Carrier ComfortPro PC6000, ComfortPro PC6002, ComfortPro PC6006, ComfortPro PC6003 Operation & Service Manual

Page 1
R
62--11175 Rev --
Operation & Service Manual
for
ComfortPro
Auxiliary
Power Unit
Models PC6000, PC6002, PC6003 & PC6006
Page 2
62-11175 COMFORTPRO SERVICE MANUAL
c-i
CONTENTS
INTRODUCTION
SAFETY
Safety Alerts ................................................................................. c-iii
Component Layout.......................................................................... c-v
GENERAL ARRANGEMENT
APU Dimensions ............................................................................ c-vi
CCU Dimensions........................................................................... c-vii
Condenser Dimensions ................................................................. c-vii
1.0 OPERATION OF MULTI–FUNCTION D.C.P
1.1 PREPARATION
1.1.1 Multi–Function D.C.P Components....................................... 1-1
1.1.2 How the ComfortPro Operates ............................................. 1-2
1.2 MANUAL OPERATIONS
1.2.1 Starting the APU ................................................................ 1-3
1.2.2 Stopping the APU ............................................................... 1-3
1.2.3 Turning the Heater ON/OFF ................................................. 1-4
1.2.4 Heating: Setting the Temperature ........................................ 1-4
1.2.5 Turning the A/C ON/OFF ..................................................... 1-4
1.2.6 Setting the A/C Temperature .............................................. 1-4
1.2.7 Fan Operation .................................................................... 1-5
1.3 AUTOMATIC OPERATIONS
1.3.1 Password Protection........................................................... 1-5
1.3.2 Entering Password ............................................................. 1-6
1.3.3 Setting the Clock ............................................................... 1-7
1.3.4 Comfort Monitor................................................................. 1-7
1.3.5 Timer ................................................................................ 1-8
1.3.6 Cold Weather Watch ......................................................... 1-10
1.3.7 Maximum Run Time.......................................................... 1-11
1.3.8 Battery Monitoring............................................................ 1-12
2.0 CLIMATE CONTROL UNIT (CCU)
2.1 PREPARATION
2.1.1 Charging the CCU............................................................... 2-1
2.2 SERVICE
2.1.2 Maintenance Schedule ....................................................... 2-2
2.1.2 CCU Spring Tune–Up .......................................................... 2-3
3.0 TROUBLESHOOTING
3.0 MANUAL OPERATIONS
3.1 APU (Auxiliary Power Unit)............................................................... 3-2
3.2 GENERATOR .................................................................................. 3-6
3.3 DRIVER CONTROL PANEL ............................................................... 3-7
3.4 CCU AIR CONDITIONING ................................................................. 3-8
3.5 CCU Fan ..................................................................................... 3-11
3.6 CCU Heat.................................................................................... 3-11
3.7 RECEPTACLE PANEL..................................................................... 3-12
Page 3
62-11175 COMFORTPRO SERVICE MANUAL
c-ii
3.0 TROUBLESHOOTING (Cont.)
3.8 TESTING PROCEDURES
3.8.1 Testing AMP draw for components ....................................... 3-13
3.8.2 Testing Voltage and Hz readings .......................................... 3-13
3.9 ADDITIONAL INFORMATION
3.9.1 Adjusting the 120 A/C Voltage............................................. 3-14
3.9.2 Capacitor Troubleshooting ................................................... 3-14
3.9.3 Capacitor Theory................................................................. 3-14
3.9.4 Potential Relay Theory......................................................... 3-15
3.9.5 Alternator Troubleshooting................................................... 3-15
APPENDICES
CAPACITIES AND SPECIFICATIONS ........................................................... A-2
FUSE LOCATIONS ................................................................................... A-4
CIRCUIT BREAKER LOCATIONS ................................................................ A-5
APU CONTROL UNIT................................................................................ A-6
CCU CONTROLLER.................................................................................. A-7
FUEL SYSTEM PURGE PROCEDURE ......................................................... A-8
COOLANT PURGE PROCEDURE ................................................................ A-9
DEFROST/HEAT & DCP SENSOR............................................................ A-11
ENGINE INTERLOCK.............................................................................. A-12
APU WIRING (Serial# KZX98002290 to Date) ......................................... A-13
Page 4
62-11175 COMFORTPRO SERVICE MANUAL
c-iii
SAFETY
DANGER
Immediate hazards that will result in severe personal injury or death.
WARNING
Hazards or unsafe practices that could result in severe personal injury or death.
CAUTION
Hazards or unsafe practices that could result in minor injury or product or property damage.
NOTICE
Information that is important to proper installation or maintenance, but is not hazard-related.
DANGER
A certified refrigeration technician must charge and test the CCU.
For example:
Safety Alerts
Throughout this manual, you will see notes labeled "Warnings" or "Cautions" to alert you to special instructions or precautions concerning a particular procedure that would be hazardous if performed incorrectly or carelessly.
Observe them carefully!
These safety alerts alone cannot eliminate hazards that can occur. Strict compliance with these special instructions when performing the installation and maintenance, plus common sense, are major accident prevention measures.
Page 5
62-11175 COMFORTPRO SERVICE MANUAL
c-iv
Safety Considerations
Inhalation of exhaust gas (containing carbon monoxide) may cause severe personal injury and/or death. Anyone suspected of suffering from CO inhalation should be removed from the hazardous area and given medical assistance immediately.
Exercise extreme caution when working near fuel or fuel-filled equipment. Do not operate equipment during fueling operations. Use eye protection when working near batteries, which contain acid and can explode. Do not smoke or use open flames near batteries.
Electric shock can cause severe personal injury, burns, and death. Before working on any unit, disconnect the batteries. Use only approved materials and methods when working on the electrical system, and follow local electrical codes. Never work on the APU or the electrical circuitry when the APU is running. Never work with electricity in wet conditions or when you are tired.
Fuel, oil, coolant, and refrigerant are toxic and in some cases, carcinogenic. Wear eye and hand protection at all times. Remove contaminated clothing immediately and wash contaminated skin. Do not breathe in vapors.
Moving parts can cause severe injury and/or death. Before working on any unit, shut it off and disconnect the battery. Do not start until protective covers have been replaced. Also, loose parts falling into rotating machinery can cause severe accidents. Always ensure bolts and clamps are correctly torqued and secured. Inspect mechanical components periodically for damage, corrosion, and proper torque.
The APU is designed to provide electrical power for heating and cooling vehicles in normal on-road conditions. Never use the APU to power critical medical equipment or sensitive electronic equipment without the manufacturer's express written approval.
Exhaust
Fuel/Batteries
Electrical
Intoxicants
Hot or Moving Parts
Misuse
WARNING
California Proposition 65 Warning: This product contains lead, a chemical known to the State of California to cause cancer and birth defects and other reproductive harm.
Page 6
62-11175 COMFORTPRO SERVICE MANUAL
c-v
COMPONENT LAYOUT
Figure C1: Main Components of the Carrier ComfortPro system and Where They Should Best be Installed on the Truck
COOLANT SUPPLY
AND RETURN
PANEL (DCP)
DRIVER CONTROL
CONDENSER
120 VAC
RECEPTACLE PANEL
UNIT (CCU)
CLIMATE CONTROL
BATTERY
VEHICLE FUEL TANK
AND RETURN
FUEL SUPPLY
AUXILIARY POWER UNIT (APU)
Page 7
62-11175 COMFORTPRO SERVICE MANUAL
c-vi
GENERAL ARRANGEMENT
TOP VIEW
REAR
LEFT SIDE
APU Dimensions (Measurements in inches)
FRONT VIEW
RIGHT SIDE
3.0
2.75 3.875
18.5
16.0
10.5
2.6
24.9
28.5
Page 8
62-11175 COMFORTPRO SERVICE MANUAL
c-vii
FRONT VIEW
BOTTOM VIEW
CCU Dimensions (Measurements in inches)
FRONT RIGHT SIDE
DOWN
Condenser Dimensions (Measurements in inches)
12"
7.9"
23.4"
24.4"
16.2"
15.2"
3.3"
3.1"
3.0"
6.9"
3.0"
6.9"
3.0"
3.4"
3.0"
12.6"
.125"
1.3"
12.9"
5.62"
13.93"
16.25"
16.90"
5.62"
26.5"
24.25"
8"
3.5"
2.0"
Page 9
62-11175 COMFORTPRO SERVICE MANUAL
c-viii
Page 10
62-11175 COMFORTPRO SERVICE MANUAL
1-1
1.0
OPERATION OF MULTI-FUNCTION DRIVER CONTROL PANEL
Figure 1-0: Multi-Function Driver Control Panel
1.1.1 Multi-Function Driver Control Panel Components
1 When visible, the heating system is heating.
2 When visible, the A/C is cooling.
3 Indicates the number of operating hours on the APU.
4 Indicates the state of the APU.
The APU engine is running.
The APU engine is off.
The APU engine is in the starting process (flashing).
5 Indicates that Battery Monitor mode is enabled.
6 Indicates that maximum run time is enabled.
7 Indicates that Cold Weather Watch mode is enabled.
8 Indicates that Comfort Monitor mode is enabled.
9 Indicates that Timer 1 or Timer 2 mode is enabled.
10 Indicates that the ComfortPro is connected to shore power.
The APU cannot be started in Shore Power mode.
