with soapsuds is satisfactory only for locating large leaks.
b. If the system is without refrigerant, charge the system
with refrigerant 134a to build up pressure between 2.1 to 3.5 bar (30.5 to 50.8 psig). To ensure complete pressurization of the system, refrigerant should be charged at the compressor suction valve and the liq­uid line service valve. Remove refrigerant cylinder and leak-check all connections.
NOTE
Only refrigerant 134a should be used to pres­surize the system. Any other gas or vapor will contaminate the system, which will require additional purging and evacuation of the sys­tem.
c. If required, remove refrigerant using a refrigerant
recovery system and repair any leaks. Check for leaks.
d. Evacuate and dehydrate the unit. (Refer to paragraph
6.3.4.)
e. Charge unit per paragraph 6.3.5.
6.3.4 Evacuation and Dehydration
General
Moisture is detrimental to refrigeration syst ems. The presence of moisture in a refrigeration system can have many undesirable effects. The most common are cop­per plating, acid sludge formation, “freezing-up” of metering devices by free water , and formation of acids, resulting in metal corrosion.
Preparation
a. Evacuate and dehydrate only after pressure leak test.
b. Essential tools to properly evacuate and dehydrate
any system include a vacuum pump (8 m
3
/hr = 5 cfm volume displacement) and an electronic vacuum gauge. (The pump is available from Carrier Trans­icold, part number 07-00176-11.)
c. If possible, keep the ambient temperature above
15.6C (60F) to speed evaporation of moisture. If the ambient temperature is lower than 15.6C (60F), ice might form before moisture removal is complete. Heat lamps or alternate sources of heat may be used to raise the system temperature.
d. Additional time may be saved during a complete sys-
tem pump down by replacing the filter drier with asec­tion of copper tubing and the appropriate fittings. Installation of a new drier may be performed during the charging procedure.
D
S
10
8
6
9
7
1. Liquid Service Connection
2. Receiver or Water Cooled Condenser
3. Compressor
4. Discharge Service Connection
5. Suction Service Connection
6. Vacuum Pump
7. Electronic Vacuum Gauge
8. Manifold Gauge Set
9. Refrigerant Cylinder
10. Reclaimer
Figure 6--4 Refrigeration System Service
Connections
Procedure - Complete System
NOTE
Refer to Partial System procedure for informa­tion pertaining to partial system evacuation and dehydration.
a. Remove all refrigerant using a refrigerant recovery
system.
b. The recommended method to evacuate and dehy-
drate the system is to connect evacuation hoses at the compressor suction and liquid line service valve (see Figure 6--4). Be sure the service hoses are suited for evacuation purposes.
c. Test the evacuation setup for leaks by backseating
the unit service valves and drawing a deep vacuum with the vacuum pump and gauge valves open. Shut off the pump and check to see if the vacuum holds.
Repair leaks if necessary. d. Midseat the refrigerant syst em service valves. e. Open the vacuum pump and electronic vacuum
gauge valves, if they are not already open. Start the
vacuum pump. Evacuate unit until the electronic vac-
uum gauge indicates 2000 microns. Close the elec-
tronic vacuum gauge and vacuum pump valves. Shut
off the vacuum pump. W ait a few minutes to be sure
the vacuum holds. f. Break the vacuum with clean dry refrigerant 134a gas.
Raise system pressure to roughly 0.14 bar (2 psig),
monitoring it with the compound gauge. g. Remove refrigerant using a refrigerant recovery sys-
tem.
6--3
T-340
Page 75
h. Repeat steps e. and f. one time.
i. Remove the copper tubing and change the filter drier.
Evacuate unit to 500 microns. Close the electronic vacuum gauge and vacuum pump valves. Shut off the vacuum pump. Wait five minutes to see if vacuum holds. This procedure checks for residual moisture and/or leaks.
j. With a vacuum still in the unit, the refrigerant charge
may be drawn into the system from a refrigerant con­tainer on weight scales.
Procedure - Partial System
a. If refrigerant charge has been removed from the low
side only, evacuate the low side by connecting the evacuation set-up at the compressor suction valve and the liquid service valve but leave the service valves frontseated until evacuation is completed.
b. Once evacuation has been completed and the pump
has been isolated, fully backseat the service valves to isolate the service connections and then continue with checking and, if required, adding refrigerant in accordance with normal procedures.
6.3.5 Refrigerant Charge
Checking the Refrigerant Charge
NOTE
Use a refrigerant recovery system whenever removing refrigerant. When working with refrig­erants you must comply with all local govern­ment environmental laws. In the U.S.A., refer to EPA Section 608.
NOTE
It may be necessary to finish charging unit through suction service valve in gas form, due to pressure rise in high side of the system.
d. Backseat manual liquid line valve (to close off gauge
port). Close liquid valve on cylinder.
e. Start unit in cooling mode. Run for approximately
10 minutes and check the refrigerant charge.
Adding Refrigerant to System (Partial Charge)
a. Examine the unit refrigerant system for any evidence
of leaks. Repair as necessary. (Refer to paragraph
6.3.3.).
b. Maintain the conditions outlined in paragraph 6.3.5.
c. Fully backseat the suction service valve and remove
the service port cap.
d. Connect charging line between suction service valve
port and cylinder of refrigerant R-134a. Open VAPOR valve.
e. Partially frontseat (turn clockwise) the suction service
valve and slowly add charge until the refrigerant appears at the proper level. Be careful not to frontseat the suction valve fully, if the compressor is operated in a vacuum, internal damage may result.

6.4 COMPRESSOR

a. Connect the gauge manifold to the compressor dis-
charge and suction service valves. For units operat­ing on a water cooled condenser, change over to air cooled operation.
b. Bring the container temperature to approximately 0C
(32F) or below. Then set the controller set point to
-25C (-13F).
c. Partially block the condenser coil inlet air. Increase the
area blocked until the compressor discharge pressure is raised to approximately 12.8 bar (185 psig).
d. On units equipped with a receiver, the level should be
between the glasses. On units equipped with a water­cooled condenser, the level should be at the center of the glass. If the refrigerant level is not correct, contin­ue with the following paragraphs to add or remove re­frigerant as required.
Adding Refrigerant to System (Full Charge)
a. Evacuate unit and leave in deep vacuum. (Refer to
paragraph 6.3.4.)
b. Place cylinder of R-134a on scale and connect charg-
ing line from cylinder to liquid line valve. Purge charg­ing line at liquid line valve and then note weight of cyl­inder and refrigerant.
c. Open liquid valve on cylinder. Open liquid line valve
half-way and allow the liquid refrigerant to flow into the unit until the correct weight of refrigerant (refer to paragraph 2.2) has been added as indicated by scales.
WARNING
Make sure power to the unit is OFF and power plug disconnected before replacing the compressor.
WARNING
Before disassembly of the compressor, be sure to relieve the internal pressure very carefully by slightly loosening the cou­plings to break the seal.
CAUTION
The scroll compressor achieves low suc­tion pressure very quickly. Do not use the compressor to evacuate the system below 0 psig. Never operate the compressor with the suction or discharge service valves closed (frontseated). Internal damage will result from operating the compressor in a deep vacuum.
6--4T-340
Page 76
6.4.1 Removal and Replacement of Compressor
a. Turn the unit ON and run it in full cool mode for 10
minutes.
NOTE
If the compressor is not operational, front--seat the suction and discharge service valves and go to step f. below.
p. Torque the four base--mounting screws to 6.2 mkg
(45 ft--lbs).
3
4
2
1
5
b. Frontseat the manual liquid line valve and allow the
unit to pull--down to 0.1 kg/cm
2
(1 psig).
c. Turn the unit start--stop switch (ST) and unit circuit
breaker (CB-- 1) OFF, and disconnect power to the unit.
d. Frontseat the discharge and suction service valves.
e. Remove all remaining refrigerant from the com-
pressor using a refrigerant recovery system.
f. Remove the compressor terminal cover, disconnect
the ground wire and pull the cable plug from the com­pressor terminals. Install the terminal cover back after removing the power cable.
NOTE
Inspect the power cable (plug) terminals to en­sure they are not deformed or have any signs of heat or arcing. If any damage is noted, replace the power cable.
g. Remove the Rotalock fittings from the suction and
discharge service connections, and uncouple the unloader and economizer lines from the com­pressor.
h. Cut the dome temperature sensor wires. The re-
placement compressor comes with a dome temper­ature sensor already assembled.
i. Remove and save the compressor base mounting
bolts. Discard the 4 top resilient mounts and wash­ers.
j. Remove (slide out) the old compressor from the unit.
k. Inspect compressor base plate for wear. Replace, if
necessary.
l. Wire tie the compressor base plate to the com-
pressor, and slide the new compressor into the unit. Refer to Figure 6--5.
NOTE
DO NOT add any oil to the replacement com­pressor. Replacement compressor is shipped with full oil charge of 60 oz.
m. Cut and discard the wire ties used to hold the base
plate to the compressor.
n. Place the new SST washers on each side of the resi-
lient mounts, and the new Mylar washer on the bot­tom of it as shown in Figure 6--5. Install the four base--mounting screws loosely.
o. Place the new Teflon seals at the compressor suc-
tion and discharge ports as well as the O--rings at the unloader and economizer line connection ports. Hand tighten all four connections.
11
2
12
6
7
8
7
9
10
1. Compressor
2. Teflon Seal for Valve Connection (2)
3. O--Ring (Unloader Connection)
4. Compressor Dis-­charge Temperature Sensor
5. O--Ring (Economizer Connection)
7. SST Washers
8. Resilient Mount
9. Mylar Washers
10. Wire Ties 1 1. Power Cable Gasket
12. Ground Connection Screw
13. Power Cable Lubricant -- Krytox (Not Shown)
6. Base Mounting Screw
Figure 6--5 Compressor Kit
q. Torque the compressor ports / connections to:
Service Valve / Connection
Suction and Discharge Rotalocks
Torque Value
108.5 to 135.5 Nm (80to100ft--lbs.)
Unloader connection 24.5to27Nm
(18to20ft--lbs.)
Economized connection 32.5to35Nm
(24to26ft--lbs.)
r. Connect (butt--splice and heat shrink) the new com-
pressor dome temperature sensor with the old sensor wires removed in step 9. Wire--tie any loose wiring as appropriate.
s. Evacuate the compressor to 1000 microns if the unit
was pumped down before the replaced compressor was removed. Otherwise, evacuate the complete unit and charge it with R--134a refrigerant (see Sec­tions 6.3.4 and 6.3.5).
t. Open the compressor terminal cover and connect
the compressor power cable following the steps be­low:
u. Liberally coat the orange gasket surfaces with the
Krytox lubricant.
v. Install the orange gasket part onto the compressor
fusite with the grooved or threaded side out. Ensure that the gasket is seated onto the fusite base.
6--5
T-340
Page 77
w. Coat the inside of the power plug (female) connector
pins with the Krytox lubricant, and insert the plug onto the compressor terminal connections. Make sure, the orange gasket has bottomed out onto the fusite and it fits securely onto the terminal pins while fully inserted into the orange plug.
x. Connect the green ground wire to the grounding tab
located inside the terminal box of the compressor us­ing the self--tapping grounding screw. Close the compressor terminal box using the terminal cover re­moved in step 20 above.
y. Backseat all service valves, connect the power to the
unit and run it for at least 20 minutes.
z. Perform a leak check of the system.

