Carrier ComfortPro PC6000, ComfortPro PC6002, ComfortPro PC6006, ComfortPro PC6003 Operation & Service Manual

R
62--11175 Rev --
Operation & Service Manual
for
ComfortPro
Auxiliary
Power Unit
Models PC6000, PC6002, PC6003 & PC6006
62-11175 COMFORTPRO SERVICE MANUAL
c-i
CONTENTS
INTRODUCTION
SAFETY
Safety Alerts ................................................................................. c-iii
Component Layout.......................................................................... c-v
GENERAL ARRANGEMENT
APU Dimensions ............................................................................ c-vi
CCU Dimensions........................................................................... c-vii
Condenser Dimensions ................................................................. c-vii
1.0 OPERATION OF MULTI–FUNCTION D.C.P
1.1 PREPARATION
1.1.1 Multi–Function D.C.P Components....................................... 1-1
1.1.2 How the ComfortPro Operates ............................................. 1-2
1.2 MANUAL OPERATIONS
1.2.1 Starting the APU ................................................................ 1-3
1.2.2 Stopping the APU ............................................................... 1-3
1.2.3 Turning the Heater ON/OFF ................................................. 1-4
1.2.4 Heating: Setting the Temperature ........................................ 1-4
1.2.5 Turning the A/C ON/OFF ..................................................... 1-4
1.2.6 Setting the A/C Temperature .............................................. 1-4
1.2.7 Fan Operation .................................................................... 1-5
1.3 AUTOMATIC OPERATIONS
1.3.1 Password Protection........................................................... 1-5
1.3.2 Entering Password ............................................................. 1-6
1.3.3 Setting the Clock ............................................................... 1-7
1.3.4 Comfort Monitor................................................................. 1-7
1.3.5 Timer ................................................................................ 1-8
1.3.6 Cold Weather Watch ......................................................... 1-10
1.3.7 Maximum Run Time.......................................................... 1-11
1.3.8 Battery Monitoring............................................................ 1-12
2.0 CLIMATE CONTROL UNIT (CCU)
2.1 PREPARATION
2.1.1 Charging the CCU............................................................... 2-1
2.2 SERVICE
2.1.2 Maintenance Schedule ....................................................... 2-2
2.1.2 CCU Spring Tune–Up .......................................................... 2-3
3.0 TROUBLESHOOTING
3.0 MANUAL OPERATIONS
3.1 APU (Auxiliary Power Unit)............................................................... 3-2
3.2 GENERATOR .................................................................................. 3-6
3.3 DRIVER CONTROL PANEL ............................................................... 3-7
3.4 CCU AIR CONDITIONING ................................................................. 3-8
3.5 CCU Fan ..................................................................................... 3-11
3.6 CCU Heat.................................................................................... 3-11
3.7 RECEPTACLE PANEL..................................................................... 3-12
62-11175 COMFORTPRO SERVICE MANUAL
c-ii
3.0 TROUBLESHOOTING (Cont.)
3.8 TESTING PROCEDURES
3.8.1 Testing AMP draw for components ....................................... 3-13
3.8.2 Testing Voltage and Hz readings .......................................... 3-13
3.9 ADDITIONAL INFORMATION
3.9.1 Adjusting the 120 A/C Voltage............................................. 3-14
3.9.2 Capacitor Troubleshooting ................................................... 3-14
3.9.3 Capacitor Theory................................................................. 3-14
3.9.4 Potential Relay Theory......................................................... 3-15
3.9.5 Alternator Troubleshooting................................................... 3-15
APPENDICES
CAPACITIES AND SPECIFICATIONS ........................................................... A-2
FUSE LOCATIONS ................................................................................... A-4
CIRCUIT BREAKER LOCATIONS ................................................................ A-5
APU CONTROL UNIT................................................................................ A-6
CCU CONTROLLER.................................................................................. A-7
FUEL SYSTEM PURGE PROCEDURE ......................................................... A-8
COOLANT PURGE PROCEDURE ................................................................ A-9
DEFROST/HEAT & DCP SENSOR............................................................ A-11
ENGINE INTERLOCK.............................................................................. A-12
APU WIRING (Serial# KZX98002290 to Date) ......................................... A-13
62-11175 COMFORTPRO SERVICE MANUAL
c-iii
SAFETY
DANGER
Immediate hazards that will result in severe personal injury or death.
WARNING
Hazards or unsafe practices that could result in severe personal injury or death.