11 Indicates the state of the 115V outlet and CCU auto-reset breakers.
115 VAC power is being supplied to the outlet.
No power is being supplied to the outlet.
CCU breaker has tripped. High Heat/Outlet breaker has tripped.
The breaker that tripped has reset automatically and the DCP needs to be reset.
NOTICE
The DCP (driver control panel), which is mounted inside the truck bunk, controls the APU and the CCU. The central panel on the DCP provides status information using words and icons:
PREPARATION 1.1
4 5
3
APU
ON/OFF
2
MENU
HOURS 00000
6 7 8 9
APU
A/ C FAN HEAT
1
10 11
SP
T2T
1
HVAC
OFF
ESC/
RESET
APU
APU
APU
T2T
1
OFF
TRIP
TRIP
RE­SET
Page 11
62-11175 COMFORTPRO SERVICE MANUAL
1-2
1.1.2 How the ComfortPro Operates
The ComfortPro has two modes of operation: manual and automatic.
Manual Mode
You start the APU from within the truck bunk using the On/Off button on the driver control panel (DCP). Once the APU is running, you can start and stop the fan, heater and air conditioning using the DCP. See page 1-3.
Once the heater or A/C is running, it will cycle (automatically turn on and off) in order to keep the truck bunk at the temperature you specify. The HVAC will continue to cycle until you turn it off. While the HVAC is cycling, the APU remains on and will only turn off when you manually turn it off using the button on the DCP.
Note that in manual mode, the APU remains on until you turn it off. But in Comfort Monitor mode (described below), the APU automatically turns off and on as required.
When the APU is running, power is supplied to the power outlet in the truck bunk (except in high heat).
In manual mode, the APU will turn off automatically if the Maximum Run Time is reached.
Automatic Mode
The ComfortPro has several functions that will start it in automatic mode.
Comfort Monitor
(page 1-7)
FEATURE DESCRIPTION
The APU and HVAC automatically turn on to maintain a comfortable temperature in the truck bunk. When the desired temperature is met, the APU and HVAC automatically turn off. When the temperature is again out of range, they will both turn on again, and cycle heat and air conditioning as needed.
Timer
(page 1-8)
At the specified time, the APU and HVAC automatically turn on. During the specified timer duration, the HVAC cycles on and off to maintain the desired temperature. When the timer duration expires, both the APU and HVAC turn off automatically and remain off.
Cold Weather Watch
(page 1-10)
The APU and heater on the HVAC automatically turn on in order to prevent the APU engine and truck engine from getting too cold. (Turning on the heater creates a “load” that makes the APU work harder and therefore warm up faster). Both the APU and HVAC turn off automatically once the preset duration time expires.
The APU automatically turns on for 90 minutes in order to recharge the batteries. The HVAC does not turn on. After the 90 minute run time, the system will sense voltage for 10 minutes, before restarting if needed.
Battery Monitor
(page 1-12)
There are icons on the DCP that flash when the APU and HVAC are running. See page 1-1. If you enter the truck bunk and APU or HVAC is on but you did not start it, you can assume it has started in one of the automatic modes, as described above. On the DCP, one icon will be flashing steadily: this is the icon for the mode that is currently operating.
Whenever the ComfortPro is running in automatic mode, if you then press the heat, A/C or fan buttons on the DCP, the ComfortPro will switch to manual mode. The APU will not automatically turn off! This icon on the DCP will also stop flashing.
Page 12
62-11175 COMFORTPRO SERVICE MANUAL
1-3
Automatic Mode and Minimum Time Off
All these automatic functions work on a "minimum time off": the ComfortPro must be off for at least 10 minutes before the automatic function will turn it on again. For example, the Timer function may be set to turn on the ComfortPro at 10:00 a.m. You have been running the ComfortPro in manual mode. You turn off the ComfortPro at 9:55 a.m. The timer will only turn on the ComfortPro again 10 minutes later, at 10:05 a.m.
Clock
In order to use the Timer correctly, you must set the DCP clock. See page 1-7.
Maximum Run Time
You can set the maximum time that the APU is allowed to continuously run in manual mode. See page 1-11.
Password Protection
You can add a password to the DCP, then you can protect one or more functions so that only a person who knows the password can set the function. See page 1-5.
WARNING
Do not start the APU when the enclosure cover is removed. Operating with the cover off may result in injury and/or death.
Press and release once.
The display shows "PLEASE WAIT – APU STARTING" and flashes.
When stops flashing, then the APU has started successfully.
The APU startup sequence consists of 20 seconds of glowing (30 seconds when the ambient temperature is below -5°C or 23°F) and up to 10 seconds of cranking.
If the sequence fails, "RESTARTING" appears for six seconds. Then the startup sequence automatically repeats up to five times or until the APU starts.
If "CRANK LIMIT" appears, see Troubleshooting section.
APU
APU
WARNING
When the APU is about to start, a buzzer sounds. Make sure no one is standing near the APU or touching it.
1.2.1 Starting the APU "One Touch Start"
Press
.
The APU will stop. The display shows .
APU
1.2.2 Stopping the APU
1.2 MANUAL OPERATIONS
HOURS 00000
APU
PLEASE WAIT
APU STARTING
HOURS 00000
APU
RESTARTING
HOURS 00000
APU
CRANK LIMIT
HOURS 00000
APU
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Page 13
62-11175 COMFORTPRO SERVICE MANUAL
1-4
1 Press to activate the heater.
The display shows "HEAT LOW".
The heater will turn on only if the temperature is too low (to adjust the temperature, see below). When the heater is on, appears.
2 Press again to switch between
high and low heat to heat the truck bunk more or less quickly. In "HEAT HIGH" mode, the power outlet is disabled and the display indicates .
The heat or A/C will turn off when the desired temperature is reached.
3 Press to deactivate heating.
NOTICE
The heat mode will not function if the temperature is higher than 85°F.
1.2.3 Turning the Heater ON/OFF
1.2.4 Heating: Setting the Temperature
1.2.5 Turning the A/C ON or OFF
1.2.6 A/C Setting the Temperature
Press or when the heater is on ("HEAT LOW"or "HEAT HIGH" shows).
The notch on the temperature bar moves. The heater will automatically turn on and off to maintain this temperature.
1 Press to activate the A/C.
The display shows "A/C LOW".
The A/C will turn on only if the temperature is too high (to adjust the temperature, see below). When the A/C is on, appears.
2 Press again to switch between
high and low A/C to cool the truck bunk more or less quickly.
3 Press to deactivate the A/C.
NOTICE
The air conditioning function will not operate if the temperature is lower than 65°F.
Press or when the A/C is on ("A/C LOW" or "A/C HIGH" shows).
The notch on the temperature bar moves. The A/C will automatically turn on and off to maintain this temperature.
HOURS 00000
APU
HEAT LOW
CH
HOURS 00000
APU
HEAT HIGH
OFF
CH
OFF
HOURS 00000
APU
A/C LOW
CH
HOURS 00000
APU
A/C HIGH
CH
Page 14
62-11175 COMFORTPRO SERVICE MANUAL
1-5
Press to toggle between low, high and off.
The speed of the fan may automatically change when the heat or A/C comes on, then automatically change back when the heat or A/C goes off.
You can still have the fan working even when the temperature is not low or high enough for the heat or A/C to come on.
The fan operation is independent of the air conditioning and heat modes. When the fan speed is manually set to high or low, the fan will return to that setting when the desired temperature has been reached as the air conditioning or heat cycles off.
1.2.7 Fan Operation
1.3.1 Password Protection
1.3 AUTOMATIC OPERATIONS
You can add a password to the DCP, then you can protect one or more functions so that only a person who knows the password can set the function.
On a newly installed DCP, the password is always 000, which means that no password protection is in place.
To password-protect functions, first change the factory password; see 'Setting up for Password Protection'. All functions will now be password protected. Then remove password protection from chosen functions, as desired; see 'Protect Functions with a Password'.
If you know the password, you can change it at any time, if you need to. Note that if you change the password to 000, you will remove password protection from all functions.
If the password is ever lost, contact your dealer to have the password reset to 000.
Setting up for PASSWORD PROTECTION
1 Press .
2 Press or until "SET/CHANGE PASSWORD" is displayed,
then press .
"ENTER PASSWORD" is displayed with three blank squares, one for each digit in the password. The first digit flashes.
HOURS 00000
APU
CH
HOURS 00000
APU
CH
FAN
LOW
FAN
HIGH
HOURS 00000
ENTER PASSWORD
APU
000
OFF
OFF
Page 15
62-11175 COMFORTPRO SERVICE MANUAL
1-6
When you try to set up a function, you may be prompted to enter the password.
1 Press or until the first number in the password
is displayed, then press .
2 Repeat for each digit in the password.
3 Press again after entering the last digit.
1.3.2 Entering the Password
3
Press or until the first number in the password is displayed
.
For example, if your password is "432" press until "4" shows,
then press .
4 Repeat for each digit in the password.
5 Press again after entering the last digit. "NEW PASSWORD"
is displayed.