6.5 HIGH PRESSURE SWITCH

6.5.1 Checking High Pressure Switch
f. Open cylinder valve. Slowly close bleed-off valve to
increase pressure on switch. The switch should open at a static pressure up to 25 kg/cm light is used, light will go out. If an ohmmeter is used, the meter will indicate open circuit.
g. Slowly open bleed-off valve to decrease the pressure.
The switch should close at 18 kg/cm
6.5.2 Replacing High Pressure Switch
a. Remove the refrigerant charge.
b. Disconnect wiring from defective switch. The high
pressure switch is located on the discharge connec­tion or line and is removed by turning counterclock­wise.
c. Install a new high pressure switch after verifying
switch settings.
d. Evacuate, dehydrate and recharge system.
e. Start unit, verify refrigeration charge and oil level.
2
(350 psig). If a
2
(250 psig).
WARNING
Do not use a nitrogen cylinder without a pressure regulator. Do not use oxygen in or near a refrigeration system as an explosion may occur.
NOTE
The high pressure switch is non-adjustable.
a. Remove switch as outlined in paragraph 6.5.2.
b. Connect ohmmeter or continuity light across switch
terminals. Ohm meter will indicate no resistance or continuity light will be illuminated if the switch closed after relieving compressor pressure.
c. Connect hose to a cylinder of dry nitrogen. (See
Figure 6--6.
1
2
4
5

6.6 CONDENSER COIL

The condenser consists of a series of parallel copper tubes expanded into copper fins. The condenser coil must be cleaned with fresh water or steam so the air flow is not restricted. To replace the coil, do the following:
WARNING
Do not open the condenser fan grille before turning power OFF and disconnecting power plug.
a. Using a refrigerant reclaim system, remove the refrig-
erant charge.
b. Remove the condenser coil guard.
c. Unsolder discharge line and remove the line to the
receiver or water-cooled condenser.
d. Remove coil mounting hardware and remove the coil.
e. Install replacement coil and solder connections.
f. Leak-check the coil connections per paragraph para-
graph 6.3.3. Evacuate the unit then charge the unit with refrigerant.

6.7 CONDENSER FAN AND MOTOR ASSEMBLY

3
1. Cylinder Valve and Gauge
2. Pressure Regulator
3. Nitrogen Cylinder
Figure 6--6 High Pressure Switch Testing
d. Set nitrogen pressure regulator at 26.4 kg/cm
psig) with bleed-off valve closed.
e. Close valve on cylinder and open bleed-off valve.
6
4. Pressure Gauge (0 to 36 kg/cm 0 to 400 psig)
5. Bleed-Off Valve
6. 1/4 inch Connection
2
=
2
(375
WARNING
Do not open condenser fan grille before turning power OFF and disconnecting power plug.
The condenser fan rotates counter-clockwise (viewed from front of unit), pulls air through the the condenser coil, and discharges horizontally through the front of the unit. To replace motor assembly:
a. Open condenser fan screen guard.
b. Loosen two square head set screws on fan. (Thread
sealer has been applied to set screws at installation.)
c. Disconnect wiring connector.
6--6T-340
Page 78
CAUTION
Take necessary steps (place plywood over coil or use sling on motor) to prevent motor from falling into condenser coil.
2. Oakite Composition No. 32, available as a liquid in cases, each containing 3.785 liters (4 U.S. gallon) bottles and also in carboys of 52.6 kg (116 lbs) net.
3. Fresh clean water.
4. Acid proof pump and containers or bottles with rubber hose.
d. Remove motor mounting hardware and replace the
motor. It is recommended that new locknuts be used
when replacing motor. e. Connect the wiring connector.
f. Install fan loosely on motor shaft (hub side in). DO
NOT USE FORCE. If necessary, tap the hub only, not
the hub nuts or bolts. Install venturi. Apply “Loctite H”
to fan set screws. Adjust fan within venturi so that the
outer edge of the fan is within 2.0 +/- 0.07 mm
(0.08” +/- 0.03”) from the outside of the orifice open-
ing. Spin fan by hand to check clearance. g. Close and secure condenser fan screen guard.
6.8 W ATER--COOLED CONDENSER CLEANING
The water-cooled condenser is of the shell and coil type with water circulating through the cupro-nickel coil. The refrigerant vapor is admitted to the shell side and is con­densed on the outer surface of the coil.
Rust, scale and slime on the water-cooling surfaces inside of the coil interfere with the transfer of heat, reduce system capacity, cause higher head pressures and increase the load on the system.
By checking the leaving water temperature and the actual condensing temperature, it can be determined if the condenser coil is becoming dirty. A larger than nor­mal difference between leaving condensing water tem­perature and actual condensing temperature, coupled with a small difference in temperature of entering and leaving condensing water, is an indication of a dirty con­densing coil.
To find the approximate condensing temperature, with the unit running in the cooling mode, install a gauge 0 to
36.2 kg/cm
2
(0 to 500 psig) on the compressor dis-
charge service valve. Example: Discharge pressure is 10.3 kg/cm
(146.4 psig). Referring to Table 6--4 (R-134a pressure/ temperature chart), the 10.3 kg/cm
2
(146.4 psig) value
converts to 43C (110F).
If the water-cooled condenser is dirty, it may be cleaned and de-scaled by the following procedure:
a. Turn unit off and disconnect main power . b. Disconnect water pressure switch tubing by loosen-
ing the two flare nuts. Install one-quarter inch flare
cap on water-cooled condenser inlet tube (replaces
tubing flare nut). De-scale tubing if necessary.
What You Will Need:
1. Oakite Composition No. 22, available as a powder in
68 kg (150 lb) and 136 kg (300 lb) containers.
NOTE
When Oakite Compound No. 32 is used for the first time, the local Oakite Technical Service representative should be called in for suggestions in planning the procedure. The representative will advise the reader on how to do the work with a minimum dismantling of equipment: how to estimate the time and amount of compound required; how to prepare the solution; how to control and conclude the de-scaling operation by rinsing and neutralizing equipment before putting it back into service. The representative’s knowledge of metals, types of scale, water conditions and de-scaling techniques will be highly useful.
Summary of Procedure:
1. Drain water from condenser tubing circuit.
2. Clean water tubes with Oakite No. 22 to remove mud and slime.
3. Flush.
4. De-scale water tubes with Oakite No. 32 to remove scale.
5. Flush.
6. Neutralize.
7. Flush.
8. Put unit back in service under normal load andcheck head (discharge) pressure.
Detailed Procedure:
1. Drain and flush the water circuit of the condenser
2
coil. If scale on the tube inner surfaces is accompa­nied by slime, a thorough cleaning is necessary before de-scaling process can be accomplished.
2. To remove slime or mud, use Oakite Composition No. 22. Mixed 170 grams (6 ounces) per 3.785 liters (1 U.S. gallon) of water. Warm this solution and circu­late through the tubes until all slime and mud has been removed.
3. After cleaning, flush tubes thoroughly with fresh clean water.
4. Prepare a 15% by volume solution for de-scaling, by diluting Oakite Compound No. 32 with water . This is accomplished by slowly adding 0.47 liter (1 U.S. pint) of the acid (Oakite No. 32) to 2.8 liters (3 U.S. quarts) of water.
6--7
T-340
Page 79
WARNING
7
Oakite No. 32 is an acid. Be sure that the acid is slowly added to the water. DO NOT PUT WATER INTO THE ACID - thiswill cause spattering and excessive heat.
WARNING
Wear rubber gloves and wash the solution from the skin immediately if accidental con­tact occurs. Do not allow the solution to splash onto concrete.
5. Fill the tubes with this solution by filling from the bot­tom. See Figure 6--7.
NOTE
It is important to provide a vent at the top for escaping gas.
6. Allow the Oakite No. 32 solution to soak in the tube coils for several hours, periodically pump-circulating it with an acid-proof pump.
An alternate method may be used whereby a pail (see Figure 6--8) filled with the solution and attached to the coils by a hose can serve the same purpose by filling and draining. The solution must contact the scale at every point for thorough de-scaling. Air pockets in the solution should be avoided by regu­larly opening the vent to release gas. Keep flames
away from the vent gases.
6
4
3
2
1
1. Pump support
2. Tank
3. Suction
4. Pump
5. Priming Connection (Centrifugal pump 50 gpm at 35’ head)
6. Globe valves
Figure 6--7 Water-Cooled Condenser Cleaning -
8. When de-scaling is complete, drain the solution and flush thoroughly with water.
9. Following the water flush, circulate a 56.7 gram (2 ounce) per 3.785 liter (1 U.S. gallon) solution of Oakite No. 22 thru the tubes to neutralize. Drain this solution.
10.Flush the tubes thoroughly with fresh water.
If the condenser cooling water is not beingused as drinking water or is not re-circulated in a closed or tower system, neutralizing is not nec­essary.
5
11
12
7. Vent
8. Close vent pipe valve when pump is running
9. Condenser
10. Remove water regulating valve
1 1. Return
12. Fine mesh screen
Forced Circulation
NOTE
8
9
10
7. The time required for de-scaling will vary, depending upon the extent of the deposits. One way to deter­mine when de-scaling has been completed is to titrate the solution periodically, using titrating equip­ment provided free by the Oakite Technical Service representative. As scale is being dissolved, titrate readings will indicate that the Oakite No. 32 solution is losing strength. When the reading remains constant for a reasonable time, this is an indication that scale has been dissolved.
1 1.Put the unit back in service and operate under nor-
mal load. Check the head pressure. If normal, a thor­ough de-scaling has been achieved.
What You Can Do For Further Help:
Contact the Engineering and Service Department of the OAKITE PRODUCTS CO., 675 Central Avenue, New Providence, NJ 07974 U.S.A. (or visit www.oakite.com) for the name and address of the service representative in your area.
6--8T-340
Page 80
1
5
2
4
3’ to 4’
3
1. Fill condenser with cleaning solution. Do not add solution more rapidly than vent can
2. Approximately 5’
3. Condenser
4. Vent pipe
5. 1” pipe exhaust gases caused by chemical action.
Figure 6--8 Water-Cooled Condenser Cleaning -
Gravity Circulation