CAUTION
Hazards or unsafe practices that could result in minor injury or product or property damage.
NOTICE
Information that is important to proper installation or maintenance, but is not hazard-related.
DANGER
A certified refrigeration technician must charge and test the CCU.
For example:
Safety Alerts
Throughout this manual, you will see notes labeled "Warnings" or "Cautions" to alert you to special instructions or precautions concerning a particular procedure that would be hazardous if performed incorrectly or carelessly.
Observe them carefully!
These safety alerts alone cannot eliminate hazards that can occur. Strict compliance with these special instructions when performing the installation and maintenance, plus common sense, are major accident prevention measures.
62-11175 COMFORTPRO SERVICE MANUAL
c-iv
Safety Considerations
Inhalation of exhaust gas (containing carbon monoxide) may cause severe personal injury and/or death. Anyone suspected of suffering from CO inhalation should be removed from the hazardous area and given medical assistance immediately.
Exercise extreme caution when working near fuel or fuel-filled equipment. Do not operate equipment during fueling operations. Use eye protection when working near batteries, which contain acid and can explode. Do not smoke or use open flames near batteries.
Electric shock can cause severe personal injury, burns, and death. Before working on any unit, disconnect the batteries. Use only approved materials and methods when working on the electrical system, and follow local electrical codes. Never work on the APU or the electrical circuitry when the APU is running. Never work with electricity in wet conditions or when you are tired.
Fuel, oil, coolant, and refrigerant are toxic and in some cases, carcinogenic. Wear eye and hand protection at all times. Remove contaminated clothing immediately and wash contaminated skin. Do not breathe in vapors.
Moving parts can cause severe injury and/or death. Before working on any unit, shut it off and disconnect the battery. Do not start until protective covers have been replaced. Also, loose parts falling into rotating machinery can cause severe accidents. Always ensure bolts and clamps are correctly torqued and secured. Inspect mechanical components periodically for damage, corrosion, and proper torque.
The APU is designed to provide electrical power for heating and cooling vehicles in normal on-road conditions. Never use the APU to power critical medical equipment or sensitive electronic equipment without the manufacturer's express written approval.
Exhaust
Fuel/Batteries
Electrical
Intoxicants
Hot or Moving Parts
Misuse
WARNING
California Proposition 65 Warning: This product contains lead, a chemical known to the State of California to cause cancer and birth defects and other reproductive harm.
62-11175 COMFORTPRO SERVICE MANUAL
c-v
COMPONENT LAYOUT
Figure C1: Main Components of the Carrier ComfortPro system and Where They Should Best be Installed on the Truck
COOLANT SUPPLY
AND RETURN
PANEL (DCP)
DRIVER CONTROL
CONDENSER
120 VAC
RECEPTACLE PANEL
UNIT (CCU)
CLIMATE CONTROL
BATTERY
VEHICLE FUEL TANK
AND RETURN
FUEL SUPPLY
AUXILIARY POWER UNIT (APU)
62-11175 COMFORTPRO SERVICE MANUAL
c-vi
GENERAL ARRANGEMENT
TOP VIEW
REAR
LEFT SIDE
APU Dimensions (Measurements in inches)
FRONT VIEW
RIGHT SIDE
3.0
2.75 3.875
18.5
16.0
10.5
2.6
24.9
28.5
62-11175 COMFORTPRO SERVICE MANUAL
c-vii
FRONT VIEW
BOTTOM VIEW
CCU Dimensions (Measurements in inches)
FRONT RIGHT SIDE
DOWN
Condenser Dimensions (Measurements in inches)
12"
7.9"
23.4"
24.4"
16.2"
15.2"
3.3"
3.1"
3.0"
6.9"
3.0"
6.9"
3.0"
3.4"
3.0"
12.6"
.125"
1.3"
12.9"
5.62"
13.93"
16.25"
16.90"
5.62"
26.5"
24.25"
8"
3.5"
2.0"
62-11175 COMFORTPRO SERVICE MANUAL
c-viii
62-11175 COMFORTPRO SERVICE MANUAL
1-1
1.0
OPERATION OF MULTI-FUNCTION DRIVER CONTROL PANEL
Figure 1-0: Multi-Function Driver Control Panel
1.1.1 Multi-Function Driver Control Panel Components
1 When visible, the heating system is heating.
2 When visible, the A/C is cooling.
3 Indicates the number of operating hours on the APU.
4 Indicates the state of the APU.
The APU engine is running.
The APU engine is off.
The APU engine is in the starting process (flashing).