6 Repeat the above steps to enter the new password. "CONFIRM"
is displayed.
7 Enter the new password again, then press to exit this function.
PROTECT FUNCTIONS with a PASSWORD
1 Press .
2 Press or until
"PASSWORD PROTECT" is displayed, then press .
If this menu item does not appear, then you have not yet changed the factory password from 000. Change the password and then try again. "ENTER PASSWORD" is displayed with three blank squares, one for each digit in the password. The first square flashes.
3 Press or until the first number in the password is
displayed, then press .
4 Repeat for each digit in the password.
5 Press again after entering the last digit.
The first feature that can be password protected is displayed with "YES" or "NO" (indicating whether it is currently password protected).
6 Press or to change the "YES" or "NO".
7 Press to move to the next feature.
Or press or to skip to the next feature.
HOURS 00000
APU
PASSWORD
PROTECT
OFF
OFF
Page 16
62-11175 COMFORTPRO SERVICE MANUAL
1-7
1.3.3 Setting the Clock
1 Press
.
2 Press or until "CLOCK"
is displayed, then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
The clock function takes you through several settings: 12/24-hour-clock, hour set, minutes set, am/pm-set (for 12-hour clock only), and day of the week.
You can set the clock on the DCP. This clock is used by the Timer function (page 1-8). If you use the Timer function, remember that as you move from one time zone to another, you must adjust the clock. Otherwise the Timer will start the APU at the wrong time.
The clock settings remain even when the APU is turned off.
3 Press or to change the setting.
4 Press to move to the next setting. Or press to cancel any
changes you have not yet accepted.
5 When done, press to exit.
1.3.4 Comfort Monitor
You can specify the temperature you want in the truck bunk. Whenever the truck bunk temperature goes 2° above or below this temperature, the APU starts and the HVAC turns on until that temperature is reached or for fifteen minutes, whichever is longer.
Turning COMFORT Monitor ON and OFF
1 Press .
2 Press or until
"COMFORT MONITOR" is displayed,
then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
The current setting remains until you change it; turning off the APU or manually starting the APU does not permanently cancel this setting.
NOTICE
The clock does not automatically adjust for time zone changes; you must adjust it.
HOURS 00000
APU
CLOCK
HOURS 00000
CLOCK: SET MODE
APU
12 HOUR
OFF
OFF
HOURS 00000
COMFORT MONITOR:
APU
ON
Page 17
62-11175 COMFORTPRO SERVICE MANUAL
1-8
You can set up the ComfortPro so that the
APU and CCU run automatically for
a specified
time on specified days of the week. There are two timers, so you
can set up two schedules.
For example, one schedule may be to run every day at 6:00 p.m. for .5 hours and the other schedule may be to run every Monday at 6.00 a.m. for .5 hours.
You must set up the timer as follows: Specify the day and time you want the APU to run, specify the duration (the length of time you want the APU to run for) and specify the temperature you want maintained in the truck bunk while the APU is running.
Turning TIMER On or Off
1 Press .
2 Press or until
"TIMER 1" or "TIMER 2" is displayed,
then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
The current setting remains until you change it; turning off the APU or manually starting the APU does not cancel the timer function.
1.3.5 Timer
Setting the TEMPERATURE
1 Press .
NOTICE
Factory Default Temperature Setting is 21°C / 70°F. Range is 18°C / 64°F to 30°C / 86°F.
2 Press or until
"COMFORT MONITOR" is displayed, then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET".
4
Press to confirm this setting. The current temperature is displayed.
5 Press or to scroll to the desired temperature.
6 Press to confirm this setting. Or press to cancel and
retain the current temperature.
7 Press to exit.
HOURS 00000
COMFORT MONITOR
APU
SET
HOURS 00000
TIMER 1
APU
ON
OFF
OFF
T
1
Page 18
62-11175 COMFORTPRO SERVICE MANUAL
1-9
Setting the Start Time/Day
1 Press .
2 Press or until
"TIMER 1" or "TIMER 2" is displayed,
then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET START".
4 Press to confirm this setting. The current start time is displayed.
5 Press or to set the hours, minutes and day.
6 Press to confirm each setting.
Setting the DURATION
1 Press .
2 Press or until
"TIMER 1" or "TIMER 2" is displayed,
then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET DURATION".
4
Press to confirm this setting. The current duration time is displayed.
5 Press or to scroll to the length of time to run the APU.
6 Press to confirm this setting. Or press to cancel and
retain the current duration.
7 Press to exit.
NOTICE
Factory Default Duration Setting
is 1 hour. Range is 0.5 hrs - 10 hrs (in 0.5 hr increments).
Setting the TEMPERATURE for the Timer
1 Press .
2 Press or until
"TIMER 1 or TIMER 2" is displayed,
then press .
NOTICE
Factory Default Temperature
Setting is
21°C / 70°F. Range is
18°C / 64°F to
30°C / 86°F.
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET TEMP".
4
Press to confirm this setting. The current temperature is displayed.
5 Press or to scroll to the desired temperature.
6 Press to confirm this setting. Or press to cancel and
retain the current temperature.
7 Press to exit.
HOURS 00000
TIMER 1
APU
SET START
OFF
T
OFF
1
HOURS 00000
TIMER 1
APU
SET DURATION
OFF
T
OFF
1
HOURS 00000
TIMER 1
APU
SET TEMP
T
1
OFF
OFF
Page 19
62-11175 COMFORTPRO SERVICE MANUAL
1-10
Setting the START TEMPERATURE
1 Press .
2 Press or until
"TEMP START" is displayed, then press .
NOTICE
Factory Default Temperature
Setting
-10°C / 14°F. Range is -
20°C / -4°F to
5°C / 41°F.
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET TEMP".
4 Press to confirm this setting. The current start temperature
is displayed.
5 Press or to scroll to the desired start temperature.
6 Press to confirm this setting. Or press to cancel and
retain the current start temperature.
7 Press to exit.
1.3.6 Cold Weather Watch
Turning Cold weather watch On and Off
1 Press .
2 Press or until
"TEMP START" is displayed, then
press .
You can set up the APU so that it automatically runs for a specified time whenever the ambient temperature goes below a specified value. This feature ensures that the APU engine and truck engine do not get so cold that they will not start.
This feature is not intended to maintain a comfortable truck bunk temperature; instead, see “Comfort Monitor”.
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
The current setting remains until you change it; turning off the APU or manually starting the APU does not permanently cancel this setting.
HOURS 00000
TEMP START
APU
ON
HOURS
00000
TEMP START : SET TEMP
APU
-10C 14F
OFF
OFF
OFF
OFF
Page 20
62-11175 COMFORTPRO SERVICE MANUAL
1-11
Setting the DURATION
1 Press .
2 Press or until
"TEMP START" is displayed, then press .
NOTICE
Factory Default Duration Setting
is 2 hours. Range is 1 hr to 4 hrs.
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET DURATION".
4 Press to confirm this setting. The current duration is displayed
in hours.
5 Press or to scroll to the
amount of time you want the APU to run before automatically shutting off.
6 Press to confirm this setting.
Or press to cancel and retain the current start temperature.
7 Press to exit.
You can set the maximum time that the APU is allowed to run continuously. If the APU runs for longer than the specified time, it automatically shuts off. You can then start it manually, if desired; the "run time" clock will start counting again.
Turning MAXIMUM RUN TIME ON OR OFF
1 Press .
2 Press or until
"MAXIMUM RUN TIME" is displayed, then press .
NOTICE
Factory Default Run Time Setting is 8 hours. Range is 2 to 24 hours.
1.3.7 Maximum Run Time
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
Setting the DESIRED RUN TIME
1 Press .
2 Press or until
"MAXIMUM RUN TIME" is displayed, then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET".
4 Press to confirm this setting.The current duration is displayed.
5 Press or to scroll to the desired number of hours.
6 Press to confirm this setting. Or press to cancel and
retain the current duration.
7 Press to exit.
HOURS 00000
TEMP START
APU
SET DURATION
OFF
OFF
HOURS 00000
TEMP START : DURATION
APU
OFF
OFF
1.0 hrs
HOURS 00000
MAXIMUM RUN TIME
APU
ON
HOURS 00000
MAXIMUM RUN TIME
APU
SET
Page 21
62-11175 COMFORTPRO SERVICE MANUAL
1-12
Turning BATTERY MONITORING ON and OFF
1 Press .
2 Press or until
"BATTERY MONITOR" is displayed, then press .
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
The current setting remains until you change it; turning off the APU or manually starting the APU does not permanently cancel this setting.
The APU starts if the battery voltage goes below the level you specify here.
Setting the Voltage Level
1 Press .
2 Press or until
"BATTERY MONITOR" is displayed, then press .
NOTICE
Factory Default Voltage Setting is
11.8V.
Range is 11.0V to 13.5V.
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET".
4 Press to confirm this setting. The current voltage level is
displayed and flashes.
5 Press or to scroll to the desired voltage.
6 Press to confirm this setting. Or press to cancel and
retain the current voltage.
7 Press to exit.
You can set up the APU so that it automatically runs for 90 minutes when the truck batteries are low.