6.9 FILTER DRIER

On units equipped with a water-cooled condenser, if the sight glass appears to be flashing or bubbles are constantly moving through the sight glass, the unit may have a low refrigerant charge or the filter drier could be partially plugged.
a. To check filter drier,
1. Test for a restricted or plugged filter drier by feeling the liquid line inlet and outlet connections of the drier cartridge. If the outlet side feels cooler than the inlet side, then the filter drier should be changed.
2. Check the moisture-liquid indicator if the indicator shows a high level of moisture, the filter drier should be replaced.
b. To replace filter drier,
1. Pump down the unit (refer to paragraph 6.3.2). Eva­cuate if unit is not equipped with service valves. Then replace filter drier.
2. Evacuate the low side in accordance with paragraph 6.3.4.
3. After unit is in operation, inspect for moisture in sys­tem and check charge.
6.10 EVAPORATOR COIL AND HEATER
ASSEMBLY
The evaporator section, including the coil, should be cleaned regularly. The preferred cleaning fluid is fresh water or steam. Another recommended cleaner is
Oakite 202 or similar, following manufacturer’s instruc-
tions.
The two drain pan hoses are routed behind the con­denser fan motor and compressor. The drain pan line(s) must be open to ensure adequate drainage.
6.10.1 Evaporator Coil Replacement
a. Pump unit down. (Refer to paragraph 6.3.2.) Evacua-
te if unit is not equipped with service valves. Refer to paragraph 6.3.4.
b. With power OFF and power plug removed, remove
the screws securing the panel covering the evapora­tor section (upper panel).
c. Disconnect the defrost heater wiring. d. Remove the mounting hardware from the coil.
e. Unsolder the two coil connections, oneat the distribu-
tor and the other at the coil header.
f. Disconnect the defrost temperature sensor (see
Figure 2--2) from the coil.
g. Remove middle coil support.
h. After defective coil is removed from unit, remove
defrost heaters and install on replacement coil.
i. Install coil assembly by reversing above steps.
j. Leak check connections. Evacuate and add refriger-
ant charge.
6.10.2 Evaporator Heater Removal and Replacement
The heaters are wired directly back to the contactor and if a heater failure occurs during a trip, the heater set con­taining that heater may be disconnected at the contac­tor.
The next pre-trip will detect that a heater set has been disconnected and indicate that the failed heater should be replaced. To remove a heater, do the following:
a. Before servicing unit, make sure the unit circuit break-
ers (CB-1 and CB-2) and the start-stop switch (ST) are in the OFF position, and that the power plug is dis-
connected. b. Remove the upper back panel.
c. Determine which heater(s) need replacing by check-
ing resistance of each heater set. Refer to paragraph
2.3 for heater resistance values. Once the set con-
taining the failed heater is determined, cut the splice
connection and retest to determine the actual failed
heater(s).
d. Remove hold-down clamp securing heater(s) to coil. e. Lift the bent end of the heater (with the opposite end
down and away from coil). Move heater to the side
enough to clear the heater end support and remove. To replace a heater, do steps a through e in reverse.
Optional 5+1 Heater Arrangement Heater Removal
and Replacement
Complete steps a. through e. noted above, then re-
move straight and Omega heaters:
f. To remove straight heater,
1. Locate holding clips positioned at the ends of the
heater element.
2. Rotate clips toward the center of the container unit.
6--9
T-340
Page 81
3. Lift heater slightly up and out to remove.
6.11.1 Replacing The Evaporator Fan Assembly
g. To remove Omega heater (see Figure 6--9)
1. Remove the two tube clamps located near the top of the heater element.
2. Locate holding clips positioned at the bottom of the heater element and rotate slightly toward the center of the container unit.
3. Carefully pull heater out to remove.
1
1. Omega Heater
2. Tube Clamps (2)
3. Holding Clips (2)
Figure 6--9 5+1 Heater Arrangement -- Omega
Heater

6.11 EVAPORATOR FAN AND MOTOR ASSEMBLY

The evaporator fans circulate air throughout the con­tainer by pulling air in the top of the unit. The air is forced through the evaporator coil where it is either heated or cooled and then discharged out the bottom of the refrig­eration unit into the container. The fan motor bearings are factory lubricated and do not require additional grease.
2
3
WARNING
Always turn OFF the unit circuit breakers (CB-1 and CB-2) and disconnect main power supply before working on moving parts.
a. Remove upper access panel (see Figure 2--2) by
removing mounting bolts and TIR locking device. Reach inside of unit and remove the Ty-Rap securing the wire harness loop. Disconnect the connector by twisting to unlock and pulling to separate.
b. Loosen four 1/4-20 clamp bolts that are located on the
underside of the fan deck at the sides of the of the fan assembly. Slide the loosened clamps back from the fan assembly.
c. Slide the fan assembly out from the unit and place on
asturdyworksurface.
6.11.2 Disassemble The Evaporator Fan Assembly
a. Attach a spanner wrench to the two 1/4-20 holes
located in the fan hub. Loosen the 5/8-18 shaft nut by holding the spanner wrench stationary and turning the 5/8-18 nut counter-clockwise (see Figure 6--10).
b. Remove the spanner wrench. Use a universal wheel
puller and remove the fan from the shaft. Remove the washers and key .
c. Remove the four 1/4-20 x 3/4 long bolts that are
located under the fan that support the motor and sta­tor housing. Remove the motor and plastic spacer.
6.11.3 Assemble The Evaporator Fan Assembly
a. Assemble the motor and plastic spacer onto the stator.
NOTE
When removing the black nylon evaporator fan blade, care must be taken to assure that the blade is not damaged. In the past, it was a com­mon practice to insert a screwdriver between the fan blades to keep it from turning. This prac­tice can no longer be used, as the blade is made up of a material that will be damaged. It is rec­ommended that an impact wrench be used when removing the blade. Do not use the im­pact wrench when reinstalling, as galling of the stainless steel shaft can occur.
b. Apply Loctite to the 1/4-20 x 3/4 long bolts and torque
to 0.81 mkg (70 inch-pounds).
6--10T-340
Page 82
c. Place one 5/8 flat washer on the shoulder of the fan
motor shaft. Insert the key in the keyway and lubricate the fan motor shaft and threads with a graphite-oil solution (such as Never-seez).
d. Install the fan onto the motor shaft. Place one 5/8 flat
washer with a 5/8-18 locknut onto the motor shaft and torque to 40 foot-pounds.
3
2
2
4
1
5
6
1. Install the air sample filter element by reversing the above steps.
6.12.2 eAutoFresh Drive System
Checking the Auto Slide
a. Checking with ohmmeter, disconnect the four pin con-
nector to the stepper motor. With a reliable digital ohmmeter, check the winding resistance. In normal ambient, the motor should have 72 to 84 ohms meas­ured on the red/green (a--b terminals) and on the white/black (c--d terminals) leads. If an infinite orzero reading occurs, check connections or replace the mo­tor. If near normal or normal reading occurs, proceed to Section 6.12.3 to check out the controller.
b. Checking with SMA--12 portable stepper drive tester
The SMA--12 portable stepper drive tester (Carrier Transicold P/N 07--00375--00) is a battery operated stepper drive which will open and close the auto slide, which allows a more thorough check of the motor.
To check operation:
1. Stop the unit, disconnect the four pin connector from the stepper drive to the stepper motor (see Figure 6--11) and attach the SMA--12 stepper drive to the connector going to the motor.
7
8
1. Stator
2. Flat washer, 5/8
3. Locknut, 5/8-18
4. Impeller Fan
5. Screw, 1/4
6. Flat washer, 1/4
7. Mylar Protector
8. Evaporator Motor
Figure 6--10 Evaporator Fan Assembly
e. Install the evaporator fan assembly in reverse order
of removal. Torque the four 1/4-20 clamp bolts to
0.81 mkg (70 inch-pounds). Connect the wiring con­nector.
f. Replace access panel making sure that panel does
not leak. Make sure that the TIR locking device is lockwired.