5 Indicates that Battery Monitor mode is enabled.
6 Indicates that maximum run time is enabled.
7 Indicates that Cold Weather Watch mode is enabled.
8 Indicates that Comfort Monitor mode is enabled.
9 Indicates that Timer 1 or Timer 2 mode is enabled.
10 Indicates that the ComfortPro is connected to shore power.
The APU cannot be started in Shore Power mode.
11 Indicates the state of the 115V outlet and CCU auto-reset breakers.
115 VAC power is being supplied to the outlet.
No power is being supplied to the outlet.
CCU breaker has tripped. High Heat/Outlet breaker has tripped.
The breaker that tripped has reset automatically and the DCP needs to be reset.
NOTICE
The DCP (driver control panel), which is mounted inside the truck bunk, controls the APU and the CCU. The central panel on the DCP provides status information using words and icons:
PREPARATION 1.1
4 5
3
APU
ON/OFF
2
MENU
HOURS 00000
6 7 8 9
APU
A/ C FAN HEAT
1
10 11
SP
T2T
1
HVAC
OFF
ESC/
RESET
APU
APU
APU
T2T
1
OFF
TRIP
TRIP
RE­SET
62-11175 COMFORTPRO SERVICE MANUAL
1-2
1.1.2 How the ComfortPro Operates
The ComfortPro has two modes of operation: manual and automatic.
Manual Mode
You start the APU from within the truck bunk using the On/Off button on the driver control panel (DCP). Once the APU is running, you can start and stop the fan, heater and air conditioning using the DCP. See page 1-3.
Once the heater or A/C is running, it will cycle (automatically turn on and off) in order to keep the truck bunk at the temperature you specify. The HVAC will continue to cycle until you turn it off. While the HVAC is cycling, the APU remains on and will only turn off when you manually turn it off using the button on the DCP.
Note that in manual mode, the APU remains on until you turn it off. But in Comfort Monitor mode (described below), the APU automatically turns off and on as required.
When the APU is running, power is supplied to the power outlet in the truck bunk (except in high heat).
In manual mode, the APU will turn off automatically if the Maximum Run Time is reached.
Automatic Mode
The ComfortPro has several functions that will start it in automatic mode.
Comfort Monitor
(page 1-7)
FEATURE DESCRIPTION
The APU and HVAC automatically turn on to maintain a comfortable temperature in the truck bunk. When the desired temperature is met, the APU and HVAC automatically turn off. When the temperature is again out of range, they will both turn on again, and cycle heat and air conditioning as needed.
Timer
(page 1-8)
At the specified time, the APU and HVAC automatically turn on. During the specified timer duration, the HVAC cycles on and off to maintain the desired temperature. When the timer duration expires, both the APU and HVAC turn off automatically and remain off.
Cold Weather Watch
(page 1-10)
The APU and heater on the HVAC automatically turn on in order to prevent the APU engine and truck engine from getting too cold. (Turning on the heater creates a “load” that makes the APU work harder and therefore warm up faster). Both the APU and HVAC turn off automatically once the preset duration time expires.
The APU automatically turns on for 90 minutes in order to recharge the batteries. The HVAC does not turn on. After the 90 minute run time, the system will sense voltage for 10 minutes, before restarting if needed.
Battery Monitor
(page 1-12)
There are icons on the DCP that flash when the APU and HVAC are running. See page 1-1. If you enter the truck bunk and APU or HVAC is on but you did not start it, you can assume it has started in one of the automatic modes, as described above. On the DCP, one icon will be flashing steadily: this is the icon for the mode that is currently operating.
Whenever the ComfortPro is running in automatic mode, if you then press the heat, A/C or fan buttons on the DCP, the ComfortPro will switch to manual mode. The APU will not automatically turn off! This icon on the DCP will also stop flashing.
62-11175 COMFORTPRO SERVICE MANUAL
1-3
Automatic Mode and Minimum Time Off
All these automatic functions work on a "minimum time off": the ComfortPro must be off for at least 10 minutes before the automatic function will turn it on again. For example, the Timer function may be set to turn on the ComfortPro at 10:00 a.m. You have been running the ComfortPro in manual mode. You turn off the ComfortPro at 9:55 a.m. The timer will only turn on the ComfortPro again 10 minutes later, at 10:05 a.m.
Clock
In order to use the Timer correctly, you must set the DCP clock. See page 1-7.
Maximum Run Time
You can set the maximum time that the APU is allowed to continuously run in manual mode. See page 1-11.