When you set up this feature, you must enter the current voltage of the batteries (see “Set the Initial Voltage”). The ComfortPro can then calculate how much the voltage drops, as the batteries are used.
Set the INITIAL VOLTAGE
1. Press .
2 Press or until
"CALIBRATE VOLTAGE" is displayed, then press .
1.3.8 Battery Monitoring
If "ENTER PASSWORD" is displayed, enter your password. If you do not know the password, then you cannot set up this function (see page 1-5).
3 Press or to set the current voltage of the batteries.
4 Press to confirm this setting.
HOURS 00000
APU
CALIBRATE
VOLTAGE
HOURS
00000
BATTERY MONITOR
APU
ON
OFF
OFF
OFF
OFF
HOURS 00000
BATTERY MONITOR : SET
APU
11.8 V
OFF
OFF
MENU
Page 22
62-11175 COMFORTPRO SERVICE MANUAL
2-1
NOTICE
The air conditioning system has a 5 minute delay timer (minimum time between cycles is 5 minutes).
CLIMATE CONTROL UNIT (CCU)
1 Pressure test the system for leaks with nitrogen.
2 Vacuum all the nitrogen for a minimum of 30 minutes to 500 microns.
3 With the high and the low side valves open, charge the system with
R-134A
vapor to break the vacuum. Once the scale stabilizes and the
high and the low side pressures match, close the high side valve.
4 With only the low side valve open, start the A/C compressor by
selecting High A/C (APU Running). If needed lower the temperature set point to start the A/C compressor.
5 Continue charging the system with vapor, on the low side only, until a
total of 64–68 oz of R-134A refrigerant has been added as measured by the scale.
Figure 2- 1: Connecting hoses to CCU to Condenser
RED
LOW
BLUE
SCALE 64–68 OZ
CCU
CONDENSER
CAUTION
Vapor charge CCU only.
2.0
WARNING
This procedure must be performed by a certified air conditioning technician who has experience with hermetic systems and Refrigerant R-134A.
NOTICE
Total System Capacity is 64–68 oz.
A scale must be used to measure the
refrigerant weight. No other method is acceptable. Failure to follow this procedure exactly will result in improper air conditioning function.
NOTICE
Refrigerant Recovery:
Venting of refrigerant is against the law and subject to fines and loss of certification.
EPA regulations require that all CFC and HCFC refrigerants be recovered before any system can be opened for service.
Recovery of refrigerant is done using a certified recovery unit.
• Before a refrigeration system can be opened to make repairs.
• Before pressurizing the system with nitrogen for leak testing.
Before disposing of any system or
component containing refrigerants.
• When it is necessary to remove excess charge from an overcharged system.
HIGH
2.1.1 Charging the CCU
PREPARATION
2.1
Page 23
62-11175 COMFORTPRO SERVICE MANUAL
2-2
2.2.1 Maintenance Schedule
2.2 SERVICE
First Every
Interval between checks (in hours of operation) 50 1000 2000
Change oil and oil filter x x Check fuel hoses, fuel pipes, and clamps x x Check fasteners, muffler clamps and frame grippers x x Check battery cable connections x x Check coolant hoses and clamps x x Check alternator fan belt tension x x Check generator belt tension x x Check APU air filter, clean or replace as necessary x Change fuel filters x Change fan belt regardless of condition x Adjust valve lash x Clean inside enclosure x Clean radiator fins x Clean condenser fins x Check CCU air filter, clean or replace as necessary. To clean, remove the
filter and vacuum or wash (soap and water). Shake dry and reattach. x Check injection nozzle opening pressure x Check injection pump timing x Check water pump performance x Check alternator performance x Check starter performance x Check air conditioning performance (HVAC) x Check heater performance (HVAC) x Check generator line voltage x Check coolant hoses and clamps (from APU to main engine) x Check engine thermostat x Check air intake hose and clamps on APU x Check fuel hoses and clamps x
Page 24
62-11175 COMFORTPRO SERVICE MANUAL
2-3
2.2.2 CCU Spring Tune-Up
Purpose:
Recommended service and maintenance:
• Condenser.
• Air ducting and outlets.
• Evaporator and temperature sensor.
• Refrigerant lines connections and routing.
• Harness Connections and wiring.
• A/C operating efficiency - charge level.
Frequency:
Annually – preferably in the spring for the coming A/C season.
Recommended 1. Check the condenser for:
Service Actions: Damage, leakage and/or contaminated fins that may restrict air flow.
2. Check air ducting and outlets for:
Damage and/or restrictions.
3. Check electrical harnesses for:
Tight connections and harness abrasions.
4. Check the evaporator for:
• Intake filter cleanliness, clean if required.
• Damaged and/or contaminated fins that may restrict air flow.
Refrigerant leaks indicated by wet spots or dark stains on the evaporator fins and connections.
• Check evaporator temperature sensor for proper function (see chart).
COMFORTPRO CCU EVAPORATOR DEFROST SENSOR TEMPERATURE – RESISTANCE CHART
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
60 65 70 75 80 85 90 95 100 105 110 115 120
TEMPERATURE (°F)
kOhm
77°F, 100 kOhm
5. Check the Refrigerant lines and connections for:
• Abrasion and wear points.
• Connection wet spots that may indicate refrigerant leakage.
Page 25
62-11175 COMFORTPRO SERVICE MANUAL
2-4
6. Check the refrigerant charge level:
• Install the A/C gauges as shown in the ComfortPro Installation Manual. Operate the A/C on high.
• Refer to chart below for high and low reference pressure.
If level is not ok, recover and recharge the A/C system with the correct amount of refrigerant as shown on page 2-1.
7. Check the CCU drain:
For damage and that it operates correctly.
COMFORTPRO AIR CONDITIONING OUTDOOR AMBIENT TEMPERATURE AND PRESSURE CHART
OUTDOOR TEMPERATURE 70°F 95°F 110°F
SUCTION PRESSURE 20 PSI 35 PSI 45 PSI
DISCHARGE PRESSURE 110 PSI 175 PSI 225 PSI
OVERALL CURRENT 5-9 AMPS 9-12 AMP 12-15 AMP Note: A/C - High Measure at 120 volt teck cable
FAN ONLY AMP READING FAN LOW 1.2-1.5 AMP FAN HGH 1.8-2.2 AMP
If both suction and discharge pressure is lower than the chart, the system is undercharged.
If both suction and discharge pressure is higher than the chart, the system is overcharged.
Page 26
62-11175 COMFORTPRO SERVICE MANUAL
3-1
3.0 TROUBLESHOOTING
3.1 APU (AUXILIARY POWER UNIT) .....................................................3-2
3.2 GENERATOR...............................................................................3-6
3.3 DRIVER CONTROL PANEL ............................................................3-7
3.4 CCU AIR CONDITIONING ..............................................................3-8
3.5 CCU FAN ..................................................................................3-11
3.6 CCU HEAT ................................................................................3-11
3.7 RECEPTACLE PANEL .................................................................3-12
3.8 ADDITIONAL INFORMATION........................................................3-13
WARNING
Before undertaking ANY repair to the APU, CCU or component of the ComfortPro system disconnect the batteries from the APU.
Page 27
62-11175 COMFORTPRO SERVICE MANUAL
3-2
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
Engine does not start No fuel • Check fuel stand pipe length • A-8
(starter works)
Air in the fuel system Bleed air A-8
Water in fuel system Drain fuel tank(s) and replace
fuel filters
Fuel solenoid not pulling in Check for rust in plunger/check
for voltage
Check for bent solenoid linkage
Fuel pipe/line clogged Clean/replace
Fuel filters clogged Replace A-8
Excessively high viscosity of Use the specified engine oil A-2
engine oil at low temperature
Fuel leak due to loose injection Tighten nut
Kubota Manual
*
pipe retaining nut
Injection nozzle clogged/defective
Clean/replace
Kubota Manual
*
Injection pump defective Replace
Kubota Manual
*
Fuel lift pump defective Replace
Low cylinder compression Repair/replace engine
Kubota Manual
*
Valve spring broken, valve stuck Repair/replace
Kubota Manual
*
Excessive valve clearance Adjust
Kubota Manual
*
Glow plugs malfunctioning Check/replace
Kubota Manual
*
Plugged air filter Clean/replace
Kubota Manual
*
3.1 APU (AUXILIARY POWER UNIT)
Each symptom is followed by a probable cause and suggested solution. To isolate the possible cause, proceed in a systematic manner to determine the faulty component. This guide does not cover all possible situations that may occur under all conditions of operation.
Before using this guide verify correct voltage and ground to components.
WARNING
Disconnect the batteries from the APU before performing any repairs.