6.12 EAUTOFRESH SERVICE

6.12.1 eAutoFresh Air Filter
a. Removing the Air Sample Filter Element
When replacing the air sample filter element it can be accessed in two ways: through the eAutoFresh side evaporator access panel (Item 2, Figure 6--11) or through the inside of the container by lowering the upper evaporator panel
a. By hand, unscrew and remove the filter cup from the
bottom of the air sample filter assembly.
b. Remove the filter element from the filter assembly.
b. Replacing the Air Sample Filter Element
1
2
1. Stepper Motor Drive (AF)
2. Stepper Motor (AF)
Figure 6--11 Stepper Components
2. Set the SMA--12 pulse per second (PPS) to one PPS and either open or close valve. Each LED should light sequentially until all four are lit. Any LED failing to light indicates an open on that leg which indicates a poor connection or an open coil. Repair or replace as required to achieve proper operation.
3. Set the step rate to 200 PPS on the SMA--12. Press open or close while watching slide mechanism for movement, this is an indication that the motor is work­ing.
4. If the slide moves in the above procedure but fails to move when connected in the unit (refer to “Checking the Drive Module” in the section that follows.)
Checking the Drive Module
a. Turn unit OFF. b. Disconnect the four pin connector to the motor. c. With voltmeterset to read 24volts AC, attach the pos-
itive lead to the drive module outlet pin A (wire 1A) of the four pin connector and the negative lead to the B pin(wire1B).
d. Turn ON unit, and watch the volt meter. After a short
delay, the reading should rise to approximately 12 volts.
6--11
T-340
Page 83
e. Repeat for pins C and D (wires 2 A and 2 B).
f. If only one set of pins reads a voltage, check connec-
tions and retest.
Controller Connector (EC)
Drive Module Connector (SD)
g. If the retest reads out the same, the drive module or
controller is faulty.
h. If no voltage is present in any step, the output from the
controller to the drive module may be faulty, and will require checking the connections and wires from the controller to the drive module. Refer to section 6.12.3
i. To replace the drive module, disconnect all connect-
ors, unscrew from mounting, and replace with a NEW drive module in reverse order.
6.12.3 Checking the Controller
a. Turn the unit OFF.
b. Disconnect the six pin connector to the stepper drive
from the controller.
c. With the voltmeter set to read 50 volts DC, attach the
positive lead to outlet pin A of the six pin connector, and the negative lead to pin B or TP--9 of the control­ler.
d. Turn ON the unit for 40 seconds, and watch the volt-
meter. There should be approximately 24 to 32 VDC shownonpinA.
e. There should be zero volts on pin B.
f. After a short delay, the reading should rise to approx-
imately 24 to 32 VDC on pin E.
g. Pins C and D will have zero to 5 volts transistor logic
(TTL) signals present, however, this can only be checked with the connector assembled as this is an open collector type circuit.
By checking the outputs on A, B and E it can be verified that the controller is supplying power to the drive module. To be thorough, and if it is desired, the signals on pins C and D can be checked as follows:
1. Install a jumper assembly (Carrier part number 07--00408--00) to connect the drive module and con­troller connectors as shown in Figure 6--12.
2. Connect the positive lead of the voltmeter to test con­nector socket C and negative lead to socket B, and run as before by resetting unit.
3. Repeat for sockets D and B.
A B C D
E
Test
Connector
Figure 6--12 Jumper Assembly
There should be approximately five volts DC on sockets “C” and “D” (S1 and S2) when measured as above. If not the connections or controller is faulty. If any of these pins are not consistent, the connections or controller is suspect. Check and replace as required.
6.12.4 eAutoFresh Drive System
To replace the drive motor assembly, do the following:
a. Remove bolts holding eAutoFresh Panel (3,
Figure 6--13) to the front of the unit. Reach in and cut tie wrap (2) and disconnect motor connector (1). Bring panel to work area.
b. Remove four screws (12) fastening the grille (11). c. Remove six screws (9) fastening the rails (6 and 7),
the slide plate (8) and the gasket plate (10). Set com­ponents aside for reassembly.
d. Remove the four screws (5) fastening the motor cup
(4) to the panel. Cut sealer on outside and inside of motor cup assembly. Push out the motor cup as­semble from the rear of the panel.
e. Mount replacement motor cup assembly in the panel
using original screws. Torque screws to 0.29 mkg (25 +/-- 1 Inch pounds)
f. Reapply sealer to inside and outside of motor cup as-
sembly.
g. Mount upper & lower rails, slide plate and gasket plate
using original hardware. Apply thread sealant and torque screws to 0.29 mkg (25 +/-- 1 Inch pounds)
h. Mount grille assembly using original hardware. Apply
thread sealant and torque screws to 0.29 mkg (25 +/-­1 Inch pounds)
i. Carry out functional test. Refer to section 4.4.4 step
Jumper
A B C D
E
c.
6--12T-340
Page 84
1
2
3
5
1
7
6
4
98
1110
12
1. Connector
2. Tie Wrap
3. eAutoFresh Panel
4. Cup, Motor
5. Motor Cup Screws
6. Rail, Top
7. Rail, Bottom
8. Plate, Slide
9. Rail Screws
10. Plate, Gasket
11. Grille
12. Grill Screws
Figure 6--13 Motor Cup Replacement
6--13
T-340
Page 85

6.13 ELECTRONIC EXPANSION VALVE

The electronic expansion valve (EEV) is an automatic device which maintains required superheat of the refrig­erant gas leaving the evaporator. The valve functions are: (a) automatic response of refrigerant flow to match the evaporator load and (b) prevention of liquid refriger­ant entering the compressor. Unless the valve is defec­tive, it seldom requires any maintenance. See Figure 6--14.
1
ensure that coil boot is properly fitted over valve body. See Figure 6--14.
3. Replace filter drier.
4. Evacuate to 500 microns by placing vacuum pump on liquid line and suction service valve.
5. Open liquid line service valve and check refrigerant level.
6. Check superheat. (Refer to Section 2.2)
7. Check unit operation by running Pre-- trip (Refer to Section 3.7).

6.14 ECONOMIZER EXPANSION VALVE

2
3
FLOW DIRECTION
1. Coil Boot
2. Coil
3. Electronic Expansion Valve
Figure 6 --14 Electronic Expansion Valve
6.13.1 Replacing Electronic Expansion Valve and Screen
a. Removing an EEV
1. Pump down the compressor (refer to paragraph
6.3.2) and frontseat both suction and discharge valves.
2. Turn unit power off and remove power from the unit.
3. Remove coil.
4. VALVE REMOVAL: The preferred method of remov-
ing the valve is to cut the connection between the brazed section and the valve, using a small tube cut­ter. Remove valve.
Alternately, use a wet rag to keep valve cool. Heat in­let and outlet connections to valve body and remove valve.
5. Clean the valve stem with mild cleaner, if necessary.
b. Installing an EEV
1. Reverse steps 1 through 4 above to install a new
valve. Install valve and screen with cone of screen pointing into liquid line at inlet to the valve.
2. During installation, make sure the EEV coil is
snapped down fully,and the coil retention tab is prop­erly seated in one of the valve body dimples. Also,
The economizer expansion valve can be found in Figure 2--4 (Item 15). The economizer expansion valve is an automatic device that maintains constant super­heat of the refrigerant gas leaving at the point of bulb at­tachment, regardless of suction pressure.
Unless the valve is defective, it seldom requires main­tenance other than periodic inspection to ensure that the thermal bulb is tightly secured to the suction line and wrapped with insulating compound.
6.14.1 Valve Replacement
a. Removing an Expansion V alve
NOTE
The economizer expansion valve is a hermetic valve and does not have adjustable superheat (See Figure 6--15).
1
2
1. Inlet
2. Outlet
Figure 6--15 Economizer Expansion Valve
1. Pump down the compressor (refer to paragraph
6.3.2) and frontseat both suction and discharge valves. Evacuate if unit is not equipped with service valves. Refer to paragraph 6.4.4.
2. Turn unit power off and remove power from the unit.
3. Remove cushion clamps located on the inlet and out­let lines.
4. Remove insulation (Presstite) from expansion valve bulb.
5. Unstrap the bulb, located on the economizer line.
6. VALVE REMOVAL: The preferred method of remov­ing the valve is to cut the connection between the brazed section and the valve, using a small tube cut­ter. Remove valve.
6--14T-340
Page 86
Alternately, use a wet rag to keep valve cool. Heat in-
x
let and outlet connections to valve body and remove valve.
7. Clean the valve stem with mild cleaner, if necessary.
b. Installing an Expansion Valve
1. The economizer valve should be wrapped in a soaked cloth for brazing. Braze inlet connection to in­let line.
2. Braze inlet connection to inlet line.
3. Braze outlet connection to outlet line.
4. Braze outlet connection to outlet line.
5. Reinstall the cushion clamps on inlet and outlet lines.
c. Replace filter drier.
d. Evacuate to 500 microns by placing vacuum pump
on liquid line and suction service valve.
6. Check superheat (see Section 2.2).

6.15 ECONOMIZER SOLENOID VALVE

a. Removing a Solenoid Valve
1. Pump down the compressor (refer to paragraph
6.3.2) and frontseat both suction and discharge valves.
2. Turn unit power off and remove power from the unit. Disconnect leads.
3. Remove top screw and o--ring. Remove coil and save mounting hardware, seals and spacer for re­use. (See Figure 6--16).
1
2
b. Installing a Solenoid Valve
1. Install the brass spacer on the valve stem.
2. Lubricate both o--rings with silicone provided in the kit.
3. Install bottom coil o--ring on the valve stem.
4. Install the solenoid coil on the valve stem.
5. Place the top coil o--ring on the coil mounting screw and secure the coil to the valve using a torque-­wrench. Torque the screw to 25 lb--in.
6. Connect coil wires using butt--splices and heat-­shrink tubing.