Password Protection
You can add a password to the DCP, then you can protect one or more functions so that only a person who knows the password can set the function. See page 1-5.
WARNING
Do not start the APU when the enclosure cover is removed. Operating with the cover off may result in injury and/or death.
Press and release once.
The display shows "PLEASE WAIT – APU STARTING" and flashes.
When stops flashing, then the APU has started successfully.
The APU startup sequence consists of 20 seconds of glowing (30 seconds when the ambient temperature is below -5°C or 23°F) and up to 10 seconds of cranking.
If the sequence fails, "RESTARTING" appears for six seconds. Then the startup sequence automatically repeats up to five times or until the APU starts.
If "CRANK LIMIT" appears, see Troubleshooting section.
APU
APU
WARNING
When the APU is about to start, a buzzer sounds. Make sure no one is standing near the APU or touching it.
1.2.1 Starting the APU "One Touch Start"
Press
.
The APU will stop. The display shows .
APU
1.2.2 Stopping the APU
1.2 MANUAL OPERATIONS
HOURS 00000
APU
PLEASE WAIT
APU STARTING
HOURS 00000
APU
RESTARTING
HOURS 00000
APU
CRANK LIMIT
HOURS 00000
APU
OFF
OFF
OFF
OFF
OFF
OFF
OFF
62-11175 COMFORTPRO SERVICE MANUAL
1-4
1 Press to activate the heater.
The display shows "HEAT LOW".
The heater will turn on only if the temperature is too low (to adjust the temperature, see below). When the heater is on, appears.
2 Press again to switch between
high and low heat to heat the truck bunk more or less quickly. In "HEAT HIGH" mode, the power outlet is disabled and the display indicates .
The heat or A/C will turn off when the desired temperature is reached.
3 Press to deactivate heating.
NOTICE
The heat mode will not function if the temperature is higher than 85°F.
1.2.3 Turning the Heater ON/OFF
1.2.4 Heating: Setting the Temperature
1.2.5 Turning the A/C ON or OFF
1.2.6 A/C Setting the Temperature
Press or when the heater is on ("HEAT LOW"or "HEAT HIGH" shows).
The notch on the temperature bar moves. The heater will automatically turn on and off to maintain this temperature.
1 Press to activate the A/C.
The display shows "A/C LOW".
The A/C will turn on only if the temperature is too high (to adjust the temperature, see below). When the A/C is on, appears.
2 Press again to switch between
high and low A/C to cool the truck bunk more or less quickly.
3 Press to deactivate the A/C.
NOTICE
The air conditioning function will not operate if the temperature is lower than 65°F.
Press or when the A/C is on ("A/C LOW" or "A/C HIGH" shows).
The notch on the temperature bar moves. The A/C will automatically turn on and off to maintain this temperature.
HOURS 00000
APU
HEAT LOW
CH
HOURS 00000
APU
HEAT HIGH
OFF
CH
OFF
HOURS 00000
APU
A/C LOW
CH
HOURS 00000
APU
A/C HIGH
CH
62-11175 COMFORTPRO SERVICE MANUAL
1-5
Press to toggle between low, high and off.
The speed of the fan may automatically change when the heat or A/C comes on, then automatically change back when the heat or A/C goes off.
You can still have the fan working even when the temperature is not low or high enough for the heat or A/C to come on.
The fan operation is independent of the air conditioning and heat modes. When the fan speed is manually set to high or low, the fan will return to that setting when the desired temperature has been reached as the air conditioning or heat cycles off.
1.2.7 Fan Operation
1.3.1 Password Protection
1.3 AUTOMATIC OPERATIONS
You can add a password to the DCP, then you can protect one or more functions so that only a person who knows the password can set the function.
On a newly installed DCP, the password is always 000, which means that no password protection is in place.
To password-protect functions, first change the factory password; see 'Setting up for Password Protection'. All functions will now be password protected. Then remove password protection from chosen functions, as desired; see 'Protect Functions with a Password'.
If you know the password, you can change it at any time, if you need to. Note that if you change the password to 000, you will remove password protection from all functions.
If the password is ever lost, contact your dealer to have the password reset to 000.
Setting up for PASSWORD PROTECTION
1 Press .
2 Press or until "SET/CHANGE PASSWORD" is displayed,
then press .
"ENTER PASSWORD" is displayed with three blank squares, one for each digit in the password. The first digit flashes.