*Kubota Workshop Manual 97897-02400
Page 28
62-11175 COMFORTPRO SERVICE MANUAL
3-3
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
Engine does not start Low battery voltage to the APU Check battery cables/charge battery A-13
(starter does not work)
Starter/solenoid defective Repair/replace
Kubota Manual
*
Poor positive cable connection Check/repair
Poor ground cable connection Check/repair
Engine will not stop Starter solenoid jammed • Replace start solenoid or starter
Kubota Manual
*
Fuel solenoid bolt missing Check bolt
Speed control linkage broken Replace control linkage
Engine runs rough Fuel filters clogged or dirty Replace A-8
Air filter plugged or dirty Clean/replace A-3
Fuel leak due to loose injection Tighten nut
Kubota Manual
*
pipe retaining nut
Injection nozzle clogged/defective Clean/replace
Kubota Manual
*
Injection pump defective Replace
Kubota Manual
*
Uneven cylinder compression Repair/replace engine
Kubota Manual
*
Incorrect valve clearance Adjust
Kubota Manual
*
Fuel return line clogged/kinked Clean/replace
Kubota Manual
*
Governor defective Repair/replace
Smoking (white or Excessive engine oil Reduce to specified level A-2
blue exhaust)
Piston ring worn or stuck Repair/replace engine
Kubota Manual
*
Incorrect injector timing Repair
Kubota Manual
*
Low cylinder compression Repair/replace engine
Kubota Manual
*
Coolant in combustion chamber Repair/replace engine
Kubota Manual
*
Smoking (black or Overloaded power draw Reduce power consumption dark gray exhaust)
Low fuel grade Use specified fuel grade
Fuel filters clogged Replace A-3
Air cleaner clogged Clean/replace A-3
Unable to bleed coolant
Air lock Run Truck engine until 185°F A-9
No coolant flow
Check for blockages using flow indicator
Kinked coolant lines Straighten
Shut-off valves 'OFF' Turn 'ON'
Incorrect plumbing Re-plumb
Small fittings on truck engine Change to larger fittings (3/4")
Excessive oil Oil ring worn Replace
Kubota Manual
*
consumption
Piston ring groove worn Replace the piston
Kubota Manual
*
Valve stem and guide worn Replace
Kubota Manual
*
Crankshaft bearing and crank Replace
Kubota Manual
*
pin bearing worn
Air filter clogged Replace filter A-3
*Kubota Workshop Manual 97897-02400
Page 29
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
Oil level increases Diesel fuel getting to oil pan Replace O-ring in lower portion
Kubota Manual
*
through governor lever of governor lever
Fuel lift pump diaphragm defective
Replace
Kubota Manual
*
Low oil pressure Engine oil insufficient Replenish A-2
Oil strainer clogged Clean
Kubota Manual
*
Oil filter clogged Replace
Kubota Manual
*
Relief valve stuck with dirt Clean
Relief valve spring weakened Replace
or broken
Excessive oil clearance of Replace
Kubota Manual
*
crankshaft bearings
Excessive oil clearance of rocker Replace
Kubota Manual
*
arm boss
Oil passage clogged Clean
Different type of oil Use the specified type A-2
Oil pump defective Repair/replace
Kubota Manual
*
High oil pressure Different type of oil Use the specified type A-2
Relief valve defective Replace
Engine overheated Engine oil insufficient Replenish A-2
Fan belt broken or loose Repair/replace A-2
Air lock Check for air lock in Kubota engine A-9
and ensure there is coolant, purge if necessary
Coolant level insufficient Add coolant, purge if necessary A-9
Coolant flow is restricted Repair Plumbing
Thermostat stuck Replace
Kubota Manual
*
Water pump defective Replace
Kubota Manual
*
Overcharging of Alternator malfunctioning Replace A-13
batteries
Poor positive/ground connections Repair
Batteries defective Load test or replace batteries
Dead batteries or Alternator malfunctioning Replace A-13 undercharge
Poor alternator connection Check alternator connection
DC load too high Reduce load
Poor positive/ground connections Check connections
Alternator belt loose/worn Replace or tighten
Kubota Manual
*
APU suddenly stops Low oil pressure See "Low oil pressure" A-6 ("Check APU" message
Overheat See "Engine overheated" A-6
on Driver Control Panel
Alternator Feedback See "Alternator Troubleshooting" 3-15, A-13
62-11175 COMFORTPRO SERVICE MANUAL
3-4
Do not turn the Driver Control Panel off. Go to the APU and look at the APU Control Unit lights for the correct code.
*Kubota Workshop Manual 97897-02400
Page 30
62-11175 COMFORTPRO SERVICE MANUAL
3-5
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
APU suddenly stops No fuel Check fuel stand pipe length/fuel level
in tank A-8
(no message on Driver
Air in the fuel system Bleed air A-8
Control Panel display)
Water in fuel system Drain fuel tank(s) and replace A-3, A-8
fuel filters
Faulty communication between the
Check APU control cable, and
APU Control Unit, CCU Control
Driver Control Panel cable for shorts
Board and/or the Driver Control Panel
or opens/replace
Fuel solenoid faulty Check for rust in plunger/wiring 3-13
Alternator belt loose or broken Tighten/replace
Kubota Manual
*
Alternator faulty Repair/replace 3-15
Low battery voltage Check battery cables/charge battery
APU stops 15 seconds Low oil pressure See "Low oil pressure" 3- 4 after starting sequence
Overheat See "Engine overheated" 3- 4
completes ("Check APU"
Truck engine interlock (optional) Stop truck engine and re-start APU A-13
message on Driver Control Panel display)
APU stops after start Alternator belt loose or broken Tighten/replace A-2 sequence completes.
Alternator Defective Repair/replace 3-15
APU will only run with
Poor connection between alternator Check connection / wire for breaks
start button depressed
and APU controller (brown wire)
(no message on Driver Control Panel display)
No "GLOWING" message
Faulty communication between the
Check APU control cable, and
on the Driver Control APU Control Unit, CCU Control
Driver Control Panel cable for shorts
Panel, but APU will start Board and/or the Driver Control Panel
or opens/replace
and run normally
No "GLOWING" message
Faulty communication between the
Check APU control cable, and
on the Driver Control APU Control Unit, CCU Control
Driver Control Panel cable for shorts
Panel and APU will only Board and/or the Driver Control Panel
or opens/replace
run with ON button depressed
APU only ‘clicks’ after Faulty APU Controller • Replace APU Controller glowing has finished and is attempting to start
(ALT POWER light not on, ALT F/B light does not come on during glowing)
APU only ‘clicks’ after Loose connection from APU controller glowing has finished to alternator, either at the APU and is attempting to start controller end or at the Alternator end
(ALT F/B light on,
• Faulty Alternator
APU controller does not
Faulty APU Harness • Troubleshoot the Alternator • 3-15
come on during glowing)
This will occur when the APU Control Unit sees a problem during or after startup
This will occur when the APU Control Unit does not see the Alternator feed back signal during or after start up.
*Kubota Workshop Manual 97897-02400
Page 31
62-11175 COMFORTPRO SERVICE MANUAL
3-6
3.2 GENERATOR
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
No voltage 35 Amp Breaker tripped Determine reason and reset A-5
Generator Belt loose/broken Tighten/replace A-2
Low voltage Generator belt loose/broken Tighten/replace A-2
(below 100 Volts)
Engine air filter dirty Clean/replace filter A-3
Engine fuel system problem Change fuel filters A-3
Engine exhaust system problem Clean/replace
Engine speed low Adjust 3- 13
Very low voltage Wiring to capacitor Repair/replace
(4-10 Volts AC)
Capacitor defective Test and replace 3- 13, 3- 14
Each symptom is followed by a probable cause and suggested solution. To isolate the possible cause, proceed in a systematic manner to determine the faulty component. This guide does not cover all possible situations that may occur under all conditions of operation.
WARNING
Disconnect the batteries from the APU before performing any repairs.
Page 32
62-11175 COMFORTPRO SERVICE MANUAL
3-7
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
APU starts and runs, No 120 Volt power to CCU Board See "Generator" section 3- 6 but no CCU functions
Controls "locked up" Re-boot by turning APU off and
work and "OUTLET
disconnecting battery power to
OFF" is displayed
APU for 30 seconds
A/C will not turn on Temperature in sleeper is too cold Temperature must be above 65°F 1- 4, 1- 8 (no icon)
(turn heat on to raise the sleeper temp)
Temperature is below Driver Control Set temperature to lower setting 1- 4, 1- 8
Panel set point
Heat will not turn on Temperature in sleeper is too hot Temperature must be below 85°F 1- 4, 1- 8 (no icon)
(turn A/C on to lower the sleeper temp)
Temperature is above Driver Control Set temperature to higher point 1- 4, 1- 8
Panel set point
"HVAC BREAKER 20 Amp CCU breaker tripped Determine reason and press reset on RESET" is displayed the Driver Control Panel
Generator belt loose Tighten/replace A-2
"TRIP W/LIGHTENING 20 Amp outlet breaker tripped Determine reason and press reset on BOLT ICON" is displayed the Driver Control Panel
Generator belt loose Tighten/replace
"LOW VOLTAGE" Generator 35 Amp breaker tripped Determine reason and reset 3-6, A-5 is displayed
Generator belt loose/broken Tighten/replace 3-6
Engine air filter dirty Clean/replace filter A-3
Engine fuel system problem Change fuel filters A-3
Engine exhaust system problem Clean/replace
Engine speed low Adjust A-2
3.3 DRIVER CONTROL PANEL
Each symptom is followed by a probable cause and suggested solution. To isolate the possible cause, proceed in a systematic manner to determine the faulty component. This guide does not cover all possible situations that may occur under all conditions of operation.