6.16 DIGITAL UNLOADER VALVE

a. Removing the DUV
1. Pump down the compressor (refer to paragraph
6.3.2) and frontseat both suction and discharge valves. In the event the DUV is stuck open and com­pressor cannot pump down, remove charge.
2. Turn unit power off and remove power from the unit.
3. Loosen bolt on top of the DUV and remove coil assembly.
NOTE
There is a loose steel spacer tube between the top of the valve and the 12 VDC coil that needs to be reinstalled into the solenoid valve coil. When removing the coil, it may fall out when lif­ted from the valve body. Take care that the spacer is not lost; the valve will not function cor­rectly without it.
4. Remove clamps holding the DUV to the discharge line.
5. Loosen the nuts attaching the DUV to the top of the compressor.
3
4
5
1. Slotted Screw
2. Top Coil (small) O--ring
3. Solenoid Coil, Enclosing Tube and Body
4. Bottom Coil (large) O--ring
5. Brass Spacer
Figure 6--16 Coil Vie w of E c onom izer Solenoid
Valve (ESV)
4. VALVE REMOVAL: The preferred method of remov­ing the solenoid valve is to cut the connection between the brazed section and the valve, using a small tube cutter. Remove valve.
Alternately, heat inlet and outlet connections to valve body and remove valve. Use a wet rag to keep valve cool whenever brazing.
5. Clean the valve stem with mild cleaner, if necessary.
2
1
3
4
56
1. Sleeve
2. O--ring (hidden)
3. Screen Valve Strainer
4. Tube
5. Solenoid Valve Body
6. He
Nut, 1/2OD
Figure 6--17 View of Digital Unloader Valve (DUV)
Assembly
6. VALVE REMOVAL: The preferred method of remov­ing the solenoid valve is to cut the connection between the brazed section and the valve, using a small tube cutter. Remove valve. (See Figure 6--17).
Alternately, use a wet rag to keep valve cool. Heat outlet connection to valve body and remove valve.
6--15
T-340
Page 87
7. Examine compressor and service valves. Ensure that the o--ring is not stuck in the gland of the valve.
8. Discard the o--ring on the o--ring face seal connec­tion.
b. Installing the V alve
1. Lubricate the gland shoulder area and o--ring with re­frigerant oil.
2. Fit new valve in position and hand--tighten the o--ring nut.
3. Use a wet rag to keep valve cool while brazing. Braze DUV to service valve connection.
4. Reinstall and tighten the brackets that secure the valve body to the discharge line.
5. Torque o--ring face seal connections to 18 to 20 ft-­lbs.
6. Install the coil onto the valve body and tighten the at­tachment bolt.
NOTE
Confirm that the small spacer tube is inserted into the coil prior to attaching it to the valve body. The valve will not function correctly without it.
7. Leak check and evacuate low side or unit as applic­able. Refer to paragraph 6.3.4.
8. Open service valves.

6.17 VALVE OVERRIDE CONTROLS

Controller function code Cd41 is a configurable code that allows timed operation of the automatic valves for troubleshooting. Test sequences are provided in Table 6--1. Capacity mode (CAP) allows alignment of
the economizer solenoid valve in the standard and economized operating configurations. DUV Capacity Modulation, % Setting (PCnt) and Electronic Expansion V a lve (EEV) allows opening of the digital unloader valve and electronic expansion valve, respectively, to various percentages. If the unit is equipped with an LIV, the Liquid Valve Setting allows the LIV to be automatically controlled, or manually opened and closed.
The Override Timer (tIM) selection is also provided to enter a time period of up to five minutes, during which the override(s) are active. If the timer is active, valve override selections will take place immediately. If the timer is not active, changes will not take place for a few seconds after the timer is started. When the timer times out, override function is automatically terminated and the valves return to normal machinery control. To oper­ate the override, do the following:
a. Press the CODE SELECT key then press an AR-
ROW key until Cd41 is displayed in the left window. The right window will display a controller communica­tions code.
b. Press the ENTER key. The left display will show a test
name alternating with the test setting or time remain­ing. Use an ARROW key to scroll to the desired test. Press the ENTER key and SELCt will appear in the left display.
c. Use an ARROW key to scroll to the desired setting,
and then press the ENTER key. Selections available for each of the tests are provided in the following table.
d. If the timer is not operating, follow the above proce-
dure to display the timer. Use an ARROW key to scroll to the desired time interval and press ENTER to start the timer.
e. The above described sequence may be repeated
during the timer cycle to change to another override.
6--16T-340
Page 88
Table 6--1 Valve Override Control Displays
Left Display
Cd 41/SELCt
Controller Communications Codes
(Right Display)
tIM
(Override Timer)
PCnt
(% Setting -- DUV Capacity Modulation)
EEV
(% Setting -- Electronic Expansion Valve)
CAP
(Capacity Mode)
LIV (If Equipped)
(Liquid Injection Valve Setting)
Setting Codes (Right Display)
000(0 minutes/0 Seconds)
In 30 second increments to
500(5 minutes/ 0 seconds)
AUtO
(Normal Machinery Control)
0 3
6 10 25 50
100
AUtO
(Normal Machinery Control)
CLOSE (Closed)
0
3
6 10 25 50
100
AUtO
(Normal Control)
Std
UnLd
(Economizer = Closed)
ECOn
(Economizer = Open)
AUto
(Normal Control)
CLOSE (Closed)
OPEn (Open)
6--17
T-340
Page 89

6.18 AUTOTRANSFORMER

If the unit does not start, check the following:
a. Make sure the 460 VAC (yellow) power cable is
plugged into the receptacle (item 3, Figure 4--1) and locked in place.
b. Make sure that circuit breakers CB-1 and CB-2 are in
the “ON” position. If the circuit breakers do not hold in, check voltage supply.
c. There is no internal protector for this transformer
design, therefore, no checking of the internal protec­tor is required.
d. Using a voltmeter, and with the primary supply circuit
ON, check the primary (input) voltage (460 VAC). Next, check the secondary (output) voltage (230 VAC). The transformer is defective if output voltage is not avail­able.