HOURS 00000
APU
CH
HOURS 00000
APU
CH
FAN
LOW
FAN
HIGH
HOURS 00000
ENTER PASSWORD
APU
000
OFF
OFF
62-11175 COMFORTPRO SERVICE MANUAL
1-6
When you try to set up a function, you may be prompted to enter the password.
1 Press or until the first number in the password
is displayed, then press .
2 Repeat for each digit in the password.
3 Press again after entering the last digit.
1.3.2 Entering the Password
3
Press or until the first number in the password is displayed
.
For example, if your password is "432" press until "4" shows,
then press .
4 Repeat for each digit in the password.
5 Press again after entering the last digit. "NEW PASSWORD"
is displayed.
6 Repeat the above steps to enter the new password. "CONFIRM"
is displayed.
7 Enter the new password again, then press to exit this function.
PROTECT FUNCTIONS with a PASSWORD
1 Press .
2 Press or until
"PASSWORD PROTECT" is displayed, then press .
If this menu item does not appear, then you have not yet changed the factory password from 000. Change the password and then try again. "ENTER PASSWORD" is displayed with three blank squares, one for each digit in the password. The first square flashes.
3 Press or until the first number in the password is
displayed, then press .
4 Repeat for each digit in the password.
5 Press again after entering the last digit.
The first feature that can be password protected is displayed with "YES" or "NO" (indicating whether it is currently password protected).
6 Press or to change the "YES" or "NO".
7 Press to move to the next feature.
Or press or to skip to the next feature.
HOURS 00000
APU
PASSWORD
PROTECT
OFF
OFF
62-11175 COMFORTPRO SERVICE MANUAL
1-7
1.3.3 Setting the Clock
1 Press
.
2 Press or until "CLOCK"
is displayed, then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
The clock function takes you through several settings: 12/24-hour-clock, hour set, minutes set, am/pm-set (for 12-hour clock only), and day of the week.
You can set the clock on the DCP. This clock is used by the Timer function (page 1-8). If you use the Timer function, remember that as you move from one time zone to another, you must adjust the clock. Otherwise the Timer will start the APU at the wrong time.
The clock settings remain even when the APU is turned off.
3 Press or to change the setting.
4 Press to move to the next setting. Or press to cancel any
changes you have not yet accepted.
5 When done, press to exit.
1.3.4 Comfort Monitor
You can specify the temperature you want in the truck bunk. Whenever the truck bunk temperature goes 2° above or below this temperature, the APU starts and the HVAC turns on until that temperature is reached or for fifteen minutes, whichever is longer.
Turning COMFORT Monitor ON and OFF
1 Press .
2 Press or until
"COMFORT MONITOR" is displayed,
then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
The current setting remains until you change it; turning off the APU or manually starting the APU does not permanently cancel this setting.
NOTICE
The clock does not automatically adjust for time zone changes; you must adjust it.
HOURS 00000
APU
CLOCK
HOURS 00000
CLOCK: SET MODE
APU
12 HOUR
OFF
OFF
HOURS 00000
COMFORT MONITOR:
APU
ON
62-11175 COMFORTPRO SERVICE MANUAL
1-8
You can set up the ComfortPro so that the
APU and CCU run automatically for
a specified
time on specified days of the week. There are two timers, so you
can set up two schedules.
For example, one schedule may be to run every day at 6:00 p.m. for .5 hours and the other schedule may be to run every Monday at 6.00 a.m. for .5 hours.
You must set up the timer as follows: Specify the day and time you want the APU to run, specify the duration (the length of time you want the APU to run for) and specify the temperature you want maintained in the truck bunk while the APU is running.
Turning TIMER On or Off
1 Press .
2 Press or until
"TIMER 1" or "TIMER 2" is displayed,
then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
The current setting remains until you change it; turning off the APU or manually starting the APU does not cancel the timer function.
1.3.5 Timer
Setting the TEMPERATURE
1 Press .
NOTICE
Factory Default Temperature Setting is 21°C / 70°F. Range is 18°C / 64°F to 30°C / 86°F.
2 Press or until
"COMFORT MONITOR" is displayed, then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET".
4
Press to confirm this setting. The current temperature is displayed.
5 Press or to scroll to the desired temperature.
6 Press to confirm this setting. Or press to cancel and
retain the current temperature.
7 Press to exit.
HOURS 00000
COMFORT MONITOR
APU
SET
HOURS 00000
TIMER 1
APU
ON
OFF
OFF
T
1
Loading...
+ 38 hidden pages