WARNING
Disconnect the batteries from the APU before performing any repairs.
Page 33
62-11175 COMFORTPRO SERVICE MANUAL
3-8
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
Does not produce Refrigerant leaked out • Check for leaks and repair • 2-3 cold air
Compressor not working Check voltage at compressor
Inlet filter clogged Clean filter A-3
Produces cold air and Evaporator blocked with ice Increase air flow, increase return air gradually stops
Low refrigerant charge Check for leaks and repair 2-1
Air Duct blocked Check and remove any blockage
Tripped high Condenser fan not working See "Condenser fan not working" 3-9 pressure switch
Condenser is dirty Clean
Poor air flow around condenser Check condenser location, relocate
if necessary
Refrigerant is over charged Reduce charge to 64–68 oz 2-1
Tripped on EVAP Evaporator blocked with ice Increase air flow, increase return air temp sensor
Low refrigerant charge Check for leaks and repair 2-1
EVAP temp sensor faulty Verify sensor operation by using Temperature vs. Resistance Chart 2-3
3.4 CCU AIR CONDITIONING
Each symptom is followed by a probable cause and suggested solution. To isolate the possible cause, proceed in a systematic manner to determine the faulty component. This guide does not cover all possible situations that may occur under all conditions of operation.
NOTE: The five minute timer is activated any time the compressor is turned off (by the thermostat, EVAP temp sensor or high pressure switch. It is used to let the pressure between the high and the low side equalize so that the compressor can start under a "no load" condition.
WARNING
Disconnect the batteries from the APU before performing any repairs.
Page 34
62-11175 COMFORTPRO SERVICE MANUAL
3-9
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
Condenser fan not A/C is not on Set temperature to lower setting 1- 4, 1- 8 working
DC power fuse blown
Determine reason and replace fuse
A-4
Wiring damaged Repair/replace
Fan defective (seized) Replace
Compressor will not High pressure switch open See "Tripped high pressure switch" 3- 8 start (no hum)
Evaporator frozen See "Produces cold air and 3- 8
gradually stops"
Five minute timer active Wait five full minutes
Overload protector tripped Let unit cool down, check for 2- 1
low refrigerant
Driver Control Panel not calling for A/C
Set temperature to lower setting
Compressor seized Replace compressor
Compressor will not Low A/C Voltage to CCU See "Generator" section 3- 6 start (hums)
Starting capacitor defective Determine reason and replace
Potential relay is open Determine reason and correct,
replace if necessary
Compressor motor winding open Replace compressor
or shorted
Internal mechanical trouble Replace compressor
in compressor
Compressor will not Low A/C Voltage to unit See "Generator" section 3- 6 start (hums but trips
Potential relay is failing to open Determine reason and correct,
on overload protection)
replace if necessary
Run capacitor is defective Determine reason and replace
Excessively high discharge pressure Check high pressure switch, possible
overcharge or insufficient cooling on condenser (fan)
Compressor motor has a winding Replace compressor
open or shorted
Internal mechanical trouble in Replace compressor
compressor (tight)
Compressor starts and Low voltage to unit See "Generator" section 3- 6 runs, but short cycles
Overload protector defective Check current and replace protector
on overload protector
Run capacitor is defective Determine reason and replace
Excessively high discharge pressure Check condenser (fan) and for
restriction in refrigeration lines
Compressor too hot – suction Check refrigerant charge (check for 2- 1
line hot leaks) and add if necessary
Compressor motor has a Replace compressor
winding shorted
Air conditioner runs Overload protector See "Compressor starts and runs, but 3- 9 OK, but short cycles short cycles on overload protector"
Driver Control Panel too close Remount away from ducts 1- 1
to ducts
Page 35
62-11175 COMFORTPRO SERVICE MANUAL
3-10
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
Air conditioner runs Driver Control Panel temp sensor Replace Driver Control Panel OK, but short cycles defective
(cont.)
High pressure cut out due to
: Check:
a) Insufficient air flow
a) Air flow through condenser (fan)
b) Overcharge b) Reduce charge to 64–68 oz. c) Air in system c) Purge air (vacuum system) d) Defective switch d) Replace
Low temp(de-ice) cut out due to: Check: 2-1
a) Insufficient air flow a) Air flow through evaporator
(fan, filter, vents closed) b) Faulty expansion valve b) Replace valve c) Faulty de-ice sensor c) Verify sensor operation by using
Temperature vs. Resistance Chart A-11 d) Undercharge d) Fix leak and recharge (64–68 oz)
A/C operates long Shortage of refrigerant Fix leak and recharge (64–68 oz) 2-1 or continuously
Driver Control Panel temp sensor Verify sensor operation by using
defective Temperature vs. Resistance Chart
Sleeper has an excessive heat load Cover windows, close sleeper curtains
Sleeper has poor insulation Insulate sleeper
Evaporator coil iced
Faulty EVAP temp sensor, Verify sensor operation by using Temperature vs. Resistance Chart 2-1
Restriction in refrigerant system Determine location and repair
Dirty condenser Clean condenser
CCU air filter dirty Clean or replace CCU filter A-3
Start capacitor open, Potential relay is not operating Replace shorted, or blown properly
Prolonged operation on start cycle Check:
due to: a) Low voltage to unit a) Determine reason and correct
(see "Low Voltage") b) Starting load too high b) Check: pressure equalization
before compressor starts,
(5 minute timer faulty)
Excessive short cycling Determine reason for short cycling
and repair (see "Unit runs OK, but short cycles")
Potential relay defective Line voltage to low or to high Determine reason and correct or burned out
Excessive short cycling Determine reason for short cycling
and repair (see "Unit runs OK, but short cycles")
Relay being influenced by a loose Remount rigidly
and vibrating mount
Suction line frosted Evaporator fan not running Determine reason and correct 3-11 or sweating
Overcharge of refrigerant Reduce charge to 64–68 oz. 2-1
Unit noisy Loose parts or mounting Find and tighten
Tubing rattle Move object that is touching the
tubing to be free of contact
Bent fan blade causing vibration Replace blade
Fan motor bearings worn Replace motor
Page 36
62-11175 COMFORTPRO SERVICE MANUAL
3-11
3.5 CCU FAN
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
CCU fan not working Fuse on CCU Board Check/replace A-4
Wiring defective Repair/replace
Capacitor defective Test/replace
CCU fan only works on Low speed resistor defective Check/replace heating element A-2 high speed
Resistor wiring defective Repair/replace A-2
CCU Board defective Test/replace
3.6 CCU HEAT
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
High Heat Mode does Heat is not on (heat icon must be on) • Turn temperature setting up 1- 4, 1- 8 not produce warm air
Thermo fuse blown Check/replace thermal fuse A-2
CCU Board defective Replace
Low Heat Mode does Heat is not on (heat icon must be on) Turn temperature setting up 1- 4, 1- 8 not produce warm air
Thermo fuse blown Check/replace thermal fuse A-2
CCU Board defective Replace
Produces warm air and Set point has been reached Turn set point up 1- 4, 1- 8 gradually stops
High temperature cut out due to Increase air flow/Increase return air
insufficient air flow
High temperature High temperature cut out due to Increase air flow, increase return air sensor tripping insufficient air flow
Temperature sensor wiring damaged Repair/replace
Temperature sensor defective Verify sensor operation by using Temperature vs. Resistance Chart A-11
Ducting blocked Check and remove any blockage
Heat works OK, but Driver Control Panel too close to duct Remount away from ducts 1- 1
short cycles
Driver Control Panel temp sensor Verify sensor operation by using
defective Temperature vs. Resistance Chart
Heat operates long or Driver Control Panel temp sensor Verify sensor operation by using continuously defective Temperature vs. Resistance Chart A-11
Sleeper has an excessive heat loss Cover windows, close sleeper curtains
Sleeper has poor insulation Insulate sleeper
CCU air filter dirty Clean/replace CCU filter A-3
WARNING
Disconnect the batteries from the APU before performing any repairs.
WARNING
Disconnect the batteries from the APU before performing any repairs.
Page 37
62-11175 COMFORTPRO SERVICE MANUAL
3-12
3.7 RECEPTACLE PANEL
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
No 120 VAC power High Heat Mode is selected Switch to 'Low Heat' position 1- 4, 1- 8
APU not running Start APU 1- 4, 1- 8
35 Amp breaker tripped at See "Generator" Section 3-6
generator
Each symptom is followed by a probable cause and suggested solution. To isolate the possible cause, proceed in a systematic manner to determine the faulty component. This guide does not cover all possible situations that may occur under all conditions of operation.
WARNING
Disconnect the batteries from the APU before performing any repairs.
Page 38
62-11175 COMFORTPRO SERVICE MANUAL
3-13
3.8 TESTING PROCEDURES
3.8.1 Testing AMP draw for components
When checking functions of individual components, place amp clamp over black (power) wire coming in from the generator to the CCU board. (As shown in below.)
When cross-referenced with the “AMP DRAW AND VOLTAGE CHART”, the components should show the same amp readings.
3.8.2 Testing Voltage and Hz readings:
When checking for 120 VAC at the CCU board, the probes are placed at the black wire terminal and the white wire terminal.