6.19 CONTROLLER

6.19.1 Handling Modules
CAUTION
Do not remove wire harnesses from module unless you are grounded to the unit frame with a static safe wrist strap.
CAUTION
Unplug all module connectors before per­forming arc welding on any part of the con­tainer.
The guidelines and cautions provided herein should be followed when handling the modules. These precau­tions and procedures should be implemented when replacing a module, when doing any arc welding on the unit, or when service to the refrigeration unit requires handling and removal of a module.
a. Obtain a grounding wrist strap (Carrier Transicold
part number 07-00304-00) and a static dissipation mat (Carrier Transicold part number 07-00277-00. The wrist strap, when properly grounded, will dissi­pate any potential buildup on the body. The dissipa­tion mat will provide a static-free work surface on which to place and/or service the modules.
b. Disconnect and secure power to the unit.
c. Place strap on wrist and attach the ground end to any
exposed unpainted metal area on the refrigeration unit frame (bolts, screws, etc.).
d. Carefully remove the module. Do not touch any of the
electrical connections if possible. Place the module on the static mat.
e. The strap should be worn during any service work on
a module, even when it is placed on the mat.
6.19.2 Controller Troubleshooting
A group of test points (TP, see Figure 6--18) are pro­vided on the controller for troubleshooting electrical cir­cuits (see schematic diagram, section 7). A description of the test points follows:
NOTE
Use a digital voltmeter to measure AC voltage between TP’s and ground (TP9), except for TP8.
TP1
This test point is not used in this application.
TP2
This test point enables the user to check if the high pres­sure switch (HPS) is open or closed.
TP3
This test point enables the user to check if the water pressure switch (WP) contact is open or closed.
TP 4
This test point enables the user to check if the internal protector for the condenser fan motor (IP-CM) is open or closed.
TP 5
This test point enables the user to check if the internal protectors for the evaporator fan motors (IP-EM1 or IP­EM2) are open or closed.
TP 6 (IF EQUIPPED)
This test point enables the user to check if the controller liquid injection valve relay (TQ) is open or closed.
TP 7
This test point enables the user to check if the controller economizer solenoid valve relay (TS) is open or closed.
TP 8
This test point is not used in this application.
TP 9
This test point is the chassis (unit frame) ground con­nection.
TP 10
This test point enables the user to check if the heat ter­mination thermostat (HTT) contact is open or closed.
6--18T-340
Page 90
12
1. Controller Software Programming Port
2. Mounting Screw
3. Controller
4. Test Points
Figure 6--18 Controller Se ction of the Control Box
6.19.3 Controller Programming Procedure
To load new software into the module, the programming card is inserted into the programming/software port.
3
4
CAUTION
The unit must be OFF whenever a program­ming card is inserted or removed from the controller programming port.
1. Turn unit OFF , via start-stop switch (ST).
2. Insert software/programming PCMCIA card contain­ing the following (example) files into the program­ming/software port. (See Figure 6--18):
menuDDMM.ml3, this file allows the user to select a file/program to upload into the controller.
cfYYMMDD.ml3, multi-configuration file.
3. Turn unit ON, via start-stop switch (ST).
If ruN COnFG is displayed, follow procedure
6.19.3.1 If Set UP is displayed, follow procedure
6.19.3.2.
6.19.3.1 Programming Procedure for
a. Procedure for loading operational software:
1. The display module will display the message ruN
2. Press the UP or DOWN arrow key until display
3. Press the ENTER key on the keypad.
Software Versions Prior to 5328 and/or Cards Without Updated Menu Option (menu0111.ml)
COnFG. (If a defective card is being used the display will blink the message “bAd CArd.” Turn start-stop switch OFF and remove the card.)
reads, LOAd 53XX for Scroll.
4. The display will alternate to between PrESS EntR and rEV XXXX.
5. Press the ENTER key on the keypad.
6. The display will show the message “Pro SoFt”. This message will last for up to one minute.
7. The display module will go blank briefly, then read “Pro donE” when the software loading has loaded. (If a problem occurs while loading the software: the dis­play will blink the message “Pro FAIL” or “bad 12V.” Turn start-stop switch OFF and remove the card.)
8. Turn unit OFF , via start-stop switch (ST).
9. Remove the PCMCIA card from the programming/ software port and return the unit to normal operation by placing the start-stop switch in the ON position.
10.Turn power on, and wait 15 seconds. The status LED will flash quickly, and there will be no display. The controller is loading the new software into memory. This takes about 15 seconds.
When complete, the controller will reset and power up normally .
1 1.Wait for default display, setpoint on the left, and con-
trol temperature on the right.
12.Confirm software is correct using keypad code se­lect 18 to view Cd18 XXXX.
13.Turn power off. Operational software is loaded.
b. Procedure for loading configuration software:
1. Turn unit OFF using start-stop switch (ST).
2. Insert software/programming PCMCIA card contain­ing the following (example) files into the program­ming/software port. (See Figure 6--18):
menuDDMM.ml3, this file allows the user to select the file/program to upload into the controller.
cfYYMMDD.ml3, multi-configuration file
3. Turn unit ON using start-stop switch (ST).
4. The display module will display the message ruN COnFG. (If a defective card is being used the display will blink the message “bAd CArd.” Turn start-stop switch OFF and remove the card.)
5. Press the ENTER key on the keypad.
6. The display module will go blank briefly and then dis­play “551 00”, based on the operational software installed.
7. Press the UP or DOWN ARROW key to scroll through the list to obtain the proper model dash num­ber. (If a defective card is being used, the display will blink the message “bAd CArd.” Turn start-stop switch OFF and remove the card.)
8. Press the ENTER key on the keypad.
9. When the software loading has successfully com­pleted, the display will show the message “EEPrM donE.” (If a problem occurs while loading the soft­ware, the display will blink the message “Pro FAIL” or “bad 12V.” Turn start-stop switch OFF and remove the card.)
10.Turn unit OFF using start-stop switch (ST).
1 1.Remove the PCMCIA card from the programming/
software port and return the unit to normal operation by placing the start-stop switch in the ON position.
6--19
T-340Change 08/10
Page 91
12.Confirm correct model configuration using the key­pad to choose code 20 (CD20). The model displayed should match the unit serial number plate.
6.19.3.2 Programming Procedure for
Software Versions 5328 and Later AND With Updated Menu Option (menu0111.ml)
The updated menu option allows the operational soft­ware to be loaded, and time and container identification to be set.
a. Procedure for loading operational software:
1. The display module will display the message Set UP.
2. Press the UP or DOWN arrow key until display reads, LOAd 53XX for Scroll.
3. Press the ENTER key on the keypad.
4. The display will alternate to between PrESS EntR and rEV XXXX.
5. Press the ENTER key on the keypad.
6. The display will show the message “Pro SoFt”. This message will last for up to one minute.
7. The display module will go blank briefly, then read “Pro donE” when the software loading has loaded. (If a problem occurs while loading the software: the dis­play will blink the message “Pro FAIL” or “bad 12V.” Turn start-stop switch OFF and remove the card.)
8. Turn unit OFF , via start-stop switch (ST).
9. Remove the PCMCIA card from the programming/ software port and return the unit to normal operation by placing the start-stop switch in the ON position.
10.Turn power on, and wait 15 seconds. The status LED will flash quickly, and there will be no display. The controller is loading the new software into memory. This takes about 15 seconds.
When complete, the controller will reset and power up normally .
1 1.Wait for default display, setpoint on the left, and con-
trol temperature on the right.
12.Confirm software is correct using keypad code se­lect 18 to view Cd18 XXXX.
13.Turn power off. Operational software is loaded.
b. Procedure for loading configuration software:
1. Turn unit OFF using start-stop switch (ST).
2. Insert software/programming PCMCIA card contain­ing the following (example) files into the program­ming/software port. (See Figure 6--18):
menuDDMM.ml3, this file allows the user to select the file/program to upload into the controller.
cfYYMMDD.ml3, multi-configuration file
3. Turn unit ON using start-stop switch (ST).
4. Press the UP or DOWN arrow key until display reads Set UP.
5. Press the ENTER key on the keypad.
6. Press the UP or DOWN arrow key until display reads XXXX the message ruN COnFG. (If a defective card is being used the display will blink the message “bAd CArd.” Turn start-stop switch OFF and remove the card.)
7. Press the ENTER key on the keypad.
8. The display module will go blank briefly and then dis­play “551 00”, based on the operational software installed.
9. Press the UP or DOWN ARROW key to scroll through the list to obtain the proper model dash num­ber. (If a defective card is being used, the display will blink the message “bAd CArd.” Turn start-stop switch OFF and remove the card.)
10.Press the ENTER key on the keypad.
1 1.When the software loading has successfully com-
pleted, the display will show the message “EEPrM donE.” (If a problem occurs while loading the soft­ware, the display will blink the message “Pro FAIL” or “bad 12V.” Turn start-stop switch OFF and remove the card.)
12.Turn unit OFF using start-stop switch (ST).
13.Remove the PCMCIA card from the programming/ software port and return the unit to normal operation by placing the start-stop switch in the ON position.
14.Confirm correct model configuration using the key­pad to choose code 20 (CD20). The model displayed should match the unit serial number plate.
c. Procedure for setting the date and time:
1. Press the UP or DOWN arrow key until display reads Set TIM.
2. Press the ENTER key on the keypad.
3. The first value to be modified is the date in YYYY MM--DD format. The values will be entered from right to left. Press the UP or DOWN ARROW key to in­crease or decrease the values. The ENTER key will enter the information for the current field and move to the next value; the CODE SELECT key will allow modification of the previous value.
4. Press the ENTER key on the keypad.
5. The next value to be modified is the time in HH MM format. The values will be entered from right to left. Press the UP or DOWN ARROW key to increase or decrease the values. The ENTER key will enter the information for the current field and move to the next value; the CODE SELECT key will allow modification of the previous value.
6. Press the ENTER key on the keypad. The date and time will not be committed until start up procedures are completed on the next power up.
d. Procedure for setting the container ID:
NOTE
The characters will be preset to the container ID already on the controller. If none exist, the de­fault will be AAAA0000000.
1. Press the UP or DOWN arrow key until display reads Set ID.
2. Press the ENTER key on the keypad.
3. The values will be entered from right to left. Press the UP or DOWN ARROW key to increase or decrease the values. The ENTER key will enter the information for the current field and move to the next value; the CODE SELECT key will allow modification of the previous value.
6--20T-340
Change 08/10
Page 92
4. When the last value is entered, press the ENTER key to enter the information to the controller; the CODE SELECT key will allow modification of the previous value.
6.19.4 Removing and Installing a Module
a. Removal:
1. Disconnect all front wire harness connectors and move wiring out of way.
2. The lower controller mounting is slotted, loosen the top mounting screw (see Figure 6--18) andlift up and out.
3. Disconnect the back connectors and remove mod­ule.
4. When removing the replacement module from its packaging , note how it is packaged. When returning the old module for service, place it in the packaging in the same manner as the replacement. The pack­aging has been designed to protect the module from both physical and electrostatic discharge damage during storage and transit.
b.Installation:
Install the module by reversing the removal steps.
Torque values for mounting screws (item 2, see Figure 6--18) are 0.23 mkg (20 inch-pounds). Torque value for the connectors is 0.12 mkg (10 inch-pounds).
6.19.5 Battery Replacement
Standard Battery Location (Standard Cells):
a. Turn unit power OFF and disconnect power supply.
b. Slide bracket out and remove old batteries. (See
Figure 3--4, Item 8.)
c. Install new batteries and slide bracket into control box
slot.
CAUTION
Use care when cutting wire ties to avoid nicking or cutting wires.
Standard Battery Location (Rechargeable Cells):
a. Turn unit power OFF and disconnect power supply.
b. Disconnect battery wire connector from control box.
c. Slide out and remove old battery and bracket. (See
Figure 3--4, Item 8.)
d. Slide new battery pack and bracket into the control
box slot.
e. Reconnect battery wire connector to control box and
replace wire ties that were removed.
Secure Battery Option (Rechargeable Cells Only):
a. Turn unit power OFF and disconnect power supply.
b. Open control box door and remove both the high volt-
age shield and clear plastic rain shield (if installed).
c. Disconnect the battery wires from the “KA” plug posi-
tions 14, 13, 1 1.
d. Using Driver Bit, Carrier Transicold part number
07--00418--00, remove the 4 screws securing the dis-
play module to the control box. Disconnect the ribbon cable and set the display module aside.
NOTE
The battery wires must face toward the right.
e. Remove the old battery from the bracket and clean
bracket surface. Remove the protective backing from the new battery and assemble to the bracket. Secure battery by inserting the wire tie from the back of the bracket around the battery, and back through the bracket.
f. Reconnect the ribbon cable to display and re--install
the display.
g. Route the battery wires from the battery along the dis-
play harness and connect the red battery wire and one end of the red jumper to “KA14,” the other end of the red jumper wire to “KA11,” and the black wire to “KA13.”
h. Replace wire ties that were removed.