When APU is running there should always be between 110 – 130 VAC present.
When APU is running the Hz reading should always be 60 +/- 2.
Page 39
62-11175 COMFORTPRO SERVICE MANUAL
3-14
3.9.1 Adjusting the 120 AC Voltage
This does not need to be adjusted under normal operation. If you find low AC voltage, check the generator belt, air filter, fuel filters and exhaust system before adjusting.
1 With the APU running turn all 120-volt components off.
2 Measuring the voltage at the outlet panel adjust the engine speed
until 120 (+/- 10) volts AC and 60 Hz +/- 2 Hz is read.
3.9.2 Capacitor Troubleshooting
1 Disconnect generator output from breaker.
2 With APU running, measure generator output voltage.
3 If voltage < 105 volts AC, try a known good capacitor and retest.
NOTE: Most multimeters will not test this capacitor reliably in either MF
(capacitance) or (resistance) modes. The above methods are the ONLY reliable means of testing the capacitor without a lab-grade capacitance meter.
3.9.3 Capacitor Theory
A single-phase motor can not be "fed" with just single-phase current (120 Volt AC), there must be some way to create an artificial second (or third) phase to smooth out the magnetic filed. Capacitors are electrical components that help create and strengthen the artificial second phase in single-phase electric motors. They work much like a battery, storing and releasing a charge of electricity (AC Voltage) that is out of phase with the oscillating (AC) current that is fed into the motor.
If single-phase induction motors do not have a second phase (created by the capacitor) then it will not have an even magnetic field. This will cause the rotor to hesitate at those spots that are uneven. This hesitation will cause the rotor to spin slowly or even stop moving (compounding the problem), draw more current (Amp's), become noisy, and overheat.
The CCU Fan and the Compressor use a Run Capacitor. Run Capacitors are designed for continuous duty, and are energized the entire time the motor is running.
The Compressor motor needs a Start Capacitor in addition to the Run Capacitor. Start Capacitors are designed for momentary use. Start capacitors stay energized long enough to bring the motor to75% of full speed (RPM) and are then taken out of the circuit by means of a Potential Relay.
3.9 ADDITIONAL INFORMATION
Page 40
62-11175 COMFORTPRO SERVICE MANUAL
3-15
3.9.4 Potential Relay Theory
In a Capacitor Start, Capacitor Run compressor the start capacitor is only designed for momentary use. The Potential Relay (NC) is used to connect and disconnect the start capacitor from the compressors start windings. Induced Voltage is generated in the start winding when of the compressor when it is running. The voltage induced in to the start winding is a function of the speed of the rotor and the magnetic field that is generated. When the compressor is first energized, the voltage in the start windings is less than the line voltage (120 VAC). As the compressor speed (RPM) increases, the voltage in the start windings increases significantly higher than the line voltage (up to 275 Volts) until full compressor speed (RPM) is reached.
The Potential Relay's coil is connected across the start windings, and is designed to respond to the increase of voltage as the compressor's speed increases. The normally closed Potential relay contacts are designed to open at a 75% of the full compressor speed (RPM). The Start Capacitor is connected to the relay contacts so when the relay opens (75% of the full compressor speed RPM) the start capacitor is disconnected from the system.
3.9.5 Alternator Troubleshooting
1 Unit switched OFF, harness connected
Check alternator feedback wire (brown) at the alternator for 5 volts.
If 5 volts are not found disconnect 'T' connector from alternator and retest. If 5 volts are found the alternator is faulty.
If 0 volt is found check alternator feedback wire (brown) for open, and power (B+) and ground (B-) to APU controller and repair as required. If no fault is found the APU controller is faulty.
2 Unit switched ON (glowing), harness connected
Check alternator field power wire (purple) for 12 volts. If 0 volt is found check alternator field power wire (purple) for open and power (B+) and ground (B-) to APU controller and repair as required. If no fault found the APU controller is faulty.
Check alternator feedback wire (brown) at alternator for 0 volt. If 5 volts are found the alternator is faulty.
3 Unit running, harness connected
Check alternator feedback wire (brown) at alternator for 5 volt. If 0 volts are found the alternator is faulty.
4 Unit running, then stops
Check alternator jumper harness (red) at alternator connection for 12.5-14.1 volts.
If 16-17 volts is found, check for alternator jumper (red) open and replace as required.
Page 41
62-11175 COMFORTPRO SERVICE MANUAL
3-16
Page 42
62-11175 COMFORTPRO SERVICE MANUAL
A-1
APPENDICES
CAPACITIES AND SPECIFICATIONS .................................................... A-2
FUSE LOCATIONS ............................................................................ A-4
CIRCUIT BREAKER LOCATIONS.......................................................... A-5
APU CONTROL UNIT ......................................................................... A-6
CCU CONTROLLER ........................................................................... A-7
FUEL SYSTEM PURGE PROCEDURE ................................................... A-8
COOLANT PURGE PROCEDURE.......................................................... A-9
DEFROST/HEAT AND DCP SENSOR CHARTS .................................... A-11
ENGINE INTERLOCK DIAGRAMS ...................................................... A-12
APU WIRING DIAGRAMS ................................................................. A-13
Page 43
62-11175 COMFORTPRO SERVICE MANUAL
A-2
Engine . . . . . . . . . . . . . . 13.9 hp Kubota, 2 cyl, 479cc (model Z482-B)
Engine Oil . . . . . . . . . . . . 3.5 US Qts (3.3L) with filter.
You can use any API Service CF, CF-4, CG-4 or CH-4 oil and any ASE Viscosity (or weight) of Oil according to the chart.
Belt Tension . . . . . . . . . . Alternator 45-55 ft-lb (61-75 N-m).
Generator 70-80 ft-lb (95-108 N-m).
Engine compression . . . . 327 PSI min. (2.26 MPa min).
Engine Speed . . . . . . . . . Approx. 2400 RPM.
Valve Clearance (Cold) . . . 0.145 to 0.185 mm (0.0057 to 0.0073 in).
Engine Drain Plug . . . . . . Torque 25 ± 2 ft/lb.
Intake & Exhaust Valves . 0.0057-0.0073" (0.145 – 0.185 mm) Cold.
Fast Burn Glow Plugs . . . . 0.9 Ohms each, 22 Amps then ramps down
to 12 Amps.
Starter . . . . . . . . . . . . . . 160 Cranking Amps (includes glow plugs and
fuel solenoid).
Alternator . . . . . . . . . . . . 60 Amps @ 14.2 Volts DC.
Generator . . . . . . . . . . . . 35 Amps @ 120 Volts AC.
Fuel Solenoid . . . . . . . . . Pull-in winding 29 Amps, Hold winding 1 Amp.
Oil pressure switch . . . . . Normally closed, opens at 7 psi.
Overheat switch . . . . . . . Normally open, closes at 245°F.
Thermostat . . . . . . . . . . . Starts to open at 160°F and fully opens at 185°F.
Air Conditioner . . . . . . . 10,000 BTU/ hr hermetic compressor.
System capacity . . . . 64–68 oz of R-134A.
System Oil capacity . . 14 oz of PVE (Polyvinylether).
Compressor . . . . . . . 6–10 Amps @ 120 Volts.
Condenser Fan . . . . . 9-12 Amps .
Binary Pressure Switch
. Normally closed between 26–335 psi. Operating pressures . . Low side, 24–45 psi, High side, 110–250 psi. Condenser Air inlet to outlet temperature difference should be no more
than 30°F. Evaporator Air inlet to outlet temperature difference 18° - 25°F.
Heat . . . . . . . . . . . . . . . 10,000 BTU/ hr (3,000 watts).
Blower Fan low
speed resister . . . . . . 25 Ohms.
Heating Coils . . . . . . . 10 Ohms each.
Thermo Fuse . . . . . . . Blows at 307.4°F (152°C).
CAPACITIES AND SPECIFICATIONS
APU
CCU
40
30
20
20W
10W
5W
5W20
5W30
10W30
15W40
20W50
243 253 263 273 283 293 303 313 323
-30 -20 -10 0 10 20 30 40 50
-22 -4 14 32 50 68 86 104 122
K
°C
°F
SINGLE
GRADE
MULTI
GRADE
AMBIENT
TEMP
Page 44
62-11175 COMFORTPRO SERVICE MANUAL
A-3
Figure A-1: Maintenance Components
OIL FILTER
FUEL FILTER
AIR FILTER
OIL DIPSTICK
AIR INLET FILTER
FUEL FILTER INLINE FUEL OIL FILTER AIR FILTER GENERATOR ALTERNATOR
FILTER BELT BELT
CARRIER 96-101-24K 30-186-01K 96-101-23K 30-724-10K 40-304-01K 96-969-03K
Maintenance Parts Crossover List
INLINE FUEL FILTER
Page 45
62-11175 COMFORTPRO SERVICE MANUAL
A-4
FUSE LOCATIONS
Figure A-2: Fuse Locations
CCU FAN FUSE 250V, 3 AMP
CCU
THERMAL FUSE x2
APU
DC POWER FUSE 12V, 20 AMP
Page 46
62-11175 COMFORTPRO SERVICE MANUAL
A-5
CIRCUIT BREAKER LOCATIONS
Figure A-3: Circuit Breaker Locations
GENERATOR
35 AMP BREAKER (MANUAL RESET)
OUTLET BREAKER (AUTO RESET)
CCU BREAKER (AUTO RESET)
CCU
Page 47
62-11175 COMFORTPRO SERVICE MANUAL
A-6
APU CONTROL UNIT
Output Indicators
STARTER – This is the output (+) to the Starter solenoid.
GLOW PLUGS – This is the output (+) to the Glow Plugs.
SOL PULL – This is the output (+) to the Fuel Solenoid Pull windings
(Only on during cranking for the first .5 seconds).
SOL HOLD – This is the output (+) to the Fuel Solenoid Hold windings.
ALT POWER – This is the output (+) to the Alternator field windings.
Input Indicators
OIL – This is the input (-) from the Oil Pressure Switch (NC). You will see
this light illuminated when the oil pressure is below 7 psi. This will shut the APU off when it is illuminated.
TEMP – This is the input (-) from the Overheat Switch (NO). You will see this light illuminated when the coolant temperature is above 245°F. This will shut the APU off when it is illuminated.
ALT F/B – This is the input (-) from the Alternator Charging light. When the APU is not running this light will be on. When the APU is running and the Alternator is charging this light will be out (or very dim). This will shut the APU off when the light is illuminated.
APU
Figure A-4: APU Control Unit
CONTROL
UNIT
STARTER
GLOW PLUGS
SOL PULL
SOL HOLD
ALT POWER
COOLANT
TEMP
ALT F/B
OIL
Page 48
62-11175 COMFORTPRO SERVICE MANUAL
A-7
Inputs
AC – This is the input from the Driver Control Panel only when it is calling
for Air conditioning. (Low or High A/C.)
HEAT – This is the input from the Driver Control Panel only when it is calling for Heat. (Low or High Heat.)
FAN LOW – This is the input from the Driver Control Panel only when it is calling for CCU Low Fan. (Used in Fan, A/C, and Heat modes.)
FAN HIGH – This is the input from the Driver Control Panel only when it is calling for CCU High Fan. (Used in Fan, A/C, and Heat modes.)
*Outputs
OUTLET – This is the output signal to the Power Outlet relay. It is On any
time 120 VAC Power is available to the Outlet. If High Heat mode is selected the Outlet will be turned off.
LOW HEAT – This is the output signal to the Low Heat relay. It is On any time Low Heat is called for.
**COMPRESSOR – This is the output signal to the A/C Compressor relay. It is On any Time the A/C is called for. (Low or High.)
**CONDENSER – This is the output signal to the Condenser Fan relay. It is On any Time the A/C is called for. (Low or High.)
LOW FAN – This is the Output signal to the CCU Low Fan relay. It is On any time the CCU Low Fan is called for. (Used in Fan, A/C, and Heat mode.)
HIGH FAN – This is the Output signal to the CCU High Fan relay. It is On any time the CCU High Fan is called for. (Used in Fan, A/C, and Heat modes.)
HIGH HEAT – This is the output signal to the High Heat relay. It is On any time High Heat is called for. High Heat and Outlet can not be on at the same time.
Service Light
If yellow Service Light is illuminated, reprogram or replacement of CCU board may be required.
*NOTE: Outputs only indicate the signal to turn the component relay on. They do not indicate that the actual component itself is working.
**NOTE: Air Conditioning is a sequence start. CCU fan will come on first,
0.5 seconds later the Condenser Fan will come on, and 0.5 seconds after the Condenser fan the A/C Compressor will come on.
CCU CONTROLLER
Figure A-5: CCU Controller
NOTICE
Yellow Service Light will flash when CCU is OFF.
Page 49
62-11175 COMFORTPRO SERVICE MANUAL
A-8
1. Start the APU with the APU Test Switch Module. If APU fails to start, crank in 15 second bursts until fuel system is purged of air and APU starts and runs smoothly.
FUEL SYSTEM PURGE PROCEDURE
FUEL FILTER
Figure A-6: Fuel Filter
OPEN TO BLEED THE FUEL SYSTEM
Page 50
62-11175 COMFORTPRO SERVICE MANUAL
A-9
1 Ensure that the coolant supply valve to the APU (located at the truck
engine) and the coolant return valve to the APU (also located at the truck engine) are open.
2 Release pressure from coolant system.
3 Remove the truck engine radiator cap.
4 Top up the coolant if necessary in the expansion tank.
5 Run the truck engine at fast idle until 185°F (85°C)is reached on truck
temperature gauge. This
should
purge most of the air out of the APU.
6 Purging Air From the Coolant.
• Place thermostat drain hose into bucket (see Figure A-7).
• Open the thermostat bleed valve, using a wrench, and let any trapped air escape until a steady stream of coolant flows from the valve.
• Close thermostat bleeder fitting.
• Top up the coolant if necessary in the truck expansion tank.
• Run the truck engine at fast idle for another 10 minutes to continue purging air.
COOLANT PURGE PROCEDURE
Figure A-7: Drain Hook-up
THERMOSTAT
DRAIN HOSE
1/2"
WRENCH
BLEEDER VALVE
OPEN 1/4–1/2 CCW
Page 51
62-11175 COMFORTPRO SERVICE MANUAL
A-10
7 Start the APU by following the instructions on page 1- 3 (Multi-Function
Driver Control Panel).
8 With the APU and truck engines running, open the thermostat bleed
valve and let any trapped air escape until a steady stream of coolant flows from the valve.
9 Shut the truck engine off.
10 Check the truck engine; ensure it is getting hot coolant from the APU.
If it is not, the APU is not purged of all its air. Stop APU by following the instructions on page 1- 3 (Multi-Function Driver Control Panel). Check for a restriction (i.e. valves/kinks etc.) and repeat steps 5 to 9.
11 Let APU run for at least 30 minutes. During this time keep checking
for signs of coolant leaks, fuel leaks and overheating.
12 Top up the coolant if necessary in the truck expansion tank and
replace the truck engine radiator cap.
13 Clean up any spilled coolant from inside APU and on the ground.
Page 52
62-11175 COMFORTPRO SERVICE MANUAL
A-11
DEFROST/HEAT & DCP SENSOR
T(°C) T(°F)
RESISTANCE
15 59 157.6
(kΩ)
16 61 150.4
(kΩ)
17 63 143.5
(kΩ)
18 64 137.1
(kΩ)
19 66 130.9
(kΩ)
20 68 125.1
(kΩ)
21 70 119.6
(kΩ)
22 72 114.3
(kΩ)
23 73 109.3
(kΩ)
24 75 104.5
(kΩ)
25 77 100.0
(kΩ)
26 79 95.7
(kΩ)
27 81 91.6
(kΩ)
28 82 87.7
(kΩ)
29 84 84.0
(kΩ)
30 86 80.5
(kΩ)
31 88 77.1
(kΩ)
32 90 73.9
(kΩ)
33 91 70.9
(kΩ)
34 93 68.0
(kΩ)
35 95 65.2
(kΩ)
36 97 62.5
(kΩ)
37 99 60.0
(kΩ)
38 100 57.6
(kΩ)
39 102 55.3
(k
)
40 104 53.1
(kΩ)
41 106 51.0
(kΩ)
42 108 49.0
(kΩ)
43 109 47.1
(kΩ)
44 111 45.3
(kΩ)
45 113 43.5
(kΩ)
46 115 41.9
(kΩ)
47 117 40.3
(kΩ)
48 118 38.7
(kΩ)
49 120 37.3
(kΩ)
50 122 35.9
(kΩ)
Temperature vs. Resistance Chart
Page 53
62-11175 COMFORTPRO SERVICE MANUAL
A-12
ENGINE INTERLOCK (PG1011)
High Side Switching
Low Side Switching
NOTE:
1 Relay is supplied by end user.
2 Ground connections MUST be common with APU controller.
APU Controller Pin 9
Wired to engage when truck ignition on
LS1
5
3
4
1
2
RELAY SPDT
APU Controller Pin 9
Wired to engage when truck ignition on
12V
LS2
5
3
4 1 2
RELAY SPDT
Page 54
62-11175 COMFORTPRO SERVICE MANUAL
A-13
APU WIRING DIAGRAM (Serial No.s KZX98002290 to Date)
CLIMATE CONTROL UNIT (CCU)VEHICLE SLEEPERAUXILLARY POWER UNIT (APU)
Page 55
Carrier Transicold Division, Carrier Corporation Truck/Trailer Products Group P.O. Box 4805 Syracuse, N.Y. 13221 U.S A
www.carrier.transicold.com
North America
Carrier Transicold 700 Olympic Drive Athens, GA 30601 USA Tel: 1--706--546--6469 Fax: 1 --706--546--5207
Mexico and Central America
Ejercito Nacional No. 418 Piso 9, Torre Yumal Col. Chapultepec Morales 11570 Mexico, D.F. Tel: (5255) 9126.0300 Fax: (5255) 9126.0373
A member of the United Technologies Corporation family. Stock symbol UTX ©2006 Carrier Corporation • PrintedinU.S.A.0706
Loading...