6.20 VENT POSITION SENSOR SERVICE

The fresh air vent position sensor alarm (AL50) will oc­cur if the sensor reading is not stable for four minutes or if the sensor is outside of its valid range (shorted or open). This can occur if the vent is loose or the panel is defective. To confirm a defective panel, assure that the wing nut is secure and then power cycle the unit. If the alarm immediately reappears as active, the panel should be replaced.
The alarm should immediately go inactive, check the 4-minute stability requirement. If the alarm reoccurs af­ter the four minutes and the panel was known to have been stable, then the sensor should be replaced.
In order to replace the VPS, the panel must be removed and replaced with another upper fresh air panel equipped with VPS.
Upon installation, a new vent position sensor assembly requires calibration as follows:
1. Rotate the vent to the 0 CMH/ CFM position.
2. Code select 45 will automatically display. Press the Enter key and hold for five seconds.
3. After the enter key has been pressed the display will read CAL (for calibration).
4. Press the ALT MODE key and hold for five seconds.
5. After the calibration has been completed, Code 45 will display 0 CMH / CFM.
a. Lower Vent Position Sensor Calibration
Calibration of the Lower VPS is only required when the air makeup slide, motor or sensor has been repaired or serviced.
The VPS is calibrated using the keypad:
1. Remove the two nuts that secure the air makeup
panel slide to the unit.
2. Rotate the gear clockwise until it stops.
3. Rotate the gear 1/4 turn counterclockwise.
4. Carefully reposition the slide onto the air makeup
panel, given that the gear is engaged with the rail and has not moved.
5. Position slide panel to the fully closed position.
6--21
T-340
Page 93
6. Code select Cd45 will automatically be shown on the left display.
7. Depress the ENTER key and hold for five seconds. CAL for calibration is displayed.
8. Depress the ALT MODE key on the keypad and hold for five seconds.
9. When calibration has been completed, Cd45 causes 0 CMH/CFM to be shown on the right display.
10.Secure the air makeup panel slide to the unit with the two nuts; stake threads.

6.21 TEMPERATURE SENSOR SERVICE

Procedures for service of the return recorder, return temperature, supply recorder, supply temperature, am­bient, defrost temperature, evaporator temperature, and compressor discharge temperature sensors are provided in the following sub paragraphs.
6.21.1 Sensor Checkout Procedure
To check a sensor reading, do the following:
a. Remove the sensor and place in a 0C (32F) ice-water
bath. The ice-water bath is prepared by filling an insu­lated container (of sufficient size to completely immerse bulb) with ice cubes or chipped ice, then fill­ing voids between ice with water and agitating until mixture reaches 0C (32F) measured on a laboratory thermometer.
b. Start unit and check sensor reading on the control
panel. The reading should be 0C (32F). If the reading is correct, reinstall sensor; if it is not, continue with the following.
c. Turn unit OFF and disconnect power supply .
d. Refer to paragraph 6.19 and remove controller to gain
access to the sensor plugs.
e. Using the plug connector marked “EC” that is con-
nected to the back of the controller, locate the sensor wires (RRS, RTS, SRS, STS, AMBS, DTS, or CPDS as required). Follow those wires to the connector and using the pins of the plug, measure the resistance. Values are provided in Table 6--2.
Due to the variations and inaccuracies in ohmmeters, thermometers or other test equipment, a reading within 2% of the chart value would indicate a good sensor. If a sensor is defective, the resistance read­ing will usually be much higher or lower than the resis­tance values given.
Table 6--2 Sensor Temperature/Resistance Chart
(+/-.002%)
Temperature
C F
AMBS, DTS,
RTS, RRS, STS,
-30 -22 177,000 1,770,000
-25 -13 130,400 1,340,000
-20 -4 97,070 970,700
-15 5 72,900 729,000
-10 14 55,330 553,000
-5 23 43,200 423,300 0 32 32,650 326,500 5 41 25,390 253,900
10 50 19,900 199,000 15 59 15,700 157,100 20 68 12,490 124,900 25 77 10,000 100,000 30 86 8,060 80,600 35 95 6,530 65,300 40 104 5,330 53,300 45 113 4,370 43,700 50 122 3,600 36,000 55 131 2,900 29,000 60 140 2,490 24,900 65 149 2,080 20,800 65 158 1,750 17,500
6.21.2 Sensor Replacement
a. Turn unit power OFF and disconnect power supply.
Include white date code label when cutting out and removing defective sensors. The label could be required for warranty returns.
b. Cut cable 5 cm (2 inches) from shoulder of defective
sensor and discard the defective probe only. Slide the cap and grommet off a bulb type sensor and save for reuse. Do not cut the grommet.
c. Cut one wire of existing cable 40 mm (1-1/2 inches)
shorter than the other wire.
d. Cut one replacement sensor wire (opposite color)
back 40 mm (1-1/2 inches). (See Figure 6--19.)
e. Strip back insulation on all wiring 6.3 mm (1/4 inch).
Resistance
(Ohms)
CPDS
SRS
NOTE
6--22T-340
Page 94
1
2
3
j. Solder spliced wires with a 60% tin and 40% lead
Rosincore solder.
k. Slide heat shrink tubing over splice so that ends of
tubing cover both ends of crimp as shown in Figure 6--20.
l. Heat tubing to shrink over splice. Make sure all seams
are sealed tightly against the wiring to prevent mois­ture seepage.
Mounting Stud Type
12
Do not allow moisture to enter wire splice area as this may affect the sensor resis­tance.
CAUTION
3
Bulb Type
1. Sensor
2. 40 mm (1 1/2 in.)
3. 6.3 mm (1/4 in.)
Figure 6--19 Sensor Types
f. Slide a large piece of heat shrink tubing over the
cable, and place the two small pieces of heat shrink tubing, one over each wire, before adding crimp fit­tings as shown in Figure 6--20.
212
1
1. Cable
2. Sensor (Typical)
3. Large Heat Shrink Tubing (1)
Figure 6--20 Sensor and Cable Splice
g. Slide large heat shrink tubing over both splices and
shrink.
h. If required, slide the cap and grommet assembly onto
the replacement sensor.
i. Slip crimp fittings over dressed wires (keeping wire
colors together). Make sure wires are pushed into crimp fittings as far as possible and crimp with crimp­ing tool.
3
4
4. Heat Shrink Tubing (3)
m.Position sensor in unit as shown in Figure 6--20 and
re-check sensor resistance.
n. Reinstall sensor, refer to paragraph 6.21.3.
NOTE
The P5 Pre-Trip test must be run to inactivate probe alarms (refer to paragraph 4.9).
6.21.3 Sensor Re-Installation
Sensors STS and SRS
To properly position a supply sensor, the sensor must be fully inserted into the probe holder. See Figure 6--21. Do not allow heat shrink covering to contact the probe hold­er. For proper placement of the sensor, be sure to posi­tion the enlarged positioning section of the sensor against the the side of the mounting clamp. This posi­tioning will give the sensor the optimum amount of expo­sure to the supply air stream, and will allow the controller to operate correctly.
Sensors RRS and RTS
Reinstall the return sensor as shown in Figure 6--22. For proper placement of the return sensor, be sure to posi­tion the enlarged positioning section of the sensor against the the side of the mounting clamp. See Figure 6--22.
Sensor DTS
The DTS sensor must have insulating material placed completely over the sensor to ensure the coil metal tem­perature is sensed.
Sensors ETS1 and ETS2
The ETS1 and ETS2 sensors are located in a tube hold­er under insulation, as illustrated in Figure 6--23. When the combo sensor is removed and reinstalled, it must be placed in a tube holder by applying thermal grease. In­sulating material must completely cover the sensor to ensure the correct temperature is sensed.
6--23
T-340
Page 95
11
10
9
8
1. Supply Air Stream
2. Insulation
3. Back Panel
4. Supply Sensor
5. Mounting Clamp
6. Sensor Wires
7. Drip Loop
1
12
2
13
3
4
5
6
7
(2.5”)
8. Gasket Mounting Plate
9. Gasketed Support Plate
10. Gasketed Cover
11. TIR Bolt s
12. STS Probe
13. SRS Probe
Figure 6--21 Supply Sensor Positioning
1
1. Mounting Clamp
2. Return Sensor
Figure 6--22 Return Sensor Positioning
2
1.50 in. (38.1cm)
4
3
1. Wire Tie
2. ETS1 and 2
3. ETS Tube Holder
4. Insulation
2
Figure 6--23 Evaporator Temperature
1.00 in. (25.4cm)
Sensor Positioning
1
6--24T-340
Page 96

6.22 ELECTRONIC PARTLOW TEMPERATURE RECORDER

off period and record it onto the chart. Thereafter, the recorder will resume normal temperature recording.
The microprocessor--based temperature recorder is designed to interface with the D ataCORD ER to log temperature with time. The electronic recorder will automatically record the return air, supply air, or both, based on the setting of temperature controller configuration code CnF37, refer to T able 3--4. The recorder reads and records data from the controller in present time, under normal operating conditions.
If the power has been OFF for more than thirty days, the recorder will NOT re-synchronize (the chart will not advance to present time), the pen tip will move to the currently recorded temperature, and the recorder will resume normal temperature recording.
If using the Electronic Partlow Recorder CTD part number 12-00464-xx Where xx= an even number (example: 12-00464-08)
The recorder will STOP when the power is OFF , and the pen tip will remain at the last recorded temperature on the chart. When power is applied, and the power off period is less than thirty days, the recorder will retrieve the logged data from the DataCORDER for the power
If the optional DataCORDER battery pack is being used and the charge is too low to enable recording during the power off period of less than thirty days, the pen tip will move to below the inner chart ring for the period when NO data was recorded by the DataCORDER.
If the power has been OFF for more than thirty days, the recorder will NOT re-synchronize (the chart will not advance to present time), the pen tip will move to the currently recorded temperature, and the recorder will resume normal temperature recording.
6.22.1 Replacing the Recorder
a. Turn power to the unit OFF .
b. Open the recorder door (item 1, see Figure 6--24).
c. Locate the connector below the recorder, and
squeeze the ears together to disconnect the plug (item 10).
d. Remove the four mounting screws (item 2), and
remove the recorder.
e. Install the new recorder by reversing the above
steps.
6--25
T-340
Page 97
1
2
3
4
10
9
8
7
1. Recorder Door
2. Change Chart Button
3. Recorder Box
4. Pen Tip
5. Stylus Arm
Figure 6--24 Electronic Partlow Temperature Recorder
6.22.2 Rezeroing the Recording Thermometer
For Electronic Partlow Recorder CTD part number 12-00464-xx Where xx= an odd number (example: 12-00464-03)
NOTE
Use chart CTD part number 09-00128-00 (F)
part number 09-00128-01 (C).
a. Press the “Calibration” button (item 7, Figure 6--24)
on the bottom of the recorder. The pen tip will drive ful­ly down scale, then move upscale to the chart ring at
-29C (-20F), and stop.
b. If the tip of the pen (item 4) is on the -29C (-20F) chart
ring, the recorder is in calibration, proceed to step c. If the tip of the pen is NOT on the -29C(-20F) chart ring, the operator must loosen the two screws on the bot­tom of the stylus arm to adjust the pen tip manually to the -29C (-20F) chart ring. Tighten the screws when adjustment is complete.
5
6
6. Connector
7. Calibration Button (Located underneath)
8. Mounting Screws, #10-24 x 7/16 inches long
9. Hold Down Tab
10. Chart Retaining Nut
For Electronic Partlow Recorder CTD part number 12-00464-xx Where xx= an even number (example: 12-00464-08)
NOTE
Use chart CTD part number 09-00128-00 (F)
part number 09-00128-01 (C).
a. Press the “Calibration” button (item 7, Figure 6--24)
on the bottom of the recorder. The pen tip will drive ful­ly down scale, then move upscale to the chart ring at 0C (32F), and stop.
b. If the tip of the pen (item 4) is on the 0C (32F) chart
ring the recorder is in calibration, proceed to step c. If the tip of the pen is NOT on the 0C (32F) chart ring, the operator must loosen the two screws on the bottom of the stylus arm to adjust the pen tip manually to the 0C (32F) chart ring. Tighten the screws when adjustment is complete.
c. Press the calibration button and the pen will position
itself to the correct temperature reading.
c. Press the calibration button and the pen will position
itself to the correct temperature reading.
6--26T-340
Page 98

6.23 MAINTENANCE OF PAINTED SURFACES

The refrigeration unit is protected by a special paint system against the corrosive atmosphere in which it normally operates. However, should the paint system be damaged, the base metal can corrode. In order to protect the refrigeration unit from the highly corrosive sea atmosphere, or if the protective paint system is scratched or damaged, clean area to bare metal using a wire brush, emery paper or equivalent cleaning method. Immediately following cleaning, apply two-part epoxy paint to the area. and allow to dry. After the first coat dries, apply a second coat.

6.24 COMMUNICATIONS INTERFACE MODULE INSTALLATION

a. CB1 is connected to the power system, see wiring
schematic. Ensure that the unit power is off AND that the unit power plug is disconnected.
b. Open control box, see Figure 6--25 and remove low
voltage shield. Open high voltage shield.
c. If using factory provisioned wiring, remove the cir-
cuit breaker panel, with circuit breaker, from the control box. Locate, wires CB21/CIA3, CB22/CIA5 and CB23/CIA7 that have been tied back in the wire harness. Remove the protective heat shrink from the ends of the wires.
d. Refit the circuit breaker panel.
e. Fit the new CIM into the unit.
f. Attach three wires CB21/CIA3, CB22/CIA5 and
CB23/CIA7 to the CIM at connection CIA.
g. Locate connectors CIA and CIB, remove plugs if re-
quired, and attach to the module.
h. Replace the low voltage shield.
Table 6--3 Recommended Bolt Torque Values
CB1
Figure 6--25 Communications Interface
Installation
Units that have been factory provisioned for installation of a communication interface module (CIM) have the re­quired wiring installed. If the unit is not factory provi­sioned, a provision wiring kit (Carrier Transicold part number 76-00685-00) must be installed. Installation in­structions are packaged with the kit. To install the mod­ule, do the following:
Communications interface Module
WARNING
Installation requires wiring to the main unit circuit breaker, CB1. Make sure the power to the unit is off and power plug disconnected before beginning installation.
BOLT DIA.
#4 #6 #8
#10
1/4
5/16
3/8
7/16
1/2
9/16
5/8 3/4
NONFREE SPINNING (LOCKNUTS ETC.)
1/4
5/16
3/8
7/16
1/2
9/16
5/8 3/4
THREADS TORQUE Nm
FREE SPINNING
40 32 32 24 20 18 16 14 13 12
11
10
20 18 16 14 13 12
11
10
5.2 in-lbs
9.6 in-lbs 20 in-lbs 23 in-lbs 75 in-lbs
11 ft-lbs 20 ft-lbs 31 ft-lbs 43 ft-lbs 57 ft-lbs 92 ft-lbs
124 ft-lbs
82.5 in-lbs
145.2 in-lbs
22.0 ft-lbs
34.1 ft-lbs
47.3 ft-lbs
62.7 ft-lbs
101.2 ft-lbs
136.4 ft-lbs
0.6
1.1
2.0
2.5
8.4 15 28 42 59 78
127 171
9.3
16.4 23 47 65 86
139 188
6--27
T-340
Page 99
Table 6--4 R-134a Temperature - Pressure Chart
Temperature Vacuum
F C “/hg cm/hg kg/cm2bar
-40 -40 14.6 49.4 37.08 0.49
-35 -37 12.3 41.6 31.25 0.42
-30 -34 9.7 32.8 24.64 0.33
-25 -32 6.7 22.7 17.00 0.23
-20 -29 3.5 11. 9 8.89 0.12
-18 -28 2.1 7.1 5.33 0.07
-16 -27 0.6 2.0 1.52 0.02
Temperature Pressure
F C psig kPa kg/cm2bar
-14 -26 0.4 1.1 0.03 0.03
-12 -24 1.2 8.3 0.08 0.08
-10 -23 2.0 13.8 0.14 0.14
-8 -22 2.9 20.0 0.20 0.20
-6 -21 3.7 25.5 0.26 0.26
-4 -20 4.6 31.7 0.32 0.32
-2 -19 5.6 36.6 0.39 0.39
0 -18 6.5 44.8 0.46 0.45
2 -17 7.6 52.4 0.53 0.52
4 -16 8.6 59.3 0.60 0.59
6 -14 9.7 66.9 0.68 0.67
8 -13 10.8 74.5 0.76 0.74
10 -12 12.0 82.7 0.84 0.83
12 -11 13.2 91.0 0.93 0.91
14 -10 14.5 100.0 1.02 1.00
16 -9 15.8 108.9 1.11 1.09
18 -8 17.1 117.9 1.20 1.18
20 -7 18.5 127.6 1.30 1.28
22 -6 19.9 137.2 1.40 1.37
24 -4 21.4 147.6 1.50 1.48
26 -3 22.9 157.9 1.61 1.58
Temperature Pressure
F C psig kPa kg/cm2bar
28 -2 24.5 168.9 1.72 1.69
30 -1 26.1 180.0 1.84 1.80
32 0 27.8 191.7 1.95 1.92
34 1 29.6 204.1 2.08 2.04
36 2 31.3 215.8 2.20 2.16
38 3 33.2 228.9 2.33 2.29
40 4 35.1 242.0 2.47 2.42
45 7 40.1 276.5 2.82 2.76
50 10 45.5 313.7 3.20 3.14
55 13 51.2 353.0 3.60 3.53
60 16 57.4 395.8 4.04 3.96
65 18 64.1 441.0 4.51 4.42
70 21 71.1 490.2 5.00 4.90
75 24 78.7 542.6 5.53 5.43
80 27 86.7 597.8 6.10 5.98
85 29 95.3 657.1 6.70 6.57
90 32 104.3 719.1 7.33 7.19
95 35 114.0 786.0 8.01 7.86
100 38 124.2 856.4 8.73 8.56
105 41 135.0 930.8 9.49 9.31
110 43 146.4 1009 10.29 10.09
115 46 158.4 1092 11.14 10.92
120 49 171.2 1180 12.04 11.80
125 52 184.6 1273 12.98 12.73
130 54 198.7 1370 13.97 13.70
135 57 213.6 1473 15.02 14.73
140 60 229.2 1580 16.11 15.80
145 63 245.6 1693 17.27 16.93
150 66 262.9 1813 18.48 18.13
155 68 281.1 1938 19.76 19.37
6--28T-340
Page 100
SECTION 7
ELECTRICAL WIRING SCHEMATICS
7.1 INTRODUCTION
This section contains the Electrical Schematics and Wiring Diagrams. The diagrams are presented as follows:
Figure 7--1 provides the legend for use with Figure 7--2, the schematic diagram for standard refrigeration units.
Figure 7--2 provides the basic schematic diagram for standard refrigeration units.
Figure 7--3 provides the legend for use with Figure 7--4, the schematic diagram for units with available options except
Vent Positioning System, eAutoFresh and Emergency Bypass.
Figure 7--4 provides the basic schematic diagram for units with available options except Vent Positioning System,
eAutoFresh and Emergency Bypass.
Figure 7--5 provides the legend for use with Figure 7--6, the schematic diagram for units with eAutoFresh and/or
Emergency Bypass. Figure 7--6 provides the basic schematic diagram for units with units with eAutoFresh and/or Emergency Bypass.
Figure 7--7 supplements Figure 7--4 and Figure 7--6 and provides schematic and wiring diagrams for Upper Vent
Figure 7--8 supplements Figure 7--4 and Figure 7--6 and provides schematic and wiring diagrams for Lower VPS.
Position Sensor (VPS).
NOTE
Options other than those mentioned below may be included in wiring diagrams.
Figure 7--9 provides the wiring diagram for standard refrigeration units with 3--phase condenser fan motors.
Figure 7--10 provides the wiring diagram for units with 2--phase condenser fan motors and/or optional 5+1 heater
Figure 7--11 provides the wiring diagram for units with eAutoFresh and/or Emergency Bypass installed.
arrangement.
7--1
T-340
Loading...